FM Approved and Fully Listed Sprinkler Pipe
Wheatlands Schedule 10 and Schedule 40
steel fire sprinkler pipe is FM Approved and UL,
C-UL and FM Listed.
Approvals and Specifications
Both products meet or exceed
the following standards:
ASTM A135, Type E, Grade A (Schedule 10)
ASTM A795, Type E, Grade A (Schedule 40)
NFPA13
Manufacturing Protocols
Schedule 10 and Schedule 40 are subjected
to the toughest possible testing protocols to
ensure the highest quality and long-lasting
performance.
Finishes and Coatings
All Wheatland black steel fire sprinkler pipe
up to 6' receives a proprietary mill coating to
ensure a clean, corrosion-resistant surface that
outperforms and outlasts standard lacquer
coatings. This coating allows the pipe to be
easily painted, without special preparation.
Schedule 10 and Schedule 40 can be ordered in
black, or with hot-dip galvanizing, to meet
FM/UL requirements for dry systems that meet
the zinc coating specifications of ASTM A795
or A53. All Wheatland galvanized material is
also UL Listed.
Product Marking
Each length of Wheatland fire sprinkler
pipe is continuously stenciled to show
the manufacturer, type of pipe, grade, size
and length. Barcoding is acceptable as a
supplementary identification method.
NOMINAL NOMINAL
NPS NOM OD NOM ID WALL WEIGHT UL PIECES
in mm in. mm in. mm lbs/ft. kg/rn CRR Lift
1'/ 1.660 42.2 1,442366 .109 2.77 181 2.69 7.3 61
11/ 00 48.3 168. 42.7 10 2.09 3 56 6
2 2.375 60.3 2.157 54.8 06 7 7" 2.64 3.93 4.7 3"
2¼ 2 875 73.0 Z.635 66.9 .120 Z,053.53 5,26 15 30
3 500 8&9 3260 828 120 105 4.34 646 26 19
.4 4500 1143 4,2601082 120 3,0E o 83" 1,6 19
5 5.563 1.3 5.295 134.5 .!,)4 3.40 7.78 1158 1. 5 13
6 6.625 1683 6,357 161 34 3.-.0 9.30 13.85 10 10
8 8.625 219.1 8.249 2098 .188 4.78 16.96 25.26 2.1
Calculated using Standard UL CRR formula, UL Fire Protection Directory, Category VIZY.
* The CRR is a ratio value used to measure the ability of a pipe to withstand corrosion.
Threaded Schedule 40 steel pipe is used as the benchmark (value of 1.0).
NOMINAL NOMINAL
NPS NOM OD NOM ID WALL WEIGHT UL PIECES
iii. mm In. mm In. mm lbs/ft. kg/nn cpe Lift
1 1,315 3-1,A 1.049 26.6 13 --1.38 1.68 2.70 1.00 70
11/4 1.660 4.2 1.380 35.1 40 3.56 2.2" 3.39 1,00 51
11/2 1,900 483 1.610 409 145 3,68 272 405 100 44
2 2.375 603 2077 52." 1 "9 361 5.145 1.00 30
Calculated using Standard UL CRR formula, UI. Fire Protection Directory, Category VIZY.
The CRR is a ratio value used to measure the ability of a pipe to withstand corrosion.
Threaded Schedule 40 steel pipe is used as the benchmark (value of 1.0).
@ C <
PROJECT: CONTRACTOR: DATE:
ENGINEER: SPECIFICATION REFERENCE: SYSTEM TYPE:
LOCATIONS: COMMENTS: AS 160211
El BLACK HOT-DIP GALVANIZE[ 951 PALOMAR AIRPORT RD
'1dTube
L . ---- .----
Fig. 24 - Hanger for CPVC Plastic Pipe & IPS Steel Pipe
Double Fastener Strap Side Mounted (Cooper B-Line 133183) ..; 1.0$
Size Range: 3/4".(20mm) thru 2" (50mm) CPVC pipe . 'IJSTED.
Material: Pre-Galvanized Steel .
Function: Intended to perform as a hanger to support CPVC piping used in
automatic fire sprinkler systems. Can be installed on the top or on the bottom - - -
ofabeam. -
Approvals: Underwriters Laboratories Listed in the USA (UL) and
Canada (cUL) to support fire sprinkler piping. May be installed in wood using
fasteners supplied with product, or into minimum 20 gauge (0.912mm) steel
using (2) 1/4 x 1 tek type screws. Meets and exceeds the requirements of -
NFPA 13,13R and 13D.
Features: Fig. 24 incorporates features which protect the pipe and .
ease installation. The flared edge design protects the CPVC pipe from .. I any rough surface. Easily attaches to the building structure using the two UL Listed hex head self threading screws* furnished with the I product. It is recommended that rechargeable electric drills fitted with I a hex socket attachment be used as installation tools. No impact •. L tools (such as a hammer) are allowed. Damage has been known to 0 result from installations using impact type tools. No pre-drilling of a L pilot hole in wood is required. s
Finish: Pre-Galvanized " " B
Order By: Figure number and pipe size A
*_Hardened hex head self threading screw is furnished with the
product and is the minimum fastener size acceptable.
With reduced spacing, consult factory.
24-/4
CPVC
Pipe
3/4
Size
(20) 2I16"
A
(58.7) 1I32
B
(27.8) 1/16"
G
(30,2)
Max. Hanger
Spacing
51/2 (1.67)
Fastener
Head
5/16"
Hex
Size
(7.9) 9
Approx. i
wt./i 00
(4.1)
24-1 1" (25) 2/8 (66]) 1/6" (33.3; 1/16" (30]) 6 (1.83) /16' (7.9) 9 (4.1)
24_11/4 11/4'1 (32) 3" 76.2 11/2 (38.1) 1/16 (30.2) 91/7 (1.98) 16 (7.9) 11 (5.0)
2411/2 11/2 (40) 31/4 (32.5) 1I8" 43.3) 1/16 (30.2) 7 (3.13) /16 (7.91 12 (54)
24-2 2" (50) 311/16 (93.7) 1 127/32" (43.6) 1I16" 1 (30.2) 8 (2.44) /16" (7.9) 1 15 (6.8)
Fig. 25 - Surge Restrainer rh O&S
o Size Range: — One size fits 3/4' (20mm) thru 2" (40mm) pipe. LISTED
3 Material: - Pre-Galvanized Steel S
i Function: — Designed to be used n conjunction with Fig. 200 band
hangers
to restrict the upward movement of piping as it occurs during sprinkler ,.
head activation or earthquake type activity. The surge restrainer is
easily and efficiently installed by snapping into a locking position on f :1
the band hanger. This product is intended to satisfy the requirements ...
as indicated in the National Fire Protection Association NFPA 13 2010
edition, 9.2.3.4.4.1 and 9.2.3.4.4.4 Can be used to restrain either steel
pipe or CPVC plastic Pipe
Approvals: — Underwriters Laboratories Listed only when used with
band hanger Fig. 200, in the USA (UL) and Canada (cUL). /
Finish: Pre-Galvanized
Order By: Figure number and band hanger, size from
3/4 (20mm) thru 2" (40mm).
- Patent #5,344,108
All dimensions in charts and on drawings are in inches. Dimensions shown in parentheses are in millimeters unless otherwise specified.
p.-.- COOPER B-Line
44
Fig. 200-1/2.20D-3/4
Fig. 200-21/2 to 200-8
Fig. 200 - "Trimline" Adjustable Band Hanger (B-Line Fig. B3170NF)
Fig 200F - "Trimline" Adjustable Band Hanger with Felt Lining (B Line Fig B317ONFF)
Fig 200C - Trimline Adjustable Band Hanger with Plastic Coated (B Line Fig B311ONFC)
Fig. 200S - "Trimline" Adjustable Band Hanger with Non-Captured Nut
Size Range:
Fig. 200 - 1/2" 115mm) thru 8" (200mm) pipe
Material: Steel, Pre-Galvanized to G90 specifications
Function: For fire sprinkler and other general piping purposes. Knurled
swivel nut design permits hanger adjustment after installation.
Features:
(1/2" (15mm) thru 2" (50mm)) Flared edges ease installation for all pipe
types and protect CPVC plastic pipe from abrasion. Captured design
keeps adjusting nut from separating with hanger. Hanger is easily
installed around pipe.
For hanger with non-captured nut order Fig. 200S.
(21/2" (65mm) thru 8' (200mm)) Spring tension on nut holds it securely in
hanger before installation. Adjusting nut is easily removed.
Approvals: Underwriters Laboratories listed (1/2" (15mm) thru 8" (200mm))
in the USA (UL) and Canada (cUL) for steel and CPVC plastic pipe and
Factory Mutual Engineering Approved (FM) (3/4" )20mm) thru 8" (200mm)).
Conforms to Federal Specifications WW-H-1 71 E & A-A-1l 92A, Type 10
.and Manufacturers Standardization Society ANSI/MSS SP-69 & SP-58,
Type 10.
Maximum Temperature: 650°F (343°C)
-Finish: Pre-Galvanized. Stainless Steel
r"nateria(s will be supplied with (2) hex nuts
in place of a knurl nut.
Order By: Figure number and pipe size
Designed to meet or exceed requirements of
FM DS 2-0.
Fig. 200C
Fig. 200-1 to 200-2
—p
Fig. 200F
Pipe Size Rod Size A B Approx. Wt.I100
Part No. in. (mm) in. (mm) in. (mm) lbs. (kg)
200 1/2 /2 15) 3/8,1-16 31/1 (794) 2/8 (667) 11 (50)
200-/4 3/4' 20) /8'-15 31/0 79.4) 272 (635) 11 5.0)
2001 1 25) /t 16 3/8 (057) 278 (667) 12 (55)
200-1I4 174' (32) 3/8'_ 16 33/4 (94.0) 2/8 (73,0) 13 (5.9)
200-11/2 172 40) 3N-16 378 (984) 27/8 (70) 14 (64)
200-2 2 (50) I8'-16 41/2' 114.31 3 (76,3) 15 (6.91
20021/2 21h (65 /8 "-16 5I8 142 9) 41/8 (1047) 27 (123)
200-3 3" (75) 3/8'16 57/3 149.1) 4" 101.6) 29 (13.3)
200-31/2 31j (90) 3/8"-16 7/s (1873) 51/4 (13.) 34 (156)
200-4 4" (100) /'-16 73/8' (107.3) 5" (127.0) 35 (160)
200-5, 5 1125) 1/2"-13 91/8 (231,M 61/4 (1507) 66 (302)
200-6 6" (150) 1/2'_13 101/8 (257.2) 6/4' (171.4) 73 (334)
200-8 6 (202) 1/2"-13 131Jo (3334) 8/4 (2222) 136 (6231
All dimensions in charts and on drawings are in inches. Dimensions shown in parentheses are in millimeters unless otherwise specified.
Fire Protection Solutions B-Line
Wood Flooding No pre -drilling required
Quick to install using the Sammy
Nut Driver with an 18V cordless
drill/driver.
Wood Joel
. Saves time from traditional
_____________ • methods.
Double Sheevock - Ceiling Reduces installation costs.
Made in the U.S.A.
(.7 darmirabon
-. www.itwbulldex.com)
"A a MM YT FOM WO OD
nn!kafir,
4 8002957 GST 100 1/4x1" 25 125
8003957 CST 200 1/4x7 1760 (H( 25 - 125
1 8004957 GST 300 14 x 3 2060 (H 25 125
J5-8007957 ST 10 1/4 xl 210 )7J1xOSB( 300 25 12
29 8008957 GST 20 1/4 x 2 1760 (Or) 850 1475 25 125
8068925 GOT 20-OS 14 x 2 1760 (Ar) 850 25 125
2 8009925 GST25-380 38x2 1/2 2111 (Hi) 100 25 125
#14 Black Q. <> CS 8010957 GST 30 1t4 x 3 2060 (Fir) 1500 1475 25 12
Nut Driver 17 806992 30-SS 1/4 x 3 2060 (Or) 2 125 Part #8113910 8011925 GST 11 1/4 x 4 2180 (F/i) -- 25 125
W '2' 8013925 GOT 2 1/4 x2 1760 (Fir)
, , - 25 125
Jj 7'
-. 8014925 .,ST2 5-380 3/8x2-1/
114-x 3'
2113 (Fir) 25 125
P. 8015925 GST 3 2275 (Fir) 25 125
#14 SW Red
Not Driver
Part #8114910
Elm
MeeEINU.s.A
OHS
.
SPECIAL NUT DRIVER SYSTEM: The nut drivers were cesigned with a unique spin-off feature which provides a fast and safe installation each time. When the face of the driver comes into
contact with the material you are installing into, continue driling until not driver spins free. Installation is then complete. Warranty reqLires the use of the appropriate nut driver for installations,
tqCI3 Fire Suppression
& Building Products
Technical Services 800-381-9312 I +1-401-781-8220
www.tyco-fire.com
Series DS-1 Dry-Type Sprinklers
5.6K Pendent, Upright, and Horizontal Sidewall
Standard Response, Standard Coverage
General
Description
TYCO Series DS-1 Dry-Type Sprinklers,
5.6K Pendent, Upright, and Horizontal
Sidewall, Standard Response (5 mm
Bulb) and Standard Coverage, are
decorative glass bulb automatic sprin-
klers typically used where:
pendent sprinklers are required on
dry pipe systems that are exposed to
freezing temperatures; for example,
sprinkler drops from unheated
portions of buildings
sprinklers and/or a portion of the
connecting piping may be exposed to
freezing temperatures; for example,
sprinkler drops from wet systems
into freezers, sprinkler sprigs from
wet systems into unheated attics, or
horizontal piping extensions through
a wall to protect unheated areas of a
building such as loading docks, over-
hangs, and building exteriors
sprinklers are used on systems that
are seasonably drained to avoid
freezing; for example, vacation resort
areas
NOTICE
Series DS-1 Dry-Type Sprinklers
described herein must be installed
and maintained in compliance with this
document, as well as with the appli-
cable standards of the National Fire
Protection Association, in addition to
IMPORTANT
Always refer to Technical Data
Sheet TFP 700 for the "INSTALLER
WARNING" that provides cautions
with respect to handling and instal-
lation of sprinkler systems and
components. Improper handling and
installation can permanently damage
a sprinkler system or its compo-
nents and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
Page 1 of 10
the standards of any. other Authorities
Having Jurisdiction. Failure to .do so
may impair the performance of these
devices.
Owners are responsible for maintaining
their fire protection system and devices
in proper operating condition. The
installing contractor or sprinkler manu-
facturer should be contacted with any
questions.
Series DS-1 Dry-Type Sprinklers must
only be installed in fittings that meet
the requirements of the Design Criteria
section.
Model/Sprinkler
Identification
Numbers (SlNs
TY3255 - Pendent
TY3155 - Upright
TY3355 - Horizontal Sidewall
Technical
Data
Approvals
UL and C-UL Listed
FM Approved
LPCB Approved: Ref No. 094a/11
CE Certified: EN 122.59-1
NYC Approved under MEA 352-01-E
Refer to Table A.
Maximum Working Pressure
175 psi (12,1 bar)
Inlet Thread Connections
1-inch NPT (Standard Order)
ISO 7-Ri
Discharge Coefficient
K = 5.6 GPM/psi112
(80,6 LPM/bar1'2)
Temperature Ratings
Refer to Table A.
MAY 2011
Finishes
Sprinkler: Natural Brass, Chrome
Plated, White Polyester
Escutcheon: White Coated, Chrome
Plated, Brass Plated
Physical Characteristics
Inlet.....................Copper
Plug ....................Copper
Yoke ..............Stainless Steel
Casing ...............Galvanized
Carbon Steel
Insert ...................Bronze
Bulb Seat ..........Stainless Steel
Bulb ......................Glass
Compression Screw........Bronze
Deflector.................Bronze
Frame ...................Bronze
Guide Tube.........Stainless Steel
Water Tube .........Stainless Steel
Spring.............Stainless Steel
Sealing Assembly. . . Beryllium Nickel
w/Teflon
Escutcheon ..........Carbon Steel
*DuPont Registered Trademark
TFP500
TFP500
Page 2of10
TY3255 Pendent TY3055 Pendent TY3355 Horizontal Sidewall
with top of Deflector-to-Ceiling
with Standard with Standard Escutcheon distance of 4 to 12 inches
Recessed Escutcheon. . (Figure 5) . . (100 to 300 mm)
(Figure 3)
with Wide Flange with Deep Escutcheon with Standard Escutcheon
Recessed Escutcheon . (Figure 6) . (Figure 9)
(Figure 4)
without Escutcheon with Deep Escutcheon
Temperature Bulb Color (Figure 7) .. . . (Figure 10)
Rating Code
TY3155 Upright without Escutcheon
(Figure 13)
without Escutcheon
(Figure 8)
SPRINKLER FINISH
Natural Chrome White Natural
I
Chrome White Natural Chrome
I
White
Brass Plated Polyester Brass Plated Polyester Brass Plated Polyester
135°F (57°C) Orange
1,23,5 1,2,5 1,2,3,4,5 1,2,4,5 1*,2*,3**,4,5 1*,2*,4,5 155°F (68°C) Red
175°F (79°C) Yellow
200°F (93°C) Green
286°F (141°C) Blue N/A 4, 5
360°F (182°C) Mauve N/A 1*, 2*, 5 N/A
Notes
Listed by Underwriters Laboratories, Inc. (maximum order 4. Loss Prevention Certification Board and CE conformity
length of 48 inches) . apply to these temperature ratings only
Listed by Underwriters Laboratories for use in Canada 5. Approved by the City of New York under MEA 352-01 -E
(maximum order length of 48 inches) Light and Ordinary Hazard Occupancies Only
Approved by Factory Mutual Research Corporation °° Light Hazard Occupancies Only
(maximum order length of 48 inches) N/A - Not Available
TABLE A
SERIES DS-1 STANDARD RESPONSE, STANDARD COVERAGE, DRY-TYPE SPRINKLERS
-LABORATORY LISTINGS AND APPROVALS -
PLUG WITH INLET
SEALING
ASSEMBLY
YOKE
SPRING INLET
BAND
WATER II II
TUBE CASING
GUIDE - INSERT
TUBE
BULB
FRAME SEAT
5 m BULB VENT HOLE
COMPRESSION
DEFLECTOR SCREW
FIGURE 1
SERIES DS- I STANDARD RESPONSE DRY-TYPE SPRINKLERS
- ASSEMBLY -
WRENCH
RECESS
WRENCH'g
FLAT
0 20
PUSH WRENCH
IN TO ENSURE
ENGAGEMENT
WITH SPRINKLER
WRENCHING AREA
FIGURE 2
W-TYPE 7 SPRINKLER WRENCH
SPRINKLER FITTING
(REFER TO DESIGN
CRITERIA SECTION)
FACE OF
SPRINKLER \
FITTING
ORDER LENGTHS:
5" to 48"
(127,0 to 1219,2 mm)
IN 1/4' (6,4 mm)
INCREMENTS
MINIMUM
1-3/4(44,5mm) -
DEFLECTOR
TO CEILING
TOP OF
DEFLECTOR
ORDER LENGTHS:
5" to 48"
(127,0 to 1219,2 mm)
IN 1/4" (6,4 mm)
INCREMENTS
SPRINKLER FITTING
(REFER TO DESIGN
CRITERIA SECTION)
FACE OF
SPRINKLER
FITTING
TFP500
Page 3 of 10
SPRINKLER FITTING
(REFER TO DESIGN
CRITERIA SECTION)
FACE OF
SPRINKLER
FITTING -
ORDER LENGTHS
2-3/4 to 48" 1-3/4 DIA. (69,9 to 1219,2 mm) (44,5 mm)
IN 1/4(6,4mm)
INCREMENTS
FACE OF
CEILING
2-3/16 ± 1/8 DIA.
(55,6 ± 3,2 mm) (76,2 mm)
FIGURE 3
PENDENT TY3255
WITH STANDARD ESCUTCHEON
SPRINKLER FITTING
(REFER TO DESIGN
CRITERIA SECTION)
FACE OF
SPRINKLER \ FIT
ORDER LENGTHS:
3-3/4k to 48"
(95,3 to 1219,2 mm)
IN 1/4" (6,4 mm) 2-1/4' DIA.
INCREMENTS (57,2 mm)
FACE OF
CEILING
1-3/8±1/8 2-7/8" DIA.
(34,9 ± 3,2 mm) -
(73,0 mm)
FIGURE 4
PENDENT TY3255
WITH STANDARD
RECESSED ESCUTCHEON
SPRINKLER FITTING
(REFER TO DESIGN
CRITERIA SECTION)
FACE OF
SPRINKLER..
FITTING ,
LIIp
ORDER LENGTHS: 3-1/2' DIA.
1/2" to 46" (88,9 mm)
(12,7to1168,4mm) 2-1/2" DI
INCREMENTS
RE, Nrl
FACE OF
CEILING
1/8"
(108.0±3,2 mm)
FIGURE 5
PENDENT TY3255
WITH DEEP ESCUTCHEON
FIGURE 6 FIGURE 7
PENDENT TY3255 UPRIGHT TY3155
WITHOUT ESCUTCHEON WITHOUT ESCUTCHEON
(76,2mm)
SPRINKLER FITTING
(REFER TO DESIGN CENTERLINE 5/16'
CRITERIA SECTION) OF WATERWAY (7,9 mm)
FIGURE 8
TY3355 HORIZONTAL SIDEWALL WITH STANDARD ESCUTCHEON
ORDER LENGTHS:
2-3/4 to 48' (69,9 to 1219,2 mrn)
IN 1/4 (6,4 mm) INCREMENTS
FACE OF FACE OF
SPRINKLER MOUNTING -
FITTING SURFACE
4±1/8
(101,6 ± 3,2 mm)
1-3/4 DIA.
(44,5 mm)
TFP500
Page 4 of 10
Operation ' .
When TYCO Series DS-1 Dry-Type
Sprinklers are in service, water 'is
prevented from entering the assembly
by the Plug with Sealing Assembly
(Figure 1) in the Inlet of the Sprinkler.
The glass bulb contains a fluid that
expands when exposed to heat. When
the rated temperature is reached, the.
fluid expands sufficiently to shatter
the glass bulb, and the BUlb Seat is
released.
The compressed Spring is then able
to expand and push the Water Tube as
well as the Guide Tube outward. This
action simultaneously pulls inward
on the Yoke, withdrawing the Plug
with Sealing Assembly from the Inlet,
allowing the sprinkler to activate and
flow water.
Design
Criteria
ORDER LENGTHS: FACE OF
1/2' t045-3/4"(12,7to1162,1 mm) MOUNTING
IN 1/4' (6,4 mm) INCREMENTS SURFACE 4-13/16' ± 1/8'
(122,2 ± 3,2 mm)
FACE OF 2-1/2' DIA.
(63,5 mm) SPRINKLER
- FITTING -
3-1/2 DIA.
(88,9 mm)
F3.5'
SPRINKLER FITTING
(REFER TO DESIGN CENTERLINE 5/16"
CRITERIA SECTION) OF WATERWAY (7,9 mm)
FIGURE 9
TY3355 HORIZONTAL SIDEWALL WITH DEEP ESCUTCHEON
ORDER LENGTHS:
5-1/2" to 48' (139,7 to 1219,2 mm)
IN 1/4'(6,4 mm) INCREMENTS MINIMUM
2-1/4' (57,2 mm)
L
FACE OF DEFLECTOR TO
SPRINKLER MOUNTING
URFACE SURFACE
SPRINKLER FITTING /(7,9 mm)
(REFER TO DESIGN CENTERLINE
CRITERIA SECTION) OF WATERWAY
FIGURE 10
TY3355 HORIZONTTAL SIDEWALL WITHOUT ESCUTCHEON
TYCO Series DS-1 Dry-Type Sprinklers
are intended for use in fire sprinkler
systems designed in accordance
with the standard installation rules
recognized by the applicable Listing
or Approval agency; for example, UL -
Listing is based on NFPA 13 require-
ments. For more information on
LPCB Approval, contact TYCO Fire
Suppression & Building Products at the
following office:
Kopersteden 1
7547 TJ Enschede
The Netherlands
Tel: +31-(0)53-428-4444
Fax: +31-(0)53-428-3377
Sprinkler Fittings
Install 1-inch NPT Series DS-1 Dry-Type
Sprinklers are to be installed in the
1-inch NPT outlet or run of the following
fittings:
malleable or ductile iron threaded
tee fittings that meet the dimen-
sional requirements of ANSI B16.3
(Class 150)
cast iron threaded tee fittings that
meet the dimensional requirements
of ANSI B16.4 (Class 125).
Do not install Series DS-1 Dry-Type
Sprinklers into elbow fittings. The Inlet
of the sprinkler can contact the interior
of the elbow.
The unused outlet of the threaded tee is
plugged as shown in Figure 12.
You can also install Series DS-1
Dry-Type Sprinklers in the 1-inch NPT
outlet of a GRINNELL Figure 730
Mechanical Tee. However, the use of
the Figure 730 Tee for this arrangement
is limited to wet pipe systems.
TFP500
Page 5 of 10
Ambient Temperature
Exposed to Discharge End of Sprinkler
Temperatures for Heated Area'
40°F (4°C) 50°F (10°C) 60°F (16°C),
Minimum Exposed Barrel Length, Inches (mm)2
40-F (4-C) 0 0 0
30'F (-1-C) 0 0 0
20°F (-7°C) 4 (100) 0 0
10-F (-12-C) 8(200) 1(25) 0
0-F (-18-C) 12 (305) 3(75) 0
-10°F (-23°C) 14 (355) 4 (100) 1 (25)
-20°F (-29°C) 14 (355) 6 (150) 3(75)
-30°F (-34°C) 16 (405) 8 (200) 4 (100)
-40°F (-40°C) 18 (455) 8 (200) 4(100)
-50°F (-46°C) 20 (510) 10 (255) 6 (150)
-60°F (-51°C) 20 (510) 10 (255) 6 (150)
Notes
For protected area temperatures that occur between values listed above, use the next cooler temperature.
These lengths are inclusive of wind velocities up to 30 mph (18,6 kph).
TABLE B
EXPOSED SPRINKLER BARRELS IN WET PIPE SYSTEMS
- MINIMUM RECOMMENDED LENGTHS -
The configuration shown in Figure 13
is only applicable for wet pipe systems
where the sprinkler fitting and water-
filled pipe above the sprinkler fitting are
not subject to freezing and where the
length of the Dry-Typo Sprinkler has the
minimum exposure length depicted in
Figure 11. Refer to the Exposure Length
section.
For wet pipe system installations of
1-inch NPT Series DS-1 Dry-Type
Sprinklers connected to CPVC piping,
use only the following TYCO CPVC
fittings:
1" x 1" NPT Female Adapter (P/N
80145)
1" x 1" x 1" NPT Sprinkler Head
Adapter Tee (P/N 80249).
For dry pipe system installations, use
only the side outlet of maximum 2-1/2-
inch reducing tee when locating Series
DS-1 Dry-Type Sprinklers directly
below the branch line. Otherwise, use
the configuration shown in Figure 12 to
assure complete water drainage from
above Series DS-1 Dry-Type Sprinklers
and the branch line. Failure to do so
may result in pipe freezing and water
damage.
L!I.)tLg4
Do not install Series DS-1 Dry-Type
Sprinklers into any other type fitting
without first consulting the Technical
Services Department. Failure to use the
appropriate fitting may result in one of
the following:
Failure of the sprinkler to operate prop-
erly due to formation of ice over the
Inlet Plug or binding of the Inlet Plug.
Insufficient engagement of the Inlet
pipe-threads with consequent leakage.
Drainage
In accordance with the minimum
requirements of the National Fire
Protection Association for dry pipe
sprinkler systems, branch, cross, and
feed-main piping connected to Dry
Sprinklers and subject to freezing
temperatures must be pitched for
proper drainage.
Exposure Length
When using Dry Sprinklers in wet pipe
sprinkler systems to protect areas
subject to freezing temperatures, use
Table B to determine a sprinkler's
appropriate exposed barrel length
to prevent water from freezing in the
connecting pipes due to conduction.
The exposed barrel length measure-
ment must be taken from the face of
the sprinkler fitting to the surface of the
structure or insulation that is exposed
to the heated area. Refer to Figure 11
for an example.
For protected area temperatures
between those given above, the
minimum recommended length from
the face of the fitting to the outside of
the protected area may be determined
by interpolating between the indicated
values.
Clearance Space
In accordance with Section 8.4.9.2
of the 2010 edition of NFPA 13, when
connecting an area subject to freezing
and an area containing a wet pipe
sprinkler system, the clearance space
around the sprinkler barrel of Dry-Type
Sprinklers must be sealed. Due to
temperature differences between two
areas, the potential for the formation
of condensation in the sprinkler and
subsequent ice build-up is increased. If
this condensation is not controlled, ice
build-up can occur that might damage
the dry-type sprinkler and/or prevent
proper operation in a fire situation.
Use of the Model DSB-2 Dry Sprinkler
Boot, described in technical data sheet
TFP591 and shown in Figures 14 and
15, can provide the recommended seal.
TFP500
Page 6 of 10
RUN
OUTLET
PLUGGED
SPRINKLER
FITTING TO DRY (SEE DESIGN SYSTEM CRITERIA
SECTION)
rr I
INTENDED
FOR FREEZER I STRUCTURES
FIGURE 12
SPRINKLER FITTING
- UNHEATED AREA -
FACE OF
SPRINKLER - -
FITTING
.
' EXPOSURE
LENGTH
(SEE DESIGN
DSB-2 CRITERIA
INTENDED SECTION)
FOR FREEZER
STRUCTURES
FIGURE 11
- EXPOSURE LENGTH -
TO WET SIDE
SYSTEM OUTLET
ri PLUGGED
mum )II1I1E1'
\
DSB-2 SPRINKLER
INTENDED FITTING
FOR FREEZER (SEE DESIGN
STRUCTURES CRITERIA
SECTION)
FIGURE 13
SPRINKLER FITTING
- HEATED AREA -
STRAP TIES
OPPOSING
SIDES OF
(ENDS ON
BOOT)
J ADHESIVE
_--DSB-2 BOOT ( DIA.
(44,5 mm)
CLEARANCE
HOLE
INSULATED
FREEZER
STRUCTURE
DS-1
SHOWN WITH
STANDARD
ESCUTCHEON
FIGURE 14
MODEL DSB-2 DRY SPRINKLER
BOOT WITH PENDENT SERIES
DS-1 DRY-TYPE SPRINKLER
1-3/4 DIA.
(44,5 mm)
CLEARANCE INSULATED HOLE FREEZER
ADHESIVE STRUCTURE
BOOT
STRAP TIES DS-1 (ENDS ON SHOWN WITH OPPOSING STANDARD SIDES OF ESCUTCHEON BOOT)
FIGURE 15
MODEL DSB-2 DRY SPRINKLER
BOOT WITH SIDEWALL SERIES
DS-1 DRY-TYPE SPRINKLER
TFP500
Page 7 of 10
Installation
TYCO Series DS-1 Dry-Type Sprinklers
must be installed in accordance with
the following instructions.
NOTICE
Series 'DS-1 Dry-Type Sprinklers must
only• be installed in fittings that meet
the requirements of the Design Criteria
section. Refer to the Design Criteria
section for other important require-
ments regarding piping design and
sealing of the clearance space around
the Sprinkler Casing.
Do not install any bulb type sprinkler if
the bulb is cracked or there is a loss of
liquid from the bulb. With the sprinkler
held horizontally, a small air bubble
should be present. The diameter of the
air bubble is approximately 1/16 inch
(1,6 mm) for the 135°F (57°C) rating to
1/8 inch (3,2 mm) for the 360°F (182°C)
rating.
Obtain a leak-tight 1-inch NPT sprinkler
joint by applying a minimum-to-
maximum torque of 20 to 30 ft. lbs.
(26,8 to 40,2 Nm). Higher levels of
.torque may distort the sprinkler Inlet
with consequent leakage or impairment
of the sprinkler.
Do not attempt to compensate
for insufficient adjustment in an
Escutcheon Plate by under or over-
tightening the Sprinkler. Re-adjust the
position of the sprinkler fitting to suit.
Install pendent sprinklers only in
the pendent position; install upright
sprinklers only in the upright posi-
tion. The deflector of a pendent or
upright sprinkler is to be parallel to
the ceiling.
Install horizontal sidewall sprinklers
in the horizontal position with their
centerline of waterway perpendic-
ular to the back wall and parallel to
the ceiling. Ensure the word "TOP"
on the Deflector faces the ceiling.
With a non-hardening pipe-thread
sealant such as Teflon applied to
the Inlet threads, hand-tighten the
sprinkler into the sprinkler fitting.
Wrench-tighten the sprinkler using
either:
a pipe wrench on the Inlet Band or
the Casing (Figure 1).
the W-Type 7 Sprinkler Wrench on
the Wrench Flat (Figure 2).
Apply the Wrench Recess of the
W-Type 7 Sprinkler Wrench to the
Wrench Flat.
Note: If sprinkler removal becomes
necessary, remove the sprinkler
using the same wrenching method
noted above. Sprinkler removal
• is easier when a non-hardening
sealant was used and torque guide-
lines were followed. After removal,
inspect the sprinkler for damage.
4. After installing the ceiling or wall and
applying a ceiling finish, slide on the
outer piece of the Escutcheon until
it comes in contact with the ceiling!
wall. Do not lift the ceiling panel out
of its normal position.
When using the Deep Escutcheon,
hold the outer piece in contact with
the mounting surface (ceiling or
wall). Then rotate the inner piece
approximately 1/4 turn with respect
to the outer piece, to hold the Deep
Escutcheon firmly together.
Care and
Maintenance
TYCO Series DS-1 Dry-Type Sprinklers
must be maintained and serviced
in accordance with the following
instructions.
NOTICE
Before closing a fire protection system
main control valve for maintenance
work on the fire protection system
that it controls, obtain permission to
shut down the affected fire protection
systems from the proper authorities
and notify all personnel who may be
affected by this action.
Absence of the outer piece of an
escutcheon, which is used to cover a
clearance hole, may delay the time to
sprinkler operation in a fire situation.
A Vent Hole is provided in the Bulb Seat
(Figure 1) to indicate if the Dry Sprinkler
is remaining dry. Evidence of leakage
from the Vent Hole indicates potential
leakage past the Inlet seal and the need
to remove the sprinkler to determine
the cause of leakage; for example, an
improper installation or an ice plug.
Close the fire protection system control
valve and drain the system before
removing the sprinkler.
Exercise care to avoid damage before,
during, and after installation. Never
paint, plate, coat, or otherwise alter
automatic sprinklers after they leave
the factory.
Never, repaint factory-painted Cover,
Plates'. When" necessary, replace
cover plates with factory-painted
units. Non-factory applied paint can
adversely delay or prevent sprinkler
operation in the event of a fire.
Replace sprinklers that:
were damaged by dropping, striking,
wrench twisting, wrench slippage, or
the like.
were modified or over-heated.
have cracked bulbs or have lost liquid
from the bulbs. Refer to the Installation
Section in this data sheet.
are leaking or exhibiting visible signs
of corrosion.
Responsibility lies with owners for the
inspection, testing, and maintenance of
their fire protection system and devices
in compliance with this document, as
well as with the applicable standards of
the National Fire Protection Association
(for example, NFPA 25), in addition to
the standards of any other Authorities
Having Jurisdiction. The installing
contractor or sprinkler manufacturer
should be contacted relative to any
questions.
Automatic sprinkler systems are recom-
mended to be inspected, tested, and
maintained by a qualified Inspection
Service in accordance with local
requirements and/or national codes.
DuPont Registered Trademark
TFP500
Page 8 of 10
15
Limited
Warranty
Products manufactured by Tyco Fire
Suppression and Building Products
(TFSBP) are warranted solely to the
original Buyer against defects in
material and workmanship when paid
for and properly installed and main-
tained under normal use and service.
This warranty will expire twelve (12)
months from installation or eighteen
(18) months from delivery, whichever
occurs first. No warranty is given for
products or components manufac-
tured by companies not affiliated by
ownership with TFSBP or for products
and components which have been
subject to misuse, improper instal-
lation, corrosion, or which have not
been installed, maintained, modified
or repaired in accordance with appli-
cable Standards of the National Fire
Protection Association, and/or the
standards of any other Authorities
Having Jurisdiction. Materials found by
TFSBP to be defective shall be either
repaired or replaced, at TFSBP's sole
option. TFSBP neither assumes, nor
authorizes any person to assume for
it, any other obligation in connection
with the sale of products or parts of
products. TFSBP shall not be respon-
sible for sprinkler system design errors
or inaccurate or incomplete infor-
mation supplied by Buyer or Buyer's
representatives.
In no event shall TFSBP be liable, in
contract, tort, strict liability or under
any other legal theory, for incidental,
indirect, special or consequential
damages, including but not limited to
labor charges, regardless of whether
TFSBP was informed about the possi-
bility of such damages, and in no
event shall TFSBP's liability exceed an
amount equal to the sales price.
The foregoing warranty is made in lieu
of any and all other warranties, express
or implied, including warranties of
merchantability and fitness for a partic-
ular purpose.
This limited warranty sets forth the
exclusive remedy for claims based
on failure of or defect in products,
materials or components, whether the
claim is made in contract, tort, strict
liability or any other legal theory.
This warranty will apply to the full
extent permitted by law. The invalidity,
in whole or part, of any portion of this
warranty will not affect the remainder.
Ordering
Procedure
Contact your local distributor for avail-
ability. When placing an order, indicate
the full product name, including
description and Part Number (PIN).
Dry Sprinklers
When ordering 5.6 K-Factor Series
DS-i, Standard Response , Standard
Coverage (5 mm Bulb), Dry-Type
Automatic Sprinklers, specify the
following information:
Model/SIN
Pendent TY3255, Upright TY3155, or
Horizontall Sidewall TY3355
Deflector Style
Order Length
Dry-Type Sprinklers are furnished
based upon Order Length as
measured per Figures 3 through 10,
as applicable. After the measurement
is taken, round it to the nearest 1/4
inch increment.
Inlet Connections
i-irch NPT or ISO 7-R1
Temperature Rating
Sprinkler Finish
Escutcheon Style and Finish, as
applicable
Part Number from Table B. Part
numbers are for i-inch NPT standard
order sprinklers. Orders for all other
sprinkler assemblies must be accom-
panied by a complete description.
Sprinkler Wrench
Specify W-Type 7 Sprinkler Wrench,
P/N 56-850-4-001.
Sprinkler Boot
Specify Model DSB-2 Dry Sprinkler
Boot, P/N 63-000-0-002. This Part
Number includes one Boot, two Strap
Ties, and 1/3 oz. of Adhesive (a suffi-
cient quantity for installing one boot).
TFP500
Page 9 of 10
1
P/N* 60
— XXX — X - XXX
MODEUSIN SPRINKLER ESCUTCHEON
FINISH FINISH (1)
96 Pendent with Standard TY3255 1 NATURAL BRASS WHITE
—
Escutcheon (1 " NPT) (Figure 3)
Pendent with Deep TY3255 4 WHITE POLYESTER WHITE Escutcheon (1' NPT) (Figure 5)
97 Pendent with Standard TY3255 9 CHROME PLATED CHROME Recessed Escutcheon (1" NPT) (Figure 4)
92 Pendent without
Escutcheon (1" NPT)
1Y3255
(Figure 6) 0 CHROME PLATED WHITE
_F 2 NATURAL BRASS BRASS PLATED
94 Sidewall with Standard TY3355
Escutcheon (V NPT) (Figure 8)
53 Sidewall with Deep TY3355
Escutcheon (1" NPT) (Figure 9)
54 Sidewall without TY3355
Escutcheon (1° NPT) (Figure 10)
0 135°F (57°C)
98 Upright without TY3155 1 155°F (68°C) Escutcheon (1° NPT) (Figure 7)
2 175°F (79°C)
Notes 3 200°F (93°C)
* Use Prefix "I" for ISO 7-R1 Connection; for example,
1-60-961-1-180). 4 286-F (141-C)
1. Escutcheon Finish applies to sprinklers provided with
escutcheons. 5 360°F (182°C)
O ',Qc°c (1fl1°C'\ ..,,l '(l° u100°(' +,m,+, -
055 5.50"
082 8.25"
180 18.00"
187 18.75"
372 37.25"
480 48.00'
TEMPERATURE ORDER
RATING (2) LENGTH (3)
UI tA flJIJ I IJ. '1.1/ t.—H—. o afr,JIy
to non-recessed sprinkler assemblies.
3. Dry-Type Sprinklers are, furnished based upon "Order
Length" as measured per Figures 3 through 10, as appli-
cable, and for each individual sprinkler where it is to be
installed. After the measurement is taken, round it to the
nearest 1/4 inch increment.
TABLE C
SERIES DS- I STANDARD RESPONSE, STANDARD COVERAGE, DRY-TYPE SPRINKLERS
— PART NUMBER SELECTION —
Copyright 0 2007, 2011 Tyco Fire Suppression & Building Products. All rights reserved.
W
Contacts
orldwide www.tyco4ire.com
Series TY-FRB, 56 K-factor
Upright, Pendent, and Recessed Pendent Sprinklers
Quick Response, Standard Coverage :
General
Description
The TYCO Series TY-FRB, 5.6 K-factor,
Upright (TY313) and Pendent (1Y323)
Sprinklers described in this data sheet
are quick response, standard coverage,
decorative 3 mm glass bulb-type spray
sprinklers designed for use in light or
ordinary hazard, commercial occupan-
cies such as banks, hotels, and shop-
ping malls.
-The recessed version of the Series TY-
FRB Pendent Sprinkler, where applica-
ble, is intended for use in areas with a
-finished ceiling. This recessed pendent
sprinkler uses one of the following:
A two-piece Style 15 Recessed
Escutcheon with recessed adjust-
ment up to 5/8 inch (15,9 mm) from
the flush pendent position.
A two-piece Style 20 Recessed
Escutcheon with recessed adjust-
ment up to 1/2 inch (12,7 mm) from
the flush pendent position.
The adjustment provided by the
Recessed Escutcheon reduces the
accuracy to which the fixed pipe drops
to the sprinklers must be cut.
Intermediate level versions of Series
TY-FRB Sprinklers are described in
Technical Data Sheet TFP357. Sprin-
kler guards and shields are described
in Technical Data Sheet TFP780.
IMPORTANT
Always refer to Technical Data
Sheet TFP 700 for the "INSTALLER
WARNING" that provides cautions
with respect to handling and
installation of sprinkler systems and
components. Improper handling and
installation can permanently damage
a sprinkler system or its components
and cause the sprinkler to fail to
operate in a fire situation or cause it
to operate prematurely.
Page 1 of 4
NOTICE
The TYCO Series TY-FRB Sprinklers
described herein must be installed and
maintained in compliance with this doc-
ument, as well as with the applicable
standards of the National Fire Protec-
tion Association, in addition to the stan-
dards of any other authorities having
jurisdiction. Failure to do so may impair
the performance of these devices.
The owner is responsible for maintain-
ing their fire protection system and
devices in proper operating condition.
The installing contractor or sprinkler
manufacturer should be contacted with
any questions.
Sprinkler
Identification
Number (SIN)
TY313 .......Upright 5.6K, 1/2 NPT
TY323 ......Pendent 5.6K, 1/2 NPT
Technical
Data
Approvals
UL and C-UL Listed
FM and VdS Approved
CE Certified
Maximum Working Pressure
175 psi (12.1 bar)
250 psi (17.2 bar)*
* The maximum working pressure of 250 psi
(17.2 bar) only applies to the listing by Un-
derwriters Laboratories, Inc. (UL).
Discharge Coefficient
K=5.6 GPM/ps11/2 (80,6 LPM/bar112)
Temperature Rating
135°F (57°C)
155°F (68°C)
175°F (79°C)
200°F (93°C)
286°F (141°C)
JANUARY 2013
Finishes
Sprinkler: Natural Brass, Chrome
Plated, Pure White (RAL 9010) and
Signal White (RAL 9003).
Recessed Escutcheon: White Coated,
Chrome Plated, or Brass Plated
Physical Characteristics
Frame ...................Bronze
Button..............Brass/Copper
Sealing Assembly .........Stainless
Steel w/TEFLON
Bulb ......................Glass
Compression Screw........Bronze
Deflector.................Bronze
TFPI72
TFPI72
Page 2 of 4
Components * Temperature rating is .**:Pipe thread connections per ISO 7-1 1 - Frame 4 - Bulb indicated on Deflector, can be provided on special request. 2 - Button 5 - Compression
3 - Sealing Screw ESCUTCHEON PLATE 1/2 7/16' (11,1 mm)
Assembly 6 - Deflector* DEFLECTOR * SEATING SURFACE NPT** NOMINAL MAKE-IN
STYLE 15 or 20
RECESSED
ESCUTCHEON
NOMINAL
(50,m
i:v
(50,8 mm)
WRENCH
L FLATS
1 1/2" NPT** DEFLECTOR* 2-7/8 (73,0 mm) DIA.
CROSS SECTION UPRIGHT PENDENT RECESSED PENDENT
FIGURE 1
SERIES TY-FRB UPRIGHT (Y313) AND PENDENT (TY323) SPRINKLERS
5.6 K-FACTOR, 112 INCH NPT, QUICK RESPONSE
Operation
The glass bulb contains a fluid which
expands when exposed to heat. When
the rated temperature is reached, the
fluid expands sufficiently to shatter the
glass bulb, allowing the sprinkler to
activate and water to flow.
Design
Criteria
The TYCO Series TY-FRB, 5.6 K-factor,
Upright (TY313) and Pendent (TY323)
Sprinklers are intended for fire protec-
tion systems designed in accordance
with the standard installation rules rec-
ognized by the applicable Listing or
Approval agency (such as, UL Listing
is based on the requirements of NFPA
13, and FM Approval is based on the
requirements of FM's Loss Prevention
Data Sheets). Only the Style 15 or Style
20 Recessed Escutcheon is to be used
for recessed pendent installations.
Installation
The TYCO Series TY-FRB, 5.6 K-factor,
Upright (TY313) and Pendent (TY323)'
Sprinklers must be installed in accor-
dance with this section.
General Instructions
Do not install any bulb-type sprinkler if
the bulb is cracked or there is a loss
of liquid from the bulb. With the sprin-
kler held horizontally, a small air bub-
ble should be present. The diameter
of the air bubble is approximately 1/16
inch (1,6 mm) for the 135°F (57°C) and
3/32 inch (2,4 mm) for the 286°F (141°C)
temperature ratings.
A leak-tight 1/2 inch NPT sprinkler joint
should be obtained by applying a min-
imum to maximum torque of 7 to 14
ft.-lbs. (9,5 to 19,0 Nm). Higher levels
of torque can distort the sprinkler Inlet
with consequent leakage or impairment
of the sprinkler.
Do not attempt to compensate for
insufficient adjustment in the Escutch-
eon Plate by under- or over-tightening
the sprinkler. Re-adjust the position of
the sprinkler fitting to suit.
Upright and Pendent Sprinklers
The Series TY-FRB Upright and Pen-
dent Sprinklers must be installed
in accordance with the following
instructions.
Step 1. Install Pendent sprinklers in the
pendent position. Install upright sprin-
klers in the upright position.
Step 2. With pipe-thread sealant
applied to the pipe threads, hand-
tighten the sprinkler into the sprinkler
fitting.
WRENCH RECESS
(USE ONLY
FIGURE 2
W- TYPE 6
SPRINKLER WRENCH
WRENCH
RECESS
PUSH WRENCH
IN TO ENSURE
ENGAGEMENT
WITH SPRINKLER
WRENCHING AREA
FIGURE 3
W- TYPE 7 RECESSED
SPRINKLER WRENCH
TFPI72
Page 3 of 4
Step 3. Tighten the sprinkler into the
sprinkler fitting using only the W-Type
6 Sprinkler Wrench (Figure 2). With ref-
erence to Figure 1, apply the W-Type 6
Sprinkler Wrench to the wrench flats.
Torque sprinklers 7 to 14 ft.-lbs. (9,5 to
19,0 Nm).
Recessed Peñdent Sprinklers
The, Series TY-FRB Recessed Pendent
Sprinklers must be installed in accor-
dance with the following instructions.
Step A. After installing the Style 15 or
Style 20 Mounting Plate over the sprin-
kler threads, and with pipe-thread
sealant applied to the pipe threads,
hand-tighten the sprinkler into the
sprinkler fitting.
Step B. Tighten the sprinkler into the
sprinkler fitting using only the W-Type
7 Recessed Sprinkler Wrench (Figure
3). With reference to Figure 1, apply the
W-Type 7 Recessed Sprinkler Wrench
to the sprinkler wrench flats. Torque
sprinklers 7 to 14 ft.-lbs. (9,5 to 19,0
Nm).
Step C. After ceiling installation and fin-
ishing, slide on the Style 15 or Style 20
Closure over the Series TY-FRB Sprin-
-kler and push the Closure over the
Mounting Plate until its flange comes in
contact with the ceiling.
Care and•
Maintenance
The TYCO Series TY-FRB, 5.6 K-factor,
Upright (TY313) and Pendent (TY323)
Sprinklers must be maintained and ser-
viced in accordance with this section.
Before closing a fire protection system
main control valve for maintenance
work on the fire protection system
that it controls, obtain permission to
shut down the affected fire protection
systems from the proper authorities
and notify all personnel who may be
affected by this action.
Absence of the outer piece of an
escutcheon, which is used to cover
a clearance hole, can delay sprinkler
operation in a fire situation.
The owner must assure that the sprin-
klers are not used for hanging any
objects and that the sprinklers are only
cleaned by means of gently dusting
with a feather duster; otherwise, non-
operation in the event of a fire or inad-
vertent operation may result.
Sprinklers which are found to be leak-
ing or exhibiting visible signs of corro-
sion must be replaced.
Automatic sprinklers must never be
painted, plated, coated, or other-
wise altered after leaving the factory.
Modified sprinklers must be replaced.
Sprinklers that have been exposed to
corrosive products of combustion, but
have not operated, should be replaced
if they cannot be completely cleaned
by wiping the sprinkler with a cloth or
by brushing it with a soft bristle brush.
Care must be exercised to avoid dam-
age to the sprinklers - before, during,
and after installation. Sprinklers dam-
aged by dropping, striking, wrench
twist/slippage, or the like, must be
replaced. Also, replace any sprinkler
that has a cracked bulb or that has lost
liquid from its bulb. (Ref. Installation
Section.)
The owner is responsible for the
inspection, testing, and maintenance of
their fire protection system and devices
in compliance with this document, as
well as with the applicable standards
of the National Fire Protection Associa-
tion (e.g., NFPA 25), in addition to the
standards of any other authorities hav-
ing jurisdiction. Contact the installing
contractor or sprinkler manufacturer
regarding any questions.
Automatic sprinkler systems are rec-
ommended to be inspected, tested,
and maintained by a qualified Inspec-
tion Service in accordance with local
requirements and/or national codes.
27/8 DlA
(73,0 mm)
2-1/4 DIA.
FACE OF (57,2 mm)
SPRINKLER
FITTING 5/8 (15,9 mm)
\ _l FLUSH
3/8±5/16"
i
I
(9,5±7,9 mm)
I L
MOUNTING
SURFACE N - \(3,2 mm)
CLOSURE SERIES MOUNTING 1-3/8 (34.9 mm)
TYFRB PLATE 3/4' (19,1 mm)
FIGURE 4
SERIES TY-FRB RECESSED PENDENT SPRINKLER ASSEMBLY (TY323)
WITH TWO PIECE 5/8 INCH TOTAL ADJUSTMENT STYLE 15
RECESSED ESCUTCHEON
- 2-7/8 DIA.
(73,0 mm)
FACE OF
SPRINKLER 2-1/4 DIA.
FITTING (57,2 mm)
5/16±1/4' 1/2 (12,7 mm) (7.9±6,4 mm) FLUSH
1/8 J MOUNTING \ SURFACE (3,2 mm)
/
CLOSURE SERIES MOUNTING 1-3/8' (34,9 mm)
TY.FRB PLATE 7/8' (22,2 mm)
FIGURE 5
SERIES TY-FRB RECESSED PENDENT SPRINKLER ASSEMBLY (TY323)
WITH TWO PIECE 1/2 INCH TOTAL ADJUSTMENT STYLE 20
RECESSED ESCUTCHEON
TFPI72
Page 4 of 4
PIN* 77 - XXX - X - XXX
SPRINKLER TEMPERATURE
FINISH RATINGS
SIN
370 5.6K UPRIGHT (lIZ NPT) TY313
371 5.6K PENDENT (1/ZNPT) TY323
* Use suffix '1° for ISO 7-1 connection;
for example, 77-370-4-175-I
1 NATURAL BRASS
4 SIGNAL WHITE (RAL 9003)
3 PURE WHITE (RAL 9010)°°
9 CHROME PLATED
Eastern Hemisphere sales only
135 135°F (57°C)
155 155°F(68°C)
175 175°F(79°C)
200 200°F (93°C)
286 286°F (141°C)
TABLE A
SERIES TY-FRB UPRIGHT AND PENDENT SPRINKLERS
- PART NUMBER SELECTION -
Ordering•
Procedure
Contact your local distributor for avail-
ability. When placing an order, indicate
the full product name and Part Num-
ber (P/N).
Sprinkler Assemblies with NPT
Thread Connections
Specify: Series TY-FRB (SIN), K=5.6,
(Upright or Pendent) Sprinkler Quick
Response, (specify) temperature rat-
ing, (specify) finish, P/N (Table A).
Recessed Escutcheon
Specify: Style 15 Recessed Escutcheon
with (specify*) finish, P/N (specify*)
Specify: Style 20 Recessed Escutch-
eon with (specify*) finish, P/N (specify*)
* Refer to Technical Data Sheet TFP770.
Sprinkler Wrench
Specify: W-Type 6 Sprinkler Wrench,
P/N 56-000-6-387
Specify: W-Type 7 Sprinkler Wrench,
P/N 56-850-4-001
GLOBAL HEADQUARTERS 11400 Pennbrook Parkway, Lansdale, PA 19446 1 Telephone +1-215-362-0700
Copyright© 2013 Tyco Fire Products, LP. All rights reserved. *tqco TEFLON is trademark of The DuPont Corporation.
® J ILPCBI
SEE VICTAULIC PUBLICATION 10.01 FOR DETAILS AreLock® Cu1etT
STYLE 922.
The Style 922 outlet-T provides a convenient method of incorporating ½, '/~, and 1/15, 20
and 25mm outlets for directly connecting sprinklers, drop nipples, sprigs, gauges, drains and
other outlet products Available for 11A through 16 .1, mm/32 to 76.1 mm piping systems Style
922 outlets are UL/ULC Listed, 1-PCB and FM Approved for branch connections and VdS
Approved for direct sprinkler connection only on wet and dry systems.
The locating collar engages into the hole prepared in the pipe. When tightened, the assembly
compresses the gasket onto the OD of the pipe. The Style 922 Outlet-T is UL/FM rated up
to 300 psi/2068 kPa and VdS rated up to 16 bar at the ambient temperatures typical for fire
protection systems.
Style 922 is suitable for use on standard, lightwall, Schedule 5 and other specialty pipes. It is
supplied with a clear, rust inhibitive coating. Contact Victaulic for other optional coatings.
*Consult Section 10.01 for specific listings/approvals
MATERIAL SPECIFICATIONS Housing: Ductile iron conforming to ASTM A-536, grade 65-45-12. Ductile iron conforming to
ASTM A-395. grade 65-45-15, is available upon special request,
Gasket:
Grade "E" EPDM - Type A
(Violet color code). FireLock products have been Listed by Underwriters Laboratories Inc. and
Approved by Factory Mutual Research for wet and dry (oil free air) sprinkler services up to the
rated working pressure using the Grade "E" Type A Gasket System.
Bolts/Nuts: Heat-treated plated carbon steel, trackhead meeting the physical and chemical
requirements of ASTM A-449 and physical requirements of ASTM A-183.
JOB/OWNER CONTRACTOR ENGINEER
System No. Submitted By Spec Sect Para__________
Location Date Approved
Date________________________________
www.victaulic.com .
vic'rsuLlc IS REGISTERED TRADEMARK OF VICTAIJLIC COMPANY. © 2009 vICTAULIC COMPANY. ALL RIGHTS RESERVED, ictauliice
REVF 10.521
PS CARBON STEEL PPE HOLE CUT PRODUCTS 10.52
FreLock® OuUetT
STYLE 922 'r
DIMENSIONS
1.0
:
30.2 4)5 27.9 983 sb,O 0.50
30.2
K 1536 142 19 122 408 25o .2
302 36 895 31,0 1036 i 650 054
131116 1.40 1,95 122 4.08 256
302 35.6 495 31.0 103.6 650 0.58
'16 1.64 230 122 08 2.6 1.3
302 417 584 31.0 036 650 0.5°
1,46 1.66 210 1.46 4.60 256 3
30.2 42.2 35 6 37 116.8 650 0,29
1i4 64 219 146 460 256 1.4
30.2 417 35,6 371 I 68 65C 064
13/16 88 254 146 460 2.6 5
30.2 478 645 37.1 116.8 6°L 06e
1 191 244 5.40 256 '6
30.2 48,5 62.0 434 7.2 65.0 0.73
15,4 185 244 1.71 540 256 1.6
30.2 480 620 43.4 37.2 650 0.73
1-i' 2.13 279 '71 540 256 1.6
30.2 54, 703 433 '372 650 , , 073
13,11, 191 2.44 171 550 250 1.6
302 485 620 434 17 65.0 073
13/,6 189 244 1.71 550 236 16
30.2 48.0 620 434 139 / 65.0 073
1 7 3 2.79 11 5.50 1% 17
75 302 5'1 709 4.3.4 1397 650 080
i Vicrauhc female threaded products are designed to accommodate standard NPT or BSPT (optional)
male pipe threads only, Use of male threaded products with special features, such as probes, dry pen-
dent sprinklers, etc, should be yenned as suitable for use with this Victauhc product Failure to verify
suitabilitv ii advance may result in assembly problems or leakage.
*Center of un to engaged pipe end for NFTF threads (dimensions are approximate)
www.victaulic.com
-III./ic-tau I i VIcTAULIC 1S REGISTERED TRADEMARK OF vIcTAuLlc cOMPANY. © 2009 vicTAuLic COMPANY. ALL RIGHTS RESERVED.
1D522 RSVP
IPS CARBON STEEL PIPE - HOLE CU1PRODUCTS 10.52
FireLock® Outlet-l"
STYLE 922
PERFORMANCE Equivalent Len,
Run Size 1!1fll :tion 16,
8.5
2.6
8.5
2.6
8.5
SC 2, 2.6
65 25 2.6
IUrr 2 8.5
Hazen-Williams coefficient of friction is 120
www.victauIic.com
VICT.AIJLIC IS A REGISTERED TRADEMARK OF VICTALILIC COMPANY. © 29 VICTAULIC COMPANY. ALL RIGHTS RESERVED.
REV .F
xkct~~—U,5
10523
STYLE 922
INSTALLATION •.: : .. Reference should aiwaysbe made to the 1-100 Victaulic Field Installation Handbook for the product•
you are instalhng Handbooks are induced with each thiment of Victaulic products for complete
installation and assembly data and are available in PDF format on our website at www.victaulic.com.
WARRANTY Refer to the Warranty section of the current Price List or contact Victaulic for details.
NOTE This product shall be manufactured by Victaulic or to Victaulic specifications. All products to be
installed in accordance with current Victaulic installation/assembly instructions. Victaulic reserves the
right to change product specifications, designs and standard equipment without notice and without
incurring obligations.