HomeMy WebLinkAbout2386 FARADAY AVE; 105 | 110; FPC2021-0048; PermitPERMIT REPORT
('7city of
Carlsbad
Print Date: 08/12/2021
Job Address: 2386 FARADAY AVE, 4* 105 & 110,
Permit Type: FIRE-Construction Commercial
Parcel 4*: 2120621700
Valuation: $0.00
Occupancy Group:
#of Dwelling Units:
Bedrooms:
Bathrooms:
CARLSBAD, CA 92008-7222
Work Class: Fire Alarm
Track 4*:
Lot 4*:
Project 4*:
Plan 4*:
Construction Type:
Orig. Plan Check #:
Plan Check 4*:
Permit No: FPC2021-0048
Status: Closed - Finaled
Applied: 04/06/2021
Issued: 04/15/2021
Finaled Close Out: 08/11/2021
Inspector:
Final Inspection:
Project Title:
Description: WINGS RECOVERY -EXPAND EXISTING FIRE ALARM NOTIFICATION SYSTEM
Applicant:
LOW VOLTAGE INTEGRATED SYSTEMS
KYLE ARGUIJO
1090 JOSHUA WAY, #STEA
VISTA, CA 92081-7800
(760) 598-4110
FPContractor:
LOW VOLTAGE FIRE INC
1090 JOSHUA WAY, 4* UNIT A
VISTA, CA 92081-7800
(760) 598-4110
FEE AMOUNT
FIRE TI Fire Alarm System $620.00
Total Fees: $620.00 Total Payments To Date: $620.00 Balance Due: $0.00
Fire Department Page 1 of 1
1635 Faraday Avenue, Carlsbad CA 92008-7314 I 760-602-4665 1 760-602-8561 f I www.carlsbadca.gov
Ffc lo 2 I - D(A
FIRE ALARM SYSTEM
SUBMITTAL
L w~itczg :
i n t 4a g r ci t $ y S t rn s
FIRE ALARM S SOUNDS DATA S MEDIA S SECURITYS CCTV S ACCESS CONTROL
SUBMITTAL
Wings Recovery STE#105& 110
2386 Faraday Ave.,
Carlsbad, CA 92008
LOW VOLTAGE INTEGRATED SYSTEMS, INC.
1090 Joshua Way Ste A
VISTA, CA 92081
(760) 598-4110 Phone
(760) 598-4107 Fax
info@sdlvis.com
License: C10, C16 # 791832
Lo wVolrae ntcgrated sys to m s
g
PHONE: (760) 598-4110
FAX: (760) 598-4107
MATERIAL LIST
PART DESCRIPTION MANUFACTURER
PC2WL HORN/STROBE @ CEILING SYSTEM SENSOR
SCWL STROBE @ CEILING SYSTEM SENSOR
Low Voltage Integrated Systems, Inc.
1090 Joshua Way, Ste A • Vista, California 92081
FIRE • SECURITY • CCTV • ACCESS CONTROL • SOUND • MEDIA
LICENSE NO. C10, C16#791832
email: info @ sdlvis.com
SYSTEM
$ SENSOR
Indoor Selectable-
Output Strobes and
Horn Strobes for
Ceiling Applications
System Sensor L -Series audible visible notification
products are rich with features guaranteed to cut
installation times and maximize profits with lower
current draw and modern aesthetics.
Features
Plug-in design with minimal intrusion into the back box
Tamper-resistant construction
Automatic selection of 12- or 24-volt operation
at 15 and 30 candela
Field-selectable candela settings on ceiling units:
15, 30, 75, 95,115, 150, and 177
Horn rated at 88+ dBA at 16 volts
Rotary switch for horn tone and two volume selections
Universal mounting plate for ceiling units
Mounting plate shorting spring feature checks wiring continuity
before device installation
Electrically Compatible with legacy SpectrAlert and SpectrAlert
Advance devices
Compatible with MDL3 sync module
Listed for ceiling mounting only
The System Sensor L-Series ofrers the most versatile and
easy-to-use line of horns, strobes, and horn strobes in the industry
with lower current draws and modern aesthetics. With white and red
plastic housings, wail and ceiling mount ng options, System Sensor
L-Series can meet virtually any application requirement.
The entire [-Series product line of ceiiing-mount strobes and horn
strobes include a variety of features that increase their application
versatility while simplifying installation. All devices feature a plug-in
design with minimal Intrusion into the sack box, making installations
fast and foolproof while virtually eliminat ng costly and time-
consuming ground faults.
To further simplify installation, the L-Series utilizes a universal
mounting plate so installers can mount tiem to a wide array of back
boxes. With an onbosrd shorting spring, installers can test wiring
continuity before the device is installed.
Installers can also easily adapt devices to a suit a wide range of
application requirements using field-selectable candela settings,
automatic selection o 12- or 24-volt cperation, and a rotary switch
for horn tones with two volume selections,
Agency Listings
SIGNALING
10
LISTED APPROVED
S5512 FM approved except 71251653:0504
S4011 tor ALERT models 7135-1653:0503
3057383
AVDS868-02 • 12/0112017 • Page 3
L-Series Specifications
General
L-Series ceiling-mount strobes and horn strobes shall mount to a standard 4 x 4 x 11/2-inch back box, 4-inch octagon back box, or double-
gang back box. Two-wire products shall also mount to a single-gang 2 x 4 x 17/8-inch back box. A universal mounting plate shall be used
for mounting ceiling and wall products. The notification appliance circuit wiring shall terminate at the universal mounting plate. Also, L-Series
products, when used with the Sync.Circuitr Module accessory, shall be powered from a non-coded notification appliance circuit output
and shall operate on a nominal 12 or 24 volts. When used with the Sync.Circuit Module, 12-volt-rated notification appliance circuit outputs
shall operate between 8.5 and 17.5 volts: 24-volt-rated notification appliance circuit outputs shall operate between 16.5 and 33 volts. Indoor
L-Series products shall operate between 32 and 120 degrees Fahrenheit from a regulated DC or full-wave rectified unfiltered power supply.
Ceiling strobes and horn strobes shall have field-selectable candela settings including 15, 30, 75, 95, 115, 150, and 177.
Strobe
The strobe shall be a System Sensor L-Series Model ______ listed to UL 1971 and shall be approved for fire protective service. The strobe
shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible
signaling appliances, flashing at 1 Hz over the strobe's entire operating voltage range. The strobe light shall consist of a xenon flash tube and
associated lens/reflector system.
Horn Strobe Combination
The horn strobe shall be a System Sensor L-Series Model listed to UL 1971 and UL 464 and shall be approved for fire protective
service. The horn strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act
requirements for visible signaling appliances, flashing at 1 Hz over the strobe's entire operating voltage range. The strobe light shall consist
of a xenon flash tube and associated lens/reflector system. The horn shall have two audibility options and an option to switch between a
temporal three pattern and a non-temporal (continuous) pattern. These options are set by a multiple position switch. The horn on horn strobe
models shall operate on a coded or non-coded power supply.
Synchronization Module
The module shall be a System Sensor Sync.Circuit model MDL3 listed to UL 464 and shall be approved for fire protective service. The module
shall synchronize L-Series strobes at 1 Hz and horns at temporal three. Also, while operating the strobes, the module shall silence the horns
on horn strobe models over a single pair of wires. The module shall mount to a 4 11/16 x 4 11/16 x 2 1/8-inch back box. The module shall also
control two Style V (class B) circuits or one Style Z (class A) circuit, The module shall synchronize multiple zones. Daisy chaining two or more
synchronization modules together will synchronize all the zones they control. The module shall not operate on a coded power supply.
Standard Operating Temperature 32°F to 120°F (0°C to 49°C)
Humidity Range 10 to 93% non-condensing
Strobe Flash Rate 1 flash per second
Nominal Voltage Regulated 12 VDC or regulated 24 DC/FWR1
Operating Voltage Range 8 to 17.5 V (12 V nominal) or 16 to 33 V (24 V nominal)
Operating Voltage Range (MDL3) 8.5 to 17.5V (12 V nominal) or 16.5 to 33 V (24V nominal)
Input Terminal Wire Gauge 12 to 18 AWG
Ceiling-Mount Dimensions (including lens) 6.8" diameter x 2.5" high (173 mm diameter x 64 mm high)
Ceiling-Mount Surface Mount Back Box Skirt Dimensions 6.9' diameter x 3.4' high (175 mm diameter x 86 mm high)
Notes:
1, Full Wave Rectified (FWR) voltage is a non-regulated, time-varying power source that is used on some power supply and panel outputs.
2. P, S, PC, and SC products will operate at 12 V nominal only for 15 and 30 cd.
AVDS868-02 • 12)01/2017 • Page 2
UL Current Draw Data
UL Max. Strobe Current Draw (MA RMS)
8-17.5 Volts 16-33 Volts 8-17.5 Volts 16-33 Volts
Candela DC DC FWR Sound Pattern dB DC DC FWR
Candela 15 87 41 60
Range 30 153 63 86
75 N/A 111 142
95 N/A 134 164
115 N/A 158 191
150 N/A 189 228
177 N/A 226 264
MS), Ceiling Horn Strobe Candela I
.-1Z5VbIts 16-33 Volts
Temporal High 39 44 54
Temporal Low 28 32 54
Non-Temporal High 43 47 54
Non-Temporal Low 29 32 54
3.1 KHz Temporal High 39 41 54
3.1 KHz Temporal Low 29 32 54
3.1 KHz Non-Temporal High 42 43 54
3.1 KHz Non-Temporal Low 28 29 54
Coded High 43 47 54
3.1 KHz Coded High 42 43 54
DC Input 15cd 30cd 15cd 30cd 75cd 95cd 1115cd 150cd 177cd
Temporal High 103 167 71 90 143 165 187 217 254
Temporal Low 96 165 54 71 137 161 185 211 249
Non-Temporal High 106 173 71 90 141 165 187 230 273
Non-Temportal Low 95 166 54 71 124 161 170 216 258
3.lKTemporal High 111 164 69 94 147 163184 229 257
3.lKTemporal Low 103 163 54 88 143 155 185 212 252
3.1 K Non-Temporal High 111 172 69 94 144 164 202 229 271
3.1K Non-Temporal Low 103 169 54 88 131 155 187 217 259
FWR Input
16-33 Volts
l5cd 30cd 75cd 95cd 1115cd 150cd 177cd
Temporal High 107 135 179 198 223 254 286
Temporal Low 78 101 151 172 199 229 262
Non-Temporal High 107 135 179 198 223 254 286
Non-Ternportal Low 78 101 151 172 199 229 262
3.1K Temporal High 108 135 179 200 225 255 289
3,lK Temporal Low 79 101 150 171 196 229 260
3.1K Non-Temporal High 108 135 179 200 225 255 289
3.1K Non-Temporal Low 79 101 150 171 196 229 260
Horn Strobe Tones and Sound Output Data
Horn Strobe Output (dBA)
8-17.5 16-33
Switch Volts Volts
Position Sound Pattern dB DC DC FWR
1 Temporal High 84 89 89
2 Temporal Low 75 83 83
3 Non-Temporal High 85 90 90
4 Non-Temporal Low 76 84 84
5 3.1 KHz Temporal High 83 88 88
6 3.1 KHz Temporal Low 76 82 82
7 3.1 KHz Non-Temporal High 84 89 89
8 3.1 KHz Non-Temooral Low 77 83 83
AVDS868-02 • 12/01/2017 • Page 3
2.47 (62.7 mm)
1.37 (34.8 mm) 6.92" diom
(175.
2.5
(64 mm)
L-Series Dimensions
A0545.00 A0546.00
Ceiling-Mount Horn Strobes Ceiling Surface Mount Back Box
-01 .01
2-Wire Ceiling Mount Horn Strobes 4-Wire Ceiling Mount Horn Strobes
with Ceiling Surface Mount Back Box with Ceiling Surface Mount Back Box
L-Series Ordering Information
Ceiling Horn Strobes Ceiling Strobes
PC2RL 2-Wire, Horn Strobe, Red SCRL Strobe, Red
PC2WL 2-Wire, Horn Strobe, White SCWL Strobe, White
PC4RL 4-Wire, Horn Strobe, Red SCWL-CLR-ALERT Strobe, White, ALERT
PC4WL 4-Wire, Horn Strobe, White Accessories
TRC-2 Universal Ceiling Trim Ring Red
TRC-2W Universal Ceiling Trim Ring White
SBBCRL Ceiling Surface Mount Back Box, Red
SBBCWL Ceiling Surface Mount Back Box, White
For a ceiling-listed horn-only device, see AVDS865 "Indoor Selectable-
Output Horns, Strobes, and Horn Strobes for Wall Applications".
4" SYSTEM 3825 Ohio Avenue • St. Charles, IL 60174
.SItJSO!? Phone: 800-SENSOR2 • Fax: 630-377-6495
@2017 System Sensor.
Product specifications subject to change w/lnout notice. V,sit oysterrmoenso1com
to Cu 0 t product formation, including the latest version of this data sheet, current 1 0
AVDS86S.02. 12/01/2017
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM
LISTING SERVICE
LISTING No. 7135-1653:0503 Page 1 of 2
CATEGORY: 7135--AUDIBLE DEVICES
LISTEE: System Sensor, Unincorporated Div of Honeywell Int'l lnc.3825 Ohio Ave, St. Charles, IL
60174
Contact: Megan Sisson (203) 484-6544 Fax (203) 484-7309
Email: megan.sisson@honeywell.com
DESIGN: System Sensor Indoor 2-wire and *4wire Models:
HWL, HRL, HGWL and HGRL Horns;
CHWL and CHRL Chimes;
P2RL, P2WL, P2GRL, P2GWL, P2RL-P, P2WL-P, P2RL-SP, P2WL-SP, *P4RL and *P4WL
Wall Horn Strobes;
PC2RL, PC2WL, *PC4RL and *PC4WL Ceiling Horn Strobes;
CHSRL and CHSWL Wall Chime Strobes;
CHSCRL and CHSCWL Ceiling Chime Strobes;
Wall Bezel Parts:
BZR-F, BZR-AL, BZR-AG, BZR-EV, BZR-P, BZR-SP, BZR-PG,
BZW-F, BZW-AL, BZW-AG, BZW-EV, BZW-P, BZW-SP, BZW-PG,
BZGR-F, BZGR-AL, BZGR-AG, BZGR-EV, BZGR-P, BZGR-SP, BZGR-PG,
BZGW-F, BZGW-AL, BZGW-AG, BZGW-EV, BZGW-P, BZGW-SP and BZGW-PG,
Ceiling Bezel Parts:
BZRC-F, BZRC-AL, BZRC-AG, BZRC-EV, BZRC-P, BZRC-SP, BZRC-PG,
BZWC-F, BZWC-AL, BZWC-AG, BZWC-EV, BZWC-P, BZWC-SP and BZWC-PG.
Color Lens:
LENS-A2, LENS-132, LENS-G2, LENS-R2, LENS-AC2, LENS-BC2, LENS-GC2 and
LENS-RC2.
WallTrim Rings:
*1R2 and *TR2W
CeilingTrim Rings:
*TRC2 and *TRC2W
Wall Surface Mounted Back Boxes:
SBBRL, SBBGRL, SBBWL and SBBGWL,
Ceiling Surface Mounted Back Boxes:
Revision 08-21-2017 dcc
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed
the test results and/or other data but does not make an independent verification of any claims. This listing is not
an endorsement or recommendation of the item listed. This listing should not be used to verify correct
operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other
Date Issued: July 01, 2020 Listing Expires June 30, 2021
Authorized By: DAVID CASTILLO,, M.E., F.P.E.
Fire Engineering Division
Listing No. 7135-1653:0503
Page 2 of 2
SBBCRL and SBBCWL
MP120KL 120 VAC Adapter Mounting Plate
Refer to listee's data sheet for detailed product description and operational considerations.
RATING: 12 VDC regulated and 24 VDC/FWR
INSTALLATION: In accordance with listee's printed installation instructions, NFPA 72, applicable codes &
ordinances and in a manner acceptable to the authority having jurisdiction.
MARKING: Listee's name, model number, electrical rating, and UL label.
APPROVAL: Listed as audible devices when used with separately listed compatible fire alarm control
units. Suitable for indoor use, wall or ceiling mounted. Authority having jurisdiction should be
consulted prior to installation. Refer to listee's Installation Instruction Manual for details.
Revision 08-21-2017 dcc
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed
the test results and/or other data but does not make an independent verification of any claims. This listing is not
an endorsement or recommendation of the item listed. This listing should not be used to verify correct
9V' operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other
Date Issued: July 01, 2020 Listing Expires June 30, 2021
Authorized By: DAVID CASTILLO,, M.E., F.P.E.
Fire Engineering Division
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM
LISTING SERVICE 0
LISTING No. 7125-1653:0504 Page 1 of 2
CATEGORY: 7125 -- FIRE ALARM DEVICES FOR THE HEARING IMPAIRED
LISTEE: System Sensor, Unincorporated Div of Honeywell Int'l Inc.3825 Ohio Ave, St. Charles, IL
60174
Contact: Megan Sisson (203) 484-6544 Fax (203) 484-7309
Email: megan.sissonhoneywell.com
DESIGN: System Sensor Indoor 2-wire Models:
SRL, SWL, SGRL, SGWL, SRL-P SWL-P, SRL-SP, SWL-CLR-ALERT and SWL-ALERT
Wall Strobes;
SCRL,JSCWLJand SCWL-CLR-ALERT Ceiling Strobes.
Wall Bezel Parts:
BZR-F, BZR-AL, BZR-AG, BZR-EV, BZR-P, BZR-SP, BZR-PG,
BZW-F, BZW-AL, BZW-AG, BZW-EV, BZW-P, BZW-SP, BZW-PG,
BZGR-F, BZGR-AL, BZGR-AG, BZGR-EV, BZGR-P, BZGR-SP, BZGR-PG,
BZGW-F, BZGW-AL, BZGW-AG, BZGW-EV, BZGW-P, BZGW-SP and BZGW-PG,
Ceiling Bezel Parts:
BZRC-F, BZRC-AL, BZRC-AG, BZRC-EV, BZRC-P, BZRC-SP, BZRC-PG,
BZWC-F, BZWC-AL, BZWC-AG, BZWC-EV, BZWC-P, BZWC-SP and BZWC-PG.
Color Lens:
LENS-A2, LENS-132, LENS-G2, LENS-R2, LENS-AC2, LENS-BC2, LENS-GC2 and
LENS-RC2.
Walllrim Rings:
TR2 and TR2W
CeilingTrim Rings:
TRC2 and TRC2W.
Wall Surface Mounted Back Boxes:
SBBRL, SBBGRL, SBBWL and SBBGWL,
Ceiling Surface Mounted Back Boxes:
SBBCRL and SBBCWL
Refer to listee's data sheet for detailed product description and operational considerations.
*Rev 04-04-19 gt
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed
the test results and/or other data but does not make an independent verification of any claims. This listing is not
an endorsement or recommendation of the item listed. This listing should not be used to verify correct
operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other
Date Issued: July 01, 2020 Listing Expires June 30, 2021
Authorized By: DAVID CASTILLO,, ME., F.P.E.
Fire Engineering Division
Listing No. 7125-1653:0504
Page 2 of 2
RATING: Regulated 12 VDC setting: 8-17.5 VDC
Regulated 24 VDCIfwr setting: 16-33 VDC
INSTALLATION: In accordance with listees printed installation instructions, NFPA 72, applicable codes &
ordinances and in a manner acceptable to the authority having jurisdiction.
MARKING: Listee's name, model number, electrical rating, and UL label.
APPROVAL: Listed as two wire strobe units used for synchronous application when used with separately
listed compatible fire alarm control units. Suitable for indoor use, vertical wall or horizontal
ceiling mounted. *Listed with software code, S05-0048-001 for low temperature
compensation. Authority having jurisdiction should be consulted prior to installation. Refer to
listees Installation Instruction Manual for details.
*Rev 04-04-19 gt
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed
the test results and/or other data but does not make an independent verification of any claims. This listing is not
an endorsement or recommendation of the item listed. This listing should not be used to verify correct
operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other
Date Issued: July 01, 2020 Listing Expires June 30, 2021
Authorized By: DAVID CASTILLO,, M.E., F.P.E.
Fire Engineering Division