HomeMy WebLinkAbout5780 FLEET ST; ; FPC2018-0060; Permitty
PERMIT REPORT Ur-isb
ö of
ad
Print Date: 02/04/2022 Permit No: FPC2018-0060
Job Address: 5780 FLEET ST, CARLSBAD, CA 92008-4702 Status: Closed - Finaled
Permit Type: FIRE-Construction Commercial Work Class: Fire Alarm
Parcel #: Track #: Applied: 02/20/2018
Valuation: $0.00 Lot #: Issued: 03/05/2018
Occupancy Group: Project #: Finaled Close Out: 08/19/2021
#of Dwelling Units: Plan #:
Bedrooms: Construction Type:
Bathrooms: Orig. Plan Check #: Inspector:
Plan Check #: Final Inspection:
Project Title:
Description: PACIFIC RIDGE CORPORATE CENTER -FIRE RECALL SYSTEM FOR ELEVATOR MOD
Applicant: FPContractor:
NOVA SECURITY NOVA SECURITY
CORY HILL 8779 COTTONWOOD AVE, # STE 103
358 RIVER TRAIL PL SANTEE, CA 92071457
SANTEE, CA 92071-6907 (619) 448-3007
(619) 448-3007
FEE AMOUNT
FIRE TI Fire Alarm System $601.00
Total Fees: $601.00 Total Payments To Date: $601.00 Balance Due: $0.00
Fire Department Page 1 of 1
1635 Faraday Avenue, Carlsbad CA 92008-7314 1 760-602-4665 1 760-602-8561 1 I www.carlsbadca.gov
PACIFIC RIDGE CORPORATE CENTER
5790 FLEET STREET
CARLSBAD, CA 92008
Fire Alarm Submittal
02/16/18
FPC20180060
5780 Fleet ST
F NEW& ~ lKh
.FILE COPY
Submitted By;
N+--:V^—SERIY
8779 Cottonwood Avenue
SUITE 103
Santee, CA. 92071
619-448-3007
Cont. Lie. C-10 # 802053
PACIFIC RIDGE CORPORATE CENTER
Qty Description
1 Fire Alarm Panel
4 Smoke Detector
2 Addressable Relays
Fire Alarm Submittal
Equipment List
Model Manufacture CSFM#
IPA-60 POTTER 7165-0328:500
PAD 100 PD POTTER 7272-0328:504
PAD100-RM POTTER 7165-0328:500
(E)POTTER IPA-60
The Symbol of Protection Fire Alarm Control Panel
Features
60 addresses available on this analog addressable system
Additional system capacity achieved via multi-point SLC modules
99 software zones
NFPA 72 Compliant Smoke Sensitivity Test Built-In
System Operates as Class A or Class B for SLC, P-Link and NACs
5 Amp Power Supply, Expandable to 310 amps
2 NACS, Regulated, Rated at 3 Amps each, expandable to 188
2 Input/Output (I/O) Circuits for system flexibility rated at 1 Amp each,
ideal for manual release and abort
Strobe Synchronization and System Wide Sync for Potter/AMSECO®,
Gentex®, Cooper Wheelock® and System Sensor® strobes
Dedicated Alarm, Supervisory and Trouble Relays
4,000 Event History Buffer
Cabinet will house up to 18 A batteries
Optional two line DACT with UD-1000 that can report General, Zone or
Point Information
Built in TP Communicator
Ethernet Port for Programming and Network Connectivity
E-Mail System Status, Reports and Event Information
Product includes 5 year warranty.
LISTED
UUKL Compliance accomplished when using DRy-SO with the Space
Age Electronics GL8
Description Technical Specifications
The IPA-60 is an analog/addressable releasing fire alarm system with a
total system capacity of 60 addresses. Additional capacity on the system
is achieved using multi-point SLC modules. The control panel utilizes
the exclusive Potter protocol that includes a complete line of sensors and
modules. Each SLC may be comprised of any combination of smoke
sensor, heat detectors or modules and allows for a total of 50 ohms of
impedance and may use any wire compliant with the National Electrical
Code (NEC).
The IPA-60 has a 5 Amp power supply with two Notification Appliance
Circuits (NACs) and two Input/Output (I/O) circuits. The NACs are rated at
3 Amps each and the I/Os are rated at I Amp each. Each output is regulated
and power limited. In addition, each output is uniquely programmable and
may be configured for steady signal, strobe synchronization, constant
power, door holder power, or releasing. The strobe synchronization
includes Potter/AMSECO, Gentex, System Sensor and Cooper/Wheelock
and with the exclusive Quadrasync each output may have a unique brand
and all strobes will flash together. The I/Os are designed for inputs such as
manual release stations and abort switches that will not require polling and
react nearly instantaneously.
The IPA-60 is listed for releasing of fire suppression systems. The
software allows cross zones, counting zones, and timers for suppression.
The system is capable of multiple release outputs across multiple hazards.
In addition, the PSN-1000 may be used to extend releasing capability.
The NACs may be expanded using the PSN-1000 series intelligent power
supplies. Each PSN-I 000 adds another 10 Amps of power, 2 additional
input circuits and the IPA-60 will support up to 31 power supplies. The
system will synchronize the strobes system wide. In addition, the PSN-
I 000E has space to allow the installation of up to six expansion cards.
The cards mount on a stacker bracket that allows access to all SLC circuit
connections.
Dimensions 16"W x 17"H x 3 718"D
3.0 Amps @ 120 VAC 50/60 HZ AC Mains 2.0 Amps @ 240 VAC 50/60 HZ
Enclosure 16 gauge cold rolled steel with removable locked door with Lexan viewing window
Standby Current-130 mA
Alarm Current-200 mA
5 Amps power for NACs, I/O, and P-Link
Battery 3 Amps per NAC, regulated
1 Amp per I/O circuit, regulated
Battery Charger range 8-55 Ah
Battery Charger voltage 27.3 VDC
P-Link maximum current of 1 Amp
Temperature and 32° to 120° (0°C to 49°C) with a maximum
Humidity Range humidity of 93% non-condensing.
NFPA 12, 12A, 13, 15, 16, 17, 17A, 70,
72, 750, and 2001
ANSI/UL 864 - Local (L), Remote Sta-
tion (RS), Central Station (CS), Propriety
(PPU), Auxiliary (AUX).Type of Service:
Automatic (A), Manual (M) Water flow
Standards (WF) Sprinkler Supervisory (SS) Type of
Signaling: Digital Alarm Communicator
(DAC), March Time (March), Non Coded
(NC), Reverse Polarity (Rev Pol), Other
Technologies (OT)
IBC 2000, 2003, 2006, 2009, 2012
Potter Electric Signal Company, LLC • St. Louis, MO • Phone: 800-325-3936 • www.pottersignal.com
8830100-REVB • 05/17 PAGE 1 0F4
(E)POTTER IPA-60
The Symbol of Protection Fire Alarm Control Panel
SLC Loop Accessories
The control panel may be connected with up to 60 addressable devices or modules in any combination. The SLC is not restricted by any special wire
requirements and may be wired with any wire that complies with the NEC.
SLC Loop Devices
Device Description
PAD 00-PD Analog Photo Electric Smoke Detector is a smoke detector with a listed obscuration of 1.02 to 3.83 percent per foot.
PADI00 PHD Combination Analog Photo Electric Smoke/Heat Detector - a smoke detector with a listed obscuration of 1.02 to 3.83 percent
obscuration and a fixed temperature 135° Fahrenheit heat detector.
PAD 100-HD Analog Fixed Temperature Heat Detector that is selectable from 135° F to 185°F.
PAD 100-DUCTR Addressable Duct Smoke Detector with Form C Relay.
PAD 100-DUCT Addressable Duct Smoke Detector.
PAD 100-6B 6" round base that is mounted to an electrical box and wired for connection of one of the above sensors.
PAD 100.4B 4" round base that may be mounted to an electrical box and wired for connection to the above sensors.
PAD! 00-TB Isolator base that interrupts a short in a SLC and prevents the short from affecting protected devices on the loop.
PAD 100-RB Addressable Relay Base that contains one relay controlled by the SLC. Relay is rated at rated at 2 amps at 30 VDC or 0.5A at 125VAC.
PAD100-SB Addressable Sounder Base that contains an addressable sounder module that may be configured for local, group and all call.
PAD 100-CD Addressable CO gas detector.
PAD 100-DD Addressable photo electric smoke detector for use in DUCT/DUCTR enclosure.
Modules
Device Description
PAD 100-MIM Micro Input Module provides a small foot print contact module for mounting inside an enclosure.
PADI 00-PSSA Single Action Addressable Pull Station.
PADI 00-PSDA Dual Action Addressable Pull Station.
PAD 100-SIM Single Input Module is a standard contact module with an LED that mounts into a 4" square electrical box.
PAD 100-DIM Dual Input Module is a device that can monitor two distinct inputs with a single device or in a Class A mode.
PAD I 00-TRTI Two Relay Two Input module provides two form C relays that are individually controlled by the control panel. Each relay is rated for 2
amps at 30VDC or 0.5 amps at 125VAC. Also provides two contact inputs.
PADTOO-NAC Notification Appliance Circuit module is an addressable remote appliance circuit controlled by the panel.
PAD100-ZM Zone Module is used to connect conventional 2-wire smoke detectors to the system.
PAD100-IM Isolater Module interrupts a short on the SLC and prevents the short from affecting protected devices on the loop.
PADlOO-RM Relay Module that provides one form C relay controlled by the control panel. Relay is rated for 2 amps at 30VDC or 0.5 amps at 125VAC.
PAD 100-LED Module provides a single addressable LED that is controlled by the control panel.
PAD1 00-SM Speaker Module provides switching for two audio channels.
PAD100-LEDK Addressable LED and key switch that mounts in a single gang box.
PAD 100-DRTS DUCTR Remote Test Switch that mounts n a single gang box and optionally supervised.
PAD100-OROI One Relay One Input Module provides one form C relay and one input. The relay is rated at 2 amps at 30VDC or 0.5 amps at 125VAC.
Potter Electric Signal Company, LLC • St. Louis, MO Phone: 800-325-3936 www.pottersignal.com
8830100-REVB • 05/17 PAGE 2OF4
® POTTER
The Symbol of Protection
IPA-60
Fire Alarm Control Panel
SLC Features
The Potter protocol is a digital protocol with a proven design for
reliability and noise immunity. The system does not require special
cable or conductors for connection of the Signaling Line Circuit
as long as the cable is compliant with NFPA 70 and NFPA 72.
The system allows for Class A or Class B installations as well as
"T-Taps", with a max wiring distance of 10,000 Ft.
Sensor Features
The sensors through the fire alarm control panel provide a real
time status as to the condition of the system. The smoke detector
sensitivity, heat detector temperature level and drift compensation
are all programmable options. The system also allows for a day/night
mode where the panel automatically adjusts the sensitivity depending
on the time of day. To assist in the reduction of false alarms, the
smoke detectors also have a maintenance warning that sends a trouble
signal when a detector is dirty to the point that it can no longer
maintain the programmed sensitivity.
User Interface
The fire alarm control panel has a 2 x 16 LCD display to provide
information to the system status. The keypad has navigation keys
to allow manipulation of the Menu on board the panel. The panel is
shipped standard with the following LEDs:
AC Power - Green
Alarm - Red
Earth Fault - Amber
Supervisory - Amber
Silenced - Amber
Trouble - Amber
Pre-Release - Amber
Release - Red
The common buttons include a Silence, Reset, Acknowledge, and
Drill. All of the buttons are accessible once the locked door is
opened.
P-Link
The IPA-60 has a proprietary communication protocol that
communicates through a RS-485 connection to field devices. Up
to 64 devices may be connected to a single P-Link connection. The
P-Link includes the communication terminals and regulated 24 VDC
connection for the field devices. The field devices may be any of the
following:
PAD IOO-SLCE-Analog/Addressable loop expansion module
RA-6075R —2 x 16 LCD annunciator with a key pad in a locked
metal enclosure.
RA-6500R(F) —4 x 40 LCD annunciator with a key pad in a locked
metal enclosure. Flush mount version available.
LED-16(F) - 16 LED annunciator with common indicators in a
locked metal enclosure. Flush mount version available.
PSN-1000(E) - 10 amp, remote intelligent power supply with
6 NACs, 2 I/Os and a P-Link repeater. This panel is listed in
conjunction with the IPA-60 as releasing circuits.
CA-6500 - Class A convertor that converts the SLC, NACs and
P-Link connection
UD-1000 —UL listed, Dual line telephone alarm communicator
DRV-50 - LED driver expander, used to connect up to 50 LEDs in a
graphic display
FCB-1000 - Fire communication bridge, provides remote mounting
of the Ethernet connection
FIB-1000 - Fiber interface module, used to extend P-Link to multi-
mode fiber (2 required)
RLY-5 - Relay module, provides 5 form C relay contacts rated at 3.0
amps 24VDC/125AC
SPG-1000 - Serial parallel gateway, allows for the connection to a
serial or parallel printer
The FIB-1000, FCB-1000 and the SPG-1000 may be installed in the
stacker bracket or ordered with the optional rack mount enclosure.
MC-1000 Multi-Connect allows up to sixty-three IPA series panels to
share a single reporting technology.
AE-2 - Two card expansion cabinet
AE-8 - Eight card expansion cabinet
AE-14 - Fourteen card expansion cabinet
Ethernet/I.P. Connection
The IPA-60 is shipped standard with an Ethernet connection.
This connection is the programming port and may be connected
to a building Wide Area Network (WAN) or Local Area Network
(LAN). Once connected to the Internet, the panel may be selectively
programmed to e-mail alarm conditions, trouble conditions,
supervisory conditions, test, Event History and detector status. An
e-mail may be sent to the panel and the panel will e-mail the event
history, detector status, configuration file or server status to an
authorized E-mail account. In addition, reminders may be set to send
an e-mail for service, testing or other conditions.
In addition, the Ethernet connection is UL listed as an IP
communicator. The IP communicator is listed to report to the UL
listed Sur-Gard III IP receiver. The IP communicator replaces the
traditional less reliable alarm communicator transmitter that utilized
telephone lines. The IP communicator is an active method of
connection and communication to the monitoring station.
Potter Electric Signal Company, LLC • St. Louis, MO • Phone: 800-325-3936 • www.pottersignal.com
8830100-REVB • 05/17 PAGE 3OF4
(E)POTTER IPA-60
The Symbol of Protection Fire Alarm Control Panel
Dimensions
0 01
TOP • DEPTH =3.75'
oj
DOOR = 16.07'
BACKBOX = 15.77 DEPTH = 3.84"
0
"0
LEFT SIDE
o BOTTOM
RIGHT SIDE
DWG #593-1
Ordering Information
Model Description I Stock No.
IPA-60 Fire Alarm Releasing Control Panel 13992714
Compatible Releasing Devices
Note: For releasing applications please order the Potter EOLD
(3005012) for circuits connected to a releasing solenoid or actuator.
Brand Description
Skinner 73218BN4UNLVN0C112CZ
732 12BN4TNLVNOC322C2
Victaulic 753-E Series
Mini Max MX 123 & MX200 wl 8876677 & 889323
Viking 11591, 11601, 11602, 13843, & 13844
TLX PA0036
Potter Electric Signal Company, LLC St. Louis, MO Phone: 800-325-3936 . www.pottersignal.com
8830100-REVB • 05/17 PAGE 4OF4
(E.)POTTER
The Symbol of Protection
Features
PAD 00-RM
Relay Module
One (I) Form C relay contact
SLC Class A, Class X & Class B
Mounts in a standard 4" or double gang box
Wiring terminals accessible when mounted in box
All wiring terminals accept 22 to 12AWG
Product includes a 5 year warranty
13
Description
The PAD 100-RM uses one (1) SLC loop address to provide one (1)
Form C relay contact. The module mounts on either a 4" square or
double gang box. The PAD 100-RM includes one red LED to indicate
the module's status. In normal condition, the LED flashes when the
device is being polled by the control panel.
Application
The PAD IOO-RM is compatible with Potter's IPA series addressable
fire alarm control panels. The PAD100-RM is an interface module
providing one (I) Form C relay contact.
Setting the Address
Each addressable SLC device must be assigned an address. The
address is set using the DIP switch located on the PAD IOO-RM. The
PAD 100-RM uses a single device address to identify relay contacts.
Before connecting a device to the SLC loop, take the following
precautions to prevent potential damage to the panel or device:
Power to the device is removed.
Field wiring is correctly installed.
Field wiring has no open or short circuits.
Technical Specifications
Operating Voltage 24.0V
Max SLC Standby 240iA Current
Max SLC Alarm
Current 2401A
Relay Contacts 2A @3OVDC, 0.5A @125VAC
Operating Temperature
Range 32 to 120°F (0 to 49°C)
Operating Humidity
Range 0 to 93% (non-condensing)
Max no. of Module Per 127 units Loop
Dimensions 4.17" (106mm)L x 4.17"
(lO6mm)W x 1.14" (29mm)D
Mounting Options Standard 4" Square or
Double Gang Box
Shipping Weight 0.6 lbs
Potter Electric Signal Company, LLC • St. Louis, MO Phone: 800-325-3936 www.pottersignal.com
8830084 -REV B • 12/17 PAGE 1 OF 2
(E)POTTER
The Symbol of Protection
PAD 00-RM
Relay Module
Installation Using Compatible Electrical Box
Fig 1
Wiring Diagram
PADIOO-RM Relay Circuit
Fig 2
FROM FACP OR
PREVIOUS MODULE
TO NEXT MODULE
0D o VD
I LM
1) FORM C E—R'~c TF: RELAY CONTACTS
0
LIJ
o a a
0 0
c o cD
It is possible that the internal relay in the PAD I 00-RM may be shipped in the non-normal I activated state. To ensure that the internal relay is set to the
normal state, connect the module to the SLC loon and reset the control nanel before terminating the wiring to the modules output.
Ordering Information
Model Description I Stock No.
PADIOO-RM Relay Module 1 3992705
Potter Electric Signal Company, LLC St. Louis, MO • Phone: 800-325-3936 www.pottersignal.com
8830084-REVB • 12/17 PAGE 2OF2
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
MPAI—S
OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM
LISTING SERVICE
LISTING No. 7165-0328:0500' Page 1 of 1'
CATEGORY:' 7165-- FIRE ALARM CONTROL UNIT (COMMERCIAL)
LISTEE: Potter Electric Signal Co1609 Park 370 Place, Hazelwood, 63042 United States
Contact: Bill Witherspoon (314) 595-6900 Fax (314) 595-6999
Email: bilIwpottersignal.com
DESIGN: Models IPA-60, IPA-100, and IPA-4000 fire alarm control units. Automatic, Manual, waterflow
and sprinkler supervisory type device and local, auxiliary, releasing, remote station (PPU),
proprietary (PPU) and central station (PPU) services. Refer to listee's Installation Instruction
Manual for details. System components (CSFM Listing 7305-0328:0200):
PAD100-DIM Dual Input Module
PAD100-LED Addressable LED Module
PAD 100-OROI One Relay-One Input Module
PAD 100-RM Relay Module
PAD 100-SIM Single Input Module
PAD 100 TRTI Two Relay-Two Input Module
PAD 100-ZM Zone Module
PAD 100-IM lolator Module
PAD 100- NAC Notification Appliance Circuit Module
PAD 100-SM Speaker Module
PAD 100-MIM Micro Input Module
PAD 100-LEDK LED Key Switch Module
PAD 100-DRTS Duct Remote Test Switch
PAD 100-SLCE127 Point SLC Expander
MC-1000 Multi-Connect
PAD 100-DUCTR
AE-2 Enclosure
RATING: 24VDC
INSTALLATION: In accordance with listee's printed installation instructions, applicable codes & ordinances
and in a manner acceptable to the authority having jurisdiction.
MARKING: Listees name, model designation, rating and UL label.
APPROVAL: Listed as fire alarm control units when use with separately listed electrically and functionally
compatible initiating and indicating devices. Refer to listee's Installation Instruction Manual
for details.
03-07-2017 dcc
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed
the test results and/or other data but does not make an independent verification of any claims. This listing is not
an endorsement or recommendation of the item listed. This listing should not be used to verify correct
operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other
Date Issued: July 01, 2017 'Listing Expires) June 30, 2018
Authorized By: DAVID CASTILLO, Program Coordinator
Fire Engineering Division
(E)POTTER PAD100-PD
The Symbol of Protection Photoelectric Smoke Sensor
Features
Low profile, less than 2 inches with the base
Wide selectable sensitivity range of 1.0 to 3.70/o/foot
Sensor communicates sensitivity to control panel
UL listed smoke calibration and sensitivity
Optional locking tab to prevent unwanted removal
Simple DIP switch address setting, no programming tool
required
LED alarm indicator
Product includes a 5 year warranty
X@
LISTED
Description
The Photoelectric Smoke Sensor is a listed Analog Addressable smoke
sensor compatible with fire alarm control panels that utilize the Potter
Addressable Device (PAD) protocol. The PAD 100-PD is a low profile
smoke sensor with a wide sensitivity range. The sensor and base (not
included) are made of a durable plastic in an off-white color to blend
in with the ceiling.
The PAD 100-PD has a sensitivity range of 1.0 to 3.7 % per foot and
is UL. The PAD100-PD features drift compensation and has built in
dirty detector warning as well as. The PAD 100-PD and the control
panel communicate over a proven and robust digital communication
path and the system analyzes the information at the particular device.
The total polling speed is less than five (5) seconds, well under the UL
requirements.
The sensor is compatible with any of the PAD series sensor bases and
simply twists on. The PAD100-PD is addressed using DIP switches
in the rear of the sensor and can be easily programmed in the field
without special tools.
Setting the Address
Each addressable device on the SLC loop must have a unique address
from 1 to 127 to function properly. The address is set using DIP
switches.
Before connecting a device to the SLC loop, take the following
precautions to prevent potential damage to SLC or device. Verify the
following:
Power to the device is removed
Field wiring is correctly installed.
Field wiring has no open or short circuits.
Technical Specifications
Operating Voltage 24 VDC
Detector Current Draw 300 tA
Alarm indicator 1 LED
Alarm set-point range 1.0 to 3.7 %/ft 3.6-12 %/m
Installation temperature 32 to 120 0 F / 0 to 49 ° C range
Operating relative 0% to 93% (Non-condensing) humidity range
Start-up time Max. I sec.
Maximum number of 127 addresses per loop
Maximum number of
lighted indicators in 30
alarm per loop.
Color Eggshell White
Weight (without base) I01g (3.56oz)
Dimensions (without Height: 1.35 in (34mm)
base) Diameter: 3.93 in (100 mm)
Wall Mount 12" max. from ceiling
Potter Electric Signal Company, LLC • St. Louis, MO • Phone: 800-325-3936 www.pottersignal.com
8830108- REV B • 12/17 PAGE 0F2
® P011ER
The Symbol of Protection
'PADI 00-PD
Photoelectric Smoke Sensor
Air Velocity Ratings
The PAD 100-PD has an Open Area of Protection air velocity rating of 0 to 300 feet per minute.
The system has a maximum of 30 LEDs that can be turned on simultaneously. If the system already has 30 LEDs on, the PAD 100-PD will operate even
though the LED may not illuminate.
Operation
The PAD IOO-PD is an analog addressable sensor that uses one address on the Signaling Line Circuit (SLC) of a compatible fire alarm control panel.
The unit communicates with the control panel as it is polled. The LEDs flash every time the unit is polled and they will flash at a fast rate if the unit is
in an active status. The polling LED can be turned off if desired for less conspicuous operation.
The PAD] 00-PD with the PAD 100-4DB or PAD100-6DB has a low profile of less than two (2) inches to blend into the surrounding environment. The
sensor includes an insect screen to prevent foreign objects from reaching the chamber and the can be cleaned to restore operation of a dirty detector.
Sensor Sensitivity
The PAD 100-PD and the compatible control panel work in tandem to keep the sensitivity consistent. As the sensor is installed over time, the sensor
compensates for the dirt in the unit until it is out of range. At that time, the panel will indicate a dirty sensor. The sensor will then have to be cleaned
or replaced.
The PAD 100-PD can be programmed to provide a maintenance alert prior to reaching the dirty sensor level which will allow for intervention prior to
the sensor going into trouble. This allows for sensor replacement or cleaning prior to a nuisance trouble occurs.
NOTE: As required by NFPA, do not install the sensors until all construction is complete and the work area has been thoroughly cleaned. If the sensors
have been installed in a construction environment, they should be cleaned or replaced before the system is placed into service.
Spacing/Mounting
The PAD 100-PD is UL listed with a recommended maximum spacing of 30 feet. Refer to NFPA 72 for specific information regarding detector spacing,
mounting location, and special applications.
Compatible Bases
All bases will mount on a single gang, double gang, octagon, 4" square or mud ring electrical box.
Device Description Stock No.
PAD 100-4DB 4" Standard Base 3992731
PAD 100-6DB 6" Standard Base 3992732
PAD 100-lB 6" base with an isolator module included. 3992730
PAD 100-RB 6" base with one Form-C relay contact. 2A @ 30VDC, 0.5A @ 125VAC 13992728
PAD 100-SB 6" base with sounder module included. Sound pattern is provided from external source. 3992729
Ordering Information
Model Description I Stock No.
PADIOO-PD Photoelectric Smoke Sensor 3992733
Potter Electric Signal Company, LLC . St. Louis, MO Phone: 800-325-3936 . www.pottersignal.com
8830108- REV B • 12/17 PAGE 2OF2
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING . BUILDING MATERIALS LISTING PROGRAM
LISTING SERVICE
LISTING No. 7272-0328:0504 Page 1 of I
CATEGORY: 7272 -- SMOKE DETECTOR-SYSTEM TYPE-PHOTOELECTRIC
LISTEE: Potter Electric Signal Co1609 Park 370 Place, Hazelwood, 63042 United States
Contact: Bill Witherspoon (314) 595-6900 Fax (314) 595-6999
Email: billw@pottersignal.com
DESIGN: Models PADIOO-PD, PADICO-DD and PAD100-PHD photoelectric smoke detector heads.
Model PAD1 00-PHD has an intergral heat detector. Refer to Listee's data sheet for detailed
product description and operational considerations.
RATING: 24Vdc
INSTALLATION: In accordance with listee's printed installation instructions, applicable codes and ordinances
and in a manner acceptable to the authority having jurisdiction.
MARKING: Listee's name, model number, electrical rating, and UL label.
APPROVAL: Models PAD100-PD' and PADIOO-PHD are listed as photoelectric smoke detector heads for
use with listee's detector base Models PAD100-4DB, PAD100-6DB, PADIOO-RB,
PADI 00-SB (CSFM#7300-0328:502) and Model PAD 100-I B (CSFM#7300-0328:501). Model
PAD100-DD is listed as a photoelectric smoke detector head for use with Model
PAD 00-DUCT (CSFM#3248-0328:0505). Refer to listee's Installation Instruction Manual for
details.
06-21-2017 dcc
To This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed
the test results and/or other data but does not make an independent verification of any claims. This listing is not
an endorsement or recommendation of the item listed. This listing should not be used to verify correct
operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other
Date Issued: July 07, 2017 Listing Expires \June 30, 2018
Authorized By: DAVID CASTILLO, Program Coordinator
Fire Engineering Division