HomeMy WebLinkAbout5600 PASEO DEL NORTE; 105A; FPC2020-0015; PermitPERMIT REPORT
(L'City of
Carlsbad
Print Date: 01/05/2021
Job Address: 5600 PASEO DEL NORTE, # 105A,
Permit Type: FIRE-Construction Commercial
Parcel #: 2110222201
Valuation: $217,713.31
Occupancy Group:
#of Dwelling Units:
Bedrooms:
Bathrooms:
Project Title:
Description: KATE SPADE -SPRINKLER TI (55 HEADS)
Applicant:
JOHNSON CONTROL FIRE PROTECTION
MARCUS ENGLISH
3568 RUFFIN RD
SAN DIEGO, CA 92123-2597
(858) 633-9125
CARLSBAD, CA 92008-4441
Work Class: Fire Sprinklers
Track #:
Lot #:
Project #:
Plan #:
Construction Type:
Orig. Plan Check #:
Plan Check #:
Permit No: FPC2020-0015
Status: Closed - Finaled
Applied: 01/29/2020
Issued:
Finaled Close Out: 02/28/2020
Inspector:
Final Inspection:
FPContractor:
JOHNSON CONTROLS FIRE PROTECTION LP
P0 BOX 3042
BOCA RATON, FL 33431-0942
(561) 341-7780
FEE AMOUNT
FIRE NFPA 13 or 13R System 7 - 100 heads $553.00
Total Fees: $553.00 Total Payments To Date: $553.00 Balance Due: $0.00
Fire Department Page 1 of 1
1635 Faraday Avenue, Carlsbad CA 92008-7314 1 760-602-4665 1 760-602-8561 f I www.carlsbadca.gov
tqcao Worldwide Contacts I www.tyco-fire.com
Series RFII - 56 K-factor
"Royal Flush II" Concealed Pendent Sprinklers
Quick & Standard Response, Standard Coverage
General
Description
The TYCO Series RFll 5.6 K-factor,
"Royal Flush II" Concealed Pendent
Sprinklers Quick Response (3-mm
bulb) and Standard Response (5-mm
bulb), are decorative sprinklers fea-
turing a flat cover plate designed to
conceal the sprinkler. These sprinklers
are optimal for architecturally sensi-
tive areas such as hotel lobbies, office
buildings, churches, and restaurants.
Each sprinkler includes a Cover Plate!
Retainer Assembly and a Sprinkler!
Support Cup Assembly. The separa-
ble, two-piece assembly design pro-
vides the following benefits:
Allows installation of the sprinklers
and pressure testing of the fire pro-
tection system prior to installation of
a suspended ceiling or application of
the finish coating to a fixed ceiling.
Permits the removal of suspended
ceiling panels for access to building
service equipment without having
to first shut down the fire protection
system and remove sprinklers.
Provides for 1/2 in. (12,7 mm) of ver-
tical adjustment to allow a measure
of flexibility in determining the length
of fixed piping to cut for the sprinkler
drops.
IMPORTANT
Refer to Technical Data Sheet
TFP2300 for warnings pertaining to
regulatory and health information.
Always refer to Technical Data
Sheet TFP700 for the "INSTALLER
WARNING" that provides cautions
with respect to handling and instal-
lation of sprinkler systems and com-
ponents. Improper handling and
installation can permanently damage
a sprinkler system or its compo-
nents and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
Page 1 of 4
The Series RFll Sprinklers are shipped
with a Disposable Protective Cap. The
Protective Cap is temporarily removed
during installation and replaced to help
protect the sprinkler during ceiling
installation or finish. The tip of the Pro-
tective Cap can be used to mark the
center of the ceiling hole into plaster
board or ceiling tiles by gently pushing
the ceiling product against the Pro-
tective Cap. When ceiling installa-
tion is complete, the Protective Cap is
removed and the Cover Plate/Retainer
Assembly is installed.
As an option, the Series RFll Standard
Response (5-mm bulb) "Royal Flush II"
Concealed Pendent Sprinklers can be
fitted with a silicone Air and Dust Seal.
(Refer to Figure 5.) The Air and Dust
Seal is intended for sensitive areas
where it is desirable to prevent air and
dust from the area above the ceiling to
pass through the cover plate.
L'I.)tL.I
The Series RFll Concealed Pendent
Sprinklers described herein must be
installed and maintained in compliance
with this document and with the appli-
cable standards of the NATIONAL FIRE
PROTECTION ASSOCIATION (NFPA),
in addition to the standards of any
authorities having jurisdiction. Failure
to do so may impair the performance
of these devices.
The owner is responsible for maintain-
ing their fire protection system and
devices in proper operating condition.
The installing contractor or sprinkler
manufacturer should be contacted with
any questions.
Sprinkler
Identification
Number (SIN)
1Y3531 = 3 mm bulb
SEPTEMBER 2018
Technical
Data
Sprinkler Approvals
Approvals apply only to the service
conditions indicated in the Design Criteria
section.
TY3531 (3 mm Bulb) is UL Listed, C-UL
Listed and NYC Approved (MEA 353-
01-E) as Quick Response.
1Y3531 (3 mm Bulb) is VdS Approved
(Certificate No. G4090007).
TY3531 (3 mm Bulb) is FM and
LPCB Approved (Ref. No. 094a/10) as
Standard Response.
Note: FM and LPCB do not approve
concealed sprinklers for quick
response.
TY3551 (5 mm Bulb) is UL Listed, C-UL
Listed, FM Approved, LPCB Approved
(Ref. No. 094a/9), and NYC Approved
(MEA 353-01-E) as Standard Response.
Approvals for Air and Dust Seal
UL and C-UL Listed for use with the RFll
Standard Response Concealed Sprinkler
(TY3551)
Maximum Working Pressure
Maximum 250 psi (17,3 bar) by UL,
C-UL, and NYC
Maximum 175 psi (12,1 bar) by FM, VdS,
and LPCB
Temperature Rating
155°F (68°C) Sprinkler with
139°F (59°C) Cover Plate
200°F (93°C) Sprinkler with
165°F (74°C) Cover Plate
TFPI8I
THREAD INTO U RETAINER
SUPPORT WITH THREAD
CUP UNTIL 0 0 %- DIMPLES
MOUNTING
SURFACE IS EJECTION
FLUSH WITH SPRING
CEILING
SOLDER COVER
TABS (3) COVER PLATE/RETAINER PLATE
ASSEMBLY
FIGURE 1
MODEL RFII CONCEALED SPRINKLER
ASSEMBLY
1/2 NPT
FRAME
SUPPOR1
CUP WITE
ROLL FORIV
THREAD
GUIDE
PINS (2)
DEFLECTOR
SPRINKLER/SUPPORT CUP
ASSEMBLY
EALING
SEMBLY
CAP
BULB
IPRESSION
CREW
FLECTOR
ROPPED
POSITION)
TFP181
Page 2 of 4
Discharge Coefficient
K= 5.6 GPM/psi1'2 (80,6 LPM/bar112)
Adjustment
1/2 inch (12,7 mm)
Finishes
See the Ordering Procedure section.
Physical Characteristics
Frame ............................Bronze
Support Cup ...................Plated Steel
Guide Pins .................. Stainless Steel
Deflector ..........................Bronze
Compression Screw..................Brass
Bulb ............................... Glass
Cap .....................Bronze or Copper
Sealing Assembly.. Beryllium Nickel w/TEFLON
Cover Plate .........................Brass
Retainer............................Brass
Ejection Spring ..............Stainless Steel
Design
Criteria
The TYCO Series RFII 5.6 K-factor,
"Royal Flush II" Concealed Pendent
Sprinklers are intended for fire protec-
tion systems designed in accordance
with the standard installation rules
recognized by the applicable Listing
or Approval agency; for example, UL
Listing is based on NFPA 13 and VdS
Approval is based on the CEA 4001.
For more information on LPCB and VdS
Approvals, contact Johnson Controlss
at the following office:
Enschede, Netherlands
Telephone: 31-53-428-4444
Fax: 31-53-428-3377
The Series RFII Concealed Pendent
Sprinklers are only listed and approved
with the Series RFII Concealed Cover
Plates having a factory applied finish.
Do not use the Series RFII in applica-
tions where the air pressure above the
ceiling is greater than that below. Down
drafts through the Sprinkler/Support
Cup Assembly can delay sprinkler
operation in a fire situation.
Operation
When exposed to heat from a fire, the
Cover Plate, normally soldered to the
Retainer at three points, falls away to
expose the Sprinkler/Support Cup
Assembly.
The Deflector - supported by the
Guide Pins - then drops down to its
operational position.
The glass bulb contains a fluid that
expands when exposed to heat. When
the rated temperature is reached, the
fluid expands sufficiently to shatter the
glass bulb, activating the sprinkler and
allowing water to flow.
Installation
The TYCO Series RFII 5.6 K-factor,
"Royal Flush II" Concealed Pendent
Sprinklers must be installed in accor-
dance with this section.
General Instructions
Do not install any bulb-type sprinkler
if the bulb is cracked or there is a loss
of liquid from the bulb. With the sprin-
kler held horizontally, a small air bubble
should be present. The diameter of the
air bubble is approximately 1/16 inch
(1,6 mm) for the 155°F (68°C) and 3/32
inch (2,4 mm) for the 200°F (93°C) tem-
perature ratings.
A leak-tight 1/2 inch NPT sprinkler
joint should be obtained by applying a
minimum to maximum torque of 7 to 14
ft.-Ibs. (9,5 to 19,0 Nm). Higher levels
of torque can distort the sprinkler Inlet
with consequent leakage or impairment
of the sprinkler.
Do not attempt to compensate for
insufficient adjustment in the Sprinkler
by under- or over-tightening the Sprin-
kler/Support Cup Assembly. Re-adjust
the position of the sprinkler fitting to
suit.
Step 1. Install the sprinkler only in the
pendent position with the center-line
of the sprinkler perpendicular to the
mounting surface.
Step 2. Remove the Protective Cap.
Step 3. With pipe thread sealant
applied to the pipe threads, hand-
tighten the sprinkler into the sprinkler
fitting.
Step 4. Wrench-tighten the sprinkler
using only the RFII Sprinkler Wrench.
(Refer to Figure 3.) Apply the RFII
Sprinkler Wrench to the Sprinkler as
shown in Figure 3.
3/16" to 11/16 MANUFACTURER DEFLECTOR COVER PLATE
(4,8 to 17,5 mm) PRESET GAP IN DROPPED RETAINER
REFERENCE 3/32" (2,4 mm) POSITION ASSEMBLY
COVER PLATE
PROFILE DEPTH
DIMENSION B
3-1/4 inches (82,6 mm)
3/16 inches (4,8 mm)
COVER PLATE
DIAMETER
DIMENSION A
2-3/8 to 2-5/8 inches (60,3 to 66,7 mm)
1-3/4 to 2-1/4 inches (44,5 to 57,2 mm)
FIGURE 2
SERIES CONCEALED SPRINKLER INSTALLATION DIMENSIONS
TFPISI
Page 3 of 4
FACE OF
SPRINKLER
FITTING
SPRINKLER
SUPPORT CUP
ASSEMBLY
1/2 (12,7 mm)
THREADED
D ADJUSTMENT
FACE
OF CEILING,
RETAINING RING
MOUNTING
SURFACE
CLEARANCE HOLE
- DIAMETER -
DIMENSION C
Step 5. Replace the Protective Cap
by pushing it upwards until it bottoms
out against the Support Cup. (Refer
to Figure 4.) The Protective Cap helps
prevent damage to the Deflector and
Arms during ceiling installation and/or
finish. You can also use the Protective
Cap to locate the center of the clear-
ance hole by gently pushing the ceiling
material up against the center point of
the Protective Cap.
AYL•1tL•i
As long as the Protective Cap remains
in place, the system is considered "Out
of Service".
Step 6. After the ceiling has been
completed with the 2-1/2 in. (63,5 mm)
diameter clearance hole and in prep-
aration for installing the Cover Plate/
Retainer Assembly, remove and discard
the Protective Cap. Verify that the
Deflector moves up and down freely.
If the Sprinkler is damaged and the
Deflector does not move up and down
freely, replace the entire Sprinkler.
Do not attempt to modify or repair a
damaged sprinkler.
Step 7. When installing an Air and
Dust Seal, refer to Figure 5; otherwise,
proceed to Step 8. To attach the Air
and Dust Seal, verify the angle of the
outside edge of the seal is oriented
according to Figure 5. Start the edge of
the Retainer in the grooved slot of the
Air and Dust Seal and continue around
the retainer until the entire Air and Dust
Seal is engaged.
TFPI8I
Page 4 of 4
Step 8. Screw on the Cover Plate!
Retainer Assembly until the Retainer
(shown in Figure 2) or the Air and Dust
Seal (shown in Figure 5) contacts the
ceiling. Do not continue to screw on the
Cover Plate/Retainer Assembly so that
it lifts a ceiling panel out of its normal
position. If you cannot engage the
Cover Plate/Retainer Assembly with
the Support Cup or you cannot engage
the Cover Plate/Retainer Assembly suf-
ficiently to contact the ceiling, you must
reposition the Sprinkler Fitting.
Care and
Maintenance
The TYCO Series RFll 5.6 K-factor,
"Royal Flush II" Concealed Pendent
Sprinklers must be maintained and
serviced in accordance with this
section.
Before closing a fire protection system
main control valve for maintenance
work on the fire protection system
that it controls, obtain permission to
shut down the affected fire protection
system from the proper authorities
and notify all personnel who may be
affected by this action.
Absence of the Cover Plate/Retainer
Assembly can delay sprinkler opera-
tion in a fire situation.
When properly installed, there is a
nominal 3/32 in. (2,4 mm) air gap
between the lip of the Cover Plate and
the ceiling, as shown in Figure 2.
This air gap is necessary for proper
operation of the sprinkler. If the ceiling
requires repainting after sprinkler
installation, ensure that the new paint
does not seal off any of the air gap.
Do not pull the Cover Plate relative to
the Enclosure. Separation may result.
Sprinklers which are found to be
leaking or exhibiting visible signs of
corrosion must be replaced.
Automatic sprinklers must never be
painted, plated, coated, or other-
wise altered after leaving the factory.
Modified sprinklers must be replaced.
Sprinklers that have been exposed to
corrosive products of combustion, but
have not operated, should be replaced
if they cannot be completely cleaned
by wiping the sprinkler with a cloth or
by brushing it with a soft bristle brush.
Care must be exercised to avoid
damage to the sprinklers - before,
during, and after installation. Sprin-
klers damaged by dropping, striking,
wrench twist/slippage, or the like, must
be replaced. Also, replace any sprin-
kler that has a cracked bulb or that has
lost liquid from its bulb. (Ref. Installa-
tion Section.)
Exercise care to avoid damage to sprin-
klers before, during, and after instal-
lation. Replace sprinklers damaged
by dropping, striking, wrench twist-
ing, wrench slipping, or the like. Also,
replace any sprinkler that has a cracked
bulb or that has lost liquid from its bulb.
(Refer to the Installation section.)
If you must remove a sprinkler, do not
reinstall it or a replacement without
reinstalling the Cover Plate/Retainer
Assembly. If a Cover Plate/Retainer
Assembly becomes dislodged during
service, replace it immediately.
The owner is responsible for the
inspection, testing, and maintenance of
their fire protection system and devices
in compliance with this document, as
well as with the applicable standards
of the NATIONAL FIRE PROTECTION
ASSOCIATION, for example, NFPA 25,
in addition to the standards of any other
authorities having jurisdiction. Contact
the installing contractor or sprinkler
manufacturer regarding any questions.
Automatic sprinkler systems should be
inspected, tested, and maintained by a
qualified Inspection Service in accor-
dance with local requirements and/or
national code.
Limited
Warranty
For warranty terms and conditions, visit
www.tyco-fire.com.
Ordering
Procedure
Contact your local distributor for
availability. When placing an order,
indicate the full product name.
Sprinkler/Support Cup Assembly
Specify: Series RFII (specify SIN),
K=5.6, "Royal Flush II" Pendent Sprin-
klers (specify) temperature rating, P/N*
(specify):
155°F (68°C) 200°F (93°C)
T'Y3531 51-792-1-155 51-792-1-200
TY3551 51-790-1-155 51-790-1-200
* Use Suffix I" for ISO 7-1 connection; for example,
51-792-1-155-I
Separately Ordered Cover Plate/
Retainer Assembly:
Specify: (temperature rating from
below) Series RFII Concealed Cover
Plate with (finish), P/N (specify).
139°F (59°C)(a) 165°F (74°C)(b)
Grey White
(RAL9002) .... 56-792-0-135 56-792-0-165
Brass .......... 56-792-1 -135 56-792-1-165
Pure White (c)
(RAL9010) .... 56-792-3-135 56-792-3-165
Signal White
(RAL9003).... 56-792-4-135 56-792-4-165
Jet Black
(RAL9005).... 56-792-6-135 59-792-6-165
Brushed
Chrome........56-792-8-135 56-792-8-165
Chrome ........56-792-9-135 56-792-9-165
Custom ........56-792-X-135 56-792-X-165
For use with 155°F (68°C) sprinklers.
For use with 200°F (93°C) sprinklers.
Eastern Hemisphere sales only.
Sprinkler Wrench
Specify: RFIl Sprinkler Wrench,
P/N 56-000-1-075
Air and Dust Seal
Specify: Air and Dust Seal,
P/N 56-908-1-001
1400 Pennbrook Parkway, Lansdale, PA 19446 I Telephone +1-215-362-0700
C 2018 Johnson Controls. NI rights reserved— MI specifications and ether lnfor,00tlon thaw,, we.'e current as of document revision dale and are subject to change without notice.
NATIONAL :IRE PROTECTION ASSOCIATION and NFPA are reginnarad t,odan,arino at National Fire Pnnnocnlon Association; TEFLON Is a registered Sndnn,nnk alOAPnnt
Johnson
Controls
Worldwide ticu Contacts www.tyco-fire.com
Series TY-FRB, 5.6 K-factor
Upright, Pendent, and Recessed Pendent Sprinklers
Quick Response, Standard Coverage
General
Description
The TYCO Series TY-FRB, 5.6 K-factor,
Upright (TY313) and Pendent (TY323)
Sprinklers described in this data sheet
are quick response, standard coverage,
decorative 3 mm glass bulb-type spray
sprinklers designed for use in light or
ordinary hazard, commercial occupan-
cies such as banks, hotels, and shop-
ping malls.
The recessed version of the Series
TY-FRB Pendent Sprinkler, where
applicable, is intended for use in areas
with a finished ceiling. This recessed
pendent sprinkler uses one of the
following:
A two-piece Style 15 Recessed
Escutcheon with recessed adjust-
ment up to 5/8 in. (15,9 mm) from
the flush pendent position.
A two-piece Style 20 Recessed
Escutcheon with recessed adjust-
ment up to 1/2 in. (12,7 mm) from
the flush pendent position.
The adjustment provided by the
Recessed Escutcheon reduces the
accuracy to which the fixed pipe drops
to the sprinklers must be cut.
Intermediate level versions of Series
TY-FRB Sprinklers are described in
Technical Data Sheet TFP357. Sprin-
kler guards and shields are described
in Technical Data Sheet TFP780.
IMPORTANT
Refer to Technical Data Sheet
TFP2300 for warnings pertaining to
regulatory and health information.
Always refer to Technical Data
Sheet TFP700 for the "INSTALLER
WARNING" that provides cautions
with respect to handling and instal-
lation of sprinkler systems and com-
ponents. Improper handling and
installation can permanently damage
a sprinkler system or its compo-
nents and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
Page 1 of 4
NOTICE
The TYCO Series TY-FRB Sprinklers
described herein must be installed
and maintained in compliance with
this document, as well as with the
applicable standards of the National
Fire Protection Association, in addition
to the standards of any other authori-
ties having jurisdiction. Failure to do so
may impair the performance of these
devices.
The owner is responsible for main-
taining their fire protection system
and devices in proper operating con-
dition. Contact the installing contrac-
tor or product manufacturer with any
questions.
Sprinkler
Identification
3.... Upright 5.6K, 1/2 in.
Technical
Data
Approvals
Refer to Table A
Maximum Working Pressure
175 psi (12.1 bar)
250 psi (17.2 bar)
* The maximum working pressure of 250 psi (17.2 bar)
only applies to the listing by Underwriters Laborato-
ries, Inc. (UL).
Discharge Coefficient
K=5.6 GPM/p5i½ (80,6 LPM/bar½)
Temperature Rating
Refer to Table A
Finishes
Sprinkler: Refer to Table B
Recessed Escutcheon: White Coated,
Black Coated, Chrome Plated, or Brass
Plated
Physical Characteristics
Frame ............................Bronze
Button ......................Brass/Copper
Sealing Assembly ... Stainless Steel wITEFLON
Bulb...............................Glass
Compression Screw .................Bronze
Deflector ..........................Bronze
AUGUST 2018
Operation
The glass bulb contains a fluid which
expands when exposed to heat. When
the rated temperature is reached, the
fluid expands sufficiently to shatter the
glass bulb, allowing the sprinkler to
activate and water to flow.
Design
Criteria
The TYCO Series TY-FRB, 5.6 K-factor,
Upright (TY313) and Pendent (TY323)
Sprinklers are intended for fire protec-
tion systems designed in accordance
with the standard installation rules
recognized by the applicable Listing or
Approval agency (such as, UL Listing
is based on the requirements of NFPA
13, and FM Approval is based on the
requirements of FM's Loss Prevention
Data Sheets). Only the Style 15 or Style
20 Recessed Escutcheon is to be used
for recessed pendent installations.
TFPI72
TFPI72
Page 2 of 4
Components:
1 - Frame 4 - Bulb
2 - Button 5 - Compression
3 - Sealing Screw
Assembly 6 - Deflector*
* Temperature rating is ** Pipe thread connections per ISO 7-1
indicated on Deflector. can be provided on special request.
ESCUTCHEON PLATE 1/2 7/16 (11,1 mm)
DEFLECTOR * SEATING SURFACE NPT** NOMINAL MAKE-IN
STYLE 15 or 20
RECESSED
ESCUTCHEON
* 6
______ I 7/16 ______ _ I \-
I
4 ______
(11,1mm) ______
_________ 2 ______ I NOMINAL
MAKE-IN _____ (50,8 mm) /8
___________
(34,9 mm)
DIA.
(50,8 mm) _______
13 2 / / 2°
WRENCH
FLATS
1/2 NPT** DEFLECTOR * 2-7/8 p3,0 mm)
CROSS SECTION UPRIGHT PENDENT RECESSED PENDENT
FIGURE 1
SERIES TY-FRB UPRIGHT (TY313) AND PENDENT (TY323) SPRINKLERS
-
5.6 K-FACTOR, 1/2 INCH NPT, QUICK RESPONSE
Installation
The TYCO Series TY-FRB, 5.6 K-factor,
Upright (TY313) and Pendent (TY323)
Sprinklers must be installed in accor-
dance with this section.
General Instructions
Do not install any bulb-type sprin-
kler it the bulb is cracked or there is
a loss of liquid from the bulb. With the
sprinkler held horizontally, a small air
bubble should be present. The diam-
eter of the air bubble is approximately
1/16 in. (1,6mm) for the 135°F (57°C) and
3/32 in. (2,4 mm) for the 286°F (141°C)
temperature ratings.
A leak-tight 1/2 in. NPT sprinkler joint
should be obtained by applying a
minimum to maximum torque of 7 to
14 lb-ft (9,5 to 19,0 N.m). Higher levels
of torque can distort the sprinkler Inlet
with consequent leakage or impairment
of the sprinkler.
Do not attempt to compensate for
insufficient adjustment in the Escutch-
eon Plate by under- or over-tightening
the sprinkler. Re-adjust the position of
the sprinkler fitting to suit.
Upright and Pendent Sprinklers
The Series TY-FRB Upright and
Pendent Sprinklers must be installed
in accordance with the following
instructions.
Step 1. Install Pendent sprinklers in the
pendent position. Install upright sprin-
klers in the upright position.
Step 2. With pipe-thread sealant
applied to the pipe threads, hand-
tighten the sprinkler into the sprinkler
fitting.
Step 3. Tighten the sprinkler into the
sprinkler fitting using only the W-Type
6 Sprinkler Wrench (Figure 2). With ref-
erence to Figure 1, apply the W-Type 6
Sprinkler Wrench to the wrench flats.
Torque sprinklers 7 to 14 lb-ft (9,5 to
19,0 N.m).
Recessed Pendent Sprinklers
The Series TY-FRB Recessed Pendent
Sprinklers must be installed in accor-
dance with the following instructions.
Step A. After installing the Style 15
or Style 20 Mounting Plate over the
sprinkler threads, and with pipe-thread
sealant applied to the pipe threads,
hand-tighten the sprinkler into the
sprinkler fitting.
Step B. Tighten the sprinkler into the
sprinkler fitting using only the W-Type
7 Recessed Sprinkler Wrench (Figure
3). With reference to Figure 1, apply the
W-Type 7 Recessed Sprinkler Wrench
to the sprinkler wrench flats. Torque
sprinklers 7 to 14 lb-ft (9,5 to 19,0 N.m).
Step C. After ceiling installation and
finishing, slide on the Style 15 or Style
20 Closure over the Series TY-FRB
Sprinkler and push the Closure over the
Mounting Plate until its flange comes in
contact with the ceiling.
/ WRENCH RECESS
(USE ONLY
FIGURE 2
.W-TYPE 6
SPRINKLER WRENCH
WRENCH
RECESS
PUSH WRENCH
IN TO ENSURE
ENGAGEMENT
WITH SPRINKLER
WRENCHING AREA
FIGURE 3
W-TYPE 7 RECESSED
SPRINKLER WRENCH
TFPI72
Page 3 of 4
Care and
Maintenance
The TYCO Series TY-FRB, 5.6 K-factor,
Upright (TY313) and Pendent (TY323)
Sprinklers must be maintained and ser-
viced in accordance with this section.
Before closing a fire protection system
main control valve for maintenance
work on the fire protection system
that it controls, obtain permission to
shut down the affected fire protection
systems from the proper authorities
and notify all personnel who may be
affected by this action.
Absence of the outer piece of an
escutcheon, which is used to cover
a clearance hole, can delay sprinkler
operation in a fire situation.
The owner must assure that the sprin-
klers are not used for hanging any
objects and that the sprinklers are only
cleaned by means of gently dusting
with a feather duster; otherwise, non-
operation in the event of a fire or inad-
vertent operation may result.
Sprinklers which are found to be
leaking or exhibiting visible signs of
corrosion must be replaced.
Automatic sprinklers must never be
painted, plated, coated, or other-
wise altered after leaving the factory.
Modified sprinklers must be replaced.
Sprinklers that have been exposed to
corrosive products of combustion, but
have not operated, should be replaced
if they cannot be completely cleaned
by wiping the sprinkler with a cloth or
by brushing it with a soft bristle brush.
Care must be exercised to avoid
damage to the sprinklers before,
during, and after installation. Sprin-
klers damaged by dropping, striking,
wrench twist/slippage, or the like, must
be replaced. Also, replace any sprin-
kler that has a cracked bulb or that has
lost liquid from its bulb. (Ref. Installa-
tion Section.)
The owner is responsible for the
inspection, testing, and maintenance of
their fire protection system and devices
in compliance with this document, as
well as with the applicable standards
of the National Fire Protection Asso-
ciation (e.g., NFPA 25), in addition to
the standards of any other authorities
having jurisdiction. Contact the install-
ing contractor or product manufacturer
with any questions.
Automatic sprinkler systems are rec-
ommended to be inspected, tested,
and maintained by a qualified Inspec-
tion Service in accordance with local
requirements and/or national codes.
Limited
Warranty
For warranty terms and conditions, visit
www.tyco-fire.com.
Ordering
Procedure
Contact your local distributor for avail-
ability. When placing an order, indicate
the full product name and Part Number
(P/N).
Sprinkler Assemblies with NPT
Thread Connections
Specify: Series TY-FRB Upright or
Pendent (specify) Sprinkler, SIN
(specify), K=5.6, Quick Response,
(specify) temperature rating, (specify)
finish, P/N (specify, refer to Table A).
Recessed Escutcheon
Specify: Style 15 Recessed Escutch-
eon with (specify*) finish, P/N (specify*)
Specify: Style 20 Recessed Escutch-
eon with (specify*) finish, P/N (specify*)
* Refer to Technical Data Sheet TFP770
Sprinkler Wrench
Specify: W-Type 6 Sprinkler Wrench,
P/N 56-000-6-387
Specify: W-Type 7 Sprinkler Wrench,
P/N 56-850-4-001
2-7/8 DIA.
(73,0 mm)
- 2-1/4 DIA.
FACE OF (57,2 mm)
SPRINKLER
5/8 (15,9 mm) FITTING
FLUSH
3/8±5/16'
(9,5±7,9 mm)
I
/
1/8
SURFACE
j MOUNTING (3,2 mm)
CLOSURE SERIES MOUNTING 1-3/8 (34,9 mm)
TY-FRB PLATE 3/4" (19,1 mm)
FIGURE 4
SERIES TY-FRB RECESSED PENDENT SPRINKLER ASSEMBLY (TY323)
WITH TWO PIECE 5/8 INCH TOTAL ADJUSTMENT STYLE 15
RECESSED ESCUTCHEON
2-7/8' DIA.
(73,0 mm)
FACE OF
SPRINKLER 2-1/4 DIA.
1/2° (12,7 mm) 5/16±1/4
\ _____________
(7,9±6,4 mm)
FITTING (57,2 mm)
FLUSH
MOUNTING /\ 1/8 J I
SURFACE/
\
(3,2 mm)
CLOSURE SERIES MOUNTING 1-3/8 (34,9 mm)
TY-FRB PLATE 7/8 (22,2 mm)
FIGURE 5
SERIES TY-FRB RECESSED PENDENT SPRINKLER ASSEMBLY (TY323)
WITH TWO PIECE 1/2 INCH TOTAL ADJUSTMENT STYLE 20
RECESSED ESCUTCHEON
TFPI72
Page 4 of 4
SPRINKLER FINISH (See Note 7)
K
FACTOR TYPE TEMPERATURE BULB LIQUID
COLOR
NATURAL
BRASS
I CHROME
PLATED ,,LYESTERC
135°F (57°C) Orange
UPRIGHT
(TY313)
and 1, 2, 3, 4, 5, 6
155°F (68°C) Red
175°F (79°C) Yellow
5.6
1/2 in. NPT
PENDENT
(TY323)
Blue
200°F (93°C) Green
286°F (141°C)
________________
135°F (57°C) Orange
RECESSED
PENDENT
(TY323)
Figures 4a and 5b
1,2,3,4 155°F (68°C) Red
175°F (79°C) Yellow
200°F (93°C) Green
Notes:
Listed by Underwriters Laboratories, Inc., (UL) as Quick Response Sprinklers.
Listed by Underwriters Laboratories, Inc., for use in Canada (C-UL) as Quick Response Sprinklers.
Approved by Factory Mutual Research Corporation (FM) as Quick Response Sprinklers.
Approved by the City of New York under MEA 354-01-E.
VdS Approved (For details, contact Johnson Controls, Enschede, Netherlands, Tel. 31-53-428-4444/Fax 31-54-428-3377.)
Approved by the Loss Prevention Certification Board (LPCB Ref. No. 094a/06) as Quick Response Sprinklers.
Where Polyester Coated Sprinklers are noted to be UL and C-UL Listed, the sprinklers are UL and C-UL Listed as Corrosion-Resistant Sprinklers.
Installed with Style 15 (1/2 in. NPT) 5/8 in. Total Adjustment Recessed Escutcheon, as applicable.
Installed with Style 20 (1/2 in. NPT) 1/2 in. Total Adjustment Recessed Escutcheon, as applicable.
C. Frame and Deflector only. Listings and approvals apply to color (Special Order).
TABLE A
LABORATORY LISTINGS AND APPROVALS FOR
5.6 K-FACTOR SPRINKLERS
P/Na77_XX_)_)OO(________
I
SPRINKLER TEMPERATURE FINISH RATINGS
1 NATURAL BRASS 135 135°F (57°C)
PURE WHITE (RAL9010)a 155 155°F (68°C) POLYESTER
Notes: SIGNAL WHITE (RAL9003) a. Use suffix 'I" for ISO 7-1 connection; for example, 4 POLYESTER 175 175-F (79-q 77-370-4-175-I - -
JET BLACK (RAL9005) 200 200°F (93°C) POLYESTER
9 CHROME PLATED 286 286°F (141°C)
Notes: a. Eastern Hemisphere sales only
TABLE
SERIES TY-FRB UPRIGHT AND PENDENT SPRINKLERS
PART NUMBER SELECTION
SIN
370 5.6K UPRIGHT (1/2 in.NPT) TY313
371 5.6K PENDENT (1/2 in.NPT) TY323
1400 Pennbrook Parkway, Lansdale, PA 19446 I Telephone +1.215.362-0700
C 2018 Johnson Controls. All rights reserved. All opocleoatlons and stoop i,do,n,atlon shown wane Ronont on of docon,nnt revision date and are subject to change wlthottt notion. Johnson
NATiONAL FIRE PROTECTION ASSOCIATION and NFPAO,0registered tredemo,t,n of Notional Are P,n,ocdan A000da11on; Controls TEFLON ,o9I,arod trRd000,k of DuPont
EXISTING TO REMAIN
Worldwide I tqL:L70 Contacts www.tyco-fire.com
Series EC41 and EC-14 Sprinklers,
11-.2-K and 14.0 K Upright and Pendent
Extended Coverage Light and Ordinary Hazard
General
Description
TYCO Series EC-11 and EC-14
Extended Coverage Upright and
Pendent Sprinklers are decorative
glass-bulb sprinklers designed for use
in light or ordinary hazard occupancies.
They are intended for use in automatic
sprinkler systems designed in accor-
dance with standard installation rules,
such as NFPA 13, for a maximum cov-
erage area of 400 ft2 (37,2 m2) as com-
pared to the maximum coverage area
of 130 ft2 (12,1 m2) for standard cover-
age sprinklers used in ordinary hazard
occupancies, or the maximum cover-
age area of 225 ft2 (20,6 m2) for stan-
dard coverage sprinklers used in light
hazard occupancies.
Series EC-11 and EC-14 Extended
Coverage Sprinklers feature a UL and
C-UL Listing that permits their use
with unobstructed or non-combusti-
ble obstructed ceiling construction as
defined and permitted by NFPA 13, as
well as a specific application listing for
use under concrete tees.
Series EC-11 and EC-14 Extended Cov-
erage Sprinklers have been fire tested
to compare their performance to that
of standard coverage spray sprinklers.
These tests have shown that the pro-
tection provided is equal to or more
effective than standard coverage spray
sprinklers.
corrosion-resistant coated sprinklers
passed standard corrosion tests of
the applicable approval agencies, this
testing is not representative of all pos-
sible corrosive atmospheres. Conse-
quently, it is recommended that the end
user be consulted with respect to the
suitability of these corrosion-resistant
coatings for any given corrosive envi-
ronment. The effects of ambient tem-
perature, concentration of chemicals,
and gas/chemical velocity should be
considered, along with the corrosive
nature of the chemical to which the
sprinklers will be exposed.
NOTICE
Series EC-11 and EC-14 Extended Cov-
erage Sprinklers described herein must
be installed and maintained in compli-
ance with this document, as well as
with the applicable standards of the
NFPA, in addition to the standards of
any other authorities having jurisdiction.
Failure to do so may impair the perfor-
mance of these devices.
The owner is responsible for main-
taining their fire protection system
and devices in proper operating con-
dition. Contact the installing contrac-
tor or product manufacturer with any
questions.
Sprinkler
Identification
Au i uli
Technical
Data
Approvals
TYCO Series EC-11 and EC-14
Extended Coverage Upright and
Pendent Sprinklers are UL and C-UL
Listed. Refer to Table A for complete
sprinkler approval information including
corrosion-resistant status. The approv-
als apply to the service conditions indi-
cated in the Design Criteria section.
Corrosion-resistant coatings, where 1111 Series EC-11 and EC-14 Extended Coy-
applicable, help extend the life of TY5137 ............Upright, 11.2K erage Sprinklers are FM Approved.
copper alloy sprinklers beyond that
approval information including corro-which occurs when exposed to
corrosive atmospheres. Although
~~,~~ K Refer to Table A for complete sprinkler
sion resistant status. The approvals
apply to the service conditions mdi-
IMPORTANT
Always refer to Technical Data
Sheet TFP700 for the "INSTALLER
WARNING" that provides cautions
with respect to handling and instal-
lation of sprinkler systems and com-
ponents. Improper handling and
installation can permanently damage
a sprinkler system or its compo-
nents and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
Page lof8
TY5137 is a re-designation for C5137, G1894, and S2510
TY5237 is a re-designation for C5237, G1893, and S2511
1V6137 is a re-designation for C6137, G1896, and S2610
1Y8237 is re-designation for C6237, G1895, and
S2611
DECEMBER 2017
caiea in the uesign tr1ier1a section.
The Style 60 Two-Piece Flush Escutch-
eon (Figure 4) is UL Listed for use with
the Series EC-11 and EC-14 Pendent
Sprinklers.
Maximum Working Pressure
175 psi (12,1 bar)
Pipe Thread Connection
3/4 in. NPT
TFP22O
ESCUTCHEON PLATE
SEATING SURFACE
'/
1-11/16°
.
(42,7 mm:
WRENCH 3/40
FLAT NPT**
CROSS
PENDENT SECTION
2-7/16°
(61,9 mm)
UPRIGHT &
PENDENT
1/2(12,7mm) J NOMINAL MAKE-IN
UPRIGHT
TFP22O
Page 2 of 8
Components:
1 1-Frame
2 - Button
3 - Sealing Assembly
2 4-Bulb
5 - Compression Screw
6 - Deflector 3
* Temperature rating is
4 indicated on Deflector.
** Pipe thread connections per
5 ISO 7-1 can be provided on
special request.
6*
FIGURE 1
SERIES EC-11 AND EC-14 EXTENDED COVERAGE SPRINKLERS
11.2 K-FACTOR UPRIGHT (TY5137) AND PENDENT (TY5237)
14.0 K-FACTOR UPRIGHT (TY6137) AND PENDENT (TY6237)
ASSEMBLY
Discharge Coefficients
K = 11.2 GPM/p51½ (161,3 LPM/bar½)
K = 14.0 GPM/psi½ (201,6 LPM/bar½)
Temperature Ratings
Refer to Table A
Finish
Sprinkler:
Refer to Table A
Recessed or Flush Escutcheon:
White-Coated, Chrome-Plated, and
Brass-Plated
Physical Characteristics
Frame............................Bronze
Button............................Bronze
Sealing Assembly . Beryllium Nickel w/TEFLON
Bulb ........................Glass (3 mm)
Compression Screw ................Bronze
Deflector...........................Brass
Operation
The glass bulb contains a fluid that
expands when exposed to heat. When
the rated temperature is reached, the
fluid expands sufficiently to shatter
the glass bulb, which- then allows the
sprinkler to activate and flow water.
Design
Criteria
TYCO Series EC-11 and EC-14
Extended Coverage Upright and
Pendent Sprinklers must only be
installed in accordance with the appli-
cable UL and C-UL Listing or FM
Approval requirements as indicated
below. Only Style 30 or 40 Recessed
Escutcheons are to be used for
recessed installation, as applicable.
Refer to Tables A, B, and C, for more
information.
UL and C-UL
Listing Requirements
Series EC-11 and EC-14 Extended
Coverage Sprinklers may be used
for the coverage areas shown in
Table D, based on maintaining the
minimum specified flow rate as a
function of coverage area and haz-
ard group for all sprinklers in the
design area.
Series EC-11 and EC-14 Extended
Coverage Sprinklers are permitted
to be used with unobstructed or
non-combustible obstructed ceil-
ing construction as defined and
permitted by NFPA 13; for example:
Unobstructed, combustible or
noncombustible, ceiling con-
struction with a deflector to
ceiling/roof deck distance of
1 t 12 in. (25 to 300 mm).
Obstructed, non-combusti-
ble, ceiling construction with a
deflector location below struc-
tural members of 1 to 6 in.
(25 to 150 mm) and a maximum
deflector to ceiling/roof deck dis-
tance of 22 in. (550 mm).
Series EC-11 and EC-14 Extended
Coverage Sprinklers, specifically
tested and listed for non-combus-
tible obstructed construction, are
permitted to be used within truss-
es or bar joists having non-com-
bustible web members greater
than 1 in. (25.4 mm) when apply-
ing the 4 times obstruction crite-
ria rule defined under "Obstruc-
tions to Sprinkler Discharge Pattern
Development".
To prevent cold soldering, the
minimum allowable spacing be-
tween Series EC-11 and EC-14 Ex-
tended Coverage Sprinklers is 8 ft
(2,4 m) for upright sprinklers and 9 ft
(2,7 m) for pendent sprinklers.
S. Series EC-11 and EC-14 Extended
Coverage Sprinklers are to be in-
stalled in accordance with all oth-
er requirements of NFPA 13 for
extended coverage upright and
pendent sprinklers; For exam-
ple, obstructions to sprinkler dis-
charge, obstructions to sprinkler
pattern development, obstructions
to prevent sprinkler discharge from
reaching hazard and clearance to
storage.
UL and C-UL Specific Application
Listing Requirements for
Installation under Concrete Tees
Series EC-11 and EC-14 Extended Cov-
erage Upright and Pendent Sprinklers
(TY5137, TY5237, TY6137 and TY6237)
have a UL and C-UL Specific Applica-
tion Listing for use under concrete tees
when installed as follows:
1. Stems of the concrete tee con-
struction must be spaced at less
than 7.5 ft (2,3 m) on center but
more than 3 ft (0,9 m) on center. The
depth of the concrete tees must not
exceed 30 in. (762 mm). The maxi-
mum permitted concrete tee length
is 32 ft (9,8 m). However, where the
concrete tee length exceeds 32 ft
(9,8 m), non-combustible baffles,
equal in height to the depth of the
tees, can be installed so that the
space between the tees does not
exceed 32 ft (9,8 m) in length.
TFP22O
Page 3 of 8
Hazard Type Temperature Bulb
Liquid
Sprinkler Finisha
Natural
Brass
I Chrome
Plated Polyester° I
J
Lead
Coated
Upright
K=11.2 (TY5137)
135 OF (57 °C) Orange
1, 2, 3C, 4 155 IF (68 °C) Red
175 OF (79 °C) Light Pendent Yellow
200°F (93 °C) Green 1, 2, 4 Table B describes
UL and c-ut
K=11.2(1Y5237)
K=14.0 (TY6237)
286 IF (141 °C) Blue
Recessed Pendent
K=11.2 (TY5237)
K=14.0 (TY6237)
135 IF (57 °C) Orange 1,2,3,4
Sensitivity Rating
Table C describes
FM
Sensitivity Rating
155 IF (68 °C) Red
175 IF (79 °C) Yellow
With Style 30
Escutcheon 1, 2, 4 I N/Ad 200 IF (93 °C) Green
286 °F(141 °C) Blue
Upright 135 IF (57 °C) Orange
155 IF (68 °C) Red
Ordinary
Table B describes
K11.2 (TY5137)
K14.0 (TY6137)
Pendent
K=11.2 (TY5237)
1,2,3,4 175°F(79°C) Yellow
200 IF (93 °C) Green
UL and C-UL
Sensitivity Rating
K=14.0 (TY6237) 286 IF (141 °C) Blue
Recessed Pendent 135 IF (57 °C) Orange Table C describes
155 IF (68 °C) Red FM
Sensitivity Rating
K=11.2 (1Y5237)
K=14.0 (TY6237)
With Style 30 or 40
1, 2, 4 I N/A 175 OF (79 °C) Yellow
200 OF (93 °C) Green Escutcheon
NOTES
Listed by Underwriters Laboratories, Inc. (UL)
Listed by Underwriters Laboratoies, Inc., for use in Canada (C-UL)
Approved by Factory Mutual Corporation (FM)
Approved by the City of New York under MEA 177-03-E
Where Polyester Coated or Lead Coated Sprinklers are noted to be UL and C-UL Listed as Corrosion Resistant Sprinklers.
Frame and Deflector only
Pendent only
N/A = Not available
TABLE A
LABORATORY LISTINGS AND APPROVALS
Light Hazard Ordinary Hazard Area Style ftxft 135°F 155°F 175°F 200°F 286°F 135°F 155°F 175°F 200°F 286°F
(57 °C) (68 °C) (79 °C) (93 °C) (141 °C) (57 °C) (68 °C) (79 °C) (93 °C) (141 °C)
Upright or Pendent - - - - - OR OR OR OR OR
14 x 14 Style 30 Recessed - - - - - OR OR OR OR OR
Style 40 Recessed - - - - - OR OR OR OR OR
Upright or Pendent OR OR OR OR OR SR SR SR SR SR
16x16 Style 30 Recessed OR OR OR OR OR SR SR SR SR SR
Style 40 Recessed N/A N/A N/A N/A N/A SR SR SR SR SR
Upright or Pendent OR OR OR OR OR SR SR SR SR SR
18 x 18 Style 30 Recessed OR OR OR OR OR SR SR SR SR SR
Style 40 Recessed N/A N/A N/A N/A N/A SR SR SR SR SR
Upright or Pendent OR OR OR SR SR SR SR SR SR SR
20 x 20 Style 30 Recessed OR OR OR SR SR SR SR SR SR SR
Style 40 Recessed N/A N/A N/A N/A N/A SR SR SR SR SR
NOTES
OR = Quick Response
SR = Standard Response
OR and SR does not apply to Upright K=14.0
Refer to Table 0 for permitted K-Factor/Area Combinations.
TABLE.B
SENSITIVITY RATING FOR UL AND C-UL LISTING OF SERIES EC-11 OR EC-14 SPRINKLERS
TFP22O
Page 4 of 8
HC-1
Linear Spacing Area Spacing
ft ft Ceiling Height
ft Ceiling Type
Max
K-factor Style Response
Mm Max Mm
Noncombustible Unobstructed, 11.2 EC Pendent or 10 20 100 400 Up to 30 Noncombustible Obstructed, or 14.0 EC Upright Combustible Unobstructed
Noncombustible Unobstructed, 11 2 EC . Pendent
10 20 100 400 Up to 30. Noncombustible Obstructed, or 14.0 EC Recessed
Combustible Unobstructed Style 30
Quick 10 20 100 400 Up to 30 Combustible Obstructed 11.2 EC
EC
Pendent or
14.0 Upright
11 2 EC . Pendent
10 20 100 400 Up to 30 Combustible Obstructed 14.0 EC Recessed Style 30
10 20 100 400 Over 30 and
up to 45 Noncombustible Unobstructed 11.2 EC
14.0 EC Upright
HC-2
Linear Spacing Area Spacing
ft ft Ceiling Height
ft Ceiling Type
Max
K-factor Style Response
Mm Max Mm
10 20 100 400 Upto30
Noncombustible Unobstructed,
11.2 EC Upright
10 20 100 400 Upto30 14.0 EC Pendent or
Upright
Combustible Unobstructed Quick
10 16 100 256 Over 30 and
up to 45
11.2 EC 14.0
EC Upright
HC-3
Linear Spacing Area Spacing
ft ft Ceiling Height
ft Ceiling Type
Max
K-Factor Style Response
Mm Max Mm
10 16 100 256 Up to 30 11.2 EC Upright
10 20 100 400 Upto30 14.0 EC Pendent or Upright Noncombustible Unobstructed,
Combustible Unobstructed Quick
10 16 100 256 Over 30 and
up to 45
11.2 EC,
14.0 EC Upright
NOTES
The design for K 11.2 EC (K 160 EC) sprinklers should not include fewer than six sprinklers or have a design pressure of less than 12 psi (0,8 bar); similarly the design for K 14.0
EC (K 200 EC)sprinklers should not include fewer than four sprinders or have a design pressure of less than 18 pal (1,2 bar).
For flow criteria, refer to FM Loss Prevention Data Sheet 3-26.
Refer to FM Loss Prevention Data Sheet 2-0 for permitted K-Factor/Area Combinations.
TABLE C
SENSITIVITY RATING FOR FM APPROVAL OF SERIES EC-11 OR EC-14 SPRINKLERS
The sprinkler deflectors are to be
located in a horizontal plane at or
above 1 in. (25,4 mm) below the
bottom of the concrete tee stems.
When the sprinkler deflectors are
located higher than a horizontal
plane 1 in. (25,4 mm) beneath the
bottom of the concrete tee stems,
the obstruction to sprinkler dis-
charge criteria requirements of
NFPA 13 for extended coverage
upright and pendent sprinklers
applies.
FM Approval Requirements
Series EC-11 and EC-14 Extended
Coverage Upright and Pendent Sprin-
klers are to be installed in accor-
dance with the applicable FM Loss
Prevention Data Sheet for limited use
in buildings of specific roof construc-
tion and for the protection of certain
specific ordinary hazard (non-storage
and/or non-flammable or combustible
liquid) occupancies. Information pro-
vided in the FM Loss Prevention Data
Sheets relates to, but is not limited to,
hydraulic design, ceiling slope, and
obstructions, minimum and maximum
allowable spacing, and deflector-to-
ceiling distance.
These criteria may differ from UL
and/or NFPA criteria. Therefore, the
designer should review and become
familiar with FM requirements before
proceeding with design.
TFP22O
Page 5 of 8
Description Area
ft x ft
Light Hazard 0.10 GPM/ft2
Group I
Ordinary Hazard
0.15 GPM/ft2
Group II
Ordinary Hazard
0.20 GPM/ft2
GPM PSI GPM PSI GPM PSI
14x14 30 7.2 30 7.2 39 12.1
16 x 16 30 7.2 39 12.1 51 20.7 TY5137
18 x 18 33 8.7 49 19.1 65 33.7 (K=11.2) Upright
20x20 40 12.8 60 28.7 80 51.0
14x14 30 7.2 30 7.2 39 12.1
16x16 30 7.2 39 12.1 51 20.7 TY5237
18x18 33 8.7 49 19.1 65 33.7 (K=11.2) Pendent
20x20 40 12.8 60 28.7 80 51.0
14x14 N/A N/A 39 7.8 51 13.3
16 x 16 N/A N/A 39 7.8 51 13.3
TY6137
18x18 N/A N/A 49 12.3 65 21.6 (K=14.0) Upright
20x20 N/A N/A 60 18.4 80 32.7
14x14 37 7.0 39 7.8 51 13.3
16x16 37 7.0 39 7.8 51 13.3
TY6237
18 x 18 37 7.0 49 12.3 65 21.6 (K=14.0) Pendent
20x20 1 40 8.2 60 18.4 80 32.7
NOTES
1ft=0.348m
1 ft2=0.093m2
1 GPM = 3.785 LPM
1 psi = 0.06895 bar
1 GPM/ft2 = 40.74 mm/mm
TABLED
FLOW CRITERIA FOR UL AND C-UL LISTING OF SERIES EC-11 AND EC-14 SPRINKLERS
Installation
TYCO Series EC-11 and EC-14
Extended Coverage Upright and
Pendent Sprinklers must be installed
in accordance with this section.
General Instructions
Do not install any bulb-type sprinkler
if the bulb is cracked or there is a loss
of liquid from the bulb. With the sprin-
kler held horizontally, a small air bubble
should be present. The diameter of the
air bubble is approximately 1/16 in.
(1,6 mm) for the 135 OF (57 °C) to
3/32 in. (2,4 mm) for the 286°F (141 °C)
temperature ratings.
A leak-tight 3/4 in. NPT sprinkler
joint should be obtained by apply-
ing a minimum-to-maximum torque of
10 to 20 ft-lb (13,4 to 26,8 N.m). Higher
levels of torque may distort the sprin-
kler inlet with consequent leakage or
impairment of the sprinkler.
Do not attempt to compensate for
insufficient adjustment in an Escutch-
eon Plate by under or over-tightening
the Sprinkler. Re-adjust the position of
the sprinkler fitting to suit.
Step 1. Install the sprinkler with the
deflector parallel to the mounting
surface. Install pendent sprinklers in
the pendent position; install upright
sprinklers in the upright position.
Step 2. After installing the Style 30, 40,
or 60 mounting plate (or other applica-
ble escutcheon) over the sprinkler pipe
threads and with pipe-thread sealant
applied to the pipe threads, hand-
tighten the sprinkler into the sprinkler
fitting.
Step 3. For upright or pendent sprin-
klers, wrench-tighten using only the
W-Type 3 (End A) Sprinkler Wrench.
For the pendent sprinkler installed
with Style 30, 40, or 60 Escutcheon,
wrench-tighten the sprinkler using only
the W-Type 22 Sprinkler Wrench.
Apply the wrench recess of the appli-
cable sprinkler wrench (Figure 5 and 6)
to the sprinkler wrench flats (Figure 1).
Care and
Maintenance
TYCO Series EC-11 and EC-14
Extended Coverage Upright and
Pendent Sprinklers must be maintained
and serviced in accordance with this
section.
Before closing a fire protection system
main control valve for maintenance
work on the fire protection system
that it controls, obtain permission to
shut down the affected fire protection
systems from the proper authorities
and notify all personnel who may be
affected by this action.
Sprinklers which are found to be
leaking or exhibiting visible signs of
corrosion must be replaced.
TFP22O
Page 6 of 8
2-7/8° DIA.
1/2±1/8 (73,0 mm) 1/2 (12,7 mm)
(12,7±3,2 mm) 2-1/4 DIA. 1/4 (6,4 mm)
SPRINKLER 1/8"
FITTING (3,2 mm)
MOUNTING MOUNTING SURFACE
___________ CLOSURE
PLATE
.
1.3/8(34,9mm)
1-1/8 (28,6 mm)
FIGURE 2
SERIES EC-11 AND EC-14 RECESSED
PENDENT SPRINKLER ASSEMBLY
WITH TWO-PIECE 1/2 IN. TOTAL ADJUSTMENT
STYLE 30 RECESSED ESCUTCHEON
2-7/8 DIA.
5/8±1/4 (73,0 mm) - 3/4' (19,1 mm)
(15,9±6,4 mm) 2-1/4 DIA. 1/4(6,4mm)
FACE OF - (57,2 mm)
SPRINKLER 1/8°
FITTING (3,2 mm)
-
..
_fJ
MOUNTING MOUNTING /7
SURFACE PLATE / _______
(34,9 mm)
CLOSURE
7/8 (22,2 mm)
FIGURE 3
SERIES EC-11 AND EC-14 RECESSED
PENDENT SPRINKLER ASSEMBLY
WITH TWO-PIECE 3/4 IN. TOTAL ADJUSTMENT
STYLE 40 RECESSED ESCUTCHEON
FACE OF
SPRINKLER FITflNG:
3/8° (9,5 mm) ABOVE
TO 1/8' (3,2 mm) BELOW
MOUNTING SURFACE I tjlll~
ESCUTCHEON PLATE -
SEATING SURFACE:
1/4' (6,4 mm) ABOVE
TO 1/2 (12,7 mm) BELOW
MOUNTING SURFACE;
3/4" (19,1 mm) TOTAL
ADJUSTMENT
Automatic sprinklers must never be
painted, plated, coated, or other-
wise altered after leaving the factory.
Modified sprinklers must be replaced.
Sprinklers that have been exposed to
corrosive products of combustion, but
have not operated, should be replaced
if they cannot be completely cleaned
by wiping the sprinkler with a cloth or
by brushing it with a soft bristle brush.
Care must be exercised to avoid
damage to the sprinklers before,
during, and after installation. Sprin-
klers damaged by dropping, striking,
wrench twist/slippage, or the like, must
be replaced. Also, replace any sprinkler
that has a cracked bulb or that has lost
MOUNTING
1/8' SURFACE
(3,2 mm)
CLOSURE
3/4, NPT 25/16 (58,7 mm)
-MOUNTING 1-13/16" (46,0 mm)
PLATE
liquid from its bulb. Refer to the Instal-
lation section, for more information.
Frequent visual inspections are rec-
ommended to be initially performed
for corrosion resistant coated sprin-
klers, after the installation has been
completed, to verify the integrity of the
corrosion resistant coating. Thereafter,
annual inspections per NFPA 25 should
suffice; however, instead of inspecting
from the floor level, a random sampling
of close-up visual inspections should
be made, so as to better determine the
exact sprinkler condition and the long
term integrity of the corrosion resistant
coating, as it may be affected by the
corrosive conditions present.
2-7/8 DIA.
(73,0 mm)
2-1/4° DIA.
(57,2 mm).
J.
INTERNAL
DIMENSIONS OF
STYLE 60 ESCUTCHEON
ACCOMMODATE
CLASS 150 MALLEABLE
IRON REDUCING
SPRINKLER FITTING
"FITTING SIDE"
TOWARDS SPRINKLER
FITTING
/\
WRENCH
RECESS /
(END "A")
FIGURE 5
W-TYPE 3 SPRINKLER
WRENCH
WRENCH
RECESS -
1i \
ri
WRENCH
HEX
FIGURE 6
W-TYPE 22 RECESSED
SPRINKLER WRENCH
FIGURE 4
SERIES EC-11 AND EC-14 PENDENT SPRINKLER ASSEMBLY
WITH 3/4 IN. TOTAL ADJUSTMENT
STYLE 60 TWO-PIECE FLUSH ESCUTCHEON
TFP22O
Page 7 of 8
P/N 51 - XXX - X - XXX
I
SIN R j S FINISHI TEMPERATURE
RATING
893 11.2K Pendent 1Y5237 1 NATURAL BRASS 135 135°F(57°C)
894 11.2K Upright 1Y5137 SIGNAL WHITE 155 155 °F (68 °C)
- POLYESTER
895 14.0K Pendent TY6237 JET BLACK (RAL9005) 175 175 °F (79 °C)
- POLYESTER
896 14.0K Upright TY6137 - 200 200 °F (93 °C)
7 LEAD COATED
286 286 °F (141 °C)
9 CHROME-PLATED -
- 000 OPEN2
NOTES:
Escutcheon ordered separately.
OPEN indicates the sprinkler assembly without glass bulb, button, and sealing assembly.
TABLE
SERIES EC-11 AND EC-14 UPRIGHTAND PENDENT SPRINKLERS
PART NUMBER SELECTION
The owner is responsible for the
inspection, testing, and maintenance
of their fire protection system and
devices in compliance with this doc-
ument, as well as with the applicable
standards recognized by the Approval
agency, such as NFPA 25, in addition to
the standards of any authorities having
jurisdiction. Contact the installing con-
tractor or product manufacturer with
any questions.
Automatic sprinkler systems are rec-
ommended to be inspected, tested,
and maintained by a qualified Inspec-
tion Service in accordance with local
requirements and/or national codes.
Limited
Warranty
For warranty terms and conditions, visit
www.tyco-fire.com.
Ordering
Procedure
Contact your local distributor for
availability. When placing an order,
indicate the full product name and Part
Number (P/N).
Sprinkler Assemblies with
NPT Thread Connections
Specify: Series EC-11 or EC-14
(specify) Sprinkler, SIN (specify),
(specify) K-factor, Pendent or Upright
(specify) Extended Coverage, (specify)
temperature rating, (specify) finish, P/N
(from to Table E)
Recessed Escutcheon, Two-Piece
Specify: Style (30 or 40) Two-Piece
Recessed Escutcheon with (specify)
finish, P/N (specify*)
--
Refer to Technical Data Sheet TFP770
Flush Escutcheon, Two-Piece
Specify: Style 60 Two-Piece Flush
Escutcheon with (specify) finish, P/N
(specify**)
**Refer to Technical Data Sheet TFP778
Sprinkler Wrenches
Specify: W-Type 3 Sprinkler Wrench,
P/N 56-895-1-001
Specify: W-Type 22 Recessed Sprinkler
Wrench, P/N 56-665-7-001
TFP22O
Page 8 of 8
1400 Ponnbrook Parkway, Lansdale, PA 194461 Telephone +1-215462-0700
C 2018 Johnsen Controls. All rights renamed. All specifications and other Information shown were current as of document revision date and are subject to change wllhOst notice. Johnson 0) )Vo
NATIONAL FIRE PROTECTION ASSOCIATION and NFPA Ore registered trodamarkn of ReSend Fire Protection A0005lallon; Controls TEFLON no retictored Paderrrarkaf Dupont