Press Alt + R to read the document text or Alt + P to download or print.
This document contains no pages.
HomeMy WebLinkAbout5928 FARNSWORTH; ; AS150270; PermitCity of Carlsbad
Sprinkler Permit
Permit No: AS150270
5928 FARNSWORTH
Job Address:
CT
Permit Type: SPRINK
Parcel No: 2120701000
Lot #: 0
Reference No.:
PC #:
Status: ISSUED
Applied 9/10/2015
Approved: 9/24/2015
Issued: 9/24/2015
Inspector:
Project Title: BLDG C OFFICE Tenant Improvement to existing 1st and 2nd floor
office space
Applicant:
ACTION FIRE SYSTEMS CO INC
9185 HARNESS ST
SPRING VALLEY CA
619-462-9210
Owner:
CARLSBAD TECHNOLOGY INC
0/0 ANDY CHENG
5922 FARNSWORTH CT
CARLSBAD CA
Fees ($) Add'l Fees ($) Total ($) Balance ($)
283 0 283 0
AS150270
Page 1 of 4
N I KJ NG* 8 MICROFAST® QUICK
RESPONSE UPRIGHT
SPRINKLER VK300 (K5.6)
The Viking Corporation, 210 N Industrial Park Drive, Hastings Ml 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
DESCRIPTION
The Viking Microfast® Quick Response Upright Sprinkler VK300 is a small,
thermosensitive, glass-bulb spray sprinkler available in several differ-
ent finishes and temperature ratings to meet design requirements. The spe-
cial Polyester and Electroless Nickel PTFE (ENT) coatings can be used in
decorative applications where colors are desired. In addition, these coat-
ings have been investigated for installation in corrosive atmospheres and
are listed/approved as corrosion resistant as indicated in the Approval
Charts. (Note: FM global approves the ENT coating as corrosion resistant. FM
Global has no approval classification Polyester coatings as corrosion resistant.)
LISTINGS AND APPROVALS
cULus Listed: Category VNIV
FM Approved: Classes 2002 and 2020
Refer to Approval Chart 1 and Design Criteria on for cULus Listing requirements and refer to Approval Chart 2 and Design Criteria
FM Approval requirements that must be followed.
3. TECHNICAL DATA
Specifications:
Minimum Operating Pressure: 7 psi (0.5 bar)*
Maximum Working Pressure: 175 psi (12 bar) wwp.
Factory tested hydrostatically to 500 psi (34.5 bar)
Testing: U.S.A. Patent No. 4,831,870
Thread size: 1/2" NPT, 15 mm BSP
Nominal K-Factor: 5.6 U.S. (80.6 metric**)
Glass-bulb fluid temperature rated to -65 °F (-55 °C)
Overall Length: 2-3/16" (56 mm)
*CULUS Listing, FM Approval, and NFPA 13 installs require a minimum of 7 psi (0.5 bar). The minimum operating pressure for LPCB and CE
Approvals ONLY is 5 psi (0.35 bar).
Material Standards:
Frame Casting: Brass UNS-C84400 or QM Brass Viking Technical Data may be found on
Deflector: Brass UNS-C23000 or Copper UNS-C19500 The Viking Corporation's Web site at
Bulb: Glass, nominal 3 mm diameter http://www.vikinggroupinc.com.
Belleville Spring Sealing Assembly: Nickel Alloy, coated on both sides with The Web site may include a more recent PTFE Tape
Screw Brass UNS-C36000 edition of this Technical Data Page.
Pip Cap and Insert Assembly: Copper UNS-C11000 and Stainless Steel UNS-
S30400
For Polyester Coated SrinkIers: Belleville Spring-Exposed
For ENT Coated Sprinklers: Belleville Spring-Exposed, Screw and Pipcap - ENT plated
Ordering Information: (Also refer to the current Viking price list.)
Order Viking Microfast® Quick Response Upright Sprinkler VK300 by first adding the appropriate suffix for the sprinkler finish and
then the appropriate suffix for the temperature rating to the sprinkler base part number.
Finish Suffix: Brass = A, Chrome = F, White Polyester = M-/W, Black Polyester = M-/B, and ENT = JN
Temperature Suffix (°F/°C): 135°/57° =A, 155°/68° = B, 175°/79° = D, 200°/93° E, and 286°/141° = G
For example, sprinkler VK300 with a 1/2" NPT thread, Brass finish and a 155 °F/68 °C temperature rating = Part No. 12978AB
Available Finishes And Temperature Ratings: Refer to Table 1.
Accessories: (Also refer to the "Sprinkler Accessories" section of the Viking data book.)
Sprinkler Wrench: Standard Wrench: Part No. 10896W/B (available since 2000)
Sprinkler Cabinets:
Six-head capacity: Part No. 01724A (available since 1971)
Twelve-head capacity: Part No. 01725A (available since 1971)
4. INSTALLATION
Refer to appropriate NFPA Installation Standards.
Form No. F_052114 Rev 15.1 (Corrected K-factor on P/N 06661 B, Page 3)
Page 2 of 4
'J IKII1GI MICROFAST® QUICK
lsl:lI['i ,7w RESPONSE UPRIGHT
SPRINKLER VK300 (K5.6)
The Viking Corporation, 210 N Industrial Park Drive, Hastings Ml 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
OPERATION
During fire conditions, the heat-sensitive liquid in the glass bulb expands, causing the glass to shatter, releasing the pip cap and
sealing spring assembly. Water flowing through the sprinkler orifice strikes the sprinkler deflector, forming a uniform spray pattern
to extinguish or control the fire.
INSPECTIONS, TESTS AND MAINTENANCE
Refer to NFPA 25 for Inspection, Testing and Maintenance requirements.
AVAILABILITY
The Viking Microfast5 Quick Response Upright Sprinkler VK300 is available through a network of domestic and international distributors.
See The Viking Corporation web site for the closest distributor or contact The Viking Corporation.
GUARANTEE
For details of warranty, refer to Viking's current list price schedule or contact Viking directly.
TABLE 1: AVAILABLE SPRINKLER•Iiil;ATURE RATINGS AND FINISHES
Sprinkler Temperature Sprinkler Nominal Maximum Ambieni Bulb Color :Cl assificátion . Temperature Rating' CeilingTemperaturé2
Ordinary 135 F (57 C) 100 °F (38 °C) Orange
Ordinary 155 ¶ (68 °C) 100 °F (38 °C) Red
Intermediate 175 °F (79 °C) 150 °F (65 °C) Yellow
Intermediate 200 °F (93 °C) 150 °F (65 °C) Green
High 286 °F (141 C) 225 °F (107 C) Blue
Sprinkler Finishes: Brass, Chrome, White Polyester, Black Polyester, and ENT
Corrosion-Resistant Coatings': White Polyester, Black Polyester, and Black PTFE. ENT in all temperature ratings except 135 °F (57 C)
Footnotes
1 The sprinkler temperature rating is stamped on the deflector.
2 Based on NFPA-13. Other limits may apply, depending on fire loading, sprinkler location, and other requirements of the Authority Having Jurisdiction.
Refer to specific installation standards.
The corrosion-resistant coatings have passed the standard corrosion test required by the approving agencies indicated in the Approval Charts. These
tests cannot and do not represent all possible corrosive environments. Prior to installation, verify through the end-user that the coatings are compat-
ible with or suitable for the proposed environment. For automatic sprinklers, the coatings indicated are applied to the exposed exterior surfaces only.
Note that the spring is exposed on sprinklers with Polyester, ENT, and PIFE coatings. For ENT coated automatic sprinklers, the waterway is coated.
Protective Sprinkler Cap-
Wrench Flat
Figure 1:
Standard Sprinkler Wrench 10896W/B
Form No. F_052114 Rev 15.1
Page 3 of 4
NlKjw4ja -
MICROFAST® QUICK
RESPONSE UPRIGHT
SPRINKLER VK300 (K5.6)
The Viking Corporation, 210 N Industrial Park Drive, Hastings Ml 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcsvikinqcorp.com
ApprovaiCharti (UL) TsmP6rawre KEY
McrofastQuick Response Eutcheon EAX (5 appli..abj Uprignt Sjirinkler VK300
MaxirTlum 175 PSI (12 bar) WJVP
Base Part Thread Size Nominal K-Factor Overall Length Listings and Approvals' SIN Number1 NPT I BSP U.S. Tnrl Inches mm cULus VdS LPCB (E
12978 VK300 1/2' 15 mm 5.6 1 80.6 2-3/16 56 Al, B2 -- --
L.11f Availabilityt77 Local Viking 1iIt
06661B VK300 1/2" 1 15 mm 1 5.6 1 80.6 11 2-3/16 56 1 Al, B2 -- I -- --
Approved Temperature Ratings Approved Finishes A - 135 °F (57 °C), 155 °F (68 °C) 175 °F (79 °C), 200 °F (93 °C), and 1 - Brass, Chrome, White Polyester56, and Black Polyester5'6 286 °F (141°C) 2 - ENT6 B - 155 °F (68 °C), 175 °F (79 °C), 200 °F (93 °C), and 286 °F (141°C)
Footnotes
1 Base part number is shown. For complete part number, refer to Viking's current price schedule.
2Metric K-factor measurement shown is when pressure is measured in Bar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0.
'This table shows the listings and approvals available at the time of printing. Check with the manufacturer for any additional approvals.
Listed by Underwriters Laboratories Inc. for us in the U.S. and Canada
Other colors are available on request with the same Listings and Approvals as the standard colors.
6 cULus Listed as corrosion resistant.
DESIGN CRITERIA UL
(Also refer to Approval Chart 1 above)
cULus Listing Requirements:
The Viking Microfast® Quick Response Upright Sprinkler VK300 is cULus Listed as indicated in Approval Chart 1 for installation in accordance with the
latest edition of NFPA 13 for standard spray sprinklers.
Designed for use in Light and Ordinary Hazard occupancies.
The sprinkler installation rules contained in NFPA 13 for standard spray upright sprinklers must be followed.
IMPORTANT: Always refer to Bulletin Form No. F_091699 - Care and Handling of Sprinklers. Also refer to page
QRI-3 for general care, installation, and maintenance information. Viking sprinklers are to be installed in ac-
cordance with the latest edition of Viking technical data, the appropriate standards of NFPA, FM Global, LPCB,
APSAD, VdS or other similar organizations, and also with the provisions of governmental codes, ordinances, and
standards, whenever applicable.
Form No. F_052114 Rev 15.1
Page 4 of 4
NlKjw4 MICROFAST@ QUICK
RESPONSE UPRIGHT
SPRINKLER VK300 (K5.6)
The Viking Corporation, 210 N Industrial Park Drive, Hastings Ml 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Approval Chart 2r (FM) Thmp KEY
Microfast Quick Response
Upright Sprinkler VK300
(5 eppcbe)
Maximum 175 PSI (12ba) WWP
Base Part Thread Size Nominal K-Factor Overall Length FM Approvals'
Number' SIN (Refer also to Design Criteria below.) NPT BSP U.S. metric Inches mm
12978 VK300 1/2" 15 mm 5.6 80.6 2-3/16 56 Al, B2
NOTICE flProduct IJTaLocal Viking t•JilT
06661B VK300 1/2" 1 15 mm 5.6 80.6 2-3/16 56 Al, B2
Approved Temperature Ratings Approved Finishes 1 -Brass, Chrome, White Polyester', and Black °C), °C), °C), °C), A- 135°F (57 155°F (68 175°F (79 200°F (93 and 286°F (141°C) Polyester' B - 155 °F (68 °C), 175 °F (79 °C), 200 °F (93 °C), and 286 °F (141°C) 2 - ENT6
Footnotes
1 Base part number is shown. For complete part number, refer to Viking's current price schedule.
2Metric K-factor measurement shown is when pressure is measured in Bar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0.
3This table shows the FM Approvals available at the time of printing. Check with the manufacturer for any additional approvals.
Other colors are available on request with the same Approvals as the standard colors.
FM approved as corrosion resistant.
DESIGN CRITERIA FM
(Also refer to Approval Chart 2 above
FM Anoroval Requirements:
The Microfast® Quick Response Upright Sprinkler VK300 is FM Approved as a quick response Non-Storage upright sprinkler as indicated in the FM
Approval Guide. For specific application and installation requirements, reference the latest applicable FM Loss Prevention Data Sheets (including Data
Sheet 2-0). FM Global Loss Prevention Data Sheets contain guidelines relating to, but not limited to: minimum water supply requirements, hydraulic
design, ceiling slope and obstructions, minimum and maximum allowable spacing, and deflector distance below the ceiling.
NOTE: The FM installation guidelines may differ from cULus and/or NFPA criteria.
IMPORTANT: Always refer to Bulletin Form No. F_091699 - Care and Handling of Sprinklers. Also refer to page
QRI-3 for general care, installation, and maintenance information. Viking sprinklers are to be installed in ac-
cordance with the latest edition of Viking technical data, the appropriate standards of NFPA, FM Global, LPCB,
APSAD, VdS or other similar organizations, and also with the provisions of governmental codes, ordinances, and
standards, whenever applicable.
Form No. F_052114 Rev 15.1 (Corrected K-factor on P/N 06661 B, Page 3)
Page 1 of 6
MIRAGE® STANDARD AND
QR CONCEALED PENDENT "4J II(IF t1Gi® SPRINKLER VK462 AND HP
SPRINKLER VK463 (K5.6)
The Viking Corporation, 210 N Industrial Park Drive, Hastings Ml 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs©vikingcorp.com
1. DESCRIPTION
Viking Mirages Standard and Quick Response Concealed Pendent Sprinkler VK462
and HP Sprinkler VK463 are thermosensitive glass-bulb spray sprinklers designed for
installation on concealed pipe systems where the appearance of a smooth ceiling is
desired.
The sprinkler is pie-assembled with a threaded adapter for installation with a low-pro-
file cover assembly that provides up to 1/2 (12.7 mm) of vertical adjustment. The two-
piece design allows installation and testing of the sprinkler prior to installation of the
cover plate. The "push-on", "thread-off' design of the concealed cover plate assembly
allows easy installation of the cover plate after the system has been tested and the
ceiling finish has been applied. The cover assembly can be removed and reinstalled,
allowing temporary removal of ceiling panels without taking the sprinkler system out
of service or removing the sprinkler. The Electroless Nickel PTFE (ENT) coating has
been investigated for installation in corrosive atmospheres and is cULus Listed as cor-
rosion resistant as indicated in the Approval Charts. The ENT finish is only available
fnr +ha onrr,L'Inr eeamkIii th rrn,nr l,,+n it, nn+ nl,,+mr4 fl/I U l IIIIflII Ci0OI I lilly, 11ICU 10 I Lii 1J1LiLLi14. I - I Viking Technical Data may be found on
The Viking Corporation's Web site at
http:IIwww.vikinggroupinc.com.
The Web site may include a more recent
edition of this Technical Data Page.
LISTINGS AND APPROVALS
cULus Listed: Category VNIV
FM Approval: Class 2015
NYC Approved: MEA 89-92-E, Volume 32
VdS Approved: Certificate G4080021
LPCB Approved: Ref. No. 096e/12
CE Certified: Standard EN 12259-1, EC-certificate of conformity 0832-CPD-2032
CCCF Approved: Approved by the China Certification Center for Fire Products (CCCF)
Refer to Approval Chart 1 Design Criteria for cULus Listing requirements, and refer to Approval Chart 2 and Design Criteria
on page for FM Approval requirements that must be followed.
3. TECHNICAL DATA
Specifications:
Available since 2006.
Minimum Operating Pressure: 7 psi (0.5 bar)*
Maximum Working Pressure: Sprinkler VK463 is rated for use with water working pressures ranging from the minimum
7 psi (0.5 bar) up to 250 psi (17.2 bar) for high-pressure systems. High-pressure (HP) sprinklers can be identified by
locating "250" stamped on the deflector. Sprinkler VK462 is rated to a maximum 175 psi (12 bar) wwp.
Factory tested hydrostatically to 500 psi (34.5 bar)
Thread size: 1/2" (15 mm) NPT
Nominal K-Factor: 5.6 U.S. (80.6 metrict)
Glass-bulb fluid temperature rated to -65°F (-55°C)
Patents Pending
*cULus Listing, FM Approval, and NFPA 13 installs require a minimum of 7 psi (0.5 bar). The minimum operating pressure for LPCB and CE
Approvals ONLY is 5 psi (0.35 bar).
tMetric K-factor measurement shown is when pressure is measured in Bar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0.
Material Standards:
Sprinkler Body: Brass UNS-C84400
Deflector: Copper UNS-C 19500 for Sprinkler VK462
Phosphor Bronze UNS-051000 for Sprinkler VK463
Deflector Pins: Stainless Steel Alloy
Bulb: Glass, nominal 3 mm diameter
Pip Cap and Insert Assembly: Copper UNS-C11000 and Stainless Steel UNS-530400
Button: Brass UNS-C36000
Screws: 18-8 Stainless Steel
Belleville Spring Sealing Assembly: Nickel Alloy, coated on both sides with Teflon Tape
Yoke: Phosphor Bronze U N S-051 000
Cover Adapter: Cold Rolled Steel UNS-G10080, Finish: Clear Chromate over Zinc Plating
Form No. F_103005 Rev 15.1 (Added CCCF Approval)
Page 2 of 6
MIRAGE® STANDARD AND
4J IF(1I1Gi i:II[.u'ytIf. QR CONCEALED PENDENT
SPRINKLER VK462 AND HP
SPRINKLER VK463 (K5.6)
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Cover Assembly Materials:
Cover: Copper UNS-C11000
Base: Brass UNS-C26000 or UNS-C26800
Springs: Nickel Alloy
Solder: Eutectic
Ordering Information: (Also refer to the current Viking price list.)
Viking Mirage® Standard and Quick Response Concealed Pendent Sprinklers and Cover Plate Assemblies must be ordered separately:
Sprinkler: Base Part No. VK462 - 13503A for Brass finish and 13503JN for ENT finish. VK463 - HP Base Part No. 13667A
Specify sprinkler temperature rating by adding the appropriate suffix for the temperature rating to the base part number:
Temperature Suffix: 155 °F (68 °C) = B, 175 °F (79 °C) = D, 200 °F (93 °C) = E
For example, sprinkler VK463 with a 155 °F (68 °C) temperature rating = 13667AB.
Cover Plate Assembly: Base Part No. 13504 (2-3/4" diameter), Base Part No. 13642 (3-5/16" diameter), or Base Part No. 15394
(square cover plate, 3-5/16" diameter)
Specify finish and temperature rating of the cover plate assembly by adding the appropriate suffixes for the finish and the cover
temperature rating to the base part number:
Finish Suffix: Polished Chrome = F, Brushed Chrome = F-/B, Bright Brass = B, Antique Brass = B-/A, Brushed Brass = B-/B,
Brushed Copper = E-/B, Painted White = M-/W, Painted Ivory = M-/l, Painted Black = M-/B
Temperature Suffix: 135 °F (57 °C) UL (139°F (59 °C) FM and LPCB) = A, 165 °F (74 °C) = C
For example, cover 13504 with a Polished Chrome finish and a 165 °F (74 °C) temperature rating = 13504FC.
Note: Square cover plate 15394 cULus Listing is for the 135°F (57 °C) temperature rated cover plate only. Refer to the Approval Chart.
Available Finishes And Temperature Ratings: Refer to Table 1.
Accessories: (Also refer to the "Sprinkler Accessories" section of the Viking data book.)
Sprinkler Wrenches**:
Heavy Duty Wrench Part No. 14047W/B (available since 2006), or
Head Cabinet Wrench Part No. 14031°°° (available since 2006)
Optional Concealed Cover Plate Installer Tool Part No. 14412 for cover 13504, or Part No. 14867 for the large diameter cover
(available since 2007) —Requires a %" ratchet (not available from Viking). —Optional for removal of the protective cap. Ideal for sprinkler cabinets.
Sprinkler Cabinet: Part No. 01731A (available since 1971)
INSTALLATION
Refer to appropriate NFPA Installation Standards.
OPERATION
During fire conditions, when the temperature around the sprinkler approaches its operating temperature, the cover plate detaches.
Continued heating of the exposed sprinkler causes the heat-sensitive liquid in the glass bulb to expand and the bulb to shatter,
releasing the yoke, pip-cap and sealing spring assembly. Water flowing through the sprinkler orifice strikes the sprinkler deflector,
forming a uniform spray pattern to extinguish or control the fire.
INSPECTIONS, TESTS AND MAINTENANCE
Refer to NFPA 25 for Inspection, Testing and Maintenance requirements.
AVAILABILITY
Viking Sprinklers VK462 and VK463 are available through a network of domestic and international distributors. See The Viking
Corporation web site for the closest distributor or contact The Viking Corporation.
GUARANTEE
For details of warranty, refer to Viking's current list price schedule or contact Viking directly.
Form No. F_103005 Rev 15.1
Page 3 of 6
MIRAGE® STANDARD AND
QR CONCEALED PENDENT "i4J II(II,416 ®TECHNICAL DATA SPRINKLER VK462 AND HP
SPRINKLER VK463 (K5.6)
The Viking Corporation, 210 N Industrial Park Drive, Hastings Ml 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcsvikingcorp.com
TABLE 1: AVAILABLE SPRINKLER TEMPERATURE RATINGS AND FINISHES
Sprinkler Temperature Sprinkler Nominal Maximum A'riibient I Temperature Rating of Cover Bulb Color Classifiëation Temperature Rating' Ceiling lempératüre2 Assembly (Required)
Ordinary 155 OF (68° C) 100 OF (38 °C) 139 °F(59 FF and LPCB Red
Intermediate 175 OF (79 °C) 150 OF (65 °C) 165 °F (74 °C) Yellow
Intermediate 200 °F (93 °C) 150 OF (65 °C) 165 OF (74 °C) Green
Cover Plate Finishes: Polished Chrome, Brushed Chrome, Bright Brass, Antique Brass, Brushed Brass, Brushed Copper, Painted White, Painted
Ivory, or Painted Black
Sprinkler Finishes: Brass and ENT
Corrosion Resistant Coatings': ENT
Footnotes
The sprinkler temperature rating is stamped on the sprinkler deflector.
2 Based on NFPA-1 3. Other limits may apply, depending on fire loading, sprinkler location, and other requirements of the Authority Having Jurisdiction.
Refer to specific installation standards.
The corrosion resistant coatings have passed the standard corrosion test required by the approving agencies indicated in the Approval Charts. These
tests cannot and do not represent all possible corrosive environments. Prior to installation, verify through the end-user that the coatings are compat-
ible with or suitable for the proposed environment. For automatic sprinklers, the ENT coating is applied to all exposed exterior surfaces, including
the waterway, but the Belleville spring is exposed.
Approval Chart I (UL)
Mirage'ConcealedPendentSprinklers VK462 and VK463 L±-* CoverPa Fn KEY
NPT Thread Nominal Maximum Listings and Approvals4 Sprinkler SIN Size K-Factor Water Working (Refer also to Design Criteria)
Inch mm J.S. metric2 cULus5 NYC VdS7 LPCB Base Part No.1 Pressure
Standard Response Applications
-- I -- AY1, CZ1 I AY1, BZ1 AY1, CZ18 AV1, CW1 13503A I VK462 ] 1/2" I 15 5.6 80.6 175 psi (12 bar) I
Quick Response Applications
13503A VK462 1/2" 15 5.6 80.6 175 psi (12 bar) AV1, BX1 AV1, BW16 - - -- --
13503JN11 VK462 1/2" 15 5.6 80.6 175 psi (12 bar) AV1, BX1 AV1, BW16 - - -- --
13667A VK463 1/2" 15 5.6 80.6 1 250 psi (17.2 bar)3 AV1, BX1 AV1, BW16 -- -- -- --
Cover Plate Assembly Temperature Ratings'
Sprinkler Temperature Ratings V - 135 OF(570) cULus Listed cover 135041, 136421 (large dram-
eter), or 153941 (square cover Finishes" Cover Plate Assembly Finishes
A 155 OF (68 °C) W - 165°F (74 °C) cover 135041 or 136421 (large diameter) 1 - Polished Chrome, Brushed Chrome, Bright Brass,
B -175°F (79 °C) and 200°F (93 °C) x - 165°F (74 °C) cover 135041, or 136421 (large diameter) Antique Brass, Brushed Brass, Brushed Copper,
C -200°F (93 °C) Y - 135°F (57 °C) cover 135041 LPCB Approved as 139°F (59 °C) Painted White, Painted Ivory, or Painted Black
Z - 165 OF (74 °C) cover 135041
Footnotes
Part number shown is the base part number. For complete part number, refer to current Viking price list schedule.
2 Metric K-factor measurement shown is when pressure is measured in Bar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0.
The Water Working Pressure rating is stamped on the deflector.
This chart shows the listings and approvals available at the time of printing. Other approvals may be in process. Check with the manufacturer for any additional ap-
provals.
Listed by Underwriter's Laboratories for use in the U.S. and Canada.
6 Accepted for use, City of New York Department of Buildings, MEA Number 89-92-E, Vol. 32.
VdS Approved, standards VdS 2344:2005-12, VdS 2100-25:2008-01, and EN 12259-1:1999 + A1:2001 + A2:2004 + A3:2006, Certificate G4080021.
8 ((Certified, Standard EN 12259-1, EC-certificate of conformity 0832-CPD-2032.
9 The 135/139°F cover has an orange label. The 165°F (74 °C) cover has a white label.
°Painted finish consists of Polyester Baked Enamel. Other paint colors are available on request with the same listings as the standard paint colors. Listings and approv-
als apply for any paint manufacturer. Contact Viking for additional information.
cULus Listed as corrosion resistant.
NOTE: Custom colors are indicated on a label inside the cover assembly. Refer to Figure 1.
Form No. F103005 Rev 15.1
Page 4 of 6
MIRAGE® STANDARD AND
QR CONCEALED PENDENT N I I(I I16i® SPRINKLER VK462 AND HP
SPRINKLER VK463 (K5.6)
The Viking Corporation, 210 N Industrial Park Drive, Hastings Ml 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
DESIGN CRITERIA - UL
(Also refer to Approval Chart 1)
cULus Listing Requirements:
Mirage® Concealed Pendent Sprinklers VK462 and VK463 are cULus Listed as quick response for installation in accordance with the latest edition of
NFPA 13 for standard coverage pendent spray sprinklers as indicated below.
For hazard occupancies up to and including Ordinary Hazard, Group II.
Protection areas and maximum spacing shall be in accordance with the tables provided in NFPA 13. Maximum spacing allowed is 15 ft. (4.6 m).
Minimum spacing allowed is 6 ft. (1.8 m) unless baffles are installed in accordance with NFPA 13.
Minimum distance from walls is 4 in. (102 mm).
Maximum distance from walls shall be no more than one-half of the allowable distance between sprinklers. The distance shall be measured
perpendicular to the wall.
The sprinkler obstruction rules contained in NFPA 13 for standard coverage pendent spray sprinklers must be followed.
NOTE: Concealed sprinklers must be installed in neutral or negative pressure plenums only.
VdS Anoroval Requirements: •
The sprinkler can be installed in a concrete ceiling (massive ceiling) or in a false ceiling made of light materials.
This sprinkler is deflector fixed type and can be only activated by heat. The housing is not tight.
Follow installation guidelines of current standards, CEA4001VdS and EN12845. These sprinklers can only be installed in LH and OH occupan-
cies, except in OH4.
NOTES: Due to the design the sprinkler type Domed-CCP' shall not be installed in false ceilings in which the false ceiling space is protected by a
water extinguishing system.
Due to the design the sprinkler type 'Domed-CCP' shall not be installed in false ceilings in which during a fire the pressure above the false ceiling
may be assumed to be higher than the pressure below the false ceiling.
The criterion for the dropping of the cover relevant for this approval is heat.
Steps of installation:
Prepare the sprinkler key.
Remove the plastic cover.
Hold the sprinkler with the wrench and fasten it.
Replace the plastic cover and do not remove until the cover is installed.
IMPORTANT: Always refer to Bulletin Form No. F_091699 - Care and Handling of Sprinklers. Also refer to page
SRI-3 or QRI-3 for general care, installation, and maintenance information. Viking sprinklers are to be installed
in accordance with the latest edition of Viking technical data, the appropriate standards of NFPA, LPCB, APSAD,
VdS or other similar organizations, and also with the provisions of governmental codes, ordinances, and stan-
dards, whenever applicable.
CUSTO4
CL-
Iclervificution of Custom Point Color:
All custom color painted co/e( plates wilt
have an identifying label affixed to the
inside of the cover that indicates custom
color and will have a representative sample
(a paint dot) of the paint on the label,
Figure 1: Identification of Custom Paint Color for Concealed Covers
Form No. F_103005 Rev 15.1
00 NOT PAINT
3-5/16" (84.1
Figure 2: Square Cover Assembly 15394
S r.
Page 5 of 6
MIRAGE® STANDARD AND
QR CONCEALED PENDENT "J I KI NC* SPRINKLER VK462 AND HP
SPRINKLER VK463 (K5.6)
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Approval Chart 2 (FM)
Mirage Standard Response Concealed Pendent Sprinkler VK462 er Plat~ FiNsh KEY
Sprinkler Base NPT Thread Size Nominal K-Factor Maximum FM Approvals'
Part No.' SIN Water Working (Refer also to Design Criteria below.) Inch mm U.S. metric2 Pressure
13503A VK462 1/2" 15 5.6 80.6 175 psi (12 bar) AWl, BX1
Cover Plate Assembly Temperature Ratings4 Cover Plate Assembly Finishes5
Sprinkler Temperature Ratings W - 139 °F (59 °C) cover 135041, 136421 (large diameter), 1 - Polished Chrome, Brushed Chrome, Bright
A- 155°F (68 °C) or 153941 (square cover plate) Brass, Antique Brass, Brushed Brass,
B -175°F (79 °C) and 200°F (93 °C) X - 165°F (74 °C) cover 135041, 136421 (large diameter), or Brushed Copper, Painted White, Painted
153941 (square cover plate) Ivory, or Painted Black
Footnotes
1 Part number shown is the base part number. For complete part number, refer to current Viking price list schedule.
2 Metric K-factor measurement shown is when pressure is measured in Bar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0.
This chart shows the FM Approvals available at the time of printing. Other approvals may be in process. Check with the manufacturer for any additiona
approvals.
The 139 °F (59 °C) cover has an orange label. The 165 °F (74 °C) cover has a white label.
Painted finish consists of Polyester Baked Enamel. Other paint colors are available on request with the same listings as the standard paint colors.
Listings and approvals apply for any paint manufacturer. Contact Viking for additional information.
NOTE: Custom colors are indicated on a label inside the cover assembly. Refer to Figure 1.
DESIGN CRITERIA - FM
(Also refer to Approval Chart 2 above)
FM Approval Requirements:
Viking Concealed Pendent Sprinkler VK462 is FM Approved as a standard response Non-Storage concealed pendent sprinkler as indicated in the FM
Approval Guide. For specific application and installation requirements, reference the latest applicable FM Loss Prevention Data Sheets (including Data
Sheet 2-0). FM Global Loss Prevention Data Sheets contain guidelines relating to, but not limited to: minimum water supply requirements, hydraulic
design, ceiling slope and obstructions, minimum and maximum allowable spacing, and deflector distance below the ceiling.
NOTE: The FM installation guidelines may differ from cULus and/or NFPA criteria.
IMPORTANT: Always refer to Bulletin Form No. F_091699 - Care and Handling of Sprinklers. Also refer to page
SRI-3 for general care, installation, and maintenance information. Viking sprinklers are to be installed in ac-
cordance with the latest edition of Viking technical data, the appropriate standards of NFPA, FM Global, LPCB,
APSAD, VdS or other similar organizations, and also with the provisions of governmental codes, ordinances, and
standards, whenever applicable.
Form No. F_103005 Rev 15.1
0
I'
Page 6 of 6
MIRAGE® STANDARD AND
QR CONCEALED PENDENT N4 I F(IFIGi SPRINKLER VK462 AND HP
SPRINKLER VK463 (K5.6)
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
diameter opening
2-1/4' (57.2 mm)
is required in
the ceiling. 7\1
- Sprinkler and
Adapter Assembly
(Protective Cap
is removed For
installation--use
Wrench 14031)K*)
Sprinkler
Frame
Arms
Sprinkler
Wrench
Flat
Step 1: Carefully slide the
wrench sideways around
the deflector and pins.
Step 2: Carefully press the
wrench upward and turn slightly
to ensure engagement with the
sprinkler wrench Flats.
DO NOT apply more than
25 Ft. tbs. of torque. A leak
tight seal should be achieved
by turning the sprinkler
clockwise 1 to 1-1/2 turns
beyond Finger tight.
Sprinkler
Wrench
(Part No.
4047
is shown)
A 1/2' ratchet
s required (not
,ilab(e From Viking)
NEVER install the sprinkler
by applying the installation
wrench across the Frame arms.
DO NOT overtighten.
Use only the designated
sprinkler wrench, Viking Part
Number 14047W/B or 14031.
Figure 3: Sprinkler Installation and Correct Use of Wrenches
NPT
(15 mm
_
2-
2-9/16' 116
Minimum
77.777771 +
II 1r1 2-3/4' (70 mm) or
3-5/16' (84,1 mm)
Note: Upon sprinkler activation, the deflector descends
to approximately 13/16' (20.6 mm) below the sprinkler body.
Figure 4: Sprinkler Dimensions and Cover Installation
Form No. F_103005 Rev 15.1 (Added CCCF Approval)