HomeMy WebLinkAbout2200 FARADAY AVE; ; AS080166; PermitCity of Carlsbad
Sprinkler Permit
Permit No: AS080166
Job Address: 2200 FARADAY AV Status: ISSUED
Permit Type: SPRINK Applied 10/15/2008
Parcel No: 2121204100 Approved: 10/16/2008
Lot #: 0
Reference No.: Issued: 10/16/2008
PC #: Inspector:
Project Title: CORRIDOR REMODEL - 2ND FLOOR TI FIRE SPRINKLER PLAN
CHECK & INSPECTIONS
Applicant:
WEST COAST FIRE PROTECTION
271 ROYMAR RD
SUITE F
OCEANSIDE, CA
(760)754-8472
Owner:
D L FARADAY L P
C/O DRA ADVISORS LLC
220 E 42ND ST #27
NEW YORK NY
Fees ($) Add'I Fees ($) Total ($) Balance ($)
130 0 130 0
many angles, reducing
assembly effort. This sprin-
kler is available in various
temperature ratings (see
chart on page 2) and fin-
ishes to meet many design
requirements.
The recessed pendent
should be utilized with a
Model V27 recessed
escutcheon which pro-
vides up to 3/4' (19 mm) of
adjustments.
Sprinkler Operation
The operating mechanism
is a frangible glass bulb
which contains a heat
responsive liquid. During a
fire, the ambient tempera-
ture rises causing the liquid
in the bulb to expand.
When the ambient temper-
ature reaches the rated
temperature of the sprin-
kler, the bulb shatters. As a
result, the waterway is
cleared of all sealing parts
and water is discharged
towards the deflector. The
deflector is designed to dis-
tribute the water in a pat-
tern that is most effective
in controlling the fire.
Coverage
For coverage area and
sprinkler placement, refer
to NFPA 13 standards.
p
XZ ictaulicic V27, K5.6
Models V2703, V2704, V2707 and V2708
Standard Spray
Upright, Pendent and Recessed Pendent
Standard and Quick Response
L 1
PRODUCT DESCRIPTION
These Model V27 standard
spray sprinklers are
designed to produce a
hemispherical spray pat-
tern for standard commer-
cia! applications. They are V2707
V2708 available with either stan-
Recessed dard or quick response
Pendent bulbs. The design incorpo-
() ()
<.>
rates state-of-the-art, heat
responsive, frangible glass
See Victautc
10.01
bulb design (standard or
publication
for cletails. quick response) for prompt, V2701
vio
-,
precise operation.
The die cast frame is more
streamlined and attractive
than traditional sand cast
Pendent frames. It is cast with a
V2703 - hex-shaped wrench boss to
V2704 allow easy tightening from
Upright
I I
TECHNICAL SPECIFICATIONS
Models: V2703, V2704, V2707
V2708
Style: Pendent, Upright or
Recessed Pendent
Nominal Orifice Size:
1/2" (13 mm)
K-Factor: 5.6 Imp. (8,1 S.I.
Nominal Thread Size:
1/2 NFl (15 mm)
Max. Working Pressure:
175 psi (1200 kP
Factory Hydrostatic Test:
100% @ 500 psi (3450 kP
Mm. Operating Pressure:
7psi (48kPa)
Temperature Rating: See
chart on page 2.
MATERIAL
SPECIFICATIONS
Upright Deflector:
Bronze per UNS C22000
Pendent Deflector:
Bronze per UNS CS 1000
Bulb: Glass with glycerin solu-
tion.
Bulb Nominal Diameter:
LI Standard: 5,0 mm
LI Quick Response: 3,0 min
Load Screw: Bronze per UNS
C65100
Pip Cap: Bronze per UNS
C65100
Spring: Beryllium nickel
Seal: Teflon* tape
Frame: Die cast brass 65-30
Lodgement Spring:
Stainless steel per UNS S30200
ACCESSORIES
Installation Wrench:
LI Open End: V27
U Recessed: V38, V38-3
U Socket: V27
Finishes:
LI Plain brass
O Chrome plated
LI White painted**
LI Custom painted**
LI Lead**
155, 200, 286SR Only-
0 Wax" o Wax over lead**
For cabinets and other accesso-
ries refer to separate sheet.
NOTE: Weather resistant recessed
escutcheons available upon request.
For K-Factor when pressure is mca-
sured in Bar, multiply S.I. units by
10.0.
Teflon is a registered trademark of
Dupont Co.
UL Listed for corrosion resistance in
all configurations.
VICTAULIC® IS AN ISO 9001 CERTIFIED COMPANY
Victaulic Company of America Victaulic Company of Canada Victaulic Europe Victaulic America Latina Victaulic Asia Pacific
Phone: 1-800-PICK-VIC (1-800-742-5842) Phone: 905-884-7444 Phone: 32-9-381-1500 Phone: 610-559-3300 Phone: 65-6235-3035
Fax: 610-250-8817 Fax: 905-884-9774 Fax: 32-9-380-4438 Fax: 610-559-3608 Fax: 65-6235-0535
e-mail:pickvicstvictaulic.com e-mail: viccanada@victaxlic.com e-mail: xiceuro@rvictaulic.be e-mail: vical@victaulic.com e-mail: vicap@victaulic.com
2544 ReeD 8f)3 0 Regiumsd Tradwnk of Victat®c 0Copyiight201)3 \fu5autc Printed in USA.
F
APPROVALSILISTINGS
Nominal Approved Temperature Ratings °F/°C t
Orifice Size K-Factor
Inches Imperial Deflector
Model millimeters S.L^ Response Type UL FM ULC NYC!MEAt CSFM §
½ 5.6 135-360 135-360 135-360 135-360 135-360 V2703 13 8.1 Standard Upright 51-182 57-182 57-182 57-182 57-182
½ 5.6 135-360 135-360 135-360 135-360 135-360
V2707 13 8,1 Standard Pendent 57-182 57 -182 57-182 57-182 57 -182
1h 5.6 Recessed Pendent 135-360 135-200 135-360 135-360 135-360
V2707 13 6.1 Standard Up to '314' Adjustment 57-182 57 -93 57-182 57-182 1 57 -182
½ 5.6 135-286 135-286 135-286 135-286 135-286 V2704 13 8,1 Quick Upright 57-141 57-141 57-141 57-141 57-141
½ 5.6 135-286 135-286 135-286 135-286 135-286 V2708 13 81 Quick Pendent 57-141 57-141 57-141 57-141 57-141
½ 5.6 Recessed Pendent 135-200 135-200 135-200 135-200 135-200
V2708 13 811 Quick UptowAdjustment 57-93 57-93 57-93 57-93 57-93
½ 5 .6 Recessed Pendent 135-200 135-200 135-200 135-200 V2708 13 8,1 Quick Up to 3/4- Adjuwrnent No 57-93 1 5793
t Listings and approval as of printing. QAII arc approved open, except for areas designated No.
For K-Factor when pressure is measured in Bar. multiply Si. units by 10.
MEA #62-99-F. § CSFM 0690-0531 Al2
RATINGS
All glass bulbs are rated for
temperatures from -67°F
(-55°C) up to those shown
in adjacent table.
Temperature - °FI°C
Nominal Maximum Sprinkler Victaulic Glass
Temperature Part Temperature Ambient Temp. Bulb
Classification Identification Rating Allowed Color
Ordinary A 135
57
100
38 Orange
Ordinary C 155 100 Red
Intermediate E 175 150 Yellow
Intermediate F 200
93
150
65 Green
High -
286
141
225
107 Blue
Extra High I K 360 300
182 149 Purple
- I M Open No Bulb
Standard response only.
All are approved open, except for areas designated N0.
—15016Sf wax coated.
ORDERING INFORMATION
Please specify the following
when ordering: 0 Sprinkler Mode! Number U K-Factor U Sprinkler Finish
U Style U Thread Size U Escutcheon Finish
U Temperature Rating 0 Quantity U Wrench Model Number
Always read and understand installation, care, and maintenance instructions, supplied with each box of sprinklers, before proceeding with installation
of any sprinklers.
Always wear safety glasses and foot protection.
Depressurize and drain the piping system before attempting to install, remove, or adjust any Victaulic piping products. . 0 • Installation rules, especially those governing obstruction, must be strictly followed.
Painting, plating, or any re-coating of sprinklers (other than that supplied by Victaulic) is not allowed.
Failure to follow these instructions could result in serious personal injury and/or property damage.
The owner is responsible for maintaining the fire protection system and devices in proper operating condition. For minimum maintenance and inspection requirements, refer to the
current National Fire Protection Association pamphlet that describes care and maintenance of sprinkler systems. In addition, the authority having jurisdiction may have additional
maintenance, testing, and inspection requirements that must be followed.
If you need additional copies of this publication, or if you have any questions about the safe installation of this product, contact Victaulic World Headquarters, P.O. Box 31, Easton,
Pennsylvania 18044.0031, 610-559-3300.
40.10-2
I
DIMENSIONS 17/1
(37 mm)
2W
(60 mm) 1%"
(41 mm)
ø— v.4
(25 mm)
Standard Pendent - V2707, V2708
1W
2W (41 mm)
(60 mm)
Standard Upright. V2703, V2704
1_2W (80 mm)
Max. Hole
r
Min. Hole
2" (51 mm
Typical Calling Tile (27 mm)
(17 mm) (
1"Aa" Finished Surface (30 mm)
______________ MAXIMUM RECESS
215W
(75 mm)
MAXIMUM EXTENSION
½" Adjustment
Recessed - V2707, V2708
(Drawing not to scale)
2W (60 mm)
Max. Hole
2" (51 mm)
Mix. Hole
gum
Typical Ceding Tile
- Finished Surface
(24 mm)
MAXIMUM RECESS
- (75 mm)
MAXIMUM EXTENSION
-Y4" Adjustment
Recessed - V2707, V2708
(Drawing not to scale)
AVAILABLE WRENCHES
V27
Socket
V38 or V38-3
Recessed
V27
Open End
V2707, V2708 Pendent
V2707, V2708 Recessed Pendent
V2703, V2704 Upright
40.10-3
(24 mm)
1wx•
(43 mm)
DISTRIBUTION PATTERNS
MODELS V2107, V2708
K5.6 STANDARD PENDENT AND RECESSED PENDENT
DISTRIBUTION PATTERNS - TRAJECTORY
10' I I I I I I I I I 3,0 in
8' 2,4 m
7psi 48 kPa
6'
1,8 m
15 psi
103 kPa
4,
1,2 m
30 psi -------
207 kPa
2- 0,6 m
0
0,6 m 1,2 a, 1,8 m 2,4 m 3,0 m 3,7 m 4,3 m
MODELS V2703, V2704
K5.6 STANDARD UPRIGHT DISTRIBUTION PATTERNS - TRAJECTORY
m
-------\—
m
_\
M -
-
M -
0,6m 1,2m 1,8m 2,4m 3,0m 3,7m 4,3m 4,9m
NOTES:
Data shown is approximate and can vary due to differences in installation.
These graphs illustrate approximate trajectories, floor-wetting, and wall-wetting patterns for these specific Victaulic FireLock Automatic Sprinklers. They are
provided as information for guidance In avoiding obstructions to sprinklers and should not be used as minimum sprinkler spacing rules for installation. Refer to
the appropriate NFPA National Fire Code and the authority having jurisdiction for specific information regarding obstructions, spacing limitations and area of
coverage requirements. Failure to follow these guidelines could adversely affect the performance of the sprinkler and will void all Listings. Approvals and War-
ranties.
All patterns are symmetrical to the centerline of the waterway.
WARRANTY Refer to the Warranty section
of the current Price List or
contact Victaulic for details.
This product shalt be ranutactired by Victaulic Company. PJI products to be installed in accordance with current Victauhc installation/assembly instructions.
Victaulic reserves the right to change product specifications, designs and standard equipnmnt without notice and without incirring obligations.
40.10-4
10'
3,0m
8 2,4
6
1,8
4
1,2
2 0,6
a
7 psi
48 kPa
15 psi
103 kPa
30 psi 207 kPa