HomeMy WebLinkAbout2382 FARADAY AVE; 140; FPC2017-0336; Permitc
PERMIT REPORT ity of
Carlsbad
Print Date: 03/22/2022 Permit No: FPC2017-0336
Job Address: 2382 FARADAY AVE. # 140, CARLSBAD, CA 92008-7219 Status: Closed - Finaled
Permit Type: FIRE-Construction Commercial Work Class: Fire Sprinklers
Parcel #: 2120621800 Track #: Applied: 11/14/2017
Valuation: $163,017.55 Lot #: Issued: 12/01/2017
Occupancy Group: Project 4*: Finaled Close Out: 02/23/2021
#of Dwelling Units: Plan 4*:
Bedrooms: Construction Type:
Bathrooms: Orig. Plan Check 4*: Inspector:
Plan Check 4*: Final Inspection:
Project Title:
Description: CARLSBAD RESEARCH CENTER (CRC) SPEC SUITE 140 -SPRINKLER TI 7-100 (28)
Applicant: FPContractor:
TOTAL FIRE PROTECTION INC TOTAL FIRE PROTECTION INC
JOHN CAPUTO 1611 5 MELROSE PL, 4* 244
1611A S MELROSE DR VISTA, CA 92081-5471
VISTA, CA 92081-5407 (760) 525-4329
(760) 525-4329
FEE AMOUNT
FIRE NFPA 13 or 13R System 7 - 100 heads $536.00
Total Fees: $536.00 Total Payments To Date: $536.00
---
Balance Due: $0.00
Fire Department Page 1of1
1635 Faraday Avenue, Carlsbad CA 92008-7314 1 760-602-4665 1 760-602-8561 f I www.carlsbadca.gov
MATERIAL DATA SUBMITTAL
CRC Spec Suite 140
2382 Faraday Avenue
Carlsbad, CA 92008
Page * Description Manufacturer
1-2 Pipe Allied Dyna-Thread Pipe ' 3-10
11-12
Fillings
Mechanical Tee
Tyco Ductile Iron Fittings
Tyco Fig 40-5 Strap Tee
) 13-19 Sprinkler Reliable F1FR56 Sprinkler
20 Hanger Afcon Fig. 300 Ring Hanger
21 Hanger Afcon Fig 655 All Thread Rod
2223 Attachment Sammy Wood Vertical Mount
FPC20I7-0336
2382 FARADAY AVE # 140
CARLSBAD RESEARCH CENTER (CRC) SPEC SUITE 140-
SPRINKLER TI 7-100(28)
2120621800
11/14/2017
FPC20I 7-0336
Total Fire Protection, Inc.
1611 A S. Melrose Dr. *244
Vista, CA 92081
(760)525-4329 fax (877) 724-4329 • tfpjohncgmaiI.com
DynawThread"
Full Line Sch-40 Replacement
Dyna Threada offers the life expectancy of Sch40 with superior hydraulics and greater value.
Dyna-Thread sprinkler pipe represents an engineering advancement for the sprinkler pipe industry. It combines the safety
and longevity of traditional Sch-40 pipe with quality and superior hydraulic advantages.
S
Dyna-Thread's inside diameter is up
to 3.6% larger than Sch-40 giving it
superior hydraulics. And, when used
in combination with Dyna-Flow pipe,
down sizing often occurs.
Dyna-Thread is filly listed and
approved by UL, ULC, and FM for
fire sprinkler applications.
The life expectancy of Dyna-Thread
and Sch40 are equal based on the
calculated wall thicknesses per UL.
The consistent quality of steel used to
make Dyna-Thread facilitates smooth
threading and lower maintenance
costs.
The exterior of Dyna-Thread is
protected by a clean, durable mill
coating for extended shelf life and
easy paint application.
(D <~> @
Listed Approved Listed
With its increased strength and lighter
weight, Dyna-Thread reduces
installation fatigue and is ideal for
retro-fit applications.
Corrosion Resistance Ratio (CRR) is a
UL (Underwriters Laboratory) term for
the estimated life expectancy of a pipe
joint. This is based on the calculated
wall thickness at the base of the first
exposed thread, assumed to be the
weakest point of the pipe length. Dyna-
Thread and Sch-40 have the same
calculated wall thicknesses at this point
and are both assigned the same CRR of
1.00.
The internal surface of all black Allied
Tube & Conduit Fire Sprinkler pipe
products up to 4.5000" in diameter is
coated with our new Antibacterial
Formula, "ABF'. In scientific laboratory
test, ABS proved to have superior
resistance to microbial colonization of
pipe walls, thereby delaying or possibly
preventing the onset of
Microbiologically Influenced corrosion
(MIC) when the First Sprinkler System
is first installed.
More wall thickness at the thread
(CRR= 1.00) gives Dyna-Thread
better life expectancy than lightwall
threadable pipe joints.
Unlike lightwall threadable pipe,
Dyna-Thread has no thread gauge
warning.
Dyna-Thread is approved for
standard hanger spacing (15 ft.
O.C.), can be used as earthquake
sway bracing, and is safe to use as
drops.
Dyna-Thread is safer to weld on.
Dyna-Thread is more widely
accepted than lightwall threadable
where Sch-40 is specified.
Super 40/Dyna-Thread pipe is
manufactured to meet: ASTM A-135,
Grade A and is in compliance with
NFPA- 13. All sizes of Super 40/Dyna-
Thread are rated at 300 psi working
pressure. Super 40fDyna-Thread is UL
and ULC Listed for wet, dry deluge and
pre-action sprinkler systems and FM
Approved for use in wet systems. Super
40/Dyna-Thread can be "hot-dip"
galvanized to meet FM requirement for
dry systems. Super 40/Dyna-Thread is
approved for all threaded couplings and
welded outlets and is suitable for all
roll-grooved, and plain-end fittings.
(See listing information).
Specifications
NPS Nominal I.D. M. WI. (H20 Filled) Pcs/ Wtllift (21') WVI.Ift (24') WUlift (25')
In; tam In; mm Lbs/Fl; Kg/rn Lbs/Fl; Kg/rn Lift Lbs; Kg Lbs; Kg Lbs; Kg
1" 1.080 1.330 1.75 70 1955 2234 232
25 27.4 2.0 2.60 70 887 1013 105
1%' 1.408 1.870 2.54 51 2002 2288 2384
32 35.8 2.8 3.78 51 908 1038 108
11/2, 1.639 2.290 3.22 44 2115 2418 2519
40 41.6 3.4 4.79 44 959 1097 114
2' 2.104 3.050 4.57 30 1921 2196 2287
50 53.4 4,5 6.80 30 871 996 103
I'. I 16100 S. Lathrop• Harvey, IL 60426 tqco/F/ow Control cijliecj 1135& Norcom Rd. . Philadelphia, PA 19154
TUBE& CONDUIT 2525 N. 27th Ave. Phoenix, AZ 85009
Customer Service:
(800) 882-5543
Fax 708-339-1801'-.----"
S3-3
Submittal Data Sheet
Dyna-Thread
Full Line Sch-40 Replacement
Dyna-Thread sprinkler pipe represents an engineering advancement for the sprinkler
pipe industry. It combines the safety and longevity of traditional Sch-40 pipe with
quality and superior hydraulic advantages.
Comparison to Schedule 40 Dyna-Threads inside diameter is up to 3.6% larger than
Sch-40 giving it superior hydraulics. Also, when used in combination with Dyna-Flow
pipe, down sizing often occurs. Dyna-Thread is fully listed and approved UL, ULC,
and FM for fire sprinkler applications. The life expectancy of Dyna-Thread and Sch-40
are equal based on the calculated wall thicknesses per UL. The consistent quality of
steel used to make Dyna-Thread facilitates smooth threading and lower maintenance
costs. The exterior of Dyna-Thread is protected by a clean, durable mill coating for
extended shelf life and easy paint application. With its increased strength and lighter
weight, Dyna-Thread reduces installation fatigue and is ideal for retro-fit applications.
Corrosion Resistance Ratio (CRR) is a UL (Underwriters Laboratory) term for the
estimated life expectancy of a pipe joint. This is based on the calculated wall thickness
at the base of the first exposed thread, assumed to be the weakest point of the pipe
length. Dyna-Thread and Sch-40 have the same calculated wall thicknesses at this
point and are both assigned the same CRR of 1.00.
Comparison to L.W.T. Pipe More wall thickness at the thread (CRRl .00) gives
Dyna-Thread better life expectancy than lightwall threadable pipe joints. Unlike
lightwall threadable pipe Dyna-Thread has no thread gauge warning. Dyna-Thread is
approved for standard hanger spacing (15 ft. O.C.), can be used as earthquake sway
bracing, and is safe to use as drops. Dyna-Thread is safer to weld on than many zinc-
coated lightwall threadable pipe products. Dyna-Thread is more widely accepted than
lightwall threadable where Sch-40 is specified.
Slamp Here
I
il I
Specifications & Approvals Super 40/
Dyna-Thread pipe is manufactured to
meet: ASTM A 135, Grade A and is in
compliance with NFPA-13. All sizes of
Super 40/Dyna-Thread are rated at 300
psi working pressure. Super 40/ Dyna-
Thread is UL and ULC Listed for wet,
dry and pre-action sprinkler systems and
FM Approved for use in wet systems.
Super 40fDyna-Thread can be "hot-dip"
galvanized to meet FM requirement for
dry systems. Super 40/Dyna-Thread is
approved for all threaded couplings and
welded outlets and is suitable for all roll-
grooved, and plain-end fittings. (See
listing information).
The internal surface of all black Fire
Sprinkler pipe up to 4.5000" in diameter
shall be coated with Allied Tube &
Conduit Antibacterial Formula "ABF".
Specifications
NPS Nominal I.D. WI. WI. (1120 Filled) Pcsl Wt)l.itt (21') Wtiuft (24') WtI1.ift (25')
In; mm In; mm Lbs/Ft; Kg/rn Lbs/Ft; Kg/rn Lift Lbs; Kg Lbs; Kg Lbs; Kg
1.080 1.330 1.75 70 1955 2234 232
25 27.4 2.0 2.60 70 887 1013 105
1¼' 1.408 1.870 2.54 51 2002 2288 2384
32 35.8 2.8 3.78 51 908 1038 108
11/2' 1.639 2.290 3.22 44 2115 2418 251
40 41.6 3.4 4.79 44 959 1097 114
2.104 3.050 4.57 30 1921 2196 228
50 53.4 4.5 6.80 30 871 996 103
American Tube and Pipe was acquired by Allied Tube and Conduit on February 1,
1997. The engineered lightwall and standard wall family of products although they
have different names are the same in all respects with regard to strength, weight,
bundle count, listings and approvals. For example,
Dyna-Flow and Super Flo are the same product as
are Dyna Thread and Super 40. XL is manufactured Us L
with Exterior galvanized coating. BIT is
manufactured with Black lacquer coating. Listed Approved Listed
Project: Sprinkler Contractor: Date:
S Engineer: Specification Reference: System Type:
Locations: Comments:
S3-4
tqC0 Fire & Building
liProducts
Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500
S
Pipe Fittings
NPT Threaded,
Ductile Iron
General
Description
The TycoO Series 800 Threaded Pipe
Fittings and California Tees & Elbows
are manufactured from ductile iron.
They are stronger and more corrosion
resistant than cast iron fittings. The
additional strength is provided by the
ductile properties and by adding mag-
nesium while the iron is being poured
into the final cast shape. Although
lighter than standard cast iron, the fit-
tings have an added advantage of be-
ing less susceptible to cracking due to
their added strength.
The Series 800, California, and Figure
719 Threaded Pipe Fittings are a re-
designation for the Central Series 800,
California, and Figure 719 Threaded
Pipe Fittings.
WARNINGS
The Threaded Pipe Fittings described
herein must be installed and main-
tained in compliance with this docu-
ment, as well as with the applicable
standards of the National Fire Pro-
tection Association, in addition to the
standards of any other authorities hav-
ing jurisdiction. Failure to do so may
impair the performance of these
devices.
The owner is responsible for maintain-
ing their fire protection system and de-
vices in proper operating condition.
The installing contractor or sprinkler
manufacturer should be contacted
with any questions.
Technical
Data
Approvals:
UL Listed and FM Approved
Maximum Working Pressure:
Series 800 and California Fittings:
250 psi (17,2 bar)
Figure 719 Plug:
250 psi (17,2 bar)
Page 1 of 10
Material:
Series 800 and California Fittings:
Ductile Iron
Figure 719 Plug:
Cast Iron
Pipe Thread:
NPT per ANSI B1.20.1
Installation
Apply Teflont tape or high quality pipe
joint compound on male pipe threads
and tighten two to three turns beyond
hand tight.
NOTE
Installers who have not used ductile
iron threaded fittings should be in-
structed that the fittings are stron-
ger than the pipe and overtightening
the fitting can create leaks and cause
damage to pipe threads. In general,
there is about one-half turn difference
between cast iron and ductile iron fit-
tings. Apply Teflon tape or high qual-
ity pipe joint compound on the male
pipe threads and tighten two to three
turns beyond hand tight. If an auto-
matic make-on machine is being used,
please exercise caution in setting the
machine to the proper parameters pri-
or to tightening fittings onto the male
pipe threads.
Limited
Warranty
Products manufactured by Tyco Fire
& Building Products (TFBP) are war-
ranted solely to the original Buyer for
ten (10) years against defects in mate-
rial and workmanship when paid for
and properly installed and maintained
under normal use and service. This
warranty will expire ten (10) years from
date of shipment by TFBP. No warran-
ty is given for products or components
manufactured by companies not af-
filiated by ownership with TFBP or for
products and components which have
been subject to misuse, improper in-
stallation, corrosion, or which have not
been installed, maintained, modified or
repaired in accordance with applicable
JANUARY, 2008
Standards of the National Fire Protec-
tion Association, and/or the standards
of any other Authorities Having Juris-
diction. Materials found by TFBP to be
defective shall be either repaired or re-
placed, at TFBP's sole option. TFBP
neither assumes, nor authorizes any
person to assume for it, any other ob-
ligation in connection with the sale of
products or parts of products. TFBP
shall not be responsible for sprinkler
system design errors or inaccurate or
incomplete information supplied by
Buyer or Buyer's representatives.
In no event shall TFBP be liable, in
contract, tort, strict liability or under
any other legal theory, for incidental,
indirect, special or consequential dam-
ages, including but not limited to labor
charges, regardless of whether TFBP
was informed about the possibility of
such damages, and in no event shall
TFBP's liability exceed an amount
equal to the sales price.
The foregoing warranty is made In lieu
of any and all other warranties, ex-
cress or implied. including warranties
of merchantability and fitness for a
Particular ourcose.
This limited warranty sets forth the ex-
clusive remedy for claims based on
failure of or defect in products, materi-
als or components, whether the claim
is made in contract, tort, strict liability
or any other legal theory.
This warranty will apply to the full ex-
tent permitted by law. The invalidity,
in whole or part, of any portion of this
warranty will not affect the remainder.
Ordering
Procedure
When placing an order, indicate the
full product name. Please specify the
quantity, figure number, wall thickness,
and size.
tregistered trademark of E. I. du Pont de Nemours and Company or Its affiliates.
TFPI7IO
Page 2of 10 TFPI7I0
S
Nominal Pipe Figure 813 Size
ANSI A Approx.
Inches Inches Weight Part
DN (mm) Lbs. Number
(kg)
1/2 1.13 0.22 86780 DN15 (28,7) (0,09)
3/4 1.31 0.33 86781 DNJ20 (33,3) (0,15)
1 1.50 0.48 86280 DN25 (38,1) (0,21)
1-1/4 1.75 0.73 86281 0N32 (44.5) (0133)
1-1/2 1.94 0.93 86282 DN40 (49,3) (0,42)
2 2.25 1.55 86283 0N50 (57,1) (0,70)
2-1/2 2.69 2.70 86782 0N65 (68,3) (1,22)
S
FIGURE 811 FIGURE 813
900 ELBOW 450 ELBOW
TABLE I
NOMINAL DIMENSIONS FIGURES 811 & 813
Figure 811
B Approx. A B
Inches Weight Part Inches Inches
(mm) Lbs. Number (mm) (mm) (kg)
0.56 0.24 86206 0.88 0.38
(14,2) (0,11) (22,4) (9,7)
0.75 0.40 86205 1.00 0.44
(19,0) (0,18) (25,4) (11,2)
0.81 0.64 86200 1.13 0.81
(20,6) (0,29) (28,7) (20,6)
1.06 0.95 86201 1.31 0.63
(26,9) (0,43) (33,3) (16,0)
1.19 1.24 86202 1.44 0.69
(30,2) (0,56) (36,6) (17,5)
1.50 1.74 86203 1.68 0.94
(38,1) (0,79) (42,7) (23,9)
1.56 3.28 86204 1.94 1.00
(39,6) (1,49) (49,3) (25,4)
TFPI7IO Page 3 of 10
FIGURE 812
900 REDUCING ELBOW
Nominal Pipe Figure 812 Size
ANSI A B C D Approx.
Weight Part Inches Inches Inches Inches Inches Lbs. DN (mm) (mm) (mm) (mm) Number
(kg)
3/4x112 1.19 1.19 0.63 0.63 0.33 86342 0N20 x 15 (30,2) (30,2) (16,0) (16,0) (0,15)
1 x 1/2 1.25 1.38 0.56 0.81 0.44 86210 DN25 x 15 (31,8) (35,1) (142) (20,6) (0,20)
1 x3/4 1.38 1.44 0.69 0.88 0.53 86211 DN25 x 20 (35,1) (36,6) (17,5) (22,4) (0,24)
1-1/4 x 1/2 1.31 1.50 0.63 0.94 0.64 86212 DN32 x 15 (33,3) (38,1) (16,0) (23,9) (0,29)-
1-1/4 x 3/4 1.44 1.63 0.75 1.06 0.75 86213 DN32 x 20 (36,6) (41,4) (19,0) (26,9) (0,34)
1-114x1 1.56 1.68 0.88 1.00 0.77 86214 DN32 x 25 (39,6) (42,7) (22,4 (25,4) (0,35)
1-1/2 x 3/4 1.50 1.75 0.75 1.19 0.95 86221 DN40x20 (38,1) (44,4) (19,0) (30,2) (0,43)
1-1/2x 1 1.63 1.81 0.88 1.13 0.99 86215 DN40x25 (41,4) (46,0) (22,4) (28,7) (0,45)
1-112x1-114 1.81 1.88 1.13 1.19 1.14 86216 DN40 x 32 (46,0) (47,8) (28,7) (30,2) (0,52)
2x314 1.63 1.94 0.88 1.38 1.39 86217 DN50 x 20 (41,4) (49,3) (22,4) (35,1) (0,63)
2x1 1.75 2.06 2.00 1.31 1.58 86218 DN50 x 25 (44,4) (52,3) (50,8) (33,3) (0,72)
2 x 1-1/2 2.00 2.19 1.25 1.44 1.67 86220 DN5O x 40 (50,8) (55,6) (31,8) (36,6) (0,76)
2-1/2x2 2.38 2.63 1.25 1.88 3.01 86262 DN65x50 (60,5) (66,8) (31,8) (47,8) (1,36)
TABLE 2
NOMINAL DIMENSIONS FIGURE 812
0
fl
S
TFPI7I0 Page 5 o 10
I]
S
Nominal Pipe
Size
Approx.
ANSI Inches
DN
Weight
Lbs.
Part
Number
(kg)
1/2 0.18 72779 DN15 (0,08)
3/4 0.26 72778 DN20 (0,11)
1 0.44 72755 0N25 (0,20)
1-1/4 0.54 72754 0N32 (0,24)
1-1/2 0.71 72753 DN40 (0,32)
2 1.15 72752 0N50 (0,52)
2-1/2 2.29 72758 DN65 (1,04)
_ 1-7
LWii
FIGURE 814 FIGURE 818
IRON TEE STRAIGHT COUPLING
1.63
Figure 814 Figure 818
A B Approx. A B
Inches Inches Weight
Lbs.
Part
Number inches Inches
(mm) (mm) (kg)
(mm) (mm)
1.13 0.56 0.33 86340 1.38 0.31
(28,7) (14,2) (0,15) (3511) (7,9)
1.31 0.75 0.50 86341 0.56
(33,3) (19,0) (0,23) (41,4) (14,0)
1.50 0.81 0.85 86230 1.75 0.38
(38,1) (20,6) (0,38) (44,4) (9,7)
1.75 1.06 1.30 86231 2.00 0.56
(44,4) (26,9) (0,59) (50,8) (14,0)
1.94 1.19 1.63 86232 2.19 0.75
(49,3) (30,2) (0,74) (55,6) (19,0)
2.25 1.50 2.63 86233 2.63 1.13
(57,1) (38,1) (1,19) (66,8) (28,7)
2.69 1.56 4.55 86234 3.00 0.75
(68,3) (39,6) (2,06) (76,2) (19,0)
TABLE 4
NOMINAL DIMENSIONS FIGURES 8148818
TFPI7I0 Page 6of 10
S
S
Page 7 of 10 TFPI7IO
FIGURE 815
REDUCING TEE
Nominal Pipe Size Figure 815
Approx.
ANSI Inches A B C D E F Weight Part
DN Inches Inches Inches Inches Inches Inches Lbs. Number (mm) (mm) (mm) (mm) (mm) (mm) (kg)
1-1/2x1-1/4x112 1.44 1.31 1.69 0.69 0.63 1.13 1.03 86257 DN40x32x15 (36,6) (33,3) (42,9) (17,5) (16,0) (28,7) (0,47)
1-1/2x1-1/4x314 1.50 1.44 1.75 0.75 0.75 1.19 1.10 86258 DN40x32x20 (38,1) (36,6) (44,5) (19,0) (19,0) (30,1) (0,50)
1-1/2 x 1-1/4 x 1 1.63 1.56 1.81 0.88 0.88 1.13 1.31 86259 DN4O x 32 x 25 (41,4) (39,7) (46,0) (22,4) (22,4) (28,7) (0,59)
1-1/2x 1-114x2 2.19 2.13 2.00 1.44 1.44 1.25 1.94 86260 ON40x32x5O (55,6) (54,1) (50,8) (36,6) (36,6) (57,1) (0,88)
1-112x1-1/2x1/2 1.44 1.44 1.69 0.69 0.69 1.13 1.14 86261 DN40x40x15 (36,6) (36,6) 1 (42,9) (17,5) 1 (17,5) (28,7) (0.52 1
1-112x1-1/2x3/4 1.50 1.50 1.75 0.75 0.75 1.19 1.23 86262 DN40x40x20 (38,1) (381) (44,4) (19,0) (19,0) (30,1) (0,56)
1-1/2x1-1/2x1 1.63 1.63 1.81 0.88 0.88 1.13 1.38 86263 DN4O x 40 x 25 (41,2) (41,2) (46,0) (22,4) (22,4) (28,7) (0,62)
1-112x1-112x1-114 1.81 1.81 1.88 1.06 1.06 1.19 1.50 86264 DN40x40x32 (46,0) (46,0) (47,6) (27,0) (27,0) (30,1) (0.68)
1-1/2x1-1/2x2 2.19 2.19 2.00 1.44 1.44 1.25 2.00 86265 0N40 x 40 x 50 (55,5) (55,5) (50,8) (36,6) (36,6) (31,7) (0,91)
2x1 x2 2.25 2.00 2.25 1.50 1.31 1.50 2.18 86266 DN50x25x50 (57,2) (50,8) (57,2) (38,1) (33,3) (38,1) (0,99)
2x1-1/4x2 2.25 2.13 2.25 1.50 1.44 1.50 2.31 86267 DN50 x 32 x 50 (57,2) (54,1) (57,2) (38,1) (36,6) (38.1) (1.05)
2x1-1/2x112 1.50 1.44 1.88 0.75 0.69 1.31 1.50 86268 0N50 x 40 x 15 (38,1) (36,6) (47,8) (19,0) (17,5) (33,3) (0,68)
2x1-1/2x314 1.63 1.50 1.94 0.88 0.75 1.38 1.61 86269 DN50x40x20 (41,4) (38,1) (49,3) (22,4) (19.0) (35,0)
2x1-112x1 1.75 1.63 2.00 1.00 0.88 1.31 1.65 86270 DN50x40x25 (44,5) (41,4) (50,8) (25,4) (22,4) (33.3) (0,75) _______
2x1-112x1-1/2 2.06 1.94 2.19 1.31 1.19 1.44 2.03 86272 DN50 x 40 x 40 (52,4) (49,2) (55,5) (33,3) (30,2) (36,6) (0,92)
2x1-1/2x2 2.25 2.19 2.50 1.50 1.44 1.50 2.37 86273 DN50 x 40 x 50 (57,1) (55,5) (63,5) (38,1) (36.6) (38,1) (1.07)
2 x 2 x 1/2 1.50 1.50 1.88 0.75 0.75 1.31 1.50 86222 DN50x50x15 (38,1) (38,1) (47.8) (19,0) (19,0) (33,3) (0,68)
2 x 2 x 3/4 1.63 1.63 1.94 0.88 0.88 1.38 1.67 86223 0N50 x 50 x 20 (41,4) (41,4) (49,3) (22,4) (22,4) (35,0) (0,76)
2x2x1 1.75 1.75 2.00 1.00 1.00 1.31 1.91 86224 DNSO x 50 x 25 (44,5) (44,5) (50.8) (25,4) (25,4) (33.3) (0,86)
2 x 2 x 1-1/4 1.88 1.88 2.13 1,13 1.13 1.44 2.05 86225 DN50 x 50 x 32 (47,8) (47,8) (54.1) (28,7) (28,7) (36,6) (0,93)
2x2x1-1/2 2.00 2.00 2.19 1.25 1.25 1.50 2.11 86226 DN50x50x40 (50,8) (50,8) (55,6) (31,8) (31.8) (38,1) (0,96)
2x2x2-1/2 2.63 2.63 2.38 1.75 1.88 1.44 3.67 86227 DN50 x 50 x 65 (66,8) (66,8) (60,5) (44,5) (47,8) (36.6) (1,66)
2-1/2x2x3/4 1.75 1.63 2.31 0.63 0.88 1.75 2.22 86274 DN65x50x20 (44,5) (41,4) (58,7) (15,9) (22,4) (44,5) (1,01)
TABLE 5(2 0F2)
NOMINAL DIMENSIONS FIGURE 815
S
Page 8 of 10 TFPI7IO
S
:1iuir flhlll
S
FIGURE 820 FIGURE 830 FIGURE 719
CAP BRASS SEAT UNION PLUG
Nominal Pipe Figure 820 Figure 830 Figure 719 Size
ANSI A Approx. A B Approx. A Approx.
Inches Inches Weight Part Inches Inches Weight Part Inches Weight Part
DN (mm) Lbs. Number (mm) (mm) Lbs. Number (mm) Lbs. Number
(kg) (kg) (kg)
1/2 0.88 0.15 72776 1.88 0.81 0.47 86207 0.94 0.10 86292 DN15 (22,4) (0,06) (47,8) (206) (0,21) (23,9) (0,04)
3/4 1.00 0.22 72777 2.00 0.94 0.66 86275 1.13 0.18 86293 DN20 (25,4) (0,10) (50,8) (23,9) (0,30) (28,7) (0,08)
1
0N25
1.18
(30,0)
0.33
(0,15) 72824 2.19
(55,6)
0.81
(20,6)
1.08
(0,49) 86276 1.25
(31,7)
0.28
(0,13)
86294
1-1/4
0N32
1.31
(33,3)
0.54
(0,24) 72756 2.50
(63,5)
1.06
(26,9)
1.54
(0,70) 86277 1.38
(35,1)
0.50
(0,23)
86295
1-1/2 1.38 0.68 72822 2.63 1.19 2.03 86278 1.44 0.70 86296 0N40 (35,1) (0,31) (66.8) (30,2) (0,92) (36,6) (0,32)
2 1.50 0.96 72823 3.13 1.63 3.15 86279 1.50 0.90 86297 DN50 (38,1) (0,43) (79,5) (41,4) (1,43) (38,1) (0,41)
2-1/2 1.75 1.80 72825 - - - - - - - 0N65 (44,5) (0,82)
TABLE 6
NOMINAL DIMENSIONS FIGURES 820,830 & 719
0
TFPI7I0 Page 9of 10
S
iii _
FIGURE 825 FIGURE 827 FIGURE 816
EXTENSION PIECE HEX BUSHING REDUCING COUPLING
TABLE 7
NOMINAL DIMENSIONS FIGURE 825, 827 & 816
Nominal Pipe Figure 825 Figure 827 Figure 816
Size Extension Piece Hex Bushing Reducing Coupling
A Approx. A Approx. A B Approx.
ANSI inches Inches Weight Part Inches Weight Part Inches Inches Weight Part
DN
(mm)
Lbs. Number (mm) Lbs. Number (mm) (mm) Lbs. Number
(kg) (kg) (kg)
1/2x1/2 1.50 0.20 72751 - - - - - - - DN15x 15 (38,1) (0,09)
112x1/2 2.00 0.27 72980 - - - - - - - DM15 x 15 (50,8) (0,12)
3/4 x 3/4 1.50 0.22 72981 - - - - - - - DN20 x 20 (38,1) (0110)
3/4 x 3/4 2.00 0.31 73982 DM20 x 20 (50,8) (0,14)
3/4x 1/2
- - - -
1.75 0.69 0.38 86772 DN20 x 15 - - (43,2) (17,5) (0,17)
1 x 1/2
- -
1.06 0.22 72726 1.69 0.50 0.38 86228 DN25 x 15 (26,9) (0,10) (42,9) (12,7) (0,17)
1 x3/4
- - -
1.06 0.16 72762 1.75 0.50 0.53
DN25x20 (26,9) (0,08) (43,2) (12,7) (0,24)
1-114x1
- - -
1.19 0.31 72763 - - - - DN32 x 25 (30,2) (0,14)
1-1/2 x
- - -
1.25 0.53 72757 - - - - DM40 x 25 (31,7) (0,24)
1-1/2x1-1/4
- -
1.25 0.35 72764 - - - - DN40x32 (31,7) (0,10)
2x1
- -
1.38 0.75 72759 - - - - DN50 x 25 (35,1) (0,34)
2 x 1-1/4
- - -
1.38 0.69 72761 - - - - DN50x32 (35,1) (0,31)
2x1-1/2
- - -
1.38 0.62 72775 - - - - DN50x40 (35,1) (0,28)
229
0
Description
J See Fire Protection
# Submittal Sheet for
Pressure Rating and
Listing/Approval Information
S tqC0 /Fire & Building
I Products
Technical Services: Tel: (800) 381-9312/ Fax: (800) 791-5500
www.tyco-fire.com
Grinnell Grooved Fire Protection Products
Figure 40-5
Strap
S
General
deluge systems.
WARNING
The Figure 40-5 Strap described herein must be
installed and maintained in compliance with this
document, as we/las withtheapplicable standards
of the National Fire Protection Association, in
addition to the standards of any otherautho rifles
ha ving jurisdiction. Failure to do so mayimpair
the parfonnance of this device.
The owner is responsible for maintaining their
fire protection system and devices in proper
operating condition. The installing contractor or
sprinklermanufacturershould be contacted with
any questions.
Technical
Data
Figure: 40-5
Outlet: Threaded
Approvals: UL, FM, ULC, and VdS;
See Fire Protection Submittal Sheet for exact
Listing /Approval information.
Page 1 of 2
Housing: Ductile iron conforming to
ASTM A-536, Grade 65-45-12
Protective Coatings:
Clear rust inhibitive coating
'Zinc electroplated conforming to
ASTM B-633, Type Ill Service 2 (optional)
U-Bolt: Carbon steel conforming to
ASTM A-307, Grade A, Zinc electroplated
Nuts: Carbon steel conforming to
ASTM A-307, Grade A, Zinc electroplated
Gasket: (specify when ordering)
Grade "E" EPDM green color code.
(See Data Sheet TFP1895 for aid in selecting
proper gasket)
U- U
When placing an order, indicate the full product
name. Please specifythe quantity,figure number,
type of gasket, Grade "E" EPDM, and size.
Grinnell Grooved Piping Products, valves,
accessories and other products are available
throughoutthe U.S., Canada, and internationally,
through a network of distribution centers. You
may write directly or call 215-362-0700 for the
distributor nearest you.
Care and
Maintenance
The owner is responsible for the inspection,
testing, and maintenance of their fire protection
system and devices in accordance with the
applicablestandards of the National Fire Protection
Association (e.g., NFPA 25), in addition to the
standards of any authority having jurisdiction.
The installing contractor or product manufacturer
should be contacted relative to any questions.
Any impairment must be immediately corrected.
It is recommended that automatic sprinkler
systems be Inspected, tested, and maintained by
a qualified Inspection Service.
September 2004
Limited
Warranty
Products manufactured by Tyco Fire Products are
warranted solely to the original Buyer for ten (10)
years against defects in material and workmanship
when paid for and property installed and maintained
under normal use and service. This warranty will
expire ten (10) years from date of shipment byTyco
Fire Products. No warranty is given for products or
components manufactured by companies not
affiliated byownershipwfthlyco Fire Products orfor
products and components which have been subject
to misuse, improperinstallation, corrosion, orwhich
have not been installed, maintained, modified or
repaired in accordance with applicable Standards of
the National Fire Protection Association (NFPA),
and/orthestandardsofanyotherAuthorities Having
Jurisdiction. Materials found byTyco Fire Products
to be defective shall be either repaired orreplaced,at
Tyco Fire Products' sole option. Tyco Fire Products
neither assumes, nor authorizes any person to
assumefor, any other obligation inconnectionwifh
the sale of products or parts of products. Tyco Fire
Productsshallnotberesponsibleforsprinklersysteni
design errors orinaccurateorincompleteInformation
supplied by Buyer or Buyers representatives.
IN NO EVENT SHALL TYCO FIRE PRODUCTS BE
LIABLE, IN CONTRACT, TORT, STRICT LIABILITY
OR UNDER ANY OTHER LEGAL THEORY, FOR
INCIDENTAL, INDIRECT, SPECIAL OR
CONSEQUENTIAL DAMAGES, INCLUDING BUTNOT
LIMITED TO LABOR CHARGES, REGARDLESS OF
WHETHER1YCO FIREPRODUCTS WAS INFORMED
ABOUT THE POSSIBILITY OF SUCH DAMAGES,
AND IN NO EVENTSHALL1YCO FIRE PRODUCTS'
LIABILITY EXCEED AN AMOUNT EQUAL TO THE
SALES PRICE.
THE FORINM WARRANTY$ AWE IIJLIEJJOF
ANYAND ALL OThER WA11EERO
(B
TFPI72O
The Figure40-5 Strap is an economical alternative
to welded pipe outlets on steel pipe. Ordering
The Figure 40-5 Strap may be used with full
lengths of pipe and eliminates threading and
welding, decreasing waste and installation time.
The 40-5 Strap may be used in wet, dry pipe and
Pipe Nominal Dimensions Hole Net
Size Size Wt. A B C D
Run x Inches Inches Inches Inches Inches Lbs.
Branch mm mm mm mm mm Kg.
1'/i" X 1/2" 2.00 1.50 3.50 1.20 1/,e 0.84
50.8 38.1 88.9 30.5 30.2 0.4
11/4" x 3/
4
0 2.00 1.50 3.50 1.20 1/I6 0.88
50.8 38.1 88.9 30.5 30.2 0.4
1V4" X 1'.12.31 1.68 3.50 1.20 13'16 1.13
58.7 42.7 88.9 30.5 30.2 0.5
11/2' X 1/2I 2.12 1.62 3.50 1.32 1/16 0.84
53.8 41.1 88.9 33.5 30.2 0.4
11/2"X3/4° 2.12 1.62 3.50 1.32 1/16 0.88
53.8 41.1 88.9 33.5 30.2 0.4
1V2"X ill 2.43 1.80 3.50 1.32 1/i 1.13
61.7 45.7 88.9 33.5 30.2 0.5
2" x 1/20 2.36 1.86 3.74 1.55 1/i 0.88
59.9 47.2 95.0 39.4 30.2 0.4
2"X3/4" 2.36 1.86 3.74 1.55 1/l6 0.95
59.9 47.2 95.0 39.4 30.2 0.4
20 1" 2.67 2.04 3.74 1.55 1/i 1.16
67.8 51.8 95.0 39.4 30.2 0.5
21/2° )( 1/2" 2.61 2.11 4.25 1.80 1/16 0.90
66.3 53.6 108.0 45.7 30.2 0.4
21/2" X3/4" 2.61 2.11 4.25 1.80 1/16 0.99
66.3 53.6 108.0 45.7 30.2 0.4
FX2. 2.92 2.29 4.25 1.80 1/16 1.21
74.2 58.2 108.0 45.7 30.2 0.5
Item Description
1 Housing
2 Gasket
3 Flanged Nut
4 U-Bolt
Fitting
Size
Equivalent Length
(1 inch pipe)
11/4"X 1" 8
11/2"X 1° 6
2°x 1,' 6
21/2°X 1" 4
The friction loss for these outlets is specified in
equivalent length of 1 inch Schedule 40 (C=120) pipe. S
Page 2012 TFP1 720
Figure 40-5 Strap
The 1 inch outlets can be used with a nipple leading Note: Outlet threads conforming to ISO 7-1 are available, contact
directly to a sprinkler. These fittings should be used Tyco Fire Products.
for hydraulically calculated systems only.
. General Notes: It is the Designer's responsibility to select products suitable for the intended service and to ensure
that pressure ratings and performance data is not exceeded. Always read and understand the installation
instructions (IH.1 000). Never remove any piping component or correct or modify any piping deficiencies without
first depressurizing and draining the system. Material and gasket selection should be verified to be compatible
for the specific application.
TYCO FIRE PRODUCTS, 451 North Cannon Avenue, Lansdale, Pennsylvania 19946 Printed U.S.A.
Upright Pendent
Vertical Sidewall Horizontal Sidewall
Recessed Concealed
Horizontal Sidewall Pendent
Bulletin 014 Rev. L
41 R 11abile Model Fl FR Series
Quick Response
Standard Spray
ct C
(t
C -J
r_
Model Fl FR56 Sprinkler Types
Standard Upright
Standard Pendent
Conventional
Vertical Sidewall
Horizontal Sidewall El
Model Fl FR56 Recessed Sprinkler Types
Standard Pendent/F1/F2/FP
Horizontal Sidewall
Model Fl FR56 Concealed Sprinkler Types
Standard Pendent
Model F1FR42, F1FRXLH & Fl FR28 Sprinkler
Types
Standard Upright
Standard Pendent
Model Fl FR42, Fl FRXLH & Fl FR28 Recessed
Sprinkler Types
Standard Pendent
Model Fl FR56LL & Fl FR42LL Low Lead Sprinkler
Types*
Standard Pendent
Less than 0.25% Lead Content
Listing & Approvals
Underwriters Laboratories Inc. and Certified for
Canada (cULus).
Factory Mutual Approvals (FM)
Loss Prevention Council (LPCB, UK)
VdS SchadenverhUtung GmbH
'NSF Certified to NSF/ANSi Standard 61 Annex G
EC Certificate: 0786-CPD-40239 (RA1414), 0786-
CPD-4025 1 (RA1 425), 0786-CPD-40252 (RA1 475)
UL Listing Category
Sprinklers, Automatic & Open (VNIV)
Quick Response Sprinkler
Product Description
Reliable Models F1FR56, F1FR56LL, F1FR42, F1FR42LL,
F1FRXLH & F1FR28 Series Sprinklers are quick response
sprinklers which combine the durability of a standard sprin-
kler with the attractive low profile of a decorative sprinkler.
The Models F1FR56, F1FR56LL, F1FR42, F1FR42LL,
XLH Upright XLH Pendent
F1FR42, F1FR42LL, F1FRXLH &
F1FR28 Series sprinklers to apply wa-
ter to a fire much faster than standard
sprinklers of the same temperature rat-
ing.
The glass bulb consists of an accu-
rately controlled amount of special fluid
hermetically sealed inside a precisely
manufactured glass capsule. This glass bulb is specially
constructed to provide fast thermal response.
At normal temperatures, the glass bulb contains the fluid
in both the liquid and vapor phases. The vapor phase can
be seen as a small bubble. As heat is applied, the liquid
expands, forcing the bubble smaller and smaller as the liq-
uid pressure increases. Continued heating forces the liquid
to push out against the bulb, causing the glass to shatter,
opening the waterway and allowing the deflector to distrib-
ute the discharging water.
Conventional
Recessed
Pendent/Fl/F2
Recessed
PendentJFP
XLH Recessed
Pendent F1/F2
XLH Recessed
Pendent FP
F1FRXLH & Fl FR28 Series Recessed automatic sprinklers •
utilize a 3.0 mm frangible glass bulb. These sprinklers have
demonstrated response times in laboratory tests which are
five to ten times faster than standard response sprinklers.
This quick response enables the Model F1FR56, F1FR56LL,
Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York 10523
S
Application
Quick response sprinklers are used in fixed fire protection systems: Wet, Dry, Deluge or Preaction. Care must be
exercised that the orifice size, temperature rating, deflector style and sprinkler type are in accordance with the latest
published standards of the National Fire Protection Association or the approving Authority Having Jurisdiction. Quick
response sprinklers are intended for installation as specified in NFPA 13. Quick response sprinklers and standard re-
sponse sprinklers should not be intermixed.
*p,nt/e
(XLH Only)
Deflector
Load Screw
Washer Bulb
Frame Cup
O14FGO6A
Model F1FR42, F1FRXLH Upright
Technical data:
Thread Max. Mm. Temperature Models Discharge Coefficient Response Size Working Working Rating Finish Pressure Pressure
F1FR56
**F1 FR56LL.0) K 5.6
Quick 1/2" NPT See See F1FR42
**F1 FR42LL0) K 4.2 Response (R1/2) 175 PSI 7 PSI "Temperature "Finish Table"
Fl FRXLH Ratings" Table.
F1FR28 K2.8
"Low Lead Sprinklers available only with Temperature Rating 200°F/93°c
Material Data:
Frame Deflector Load Screw *pintle Cup Washer Bulb
DZR Brass CDA Alloy 260,
CDA Alloy 220 CDA Alloy 360 CDA Alloy 360 CDA Alloy 651 Nickel Alloy 440 or Alloy 360
QM Brass or or or coated with PTFE Adhesive Glass
**Low Lead Brass or
CDAAlloy51O CDA Alloy 544 CDA Alloy 544 CDA Alloy 693 Tape
2.
Model Fl FR56, Upright, Pendent & Conventional Sprinklers
Model Fl FR42, Fl FRXLH & Fl FR28 Upright & Pendent Sprinklers
Installation Wrench: Model D Sprinkler Wrench
Installation Data:
Nominal
Orifice
Thread
____________
Nominal K Factor
_______________
Sprinkler
__________
Approval
__________
Sprinkler Identification Number
(SIN)
Size US J Metric Height Organization Upright Pendent
Standard-Upright (SSU) and Pendent Deflectors Marked to Indicate Position
1/2" (15mm)(1( 1/2' NPT (R1/2) 5.6 I 80 2.25" (57mm) 1, 2, 3, 4, 6
7/16" (10mm) 1/2" NPT (R1/2) 4.2 60 2.25" (57mm) 1 RA142314 RA14134
3/8" (10mm) 1/2" NPT (R1/2) 2.8 40 2.25" (57mm) 1 RA142114 RA14114
Conventional-Install in Upright or Pendent Position
15mm (1) 1/2" NPT (R1/2) 5.6 1 80 1 57mm J 3, 4, 6 1 RA14753
cULus listed corrosion resistant (Polyester coated) sprinkler.
Polyester coated FM approved sprinkler.
Polyester coated LPCB & VdS approved sprinkler RA1425, RA1414 & RA1475.
Electroless Nickel PTFE (Teflon)* Plated - cULus listed Corrosion Resistant
Upright Pendent Conventional
Model Fl FR56LL & Fl FR42LL Pendent Sprinklers
Installation Wrench: Model D Sprinkler Wrench
Installation Data:
Nominal
Orifice
Thread
____________
Nominal K Factor
_______________
Sprinkler (SIN) __________
Approval
__________
Sprinkler Identification Number
Size US Metric Height Organization Pendent
Standard-Pendent Deflectors Marked to Indicate Position
1/2" (15mm))1) 1/2" NPT (R1/2) 5.6 80 2.25" (57mm) 1 1,5 RA1415
7/16(11mm) 1/2" NPT (R1/2) 4.2 _60 2.25"(57mm) 1,5 RA1410
(1) cULus listed corrosion resistant (Polyester coated) sprinkler.
*DuPont Registered Trademark
3.
4.
Vertical Sidewall
*DuPont Registered Trademark
Sprinkler Type Deflector to Ceiling Distance
(Mm. - Max.)
Upright 4(102mm) - 12" (305mm)
Pendent 4" (102mm) - 12" (305mm)
Model Fl FR56, Fl FR42, Fl FRXLH & Fl FR28 Quick Response Recessed Pendent SprinkIer(1
Installation Wrench: Model GF192 Sprinkler Wrench
Installation Data:
Nominal
Orifice
Thread
Size
K Factor Sprinkler
Height
Sprinkler Identification Number
(SIN) US Metric
1/2" (15mm) 1/2' NPT(R½) 5.6 80 2.25" (57mm) RA1414
7/16" (10mm) 1/2" NPT(R1/2) 4.2 60 1 2.25" (57mm) RA1413
3/8" (10mm) 1/2" NPT(R1/2) 2.8 1 40 1 2.25" (57mm) RA1411
(1) Refer to escutcheon data table for approvals & dimensions
Model Fl FR56LL & Fl FR42LL Quick Response Recessed Pendent Sprinkler(1)
Installation Wrench: Model GFR2 Sprinkler Wrench
Installation Data:
Nominal
Orifice
Thread
Size
K Factor Sprinkler
Height
Sprinkler Identification Number
(SIN) US Metric
1/2" (15mm) 1/2" NPT(R½) 5.6 80 2.25" (57mm) RA1415
7/16(10mm) 1/2" NFl (R1/2) 1 4.2 60 1 2.25" (57mm) RA1410
S
Refer to escutcheon data table for approvals & dimensions
f
V_•U/URm
EC,i / FAEE OF ACENC
r 1 SE FACE OF COONS &MENSON
FE JlONSS I
A MWIMU.
_
, ir4-
I
__ .,r MESIMUM RECESS - liii II) till
I r M&RIMUM RE -?/8T2NOr,,mj AT MINIMUM RECESS - -5/874E.Jmm)
.. • SS ________
Model F1 FR56, F1FR56LL, F1FR42, F1FR42LL, F1FRXLH &
F1FR28F1 or F2
I i• x t • REDUCER
2 5 O -
HOLE IN COILING
2 5/I6 COt [58.7,nm1 Cup
CEILING £FAXE Q/ OIlING I TO FACE OF C0UW I DIMENION
AT MIX/MUM
RECESS
- E—I/238m,,,]
AT MIX/MUM RECESS — IT25.4m,J
I AT MAXIMUM RECESS - 9/I6TI43m,,,J J4IZ7soJ
.T
AT MINIMUM RC - IT25.4mmJ
3114 DL4.(82Mm,,,)
Model F1 FR56, F1FR56LL, F1FR42, F1FR42LL, F1FRXLH &
F1FR28 FP
Model Fl FR56 Quick Response Vertical Sidewall Sprinkler
Installation Wrench: Model D Sprinkler Wrench
Installation Position: Upright or Pendent
Approval Type: Light Hazard Occupancy
Installation Data:
Nominal K Factor Sprinkler Nominal Thread Size Sprinkler Approval Identification Orifice US Metric Height Organizations Numbers (SIN)
½" (15mm) ½" NPT (R1/2) 5.6 80 2.25" (57mm) 1, 2, 3 RA1 485(2)(3)
15mm ½" NPT(R1/2) 5.6 80 2.25" (57mm) 3(1)
LPC Approval is for pendent position only.
cULus Listed corrosion resistant (Polyester coated) sprinkler.
Electroless Nickel PTFE (Teflon")* Plated - cULus listed Corrosion Resistant
S
11
Model Fl FR56 Quick Response Horizontal Sidewall Sprinkler
Deflector: HSW
Installation Wrench: Model D Sprinkler Wrench
Installation Data: Horizontal Sidewall
Nominal K Factor Sprinkler Approval Organizations Sprinkler
_________________
Height and Type of Approval Nominal Orifice Thread Size Identification I
US Metric Light Hazard I
Ordinary Numbers (SIN) Hazard
1/2" (15mm) ½" NPT (R1/2) 5.6 80 2.63" (67mm) 1,2 1
" cULus Listed corrosion resistant (Polyester coated) sprinkler.
Polyester coated FM approved sprinkler.
Electroless Nickel PTFE (Teflon®)* Plated - cULus listed Corrosion Resistant
FACE OF FITTING
TO FACE OF CEILING DIMENSION
Fl ESCUTCHEON
AT MAXIMUM RECESS = 1725.4mm]
AT MINIMUM RECESS = 3/879.5mm]
F2 ESCUTCHEON
AT MAXIMUM RECESS 3/4719mm]
AT MINIMUM RECESS = 3/879.5mm]
2 1/4 HOLE DIA.
[57.2mm]
7" X 7/2" REDUCER
Fl ESCUTCHEON
AT MAXIMUM RECESS = 1-3/8734.9mm]
-- 7 AT MINIMUM RECESS 2-7/76752.4mm]
VI F2 ESCUTCHEON
I AT MAXIMUM RECESS = 7-5/8741.3mm/
k -1/8" AT MINIMUM RECESS = 2-7/76752.4mm]
[3.2mm]
Horizontal Sidewall
1 15/76 OIA.\
49.2mmJ 7
7 (1)
I 4"-72"
I [IOI.6mm-304.6mm] 27/32" OIA. CEILING TO
[72.2mm] DEFLECTOR
TURN COLLAR UNTIL -
TIGHT AGAINST SPRINKLER
WRENCH BOSS. \ I F? ESCUTCHEON
j 3/4719mm] ADJUSTMENT
F2 ESCUTCHEON
1/2712.7mm] ADJUSTMENT
RECESSED HSW W/F1 OR F2 ESCUTCHEON
(1) FM APPROVED FOR 4" - 6" [70 7.6MM - 152.4MM] CEILING TO DEFLECTOR WITH F2 ONLY.
Note: For Recessed HSW Sprinklers use installation wrench GFR2.
cULus permits use with Fl, F2 or FP escutcheons for "Light Hazard"
only. While FM limits use for the same hazard with the F2 escutcheon
only.
Model Fl FR56 Quick Response Concealed Pendent Sprinklers
Installation Wrench: Model AOl Sprinkler Wrench
Technical Data:
Nominal
Orifice
"K" Factor Thread
Size Model
Temp. Rating Max.
Ambient
Temp
Bulb
Color Approvals
Sprinkler
Identification
Number(SIN) US Metric Sprinkler Cover
½" (15mm) 5.6 80 ½" NPT F1 FR 1350F/570C 1350 F/570C 100°F/38°C Orange 1 RA1414
½" (15mm) 5.6 80 ½" NPT F1 FR 1550F/680C 1350F/570C 100°F/380C Red 1, 4(1), 6 RA1414
½" (15mm) 5.6 80 ½" NPT F1 FR 1750F179°C 165°F/74°C 100°F/38°C Yellow 1 RA1414
½" (15mm) 5.6 80 ½" NPT F1 FR 200°F/930C 1650F/740C 150°F/650C Green 1 RA1414
(I) For VdS only = 155°F/68°C Norbulb and 1/2" [12,7mm] adjustment.
Model Fl FR56LL Quick Response Concealed Pendent Sprinklers
Installation Wrench: Model RC Sprinkler Wrench
Technical Data:
Nominal
Orifice
"K" Factor I Thread
Size I Model I
Temp. Rating Max.
Ambient Bulb
Color Approvals
Sprinkler
Identification US Metric Sprinkler
I
I Cover Temp Number(SIN)
½" (15mm) 5.6 80 ½" NPT F1FR56LL 200°F/930C 1650F1740C 150°F/65°C Green 1,5 RA1414
*DuPont Registered Trademark
5.
-2 5/8" DIA.
HOLE IN CEILING
I 7/2" MAX.
FACE OF FITTING
_...._.TO FACE OF CEILING
DIMENSION
15/16"
I" x 1/2" REDUCING
TEE OR ELBOW ""
2 5/16" 0/A -
CUP
CEILING-" -
1/2" MAX. I
COVER ADJUSTMENT
COVER PLATE -
ASSEMBLY 0/A.
SPRINKLER
- 2 5/8" DIA.
HOLE IN CEILING
1 1/2" MAX.
FACE OF FITTING
TO FACE OF CEILING
DIMENSION
3/4"
- x 1/2" REDUCING
TEE OR ELBOW
2 5/16" 0/A -
CUP -...
:
COVER ADJUSTMENT
5/16" MAX. J
COVER PLATE-
ASSEMBLY 5116" DIA.
SPRINKLER
CONCEALED, 1/2" ADJUSTMENT
Figure 1
Installation Aid
A protective cap is included for use during installation.
Important: The F1FR56 Sprinkler with Model OCR cover
plate is not an FM Approved combination.
Installation
Quick response sprinklers are intended for installation as
specified in NFPA 13, Quick response sprinklers and stan-
dard response sprinklers should not be intermixed.
The Model F1FR56, F1FR56LL, F1FR42, F1FR42LL,
F1FRXLH & F1FR28 Recessed Quick Response Sprin-
klers are to be installed as shown. The Model Fl or F2 Es-
cutcheons illustrated are the only recessed escutcheons
to be used with the Model F1FR56, F1FR56LL, F1FR42,
F1FR42LL, F1FRXLH & F1FR28 Sprinklers, The use of any
other recessed escutcheon will void all approvals and ne-
gate all warranties.
When installing Model F1FR56, F1FR56LL, F1FR42,
F1FR42LL, F1FRXLH & Fl FR28 Sprinklers, use the Model
D Sprinkler Wrench. Use the Model GFR2 Wrench for install-
ing F1FR56, F1FR56LL, F1FR42, F1FR42LL, F1FRXLH &
F1FR28 Recessed Pendent Sprinklers, Any other type of
wrench may damage these sprinklers.
NOTE: A leak tight 1/2" NPT (19112) sprinkler joint can be
obtained with a torque of 8-18 ft-lbs (10,8 - 24,4 N-m). Do
not tighten sprinklers over maximum recommended torque.
It may cause leakage or impairment of the sprinklers,
The Models F1FR56/CCP & F1FR56LL/CCP Concealed
Sprinkler use the 1/2" orifice, ½" NPT (191/2), Model F1FR56
& F1FR56LL Pendent Sprinkler with a threaded Model COP
cup which is factory attached to the sprinklers. The Model
F1FR56 Pndent is available in temperature rating of 135°F
(570C), 155°F (68°C), 175°F (79°C) or 200°F (930C). The
Model F1FR56LL Pendent is available only in a rating of
200°F (93°C). The concealed sprinkler assemblies are com-
pleted by the installation of the attractive low profile Model
CCP push on cover plate assembly, rated 135°F (57°C) or
165°F (74°C) for the Fl FR56 and 165°F (74°C) for the Fl FR56
LL. The cover plate and sprinkler cup assemblies are joined
using a cover plate skirt with flexible tabs for threaded en-
*DuPont Registered Trade Mark
CONCEALED. 5/16" ADJUSTMENT
Figure 2
gagement. A choice of two cover plate assemblies provide
either 1/2(13mm) or 5/8" (8mm) of cover adjustment,
Do not install these sprinklers in ceiling which have positive
pressure in the space above.
After a 2/8" (67mm) diameter hole is cut in the ceiling, the
sprinkler is easily installed with the Model RC1 Wrench. A
Teflon* based thread sealant should be applied to the sprin-
kler threads only. The Model RC1 Wrench is then used to
engage the sprinkler wrenching surfaces and to install
the sprinkler in the fitting. When inserting or removing the
wrench from the sprinkler/cup assembly, care should be tak-
en to prevent damage to the sprinkler. DO NOT WRENCH
ON ANY OTHER PART OF THE SPRINKLER. The cover
plate is then pushed onto the cup. Final adjustment is made
by hand turning the cover plate until the skirt flange makes
full contact with the ceiling. Cover plate removal requires
turning in the counter clockwise direction.
After installation, inspect all sprinklers to ensure that there
is a gap between the cover plate and ceiling and that the
four cup slots are open and free from any air flow impedi-
ment to the space above.
Concealed cover plate/cup assemblies are listed only for
use with specific sprinklers. The use of any other concealed
cover plate/cup assembly with the Model F1FR56 Pendent
Sprinkler or the use of the Model CCP Concealed cover
plate assembly on any sprinkler with which it is not specifi-
cally listed my prevent good fire protection and will void all
guarantees, warranties, listings and approvals.
Glass bulb sprinklers have orange bulb protectors to
minimize bulb damage during shipping, handling and in-
stallation. REMOVE THIS PROTECTION AT THE TIME THE
SPRINKLER SYSTEM IS PLACED IN SERVICE FOR FIRE
PROTECTION. Removal of the protectors before this time
may leave the bulb vulnerable to damage. RASCO wrench-
es are designed to install sprinklers when covers are in
place. REMOVE PROTECTORS BY UNDOING THE CLASP
BY HAND, DO NOT USE TOOLS TO REMOVE THE PRO-
TECTORS.
Temperature Ratings
Classification
Sprinkler
Temperature Max. Ambient
Temp. Bulb Color
0 I OF
Ordinary 57 135 100°F (38°C) Orange
Ordinary 68 155 100°F (38°C) Red
Intermediate 79 175 150°F (66°C) Yellow
Intermediate 93 200 150°F (66°C) Green
High " 141 286 1 225°F (107°C) Blue
(1) Not available for recessed sprinklers.
Escutcheon Data (1)
(1) SIN RA1435 - cULus permits use with Fl F2 or FP escutcheons for light
hazard" on while FM limits use for same hazard with F2 escutcheon on
Maintenance
The Model F1FR56, F1FR56LL, F1FR42, F1FR42LL,
F1FRXLH and Model F1FR56, F1FR56LL, F1FR42,
F1FR42LL, F1FRXLH & F1FR28 Recessed Sprinklers should
be inspected and the sprinkler system maintained in accor-
dance with NFPA 25. Do not clean sprinklers with soap and
water, ammonia or any other cleaning fluids. Remove dust
by using a soft brush or gentle vacuuming. Remove any
sprinkler which has been painted (other than factory ap-
plied) or damaged in any way. A stock of spare sprinklers
should be maintained to allow quick replacement of dam-
aged or operated sprinklers. Prior to installation, sprinklers
should be maintained in the original cartons and packaging
to minimize the potential for damage to sprinklers that would
cause improper operation or non-operation.
Sprinkler Types
Standard Upright
Standard Pendent
Conventional
Recessed Pendent
Vertical Sidewall
Horizontal Sidewall
Recessed Horizontal sidewall
Concealed pendent
Maximum Working Pressure
175 psi (12 bar)
100% Factory tested hydrostatically to 500 psi (34.5 bar)
*DuPont Registered Trademark
Finishes (1)
Standard Finishes
Sprinkler Escutcheon Cover plate')
Bronze Brass Chrome
Chrome Plated Chrome White
Polyester Plated
Coated (4)(5)(6) White Painted
Special Application Finishes
Sprinkler Escutcheon Cover plate1
Electroless Nickel
PTFE(TefIon )*(7)
Electroless Nickel
PTFE (Teflon®)* Bright Brass
Bright Brass (3) Bright Brass Black Plating
Black Plated Black Plated Black Paint
Black Paint26 Black Paint Off White
Off White (1)(6) Off White I Satin Chrome
Chrome Dull I Chrome Dull I
Other finishes and colors are available on special order. Consult the
factory for details. Custom color painted sprinklers may not retain their
UL Corrosion resistance listing. Coverplate custom paint is semi-gloss,
unless specified otherwise,
cULus Listed only.
200°F (93°C) maximum.
cULus listed "corrosion resistance" applies to SIN Numbers RA1435
(HSW), RA1485(VSW), RA1425 (Upright), RA1414 (Pendent) and
RA1415 (Pendent) in standard black or white. Corrosion resistance in
other polyester colors is available upon request.
FM Approvals finish as "Polyester coated" applies to SIN Number
RA1414, RA1435 and RA1425 in standard black or white.
LPCB and VdS Approved finish applies onlyto RA1425, RA1414 and RA1475.
cULus listed Corrosion Resistant
Ordering Information
Specify:
Sprinkler Model
Sprinkler Type
Orifice Size
Deflector Type
Temperature Rating
Sprinkler Finish
Escutcheon Type
Escutcheon Finish (where applicable)
Cover plate Model
Cover plate Thread size
Cover plate Temperature
Cover plate Adjustment
Cover plate Finish
Note: When Model Fl FR56 Recessed sprinklers are ordered, the sprinklers
and escutcheons are packaged separately.
S
7.
1]
300
RING HANGER
<jR> C®US I thru 4 inch pipe 112 and 3/4 Inch pipe
5 thru 8 inch pipe
SIZE - 1/2 thru 8 inch pipe.
MATERIAL - Carbon Steel, Mu. Galvanized to G-90 specification.
FINISH - Mil. Galvanized and Stainless Steel.
LISTING - UL in US and CANADA.
APPROVAL - Factory Mutual Research.
CONFORMS WITH: Federal Specification WW-H- 171 (Type 10),
Manufacturers Standardization Society ANSI/MSS-SP-58 (Type 10); install
in accordance with ANSI/MS S- SP-69.
MAXIMUM TEMPERATURE - 650°F.
FUNCTION - For fire sprinkler and general piping purposes.
Swivel nut permits hanger adjustment after installation.
FEATURES -
1 thru 4 inch:
* Offset edge for EASY pipe insertion.
1 thru 8 inch:
* Full length knurl on swivel nut for better grip.
UNIQUE FEATURES
1 thru 3 inch:
* UL listed to accept AFCON #310 Surge Restrainer.
* Swivel nut
Retained in ring to keep the assembly intact prior to installation.
Removed easily if needed.
* UL listed for use on CPVC pipe.
ORDERING - Part # and pipe size.
Index
IMPERIAL MAX REC.
LOAD LBS.
METRIC"
PIPE ROD PIPE ROD
1/2 3/8 400 10
3/4 400 20 10
1 3/8 400 25 10
11/4 3/8 400 1 32 to
11/2 3/8 400 1 40 10
2 3/8 400 50 10
21/2 3/8 600 65 10
3/8 600 80 10
31/2 3/8 600 10
4 3/8 1000 100 10
5 1250 125 12
6 112 1250
1 1250 00
150 12
8 112
* Order Part #300m
Note: 1/2" Ring Hanger not <FM> approved
F~
Fcn
655
ALL THREADED ROD CUT TO LENGTH
ROD
SIZE
MAX. REC. LOAD LBS.
FOR SERVICE TEMP.
650°F 750°F
3/8 610 540
1/2 1130 1010
5/8 1810 1610
3/4 2710 2420
7/8 3770 3360
NOTE; maximum Temperature: 750°F
SIZE - 3/8 thru 7/8 inch rod in linch
increments.
MATERIAL - Carbon Steel.
FINISH - Plain, Electro-Galvanized and
Stainless Steel.
ORDERING - Part #, rod diameter, rod
length and finish.
n
2/00 E,
S
S
!OII]D
Use #14 Nut
- 1/4 " Rodr&viii i rmrim
Driver (Item #100)
_
Item# Model Shk Lgth Shk Dia Box Qty Weight
(per 100) Case Qty
20 GST .750 3/4 1/4 100 4.75 1000
21 GST 100 1 1/4 100 5.00 1000
22 GST 200 2 1/4 100 6.50 1000
23 GST300 3 1/4 100 7.50 1000
24 GST 600 6 1/4 50 9.00 500
[1 14!
i
#14
(Item #100-black)
Sammys 1/4,318" rod
d Joist
mum 2" imbedment into base
rial for NFPA 13 compliance
Page 4
WOOD - Sammys
WOOD 1kIIRod (Vertical 1L1 rmiii
Use #14 Nut Driver (Item #100)
Approals Item# Model ShkLgth ShkDia FMTest
Load, lb.
ULTest
Load lb.
ULIFM
Pipe Size
Actual Pullout Box Qty
10 GST.75 3/4 1/4 564#-6Ply 100
NFPA 11 GST 10 1 1/4 210# - 7/16
670# - 3/4"
OSB
Ply 100
UL•FM•NFPA 12 GST20 2 1/4 940# 850# 3/4-2 1/2 1760# - Fir 100
UL-NFPA * 27 GST 25-380 21/2 3/8 1500# 4 2113#-Fir 50
UL-FM-NFPA 13 GST 30 3 1/4 1475# 1500# 3/4-4 2060# -Fir 100
NFPA 403 GST40 4 1/4 2180# - Fir 50
NFPA 14 JGST60 1 6 1 1/4 2230# - Fir 50
#I4SW
(Item #101-red)
Sidewinders &
Sammys 1/2' rod
i1!(III] VMIRodt&7Tfl1 l IITTT1TI
Use #14SW Nut Driver (Item #101)
Item # Model Shk Lgth Shk Dia Actual Pullout Box Qty Weight Case (per 100) Qty
8 GST2 2 1/4 1760#-Fir 50 7.00 500
* 06 GST2.5-380 21/2 3/8 2113#-Fir 50 10.00 500
15 I GST3 1 3 1 1/4 1 2275# - Fir 1 50 10.50 500
16 JGST4 1 4 1 1/4 1 2180#-Fir 50 10.60 500
17 JGST6 1 6 1 1/4 1 22309 - Fir 50 10.95 500
Not less than
2" nominal width
(11/2")
TJI Joist! Truss
Consult truss manufacturer for
recommended installation point.
*pre_drilling may be required
for items #27 and #06.
Tools available on page 9.
For vertical use.
i W-M Install in center
I oflowerface.
Note: Screws must be installed with appropriate nut driver to comply with warranty
Rod ri(Ho6zontallk riimn
Use #14SW Nut Driver (Item #101)
Item# I Model I Shk Shk I Actual
'Shear/Pullout Box Qty I I Weight I Case Qty (per 100)
4016 SWG100 1 1/4 I 100 7.50 I 1000
300 1SWG200 2 1/4 1725# -Fir 100 8.00 1000
WOOD -
Use #14SWNutDriver
3/8" Rodri I mw ifl1 T!TITI
(Item#101)
Approvals Item# Model Shk Lgth Shk Dia UL Test
Load lb.
UIJFM
Pipe Size
ActualBox Shear/Pullout Qty Weight
(per 100)
18 SWG10 1 1/4 100 6.00
UL•NFPA 19 SWG20 2 1/4 12504 3 17254-Fir 100 7.00
UL•NFPA * 26 SWG25-380 21/2 3/8 1500# 4 2249# - Fir 50 10.25
-
25 ISWG30 1 3 1 1/4 1 1 1 50 1 8.50
#I4SW
(Item #101-red)
Sidewinders &
Sammys 1/2" rod
Prestressed Concrete
Pali e-5
WOOD —Sidewinders
Not less than 2" nominal width (11/2") up
to 3 1/2" pipe; not less than 3" nominal
I- width 4" & 5" pipe
Floor Joist r I ____
TJI Joist! Truss
Consult truss manufacturer for
recommended installation point
*pre..drilling may be required
for item #26.
Tools available on page 9.
S
1113 Minimum 2 1/2" from bottom for
branch lines. Minimum 3" from
bottom for mainlines. Exception:
I
This requirement shall not apply to
2" or thicker nailing strips resting
SHEETROCK - Tog g i e
on top of steel beams.
ii :1 N SI rriuiRod(Veftical rmnTi
Use #14 Nut Driver (Item#100)
Item # I Model Shk Lgth Shk Dia Actual Pullout Box Qty Weight Case Qty (per 100)
71 SST300 3 1/4 450# Lath & Plaster 50 12.00 500 404# 2 Layers 5/8 Rock
#14
(Item #100-black)
Sammys 1/4", 3/8" rod
iiSHEETROCK Ji:iRod (Vertical Mount)
Use #14 Nut Driver (Item #100)
Item# Model Shk Lgth1 Shk Dia Actual Pullout Pkg Qty Weight Case Qty
_______________ (per 100)
70 SST 30 I
1/4 450# Lath & Plaster 50 12.00 500 404# 2 Layers 5/8 Rock
Note: Screws must be installed with appropriate nut driver to comply with warranty