HomeMy WebLinkAbout2910 JEFFERSON ST; ; AS160224; PermitCity of Carlsbad
Sprinkler Permit
Permit No: AS160224
2910 JEFFERSON
Job Address:
ST
Permit Type: SPRINK
Parcel No: 2033541300
Lot #: 0
Reference No.:
PC #:
Status: ISSUED
Applied 8/2/2016
Approved: 8/2/2016
Issued: 8/2/2016
Inspector:
Project Title: 2910 JEFFERSON BACKFLOW DEMO EXISTING SINGLE
DETECTOR CHECK VALVE & INSTALL NEW 4" WLKINS 375ADA
(RPDA) BACKFLOW PREVENTOR. RELOCATED EXISTING FDC
& WAFER CHECK VALVE.
Applicant:
COSCO FIRE PROTECTION
4990 GREEN CRAIG LN
SAN DIEGO, CA
858-444-2000
Owner:
BESAW FAMILY TRUST 10-21-01
34382 STARBOARD LANTERN
DANA POINT CA
Fees ($) Add'l Fees ($) Total ($) Balance ($)
445 0 445 0
San Diego Branch Office cosco 4990 Greencraig Lane ,.
San Diego, CA 92123 I s......
4-2000 fax: 444-2056 Fire Protection (858) 44
CA Lic.: C-16 #577621
www.coscoflre.com
MATERIAL SUBMITTAL &
HYDRAULIC
CALCULATIONS
Date: 6-27-16
2910 JEFFERSON
BACKFLOW
2910 JEFFERSON STREET
CARLSBAD, CA. 92008
JOB # 10.CD 5690
All material submitted, may be substituted
by material of equal performance & design, &
shall be deemed acceptable by purchaser.
AS 1 60224
Submitted by: HUGO A. 2910 JEFFERSON ST
Los Angeles 0 San Francisco 0 Orange 0 Fresno 0 San Diego 0 Seattle
U
ZURN Model 375ADA
WILKINS Reduced Pressure Detector Assembly
0
Application
Designed for installation on water lines in fire protection sys-
tems to protect against both backsiphonage and backpressure
of contaminated water into the potable water supply. The
Model 375ADA shall provide protection where a potential
health hazard exists. Incorporates metered by-pass to
detect leaks and unauthorized water use.
Standards Compliance
ASSE® Listed 1047 (2 1/2 - 8')
CSA® Certified B64.4 (2-1/2 - 8)
AWWA Compliant C550
UL® Classified
C-UL® Classified
FM® Approved
Approved by the Foundation for Cross Connection
Control and Hydraulic Research at the University of Southern
California.
NYC MEA 104-05-M
NSF® Listed-Standard 61, Annex G*
*(025% MAX. WEIGHTED AVERAGE LEAD CONTENT)
By-Pass Backflow Assembly 3/4" Model 975XLD
Materials
Main valve body Ductile Iron ASTM A 536 Grade 4
Access covers Ductile Iron ASTM A 536 Grade 4
Coatings FDA Approved fusion epoxy finish
Internals Stainless steel, 300 Series
NORYLTM, NSF Listed
Fasteners & Springs Stainless Steel, 300 Series
Elastomers EPDM (FDA approved)
Buna Nitrile (FDA approved)
Polymers NORYLTM, NSF Listed
Sensing line Stainless steel, braided hose
Features
Sizes: 2 1I2*, 3* 4", 6", 8", 10"
Maximum working water pressure 175 PSI Maximum working water temperature 140°F
Hydrostatic test pressure 350 PSI
End connections (Grooved for steel pipe) AWWA C606
(Flanged) ANSI B16.1
Class 125 *2 1/2" & 3" sizes use 4' body & reducer coupling
Dimensions & Weights (do not include pkg.)
WILKINS
Options (with OS&Y gates)
(Suffixes can be combined)
El - with OS & Y gate valves (standard)
E] L - less shut-off valves (grooved body con-
nections)
LM - less water meter
- with remote reading meter
- with gallon meter (standard)
- with cu ft/min meter
G - with groove end gate valves
El FG - with flanged inlet gate connection and
grooved outlet gate connection
MS - with Integral Relief Valve Monitor Switch
BG - with grooved end butterfly valves with
integral supervisory switches
El BF - with flanged end butterfly valves with
integral supervisory switches
L P1 - with Post Indicator Gate Valve
Accessories
0 Air gap (Model AG)
Repair kit (rubber only)
E] Thermal expansion tank (Model XT)
fl OS & Y Gate valve tamper switch (OSY-40) El QT-SET Quick Test Fitting Set
MODEL
375ADA with
standard OS&Y
WEIGHT MODEL WITHOUT WITH WITH 375ADA GATES WITH OS&Y WITH OS&Y BUTTERFLY BUTTERFLY SIZE GATES (GXF) GATES (GXG) VALVES VALVES
(GXG) (GXF)
in. Immlbs s jths ths Ibsj
21/2 65 112 50.8 214 97 206 93.5 154 70 164 74
380 111 50 23110&8 221 1003 156 7116977 41009845 252 114226 103 1 146 66 68 76
6 ThU Thi 69 387 176 357 162 225 102 255 116
200321 146 797 362 773 351 465 . 211 511 232
MODEL
375ADA With
BG option
Attention: Model 375ADA
(grooved body) and Model
375DA (flange body) have
different lay lengths.
MODEL 1 375ADA I I A WITH
SIZE I A I BUTTERFL'
VALVES
in. I mm I in. I mm I in. I mm
DIMENSION (apero
BLESS I I I l 6 I EWITH I GATE I c I c IoS&YEoPENI OS&Y I BUTTERFLY I VALVES I I I CLOSED I VALVES I
In. I mm I In. I mm I in. I mm I In. I mm I in. I mm I in. Imm I in.
Zurn Industries, LLC I Wilkins
1747 commerce Way, Paso Robles, CA U.S.A. 93446 Ph. 855-663-9876 Fax 805-238-5766
In Canada I Zurn Industries Limited
3544 Nashua Drive Mississauga, Ontario L4V 1L2 Ph. 905-405-8272, Fax 905-405-1292
www.zurn.com
Rev. E
Date: 10/15
Document No. BF-375ADA
Patent No. 5,913,331
Product No. Model 375ADA
Page 1 of 2
C
O Rated Flow (established by approval agencies)
31.5
to 104 CL
69
uj
35
Soo
101.0
104 a
150MM V)
35
0 400 800 1200 1600 FLOW RATES (GPM)
MODEL 375ADA 8" & 10" (STANDARD & METRIC)
FLOW RATES (us) 0.0 63.1 126.2 189.3 252.4
- -
Flow Characteristics
MODEL 375ADA2-112" -3" (STANDARD AND METRIC)
0 6.3 12.6 FLOW RATES (us) 18.9 25.2 19 15 a.
;
1:
IL 0 100 200 FLOW RATES (GPM) 300 400
MODEL 375ADA4" & 6" (STANDARD & METRIC) FLOW RATES (Us)
-
0.0 25.2 50.5 75.7
C
i o a
104
0 -J
69 uj
35 co A OL
4000
U, U,
a.
0 1000 2000 3000
FLOW RATES (GPM)
Typical Installation
Local codes shall govern installation requirements. To be
installed in accordance with the manufacturer's instruc-
tions and the latest edition of the Uniform Plumbing
Code. Unless otherwise specified, the assembly shall be
mounted at a minimum of 12' (305mm) and a maximum
of 30' (762mm) above adequate drains with sufficient side
clearance for testing and maintenance. The installation shall
be made so that no part of the unit can be submerged.
Capacity thru Schedule 40 Pipe (GPM) Pipe size 5 ft/sec 7.5 ft/sec 10 ft/sec 15 ft/sec 2 1/2" 75 112 149 224 115 173 230 346 198 298 397 595 6" 450 675 900 1351
8" 780 1169 1559 2339
10" 1229 1843 2458 3687
12" 1763 1 2644 1 3525 5288
p.=. •% ..IwI.:.. l.JI .4 FIX $ aIIfr:UØ2iII
DIRECTION OF FLOW C)
DIRECTON OF FLOW 4) OUTDOOR INSTALLATION (MODEL 375ADA with BG option) INDOOR INSTALLATION (MODEL 375ADA with G option)
Specifications
The Reduced Pressure Detector Backflow Prevention Assembly shall be ASSE® Listed 1047, and supplied with full port OS
& V gate valves. The main body and access cover shall be epoxy coated ductile iron (ASTM A 536 Grade 4), the seat ring and
check valve shall be NORYLTM, the stem shall be stainless steel (ASTM A 276) and the seat disc elastomers shall be EPDM.
The checks and the relief valve shall be accessible for maintenance without removing the device from the line. The Reduced
Pressure Detector Backflow Prevention Assembly shall be a WILKINS Model 375ADA.
Zum Industries, LLC I Wilkins
1747 Commerce Way, Paso Robles, CA U.S.A. 93446 Ph. 855-663-9876, Fax 805-238-5766
In Canada I Zurn Industries Limited
3544 Nashua Drive, Mississauga, Ontario L4V 11_2 Ph. 905-405-8272, Fax 905405-1292
www.zurn.com Page 2 of 2
OSYSU Series
Outside Screw an4 Yoke Vqlv go.POTTER
The Symbol of Protection Supervisory Swztca
Features
NEMA 4X* (IP 65) and 6P (IP 67)
*Enclosure is 4X For additional corrosion protection of
mounting hardware, use model OSYSU-2 CR1-I
-40° to 1400 (-40°C to 60°C) operating temperature range
Visual switch indicators
Two conduit entrances
Adjustable length trip rod
Accomodates up to I2AWG wire
Three position switch detects tampering and valve closure
Knurled mounting bracket prevents slipping
Fine adjustment feature for fast, easy installation
RoHS compliant
One or two SPDT contact models (-1,-2)
I Before any work is done on the fire sprinkler or fire alarm system, the I SIGNALING
I building owner or their authorized representative shall be notified. I I Before opening any closed valve, ensure that opening the valve will not C®US ( E cause any damage from water flow due to open or missing sprinklers, I LISTED + APPROVED piping, etc. I .Important: This document contains important information on the installation and operation of OS&Y valve supervisory switches. Please read all
instructions carefully before beginning installation. A copy of this document is required by NFPA 72 to be maintained on site.
Description
The OSYSU is used to monitor the open position of an OS&Y
(outside screw and yoke) type gate valve. This device is available in
two models; the OSYSU-1, containing one set of SPDT (Form C)
contacts and the OSYSU-2, containing two sets of SPDT (Form C)
contacts. These switches mount conveniently to most OS&Y valves
ranging in size from 2" to 12" (50mm to 300mm). They will mount
on some valves as small as '/2" (12,5mm).
The cover is held in place by two tamper resistant screws that require
a special tool to remove. The tool is furnished with each device.
Testing
The operation of the OSYSU and its associated protective monitoring
system shall be inspected, tested, and maintained in accordance
with all applicable local and national codes and standards and/or the
Authority Having Jurisdiction (manufacturer recommends quarterly
or more frequently). A minimum test shall consist of turning the valve
wheel towards the closed position. The OSYSU shall operate within
the first two revolutions of the wheel. Fully close the valve and ensure
that the OSYSU does not restore. Fully open the valve and ensure that
the OSYSU restores to normal only when the valve is fully opened.
A CAUT1014
Close the valve fully to determine that the stem threads do not
activate the switch. The switch being activated by the stem threads
could result in afalse valve open indication.
Technical Specifications
Dimensions See Fig 8
Weight 1.6 lbs (0,73 kg)
Cover: Die Cast Finish: Red Powder Coat
Enclosure Base: Die Cast Finish: Black Powder Coat
All parts have corrosion resistant finishes
Tamper Resistant Screws Cover Tamper
Optional Cover Tamper Switch Available
OSYSU-l: One Set of SPDT (Form C)
OSYSU-2: Two Sets of SPDT (Form C)
Contact
Ratings 10.0 Amps at 125/250 VAC
2.0 Amps at 30VDC Resistive
10 mAmps minimum at 24 VDC
-40° F to 140°F (-40°C to 60°C)
Environmental NEMA 4X (IP 65) and NEMA 6P (IP 67) Enclosure
Limitations (Use suitably rated conduit and connector)
Indoor or Outdoor Use (See OSYSU-EX Bulletin
5400705 for Hazardous locations)
Conduit Two Knockouts for 1/2" conduit provided
Entrances (See Notice on Page 6 and Fig. 9 on Page 5)
Service Use NFPA 13,13D, 13R, 72
Specifications subject to change without notice
Potter Electric Signal Company, LLC • St. Louis, MO • Tech Support: 866-956-0988 / Customer Service: 866-572-3005 • www.pottersignal.com
5401525- REV E • 8/15 PAGE 10F6
I
OSYSU Series POTTER Outside Screw and Yoke Vqlvç The Symbol of Protection Supervisory Swztcn
Theory of Operation
The OSYSU is a 3 position switch. The center position is the normal installation position. Normal is when the switch is installed on the OS&Y valve, the
valve is fully open and the trip rod of the OSYSU is in the groove of the valve stem. Closing the valve causes the trip rod to ride up out of the groove and
activates the switches. Removing the OSYSU from the valve causes the spring to pull the trip rod in the other direction and activates the switches.
Visual Switch Status Indication
There are 3 visual indicators to determine the status of the switches.
Fig I; the actuator button of the micro switches are on the raised section of the switch actuator.
Fig 2; the trip rod is perpendicular to the base and lined up with the alignment mark on the mounting bracket.
Fig 3; the white visual indicator is visible through the window on the back of the switch actuator.
A final test is to meter the contacts marked COM and N.O. to ensure they are an open circuit when the valve is open and that they close and have continuity
within 2 revolutions of turning the valve handwheel towards the closed position and the contacts remain closed as the valve is completely closed and until
the valve is completely opened when the trip rod drops back into the groove in the valve stem.
Potter Electric Signal Company, LLC St. Louis, MO Tech Support: 866-956-0988 / Customer Service: 866-572-3005 • www.pottersignal.com
5401525- REV E • 8/15 PAGE 2OF6
OSYSU Series (P) POTTER Outside Screw and Yoke Valve The Symbol of Protection Supervisory Switch
Small Valve Installation - 1/2" Through 2 1/2" Sizes Fig
uu
Slotted mounting holes and micro-adjustment
feature may be used for fine adjustment of
switch assembly to mounting bracket.
Re-tighten screws to 20 in-lbs minimum.
Small Valve Installation
NOTE: If the valve stem is pre-grooved at 1/8" minimum
depth; proceed to step 7. . 1. Remove and discard "E" ring and roller from the trip rod.
With the valve in the FULL OPEN position, locate the
OSYSU across the valve yoke as far as possible from the
valve gland so that the spring loaded trip rod of the OSYSU
is pulled against the non threaded portion of the valve stem.
Position the OSYSU with the bracket near the handwheel as
shown in Fig. 6 if possible to avoid creating a pinch point
between the wheel and the OSYSU.
Loosen the locking screw that holds the trip rod in place and
adjust the rod length (see Fig. 5). When adjusted properly,
the rod should extend past the valve screw, but not so far
that it contacts the clamp bar. Tighten the locking screw to
5 in-lbs minimum to hold the trip rod in place and properly
seal the enclosure.
NOTE: If trip rod length is excessive, loosen the locking
screw and remove the trip rod from the trip lever. Using
pliers, break off the one (1) inch long notched section (see
Fig. 10). Reinstall trip rod and repeat Step 3 procedure.
Mount the OSYSU loosely with the carriage bolts and clamp
bar supplied. On valves with limited clearance use J-hooks
supplied instead of the carriage bolts and clamp bar to mount
the OSYSU.
Mark the valve stem at the center of the trip rod.
Remove the OSYSU. Utilizing a 3/16" or 1/4" diameter
straight file, file a 1/8" minimum depth groove centered on
the mark on the valve stem. Deburr and smooth the edges
of the groove to prevent damage to the valve packing and to
allow the trip rod to move easily in and out of the groove as
the valve is operated.
NOTE: A groove depth of up to approximately 3/16" can
make it easier to install the OSYSU so that it does not restore
as it rolls over by the threads of the valve stem.
Mount the OSYSU on the valve yoke with the spring loaded
trip rod of the OSYSU pulled against the valve stem and
centered in the groove of the stem. If possible, position the
OSYSU with the flat side of the bracket toward the hand
wheel, as shown in Fig. 6, to help avoid creating a pinch
point between the wheel and OSYSU. When in this preferred
mounting position, it is usually best to use the white indicator
visible through the window, as illustrated in Fig. 3, to aid in
initially locating the OSYSU in the correct position on the
yoke. If the unit must be installed inverted with the white
indicator no longer easily visible, use the visual indicators
of the actuator buttons on the micro-switches, as illustrated
in Fig. 1, or the trip rod alignment mark on the bracket, as
illustrated in Fig. 2 , to aid in initially locating the OSYSU.
Final adjustment can be made by slightly loosening the two
screws on the bracket and using the fine adjustment feature
(see Fig. 5). The adjustment is correct when the plungers
on the switches are depressed by the actuator and there is
no continuity between the COM and NO terminals on the
switches.
Tighten the adjustment screws and all mounting hardware
securely (20 in-lbs minimum). Check to insure that the rod
moves out of the groove easily and that the switches activate
within two turns when the valve is operated from the FULL
OPEN towards the CLOSED position.
Reinstall the cover and tighten the cover screws to 15 in-lbs
minimum to properly seal the enclosure.
A CAUTION
Close the valve fully to determine that the stem threads do not
activate the switch. The switch being activated by the stem threads
could result in afalse valve open indication.
Potter Electric Signal Company, LLC • St. Louis, MO • Tech Support: 866-956-0988 / Customer Service: 866-572-3005 • www.pottersignal.com
5401525. REV E • 8/15 PAGE 3OF6
OSYSU Series POTTER Outside Screw and Yoke Vqlvç The Symbol of Protection Supervisory Switch
Fig 7 Large Valve Installation - 3" Through 12" Sizes
Slotted mounting holes and micro-
adjustment feature may be used for
fine adjustment of switch assembly to
mounting bracket. Re-tighten screws to
20 in-lbs minimum.
Large Valve Installation as it rolls over by the threads of the valve stem.
NOTE: If the valve stem is pre-grooved at 1/8" minimum 6. Mount the OSYSU on the valve yoke with the spring loaded
depth; proceed to step 6. trip rod of the OSYSU pulled against the valve stem and
centered in the groove of the stem. If possible, position the With the valve in the FULL OPEN position, locate the OSYSU with the flat side of the bracket toward the hand OSYSU across the valve yoke as far from the valve gland wheel, as shown in Fig. 7, to help avoid creating a pinch as possible so that the spring loaded trip rod of the OSYSU point between the wheel and OSYSU. When in this preferred is pulled against the non threaded portion of the valve stem, mounting position, it is usually best to use the white indicator Position the OSYSU with the bracket near the handwheel as visible through the window, as illustrated in Fig. 3, to aid in shown in Fig. 7 if possible to avoid creating a pinch point initially locating the OSYSU in the correct position on the between the wheel and the OSYSU. yoke. If the unit must be installed inverted with the white
Mount the OSYSU loosely with the carriage bolts and clamp indicator no longer easily visible, use the visual indicators
bar supplied, of the actuator buttons on the micro-switches, as illustrated
Loosen the locking screw that holds the trip rod in place and in Fig. 1, or the trip rod alignment mark on the bracket, as
adjust the rod length (see Fig. 5). When adjusted properly, illustrated in Fig. 2 , to aid in initially locating the OSYSU.
the rod should extend past the valve screw, but not so far 7. Final adjustment can be made by slightly loosening the two
that it contacts the clamp bar. Tighten the locking screw to screws on the bracket and using the fine adjustment feature
5 in-lbs minimum to hold the trip rod in place and properly (see Fig. 5). The adjustment is correct when the plungers
seal the enclosure, on the switches are depressed by the actuator and there is
NOTE: If trip rod length is excessive, loosen the locking no continuity between the COM and NO terminals on the
screw and remove the trip rod from the trip lever. Using switches.
pliers, break off the one (1) inch long notched section (see & Tighten the adjustment screws and mounting hardware
Fig. 10). Reinstall trip rod and repeat Step 3 procedure. securely (minimum 20 in-Ibs). Check to insure that the rod
Mark the valve stem at the center of the trip rod, moves out of the groove easily and that the switches activate
within two turns when the valve is operated from the FULL Remove the OSYSU. Utilizing a 3/8" or '/2" diameter straight OPEN towards the CLOSED position. file, file a 1/8" minimum depth groove centered on the mark
9. Reinstall the cover and tighten the cover screws to 15 in-lbs on the valve stem. Deburr and smooth the edges of the
minimum to properly seal the enclosure. groove to prevent damage to the valve packing and to allow
the trip rod to move easily in and out of the groove as the I A CAUTION valve is operated. I I I NOTE: A groove depth of up to approximately 3/16" can Close the valve fully to determine that the stem threads do not I
make it easier to install the OSYSU so that it does not restore I activate the switch. The switch being activated by the stem threads
could result in afalse valve open indication.
Potter Electric Signal Company, LLC • St. Louis, MO • Tech Support: 866-956-0988 / Customer Service: 866-572-3005 • www.pottersignal.com
5401525- REV E • 8/15 PAGE 4OF6
Nj
EM
Rod retracted and
(2672) breakaway section removed
[93.26
Rod fully extended
Cover Tamper Switch
(2)o.886
Knockouts For I/
Electrical Conduit
Connections
Ground S
)/4"-20]
Hardwar
Clamp Bar
ved
9.09
(77.47
2.23
157 113
0
rP) POTTER
The Symbol of Protection
OSYSU Series
Outside Screw and Yoke Vqlvç
Supervisory Switch
Dimensions
Fig 8
Knockout Removal
Fig 9
To remove knockouts: Place screwdriver at inside edge of knockouts, not in
the center.
NOTE: Do not drill into the base as this creates metal shavings which
can create electrical hazards and damage the device. Drilling voids the
warranty.
Potter Electric Signal Company, LLC • St. Louis, MO Tech Support: 866-956-0988 / Customer Service: 866-572-3005 • www.pottersignal.com
540)525- REV E • 8/15 PAGES OF 6
rP') POTTER
10
The Symbol of Protection
Breaking Excessive Rod Length
Fig 10 mm~
Switch Terminal Connections
Clamping Plate Terminal
Fig 11
All conduit and connectors selected for the installation of this product
shall be suitable for the environment for which it is to be used and shall be installed to the manufacturer's installation instructions. For NEMA 4, 4X, 6,
6P installations, the cover screws are recommended to be tightened to 15 in-
lbs minimum and the trip rod locking screw tightened to 5 in-lbs minimum
to properly seal the enclosure.
Typical Electrical Connections
Fig 12
EOLR
CM NC N NO NCCOM
TO FIRE ALARM PANEL
S
An uninsulated section of a single conductor should not be looped around
the terminal and serve as two separate connections. The wire must be .severed, thereby providing supervision of the connection in the event that
the wire become dislodged from under the terminal. Failure to sever the
wire may render the device inoperable risking severe property damage
and loss of life. Do not strip wire beyond 3/8" of length or expose an
uninsulated conductor beyond the edge of the terminal block. When using
stranded wire, capture all strands under the clamping plate.
OSYSU Series
Outside Screw and Yoke Vqlvç
Supervisory Switch
Ordering Information
Model Description Stock No.
OSYSU-1 Outside Screw & Yoke 1010102
Supervisory Switch
(Single switch)
OSYSU-2 Outside Screw & Yoke 1010202
Supervisory Switch
(Double switch)
OSYSU-2 Outside Screw & Yoke Supervisory 1010210
CRH Switch (Double Switch). Corrosion
resistant hardware of 316 stainless steel
& nickel plated to ASTM B377 Type
V Brackets
Cover Screw 5490424
Hex Key for Cover Screws and 5250062
Installation Adjustments
Optional Cover Tamper Switch Kit 0090200
Engineering Specifications: OS&Y
Valves
UL, CUL Listed / FM Approved and CE Marked valve supervisory switches shall be furnished and installed on all OS&Y type valves
that can be used to shut off the flow of water to any portion of the
fire sprinkler system, where indicated on the drawings and plans and
as required by applicable local and national codes and standards.
The supervisory switch shall be NEMA 4X and 6P rated and capable
of being mounted in any position indoors or out and be completely
submerged without allowing water to enter the enclosure.. The
enclosure shall be held captive by tamper resistant screws. The device
shall contain two 1/2 conduit entrances and one or two Single Pole
Double Throw (SPDT) switches. There shall be a visual indicator to
display the status of the switches. To aid in installation, it shall be
possible to make fine adjustments to the position of the switch on the
valve without loosening the mounting bracket from the valve. The
device shall contain an adjustable length trip rod and roller, the trip
rod shall be held captive by a set screw accessible upon removal of the
cover. The switch contacts shall be rated at I OA, 125/250VAC and 2A,
30VDC. OS&Y Valve supervisory switch shall be model OSYSU-1
for the single switch model and OSYSU-2 for the two switch model
manufactured by Potter Electric Signal Company LLC
Es) I [I
Supervisory switches have a normal service life of 10-15 years.
However, the service life may be significantly reduced by local
environmental conditions.
Potter Electric Signal Company, LLC St. Louis, MO Tech Support: 866-956-0988 / Customer Service: 866-572-3005 • www.pottersignal.com ISO 9001:2008 1 DESIGNING, MANUFACTURING,
WI I $11 & DISTRIBUTING QUALITY SYSTEMS 5401525 - REV £ • 8/15 PAGE 6 OF 6
QL4
Municipal Water District
APPROVED MATERIALS LIST FOR CONSTRUCTION OF POTABLE
WATER, RECYCLED WATER AND SEWER FACILITIES
Please submit a completed Approved Materials List to the District's Share File site (all
11 pages). The Project Name should be listed at the top of each page. To obtain a link
to the Share File site please contact the Engineering Department Assistant.
PROJECT NAME:
Supplier Name: (W F2-
Contact Person: /xc. A-&1o, Ur-
Phone: (i) 2LC-7 ._9f571
- FOR DISTRICT USE ONLY BELOW THIS LINE
REVIEWED ONLY FOR GENERAL CONFORMITY TO PLANS AND STANDARD SPECIFICATIONS
U APPROVED PROJECT #:
U APPROVED AS NOTED
U MAKE CORRECTIONS NOTED & RESUBMIT
U REJECTED EAM WO#:
Initials Date
As-Built Stamp:
,fl
CARLSBAD FIRE DEPARTMENT
Fire Prevention Division
1635 Faraday Avenue - Carlsbad, CA 92008
760.602.4665
WATER AVAILABILITY FORM
SECTION A: TO BE COMPLETED BY CUSTOMER
PROJECT NAME: 2910 Jefferson St. SR#:
(Assigned upon plan submittal)
PROJECT ADDRESS: 2910 Jefferson St. CITY: Carlsbad
PHONE: (_858 ) 444-2000 x 1715 (Cosco Fire Protection, Inc.) FAX NUMBER: (858) 444-2056
Largest Building (ft.2): Sprinkled? __ Construction Type:__________________
SECTION B: TO BE COMPLETED BY LOCAL WATER COMPANY. CUSTOMER TO PROVIDE RESULTS TO CFD.
Water Purveyor: City of Carlsbad
Location of test (reference map required): southeast corner of Grand and Jefferson
TEST INFORMATION IS VALID FOR 6 MONTHS FROM DATE PERFORMED
Flow Test Results
Static pressure: 86 PSI Hydrant Number (if applicable): H62262
Elevation of test 56 Feet Date/Time of Test1
Pitot Tube Reading: PSI Corresponding Flow: GPM
Total Flow: 6,375 GPM Residual Pressure 20 PSI
At peak demand. this water system is capable of providing a fire flow discharge @ 20 psi of 6,375 gpm. This flow does
not exceed the maximum 15 fps criteria for the City.
'Test to be performed as close as possible to the time the most conservative flows and pressures are expected.
Note: If the water availability information was obtained in a manner other than a flow test (i.e. computer
modeling), fill out the information above as applicable and check here: x
I have witnessed and/or reviewed this water flow information and by personal knowledge and/or on-site
observation certify that the above information is correct.
Name: Jennifer R.Mael,P.E. Eng. Lic. No. (if applicable): C69606
Signature: 7)1/
Tit?e/Org: PiectManager Date: 06/30/2016
. . 2910 Jefferson St Fire Flow Availability
Prepared By: Jennifer R. Mae[, P.E. - MCS Date: Thursday, June 30, 2016
0
Fire Protection by Computer Design
COSCO FIRE PROTECTION
4990 Greencraig Lane
San Diego, CA. 92123
(858) 444-2000
Job Name : JEFFERSON BACKFLOW PROOF CALC
Building : FP1
Location 2910 Jefferson Street Carlsbad, CA. 92008
System : EXISTING
Contract 10.CD_5690
Data File PROOF CALC.WXF
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
I
COSCO FIRE PROTECTION
JEFFERSON BACKFLOW PROOF CALC
16 HYDRAULIC CALCULATIONS
for
Project name: Jefferson Backflow
Location: 2910 Jefferson Street Carlsbad, CA. 92008
Drawing no: FP1
Date: 6-30-16
Design
Remote area number: EXISTING
Remote area location: EXISTING BLDG
Occupancy classification: N/A
Density: .068 - Gpm/SqFt
Area of application: 3000 - Sq Ft
Coverage per sprinkler: N/A - Sq Ft
Type of sprinklers calculated: N/A
No. of sprinklers calculated: EXIS ITNG
In-rack demand: N/A - GPM
Hose streams: 500 - GPM
Total water required (including hose streams): -GPM
Type of system: WET
Volume of dry or preaction system: N/A - Gal
Water supply information
Date: 6-30-16
Location: JOB SITE . Source: STATIC: 86 PSI, RES.:20 PSI, FLOW: 6375 GPM
Name of contractor: COSCO FIRE PROTECTION
Address: 4990 GREENCRAIG LANE SAN DIEGO, CA. 92123
Phone number: (858) 444-2000
Name of designer: H.A.
Authority having jurisdiction: CARSLBAD FIRE DEPARTMENT
Notes: (Include peaking information or gridded systems here.)
Page 1
Date 6-30-16
@ -Psi
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Water Sup .urve C
COSCO FIRE P OTECTION
JEFFERSON BACKFLOW PROOF CALC
S
Page 2
Date 6-30-16
City Water Supply: Demand: Cl - Static Pressure : 86 Dl - Elevation : 0.217 C2 - Residual Pressure: 20 D2 - System Flow : 232.9 C2 - Residual Flow : 6375
. D2 - System Pressure : 68.001
Hose ( Demand) : 500
D3 - System Demand : 732.9
Safety Margin : 16.792
150
140
130
p120
110 R
E10°
590 :
580
U 70
60
-
R 13
E5°
40
30
20 C2
10
.... .... .
75911500 2250 3000 3750 4500 5250 6000 6750 FLOW (NA1.85)
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Fittings USummary
COSCO FIRE OTECTION Page 3 JEFFERSON BACKFLOW PROOF CALC Date 6-30-16
Fitting Legend
Abbrev. Name 1/2 % 1 1% 1'/2 2 21/2 3 31/2 4 5 6 8 10 12 14 16 18 20 24
E NFPA 13 90' Standard Elbow 1 2 2 3 4 5 6 7 8 10 12 14 18 22 27 35 40 45 50 61 G NFPA 13 Gate Valve 0 0 0 0 0 1 1 1 1 2 2 3 4 5 6 7 8 10 11 13 I NFPA139O' Flow thruTee 3 4 5 6 8 10 12 15 17 20 25 30 35 50 60 71 81 91 101 121
Units Summary
Diameter Units Inches
Length Units Feet
Flow Units US Gallons per Minute
Pressure Units Pounds per Square Inch
Note: Fitting Legend provides equivalent pipe lengths for fittings types of various diameters.
Equivalent lengths shown are standard for actual diameters of Sched 40 pipe and CFactors
of 120 except as noted with * The fittings marked with a * show equivalent lengths values
supplied by manufacturers based on specific pipe diameters and CFactors and they require no
adjustment. All values for fittings not marked with a * will be adjusted in the calculation
for CFactors of other than 120 and diameters other than Sched 40 per NFPA.
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Pressure / Flow Summary - STANDARD
COSCO FIRE PROTECTION Page 4 JEFFERSON BACKFLOW PROOF CALC Date 6-30-16
Node Elevation K-Fact Pt Pn Flow Density Area Press o. Actual Actual Req.
BOR 0.5 64.9 na 232.9 UG1 -3.0 66.62 na BF1 -3.0 67.51 na BF2 -3.0 68.36 na TEST 0.0 68.0 na 500.0
The maximum velocity is 5.66 and it occurs in the pipe between nodes BOR and UG1
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Final Calculations - Hazen-Williams - 2007
cosco FIRE PROTECTION Page 5 JEFFERSON BACKFLOW PROOF CALC Date 6-30-16
.Hyd.
Qa Dia. Fitting Pipe Pt Pt Ref. "C" or Ftng's Pe Pv ******* Notes Point Qt P1/Ft Eqv. Ln. Total P1 Pn
*UG PIPING
BOR 232.90 4.1 E 14.534 2.750 64.900 Qa = 232.90 to 140.0 - 0.0 14.534 1.516 UG1 232.9 0.0120 0.0 17.284 0.208 Vel = 5.66
UG1 0.0 4.1 3E 43.601 30.500 66.624 to 140.0 0.0 43.601 0.0 BF1 232.9 0.0120 0.0 74.101 0.890 Vel = 5.66
BFI 0.0 4.1 T 29.067 12.000 67.514 to 140.0 2E 29.067 58.134 0.0 BF2 232.9 0.0120 0.0 70.134 0.843 Vel = 5.66
BF2 0.0 4.1 E 14.534 32.000 68.357 to 140.0 G 2.907 46.508 -1.299
TEST 232.9 0.0120 1 29.067 78.508 0.943 Vel = 5.66
500.00 Qa = 500.00 732.90 68.001 K Factor= 88.88
C
S
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Oil VENHAIN MUNICIPAL WATER DISTRICT
APPROVED MATERIALS LIST FOR CONSTRUCTION OF POTABLE WATER,
0
RECYCLED WATER AND SEWER FACILITIES
*All Material Being Used Shall Conform w/OMWD's Standard Specifications
Project
PLEASE INDICATE WHICH PRODUCT YOU ARE USING BY PLACING AN "X" ON THE
APPROPRIATE LINE TO THE RIGHT OF EACH MANUFACTURER
Item Description Std Manufacturer
Spec
Section
AIR/VACUUM VALVE 2 Piece Assembly with Bolt Down Base and 15092 VCAS-1424-SM w/tape & screen ENCLOSURE Removable Cover, Polyethylene Material, Sandstone VCAS-1830-SM w/tape & screen *must be accompanied by Color with Identification Band, OSHA Blue for VCAS-2436-SM w/tape & screen
- a shop drawing WATER, OSHA Purple for Recycled Water
1424 for 1" r Potable 1830 for 2"
2436 for 3" r RCW
ANGLE METER STOP, 1" Bronze Angle Meter Stop (Ball Valve) with 90 15081 Ford BA43-444W-Q-NL QUICK JOINT X Degree Lockwing, Inlet Quick Joint for Copper Jones - J1963WSG METER NUT Water Tube x Meter Swivel Nut Outlet McDonald 74602BQ
Mueller - B24258
ANGLE METER STOP, 1-1/2", 2" Bronze Angle Meter Stop (Ball Valve) 15081 Ford BFA43-777W-Q-NL QUICK JOINT X with 90 Degree Lockwing, Inlet Quick Joint for Jones - J1975WSG
- METER FLANGE Copper Water Tube x Meter Flange Outlet McDonald 74602BQ
- Mueller - B24276
ANGLE VALVE Bronze Angle Valve, 2" and Smaller 15080 Nibco T-375-B
- 300 PSI Rated, Female Threaded Ends Jones J-380
-
ANGLE VALVE Bronze, Angle Design, 300 PSI Rated, 4" Inlet 15080 Jones J-344HP
- HYDRANT HEAD Female IPT, 2-1/2" Outlet National Standard Hose
Thread, Cap and Chain
ANODE, MAGNESIUM High or Standard Potential Anode with a Galvanized 13110 Corrpro
- *n:ust be accompanied by Steel Core Encased in a Square Magnesium Alloy Corrosion Control Products
- a shop drawing Ingot Pre-Packaged in a Permeable Cotton Cloth Farwest
Bag. Provide Ingot Weight as Specified on the Calpico
Approved Plans
ANODE, ZINC Each Zinc Anode shall be Pre-Packaged in a 13110 Corrpro
- Permeable Cloth Bag and shall Weigh 30 Pounds Corrosion Control Products
-
Farwest
Calpico
Please Contact the District's Inspection Dept. for the material to be used if the
Part or Model numbers shown are no longer available.
Pg 2 Revised 08/19/14
0
OLIVENHAIN MUNICIPAL WATER DISTRICT
APPROVED MATERIALS LIST FOR CONSTRUCTION OF POTABLE WATER,
10 RECYCLED WATER AND SEWER FACILITIES
*All Material Being Used Shall Conform w/OMWD's Standard Specifications
Project f?g& i3Fe)
PLEASE INDICATE WHICH PRODUCT YOU ARE USING BY PLACING AN "X" ON THE
APPROPRIATE LINE TO THE RIGHT OF EACH MANUFACTURER
Item Description Std Manufacturer
Spec
Section
BACKFLOW Reduced Pressure Principal Type Assemblies as 15112 List of Approved Backflow
PREVENTER Approved by the State of California, Department of Prevention Assemblies *n,ust be accompanied by Health Services -
a shop drawing
BOLT KIT, 316 SS Hex-Head Machine, ASTM A193, Grade B 8M 15050 Tripac Fasteners
- *for specific uses only Bolts and ASTM A 194, Grade 8M Nuts, Grade 8M Pacific Coast Bolt
- Flat Washers ITP, Inc.
- Bolt Kit includes: Bolts, Nuts, and Flat Washers
BOLT KIT Hex-Head Machine, Cadmium/Zinc Plated, ASTM 15050 Tripac Fasteners
- A307, Grade B Bolts and A307 2H Heavy Hex Nuts Pacific Coast Bolt
Bolt Kit includes: Bolts, Nuts, and Flat Washers ITP, Inc.
BURY ELBOW, 16' DI Long Radius Bury El, MJ or P0 15109 Clow
- DUCTILE IRON Holiday Free Epoxy Lined Bells Star
Sigma
-
South Bay Foundry
CATHODIC TEST 54 Lb Concrete Body with 12 Lb Ductile Iron Lid 13110 Brooks 1 -RT
- STATION BOX and Lid Ring. "CP TEST" shall be Cast into the Lid Farwest Type 1-RT
- in 1" Letters. For Cathodic Protection Test Stations, J&R 3RT
- Anode Ground Beds and Insulated Flange Test
Stations
CATHODIC WELDING For Welding Cathodic Bond Wires to Steel Pipelines 13110 Cadweld
-
COATING, INTERNAL For Coating the Internal Pipe Lining for an Insulated 13110 Aquatapoxy CCI
- PIPE Flange Kit Hydro-Pox
-
CONNECTOR, All Brass Split Bolt to be Accompanied and Encased 15292
TRACER WIRE with Rubberized Tape, and then Electrical Tape 15293
SPLICING KIT
Please Contact the District's Inspection Dept. for the material to be used if the
Part or Model numbers shown are no longer available.
Pg 3 Revised 08/19/14
0
OLIVENHAIN MUNICIPAL WATER DISTRICT
APPROVED MATERIALS LIST FOR CONSTRUCTION OF POTABLE WATER,
0 RECYCLED WATER AND SEWER FACILITIES
*All Material Being Used Shall Conform w/OMWD's Standard Specifications
Project e4y22,c ek)
PLEASE INDICATE WHICH PRODUCT YOU ARE USING BY PLACING AN "X" ON THE
APPROPRIATE LINE TO THE RIGHT OF EACH MANUFACTURER
Item Description Std Manufacturer
Spec
Section
CORPORATION STOP, Bronze Ball Valve, Male Iron Pipe Thread x Quick 15080 Ford FB 1100-x-Q-NL
- MIPT X QUICK JOINT Joint (T-Head Only), 1", 1-1/2" and 2" Full MCD 74704BQ
- Opening Mueller - B25028
- 1" 1-1/2" 2" Jones - J1935 SG 0 0
COUPLING, C900 PVC, 4" through 12" Solid PVC for Obtaining Deflection 15292 CertainTeed
- HIGH DEFLECTION Only. Provides 4 Degree Maximum Deflection
4" 6" 8" 10" 12"
30000
COUPLING, C900 PVC, 4" through 12" Solid PVC for Closure or Repair 15292 CertainTeed
- CLOSURE / REPAIR 4" 6" 8" 10" 12"
]000
COUPLING, C905 PVC, 4" through 12" Solid PVC for Obtaining Deflection 15293 Specified
HIGH DEFLECTION Only. Provides 4 Degree Maximum Deflection
14" 16" 18" 20" 24"
30000
COUPLING, Use for Above Ground DI or Steel Pipe 15061 Grinnell #7001
- MECHANICAL 4" or Larger 15240 Tyler 500
- CLAMP-TYPE 15251 Victaulic #44, #77
- *must be accompanied by
a shop drawing
COUPLING, 4" and Larger, Steel or Ductile Iron Construction, 15122 APAC 301
STRAIGHT Slip x Slip, Epoxy Coated with 304 or 316 Stainless Ford FC1
- FLEXIBLE Steel Bolts and Nuts. Powerseal 3501
- *n,usf be accompanied by For Use on AC, PVC, DI, or Steel Pipe Romac 501
- a shop drawing Must be Restrained When Used with AC Pipe Smith-Blair 411
- Indicate Size
Please Contact the District's Inspection Dept. for the material to be used if the
Part or Model numbers shown are no longer available.
Pg 4 Revised 08/19/14
C
n
61
C
OLIVENHAIN MUNICIPAL WATER DISTRICT
APPROVED MATERIALS LIST FOR CONSTRUCTION OF POTABLE WATER,
RECYCLED WATER AND SEWER FACILITIES
*All Material Being Used Shall Conform w/OMWD's Standard Specifications
Project 4t L) tk-)
PLEASE INDICATE WHICH PRODUCT YOU ARE USING BY PLACING AN "X" ON THE
APPROPRIATE LINE TO THE RIGHT OF EACH MANUFACTURER
Item Description Std Manufacturer
Spec
Section
COUPLING, 4" and Larger, Steel or Ductile Iron Construction, 15122 APAC 311, 313 TRANSITION Holiday Free Epoxy Coated with 304 or 316 SS Ford FC2A
- FLEXIBLE Bolts and Nuts. Powerseal 3501, 3506
- *n,ust be accompanied by For use on AC, PVC, DI, or Steel Pipe. Romac XR501
- a shop drawing Must be Restrained When Used with AC Pipe Smith-Blair 413
- Indicate Size
DISMANTLING JOINT Telescoping, Adjustable, Double Flanged Fitting, Romac Flexijoint
- *must be accompanied by with High Tensile Strength Zinc Plated Tie Bars. Star - StarFiex a shop drawing NSF-61 Epoxy or Nylon Interior and Exterior
Coating
FIRE HYDRANT, Cast Iron 12" through 18" Long with Machined 15109 South Bay Foundry
BREAK-OFF RISERS V-Groove 4" from One End, Groove to be 1/8" to 15090 Clow
3/16" Deep and ¼" Wide Sigma
-
Star
FIRE HYDRANT 6" High Pressure 200 PSI Wet Barrel, Bronze Fire 15109 Clow 2060, 2065
- Up To 200 PSI Hydrant, with Six-Hole Bolt Pattern Jones J3765, J3775
-
American AVK 2464X, 2468X
-
FITTING, DUCTILE Flanged, Push On, Tees, Bends, Crosses, Reducers, 15240 Bachman
- IRON, 4" Adapters, etc. For 4", Per AWWA Cl 10, C1 11, 15292 Sigma
C153 and OMWD Standards. Holiday Free Epoxy 15293 Star
- Lined Bells Tyler
111/4 22 1/2 45 90 Tee End Cap US Pipe 0 00 00
FITTING, DUCTILE Flanged, Push On, Tees, Bends, Crosses, Reducers, 15240 Bachman
- IRON, 6" Adapters, etc. For 6", Per AWWA Ci 10, C1 11, 15292 Sigma
- C1 53 and OM\VD Standards. Holiday Free Epoxy 15293 Star
Lined Bells Tyler
- 111/4 221/2 45 90 Tee End Cap US Pipe 0 0000
-
Please Contact the District's Inspection Dept. for the material to be used if the
Part or Model numbers shown are no longer available.
Pg 5 Revised 08/19/14
Oil VENHAIN MUNICIPAL WATER DISTRICT
APPROVED MATERIALS LIST FOR CONSTRUCTION OF POTABLE WATER,
RECYCLED WATER AND SEWER FACILITIES
*All Material Being Used Shall Conform w/OMWD's Standard Specifications
Project 1F7Q'( 73'jfti)
PLEASE INDICATE WHICH PRODUCT YOU ARE USING BY PLACING AN "X" ON THE
APPROPRIATE LINE TO THE RIGHT OF EACH MANUFACTURER
Item Description Std Manufacturer
Spec
Section
FITTING, DUCTILE Flanged, Push On, Tees, Bends, Crosses, Reducers, 15240 Bachman
IRON, 8" Adapters, etc. For 8", Per AWWA C1 10, C1 11, 15292 Sigma
C153 and OMWD Standards. Holiday Free Epoxy 15293 Star
Lined Bells Tyler
- 111/4 22 1/2 45 90 Tee End Cap US Pipe O 00000
FITTING, DUCTILE Flanged, Push On, Tees, Bends, Crosses, Reducers, 15240 Bachman
IRON, 10" Adapters, etc. For 10", Per AWWA Ci 10, Ci 11, 15292 Sigma
C153 and OMWD Standards. Holiday Free Epoxy 15293 Star - Lined Bells Tyler
11-1/4 22-1/2 45 90 Tee End Cap US Pipe o 0 000 0
FITTING, DUCTILE Flanged, Push On, Tees, Bends, Crosses, Reducers, 15240 Bachman
- IRON, 12" Adapters, etc. For 12", Per AWWA C 10, Ciii, 15292 Sigma
C15 3 and OMWD Standards. Holiday Free Epoxy 15293 Star
Lined Bells Tyler
11-1/4 22-1/2 45 90 Tee End Cap US Pipe
0 0 DO DO
FLANGE COUPLING 6" and Larger, Mechanical x Flange. Steel or Ductile 15.122 Dresser 127, 128 - ADAPTER Iron without Anchor Pins, Holiday Free Epoxy Ford FFCA Style
Coated, 304 SS Bolts and Nuts. Baker 601, 602
Powerseal 3521, 3526
Romac FCA501, FC400
Smith-Blair 912, 913
GASKET, PAPER 1/8" Thick Full Face or Ring, Aramid Fiber Bound 15050 Garlock Bluegard
- with Nitrile. No Asbestos Content Klinger C4400
- Full Face Tripac 5000 X. 0 Calpico
-
S
Please Contact the District's Inspection Dept. for the material to be used if the
Part or Model numbers shown are no longer available.
Pg 6 Revised 08/19/14
I—]
Oil VENHAIN MUNICIPAL WATER DISTRICT
APPROVED MATERIALS LIST FOR CONSTRUCTION OF POTABLE WATER,
RECYCLED WATER AND SEWER FACILITIES
*All Material Being Used Shall Conform w/OMWD's Standard Specifications
Project 1rr))v
PLEASE INDICATE WHICH PRODUCT YOU ARE USING BY PLACING AN "X" ON THE
APPROPRIATE LINE TO THE RIGHT OF EACH MANUFACTURER
Item Description Std Manufacturer
Spec
Section
GROUT Non-Shrink Cement Based Construction Grout for 03000 UPCON High Flow
- Crack Repair, Flooring Mortar, Dowel Grouting, Master Flow 713
- Crack Sealing and General Binding
INSULATING BLANKET Insulating Blanket for Corrosion Interference 13110
*must be accompanied by Mitigation
a shop drawing
INSULATING Insulating Couplings for Corrosion Protection of 15080 Wilkins Model DUXL
- COUPLINGS Pipelines/Appurtenances Watts Model LF3 003
*must be accompanied by 1" 1 1/2" 2" 3"
a shop drawing 0 0 0 0
INSULATING FLANGE Insulating Flange Kits for Corrosion Protection of 13110 Advance Product Systems
KIT Pipelines/Appurtenances Calpico
Corrpro
Farwest
JOINT RESTRAINT 360 Degree Wedge Type Restraint System for 15240 Ford Uniflange 1300 Series
- ASSEMBLY Ductile Iron and C900 PVC, Sizes 6" Through 24" 15292 Ford Uniflange 1500 Series
EBAA Iron
Sigma PV-LOK
-
Romac DI- Roma Grip
Romac 600 Series
MARKING TAPE 6" wide, Warning/Identification (Metallic) Marking 15061 Linetec
- Tape for Buried Facilities 15240 Terra Tape
- POT RCW S FM ELEC FIBER 15292 Calpico
- 0 0 0 0 0 0 15293 Christy
-
S
Please Contact the District's Inspection Dept. for the material to be used if the
Part or Model numbers shown are no longer available.
Pg 7 Revised 08/19/14
S
I
Oil VENHAIN MUNICIPAL WATER DISTRICT
APPROVED MATERIALS LIST FOR CONSTRUCTION OF POTABLE WATER,
RECYCLED WATER AND SEWER FACILITIES
*All Material Being Used Shall Conform w/OMWD's Standard Specifications
Projecti 8TC/) Lk414l')
PLEASE INDICATE WHICH PRODUCT YOU ARE USING BY PLACING AN "X" ON THE
APPROPRIATE LINE TO THE RIGHT OF EACH MANUFACTURER
Item Description Std Manufacturer
Spec
Section
METER BOX 17"x28" Precast Meter Box and 2 Piece Polymer 15081 J&R Concrete Products, Inc.
*must be accompanied by Concrete Cover with Reading Lid for 1" Water 15090 Armor Cast
a shop drawing Service, Use Purple Covers for Recycled Water, 15091 Old Castle
- For Water Service Installation, Polymer Concrete
Cover Shall Have Hole for Touch Read Device.
MAR and Blowoff Installation Does Not Require
Hole Cut Out
WS MAR/130
0
METER BOX 24"x36" Precast Meter Box and 2 Piece Polymer 15081 J&R Concrete Products, Inc.
- *must be accompanied by Concrete Cover with Reading Lid for 1" Water Armor Cast a shop drawing Service, Use Purple Covers for Recycled Water Old Castle
- For Water Service Installation, Polymer Concrete
Cover Shall Have Hole for Touch Read Device
MAR and Blowoff Installation Does Not Require
Hole Cut Out
WS MAR/130
0
OUTLET, WELD-ON Weld-On Outlet with Reinforcing Collar or Wrapper 15080 Pipeline Products
*must be accompanied by for Connection to CML&C Steel Pipe
a shop drawing
PIPE, COPPER WATER Type K Soft Seamless Rolled Tubing, Type K Soft 15220 Cerro
- TUBE Seamless Straight Lengths, Type K Hard Seamless Mueller
- Straight Lengths (Soft - Buried Applicaton ONLY) Cambridge-Lee
(Hard - Above Ground ONLY)
Soft Hard 1" 1-1/2" 2" 3"
0 0 0 00
I
Please Contact the District's Inspection Dept. for the material to be used if the
Part or Model numbers shown are no longer available.
Pg 8 Revised 08/19/14
I
OLIVENHAIN MUNICIPAL WATER DISTRICT
APPROVED MATERIALS LIST FOR CONSTRUCTION OF POTABLE WATER,
RECYCLED WATER AND SEWER FACILITIES
*All Material Being Used Shall Conform w/OMWD's Standard Specifications
projectfr&
PLEASE INDICATE WHICH PRODUCT YOU ARE USING BY PLACING AN "X" ON THE
APPROPRIATE LINE TO THE RIGHT OF EACH MANUFACTURER
Item Description Std Manufacturer
Spec
Section
PIPE, DUCTILE IRON For Water Lines 4" and Larger Manufactured per 15240 American Pipe
- *,,,ust be accompanied by AWWA C15 I Griffin
- a shop drawing and lay Pacific States
sheets U.S. Pipe
PIPE, PVC C900 For Water Lines 4" through 12" Manufactured per 15292 Diamond Plastics
- AWWA C900 in Class 150 and 200 Vinyllech
- DR14 DR18 North American Pipe
- 4" 6" 8" 10" 12" IM Eagle 00 D 0
PIPE, PVC C905 For Water Lines 14" through 24" Manufactured per 15293 Diamond Plastics
AWWA C905 VinylTech
- 14" 16" 18" 20" 24" North American Pipe 0 0 0 0 0 JMEagle
PLASTIC 8-MTh Thick Polyethylene Encasement Tube for 09954
POLYETHYLENE Ductile Iron Pipe, CML&C.
ENCASEMENT
109952 PLASTIC WRAPPER Clear Plastic Wrapper over Wax Tape Coating and Denso Tape PVC Self-Adhesive
- Primer in Underground Applications Trenton Poly-Ply
POLYETHYLENE 8-MIL Thick Polyethylene Encasement Sheet for 09954
WRAP Buried Fittings and Valves. Purple Color for
Recycled Water
SERVICE SADDLE Cast Bronze Body with Stainless Steel Double Band 15080 Ford - 202BS
FOR ACP, DIP, AND Straps or Single Wide Strap with 4 Bolts, IF Outlet Romac - 202BS
- PVC PRESSURE PIPE Sizes McDonald -3846
- ACP DIP PVC Jones - J-969 0 0
-
1" 1-1/2" 2"
0 0
Please Contact the District's Inspection Dept. for the material to be used lithe
Part or Model numbers shown are no longer available.
Pg 9 Revised 08/19/14
Oil VENHAIN MUNICIPAL WATER DISTRICT
APPROVED MATERIALS LIST FOR CONSTRUCTION OF POTABLE WATER,
RECYCLED WATER AND SEWER FACILITIES
*All Material Being Used Shall Conform w/OMWDs Standard Specifications
Project ftEl2't 42i)
PLEASE INDICATE WHICH PRODUCT YOU ARE USING BY PLACING AN "X" ON THE
APPROPRIATE LINE TO THE RIGHT OF EACH MANUFACTURER
Item Description Std Manufacturer
Spec
Section
TAPE, PLASTIC 10 to 50 MIL x 2" Wide General Utility Tape for 09954 Calpico Vinyl Tape
- ADHESIVE Corrosion Protection of Above and Below Ground 09952 Christy
Pipes and Fittings Northtown
-
Polyken-900
-
Scotchwrap - 50
-
TAPPING SLEEVE Fabricated Stainless Steel Tapping Sleeve with 15080 Ford - FTSS
- FOR ACP, DI, AND PVC Stainless Steel Bolts and Nuts PowerSeal - 3460AS PIPE Romac - SSTIII
- Smith Blair - 665 -
THREDOLET Forged Steel Fitting ASTM A105. 3000#, NPT 15061 Bonney Forge
- Threads Allied Piping Products
Pipeline Products
TRACER WIRE AWG No. 8 Stranded Copper Wire with High 15292 Calpico - HMW/PE #8
- Molecular Weight Polyethylene (BMW/PE) 15293 Farwest - BMW/PE #8
- Insulation Specifically Designed for Direct Burial in KALAS - w-08hmwpe-str
Corrosive Soil or Water
VALVE BOX AND Cast Iron Frame and Lid and 12" Pipe Sleeve. Cast 15092 South Bay Foundry - SBF 1243 COVERS, on the Lid the Words "OMWD", and "WATER" or
MANUAL AIR RELEASE "RW"
AND BLOW-OFF (For Street Use Only)
ASSEMBLIES
*must be accompanied by
a shop drawing
VALVE BOX AND Cast Iron Frame and Cover and Extension Pipe. Cast 15101 South Bay Foundry - SBF 1208-N
- COVERS, on the Cover the Words "OMWD", and "WATER"
GATE VALVE or "RW"
Please Contact the District's Inspection Dept. for the material to be used if the
Part or Model numbers shown are no longer available.
Pg 10 Revised 08/19/14
n
OLIVENHAIN MUNICIPAL WATER DISTRICT
APPROVED MATERIALS LIST FOR CONSTRUCTION OF POTABLE WATER,
RECYCLED WATER AND SEWER FACILITIES
*All Material Being Used Shall Conform w/OMWD's Standard Specifications
Project f1ZoA1 /Zc)
PLEASE INDICATE WHICH PRODUCT YOU ARE USING BY PLACING AN "X" ON THE
APPROPRIATE LINE TO THE RIGHT OF EACH MANUFACTURER
Item Description Std Manufacturer
Spec
Section
VALVE, Single Chamber, HDPE Control Floats, Stainless 15108 Vent-O-Mat DN25 RBX 2521
COMBINATION AIR Steel Body, 1/4" NPT Test/Bleed Cock Vent-O-Mat DN50 RBX 4021
- RELEASE & Vent-O-Mat DN80 RBX 1631
- AIR/VACUUM, 3" AND Vent-O-Mat DNIOO RBX 2531
- SMALLER
VALVE, GATE, 3" through 24" Resilient Seated, Non-Rising Stem, 15101 AVK or Approved Equal
- RESILIENT SEATED Counter-Clockwise Opening, Type 304 or 316 SS
*must be accompanied by Body Bolts, 250 PSI Working Pressure, Holiday
a shop drawing Free Interior Lining
WAX TAPE COATING 4 Part, Cold Applied Wax Tape Coating System for 09952 Denso Densyl Tape
Buried Piping Components Trenton No.1 Wax Tape
- System Includes: Primer, Wax Tape, Clear Wrap, 10
MIL Tape, and 8 MIL Thick Polyethelene Sheet
so
Please Contact the District's Inspection Dept. for the material to be used if the
Part or Model numbers shown are no longer available.
Pg 11 Revised 08/19/14