HomeMy WebLinkAbout705 PALOMAR AIRPORT RD; 300; FPC2020-0103; PermitPERMIT REPORT
Ccity of
Carlsbad
Print Date: 01/25/2022
Job Address: 705 PALOMAR AIRPORT RD, #300,
Permit Type: FIRE-Construction Commercial
Parcel #: 2101001600
Valuation: $277,106.58
Occupancy Group:
#of Dwelling Units:
Bedrooms:
Bathrooms:
CARLSBAD, CA 92011-1060
Work Class: Fire Alarm
Track #:
Lot #:
Project #:
Plan #:
Construction Type:
Orig. Plan Check #:
Plan Check #:
Permit No: FPC2020-0103
Status: Closed - Finaled
Applied: 06/11/2020
Issued: 07/07/2020
Finaled Close Out: 08/17/2020
Inspector:
Final Inspection:
Project Title:
Description: AEROTEK - PROVIDE & INSTALL HORNS & STROBES THROUGHOUT SPACE (16 DEVICES & 1 NEW POWER SUPPLY)
FPContractor:
RIVER FIRE AND SECURITY INC
8920 ACTIVITY RD, # STE
SAN DIEGO, CA 92126-4458
(858) 752-6250
FEE AMOUNT
FIRE TI Fire Alarm System $620.00
Total Fees: $620.00 Total Payments To Date: $620.00 Balance Due: $0.00
Fire Department Page 1 of 1
1635 Faraday Avenue, Carlsbad CA 92008-7314 1 760-602-4665 760-602-8561 f I www.carlsbadca.gov
Frczoio o5
* S
•
SUBMITAL BOOK FOR:
AEROTEK
705 PALOMAR AIRPORT RD., STE. 300
CARLSBAD CA 92011
RIVER FIRE AND SECURITY
8920 ACTIVITY RD. STE. J
SAN DIEGO CA 92126
C 1 896646
CUTSHEETS AND CSFM LISTINGS FOR:
5495 POWER MODULE
HSWC HORN STROBE
5495
Honeywell
3 sllBT. KNIGHT
5495
Distributed Power Module
The 5495 Distributed Power Module is the most powerful and cost-
effective power supply available today. It delivers 6 amps of notification
appliance circuit power and built-in synchronization for appliances from
System Sensor',Gentex ', AMSECO ". and Wheelock. The 6495's switch
mode power SUpply design is up to 500/ more efficient than competitive
linear mode power supplies. Also, ADA retrofits are easier and less
expensive with the 5495 because it integrates into current systems
without the costly investment in new components.
The 5495 is a 6 amp notification power expander that provides its own AC
power connection, battery charging circuit, and backup battery. The 5495
is the costeffective solution for powering notification appliances required
by the Americans with Disabilities Act (ADA). The 5495 has built-in ANSI
cadence pattern, which can upgrade older control panels that lack
cadence capability.
CONNECTION TO LOCAL FIRE CONTROL
The 5495 may be connected to a local fire control which utilizes Class Aor
Class B type notification circuits operating between 9 and 32 VDC. The
control panel's notification circuit is connected to one of the inputs on the
5495. The control panel's notification circuit end-of-line resistor is also
connected across two terminals on the 5495, which provides supervision
between the 5495 and the fire control panel. Polarized audible and/or
visual notification devices are then connected to the 5495 signal circuits
using the 4,7kQ end-of-line resistors provided. Since the 5495 draws very
little power from the control, it is possible to connect one 5495 to each
notification circuit on the control panel and still provide full supervision of
the notification circuits all the way back to the control panel.
FEATURES & BENEF I TS
UL Listed for 6 amps
of notification power
Power supply's
advanced switch mode
design reduces
damaging heat and
manages power uo to
501)/o more efficenty
than other systems
Dip Switches allow for
easy reconfiguration
24VDC filtered output
voltage
Four power-limited
notification outputs; 2
Class A or 4 Class B, or
1 Class A and 2 Class
B
Additional continuous
auxiliary output
3 amps per output
circuit
2 inputs, 2 Class B or 2
Class A
Ground fault detector!
indicator
Independent trouble
relay
AC loss delay option
shut:.; off power to
non - essent a
high current
accessories like
magnetic door holders
Built-in Operates with most
synchronization for polarized. UL Listed
appliances from notification devices
System Sensor, ANSI Cadence pattern
Gentex , AMSECO, output capability and Wheelock
built-in
Stand alone operation
Lightweight design
adds to ease of
installation and
reduces shipping
costs
Model 5495 Block Diagram
Signal Circuit Output Signal 1 Signal I
Input
Signal Circuit Output S' 12 Distributed
Power
Module 5495
Signal 2
________ Signal 3
(Optional)
Signal
120 VAC Aux. Power
Trouble Output
Local Fire Control (Alternative to notification
circuit trouble.)
5495 Technical Specifications
SUPERVISION
The 5495 supervises a variety of functions
including:
Low AC power
Low battery condition
Earth ground fault
Auxiliary output power limit condition
EOL supervision trouble or power limited
condition at an output
When a trouble condition occurs, the 5495 creates
a trouble condition on the host control signal
circuits to which it is connected. the 5495 still
maintains the ability to be activated by the host
control. In addition, the 5495 provides a Form C
trouble relay output as an alternative to using the
notification circuit trouble.
PHYSICAL
Dimensions: 12.25W x 16H x 3D (30.88 cm VV x
40.64 cm H x 7.62 cm D)
ENVIRONMENTAL
Operating Temperature: 32°F to 120°F (0°C to
49°C)
Humidity: 10% - 93% non-condensing)
ELECTRICAL
AC input: 120 VAC at 24
Output: 24 VDC at 64
Current: Standby 75mA; Alarm 205m4
Auxiliary power circuit: 1
Notification circuits 4
Output configuration:2 Class A (Style Z): 4 Class B
(Style Y) (1 Class A & 2 Class B)
Amps per output circuit: 3.0(6.0 amps total)
Notification circuit output: Alarm Current (for
typical voltages) drawn from main panels
notification appliance circuits.
12 VDC 6.5 mA
24 VDC One input circuit: 15 mA: Both input
circuits: 0 mA
No. of inputs: 2
Input configuration: 2 Class B or 2 Class A
Input voltage range: 9- 32VDC
Battery charging capacity: 35.OAH
INDICATOR LIGHTS
AC power on: Green
Battery trouble: Yellow
Ground fault: Yellow
Aux trouble: Yellow
Output troubles (1-4): Yellow
ORDERING INFORMATION
5495: Distributed Power Module
ACCESSORIES
SK-SCK: Seismic Compliance Kit
AGENCY LISTINGS
DL listed
CSFM 7300-0559:123
Meets NFPA 72 requirements
MEA 429-92-E Vol Xli
OSHPD (CA) OSP-0065-10
For a complete listing of all
comoliance approvals and
certifications, please visit
www.silentknight.com.
Microsoft. Windows, and
the Windows Logo are
registered trademarks
or trademarks of
Microsoft Corporation.
System Sensor and
Honeywell are registered
trademarks of Honeywell
International, Inc
This document is not
intended to be used for
installation purposes. We
try to keep our product
information up-to
date and accurate. We
cannot cover all specific
applications or anticipate
all requirements. Ail
specifications are subject
to change without notice.
For Technical Support,
call 800-446-6444.
For more information
Learn more about Honeywell Silent Knight and other
products by visiting www.silentknight.com
Honeywell Silent Knight
12 Clintonville Road
Northford, CT 06472
800-323-0103
Doc 3503951 Rev HI 11/17
5)2017 Honeywell International Inc.
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM
LISTING SERVICE
LISTING No. 7300-0559:0123 Page 1 of 1
CATEGORY: 7300 - FIRE ALARM CONTROL UNIT ACCESSORIES/MISC. DEVICES
LISTEE: SILENT KNIGHT SECURITYOne Fire-Lite Place, Northford, CT 06472-1653
Contact: Megan Sisson (203) 484-6127 Fax (203) 484-7309
Email: megan.sissonhoneywell.com
DESIGN: Models 5395, *5495 and *5499 Distributed Power Module (Indicating Circuit Expander). Unit
is power-limited and consists of an enclosure, printed circuit board, terminal boards,
end-of-line resistors and two 12VDC, 7Ah rechargeable batteries. The unit provides up to 4
indicating zones and 1 auxiliary output. Refer to listee's data sheet for additional detailed
product description and operational considerations.
RATING: Input: 120 VAC, 2A, 60 h
Output: 24 VDC
INSTALLATION: In accordance with listee's printed installation instructions, applicable codes & ordinances
and in manner acceptable to the authority having jurisdiction. Unit must be able to provide 24
hour battery back-up as required per code.
MARKING: Listee's name, model number, electrical rating and UL label.
APPROVAL: Listed as indicating circuit expanders for use with separately listed compatible indicating
devices and polarized, 24 VDC, fire alarm control unit. Model 5495 and 5499 can generate a
distinctive temporal pattern fire alarm signal as required per NFPA 72, 2002 Edition. If
required, models 5395 must be use with fire alarm control unit or indicating signaling devices
that can produce the temporal code pattern. Refer to listee's Installation Manual for details.
NOTE:
Recert. 08-17-2006 jw
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed
the test results and/or other data but does not make an independent verification of any claims. This listing is not
an endorsement or recommendation of the item listed. This listing should not be used to verify correct
operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other
Date Issued: July 01, 2019 Listing Expires June 30, 2020
Authorized By: DAVID CASTILLO, Program Coordinator
Fire Engineering Division
- Save up to 48% in current draw*
- Up to 9 models now in 1 appliance
- Save up to 14% cost of installation**
&
A
Sleek Modern Aesthetics
Finger Slide Switches'
Voltage Test Points
Multiple Voltages
3 Audible Settings
90, 95, 99 dB
O 8 Candela Settings
Wall - 15/1575/30/75/95/110/135/185
Ceiling - 15/30/60/75/95/115/150/177
o Universal Mounting Base
cr
Ceiling and Wall
Mounts to 5 Backbox Types
COOPER Notification
EJWC~E~' Strobe, Horn Strobe, and Horn
Notification Appliances
Ceiling Wall
Description:
The Wheelocka ExcederTM Series of notification appliances feature
a sleek modem design that will please building owners with reduced
total cost of ownership. Installers will benefit from its comprehensive
feature list, including the most candela options in one appliance,
low current draw, no tools needed for setting changes, voltage test
points, 12/24 VDC operation, universal mounting base and multiple
mounting options for both new and retrofit construction.
The Wheelock® ExcederlM Series incorporates high reliability and
high efficiency optics to minimize current draw allowing for a greater
number of appliances on the notification appliance circuit. All strobe
models feature an industry first of 8 candela settings on a single
appliance. Models with an audible feature 3 sound settings (90, 95,
99 dB). All switches to change settings, can be set without the use
of a tool and are located behind the appliance to prevent tampering.
Wall models feature voltage test points to take readings with a
voltage meter for troubleshooting and AHJ inspection.
The Wheelock® ExcederTM Series of wall and ceiling notification
appliances feature a Universal Mounting Base (UMB) designed
to simplify the installation and testing of horns, strobes, and
combination horn strobes. The separate universal mounting
base can be pre-wired to allow full testing of circuit wiring before
the appliance is installed and the surface is finished. It comes
complete with a Contact Cover for protection against dirt, dust, paint
and damage to the contacts. The Contact Cover also acts as a
shunting device to allow pre-wire testing for common wiring issues.
The Contact Cover is polarized to prevent it from being installed
incorrectly and prevents the appliance from being installed while
it is on the UMB. When the Contact Cover is removed the circuit
will show an open until the appliance is installed. The UMB allows
for consistent installation and easy replacement of appliances if
required. Wall models provide an optional locking screw for extra
secure installation, while the ceiling models provide a captivated
screw to prevent the screw from falling during installation.
Environmentally Friendly
Low current Draw
Compatibility and Requirements
- Synchronize using the Wheelock Sync Modules or panels with built-in Wheelock Patented Sync Protocol
- Compatible with U L "Regulated Voltage" using filtered VDC or unfiltered VRMS input voltage
- Strobes produce 1 flash per second over the "Regulated Voltage" range
"Compared to competitive models "" Patented
""Compared to previous models
NOTE: All CAUTIONS and WARNINGS are identified by the symbol A. All warnings are printed in bold capital letters. A WARNING: PLEASE READ THESE SPECIFICATIONS AND ASSOCIATED INSTALLATION INSTRUCTIONS CAREFULLY BEFORE USING, SPECIFYING
OR APPLYING THIS PRODUCT. VISIT WWW.COOPERNOTIFICATION.COM OR CONTACT COOPER NOTIFICATION FOR THE CURRENT INSTALLATION
INSTRUCTIONS. FAILURE TO COMPLY WITH ANY OF THESE INSTRUCTIONS, CAUTIONS OR WARNINGS COULD RESULT IN IMPROPER APPLICATION,
INSTALLATION AND/OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD RESULT IN PROPERTY DAMAGE, AND
SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS.
Genera! Notes:
General Notes:
Strobes are designed to flash at I flash per second minimum over their Regulated Voltage Range.
All candela ratings represent minimum effective strobe intensity based on UL Standard 1971
Series Exceder Strobe products are Listed under UL Standards 1971 and 464 for indoor use with a temperature range of 32F to 120F (0C to 49C) and
maximum humidity of 93% (± 2%) UL464 (85% UL 1971).
Series Exceder horns are under UL Standard 464 for audible signal appliances (Indoor use only).
Horn Strobe Ratings per UL 1971 & Anechoic at 24VDC
UL Max Current* at Anechoic 99 dBA
24VDC 12VDC
Model Regulated Voltage
Range VDC 15 15/75 30 60 75 95 110 115 135 150 177 185 15 15/75
HS 8.0-33.0 0.082 0.095 0.102 0.148 0.176 0.197 0 21 0.282 0.125 0.159
HSC 8.0-33.0 0.082 . 0.102 0.141 0.148 0.176 .• 0.197 0.242 0.282 0.125
UL 1E l• I
24VDC 12VDC
Model Regulated Voltage
Range VDC 15 15/75 30 60 75 95 110 115 135 150 177 185 15 15/75
HS 80330 0.073 0.083 0.087 0.139 0.163 0.186 0230 0272 0.122 0.153
HSC 80330 0.073 0087 0U8 01 01 0.186 02 02 0U2 I •E Max Current* at Anechoic 90 dBA
24VDC - 12VDC
Model Regulated Voltage
Range VDC 15 15/75 30 60 75 95 110 115 135 150 177 185 15 15/75
HS 80330 -
0.065 0.075 0.084 0.136 0.157 0.184 0.226 0.267 0.120 0.148
HSC 80330 0.065 0.226
-
0.267 7770.1 2D
HornRatings per UL Anechoic
Model Regulated Voltage
Range VDC 99 dB 95 dB 90 dB
HN 16-33.0 0.064 0.044 0.022
HNC 16-33.0 0.084 0.044 0.022
HN 8.0-17.5 0.047 0.026 0.017
HNC 8.0-17.5 0.047 0.026 0.017
* UL max current rating is the maximum RMS current within the listed voltage range (16-33 VDC for 24 VDC units). For strobes the
UL max current is usually at the minimum listed voltage (16 VDC for 24 VDC units). For audibles the max current is usually at the
maximum listed voltage (33 VDC for 24 VDC units). For unfiltered ratings, see installation instructions.
Specification & Ordering Information
Sync WI
Model Strobe DSM or 12/24 VDC* Mounting
Candela Wheelock Power Options
Supplies
H 15/1575/30f75/9511101135/185 X X UMB**
HSW 15/157513017519511101135/185 X X UMB*
HSRC 15/30/60/75/95/115/150/177 X X UMB**
HSWC 15/30160175/95/115/150/177 X X UMB**
STR 1511575/30/75195/110(135/185 X X UMB*
STW 15/1575/30/75/95/110/135/185 X X UMB**
STRC 15/30/60/75/95/115/150/177 X X UMB**
ST\NC
:11111
15/30/60/75/951115/1501177 X X UMB**
HNR • X X UMB**
HNRC
HNW X
X
X UMB**
X UMB
HNWC 77 ME, X X UMB
NOTE: Due to continuous development of our products, specifications and offerings are subject to change without notice in accordance
with Cooper Wheelock Inc., dba Cooper Notification standard terms and conditions.
Architects and Engineers Specifications
The notification appliances shall be Wheelock Exceder Series HS Audible Strobe appliances, Series ST Visual Strobe appliances
and Series HN Audible appliances or approved equals. The Series HS and ST Strobes shall be listed for UL Standard 1971 (Emergency
Devices for the Hearing-Impaired) for Indoor Fire Protection Service. The Series HS and HN Audibles shall be UL Listed under Standard
464 (Fire Protective Signaling). All Series shall meet the requirements of FCC Part 15 Class B. All inputs shall be compatible with
standard reverse polarity supervision of circuit wiring by a Fire Alarm Control Panel (FACP) with the ability to operate from 8 to 33 VDC.
Indoor wall models shall incorporate voltage test points for easy voltage inspection.
The Series HS Audible Strobe and ST Strobe appliances shall produce a flash rate of one (1) flash per second over the Regulated
Voltage Range and shall incorporate a Xenon flashtube enclosed in a rugged Lexan® lens. The Series shall be of low current design.
Where Multi-Candela appliances are specified, the strobe intensity shall have 8 field selectable settings at 15, 15/75, 30, 75, 95, 110,
135, 185 candela for wall mount and 15, 30, 60, 75, 95, 115, 150, 177 candela for ceiling mount. The selector switch for selecting
the candela shall be tamper resistant. The 15/75 candela strobe shall be specified when 15 candela UL Standard 1971 Listing with
75 candela on-axis is required (e.g. ADA compliance). Appliances with candela settings shall show the candela selection in a visible
location at all times when installed.
The audible shall have a minimum of three (3) field selectable settings fordBA levels and shall have a choice of continuous or temporal
(Code 3) audible outputs.
The Series HS Audible Strobe, ST Strobe and Series HN Audible shall incorporate a patented Universal Mounting Base that shall allow
mounting to a single-gang, double-gang, 4-inch square, 3.5-inch octal, 4-inch octal or 100mm European type back boxes. Two wire
appliance wiring shall be capable of directly connecting to the mounting base. Continuity checking of the entire NAC circuit prior to
attaching any notification appliances shall be allowed. Product shall come with Contact Cover to protect contact springs. Removal of
an appliance shall result in a supervision fault condition by the Fire Alarm Control Panel (FACP). The mounting base shall be the same
base among all horn, strobe, horn strobe, wall and ceiling models. All notification appliances shall be backwards compatible.
The Series HS and ST wall models shall have a low profile measuring 5.24" H x 4.58W x 2.19' D. Series HN wall shall measure 5.24"
H x 4.58" W x 1.6" D. The Series HSC and SIC shall been round and have a low profile with a diameter of 6.68" x 2.63" D. Series
HNC ceiling shall have a diameter of 6.68" x 1.50" D.
When synchronization is required, the appliance shall be compatible with Wheelock's DSM Sync Modules, Wheelock® Power Supplies
or other manufacturer's panels with built-in Wheelock® Patented Sync Protocol. The strobes shall not drift out of synchronization at any
time during operation. If the sync protocol fails to operate, the strobe shall revert to a non-synchronized flash-rate and still maintain (1)
flash per second over its Regulated Voltage Range. The appliance shall also be designed so that the audible signal may be silenced
while maintaining strobe activation when used with Wheelock® synchronization protocol.
Wall Appliances - UL Standard 1971, UL Standard 464, California State Fire Marshal (CSFM), ULC, FM
Ceiling Appliances - UL Standard 1971, UL Standard 464, California State Fire Marshal (CSFM), ULC, FM
Member
WE ENCOURAGE AND SUPPORT NICET CERTIFICATION
3 YEAR WARRANTY
Exceder - Spec Sheet 6/11
Cooper Notification is Wheelock MEDCJ SAFEPATH WAVE
_?
?COOPER Notification
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM
LISTING SERVICE
LISTING No. 7125-0785:0168 Page 1 of 1
CATEGORY: 7125-- FIRE ALARM DEVICES FOR THE HEARING IMPAIRED
LISTEE: Cooper Wheelock Inc.7246 16th St. E., Ste. 105, Sarasota, FL 34243
Contact: Tom Conover (941) 487-2336
Email: thomas.conover@cooperindustries.com
DESIGN: Exceder Series: Models ST strobe, HS horn strobe and HN horn. Model ST is a synchronous
and non-synchronous strobe light. Model HS a visual/audible appliance and Model HN is an
audible signal appliance. All units followed by R (red) or W (white). Additionally, a 'C' may be
added for ceiling models and/or a '-NR' may be added for non-resettable models. For non
-NR models and optional 'S for silver fascia may be added*. Refer to listees data sheet for
additional detailed product description and operational considerations.
RATING: Electrical: 12 VDC/24VDCIFWR
Candela (wall)*: 15, 15/75, 30, 75, 95, 110, 135 & 185
Candela (ceiling)*: 15, 30, 60, 75, 95, 115, 150, & 177
INSTALLATION: In accordance with listee's printed installation instructions, applicable codes and ordinances
and in a manner acceptable to the authority having jurisdiction. All models are for indoor use
and for wall mount only or ceiling mount only*
MARKING: Listee's name, model number, electrical/candela rating, and UL label.
APPROVAL: Listed as horn for fire alarm signaling and strobe, horn/strobe for the hearing impaired when
used with separately listed electrically compatible fire alarm control units. Refer to Iistee 'S
Installation Instructions Manual for details.
*Rev. 9-24-09 fm
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed
the test results and/or other data but does not make an independent verification of any claims. This listing is not
an endorsement or recommendation of the item listed. This listing should not be used to verify correct
V* operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other
Date Issued: July 01, 2019 Listing Expires June 30, 2020
Authorized By: DAVID CASTILLO, Program Coordinator
Fire Engineering Division