HomeMy WebLinkAbout2525 EL CAMINO REAL; 207; FPC2018-0112; PermitII A'604 11] l
(city of
Carlsbad
Print Date: 01/12/2022
Job Address: 2525 EL CAMINO REAL, # 207, CARLSBAD, CA 92008-1206
Permit Type: FIRE-Construction Commercial Work Class: Fire Sprinklers
Parcel U: 1563022700 Track U:
Valuation: $209,295.00 Lot #
Occupancy Group: Project U:
#of Dwelling Units: Plan U:
Bedrooms: Construction Type:
Bathrooms: Orig. Plan Check U:
Plan Check U:
Project Title:
Description: FOOTLOCKER (LANDLORD SHELL) -SPRINKLER TI (48 HEADS)
Permit No: FPC2019-0112
Status: Closed - Finaled
Applied: 04/17/2018
Issued: 04/24/2018
Finaled Close Out: 02/02/2021
Inspector:
Final Inspection:
Applicant: FPContractor:
BRADSHAW ENGINEERING CORP BRADSHAW ENGINEERING CORP
DAVID BILODEAU 8645 ARGENT ST
8645 ARGENT ST SANTEE, CA 92071-4179
SANTEE, CA 92071-4179 (619) 448-4300
(619) 444-4300
FEE AMOUNT
FIRE NFPA 13 or 13R System 7- 100 heads $536.00
Total Fees: $536.00 Total Payments To Date: $536.00 Balance Due: $0.00
Fire Department Page 1 of 1
1635 Faraday Avenue, Carlsbad CA 92008-7314 1 760-602-4665 1 760-602-8561 f I www.carlsbadca.gov
1. Fric.2-019 -Dill
Page 1 of 7
MICROMATIC@ STANDARD
CHNI ALDATA RESPONSE PENDENT
SPRINKLER VK1 02 (K5.6)
The Viking Corporation, 210 N Industrial Park Drive, Hastings Ml 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com
DESCRIPTION
The Viking Micromatic® Standard Response Pendent VK102 Sprinkler is a small,
thermosensitive, glass-bulb spray sprinkler available in several different finishes and
temperature ratings to meet design requirements. The special Polyester, and Electroless
Nickel PTFE (ENT) coatings can be used in decorative applications where colors are
desired. In addition, these coatings have been investigated for installation in corrosive
atmospheres and are listed/approved as corrosion resistant as indicated in the Approval
Charts. (Note: FM Global approves the ENT coating as corrosion resistant. FM Global has no
approval classification for Polyester coatings as corrosion resistant.)
Viking standard response sprinklers may be ordered and/or used as open sprinklers (glass bulb
and pip cap assembly removed) on deluge systems. Refer to Ordering Instructions.
LISTINGS AND APPROVALS
cULus Listed: Category VNIV
FM Approved: Class Series 2000
VdS Approved: Certificate G414006 & G414004
LPCB Approved
CE CE Certified: Standard EN 12259-1, EC-certificate of conformity 0832-CPD-2021
CCCF Approved: Approved by the China Certification Center for Fire Products (CCCF)
NOTE: Other International approval certificates are available upon request.
Refer to Approval Charts and Design Criteria for listing and approval requirements that must be followed.
TECHNICAL DATA
Specifications:
Minimum Operating Pressure: 7 psi (0.5 bar)t
Maximum Working Pressure: 175 psi (12 bar) wwp
Factory tested hydrostatically to 500 psi (34.5 bar)
Thread size: 1/2" NPT, 15 mm BSP
Nominal K-Factor: 5.6 U.S. (80.6 metric**)
Glass-bulb fluid temperature rated to -65 °F (-55 °C)
Overall Length: 2-1/4" (57 mm)
t cULus Listing, FM Approval, and NFPA 13 installs require a minimum of 7 psi (0.5 bar). The minimum operating pressure for LPCB and CE
Approvals ONLY is 5 psi (0.35 bar).
Material Standards:
Frame Casting: Brass UNS-C84400 or QM Brass
Deflector: Phosphor Bronze UNS-051000tt or Copper UNS-C19500
Bulb: Glass, nominal 5 mm diameter
Belleville Spring Sealing Assembly: Nickel Alloy, coated on both sides with PTFE Tape
Screw: Brass UNS-C36000
Pip Cap and Insert Assembly: Copper UNS-C11000 and Stainless Steel UNS-530400
For Polyester Coated Sprinklers: Belleville Spring-Exposed
For ENT coated Sprinklers: Belleville Spring - Exposed, Screw and Pipcap - ENT plated.
ttNot for FM Approval.
Ordering Information: (Also refer to the current Viking price list.)
Order Micromatic® Standard Response Pendent VK102 by first adding the appropriate suffix for the sprinkler finish and then the
appropriate suffix for the temperature rating to the sprinkler base part number.
Finish Suffix: Brass = A, Chrome = F, White Polyester = M-/W, Black Polyester = M-/B, Wax Coated = C, Wax Over Polyester = V-NV,
ENT = JN
Form No. F_031414 17.10.05 Rev 17.2 Replaces Form No. F_031414 Rev 17.1
(Added new standard wrench 21475)
Page 2 of 7
MICROMATICO STANDARD
RESPONSE PENDENT
SPRINKLER VK102 (K5.6)
The Viking Corporation, 210 N Industrial Park Drive, Hastings Ml 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com
Temperature Suffix: 135 °F (57 °C) = A, 155 °F (68 °C) = B, 175 °F (79 °C) = D, 200 °F (93 °C) = E, 212 °F (100 °C) = M, 286 °F
(141 °C) = G, 360 °F (182 °C) = H, 500 °F (260 °C) = L.
For example, sprinkler VK102 with a 1/2" thread, Brass finish and a 155 °F (68 °C) temperature rating = Part No. 12987AB
Available Finishes And Temperature Ratings: Refer to Table 1.
Accessories: (Also refer to the Viking website.)
Sprinkler Wrenches:
Standard Wrench: Part No. 21475M/B (available since 2017).
Standard Wrench for Wax Coated Sprinklers: Part No. 10896W/B (available since 2000)
Socket Wrench for Recessed Pendent Sprinklers: Part No. 13655W/B* (available since 2006)
Optional Protective Sprinkler Cap Remover/Escutcheon Installer Tool** Part No. 15915 (available since 2010.)
Socket Wrench for Wax Coated Sprinklers: Part No. 13577W/B* (available since 2006)
*A 1/2 ratchet is required (not available from Viking).
**Allows use from the floor by attaching a length of 1" diameter CPVC tubing to the tool. Ideal for sprinkler cabinets. Refer to Bulletin F_051808.
Sprinkler Cabinets:
Six-head capacity: Part No. 01724A (available since 1971)
Twelve-head capacity: Part No. 01725A (available since 1971)
INSTALLATION
Refer to appropriate NFPA Installation Standards.
OPERATION
During fire conditions, the heat-sensitive liquid in the glass bulb expands, causing the glass to shatter, releasing the pip cap and
sealing spring assembly. Water flowing through the sprinkler orifice strikes the sprinkler deflector, forming a uniform spray pattern
to extinguish or control the fire.
INSPECTIONS, TESTS AND MAINTENANCE
Refer to NFPA 25 for Inspection, Testing and Maintenance requirements.
AVAILABILITY
The Viking Micromatic® Standard Response Pendent Sprinkler VK102 is available through a network of domestic and international
distributors. See The Viking Corporation web site for the closest distributor or contact The Viking Corporation.
GUARANTEE
For details of warranty, refer to Viking's current list price schedule or contact Viking directly.
Form No. F_031414 17.10.05 Rev 17.2
Page 3 of 7
f to
MICROMATIC@ STANDARD
6AL RESPONSE PENDENT
SPRINKLER VK1 02 (K5.6)
The Viking Corporation, 210 N Industrial Park Drive, Hastings Ml 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com
-NI "_ WIN jy1glaR&IIIjIlli mg.111 1* if-
Sprinkler Temperature Sprinkler Nominal Maximum,, Ambient U 0 O( Bulb Color Classification Temperature Rating' Ceiling Temperature'
Ordinary 135 °F (57 °C) 100 °F (38 00) Orange
Ordinary 155 °F (68 °C) 100 OF (38 0C) Red
Intermediate 175 °F (79 °C) 150 °F (65 °C) Yellow
Intermediate 200 °F (93 °C) 150 °F (65 °C) Green
High 286 °F (141 00) 225 °F (107 °C) Blue
Extra High 360 °F (182 00) 300 °F (149 °C) Mauve
Ultra High' 500 °F (260 °C) 465 °F (240 °C) Black
Sprinkler Finishes: Brass, Chrome, White Polyester, Black Polyester, and ENT
Corrosion-Resistant Coatings4: White Polyester and Black Polyester in all temperature ratings. ENT in all temperature ratings ex-
cept 135 °F (57 00) Wax-Coated Brass and Wax over Polyester' for sprinklers with the following temperature ratings:
155 °F (68 00) Lt. Brown Wax 175 °F (79 00) Brown Wax 200 °F (93 00) Brown Wax
212 °F (100 °C) Dk. Brown Wax' 286 °F (141 00) Dk. Brown Wax'
Footnotes
1 The sprinkler temperature rating is stamped on the deflector.
2 Based on NFPA-1 3. Other limits may apply, depending on fire loading, sprinkler location, and other requirements of the Authority Having Jurisdiction.
Refer to specific installation standards.
Sprinklers of Ultra-High temperature rating are intended for use inside ovens, dryers, or similar enclosures with normal operating temperatures above
300 °F (149 00) Where the ambient temperature around the Ultra-High temperature rated sprinkler is significantly reduced below 300 °F (149 °C),
response time may be severely retarded.
The corrosion-resistant coatings have passed the standard corrosion test required by the approving agencies indicated in the Approval Charts. These
tests cannot and do not represent all possible corrosive environments. Prior to installation, verify through the end-user that the coatings are com-
patible with or suitable for the proposed environment. For automatic sprinklers, the coatings indicated are applied to the exposed exterior surfaces
only. Note that the spring is exposed on sprinklers with Polyester and ENT coatings. For ENT coated automatic sprinklers, the waterway is coated.
Wax melting point is 170 °F (76 0C) for 212 °F (100 0C) and 286 °F (141 °C) temperature rated sprinklers.
Wrench Flat
Protective Sprinkler Cap
Standard Sprinkler Standard Sprinkler Wrench for Wax
Wrench 21475M/B Coated Sprinklers 10896W/B
Figure 1:
Standard Sprinkler Wrenches
FormNo.F_031414 17.10.05 Rev 17.2
Page 4 of 7
MICROMATICO cii HNICALIDA RESPONSE
'JI 11(?I iiL rZ jioZi J
The Viking Corporation, 210 N Industrial Park Drive, Hastings Ml 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com
Approval Chart I (UL)
Mromatic"° Standard Response Pendent Sprinkler VK102 [AI-X4 Maximum 175 PSI (12 bar) WWP
Sprinkler Thread Size Nominal Overall Length Listings and Approvals3
Base Part SIN K-Factor (Refer also to UL Design Criteria.)
Number' NPT BSP U.S. I metric2 Inches I mm cULus' JVdSJ LPCB (( 8
Standard Orifice
12987 VK102 1/2" 15 mm 5.6 80.6 2-1/4" 57 Al, 84, BlY, C5, 03, E6, G6Z A2 A2, B4, B2Y F2, G2Y -- --
12989 VK102 -- 15 mm 5.6 80.6 2-1/4" 57 Al, 84, B1Y, C5, 03, E6, G6Z A2 A2, B4, B2Y F2, G2Y -- --
19776 VK102 1/2" -- 5.6 80.6 2-1/4" 57 - -- -- -- -- E7
20229 VK102 -- 15 mm 5.6 80.6 2-1/4" 57 - -- -- -- -- E7
10139 rvK102 1/2" 15 mm 5 80.6 2-1/4" 57 Al, B4, B1Y, C5, D3, E6, G6Z -- -. -- -- --
10173 VK102 -- 15 mm 5.6 80.6 2-1/4" 57 Al, B4, B1Y, C5, D3, E6, G6Z A2 A2, B4, B2Y -- -- --
18020 VK102 1/2" 15 mm 5.6 80.6 2-1/4" 57 Al, B4, B1Y, C5, D3, E6, G6Z A2 A2, B4, B2Y F2, G2X F29'1° --
Approved Temperature Ratings
A - 135 "F (57 °C), 155 "F (68 °C), 175 °F (79
"C), 200 °F (93 "C), 286 "F (141 °C), and 360 Approved Finishes
°F (182 °C) 1 - Brass, Chrome, White Polyester5'6, and Black 5.6 Approved Escutcheons
B - 135 °F (57 °C) 155 "F (68 °C) 175 °F (79 Polyester
Recessed th the Viking MicromaticO Model °C), °F "C) ' and 200 (93 2 - Brass, Chrome, White Polyester6, and Black Polyester6 E-1, E-2, or E- Recessed Escutcheon
C - 286 °F (141 "C) 3 - Brass and Chrome V - Standard surface-mounted escutcheon or the
D - 500 °F (260 "C)7 4 - Wax-Coated Brass and Wax Over Polyester' Viking Microfast® Model F-i Adjustable Escutcheon
E - 155 °F (68 °C), 175 "F (79 °C), 200 "F (93 5-High Temperature 200°F (93 °C) Wax Coating (corro- or recessed with the Viking Micromatic® Model E-1,
"C), 286 "F (141 "C), 360 "F (182 °C), and 500 sion resistant); maximum ambient temperature allowed at E-2, or E-3 Recessed Escutcheon
°F (260 "C)7 ceiling = 150 °F (65 °C) Z - Standard surface-mounted escutcheon or re-
F - 155 °F (68 "C), 175 °F (79 °C), 200 °F (93 6- ENT5 cessed with the Viking Micromatic® Model E-1
°C), 286 °F (141 °C), and 360 "F (182 °C) 7 - Chrome
G - 155 "F (68 °C), 175 °F (79 °C), and 200 °F
(93 °C)
Footnotes
Base part number is shown. For complete part number, refer to Viking's current price schedule,
2 Metric K-factor shown is for use when pressure is measured in bar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0.
'This table shows the listings and approvals available at the time of printing. Check with the manufacturer for any additional approvals.
4Listed by Underwriters Laboratories Inc. for use in the U.S. and Canada.
cULus Listed as corrosion resistant.
Other colors are available on request with the same Listings and Approvals as the standard colors.
Sprinklers of Ultra-High temperature rating are intended for use inside ovens, dryers, or similar enclosures with normal operating temperatures above 300 °F (149 °C). Where the
ambient temperature around the Ultra-High temperature rated sprinkler is significantly reduced below 300°F (149 °C), the response time of the Ultra-High temperature rated sprinkler
may be severely retarded.
8CE Certified, Standard EN 12259-1, EC-certificate of conformity 0832-CPD-0021.
MED Certified, Standard EN 12259-1, EC-certificate of conformity 0832-MED-1003 and 0832-MED-1008.
° IVIED Certified, RINA Certificate No. ME0497705C5.
DESIGN CRITERIA UL
(Also refer to Approval Ch a rl 1
cULus Listing Requirements:
The Viking Micromatic® Standard Response Pendent Sprinkler VK102 is cULus Listed as indicated in Approval Chart 1 for installation in accordance
with the latest edition of NFPA 13 for standard spray sprinklers.
Designed for use in Light, Ordinary, and Extra Hazard occupancies.
The sprinkler installation rules contained in NFPA 13 for standard spray pendent sprinklers must be followed.
IMPORTANT: Always refer to Bulletin Form No. F_091699 - Care and Handling of Sprinklers. Also refer to page F_080614 for
general care, installation, and maintenance information. Viking sprinklers are to be installed in accordance with the latest
edition of Viking technical data, the appropriate standards of NFPA, LPCB, APSAD, VdS or other similar organizations, and
also with the provisions of governmental codes, ordinances, and standards, whenever applicable.
Form No. F031414 17.10.05 Rev 17.2
Page 50f7
MICROMATICO STANDARD
Jr HN GA RESPONSE PENDENT xN SPRINKLER VK1 02 (K5.6)
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com
Approval Chart 2 (FM)
-
KEY Micromatic Standard Response Pendent Sprinkler VK102
Maximum 175 PSI (12 bar) WWP AIX,4_
Sprinkler Base Thread Size Nominal K-Factor Overall Length FM Approvals3
Part Number'
f
SlNj (Refer also to Design Criteria below.) NPT I BSP U.S. I metric2 Inches mm
Standard Orifice
12987 VK102 1 1/2" 15 mm 5.6 80.6 2-1/4" 1 57 Al, B2, C3, Dl, E4, G1Y, G4Z
12989 VK102_j -- 15 mm 5.6 80.6 2-1/4"57 Al, B2, C3, Dl, E4, G1Y, G4Z
10139 VK102 1/2" 15 mm 5.6 80.6 2-1/4" 57 Al, B2, C3, Dl, E4, G1Y, G4Z
10173 VK102 -- 15 mm 5.6 80.6 2-1/4" 57 Al, B2, 03, Dl, E4, G1Y, G4Z
18020 VK102 1/2" 15 mm 5.6 80.6 2-1/4" 57 Al, B2, 03, Dl, G1Y
Approved Temperature Ratings
A - 135 F (57 °C), 155 °F (68 0C), 175 0F (79
°C), 200 °F (93 °C), 212 °F (100 °C),
286 °F (141 °C), and 360 °F (182 °C) Approved Finishes Approved Escutcheons
B - 135 0F (57 °C), 155 °F (68 °C), 175 0F (79 °C), 200 F 1 - Brass, Chrome, White Polyester', and Y - Standard surface-mounted escutch-
(93 00), and 212 °F (100 °C) Black Polyester' eon or the Viking Microfast® Model F-i
C - 286 0F (141 00) 2 - Wax-Coated Brass (corrosion resistant) Adjustable Escutcheon or recessed with the
D - 500 °F (260 00)5 3 - High Temperature 200 °F (93 00) Wax Viking Micromatic® Model E-1, E-2, or E-3
E - 155 °F (68 00) 175 °F (79 00) 200 °F (93 00) 286 °F Coating (corrosion resistant); maximum am- Recessed Escutcheon
(141 00), 360 °F (182 00) and 500 °F (260 00)5 bient temperature allowed at the ceiling = Z - Standard surface-mounted escutcheon
0F 00) 150 (65 or re- cessed with the Viking Micromatic® F - 135 °F (57 00) 155 °F (68 00) 175 °F (79 00) and ENT6 Model E-1
200 °F (93 00)
G - 155 °F (68 00) 175 0F (79 00) and 200 °F (93 °C)
Footnotes
1 Base part number is shown. For complete part number, refer to Viking's current price schedule,
2 Metric K-factor shown is for use when pressure is measured in bar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0.
This table shows the listings and approvals available at the time of printing. Check with the manufacturer for any additional approvals.
Other colors are available on request with the same Approvals as the standard colors.
Sprinklers of Ultra-High temperature rating are intended for use inside ovens, dryers, or similar enclosures with normal operating temperatures above 300 0F (149 0C).
Where the ambient temperature around the Ultra-High temperature rated sprinkler is significantly reduced below 300 0F (149 0C), the response time of the Ultra-High
temperature rated sprinkler may be severely retarded.
6 FM approved as corrosion resistant.
DESIGN CRITERIA - F,V1
(A so I 5101 ( Apis vol Chori 2
FM ADoroval Reauirements:
The Viking Micromatic® Standard Response Pendent Sprinkler VK102 is is FM Approved as standard response Non-Storage pendent sprinkler as
indicated in the FM Approval Guide. For specific application and installation requirements, reference the latest applicable FM Loss Prevention Data
Sheets (including Data Sheet 2-0). FM Global Loss Prevention Data Sheets contain guidelines relating to, but not limited to: minimum water supply
requirements, hydraulic design, ceiling slope and obstructions, minimum and maximum allowable spacing, and deflector distance below the ceiling.
NOTE: The FM installation guidelines may differ from cULus and/or NFPA criteria.
IMPORTANT: Always refer to Bulletin Form No. F_091699 - Care and Handling of Sprinklers. Also refer to page F_080614 for
general care, installation, and maintenance information. Viking sprinklers are to be installed in accordance with the latest
edition of Viking technical data, the appropriate standards of NFPA, FM Global, LPCB, APSAD, VdS or other similar organiza-
tions, and also with the provisions of governmental codes, ordinances, and standards, whenever applicable.
Form No. F_031414 17.10.05 Rev 17.2
..;•;.. V
Sprinkler wrench 13655W/B**
for recessed pendent
sprinklers
** A 1/2" ratchet is required
(not available from Viking)
Step 1: Carefully slide the I wrench sideways around the
deflector, ensuring engage-
ment with the sprinklger
wrench flats.
IN-
Pendent Sprinkler
Sprinkler wrench 13577W/B**
must be used for installing
wax coated sprinklers.
Page 6o17
MICROMATICO STANDARD
RESPONSE PENDENT
The Viking Corporation, 210 N Industrial Park Drive, Hastings Ml 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com
Carefully slide the wrench sideways around
the protective cap, ensuring engagement with
the sprinkler wrench flats
Figure 2: Wrench 13655W/B for Recessed Pendent Sprinklers
** A 1/2" ratchet is required Step 2: Carefully press the wrench upward and
(not available from Viking) ensure engagement with the sprinkler wrench
flats.
Figure 3: Socket Wrench for Wax Coated Sprinklers 13577W/B
Form No. F_031414 17.10.05 Rev 17.2
1-1/8"
(29 mm)
Mm.
1-1/81,
(5 l
Ceiling Opening Size:
2-5/16" (59 mm) minimum
2-1/2" (64 mm) maximum
Page 7of7
MICROMATIG& STANDARD
RESPONSE PENDENT
SPRINKLER VK102 (K5.6)
The Viking Corporation, 210 N Industrial Park Drive, Hastings Ml 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcsvikingcorp.com
Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com
Ceiling Opening Size:
2-5/16" (59 mm) minimum 1/2" -. 2-1/2" (64 mm) maximum (15
NPT
mm)
L.. -.
j__T8l
T(3E 2-3/16" Ipql !P 1-3/4" 2" mm) (56 mm) II [1 II 1 (51 mm) '-i.I Miii. (45 Max.
Installed with a standard Installed with a Microfast Note: At maximum, adapter is 1/8" surface-mounted Model F-I Adjustable exposed 1/2" (13 mm) from fac
escutcheon Escutcheon of ceiling
Figure 4: Sprinkler Dimensions with a Standard Escutcheon and the Model F-I Adjustable Escutcheon
_C
I._ 2-1/8"
(54 mm)
1-3/4"
(45 mm)
Max.
Installed with a Installed with a Model
Model E-1 Recessed E-2 Thread-on Recessed
Escutcheon Escutcheon
Figure 5: Sprinkler Dimensions with the Model E-I and E-2 Recessed Escutcheons
Form No. F_031414 17.10.05 Rev 17.2 Replaces Form No. F_031414 Rev 16.2
(Added new standard wrench 21475)