HomeMy WebLinkAbout1917 PALOMAR OAKS WAY; ; FA160047; Permit12/16/21, 4:07 PM FA160047 Permit Data
City of Carlsbad
Fire Alarm Permit
Permit No: FA160047
1917 PALOMAR
Job Address:
OAKS WY
Permit Type: FALARM
Parcel No: 2120911900
Lot #: 0
Reference No.:
PC #:
Status: ISSUED
Applied 8/29/2016
Approved: 9/6/2016
Issued: 9/6/2016
Inspector:
Project Title: ARBOR SCENTIA T.I.: NEW STROE AND HORN STROBE
DEVICES ON 2ND FLOOR
Applicant:
RED HAWK FIRE & SECURITY
920 SOUTH ANDREASEN DR
SUITE 102
ESCONDIDO, CA
760-233-9787
Owner:
WASATCH CORNERSTONE HOLDINGS L
LC
595 S RIVERW000S PKWY #400
LOGAN UT
Fees ($) Add'I Fees ($) Total ($)!Balance($)
314 0 314 j 0
1/1
FIRE ALARM SYSTEM SUBMITTAL
For
ARBOR SCENTIA
CORNERSTONE CORPORATE CENTER
1917 PALOMAR OAKS WAY, SECOND FLOOR,
CARLSBAD, CA 92008
Submitted By:
Red Hawk Fire & Security
920 South Andreasen Drive, Suite 102,
Escondido, California 92029
(760) 233-9787
P FA1 60047
1917 PALOMAR OAKS WY 20
PROJECT INFORMATION SHEET
PERMIT NUMBER:
INSTALLING CONTRACTOR: Red Hawk Fire & Security
920 South Andreasen Drive, Suite 102,
Escondido, California 92029
Phone: (760) 233-9787
CONTRACTORS LICENSE: C-10/C-16 #713099,11/30/16
PROJECT MANAGER: John Stasukevich
PROJECT NAME: ARBOR SCENTIA
PROJECT ADDRESS: CORNERSTONE CORPORATE CENTER
1917 PALOMAR OAKS WAY, SUITE 200,
CARLSBAD, CA 92008
SCOPE OF WORK: TENANT IMPROVEMENT
S
August 25, 2016
Re: Arbor Scentia
Cornerstone Corporate Center
1917 Palomar Oaks Way, Suite 200, Carlsbad, CA 92008
Tenant Improvement
Red Hawk Fire & Security is pleased to submit the following equipment for your approval. All
equipment is U.L. approved and California State Fire Marshall listed. The building is 100% sprinklered.
QTY. MODEL NO. DESCRIPTION C.S.F.M.
2 ZR-MC-CW Multi Candela Strobe, Ceiling Mount 7125-0067:0252
3 ZH-MC-CW Multi Candela Horn Strobe, Ceiling Mount 7125-0067:0248
Respectfully Submitted,
RED HAWK FIRE & SECURITY
0
SIEMENS Data Sheet
Fire Safety Products
Notification Appliances
ZH & ZR - Strobes, Horns, & Horn I Strobes I Application: Indoor
L '1 • Fl$E
______
RTLI ZR&Z%t.
1iiëJ 1(Ies1 (for mounting)
Product Overview
- Strobes can be synchronized using the Siemens DSC sync modules, the Siemens 50-point,
252-point and 504-point addressable fire alarm control panels (FACP5), as well as with:
FireFinder® XLS and MXL® FACPs
PAD-3 or PAD-4TM NAC Extenders with built-in sync protocol
- Selectable Continuous Horn or Temporal (Code-3) Tones with 90 or 95 dBA
selectable setting (Series 'ZH')
- Ceiling-mount models feature field-selectable Candela settings of 1 5/30175195cd and 115/177cd
- Wall-mount models feature field-selectable Candela settings of 15130/75/11 Ocd and 1 35/1 85cd
- Base plate is protected by a disposable cover, and the appliances can quickly snap onto the base
after the walls are painted
- Strobes produce one (1) flash per second
- "Special Applications" listed with Siemens panels
- EZ Mount Universal Mounting Plate (Model ZB Series) —uses single plate
for ceiling and wall mount installations
- EZ Mount design—with separate base plate _provides ability to pre-wire the base
and test the circuit wiring before the walls are covered
- ®UL Listed & @ULC Listed, FM (#3028994) Approved;
CSFM Approved (Series 'ZH': #71250067:0248 —> Fire Alarm Devices For The Hearing Impaired)
CSFM Approved (Series 'ZR': #71250067:0252 —> Fire Alarm Devices For The Hearing Impaired)
- ADA! NFPA compliant
Specifications
General
- Audible/Visual notification appliances are listed for indoor use only
- Appliances are listed under ®UL Standard 1971 (Standard for Safety Signaling Devices
for Hearing Impaired) and ®UL Standard 464 (Fire Protective Signaling)
- Appliances use a universal back plate, which allows mounting to a
single-gang, double-gang, 4-inch-square (10.2 cm.), 4"-octal (10.2 cm.), or a 3-1/2" (8.9 cm.) octal backbox
- Two-wire configurations allows capability for directly connecting appliances to the mounting back plate
- Continuity check will occur for entire NAC circuit prior to attaching any audible I visual-notification appliances
- A cover fits over the mounting plate for protection to dust and other outside elements
S . Cover is easily removed when the appliance is installed over the back plate
- Removal of an appliance will result in a Trouble condition by the Siemens Fire Alarm Control Panel (FACP)
'Z' Series Notification Appliances 2584
SIEMENS Industry, Inc.
Building Technologies Division
Specifications - (continued)
. Strobes and Audible Strobe Combinations
- Strobe appliances produce a minimum flash rate of 60 flashes per minute
(one [1] flash per second) over the Regulated Input Voltage Range, and
incorporate a Xenon flashtube enclosed in a rugged Lexan® lens
- Strobes are available with two (2) or four (4) field-selectable settings
in one (1) unit, and are rated - per ®UL 1971 - for up to:
15/30175/110cd for wall mounted
1 351185c for wall mounted
1 5130175195cd for ceiling mounted
11 5/1 77cd for ceiling mounted
- Strobes operate over an extended temperature range of 32°F to 120°F
(0°C to 490C), and be listed for maximum humidity of 95% RH
- Strobe inputs are polarized for compatibility with standard reverse-polarity
supervision of circuit wiring by a Siemens FACP
Audible and Audible I Strobe Combinations
- Horns and horn I strobes are listed for Indoor use under ®UL Standard 464
- Horns are able to produce continuous synchronized output or a
Temporal Code-3 synchronized output
- Horns have at least two (2) sound-level settings of 90 and 95 dBA
Synchronization Modules
- The strobe portion, when synchronization is required, is compatible with the
Siemens DSC sync modules; the Siemens 50-point, 252-point and 504-point
S addressable FACPs, as well as with:
FireFinder® XLS and MXL® FACPs
PAD-3 or PAD-4 TM NAC Extenders with built-in sync protocol
- The strobes will not drift out of synchronization at any time during operation
- Audibles and strobes are able to synchronize on a two-wire circuit with the capability
to silence the audible, if required
- Strobes revert to a non-synchronized flash-rate, if the sync module or
power supply should fail to operate (i.e. - contacts remain closed)
- All notification appliances are listed for Special Applications:
Strobes are designed to flash at 1-flash-per-second
minimum over their "Regulated Input Voltage Range"
> Note: NFPA-72 specifies a flash rate of 1-to-2 flashes per second,
and ADA Guidelines specify a flash rate of 1-to-3 flashes per second
All candela ratings represent minimum-effective Strobe intensity, based on ®UL Standard 1971
Series ZH Strobe products are listed under ®UL Standards 1971 and 464 for indoor use
with a temperature range of 32°F to 120°F (0°C to 49°C) and maximum humidity of 93°h (1 2%)
Series ZH horns are listed under ®UL Standard 464 for audible signal appliances (Indoor use only)
Mounting Diagram
4.85 - i.- I. S6 -! - -
H
-
SIEMENS Industry, Inc. (Shown In Inches)
Building Technologies Division
Mounting Diagram
-OPTIONAL
SECURING
SCREWS slut
SCREWDrM2-..-J Installation
With the provided pan head screws, install mounting
plate to a:
- single-gang;
- double-gang;
-4" (10.2 cm.) square;
-4" (10.2 c., octagon backbox
Connect the field wiring.
3.) Address wires back into bachbox.
Place dust cover over mounting plate to protect the
terminals while performing the wiring-continuity check.
Remove dust cover before snapping or
installing the appliance onto the mounting plate
Technical Data
Removal -r-
)gpodant: Device only has one (1)mounting
orientation. Match the top of the base to the
top of the device.
1.) if it is desired to further secure the device to the
base, then use the two (2) optional screws which
are provided in the shipment. To install, punch
out the screw holes located at the top and
bottom of the device.
8.) To remove the appliance, push a small, flat-bladed
screwdriver into the side opening. The screwdriver
must clear the snap release opening by 1/4 '(0.64cm.),
in order for the appliance's snap to disengage.
Iiupori.ani: Do not pry off the housing with a screw driver.
ZH Horn: Wall and Ceiling Mount
Operating Voltage (Special Application)
Per ®UL 464
Input Voltage Low* High*
7DC 16.0-33.OVDC 0.018 0.044
FWR 16.0-33.OVRMS 0.045 0.075
* Current draw is the tame for the Continuous Horn, Code 3 . Horn, and March Time settings
ZH Horn I Strobe Series: Wall Mount
S
Current Ratings (AMPS)
MAXIMUM RMS Current- with jgh dBA Setting
Input Voltage 15cd 30cd I 75cd ll0cd 135cdf 185cd
DC 116.0-33.OVDC 0.078 0.113 10.19510.25910.3711 0.506
FWR 16.0-33.0VRMS0.141 0.200 10.30210.40610.52110.722
Current Ratings (AMPs)
MAXIMUM RMS Current- with Low dBA Setting
Input Voltage j 15cd 30cd I 75cd 95cd 11 35c I 185cd
DC 1 16.0- 33.OVDC 0.070 10.107 10.188 0246
10.29010.39110.497
324 10.455
FWR 116.0-33.OVRMSI 0.123 10.179 10.699
ZR Strobe Series: Wall Mount
Current Ratings (AMPs)
Strobe Setting - (Cd)
Input Voltage 15cd I 30cd I 75cd llOcd 135cd 185cd
DC 16.0-33.OVDC 10.06410.09810.17510.2331-o-.-318][0-445
FWR 16.0-33.0VRMS0.108 0.164 0.268 0.368 0.482 0.684
Current Ratings (AMPs)
Strobe Setting - (Cd)
Input Voltage 1 001 30cd I 75cd I 95cd 111 5c I 177cd
DC 116.0-33.0VDC 11M70601 0.111 0.200 0.264 0.318 10.445
FWR 16.0-33.OVRMS 0.117 0.180 0.297 0.398 0.482 0.684
tfiIULC Directional Characteristics
-3 dBA 35 degrees left; 40 degrees right
.6 dBA 55 degrees left; 65 degrees right
SIEMENS Industry, Inc.
Building Technologies Division
Current Ratings (AMPs)
MAXIMUM RMS Current- with High dBA Setting
Input Voltage t5td 30cd (Z5tt}95cd 115cd 177cd
DC 16.0-33.OVDC 0.131 22-10.29210.37110.506
FWR 16.0 - 33.OVRMS 0.14910.21610.33110.4361 0.5211 0722
Current Ratings (AMPS)
MAXIMUM RMS Current- with Low dBA Setting
Input Voltage 15cd 30cd 75cd 95cd ll5cd 177cd
DC 16.0-33.OVDC 0.075 10.12110.213 0.277 0.324 10.455
FWR 116.0-33.OVRMS 0.131 0.195 10.319 0.421 0.497 10.699
ZH and ZH-MC Series: Wall and Ceilinq Mount
dBA Sound Output
Description Volume Reverberant Per IJL 464
16.0 VDC 24.0 VDC 33.0 VDC
Continuous
Horn
Low 77 81 83
High 83 87 90
Code 3 Horn 11
(or March Time)*
Low 72 76 79
I High 79 82 86
dBA Sound Output
Description Volume Reverberant Per fiWLC-5525-99
20.0 VDC 24.0 VDC 31.0 VDC
Continuous
Horn
Low 88 90 91
High 93 95 96
Code 3 Horn
(or March Time)
Low 88 90 91
High 93 1 95 96
** Available only in sync mode.
Technical Data - (continued)
Notes: 1. Strobes will produce 1 flash per second over the Input Voltage range.
These horn/strobe models are ®UL Listed to operate over a Voltage Range Limit from 1 6.OVDC to 33.OVDC
for 24VDC applications using filtered DC or unfiltered Full-Wave-Rectified (FWR) input voltage.
All models are ®UL Listed for indoor ceiling use with a temperature range of +0°C to +49°C
(+32°F to +120°F) and maximum humidity of 93% +1- 2% RH.
The effect of shipping and storage temperatures will not adversely affect the performance of the appliance
when stored in original cartons, and is not subjected to either misuse or improper handling of shipment.
Details for Ordering - (Including Mounting Options & Agency Approvals)
Agency Approvals
Model Part Number Description Mounting UL Options*
ULC FM CSFM
ZH-R 500-636159 Z Horn: Red B,D,E,F,X V V V V
ZH-W 500-636160 Z Horn: White B,D,E,F,X V V V V
ZH-MC-R 500-636161 Z Horn: Multi Candela (Wall), Red B,D,E,F,X V V V V
ZH-MC-W 500-636162 Z Horn: Multi Candela (Wall), White B,D,E,F,X V V V V
ZH-HMC-R 500-636163 Z Horn: Hi Multi Candela (Wall), Red B,D,E,F,X V V V V
ZH-HMC-W 500-636164 Z Horn: Hi Multi Candela (Wall), White B,D,E,F,X V V V V
ZH-MC-CR 500-636165 Z Horn: Multi Candela (Ceiling), Red B,D,E,F,X V V V V
500-636166 Z Horn: Multi Candela (Ceiling), White B,D,E,F,X V V V V
ZH-HMC-CR 500-636167 Z Horn: Hi Multi Candela (Ceiling), Red B,D,E,F,X V V V V
ZH-HMC-CW 500-636168 Z Horn: Hi Multi Candela (Ceiling), White B,D,E,F,X V V V V
ZR-MC-R 500-636169 Z Strobe: Multi Candela (Wall), Red B,D,E,F,X V V V V
ZR-MC-W 500-636170 Z Strobe: Multi Candela (Wall), White B,D,E,F,X V V V V
ZR-HMC-R 500-636171 Z Strobe: Hi Multi-Candela (Wall), Red V V V V
ZR-HMC-W 500-636172 Z Strobe: Hi Multi-Candela (Wall), White V V V V
ZR-MC-CR 500-636173 Z Strobe: Multi Candela (Ceiling), Red
I
V V V V
500-636174 Z Strobe: Multi Candela (Ceiling), White V V V V
ZR-HMC-CR 500-636175 Z Strobe: Hi Multi Candela (Ceiling), Red V V V V
ZR-HMC-CW 500-636176 Z Strobe: Hi Multi Candela (Ceiling), White I B,D,E,F,X I V V V V
ZB-R 500-636193 Accessory - (Includes base, dust cover,
mounting _screws _and _installation _sheet)
V V V V
Z8-W 500-636194 Accessory - (Includes base, dust cover,
mounting screws and installation sheet) V V V V
V = Listed /Approved
* = Refer to data sheet #: 2585
for detailed mounting options
Notice: This marketing data sheet is not intended to be used for system design or installation purposes.
For the most up-to-date information, refer to each product's installation instructions.
Fire Safety Fire Safety
8 Fernwood Road 1577 North Service Road
SIEMENS Industry, Inc. Florham Park, NJ 07932 East Oakville, Ontario August 2016
Building Technologies Division Tel: (973) 593-2600 (511) L6H 0H6 / Canada Supersedes sheet dated 6/2015
FAX: (908) 547-6877 Printed in U.S.A. Tel: [905] 465-8000 (Rev. 5)
URL: www.usa.Siemens.com)Fire URL: www.Siemens.CA
S
STATE FIRE
MARSHAL LISTING
S
SHEETS
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
OFFICE OF THE STATE FIRE MARSHAL -
FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM
LISTING SERVICE
LISTING No. 57'0252 Page 1 of I
CATEGORY: 7125-- FIRE ALARM DEVICES FOR THE HEARING IMPAIRED
LISTEE: Siemens Industry, Inc. Building Technologies Division8 Fernwood Road, Florham Park, NJ
07932
Contact: Evelyn Esteban (973) 593-6582 Fax (973) 593-6652
Email: evelyn.esteban@siemens.com
DESIGN: Models ST-MC-RETRO-R, ZR-MC-W, ZR-MC-R, ZR-HMC-R, ZR-HMC-W intended for indoor
use on walls.
Models ST-MC-CW, ST-HMC-CW, ZR-MC-CR, ZR1tCC ZR-HMC-CR, and ZR-HMC-CW
multi candela intended for indoor use mounted on the ceiling only.
Z -series strobes are intended for use with models ZB-R or ZB-W back boxes. ST - series
strobes are intended for use with models SHBBS surface back boxes. Model numbers may
be followed by alpha characters indicating lens orientation, lettering, and color. Refer to
listee's data sheet for additional detailed product description and operating considerations.
RATING: Electrical 16-33VDC/FWR
Candela: ST-MC-RETRO-R 15cd, 30cd, 75cd, 110cd
ZR-MC-W, ZR-MC-R 15cd, 30cd, 75cd, llOcd
ZR-MC-CR, ZR-MC-CW 15cd, 30cd, 75cd, 95cd
ST-MC-CW 15cd, 30cd, 75cd, 95cd
ZR-HMC-R, ZR-HMC-W 135/185cd
S ZR-HMC-CR, ZR-HMC-CW 115/177cd
Flash Rate: 60 flashes / minute
INSTALLATION: In accordance with Listee's printed installation instructions, applicable codes &
ordinances and in a manner acceptable to the authority having jurisdiction. Models with suffix
-w are wall mount only. Models with suffix -C are ceiling mount only. All models are for
indoor use only.
MARKING: Listee's name, model number, electrical / candela rating and UL label.
APPROVAL: Listed as strobe light suitable for the hearing impaired when used with separately listed
electrically compatible fire alarm control units. Refer to listee's installation instruction manual
for details.
NOTE:
9-1 O-2007mt
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed
the test results and/or other data but does not make an independent verification of any claims. This listing is not
an endorsement or recommendation of the item listed. This listing should not be used to verify correct
I?V, operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other
Date Issued: July 01, 2016 Listing Expires June 30, 2017
Authorized By: DAVID CASTILLO, Program Coordinator
Fire Engineering Division
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM
LISTING SERVICE
LISTING No. 7d250.0:62:Q248 Page 1 of I
CATEGORY: 7125-- FIRE ALARM DEVICES FOR THE HEARING IMPAIRED
LISTEE: Siemens Industry, Inc. Building Technologies Division8 Fernwood Road, Florham Park, NJ
07932
Contact: Evelyn Esteban (973) 593-6582 Fax (973) 593-6652
Email: evelyn.estebansiemens.com
DESIGN: Models NH-R, NH-W, NH-CR, NH-CW, ZH-R, and ZH-W horns and models NS-MC-R,
NS-MC-W, ZH-MC-R, ZH-MC-W, ZH-HMC-R, AND ZH-HMC-W Horns / Strobes. Models
NS-MC-CR, NS-MC-CW, NS-HMC-CR, NS-HMC-CW, ZH-MC-CR, C=OW ZH-HMC-CR,
ZH-HMC-CW are horn / strobes for ceiling mount only. Suffix CR or CW are for ceiling and
color. Units are synchronized or non-synchronized strobes. Refer to Listee's data sheet for
additional detailed product description and operational
RATING: Electrical 16-33VDC/FWR
Candela: NS-MC-C, ZH-MC-C = 15/30/75/95 candela
NS-HMC-C, ZH-HMC-C = 115 / 177 cd
NS-MC, ZH-MC = 15/30/75/110 cd
ZH-HMC, = 135/185 cd
Flash Rate: 60 flashes / minute
•
INSTALLATION: In accordance with Listee's printed installation instructions, applicable codes &
ordinances and in a manner acceptable to the authority having jurisdiction.
MARKING: Listee's name, model number, electrical / candela rating and UL label.
APPROVAL: Listed as audible and audible /1 visual signaling devices for use with separately listed
electrically compatible fire control units. Models with strobe lights are suitable for the hearing
impaired. For indoor use only. All synchronization strobes shall be used with model DSC
sync control module (CSFM listing No. 7300-0067:212). Refer to manufacturer's installation
manual for details
Note: These appliances can produce a distinctive three-pulse Temporal Pattern Fire Alarm
Evacuation Signal (for total evacuation ) in accordance with NFPA 72, 2002 Edition.
NOTE:
09-07-2007
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed
the test results and/or other data but does not make an independent verification of any claims. This listing is not
an endorsement or recommendation of the item listed. This listing should not be used to verify correct
operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other
Date Issued: July 01, 2016 Listing Expires June 30, 2017
Authorized By: DAVID CASTILLO, Program Coordinator
Fire Engineering Division