HomeMy WebLinkAbout1917 PALOMAR OAKS WAY; ; FPC2018-0345; PermitPERMIT REPORT
(City of
Carlsbad
Print Date: 01/12/2022 Permit No: FPC2018-0345
Job Address: 1917 PALOMAR OAKS WAY, CARLSBAD, CA 92008-5512 Status: Closed - Finaled
Permit Type: FIRE-Construction Commercial Work Class: Fire Alarm
Parcel #: Track U: Applied: 10/18/2018
Valuation: $0.00 Lot U: Issued: 11/05/2018
Occupancy Group: Project U: Finaled Close Out: 01/14/2020
#of Dwelling Units: Plan U:
Bedrooms: Construction Type:
Bathrooms: Orig. Plan Check U: Inspector:
Plan Check U: Final Inspection:
Project Title:
Description: WASATCH CORNERSTONE - FIRE ALARM REPLACE MXL IQ PANEL WITH NEW XLS PANEL
Applicant: FPContractor:
SIEMENS SIEMENS INDUSTRY INC
CHRIS BISCHEL P0 BOX 80600
10100 WILLOW CREEK RD INDIANAPOLIS, IN 46280-0600
SAN DIEGO, CA 92131-1636 (630) 857-2100
(858) 265-9894
FEE AMOUNT
FIRE TI Fire Alarm System $620.00
Total Fees: $620.00 Total Payments To Date: $620.00 Balance Due: $0.00
Fire Department Page 1 of 1
1635 Faraday Avenue, Carlsbad CA 92008-7314 1 760-602-4665 1 760-602-8561 f I www.carlsbadca.gov
SIEMENS
Industry, Inc.
10100 Willow Creek Rd
San Diego, Ca 92131
Phone: 858-880-2085
Fax: 855-866-7942
Wasatch Cornerstone
MXL to XLS Migration
1917 Palomar Oaks Way
Carlsbad, CA 92008
FPC20I8-0345
1917 Palomar Oaks WAY
WASATCH CORNERSTONE - FIRE ALARM REPLACE MXL
0 PANEL WITH NEW XLS PANEL
10/2212018
FPC20I8-0345
V
Modular assembly
Supervised remote printer
32-character custom messages
40 programmable macro, function buttons
Thermal strip printer
Security-device monitoring
(®UL 1076 Listed)
Sprinkler Supervision
Degrade-mode operation
User help screens
Coded outputs
Distributed processing
UUKL Listed for smoke control
®UL 864 9th Edition Listed & OULC Listed;
FM, CSFM & NYC Fire Dept. Approved
- UUFLU by all rite Salety
Management Stations
Multiple command stations
Menu-driven operator commands
5000-event, history-logging capability
with on-line and off-line reports
Multiple levels of password protection
Automatic environmental compensation
for smoke detectors
Alarm verification
by device or zone
I Pre-alarm operation
Logic-controlled output functions
Time-based-controlled output functions
Holiday schedule
City tie! leased line
200 notification-appliance-circuits
(NACs) capacity
Up to 3.0 amps (24VDC) per NAC
Built-in strobe synchronization protocol
Supports pre-action,
deluge and agent releasing
Voice evacuation system (optional)
NEC 760 power-limited circuits
(®UL 864 Compliant)
Intelligent interface to building! process
management systems
Operates as interactive peer with other
XLS or XLSV units in a XNET network
Detector Sensitivity Readout! Printout
perNFPA72
SIEMENS Data Sheet
Fire Safety Products
FireFinder® XLS
Advanced Fire Alarm Control Panel
ARCHITECT AND ENGINEER SPECIFICATIONS
Standard! 2500-point-capacity -
addressable fire-alarm control
panel (FACP)
Ability to network with other
FireFinder XLS systems
Powerful, easy-to-use
programming capabilities
Fully field programmable, via
Windows® laptop PC
6(15.2 cm), backlit LCD display
User-friendly system interface
Touch screen for maintenance
operations and function keys
Global annunciation and control
capability
Multi-language display
Universal AC power input:
120VAC - 240VAC @ 50/60Hz
l2 amps of system power
(expandable to 48 amps)
Numerous Relays: Alarm, Trouble,
Programmable, etc.
Sure Wir&1" addressable-loop technology
Polarity-insensitive detection circuits
(patented)
Useful diagnostic LEDs on all cards
Supports FirePrintTm application-specific
detection
Intelligent/analog detection circuits:
'Class A' or'Class B'
Supports single-person 'Walk Test'
Seismic certified
1'
System Overview
FireFinder XLS is a microprocessor-based, advanced
fire-safety system that has a 6' display and large, lighted
buttons; making it a highly intuitive fire-alarm user
interlace. Additionally, each FireFinder XLS panel has a
unique multiprocessor 'Network design - as well as
providing connectivity to detection devices.
FireFinder XLS is ideally suited for commercial,
institutional and industrial fire detection and notification
applications. This FACP complies with the requirements
of NFPA Standard 72, and is listed by Underwriters
Laboratories under their ®UL 864 standard.
Underwriters Laboratories of Canada also lists
FireFinder XLS FACP5 under tULC-S527.
SIEMENS Industry, Inc.
Building Technologies Division
FireFinder XLS is Factory Mutual (FM 43010) Approved; as
well as California State Fire Marshals (CSFM 07165-
0067:0222) and NYC Fire Department (4t6160) Approved.
Additionally, FireFinder XLS is ®UL Listed under the category
UUKL for smoke control.
FireFinder XLS is also ®UL Listed and FM Approved for
Sinorix® clean-agent systems and pre-action or deluge
sprinkler systems, which include foam or water applications.
FireFinder XLS operates on the releasing requirements
specified in NFPA 13 and 2001.
FireFinder XLS is listed as a Fireman's Smoke Control Station
in high-rise office buildings, malls and other large structures.
FireFinder® XLS System Overview 6300
System Overview - (continued)
The FireFinder XLS system has been seismic
qualified in accordance with:
International Building Code, 2006 Edition
California Building Code, 2007 Edition
ASCE Standard 7, 2005 Edition
OSHPD, OSP-0057-10
OSHPD CAN 2-1708A.5, Rev. 3
ICC-ES AC 156, effective 1/1/2007
System Components
A basic FireFinder XLS FACP consists of the following sub-
assemblies: Person Machine Interface (Model PMI-2); Power
Supply (Model PSC-i 2); Device Loop Card (Model DLC); Zone
Indicating Card (Model ZIC-4A); Card Cage (Model CC-5);
Inner Door Blank Single Plate (Model ID-SP); CAB-1, CAB-2 or
CAB-3 enclosures.
Optional modules that can be installed with this FACP
include: Card Cage (Model CC-2); Network Interface Card
(Model NIC-C); 8-Circuit Zone Indicating Card (Models ZIC-
813 I Z[C-20; Control Relay Card (Model CRC-6); Output
Control Module (Model OCM-16); Switch Control Module
(Model SCM-8); LED Control Module (Model LCM-8); Fan
Control Module (Model FCM-6); Supervised Input Module
(Model SIM-16); Power Supply Extender (Model. PSX-12);
Remote Network Interface (Model RNI); Remote Printer
Module (Model RPM); System Status Display (Model SSD);
Multi-Point Digital Alarm Communicator (Model MDACT);
Two-Module Remote Enclosure (Model REMBOX2);
Four-Module Remote Enclosure (Model REMBOX4).
FireFinder XLS is compatible with a full line of intelligent
initiating devices, highlighted by the FirePrint application-
specified detectors: Models HFP-1 1 and HFPT-1 1.
FireFinder XLS functions with the Siemens Fire Safety
portfolio of graphics command centers.
Fire Safety Management Stations - XLS Compatible
FireFinder XLS Compatibility with Siemens
Fire Safety Management Stations
FireFinder XLS panels are compatible with Siemens Fire
Safety Management Stations, which provide integrated
and reliable FACP monitoring and control of XLS system
events - including: Alarm, Trouble, Security and
Supervisory commands.
Each management station includes PC-,based, color-
graphics software designed for use with the XNET
network, offering full control and annunciation.
An extensive history log of all XLS-FACP events, as well as
extensive report-generation capabilities, is easily
maintained. Additionally, user-programmable function
buttons allow site-specific control functions.
SIEMENS Industry, Inc.
Building Technologies Division
PMI-3 -*Person Machine Interface 3
PMI-3 - Person Machine Interface 3
The Person Machine Interface 3 (Model PMI-3) is the
primary user interface and central microprocessor for each
FireFinder FACP. Additionally, Model PMI-3 serves as both
operator interface and central microprocessor for each XLS.
Enhancements to the third version of the Person Machine
Interface include go-to-beginning, go-to-end queue buttons;
a front-end command screen with Alarm I Supervisory
I Trouble light-emitting diodes (LEDs), and three (3) types
of alternate-language overlays orderable in a single (1) part.
(see: Details for Ordering section below for more info.)
FireFinder XLS FACPs are controlled and operated from
Model PMI-3, which uses large, lighted buttons to prompt
the end-user to the next available, correct system operation
(i.e. - Acknowledge I Silence I Unsilence I Audible I Reset).
The controller in Model PMI-3 provides a 6" (15.2 cm.) front-
end touch screen comprised of system-status LEDs as well as
a liquid-crystal display (LCD) of 1200 -x-800 pixels.
There are overlays that provide naming in alternate
languages for visual indicators found on the front of each
Model PMI-3. Each overlay is assigned on the outer
assembly, respectively, when affixed to the display on the
user interface.
Model PMI-3 contains the site-specific program
configuration created in the software tool, Zeus.
ZIC-4A -*Zone Indicating Card
ZIC-4A Zone Indicating Card
The Zone Indicating Card (Model ZlC-4A) provides four (4)
fully supervised, programmable output circuits for use on
each FireFinder XLS. Model ZlC-4A supplies four (4) 'Class B'
(Style Y) or 'Class A' (Style Z) type output circuits, power
limited to 3.0 amps maximum per circuit.
Each circuit for Model ZlC-4A can be independently
programmed for use with listed audible or visual notification
appliances; listed emergency audio speakers; municipal tie
boxes; leased lines, or as releasing circuits.
FireFinder XLS Components - (cont.'d)
Model ZIC-4A plugs into one (1) slot in the Model CC-5 or
Model CC-2 card cage, and has on-board LEDs for system
status and troubleshooting.
Indication of power, communication, internal operation,
and ground-fault conditions are provided, as well as
indication of circuit activation or Trouble conditions.
ZIC-8B I ZIC-2C -* Zone Indicating Cards
ZIC-8B I ZIC-2C
The Zone Indicating Card (Model ZIC-813) provides eight (8)
fully supervised, programmable output circuits for use on
FireFinder XLS. Model ZIC-813 supplies eight (8) 'Class B'
(Style Y) type output circuits, power limited to 2.0 amps
maximum per circuit. Each circuit can be independently
programmed for use with listed audible or visual notification
appliances, or listed emergency audio speakers. Model ZIC-
813 plugs into one (1) slot in the Model CC-5 or Model CC-2
card cage, and has on-board LEDs for system status.
Model ZIC-2C mounts directly on Model ZJC-813, and
allows each of the Model ZIC-813 output circuits to be used
for two-channel voice applications. Indication of power,
communication, internal operation, and ground-fault
conditions are provided, as well as indication of circuit
activation or Trouble conditions.
DLC Device Lopp Card
The Device Loop Card (Model DLC) is the interface for
connection with FireFinder XLS detectors and initiating
devices - including manual stations, control and input
devices. Model DLC plugs into one (1) slot of the CC-2 or CC-
5 card cage. Programming Model DLC is accomplished using
the FireFinder XLS system-programming tool, Zeus.
Model DLC takes one (1) address on the network, and
communicates with two (2) device circuits for a total of 252
detectors and devices. Model DLC has 12 LEDs for diagnostic
purposes, and provides ground-fault detection and zone-
isolation circuitry.
NIC-C Network Interface Card
The Network Interface Card (Model NIC-C) provides HNET or
XNET network communications between enclosures. In
addition to the HNET or XNET communication, Model NIC-C
provides CAN network communication within an enclosure
or external to the enclosure. HNET or XNET communication
can be wired Style 4 or Style 7, but the CAN network can be
wired Style 4 only.
When used for HNET communications, Model NIC-C
provides contact between enclosures on a single system.
When Model NIC-C is used for XNET communications,
Model NIC-C provides communication between systems.
The maximum of XNET Model NIC-C cards on a single
system (single node) is one (1), for a total of 64 XNET
Model N IC-C cards on a peer-to-peer networked system.
Model NIC-C has diagnostic LEDs that indicate: Card Fail,
CAN Fail, HNET Fail, XNET Fail, Ground Fault, Loop 'A' Fail
and Loop 'B' Fail. Model NIC-C Card also has LEDs to indicate
Power, Style and Active Networks.
I fm
HCP -* Control Point Module
HCP Control Point Module
Model HCP provides an intelligent control point for the
FireFinder XLS. Model HCP can be programmed as an
independent, remotely located telephone zone, speaker
zone or notification appliance circuit. Model HCP is
designed to be used with the Siemens - Fire Safety Alarm
Signaling Devices product line.
Model HCP communicates through the Model DLC analog
loop, and can be wired either 'Class A' (Style Z) or 'Class B'
(Style Y). The 24 VDC power input comes from either the
control panel or from any ®UL Listed power-limited,
auxiliary power supply.
MLC -* MXL Line Card [for FireFinder XLS]
SIEMENS Industry, Inc. —3 — Building Technologies Division
FireFinder XLS Components - (cont.'d)
MLC - MXL Line Card [for FireFinder XLS]
The MXL Line Card (Model MLC) is an optional card for
the FireFinder, XLS panel that supplies two (2)
intelligent analog circuits, utilizing the Model ' I ' series;
Model ' ID ' series; Model IL ' series or Model ' FP
series-type intelligent devices. Model MLC occupies two
(2) addresses on the HNET network, ard devices
connected to the Model MLC circuits are dynamically
supervised by FireFinder XLS through the use of a
unique communications protocol.
CRC-6 Controllable Relay Card
The Controllable Relay Card (Model CRC-6), Model CRC-6, is
designed to provide auxiliary control of building functions,
such as: door-holder release, elevator capture, smoke control,
lock release, etc. Model CRC-6 plugs into one (1) slot in the
Model CC-5 or Model CC-2 card cage. Model CRC-6 provides
six (6), fully programmable relays. Each relay contains one (1)
set of SPDT contacts rated at 4 Amps 30 VDC I 120VAC
resistive and 3.5 amps 120VAC inductive (0.6 P.F.)
NRC —* Network Ring Card
NRC Network Ring Card — Second Generation
Model NRC, which is the 2nd generation of Model NRC, is a
networking ring card that transmits single-mode or multi-
mode network communication via fiber-optic or copper
lines. Each card uses a 'Class A' (Style 7) ring configuation
for connection with each FireFinder XLS FACP.
One (1) Model NRC (per system node) provides XNET, peer-
to-peer communication between FireFinder XLS FACPs,
allowing a max, 64, XLS FACPs to be networked together.
CDC-4 —Conventional Detector Card
CDC-4 Conventional Detector Card
The Conventional Detector Card (Model CDC-4) is used
to monitor Siemens Fire Safety conventional detectors
on the FireFinder XLS system. Model CDC-4 can be
used in applications where conventional detectors are
more suited than addressable detectors, such as
hallways or large meeting rooms. Also, Model CDC-4
can be used to upgrade Siemens conventional fire-alarm
panels to the FireFinder XLS system without requiring
detector replacement.
SIEMENS Industry, Inc.
Building Technologies Division
SIM-16 -3 Supervised Input Module
SIM-1 6 Supervised Input Module
The Supervised input Module (Model SIM-1 6) is a remotely
located, general-purpose input module. Model SIM-1 6
provides 16 input circuits for remote system monitoring. Each
input can be individually programmed as supervised (dry-
contact only) or unsupervised (general-purpose input.)
Model SIM-1 6 has two (2) 'Form C' relays. The relays and
inputs are programmed using the Zeus system software-
programming tool.
FCM-6 -* Fan, Motor, Dampers Control Module
FCM-6 Fan, Motor, Dampers Control Module
The Fan. Motor, Dampers Control Module (Model FCM-6) is a
FireFinder XLS command-console option module that
provides manual control of building HVAC system fans,
motors, and dampers. Each Model FCM-6 module provides
six (6) sets of three (3) push-button switches for manual-
system control. Each switch has three (3), associated LEDs to
indicate Fan I Damper / Motor status: OFF (RED LED), ON
(GREEN LED), Trouble (YELLOW LED).
0
MIA
VNTPC -* Virtual Network Tunnel
VNTPC Virtual Network Tunnel
The Virtual Network luhnel (VNT) is an efficient means for real-
time communication, as well as providing support to HNET,
XNET and DNET monitoring and supervision — when used as
part of a Fire Command Center or a Building network. Each
Model VNTPC is a fanless, headless industrial computer,
receiving its operating power from an XLS/V panel.
FireFinder XLS Components —(cont.'d)
CC-2 —Card Cage-2 Slots CC-5 -*Card Cage-5 Slots
CC-5 I CC-2 Card Cages
The Models CC-5 I CC-2 card cages provide the physical
mounting location and all wiring connection points for all
fire-and-voice system options cards for the FireFinder XLS
system. Model CC-5 has five (5) slots, while Model CC-2
has two (2) slots.
All cards plugged into the CC-5 I CC-2 card cage
communicate with other FireFinder XLS modules via a
common data bus. Connectors are provided on the left and
right side of the CC-5 to connect a 60-pin cable for
communications with the FireFinder XLS operator interface,
power supplies and amplifiers modules.
Field wiring to devices and circuits terminates on the
Models CC-5 I CC-2 card cages. All cards designed for use
with the Models CC-5 I CC-2 route their field wiring
terminations to the 'top' of the Model CC-5 I CC-2 card
cages. These connections are all power limited. Internal
wiring connections distribute 24VDC to cards or high-level
audio signals (depending on application used) connect to
the 'bottom' of the Model CC-5 / CC-2 card cages. These
connections are all non-power limited.
All wiring connections to the Model CC-5 / CC-2 card cages
are to removable terminal blocks. Terminal blocks are
rated for use with wire sized 12 American Wire Gauge
(AWG) to 24AWG. Each connector is numbered to make
wiring terminations to the correct position on the
terminal block simple in order to reduce potential wiring
errors.
SCM-8 -* Switch Control Module
SCM-8 Switch Control Module
The Switch Control Module (Model SCM-8) is a FireFinder
XLS-option module that provides manual control to the
Emergency Voice Evacuation System (EVAC) or manual
fire-system control. Each Model SCM-8 module provides
eight (8) momentary push-button switches and 16
light-emitting diodes (LEDs) to indicate their status.
Each switch is assigned two (2) LEDs, as well as a label
to indicate the switch's programmed usage. The label
slides behind a clear protective membrane. One set of
LEDs assigned to each switch is a dual-colored LED,
which is used to indicate what type of signal is active.
SIEMENS Industry, Inc. 5 Building Technologies Division
Each Model SCM-8 switch is fully programmable, and may
be used to control speaker circuits and a wide range of
general-system functions such as: All Call, All Evac,
Warden's Page, Speaker, etc. Any number of circuits may
be grouped and controlled by a single switch.
Switch usages and zone groupings are assigned using the
Zeus system software-programming software. Model
SCM-8 modules are mounted on a hinged panel, as a part
of the FireFinder XLS Command Console enclosure.
LCM-8 - LED Control Module
LCM-8 LED Control Module
The LED Control Module (Model LCM-8) is a FireFinder
XLS-option module that provides LED annunciation for
FireFinder XLS system activity. Each Model LCM-8
contains eight (8) groups of two (2) LEDs - each of which
can be assigned to desired outputs using the Zeus
system software-programming tool.
Eight (8) LEDs are dual-color capable (Red or Green I
flashing or steady). The remaining LEDs are Amber
flashing or steady. A space is provided for labeling of LED
functions. The label slides behind a clear, protective
membrane. Model LCM-8 dimensions are identical to
Model SCM-8, and Model LCM-8 is mounted on the same
hinged panel, as a part of the FireFinder XLS Command
Console enclosure.
RNI -* Remote Network Interface
RNI Remote Network Interface
The Remote Network Interface (Model RN!) provides a
connection point for use with equipment mounted in a
remote-lobby enclosure on the FireFinder XLS FACP.
Model RNI is used to provide additional input, output and
control features to the system remotely, via the main FACP.
These additional features may include control switches
and indicators: (Models SCM-8, LCM-8 and FCM-6),
remote-emergency paging microphones or telephones:
(Models LVM, FMT), or controls used in graphic annunciators
(Models SIM-i 6, 0CM-1 6) or system-status display with the
ability to acknowledge alarms, silence audibles and
reset the system (Model SSD-C-REM).
Model RN! allows The Person Machine Interface to be
mounted in the Model REMBOX2 or Model REMBOX4
remote lobby enclosure.
FireFinder XLS Components - (cont.'d)
111111 'MIlD
g
$019140 11111111
uIluI
II 0'
II 01fl40 II Iuiffi II Ill JI 'I, Ill II I
II iiIii
Ii II
PSC-12 -* Power Supply Charger Module
PSC-12 Power Supply Charger Module
The Power Supply Charger Module (Model PSC-12) is a
high-current power supply that provides the FireFinder
XLS primary-regulated 24VDC power to operate. Model
PSC-12 is rated at 12Amps (Alarm) / 5Amps (Standby),
and has a built-in battery charger, capable of charging up to
100 AH batteries. Model PSC-12 is an addressable-
intelligent, microprocessor-controlled module that
communicates its status to the system-operator interface.
Each Person Machine Interface is then able to query the
status of the power supply to obtain data regarding
system-charging current, terminal-loading information,
ground-fault conditions and more.
PSX-1 2 -* Power Supply Extender
PSX-12 Power Supply Extender
The Power Supply Extender (Model PSX-1 2) is a high-current,
auxiliary power supply that expands the main Model PSC-1 2
power supply and battery charger of the FireFinder XLS
system with an additional 24VDC power. Model PSX-1 2
is rated at 12 Amps.
RPM - Remote Printer Module
RPM Remote Printer Module
The Remote Printer Module (Model RPM) provides a
means of connecting the FireFinder XLS system to a
printer, such as Model PAL-1, for creating a hard copy of
system status and configuration reports. Concurrently,
Model RPM provides an output port that can be
configured to communicate with external systems.
SIEMENS Industry, Inc. 6 Building Technologies Division
-
PTB • Power Termination Board
PTB Power Termination Board
Model PSC-12 comes packaged with a module called the
Power Termination Board (Model PTB). Model PTB is
required for operation with Model PSC-12. Model PTB
filters the power from the incoming AC mains, and
distributes it to the Model PSC-12 power supply and the
optional Model PSX-12 power-supply extender.
Model PTB has an optional connector that can be used
during system installation, commissioning and service to
provide the technician with a place to plug in their laptop
PC, if required. Model AC-ADPT is an optional accessory
cable that allows connection on one side to Model PTB, via
a keyed connector and on the other end directly into to the
laptop's transformer.
Most laptop-computer external power transformers have
removable AC power cords, which can be replaced by the
optional Model AC-ADPT to temporarily provide an AC
power source for laptop-PC usage during system
installation, service and maintenance calls when needed.
SNU-ASSY -* Single-Node Upload (SNU) Module
SNU-ASSY Single-Node Upload (SNU) Module
The Thermal Strip Printer (Model TSP-40A) is the Single-
Node Upload (SNU) is an optional system module that
provides a solution for uploading I downloading XLS I XLSV
configuration data remotely. SNU can easily transmit data
from a PC running the Zeus custom-configuration tool to a
maximum 64 Person Machine Interfaces.
Each SNU module has three (3) connections: Power,
Ethernet and USB. The data transported ; between the Zeus
tool and SNU is made through a direct 128-bit, Secure
Sockets Layer (SSL) connection.
FireFinder XLS Components —(cont.'d)
RNI Remote Network Interface
System-Status Display
SSD-Series System-Status Display
The System Status Display (SSD-series model displays) is a
remote LED / LCD display that shows the local status of a
FireFinder XLS system. An LED illuminates when Alarm,
Supervisory, Trouble, and Security events occur on the
system. A (4) four-line liquid-crystal display (LCD) will give
details of the event in alphanumeric form.
The display can be toggled to display additional events.
Optional remote system control capabilities are available.
Models SSD-C, SSD-C-INT, and Model SSD-C-REM have
three (3) additional control buttons to acknowledge
events, silence audible circuits, and reset the system.
'IC
4 *________ •!
lic -> Interface Isolation Card
IIC - Interface Isolation Card
The Interface Isolation Card (Model TIC) is designed to
isolate network signals when used with a Model NCC ring
configuration, via Model NRC. Model TIC executes the
aforementioned isolation by removing the backplane
network signals from each Model CC-2 card cage. Model
JIC also provides one (1) end of CAN termination on each
side of Model CC-2.
Models SSD-C and SSD-C-INT have an integral keyswitch
that enables these control buttons to operate. Model SSD-
C-REM is located within a locked cabinet. Therefore, no
additional keyswitch is required for manual activation of
the control buttons.
XDACT-ASSY--* XDACT Assembly
XDACT-ASSY XDACT Assembly
The XDACT Assembly (Model XDACT-ASSY) is the blank plate
used for holding the optional Digital Alarm Communication
Transmitter (DACT), Model F2015-Ui on FireFinder XLS.
Model XDACT-ASSY can be mounted on all CAB-series
enclosures. Each assembly must be located in the Global
Person Machine Interface cabinet for global configurations.
Available communication protocols on a DACT module
include: SIA DCS 8 I SIA DCS 20 I Ademco Contact ID.
SIEMENS Industry, Inc.
Building Technologies Division
MDACT - Multi-Point Digital Alarm
Communicator Transmitter
MDACT - Multi-Point Digital Alarm
Communicator Transmitter
The Multi-Point Digital Alarm Communicator Transmitter
(Model MDACT) is used in FireFinder XLS systems where
point identification of Alarm, Supervisory, Security and
Trouble events is required at Central or Remote Receiving
Stations. An intelligent RS-485 communications protocol
transmits all system information to Model MDACT.
The installer selects the specific event or groups of
events that are set to transmit from Model MDACT over
phone lines to listed receiving station equipment.
In turn, Model MDACT can transmit point information, via
the Ademco Contact ID and the SIA protocol. A mounting
plate (Model MOM2-XMP), MOM-2 card cage, and an XMl
Interface Card are required for installation.
CAB1 -4 Single Row Enclosure
CAB1 Single Row Enclosure
Model CAB 1, the smallest of the FireFinder XLS
enclosures, can house a single Model CAB-MP cabinet
mounting plate for mounting card cages, power supplies
and bulk amplifiers. Model CAB1 also has four (4)
mounting slots on the inner door for mounting The Person
Machine Interface and Model ID-MP switch module
brackets.
Model CAB1 comes complete with a black back box; black
inner and outer doors; a single lock and key set on the outer
door; a single, installed cabinet mounting plate (Model
CAB-MP), and a single, installed outer door lens plate
(Model OD-LP). A red version (Model CAB1-R) is also
available.
Approximate size: 27" (68.6cm.) high, 26" (66cm.)
wide, and 8" (20.3cm.) deep.
FireFinder XLS Components —(ccnt.'d)
ji
CAB2 -* Two-Row Enclosure
CAB2 Two-Row Enclosure
The Two-Row Enclosure (Model CAB2) is the mid-sized
FireFinder XLS enclosure capable of housing up to two
(2) Model CAB-MP cabinet mounting plates. The inner
door has two (2) rows of four (4) mounting slots.
The outer door has space for mounting two (2) outer door
plates (Models OD-LP, OD-BP or OD-GP), and can be
configured to open from either side. Model CAB2 consists
of the black Model CAB2-BB back box, the Model CAB2-BD
black inner and outer door package, and one (1) Mocel OD-
LP lens plate. The outer door has a single lock and key set
installed. A red version (Model CAB2R) is also available, and
a CAB2- RB back box is used with Model CAB2R.
Approximate size is 45" (114.3cm.) high, 26" (66cm.
wide, and 8" (20.3cm.) deep.
CAB3 -+ Three-Row Enclosure
CAB3 Three-Row Enclosure
Model CAB3, the single largest FireFinder XLS
enclosure available, can house a maximum three (3)
Model CAB-MP cabinet mounting plates in the enclosure,
and three (3) rows of inner-door mounting slots.
The outer door can be configured to open from either
side. Model CAB3 consists of the Model CAB3-3B back
box, the Model CAB3-BD black inner and outer door
package, and one (1) Model OD-LP lens plate. The outer
door has two (2) locks and key sets installed. A red
version (Model CAB3R) is also available.
Approximate size is 63" (1 60cm.) high, 26" (66.4cm.)
wide, and 8" (20.3cm.) deep.
CAB-MP -* cabinet Mounting Plate
SIEMENS Industry, Inc. —8— Building Technologies Division
CAB-MP Cabinet Mounting Plate
The Model CAB-MP cabinet mounting plate provides
mounting for a single row of modules in a FireFinder
XLS cabinet. Four (4) module spaces are available on
Model CAB-MP, which is used to mount the Model CC-5
card cage; the Modell, CC-2 card cage; the Model PSC-12
power supply; the Model PSX-12 power-supply extender,
and the Model ZAM-80 /180-zone amplifiers.
Enclosure Trim Kits
Trim kits are available for all system enclosures for semi-
flush mounting applications. Model CAB1-IK (for black
enclosures) and the Model CAB1 R-TK (for red enclosures)
fit inside the Models CAB1 and CAB1-R enclosures.
Similarly, Models CAB2-TK and CAB-2R-TK fit inside the
Model CAB-2 enclosure, while Models CAB3-TK and CAB3R-
1K fit the Model CAB-3 enclosure.
Remote Transponders
The FireFinder XLS system can use remote transponders
for mounting additional modules such as amplifiers
without requiring a Person Machine Interface or any
control switches. Special doors are available for systems
using Model CAB-2 or Model CAB-3 remote transponders.
These doors (Models CAB2-XBD and CAB3-XBD) omit the
unused inner door, and come complete with ventilation
louvers built into the door.
Model CAB2-XBD fits into Model CAB2-BB, and Model CAB3-
XBD fits into Model CAB3-BB. Model CAB2-XBD and CAB3-
XBD are supplied in black. Red versions (Models CAB2-XRD
and CAB3-XRD) are also available. Complete box and door
kits are available, Models CAB2-X and CAB3-X.
ID-MP -> Inner Door Mounting Plate
ID-MP Inner Door Mounting Plate
The inner door mounting plate (Model ID-MP) is mounted
on the inner door of any given model CAB enclosure.
Model ID-MP plates are used to mount switch-control
modules (Model SCM-8); LED control modules (Model
LCM-8), or fan-control modules (Model FCM-6).
Four (4) mounting plates are included with each order of
Model ID-MP. Each mounting plate has four (4) spaces for
control modules, and can hold either four (4) Model SCM-
8 modules (one [1] control module space for each
module); four (4) LCM-8 (one [1]control module space
for each module), or two (2) Model FCM-6 modules (two
[2] module spaces for each module).
FireFinder XLS Components —(cont.'d)
ID-MP Inner Door Mounting Plate
Combinations are also allowed. Blank spaces in Model ID-
MP can be covered using the blank-control-module
plate (Model BCM). Up to four (4) Model ID-MP
-modules can be mounted in a single row on the inner
door. OD-BP -* Outer Door Blank Plate
OD-BP Outer Door Blank Plate
The Outer Door Blank Plate (Model OD-BP) entirely
covers an unused row of a XLS system cabinet, and is
mounted on the outer door. One (1) blank plate is
included with each order of Model OD-BP.
ID-SP -4 Inner Door Blank Single Plate
ID-SP Inner Door, Blank Single Plate
The inner door, blank single plate (Model ID-SP) is used
to cover any single-module blank spaces within the inner
door where no Person Machine Interface or Model ID-MP
is being used. Up to four (4) Model ID-SP modules can be
mounted in a single row on the inner door. Two (2)
blank plates are included with each order of Model ID-SP.
BCM -* Blank Control Module Plate
BCM Blank Control-Module Plate
Model BCM plates can be mounted on a single ID-MP.
Four (4) blank module plates are included with each
order of Model BCM.
OD-LP -* Outer Door Lens Plate
OD-LP Outer Door Lens Plate
The Outer Door Lens Plate (Model OD-LP) is a clear plastic
lens plate mounted on the outer door of a system
cabinet. Model OD-LP is used to allow operators to see
the system interface and controls mounted on the inner
door, but restricts access to unauthorized users. The plate
covers an entire row on the outer door. A single lens
plate is included with each order of Model OD-LP.
SIEMENS Industry, Inc.
Building Technologies Division
OD-GP --> Outer Door Grill Plate
OD-GP Outer Door Grill Plate
The Outer Door Grill Plate (Model OD-GP) also covers an
entire row on the outer door of a system cabinet, but has
four (4) rows of ventilation louvers on it. Model OD-GP is
mounted in front of system bulk amplifiers, card
amplifiers, or other modules that generate heat. Using
Model OD-GP will permit airflow across these modules to
aid in heat dissipation. One (1) grill plate is included
with each order of Model OG-GP.
Remote System Enclosures
Models REMBOX2 and REMBOX4 are FireFinder XLS
system enclosures that are used for remotely mounting
inner-door modules, such as: Person Machine Interfaces;
switch modules (Model SCM series); Live Voice Modules
(Model LVM), and Firefighters' Master Telephone (Model
FMT) modules.
Models REMBOX2 and REMBOX4 are thinner than regular
Model CAB-series of enclosures - just 5" (12.7cm.) deep
overall, and are perfect for mounting in limited-space areas
(e.g. - office-complex lobbies or behind a receptionist's
desk).
No card cages, power supplies or bulk amplifiers can be
mounted in a given Model REMBOX-series enclosure due
to their smaller depth. However, Person Machine
Interfaces and some modules (e.g. - the remote network
interface module [Model RN!]; the output control module
[Model OCM-16], and the supervised input module
[Model SIM-16]) can be mounted in a given Model
REMBOX-series enclosure.
Due to the depth of Models LVM and FMT, no Model 0CM-
16 or Model SIM-16 modules can be used simultaneously
with Model LVM or Model FMT. Model REMBOX2 and
Model REMBOX4 are designed for flush mounting with no
trim kit required. Both enclosures also come with a clear
lens plate on the cover.
FireFinder XLS Components - (cont.'d)
REMBOX2 - Two-Module Remote Enclosures
REMBOX2 Two Module Remote Enclosures
Model REMBOX2 has two (2) inner-door module spaces,
and can hold a single Person Machine Interface, up to two
(2) switch module brackets and one (1) Model LVM.
Combinations are also allowed.
Model REMBOX2 can also mount a single RNI remote
network interface on a bracket included in the backbox.
A bracket, known as Model REMBOX2-MP, can be used to
mount up to four (4) Model OCM-16 output control
modules or SIM-1 6 supervised input modules.
Model REMBOX2-MP must be purchased separately.
Approximate size of Model REMBOX2 is 14-1/2" (3 6.8cm.)
wide, 181/2" (47cm.) high and 5" (12.7cm.) deep.
REMBOX4 -> Four-Module Remote Enclosures
REMBOX4 Four-Module Remote Enclosures
Model REMBOX4 has space for mounting four (4) inner-door
modules. Any combination of A Person Machine Interface
(two-module spaces); switch module brackets; Model
LVM, or Model FMT (one-module space each) can be
used. Unused module spaces can be covered with Model
ID-SP blank plates. Model REMBOX4 can also mount a
single, remote network interface (Model RNI) on a
bracket included in the backbox.
A bracket known as Model REMBOX4-MP can be used to
mount up to eight (8) output control modules (Model
0CM-1 6) or supervised input modules (SIM-1 6).
Approximate size of Model REMBOX4 is 24" (61 cm.)
wide, 18-112"(47cm.) high and 5" (12.7cm.) deep.
Model REMBOX4-MP must be purchased separately.
XLS-MSE2-ADPT —*Enclosure Adapter
XLS-MSE2/R-ADPT - XLS MSE-2/11 Enclosure Adapter
Model XLS-MSE2-ADPT, which must be used in conjunction
with Model CAB-MP, is an adapter that allows FireFinder
XLS cards to be mounted in older-generation MXL Model
MSE-2 small black enclosures.
Model XLS-MSE2R-ADPT, which must be used in
conjunction with Model CAB-MP, is an adapter that allows
FireFinder XLS cards to be mounted in older-generation
MXL Model MSE-211 small red enclosures.
XLS-MME3-ADPT —*Enclosure Adapters
XLS-MME3/R-ADPT - XLS MME-3/11 or MBR-2
Enclosure Adapters
Model XLS-MME3-ADPT, which must be used in
conjunction with Model CAB-MP, is an adapter that allows
FireFinder XLS cards to be mounted in older- generation
MXL Model MME-3 or Model MBR-2 medium black
enclosures.
Model XLSMME3R-ADPT, which must be used in
conjunction with Model CAB-MP, is an adapter that allows
FireFinder, XLS cards to be mounted in older-generation
MXL Model MME-311 medium red enclosures.
XLS-MLE6-ADPT —'Enclosure Adapter
XLS-MLE6/R-ADPT - XLS MLE-6/11 Enclosure Adapter
Model XLS-MLE6-ADPT, which must be used in
conjunction with Model CAB-MP, is an adapter that
allows FireFinder XLS cards to be mounted in older-
generation MXL Model MLE-6 large black enclosures.
Model XLS-MLE6R-ADPT, which must be used in
conjunction with Model CAB-MP, is an adapter that
allows FireFinder XLS cards to be mounted in older-
generation MXL MLE-6R large red enclosures.
SIEMENS Ind ustry,.Inc. _10— Building Technologies Division
FireFinder XLS Components —(cont.'d)
XLS-MSE3-ADPT 'Enclosure Adapters
XLS-MSE3IR-ADPT - XLS MSE-3LIR or MSE-3MIR
Enclosure Adapters
Model XLS-MSE3-ADPT is an adapter that allows
FireFinder XLS cards to be mounted in older-
generation MXL-IQ Model MSE-3L or Model MSE-3M
black enclosure.
Model XLS-MSE3R-ADPT is an adapter that allows
FireFinder XLS cards to be mounted in older-
generation MXL-IQ Model MSE-3LR or Model MSE-
3MR red enclosure.
EL.i
XLS-Rcc,-ADPT --'Enclosure Adapter
XLS-RCC-1-ADPT - XLS RCC-1 Enclosure Adapter
Model XLS-RCC1 -ADPT is an adapter that allows the
FireFinder XLS Model SSDI-C series remote annunciator
to be mounted in older-generation Model RCC-1 surface-
mount enclosure.
XLS-Rcc13F4ADPT -*Enclosure Adapters
XLS-RCC1 3F/R-ADPT - XLS RCC-1 F/R or RCC-3 FIR
Enclosure Adapters
Model XLS-RCC1 3F-ADPT is an adapter that allows the
FireFinder XLS Model SSDI-C series remote annunciator
to be mounted in older-generation Model RCC-1 F or
Model RCC-3F black, flush-mount enclosure.
Model XLS-RCC1 3FR-ADPT is an adapter that allows the
Model SSD/-C series to be mounted in older-generation
RCC-1 FR and RCC-3FR, red flush-mount enclosure.
Ii
VPM -* VESDA VESDA-HLI-KIT -* VESDA High-
Interface Equipment Level Interface Kit
SIEMENS Industry, Inc.
Building Technologies Division
F--i
VPM-MP -* VESDA Mounting Plate
VPM, VESDA-HLI-KIT and VMP-MP -
VESDA Interface Equipment
The Very Early Smoke Detection Aspiration (VESDA)
Peripheral Module (Model VPM) and the VESDA High-
Level Interface Kit (Model VESDAHLI-KIT) are optional
FireFinder XLS modules that work in conjunction to
provide bi-directional communication between the
FireFinder XLS FACP and multiple VESDA detection
networks for the following types of VESDA detectors:
LaserCOMPACT
LaserFOCUS
LaserPLUS
LaserSCANNER
Model VPM allows each FireFinder XLS FACP to
annunciate 'Alert,' 'Action,' 'Fire 1,' and 'Fire 2' levels,
as well as provide 'faults' from any zone on a
connected VESDA network.
The VPM Mounting plate (Model VPM-MP) allows
mounting one (1) Model VPM and two (2) of Model
VESDAHU-KIT inside a standard FireFinder XLS Model
CA131, Model CA132 or Model CAB3 enclosure. Model
VPM-MP utilizes two (2) module spaces on a single
row of each enclosure.
C900V2 -*Dialer-Capture Ethernet Module
C900V2 - Dialer-Capture Ethernet Module
The Dialer-Capture Ethernet Module (Model C900V2)
links the data output of Model MDACT from the
FireFinder XLS FACP to an Ethernet connection - on a
local-area network (LAN) or wide-area network (WAN) -
for communication to a central station over the Internet.
Model C900V2 also allows Model MDACT to be
optionally linked to the public switched telephone
network (PSTN) for communication to a central station
over telephone lines.
Temperature and Humidity Range
FireFinder XLS components are ®UL 864 91h Edition
Listed for indoor dry locations within a temperature
range of 1 20+/-3'F (49+1-2°C) to 32+/-3°F (0+/-2°C)
and a relative-humidity range of 93+/-2%
at a temperature of 90+/-3°F (32+/-2'C).
Details for Ordering Details for Ordering - (continued)
Model Part Number Description
AC-ADPT 500-633992 Technician Laptop-Power connector
BCM 500-033320 Blank control module plate,
four (4) per package]
C900V2 S54430-Cl 3-A2 Dialer-Capture Ethernet Module
CAB-1 500-633007 Complete Single-Row Cabinet, black
CAB-1 R 500-633728 Complete Single-Row Cabinet, red
CABi -TK 500-633013 Single-Row Trim-kit Cabinet, black
CAB R-TK 500-633729 Single-Row Trim-kit Cabinet, red
CAB2-BB 500-633009 (2) Two-Row Back Box, black
CAB2-RB 500-634941 (2) Two-Row Back Box, red
CAB2-BD 500-633008 (2) Two-Row Inner & Outer Door set, black
CAB2-RD 500-633755 (2) Two-Row Inner & Outer Door set, red
CAB2-TK 500-633014 (2)Two-Row Trim-kit Cabinet, black
CAB2R-TK 500-633753 (2) Two-Row Trim-kit Cabinet, red
CAB2-XBD 500-633768 CAB2 Transponder Door
CAB2-X 599-034252 Complete CAB2 wl Transponder Door
no inner door]
CAB2-XRD 500-633792 Medium-Enclosure Transponder Door, red
mounts to Model CAB2-RB1
CAB3-BB 500-633011 (3) Three-Row Back Box, black
CAB3-RB 500-634942 (3) Three-Row Back Box, red
CAB3-BD 500-633010 3) Three-Row Inner & Outer Door Set, black
CAB3-RD 500-633757 (3) Three-row Inner & Outer Door set, red
CAB3-TK 500-633015 (3) Three-Row Trim-kit Cabinet, black
CAB3R-TK 500-633754 (3) Three-Row Trim-kit Cabinet, red
CAB3-XBD 500-633769 CAB3 Transponder Door
CAB3-X 599-034253 Complete CAB3 wl Transponder Door
no inner door]
CAB3-XRD 500-633793 Large-Enclosure Transponder Door, red
mounts to Model CAB3-RBI
CAB-MP 500-633012 Back Box Module Mounting Plate
CCL 599-634214
CAN Cable
3ft. (91.4 cm.) Length required for:
SCM I LCM I FCM modules from Models CC-5 I CC-2
Inner Doors and from Row-to-Row on
Model CAR-series Inner Doors
CC-2 500-633440 Two (2) Slot Card Cage
CC-5 500-633037 Five (5) slot Card Cage
CDC-4 500-034200 Conventional Detector Card
COM-BRK S54430-B7-Ai Communications Bracket
CRC-6 500-033250 Controllable Relay Card
CSB 500-033130 CAN Sounder Board
DCT-P 500-699291 MDACT Programmer
DLC 500-033090 Device Loop Card
FCM-6 500-033140 Fan-Control-Module Switches
(ON OFF, AUTO]
GPMI-UK 500-650066 Software-Upgrade Kit for PMI (vers. 1)
[to allow global functionalityl
GPMI-2 554430-C3-Ai Model PMI -2 [with GPMt-HW-KEY]
HCP 500-034860 Intelligent Control Point Module
HUM 500-033170 Line-Isolator Module
ID-MP 500-633027 Inner-Door Enclosure Mounting Plate,
[four (4) per package]
ID-SP 500-633028 Single-Module Inner-Door Enclosure
Mounting Plate, [two (2) per package]
TIC 500-850328 Interface Isolation Card
LCM-8 500-033100 LED Annunciator Module
[eight (8) LED sets]
MDACT 500-699254 Multi-Point Digital-Alarm
Communication Transmitter
MLC S54431 -B4-A1 MXL Addressable-Device Line Card
MOM2-XMP 500-634822 Mounting Plate for Model MOM-2
MOM-2 500-892766 MXL Module Card Cage
lone (1) full slot]
Model Part Number Description
NIC-C 500-033240 Network Interface Card
NRC S54430-A2-Ai Network Ring Card: 2nd Generation
OD-BP 500-633017 Outer Door Blank Plate
OD-BP-R 500-634919 Outer Door Blank Plate, red
OD-GP-R 500-634920 Outer Door Grill Plate, red
OD-GP 500-633018 Outer Door Grill Plate
OD-LP 500-633016 Outer Door Lens Plate
PAL-1 500-692407 &UL Listed Parallel Printer
PMI-3 S54430-C1 5-Al Person Machine Interface 3
PMIT-3
(Overlays) S54430-C16-A1 Alternate-language Overlays for navigation
on a FireFinder XLS operation interface
PSC-1 2 500-033340 Power supply with battery charger
PSX- 12 500-034120 Power supply extender
[12A@24VDC]
PTB 500-033390 Power termination board
REMBOX2 500-633772 (2) Two-module remote lobby enclosure, black
REMBOX2R 500-650612 (2) Two-module remote
lobby enclosure, red
REMBOX2-MP 500-634211 Mounting plate for Models
0CM-1 6/ SIM-i 6 in Model REMBOX2
REMBOX4 500-633914 (4) Four-module remote lobby enclosure, black
REMBOX4-MP 500-634212 Mounting plate for Models 0CM-1 6/
SIM-16 in Model REMBOX4
REMBOX411 500-650613 (4) Four-module remote lobby enclosure, red
RNI 500-033420 Remote network interface module
RPM 500-033270 Remote printer module
SCM-8 500-033040 Switch module, eight (8) switches
SIM-16 500-034060 Supervised input module
SNU-ASSY S54430-A3-A1 SNU Processor and USB cables (wl SNUIOM)
SSD 500-034740 ystem-status display
SSD-C 500-648733 System-status display with control
SSD-INT 500-034740 System-status display
with multi-lingual overlays
SSD-C-INT 500-034750 System-status display with control
and multi-lingual overlays
SSD-C-REM 500-634773 System-status display with control for
'emote lobby enclosure
TSP-XB 500-849949 Brackets for thermal-strip printer
TSP-XC 500-849950 Cables for thermal-strip printer
VNTPC 500-650490 Virtual Network Tunnel
VPM S54430-F93-A2 VESDA Peripheral Module
VPM-MP S54430-F95-A2 Mounting Plate for VESDA
Peripheral Module
VESDA-HU-KIT S54430-F99-A2 VESDA High-Level Interface Kit
XDACT-ASSY S54430-A5-Ai XDACT mounting plate (wl cable)
XLS-MLE6-ADPT S54430-C9-A1 MLE-6 enclosure adapter for XLS, black
XLS-MLE6R-ADPT S54430-C9-A2 MLE-611 enclosure adapter for XLS, red
XLS-MME3-ADPT S54430-C8-Ai
MME-3 and MBR-2 enclosure adapters
for FireFinder XLS, black
XLS-MME3R-ADPT S54430-C8-A2 MME-311 enclosure adapter for XLS, red
XLS-MSE2-ADPT S54430-C7-Ai MSE-2 enclosure adapter for XLS, black
XLS-MsE2R-AoPT S54430-C7-A2 MSE-211 enclosure adapter for XLS, red
XLS-MsE3-ADPT S54430-C14-A1
MXL-IQ MSE-3L and MSE-3M enclosure adapters
for FireFinder XLS, black
XLS-MSE3R-ADPT S54430C14A2 MXL-IQ MSE-3LR & MSE-3MR enclosure
adapters for XLS, red
XLS-RCC1 -ADPT S54430-Z14-A1 RCC-i enclosure adapter for XLS-SSD, black
XLS-RCC1 3F-AOPT S54430-Z1 3-Ai RCC-i F & RCC-3F enclosure adapters, black
XLS-Rcc13FR-ADP S54430-Zi 3-A2 RCC-i FR & RCC-3FR enclosure adapters, red
ZIC-2C 500-648671 (2) Two-channel adapter card,
via (Model ZIC-8B)
ZIC-4A 500-033050 (4) Four-circuit zone indicating card
ZIC-8B 500-648670 (8) Eight-circuit zone indicating card
Notice: This marketing data sheet is not intended to be used for system design or installation purposes.
For the most up-to-date information, refer to each product's installation instructions.
Fire Safety Fire Safety
8 Fernwood Road 1577 North Service Road
SIEMENS Industry, Inc. Florham Park, NJ 07932 East Oakville, Ontario April 2017
Building Technologies Division Tel: (973) 593-2600 (sn-FS) L6H 0H6 / Canada supersedes sheet dated 4/2015
FAX: (908) 547-6877 Printed in U.S.A. Tel: [9051465-8000 (Rev. 161
URL: www.usa.Sjemens.com/Fjre URL: www.Siemens.CA
Watertight housing
(Model FDBZ-WT)
SIEMENS Data Sheet
Fire Safety Products
Specialized Devices
Air-Duct Housings —> FDBZ Series
Models FDBZ492, FDBZ492-HR, FDBZ492-R and FDBZ492-RP (with FDBZ-WT and FDBZ492-RTL)
ARCHITECT AND ENGINEER SP ECIFICATIONS
Four (4) models available -
Addressable and conventional (with and without relays) r
Compatible with Siemens - Fire Safety conventional
and addressable fire-alarm control panels (FACPs) tmim
L FDBZ-series of air-duct housings
Magnet test feature with the Model 0P121 (FDBZ492, FDBZ492-HR, FDBZ492-R and FDBZ492-RP)
conventional detector Remote alarm
Design for air-velocity range of 100 to 4,000 indicator
feet-per-minute (fpm) (Model FDBZ492-RTL)
Robust, compatible conventional remote indicator test
switch that incorporates tn-color light-emitting diode (LED)
Clear housing cover with smoke test port on cover
for quick identification of detector type
Removable with four (4) captive-thumb screws (no tools required)
Includes a smoke/ aerosol detector test port
Optional NEMA4X-reinforced, stainless-steel and
watertight enclosure available, Model FDBZ-WT
No tools required for cover removal,
sampling and exhaust-tube installations
Trouble-event activation upon front-cover removal
Alarm LED visible from front
Product Overview
The Siemens - Fire Safety Model 'FDBZ'-series of air-
duct-detector housings are designed to be used with
the Siemens Model 'H'-series, 'FD'-series and the Model
OP1 21 detectors. Designed for installation directly to
heating, ventilating and air-conditioning (HVAC) duct
systems, the Model 'FDBZ-series complies with National
Fire Protection Association Standard (NFPA) No.'s 72
and 90A, and is Underwriters' Laboratories Listed.
When equipped, the air-duct detector housing will
signal the presence of smoke being carried through the
duct system. Air-duct detectors are not intended to be
substituted for open-area detection.
Notes: Most conventional time-control equipment
guarantee only one (1) detector per zone when
the detector's operated relay function is critical.
The connection of a remote lamp and a remote
relay —per detector— is allowed.
Refer to the installation manual for the
respective conventional fire system.
Self-contained model available with 'on-board'
power supply for conventional detectors
Expanded temperature range
Relay models available
®UL268A Listed, ULC-S529 Listed;
FM C3010), CSFM (#3240-0067:0265) Approved
Notes - (cont.'d): With either the Desigo® series or
FireFinder® XLS series of FACP5, up to 252-addressable
detectors with relays per circuit may be used. The connection
of an intelligent remote lamp (ILED) and a remote relay is
allowed for each detector simultaneously.
Specifications
The Model 'FDBZ-series of air-duct housings are uniquely
designed to use with the photoelectric detector. Sensitivity
of Models PE-1 1, PE-1 1 C and 0P121 detectors can be
verified for calibration via LED visual status or a Model
RSAW-1 1, Model RSAC-1 1 or Model FDBZ492-RTL multi-
color remote lamp. A green flash indicates the detector
has passed its self test. Amber indicates a Trouble
condition, and red indicates an Alarm event.
Sensitivity range for Models HFP-1 1, FP-1 1, SFP-1 1, HFPO-
11, SFP0-11, FD0421, FDOOT441 and FDOOTC441is
verified from the multi-color LED of the respective detector,
or its sensitivity reading may be printed by command from
the corresponding FACP to an optional printer.
Model 'FDBZ'—Series of Air-Duct Housings and Detectors 6156
SIEMENS Industry, Inc.
Building Technologies Division
Specifications - (continued)
The remote alarm indicator (Model FDBZ492-RTL) allows
for manual testing via a key-switch for conventional anc
addressable detectors, as well as the conventional and
addressable air-duct housing with relay. Model
FDBZ492-RTL, which mounts remotely from the
conventional and addressable air-duct housing, allows
for manual relay-output control. The duct-detector
remote indicator key-switch also indicates the current
state of the detector.
The watertight housing (Model FDBZ-WT), which allows
the air-duct detector housing to be installed inside the
separate NEMA 4X enclosure, is for installations for
either an outdoor area or in environments where
excessive moisture is prevalent.
Each detector unit employs a cross-sectional sampling
principle of operation. Inlet sampling tubes are
available in four (4) lengths (see: Sampling Tube
Selection Table). Outlet sampling tubes are one (1)
common length and draw. A continuous, cross-
sectional sample of air moves through the duct.
Stratification or skin affect phenomenon that occurs in
the duct can prevent smoke (especially in large ducts)
from reaching a spot-type detector.
In addition, the unique design of the sampling chamber
insures uniform sensitivity in air velocities, ranging
from a low of 100 fpm to as high as 4,000 fpm. Each
housing comes with three (3) wiring entry ports:
Two (2) 3/4" conduit knockouts
One (1) 1/2" conduit opening
The inlet sampling tube length is determined by the
width of the air duct being protected. The inlet tube -
greater than and nearest to the duct width - should be
used (see: Sampling Tube Selection Table). The inlet
tube can then be trimmed at the job site to theexact
width of the duct. The outlet sampling tube for all ducts
- irrespective of width - has a fixed length of
approximately 5.5 inches (14cm.), and is supplied with
the air-duct housing.
Note: When the use of a remote relay is required, order
Model FDBZ492-R for conventional systems; Model
FDBZ492-HR for addressable systems. When required, a
separate watertight enclosure (Model FDBZ-WT), which
is designed to contain the air-duct housings is
available.
(For full details, refer to installation instructions for the
respective air-duct housing.)
Note: When a self-contained duct detector with power supply
is required, order Model FDBZ492-RP.
(For full details, refer to installation instructions part
number A6V1 0330327.)
SIEMENS Industry, Inc.
Building Technologies Division
Sampling Tube Selection Table
Sampling Tube Duct Width (Model No.)
For duct widths 6"to1' ST-1
For duct widths 1'to 3' ST-25
For duct widths 3' to 5'
(requires support)
ST-50
For duct widths 5'to 10'
(requires support)
ST-i 00
Maintenance of the detector is easily accomplished
via the removal of the duct-housing sampling
chamber cover. The detector, which plugs into the
housing, is easily removed for cleaning or replacing by
a trained technician.
All that is necessary for installation of the air-duct
detector is the cutting of three (3) small holes for the
Sampling Tube installation (template included), and
the drilling of two (2) holes for mounting the air-duct
housing. The unit is then easily mounted in place,
and connection made to the existing wires or
terminals - if optional accessories are utilized. No
mechanical tools are required for removing the cover or
connecting the sampling and exhaust tubes to an air-
duct housing.
Models ST-SO and ST-1 00 require support. However,
Model ST-100 is shipped in two (2) 5-ft. (152 cm.)
pieces with a coupling for field assembly.
Technical Data
Operating
Temperature +32°F (0°C) to 120°F (49°C)
Ranges:
Sampling Tube Pressure >0.01 inches;
Range of Differences: < 1.2 inches
of water column
Relative Humidity: 0-95%; non-condensing
Air Pressure I No effect /
Altitude Range: No limitations
Air-Duct Velocity: 100— 4,000 ft. / mm
(0.51— 20m / sec)
Dimensions: { H -x- W -x- D }
Rectangular: 14.38"-x-5"-x-2.5"
(37 cm. -x- 12.7 cm. -x- 6.36 cm.)
Square: 7.75"-x-9"-x-2.5"
(119.7 cm. -x- 22.9 cm. -x- 6.36 cm.)
Detector Weight: 1.8 Lbs. (0.82 Kg.)
Notes to Architect: When building codes regulate he location of
detectors within ventilating systems, make
sure the number and locations of detectors
are in accordance with the code
regulations.
For additional electrical specifications,
please see the installation instructions of
the corresponding air-duct housing.
Operation
Based on the monitoring results, the LED indicator
flashes the following colors based on the following
conditions:
lash Flash
Color Condition Interval
(in seconds)
Normal supervisory operation.
Green*: Smoke sensitivity is within 10
rated limits.
Detector is in Trouble
Yellow: condition, and needs either 4
repair or replacement.
Red: Alarm condition. 1
No Flash: Detector is not powered. --
* LED can be turned OFF.
Please follow the corresponding description of the panel used.
Products included with the air-duct housing:
short-return (outlet) tube
- (I) stopper
#12 + 314" sheet-metal screws
- (1) mounting template
Note: Detector and sampling tube to be purchased separately.
Minimum hardware required is: one (1) air-duct housing
assembly; one (1) sampling tube and one (1) detector.
Details for Ordering
Model Part
Number Description
A two-wire addressable or conventional
duct detector (without relays) designed for
direct use on heating, ventilating and air-
conditioning (HVAC) air-duct systems.
When equipped, the air-duct detector
S54319-housing will signal the presence of smoke
FDBZ492 being carried through the duct system. B22-A1 For use with the following Models:
- HFP-11 - FD0421
- 0P121
- SFP-1 1 - FDOOT441
- PE-1 1
- HFP0-11 - FDOOTC441 PE-11C
- SFP0-1 1 - FP-1 1
A two-wire addressable duct detector (with
relays) designed for direct use to HVAC air-
duct systems and works with the Remote
FDBZ492- Test Switch (FDBZ492-RTL). This part has a
HR programmable relay base, and when
S54319- equipped, the addressable air-duct detector
B23-A1 housing will signal the presence of smoke
being carried through the duct system.
For use with the following Models:
- F00421 - FP-1 1
- sFP-1 1 F000T441 - HFP-li
- SF P0-1
- FDOOTC441
SIEMENS Industry, Inc.
Building Technologies Division
Details for Ordering - (continued)
Model Part Description Number
A two-wire conventional duct detector with
relays designed for direct use on HVAC air-
duct systems. This detector has a relay
FDBZ492 base, and when equipped with conventional
R S54319- air-duct housing, will signal the presence of
B24-Al smoke being carried through the duct
system.
For use with the following Models:
- OPi2i
- RE-li -ps-nc
A four-wire conventional duct detector with
relays and a built-in power supply. Housing
is designed for direct use to HVAC air-duct
FDBZ492- systems. It has a relay base with a built-in
RP CAD1 i :2
power source. When equipped with
conventional air-duct housing, this duct
B25-Al detector will signal the presence of smoke
being carried through the duct system.
For use with the following Models:
- 0P121
- RE-li - PE-11C
Device is used for manual testing via a key-
switch for duct-housing Models FDBZ492-
R, FDBZ492-RP and FDBZ492-HR. Device
FDBZ492- mounts remotely from the conventional
RTL '
and addressable air-duct housing, allowing
for manual relay-output control. The duct-
S27-Al detector remote key-switch also indicates
the current state of the detector.
For use with the following Models:
- FDBZ492-R
- FDBZ492-RP - FDBZ492-HR
An optional, separate watertight NEMA 4X
enclosure (Model FDBZ-WT) that provides
added watertight protection for any of the
Model FDBZ492-series duct housings. The
duct housing fits into the separate 4X
enclosure. This part allows the air-duct
FDBZ-WT S54319- detector housing to be installed in the
B26-A1 separate enclosure, and can be used in
either an outdoor area or in environments
where excessive moisture is prevalent.
For use with the following Models:
- FDBZ492 - FDBZ492-R
- FDBZ492-HR - FDBZ492-RP
ST- i 0 500-649710 Sampling tube for Ducts 6" to 1'
ST-25 500-649711 Sampling tube for Ducts over 1' to 3'
ST-50 500-649712 Sampling tube for Ducts 3" to 5'
ST-100 500-649713 Sampling tube for Ducts 5'to 10'
Notice: This marketing data sheet is nc:t intended to be used fo- system design or installaton purposes.
For the most up-to-date informEtion, refer to each product's installation instructions.
Fire Safety Fire Safety
8 Fernwood Road 1577 North Service Road
SIEMENS Industry, Inc. Florham Park, NJ [7932 East Oakville, Ortario September 2014
Building Technologies Division Tel: (973) 593-2600 (311-FS) L6H 3H6 /Canada Supersedes sheet dated 8/13
FAX: (908) 547-E77 Printed .n USA. Tel: 19051465-8000 (Rev. 4)
URL: www.usa .S eiens.conlFi-e URL: www.Siemans.cA
O Compatible with Siemens Model The Photoelectric Smoke Detector (Model FD0421) uses state-of-the-art
H'-series devices on the same loop microcontroller circuitry and surface-mount technology for maximum reliability.
(with Desigo Fire Safety Modular I Model FD0421 incorporates an optical sensor using a light-scattering detection
FireFinder XLSIV I FCIFV20-series principle. The device utilizes advanced software algorithms to analyze the signals, fire-alarm control panels and provides highly stable and accurate smoke detection.
O Compatible with Model DPU Model FD0421 also uses state-of-the-art microprocessor circuitry with error check; (device programmer/ loop tester)
detector self-diagnostics, and supervision programs.
O Each detector is self-testing:
- self-monitored for sensitivity Field-Device Programmer! Test Unit
with UL Listed limits
Model FD0421 is compatible with the Siemens field-device programmer I test
- complete diagnostics
performed every 10 seconds unit (Model DPU), which is a compact, portable and menu-driven accessory for
electronically programming and testing these addressable detectors promptly and
O Polarity insensitive via reliably. For instance, the field technician selects the accessory's program mode, Sure Wire"' technology and enters the desired address.
Functions with Model DB- Model DPU eliminates the need for cumbersome, unreliable mechanical 11-series mounting bases programming methods (e.g. - dials and rotary switches), and reduces installation
0 Tr-color detector-status light-emitting and service costs by electronically programming and testing the detector prior to
diode (LED) with 360'view installation. When set in 'test' mode, Model DPU will perform a series of
O Field-selectable application- diagnostic tests without altering the address or other stored data, allowing
sensitivity profiles technicians to determine if the detector is operating properly.
Remote sensitivity-
measurement capability
Utilizes advanced, microprocessor-based
signal processing
Extended temperature-and-
humidity operating range
Automatic environment compensation
Superior electromagnetic interference
(EM!) and radio-frequency interference
(RFI) immunity
Restriction of Hazardous
Substances (RoHS compliant)
UL 268A Listed [for direct air-duct use],
ULC Listed; FM (#3230, #3210), CSFM
(#7272-0067:0258) Approved
@@<~>X
Siemens
Building Technologies Division
Each field-device programmer I test unit
operates on AC power or rechargeable
'batteries, providing flexibility and
convenience in the programming I testing of
fire-safety equipment from practically any
location. Additionally, with the use of a
Model DPU unit, there is no longer a cause
for concern with any vibration, corrosion and
other deteriorating conditions that can
accompany the vitality of a mechanical-
addressing mechanism. Photoelectric Smoke Detector
Data Sheet 6152
usa.siemens.comldesigo-fire-safety
Labyrinth
Optical
transmitter
Optical
receiver
I ti11hWEJ)
Each detector fits into one (1) wall-or-ceiling footprint, and only occupies one (1) address on the signal-line circuit (SLC).
Model FD0421 is a plug-in, two-wire and addressable photoelectric smoke detector.
Model FD0421 is Underwriters' Laboratories Listed [UL268A Listed for direct in-air duct usage].
Each detector consists of a dust-resistant photoelectric chamber and microprocessor-based electronics
with a low-profile plastic housing. Every Model FD0421 fire detector is shipped with a protective dust cover:
Model FD0421 is a wide-spectrum, photoelectric smoke detector that
incorporates an infrared light-emitting diode (IRLED), as well as a light-
sensing photodiode. Under normal conditions, light transmitted by the
LED is directed away from the photodiode and scattered through the
smoke chamber in a controlled pattern.
The smoke chamber is designed to manage light dissipation and
extraneous reflections from dust particles or other non-smoke, airborne
contaminants in such a way as to maintain stable, consistent detector
operation. When smoke enters the detector chamber, light emitted from
the IRLED is scattered by the smoke particles, and is received by the
photodiode (see: the computer-graphic images at the top of this page).
Dust cover
Photoelectric
smoke detector
Application Parameter Sets
Model FD0421 provides four (4) pre-programmed sensitivity parameter sets that can be selected by the
Siemens fire-alarm control panel in order to match the expected application or environmental conditions:
Sensitive
Standard
Robust
Air-duct
Sensitive: This application parameter set is practically suitable for areas where few misleading sources
of false alarm are present, and is appropriate where priority is given to detecting open fires as
soon as possible (e.g. —typically a clean application with controlled environmental conditions).
Standard: This application parameter set, which is ideal for normal office I hotel-lobby-type
applications, is the default setting.
Robust: This application parameter set offers improved resistance to false alarms in areas where
misleading sources, such as cigarette smoke or exhaust fumes, may cause a nuisance alarm.
Air-Duct: This application parameter set is used when the detector is used a UL268A (DI) compliant,
direct in-air duct application without a duct housing.
Model FD0421 does not require a field sensitivity test. Model FD0421 is UL Listed as a self-testing device
and complies with NEPA 72 as a self-monitoring detector and control-panel arrangement. This parameter
set is also used when Model FD0421 is used in air-duct housings (Models FDBZ492 and FDBZ492-HR).
Siemens
Building Technologies Division —2— usa.siemens.com/desigo-fire-safety
Application Parameter Sets - (continued)
Air-Duct: A quick visual inspection is sufficient to indicate the condition of Model FD0421 at any time.
If more detailed information is required, a printed report can be provided from the compatible FACP,
indicating the status and settings assigned to each individual detector. When Model FD0421 moves to
Alarm'imode, the detector will flash RED and continue flashing until the system is reset at the FACP.
At that same time, any user-defined, system-alarm functions programmed into the system are activated.
Model FD0421 contains a tn-color LED indicator, capable of flashing any one (1) of three (3) distinct colors:
GREEN I YELLOW I RED. During each flash interval, the microprocessor-based detector
monitors the following scenarios:
Smoke sensitivity is within the range indicated on-the nameplate label
Smoke in its sensing chamber
Internal sensors and electronics are functional
Based on the results of the monitoring, the LED indicator flashes the following:
FLASH COLOR CONDITION FLASH INTERVAL
[in seconds]
GREEN*. Normal supervisory operation.
Smoke sensitivity is within rated limits. 10
YELLOW: Detector is in trouble and needs replacement. 4
'Alarm' condition 1
NO FLASH: Detector is not powered. -
* denotes LED can be turned OFF
Please follow the corresponding description of the panel used.
A quick visual inspection is sufficient to indicate the condition of the detector at any time.
If more detailed information is required, a printed report can be provided from the respective Fire Safety Modular
FireFinder XLS/V I FC/FV20—series FACP that indicates the status and settings assigned to each individual detector.
All Model FD0421 intelligent, addressable detectors use a surface-mounting base (Model D13-1 1 or
D13-1 1 E), which mounts on a 4-inch (10.2 cm.) octagonal, square or single-gang electrical back box. The base
utilizes screw-clamp contacts for electrical connections and self-wiping contacts for increased reliability.
The Model DB-1 1 detector base can be used with the optional Siemens Model LK-1 1 detector locking kit,
which contains 50 detector locks and an installation tool to prevent unauthorized removal of the
detector head. Model DB-1 1 has aesthetically conducive plugs to cover the outer mounting-screw holes.
Model FD0421 may be installed on the same initiating circuit with the Siemens Model 'H'-series detectors
[when used with Desigo Fire Safety Modular I FireFinder XLS/V I FC/FV20—series FACP5] -
HFP-11, HFPT-11
Model 'XTRI'-series interfaces
Model 'HTRI'-series interfaces
Model 'HMS'-series manual stations
Model HCP output-control detection devices
Model 'HZM'-series of addressable, conventional zone modules
Each detector, which is shipped with a protective dust cover,
consists of the following:
Dust-resistant photoelectric chamber
Solid-state, non-mechanical thermal sensor
Microprocessor-based electronics with a low-profile plastic housing
All Model FD0421 intelligent, addressable detectors are approved for operation with
the Underwriters' Laboratories-specified temperature range of 32° to 120° (0° to 49°C).
(See: installation manual P/N—A6V10323928 for further details)
Siemens
Building Technologies Division -3- usa.siemens.com/desigo-fire-safety
Installation of Model FD0421 smoke detectors requires a two-wire circuit. In many retrofit cases, existing wiring may
be used. 'T-tapping' is permitted only for Style 4 (Class B) wiring. Model FD0421 is polarity insensitive, which can
greatly reduce installation and debugging times.
Model FD0421 detectors can be applied within the maximum 30-feet center spacing (900 sq. ft. areas,)
as referenced in NFPA 72. This application guideline is based on ideal conditions - specifically, smooth ceiling surfaces;
minimal air movement, and no physical obstructions between potential fire sources and the actual detector. Do not
mount detectors in close proximity to ventilation or heating and air conditioning outlets. Exposed joists or beamed
ceilings may also affect safe spacing limitations for detectors.
Should questions arise regarding detector placement, observe NFPA 72 guidelines. Good fire-protection-system
engineering and common sense dictate how and when fire detectors are installed and used. Contact your local
Siemens - Fire Safety distributor or sales office whenever you need assistance applying Model FD0421 in unusual
applications. Be sure to follow NFPA guidelines and UL Listed I ULC Listed installation instructions - included with
every Siemens - Fire Safety detector - and local codes as for all fire protection equipment.
L -• ________
OPERATING '32'-'120'F
TEMPERATURE: (0' - M9°C)
RELATIVE 0- 95%
HUMIDITY: (non-condensing)
AIR PRESSURE: No effect
AIR ',ELOCITY. 0 -4,000 feet-per-minute (fpm)
(0-20 meters-per-second)
INPUT VOLTAGE 16VDC - 30VDC RANGE:
'ALARM'
CURRENT, MAX.: 280pA
~F
'STANDBY'
CURRENT, MAX.: 2801JA, max. (average)
MAXIMUM 30-ft. centers (900 sq. ft.),
SPACING: per NFPA 72
DETECTOR 0.317 Lbs. (0.144 kg.)
MECHANICAL
P PROTECTION UL and ULC Listed
(with STI Guard Model STI-9604) GUARD:
ji1ft1 11
MODEL) DATA PANEL OR TYPE )SHEET
XLS 6300 FireFinder® (fire)
XLSV 6340 FireFinder (fire WI voice)
DESIGO 7300 MODULAR
Desigo Modular (overview)
FC2005 6813 Desigo Fire Safety
-
50-point addressable
FC2025 Desigo Fire Safety 252-pt.
6815 addressable (fire)
FC2050 Desigo Fire Safety 504-pt.
- addressable (fire)
Desigo Fire Safety
FV2025 252-point addressable
(fire W/ Intelligent Voice
6821 Communication [IVC]) __
504 -pt. addressable
:FV:2050] (fire w/ Intelligent Voice
Communication [IVC])
MODEL II PART II
PRODUCT ORTYPE ft NUMBER ft
FD0421 S54320-F4-A1 F
Photoelectric
I Smoke Detector
Compatible Devices:
MODEL PART
OR TYPE ft NUMBER
PRODUCT
DB-1 1 500-0941 51 Detector
Mounting Base
DB-1 1 E j 500-094151 E Detector Base, small
Detector Mounting DB2-HR ] S54370-Fl 2-Al Base with Relay
Remote Alarm
RL-HC 500-033230 Indicator: 4"
(10.2 cm) octagon-
box mount, red
Remote Alarm
RL-HW 500-033310 Indicator: single-
gang box mount, red
FDBZ492 S54319-B22-A1 Addressable
Air-Duct Housing
Addressable Air- FDBZ492.HR S54319-B23-A1 Duct Detector
with Relay
LK-1 1 500-695350 Base Locking Kit
See: www.STI-USA.com for further
details on ordering Model 511-9604
In Canada order:
MODEL II PART
ORTYPE ft NUMBER PRODUCT
Detector
DB-1 1 C 500-095687 Mounting Base,
ULC Listed
- The information contained in this data-sheet document is intended only
as a summary, and is subject to change without notice.
The product(s) described here has/have a specific instruction sheet(s)
that cover various technical, limitation and liability information.
Copies of install-type, instruction sheets -as well as the General Product
Warning and Limitations document, which also contains important data,
are provided with the product, and are available from the Manufacturer.
Data contained in the aforesaid type of documentation should be consulted
with a fire-safety professional before specifying or using the product.
Any further questions or assistance concerning
particular problems that might arise, relative to the
proper functioning of the equipment, please contact
the Manufacturer.
SIEMENS
SIEMENS Data Sheet
Fire Safety Products
Intelligent Detection Devices
Thermal (Heat) Detector
Model FDT421
ARCHITECT AND ENGINEER SPECIFICATIONS
Provides seven (7) field-selectable settings in the 135°— 174°F (57.20 — 78.9°C) temperature range
Tr-color detector-status light-emitting diode (LED) with 3600 viewing
Compatible with Model DPU (device programmer I loop tester)
Utilizes advanced microprocessor-based signal processing
Polarity insensitive utilizing Sure Wire technology .•
- t
Provides a low-temperature warning at 40°F (4.4°C) J
l.•' '1;
Each detector is self-testing:
complete diagnostics performed every 10 seconds
Compatible with Model D13-1 1—series mounting bases
Field programmable as rate-of-rise or fixed temperature '(/
_- Compatible with Siemens Model 'H'-series devices on the
same loop (with FireFinder®XLS and Desigo fire systems) -
Superior EMI I RFI immunity • ®UL5;lListed and @ULC Listed;
Restriction of Hazardous Substances FM C3230,3210),
(RoHS) compliant CSFM (#72720067:0258) Approved
Product Overview
The Model FDT421 Intelligent Thermal (Heat)
Detector provides an advanced method of detection,
address programming and supervision -combined
with sophisticated FACP communication. Model
FDT421 uses a state-of-the-art thermistor,
microprocessor and advanced signal analysis,
providing high reliability and accuracy.
Further, Model FDT421 is a cost-effective two-wire I
addressable thermal detector that provides a unique,
advanced feature: field-selectable temperature
settings specially tailored for application-specific
detection needs.
Model FDT421 provides seven (7) field-selectable
temperature-range settings: 1350F (57°C) - 174°F
(79°C) with fixed and rate-of-rise programmability.
This variance provides the customer with maximum
flexibility to program the temperature settings to suit
multiple application needs and changing
environmental conditions.
Additionally, Model FDT421 can be configured to provide
a low-temperature warning signal at 40°F (4.40C). With
use of a compatible FACP (FireFinder XLS and Desigo Fire
Safety panels), this feature serves as prevention of water
freezing in pipes for sprinkler systems, and meets NFPA
72 code.
Model DPU
Model FDT421 is compatible with the Siemens field-device
programmer/ test unit (Model DPU), which is a compact,
portable, menu-driven accessory for electronically
programming and testing detectors, easily and reliably.
Model DPU eliminates the need for cumbersome, unreliable
mechanical programming methods - such as dials or
switches—and reduces installation and service costs by
electronically programming and testing the detector prior to
installation. Each detector consists of a solid state, non-
mechanical thermal sensor, and microprocessor-based
electronics with a low-profile plastic housing.
Model FDT421 is®Underwriters' Laboratories (®UL521)
Listed as a thermal (heat) detector.
Thermal (Heat) Detector 6151
SIEMENS Industry, Inc.
Building Technologies Division
Product Overview— (continued)
Each Model FDT421 detector base also contains a
provision for an optional, concealed locking mechanism
to prevent unauthorized removal of the detector head
(Model LK-1 1.)
For proper operation of Model DPU, the technician selects
the accessory's program mode, and enters the desired
address. In turn, Model DPU automatically sets and verifies
the address, as well as tests the detector. When in the 'test
mode, Model DPU will perform a series of diagnostic tests
without altering the address or other stored data, allowing
techs to determine if the detector is operating properly.
Model DPU operates on AC power or rechargeable batteries,
providing flexibility and convenience in programming and
testing equipment from practically any location.
Operation
Model FDT421 also utilizes a modern, accurate and shock-
resistant thermistor to sense temperature changes:
I Thermister
Each Model FDT421 detector provides seven (7) pre-
programmed, FACP-selectable parameter sets.
Detector Supervision and Testing
Model FDT421, which is listed as a self-testing device,
contains a tn-color light emitting diode (LED) indicator,
capable of flashing any one (1) of three (3) distinct colors:
Green, Yellow, or Red. During each flash interval; the
microprocessor-based detector monitors the folloing:
Temperatures reaching programmed thresholds
Internal sensors and electronics are functional
Based on the monitoring results, the LED indicator flashes
the following colors based on the following conditions:
lash Flash
Color Condition Interval
(in seconds)
Normal supervisory operation.
Green*: Temperature has not reached 10
programmed alarm thresholds
or set points.
Yellow: Detector is in trouble and 4 needs replacement.
Red: Alarm condition. 1
No Flash: Detector is not powered. -
* LED can be turned OFF.
Please follow the corresponding description of the panelused.
SIEMENS Industry, Inc.
Building Technologies Division
A quick visual inspection is sufficient to indicate the condition
of the detector at any time. If more detailed information is
required, a printed report can be provided from the Model
FC20-series FACPs indicating the status and settings assigned
to each individual detector.
Installation
All Model FDT421 detectors use a surface-mounting base,
Model DB-1 1 or Model DB-1 1 E, which mounts on a 4-inch
octagonal, square or single-gang electrical box. The base
utilizes screw-clamp contacts for electrical connections and
self-wiping contacts for increased reliability.
The Model DB-1 1 base can be used with the optional Model
LK-1 1 detector locking kit, which contains 50 detector locks
and an installation tool to prevent unauthorized removal of
the detector head. Model DB-1 1 has decorative plugs to
cover the outer mounting screw holes.
Model FDT421 may be installed on the same initiating
circuit with the following Siemens Model 'H'-series
detectors [when used with FireFinder XLS and Desigo
Fire Safety panels] -
Model HFP-1 1
Model 'HMS'-series manual stations
Model 'HTRI'-series interfaces
Model HCP output-control devices
Model 'HZM'-series of addressable,
conventional zone modules
Application Data
Installation of Model FDT421 detectors requires a (2) two-
wire circuit. In many retrofit cases, existing wiring may be
used. T-tapping' is permitted only for Style 4 (Class B)
wiring. Model FDT421 is polarity insensitive, which allows
a substantial reduction in installation and debugging time.
Model FDT421 can be applied within the maximum 50-feet
center spacing (2,500 sq. ft. areas), per ®UL This application
guideline is based on ideal conditions— specifically, smooth
ceiling surfaces, minimal air movement, and no physical
obstructions between potential fire sources and the actual
detector. Do not mount detectors in close proximity to
ventilation or heating and air conditioning outlets. Exposed
joints or beamed ceilings may also affect safe spacing
limitations for detectors.
Should questions arise regarding detector placement,
observe NFPA 72 guidelines. Good fire-protection system
engineering and common sense dictate how and when fire
detectors are installed and used. Contact your local
Siemens- Fire Safety distributor or sales office whenever
you need assistance applying Model FDT421 in unusual
applications. Be sure to follow NFPA guidelines and ®UL
Listed I OULC Listed installation instructions - included with
every Siemens - Fire Safety detector - and local codes as
for all fire protection equipment.
Specifications
Model FDT421 is a plug-in, (2) two-wire thermal (heat)
detector, compatible with FireFinder XLS and Desigo
Fire Safety panels. Each Model FDT421 detector has
microcomputer-chip technology and highly stable, solid-
state electronic circuitry.
The Model FDT421 detector utilizes a modern, accurate
and shock-resistant thermistor to sense temperature
changes.
This electronic-sensing method virtually eliminates thermal
lag associated with mechanical temperature-sensing
devices, and provides almost instantaneous temperature
status to the FACP.
Model FDT421 provides seven (7) field-selectable, pre-
programmed temperature settings:
Fixed 1 35°F (570C)
Fixed 145°F (630c)
Fixed 155°F (680c)
Fixed 165°F (74°C)
Fixed 174°F (79°c)
Rate-of-Rise: 15°F! mm. (8.3°c) at fixed 1 35°F (570c)
Rate-of-Rise: 15°F ! mm. (8.30c) at fixed 174°F (79°C)
Additionally, the Model FDT421 detector has the
following optional feature:
Model FDT421 provides indication of potential freezing
for sprinkler systems, via a configuration for reporting a
low-temperature warning of 40°F (4.4°c).
This feature is compatible with Models FC2025, FC2050
and FireFinder XLS.
Technical Data
Operating
Temperature +32°F (0°C) to 100°F (38°C)
Range: [with 135°F (57°C) alarm-threshold setting]
Relative Humidity: 0-95%; non-condensing
Air Pressure: No effect
Input Voltage Range: 1 6VDC - 3OVDC
Alarm Current (max.): 41 OpA
Standby Current (max.): 250pA, max.
(Average)
Maximum Spacing: 50-foot centers (2,500 sq. ft.),
per NFPA 72 and ULC-S524
Thermal Rating:
Model FDT421 provides up to seven (7) field-selectable, pre-
programmed temperature settings:
Fixed 135°F (57°C)
Fixed 145°F (63°C)
Fixed 155°F (68°C)
Fixed 165°F (74°C)
Fixed 174°F (79°C)
Rate-of-Rise: 1 5°F I mm. (8.3°C / mm) at fixed 135°F (57°C)
Rate-of-Rise: 157 / mm. (8.3°C / mm) at fixed 174°F (79°C)
Detector Weight:
0.32 Lbs.
(0.144 Kg.)
SIEMENS Industry, Inc.
Building Technologies Division
Compatible FACPs
Model
Data
Sheet
Number
Description
- 6300 FireFinder XLS
FC2005 6813 50-point addressable FACP
FC2025 6815 252-point addressable FACP
FC2050 6815 504-point addressable FACP
Details for Ordering
Model
Part
Number Description
FDT421 554320-F5-A1 Thermal (Heat) Detector
DB-1 1 500-094151 Detector Mounting Base
DB-1 1 E 500-094151 E Detector Base {small}
DB2-HR S54320-F1 2-Al Relay Base
RL-HC 500-033230 Remote Alarm Indicator:
4" octagon-box mount, red
RL-HW 500-033310 Remote Alarm Indicator:
Single-gang box mount, red
LK-1 1 500-695350 1 Base Locking Kit
I 511-9604 I - I STI Mechanical Protection Guard
See: www.STI-USA.com for further details on ordering
Model STi-9604.
In Canada, order:
I Part I
Model I Number Description
DB-1 1 C 500-095687 I Detector Mounting Base
for Series 11 Detectors (ULC Listed)
Mounting Diagram
Dimensions
4.13 (10 cm)—.--
PD
I .3••
4.9
Notice: This marketing data sheet is not intended to be used for system design or installation purposes.
For the most up-to-date information, refer to each product's installation instructions.
Fire Safety Fire Safety
8 Fernwood Road 1577 North Service Road
SIEMENS Industry, Inc. Florham Park, Ni 07932 East Oakville, Ontario
Building Technologies Division Tel: (973) 593-2600 sii-sj L6H 0H6 /Canada
FAX: (908) 547-6877 Printed in USA. Tel: [905] 465-8000
uRL: www.usa.Siernens.com/Fire URL: www.Siemens.CA
April 2014
Supersedes sheet dated 11/13
(Rev. 4)
Electronic address programming
is easy and dependable
®UL Listed & tULC Listed;
FM, CSFM and NYCFD Approved
SIEMENS Data Sheet
Fire Safety Products
HTRI-Series Interface Modules
Models HTRI-D, HTRI-R and HTRI-S (and USCG-HPLATE for Marine installs)
ARCHITECT AND ENGINEER SPECIFICATIONS
Interfacing and supervising normally open (N.0)
or normally closed (N.C) contacts
Integral single-pole, double-throw (SPDT) relay on
Model HTRI-R (up to 4 amps)
Dual input on Model HTRI-D, using a single address
Polarity insensitive with Sure WirelM technology
Dynamic supervision
Two-wire operation
Multi-color light-emitting diode (LED) indicates system status:
GREEN I AMBER I RED
Mounts in a 4-inch (10.2 cm.) square, 2-1/4" (5.7 cm.)
deep single-gang or double-gang back box
Easy front access to programming port and wiring terminals
Comes with 5"-x- 5" (12.7 -x- 12.7 cm.) plastic faceplate
Separate metal cover plate required for use in Marine installations
Electronic address programming is easy and dependable
Device Programmer/ Tester programs and verifies address
of the device and tests for proper functionality
Product Overview
The Siemens - Fire Safety HTRI-series Intelligent
interface modules are designed to provide the means
of interfacing direct shorting devices to the fire-alarm
control panel (FACP) loop circuit.
The HTRI-series modules provide the most advanced
method of address programming and supervision on
the market—combined with sophisticated control
panel communication. Each HTRI-series interface
module incorporates a microcomputer chip, and each
interface module achieves the state of an 'intelligent
device' through its microcomputer-chip technology,
combined with its sophisticated, bi-directional
communication capabilities with the FACP.
Specifications
The Siemens Mode HTRI-series intelligent interface
modules are available in three (3) types: Model HTRI-
D, as well as Models HTRI-S and HTRI-R, which are both
designed to monitor a (N.0) or (N.C) dry contact.
The interface module reports the status of the (N.0) or
(N.C) contact to the control panel.
Model HTRI-S can only monitor and report the status
of the contact, while Model HTRI-R incorporates an
addressable 'Form C' relay.
The Model HTRI-R relay and contact device input are
controlled at the same address. For the FACP, the
relay and input contact can be controlled as a
separate function. The relay is typically used where
control or shunting of external equipment is required.
The Model HTRI-D is a dual-input module that is
designed to supervise and monitor two (2) sets of dry
contacts. Model HTRI-D only requires one (1)
address, but responds independently to each input.
Model HTRI-D is ideal for monitoring a water-flow
switch and its respective valve tamper switch.
Model HTRI-D flashes twice - once for each address,
and Model HTRI-R LED indicates a change of state in
the relay. The device's microcomputer chip has the
capacity of storing, in memory, identification
information; as well as important operating-status data.
HTRI Series Interface Modules 6304
SIEMENS Industry, Inc.
Building Technologies Division
Specifications (continued)
Each Model HTRI device has a multi-color LED that
flashes GREEN when operating in Normal; AMBER if
unit is in Trouble condition, and RED to indicate a
change of state.
Field-Device Programmer
Siemens - Fire Safety innovative technology allows
HTRI-series intelligent interface modules to be
programmed via the Device Programming /Test
Unit: a compact, portable and menu-driven
accessory that makes programming and testing an
interface device faster, easier and more dependable
than previous methods.
The programmer I tester eliminates the need for
mechanical addressing mechanisms, such as:
program jumpers, DIP switches or rotary dials, since
Model DPU electronically sets the HTRI-series
interface address into the non-volatile memory of
the interface microcomputer-chip.
Vibration, corrosion and other conditions that
deteriorate mechanical addressing mechanisms are
no longer a cause for concern.
The HTRI-series is fitted with screw terminals for
connection to an addressable circuit, and s fully
compatible on the same Siemens FACPs with
Siemens Model 'H'-series intelligent detectors;
Model 'HMS'-series addressable manual stations, or
any other addressable intelligent modules
(e.g. - Model HZM or Model HCP).
Temperature and Humidity Range
Model HTRI-series intelligent interface modules are
®UL Listed. Environmental operating conditions for
HTRI-D, HTRI-R and HTRI-S modules are 32°F (0°C) to
120°F (49°C) with a relative humidity of no greater
than 93%, non-condensing.
Electrical Ratings
Current Draw 1.3mA (Active or Standby)
I
Relay Ratings, Model HTRI-R
Resistive: 4 Amps, 125 VAC
4 Amps, 30 VDC
Electrical Ratings
Relay Ratings, Model HTRI-R - (cont.'d)
3.5A, 120 VAC (0.6P.F.)
3.OA, 30 VDC (0.6P.F.)
Inductive: 2.OA, 120 VAC(0.4P.F.)
2.OA, 120 VAC (0.35P.F.)
2.0A1 30 VDC (0.35P.F.)
Mounting Diagram
Models HTRI-S, HTRI-D and HTRI-R mount directly
into a 4-inch (10.2 cm.) square, 2 1/4" (5.7 cm.)-deep
box back box, or to a user-supplied double-gang back
box. A 5" (12.7 cm.) square, off-white faceplate is
included with each HTRI-series module.
Note: For Marine installations, a metal cover faceplate (Model
USCG-HPLATE) is available separately. The faceplate must
be used to protect Siemens HTRI-series interface modules
from receiving radio-frequency interference (RFI).
MOUNTING SLOTS
FOR 4-INCH
SWITCH BOX
0 0
HTRI-S/-D/-R
—MODULE
I2
OUNTING
FOR
2
>S'
[1 HOLES
WITCHPLATE
MOUNTING SLOTS
FOR DOUBLEGANG
SWITCHBOX
Details for Ordering
Part Model Description Number
HTRI-R 500-033300 Single Input Module with Relay
HTRI-D 500-033360 Dual Input Module
HTRI-S 500-033370 Single Input Module
USCG- I Cover Plate for I *Metal
HPLATE S54319-112-Al { HTRI Series Interface Modules
*denotes for required use with Marine-only
installations / applications
Notice: This marketing data sheet is not intended to be used for system design or
installation purposes. For the most up-to-date information, refer to each product's installation instructions.
SIEMENS Industry, Inc.
Building Technologies Division
Fire Safety
8 Fernwood Road
Florham Park, NJ 07932
Tel: (973) 593-2600
FAX: (908) 547-6877
URL: www.USA.Siemens.com1FIRE
Fire Safety
1577 North Service Road
East Oakville, Ontario
(511-FS) L6H 01-16 / Canada
Printed in U.S.A. Tel: [905] 465-8000
URL: www.5iemens.OA
February 2016
Supersedes sheet dated 6/2015
(Rev. 6(
SIEMENS Data Sheet
Fire Safety & Security Products
Intelligent Initiating Devices
Intelligent Device Interface Module
Model HTRI-M {STRI-M for Canada}
ARCHITECT AND ENGINEER SPECIFICATIONS
Interfaces and supervises normally open (N.O.) contacts:
[i.e. - fire detection]
Interfaces and supervises normally closed (N.C.) contacts:
[i.e. - security detection]
Compact size allows mounting in single-gang box behind equipment
Polarity insensitive with Sure WireTM technology
Innovative technology supports comprehensive system and
interface communication • MI .Lr
Dynamic supervision
1 I Two-wire operation REFERTOOSTLMSM
Device Programmer! Test Unit programs and verifies address and SIEWNS test functionality
.. p.a..,Wo At
®UL Listed, €ULC Listed;
FM, CSFM and NYC Fire Department Approved -
Product Overview Specifications
The Intelligent Interface Module (Model HTRI-M)
is designed to provide the means of interfacing
direct shorting devices to the Device Program I
Test Unit (Model DPU) for various Siemens -Fire
Safety fire-alarm control panels (FACPs).
Model HTRI-M provides the most advanced
method of address programming and supervision
-including sophisticated FACP-communication -
in the fire and life safety market. Each Model
HTRI-M interface module incorporates
microcomputer-chip technology, and advanced
bi-directional communication capabilities with the
respective FACP.
Model HTRI-M is designed to monitor a N.O. or
N.C. dry contact, and reports the contact status to
the FACP. The microcomputer chip for Model
HTRl-M has the capacity of storing -in memory -
identification information, as well as integral
operating-status data.
Each Model HTRI-M interface module is
programmed, via Model DPU, which is a compact,
portable and menu-driven accessory that makes
programming and testinga given interface more
accurately and efficiently than ever before.
Model DPU eliminates the need for mechanical-
addressing mechanisms -such as program
jumpers, DIP switches or rotary dials - since
Model DPU sets the interface address of Model
HTRI-M into its microcomputer-chip, non-volatile
memory electronically.
Vibration, corrosion and other conditions that
deteriorate mechanical-addressing mechanisms
are no longer a cause for concern. Model HTRI-M
is connected to Model DPU with the programming
cable provided with the tester. This programming
cable (P/N 110-694927)utilizes two (2) alligator
clip connectors, to attach to the HTRI-M.
Intelligent Device Interface Module 6308
SIEMENS Industry, Inc.
Building Technologies Division
Specifications - (continued)
Model HTRI-M has five (5) leads [one (1) of the
five (5) leads is for grounding], which are wired
to the system with user-supplied wire nuts.
Model HTRI-M is fully compatible on the same
Model DLC circuit with all intelligent Siemens
Model 'H'-series detectors; Model 'HMS'-series
addressable, manual stations; or any other
Model 'H'-series addressable intelligent modules
(i.e. - Model HZM or Model HCP).
Electrical Rating
Current Draw: 1.5mA (Active or Standby)
Details for Ordering
Model
Number
Part
Number Description
HTRI-M 500-034000 Single-Input Intelligent Interface Module
In Canada, order:
Model
Number
Part
Number Description
STRI-M 500-034000c Single-Input Intelligent Interface Module
For shipping-weight considerations, each Model
HTRI-series is approximately 3.5 oz. (0.1 kg).
Notice: This marketing data sheet is nDt intendea to be used for system design or installation purposes.
For the most up-to-date information, refer to each product's installation instructions.
Fire Safety Fire Safety
8 Fernwood Road 2 Kenview Boulevard
SIEMENS Industry, Inc. Florham Park, NJ 07932 Brampton, Ontario June 2013
Building Technologies Division Tel: (973) 593-2600 SIHS L6T 5E4 I Canada supersedes sheet dated 12/I1 FAX: (908) 547-6877 Printed in U.S.A. Tel: (905) 799-9937 (Rev.3(
URL: www.usa.Siemens.comtire FAX: (905) 799-9858
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM
LISTING SERVICE
LISTING No. 7165-0067:0508 Page 1 of 3
CATEGORY: 7165-- FIRE ALARM CONTROL UNIT (COMMERCIAL)
LISTEE: Siemens Industry, Inc. Building Technologies Division8 Fernwood Road, Florham Park, NJ
07932
Contact: Evelyn Esteban (973) 593-6582 Fax (973) 593-6652
Email: evelyn.esteban@siemens.com
DESIGN: Model Desigo Fire Safety Modular and Cerbrus Pro Modular fire alarm control unit. Local,
auxiliary, remote station (protected premises), proprietary, central station (protected
premises), releasing service, waterflow, mass notification and sprinkler supervisory service.
Refer to listee's data sheet and control unit's installation instructions for additional detailed
product description and operational considerations. System components:
PMI-3, GPMI-3 Person Machine Interface
FCM 2041-U2, FCM 2041-U3 Operator Interface
PSC-12 Power Supply
PTB Power Termination Board
RPM Remote Printer Interface
CRC-6 Relay Card
CC-2, -5 Card Cage
ZIC-4A Zone Indicating Card
DLC Device Loop Card
XDLC Device Loop Card
MLC MXL Line Loop Driver Card
HTSW-1 Tamper Switch
NIC-C Network Interface Card
5128, 5129 Silent Knight Dialer/DACT
LLM-1 Line Module
FCM-6 Fan Control Module
SCM-8 Switch Control Module
LCM-8 LED Control Module
CSB CAN Sounder Board
PSX-12 Extender Power Supply
SIM-16 Supervised Input Module
OCM-16 Output Control Module
RNI Remote Network Interface
HTRI-M , -5, -D, -R Addressable Monitor Module
CAB2-BB, CAB3-BB Enclosure
CAB-MP Mounting Plate
CAB2-BD, -RD, -XBD Enclosure Door
07-12-2018
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed
the test results and/or other data but does not make an independent verification of any claims. This listing is not
an endorsement or recommendation of the item listed. This, listing should not be used to verify correct
operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other
Date Issued: July 24, 2018 Listing Expires June 30, 2019
Authorized By: DAVID CASTILL.O, Program Coordinator
Fire Engineering Division
Listing No. 7165-0067:0508
Page 2 of 3
CAB3-BD, -RD, -XBD Enclosure Door
CAB1 -TK, CAB1 R-TK, CAB2-TK, Enclosure Trim Kit
CAB2R-TK, CAB3-TK, CAB3R-TK Enclosure Trim Kit
CAB-BATT Battery Box
CAB-55-BRKT, CAB-100-BRKT Battery Bracket
REMBOX2-MP Mounting Plate
REMBOX2, REMBOX2R, REMBOX4, REMBOX4R; Remote System Enclosure
REMBOX4-MP Mounting Plate
MI-REM Remote PMI
PM I-INTL PMI International
SSD, SSD-C, SSD-C-REM System Status Display
ZIC-2C Dual Channel Audio Card
ZIC-813 NAC Card
ZIC-SPC Strobe Power Conditioner
HZM Conventional Zone module
OD-LP, -BP, -GP Door plate
ID-SP, -FP Door Plate
CAB1, CAB1R Cabinet
BP-61, BTX-1 BTX-2, BTX-3 Battery Sets
HUM Loop Isolator Module
REL-EOL, EL-33 Resistor Kits
ILED-HC, ILED-HW Remote Alarm Lamp
CDC-4 Conventional Detector Card
XLS-RK19 Rack
XDACT-ASSY Mounting Bracket Assembly
MPF-RK Front Panel
MPR-RK, PTB-RK Back Panels
BP-RK Blank Plate
SNU Single Node Upload
XLS-MSE2-ADPT, XLS-MSE2R-ADPT Enclosure Door Adaptor Kit
XLS-MSE3-ADPT, XLS-MSE"R-ADPT Enclosure Door Adaptor Kit
XLS-MLE6-ADPT, XLS-MLE6F-ADPT Enclosure Door Adaptor Kit
XLS-MME3-ADPT, XLS-MME3R-ADPT Enclosure Door Adaptor Kit
XLS-RCC 1 -ADPT Remote Enclosure Door Kit
XLS-RCCI3F-ADPT, XLS-RCCI3FR-ADPT Remote Enclosure Door Kit
VPM VESDA peripheral moduie
VPM-MP mounting bracket
VESDA HLI KIT interface
XDMC digital audio message card
FCA2015-UI Serial digital alarm communicator transmitter (DACT)
RATING: 120 VAC Primary Supply Input
24 VDC Output
07-12-2018
This listing is based upon technical data submitted by the appl,car,t. CSFM Fire Engineering staff has reviewed
the test results and/or other data but does not make an independent verification of any claims. This listing is not
an endorsement or recommendation cf the item listed. This listing should not be used to verify correct
operational requirements or installation criteria. Refer to listees data sheet, installation instructions and/or other
Date Issued: July 24, 2018 Listing Expires June 30, 2019
Authorized By: DAVID CASTILLO, Program Coordinator
Fire Engineering Division
Listing No. 7165-0067:0508
Page 3 of 3
INSTALLATION: In accordance with listee's printed installation instructions, applicable codes and ordinances,
and in a manner acceptable to the authority having jurisdiction.
MARKING: Listee's name, model number, electrical rating, and UL label.
APPROVAL: Listed as fire alarm control unit for use with optional Voice Communication Accessories
(CSFM Listing No. 6912-0067:237) and separately listed compatible initiating and indicating
devices. Refer to manufacturer's Installation Manual for details.
This control unit can generate a distinctive three-pulse Temporal Pattern Fire Alarm
Evacuation Signal (for total evacuation) in accordance with NFPA 72, 2002 Edition.
Strobe devices can be controlled by the ZlC-4A for (synchronized or unsynchronized)
operation. The ZIC-4A output can also be configured as connection to municipal tie, releasing
service per NFPA 13 and NFPA 2001.
This control unit meets the requirements of UL-864, 10th Edition Standard.
NOTE: 1. For Fire Alarm Verification Feature (Delay of fire alarm), the maximum
Retard/Reset/Restart period must be adjusted to 30 seconds or less.
Combined with 7170-0067:236
XLDC device loop card provides 4 class A/B/X SLC loops with separately listed X series
addressable devices (CSFM Listing No. 7300-0067-0501.
4.The separately listed PAD-5, PAD 5-MB, PAD-5-CLSA, and PAD-5-CDC (CSFM Listing
No. 7135-0067:0507) can connect to the Desigo Fire Safety Modular or Cerbrus Pro Modular
control unit via the P2 SLC loop.
07-12-2018
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed
the test results and/or other data but does not make an independent verification of any claims. This listing is not
an endorsement or recommendation of the item listed. This listing should not be used to verify correct
operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other
Date Issued: July 24, 2018 Listing Expires June 30, 2019
Authorized By: DAVID CASTILLO, Program Coordinator
Fire Engineering Division
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM
LISTING SERVICE
LISTING No. 7300-0067:0134 Page 1 of 1
CATEGORY: 7300 -- FIRE ALARM CONTROL UNIT ACCESSORIES/MISC. DEVICES
LISTEE: Siemens Industry, Inc. Building Technologies Division8 Fernwood Road, Florham Park, NJ
07932
Contact: Evelyn Esteban (973) 593-6582 Fax (973) 593-6652
Email: evelyn.esteban@siemens.com
DESIGN: Models DB4T, DB4TS, DB4F, DB4TF, DB4FS, DB3S, ADB3, ADBX3, DB-HR, *DB2HR
DBX3RS, DB-1 1, DB-X1 iRS, ADBI60, ADB-1 1, ADBH-1 1,SBGA-34, ADBX-1 I and 8837
detector bases and Model DB-ADPT detector/base adapter. Suitable for use with Models
RR2 or RR3 auxiliary relays. Model DB-1 I is suitable for use only with Model RR-1 I or
RR-1 IF auxiliary relay. Models DB-11 base, ADBH-11 audible base, and DB-HR, *DB2HR
relay bases are intended to be used with Models HFP-1 1, *HFpO..1 1 and HFPT-1 1 Intelligent
Series smoke and heat detectors (CSFM Listing No. 7272-0067:0223 and 7270-0067:0224).
Model SBGA-34 audible base is intended to be used with Models HFP-1 1, HFPT-1 1, or
HFPO-1 I detectors (CSFM Listing No. 7272-0067:0223 and 7270-0067:0224), Models
FDOT421, FD0421, 0H921 and 0P921 detectors (CSFM Listing No.7272-0067:0258),
Models FDT421 and H1921 detectors (CSFM Listing No.7270-0067:0262), and Models
FDOOT441, FDOOTC441, 00HC941 and 00H941 detectors (CSFM Listing
No.7270-0067:0260). *Model DB2-HR Relay Base can be used also with intelligent Series
smoke detectors type FDOT421, FD0421, 01-1921, 0P921 (CSFM Listing
No.7272-0067:0258), FDT421, H1921 (CSFM Listing No.7270-0067:0262), and FDOOT44I,
FDOOTC44I, OOHC94I, 00H941 (CSFM Listing No.7270-0067:0260). Refer to listee's data
sheet for additional detailed product description and operational considerations.
INSTALLATION: In accordance with listee's printed installation instructions, applicable codes & ordinances
and in a manner acceptable to the authority having jurisdiction. Model DB-11, ADBH-11,
SBGA-34, DB-HR and *DB2..HR may be installed on the ceiling or on the wall.
MARKING: Listee's name or SIEMENS, model number, electrical rating and UL label.
APPROVAL: Listed as detector bases for use with separately listed compatible smoke detector heads
and fire alarm control units.
*Rev. 04-15-14 gt
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed
the test results and/or other data but does not make an independent verification of any claims. This listing is not
an endorsement or recommendation of the item listed. This listing should rot be used to verify correct
operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other
Date Issued: July 01, 2018 . Listing Expires June 3O,2019
Authorized By: DAVID CASTILLO, Program Coordinator
Fire Engineering Division
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION 11 f2 OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM
LISTING SERVICE
LISTING No. 7300-0067:0242 Page 1;of I
CATEGORY: 7300 -- FIRE ALARM CONTROL UNIT ACCESSORIES/MISC. DEVICES
LISTEE: Siemens Industry, Inc. Building Technologies Division8 Fernwood Road, Florham Park, NJ
07932
Contact: Evelyn Esteban (973) 593-6582 Fax (973) 593-6652
Email: evelyn.esteban@siemens.com
DESIGN: Control Unit Accessories. Refer to listee's data sheet for detailed product description and
operational considerations. Accessories are listed as follows:
HTRI-S, -D, -R Addressable Switch Interface Module
HTRI-M Addressable Interface Module
HUM Loop Isolator Module
HZM Conventional Zone Loop
ILED-HC, -HW Remote Lamps
RATING:
INSTALLATION: In accordance with listee's printed installation instructions, applicable codes and ordinances
and in a manner acceptable to the authority having jurisdiction.
MARKING: Listee's name, model number, and UL label.
APPROVAL: Listed as control unit accessories for use with separately listed fire alarm control units. Refer
to listee's Installation Instruction Manual for details.
NOTE:
11-04-2004
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed
the test results and/or other data but does not make an independent verification of any claims. This listing is not
an endorsement or recommendation of the item listed. This listing should not be used to verify correct
operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other
Date Issued: July 01, 2018 Listing Expires June 3O,2019
Authorized By: DAVID CASTILLO, Program Coordinator
Fire Engineering Division
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM
LISTING SERVICE
LISTING No. 7272-0067:0258
CATEGORY: 7272 -- SMOKE DETECTOR-SYSTEM TYPE-PHOTOELECTRIC
Page 1 of 1
LISTEE: : Siemens Industry, Inc. Building Technologies Division8 Fernwood Road, Florham Park, NJ
07932
Contact: Evelyn Esteban (973) 593-6582 Fax (973) 593-6652
Email: evelyn.esteban@siemens.com
DESIGN: Models FD0421 and 0P921 photoelectric addressable smoke detectors. Models FDOT42I
and 0H921 photoelectric smoke detector with complementary automatic heat detectors. All
models are to be used with liste's separately listed base models DB-1 1 and DB-1 1 E. Refer
to listee's data sheet for additional detailed product description and operational
considerations.
RATING: 13-33VDC
INSTALLATION: In accordance with listee's printed installation instructions, applicable codes & ordinances
and in a manner acceptable to the authority having jurisdiction.
MARKING: Listees name, model number, and UL label.
APPROVAL: Listed as photoelectric type smoke detectors for use with listee's separately listed base
models DB-11 and DB-IIE (CSFM listing number 7300-0067:134) and listee's separately
listed alarm indicator models RL-HC and RL-HW (CSFM listing number 7300-0067:225).
07-12-11 mt
This listing is based upon technical data submitted by the applicant. CSFM Fie Engineering staff has reviewed
the test results and/or other data but does not make an independent verification of any claims. This listing is not
an endorsement or recommendation of the item listed. This listing should rot be used to verify correct
operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other
Date Issued: July 01, 2018 Listing Expires June 30, 2019
Authorized By: DAVID CASTILLO, Program Coordinator
Fire Engineering Division
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM
LISTING SERVICE
CAL I FIRE
SIN-
LISTING No.
CATEGORY:
LISTEE:
DESIGN:
RATING:
INSTALLATION
MARKING:
APPROVAL:
7270-0067:0262 Page 1 of 1
7270 -- HEAT DETECTOR
Siemens Industry, Inc. Building Technologies Division8 Fernwood Road, Florham Park, NJ
07932
Contact: Evelyn Esteban (973) 593-6582 Fax (973) 593-6652
Email: evelyn.esteban@siemens.com
Models FDT42I and H1921 fixed temperature/rate-of-rise heat detectors. Refer to listee's
data sheet for additional detailed product description and operational considerations.
16-30 Vdc
In accordance with listee's printed installation instructions, applicable codes & ordinances
and in a manner acceptable to the authority having jurisdiction.
Listees name, model number, temperature rating and UL label.
Listed as heat detector for use with listee's separately listed compatible detector bases.
02-14-12 gt
014, This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed
the test results and/or other data but does not make an independent verification of any claims. This listing is not
an endorsement' or recommendation of the item listed. This listing should not be used to verify correct
operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other
Date Issued: July 01, 2018 Listing Expires June 3O,2019
Authorized By: DAVID CASTILLO, Program Coordinator
Fire Engineering Division
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
OFFICE OF THE STATE FIRE MARSHAL _____
FIRE ENGINEERING -BUILDING MATERIALS LISTING PROGRAM
LISTING SERVICE
LISTING No. 3240-0067:0265 Page 1 of 1
CATEGORY: 3240 -- DUCT SMOKE DETECTOR HOUSING/BASE
LISTEE: Siemens Industry, Inc. Building Technologies Division8 Fernwood Road, Florham Park, NJ
07932
Contact: Evelyn Esteban (973) 593-6582 Fax (973) 593-6652
Email: evelyn.esteban@siemens.com
DESIGN: Models FDBZ492, FDBZ492-R, *FDBZ492..PR and FDBZ492-HR air duct housings.
Accessories:
Model FDBZ492-RTL; Remote alarm indicator
Model FDBZ-WT; metal enclosure for indoor wet applications
Refer to listee's data sheet for additional detailed product description and operational
considerations.
RATING: 16-27Vdc
INSTALLATION: In accordance with listee's printed installation instructions, applicable codes and ordinances
and in a manner acceptable to the authority having jurisdiction.
MARKING: Listee's name, model number, electrical rating, and UL label.
APPROVAL: Listed as air duct housings for use with listee's separately listed detector heads.
*Rev 08-13-13 gt
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed
the test results and/or other data but does not make an independent verification of any claims. This listing is not
an endorsement or recommendation of the item listed. This listing should not be used to verify correct
?VI operational requirements or installation criteria. Refer to listee's data sheet, ins:allation instructions and/or other
Date Issued: July 01, 2018 Listing Expires June 30, 2019
Authorized By: DAVID CASTILLO, Program Coordinator
Fire Engineering Division