HomeMy WebLinkAbout1896 RUTHERFORD RD; ; FPC2016-0002; Permit(city of
Carlsbad
Print Date: 03/21/2022 Permit No: FPC2016-0002
Job Address: 1896 RUTHERFORD RD, CARLSBAD, CA 92008-7326 Status: Closed - Finaled
Permit-Type: FIRE-Construction Commercial Work Class: Fire Alarm
Parcel #: Track #: Applied: 11/08/2016
Valuation: $0.00 Lot #: Issued: 11/21/2016
Occupancy Group: Project #: Finaled Close Out: 03/14/2017
#of Dwelling Units: Plan #:
Bedrooms: Construction Type:
Bathrooms: Orig. Plan Check U: Inspector:
Plan Check U: Final Inspection:
Project Title:
Description: INSTALLATION OF NEW CELL COMMUNICATOR TO MONITOR EXISTING FACP
Applicant:
M AND B ELECTRIC INC
14460 KENTFIELD PL
POWAY, CA 92064-3361-SAN DIEGO
(858) 668-2803
FEE AMOUNT
Fire Inspection Fee Manual $156.00
Fire Protection Sys Manual $175.00
Total Fees: $331.00 Total Payments To Date: $331.00 Balance Due: $0.00
Fire Department Page 1 of 1
1635 Faraday Avenue, Carlsbad CA 92008-7314 1760-602-4665 760-602-8561 f I www.carlsbadca.gov
I
From Tyco Security Products FPC20I6-0002
1896 Rutherford RD
3G technology from DSC!
Features That
Make a Difference:
Uses HSPA (3G) network for
high-speed, reliable and low-
cost communications to an IP
receiver
Automatically switches to 2G
(EDGEIGPRS) if 30 service is
not available
Compatible with control panels
that communicate using Contact
ID or SIA (300 baud) formats
Full event reporting
4 on-board inputs with NC, NO
or SEOL supervision
4 on-board outputs (open
collector)
Activation and initialization via
automated telephone activation
system (VRU), web-user or
mobile interface provided by
C24 Communications
View communicator status
directly from your mobile phone
to support on-site or remote
troubleshooting
Compatible with Sur-Gard
System l-IP/II/III/IV/5 monitoring
station receivers
Includes UL listed power
supply, transformer and 7 Ah
rechargeable battery
UL 864 listed
CSFM listed
The 3G4010CF connects the alarm
control panel to the Cellular network
and reports alarm signals directly to
a monitoring station receiver
(Sur-Gard System l-lP/lVlll/IV/5). The
3G401 OCF uses the Cellular network
to ensure low-cost, high-speed and
reliable alarm communications and is
compatible with control panels that
communicate using the Contact ID or
SIA (300 baud) format.
The 3G4010CF is compliant
with the latest requirements for
Communications Methods as per
UL864 and NFPA72 2010 and
2013 Editions. It can be used in
Fire Monitoring applications as a
single communications technology,,
n which case any failure of the
communications path shall be
annunciated at the supervising station
within 5 minutes (NFPA72 2010) or,
1 hour (NFPA72 2013) of the failure,
or it can be used as part of a multiple
communications technologies (for
example in conjunction with a DACT).
When used as a back-up provision
shall be made to monitor the integrity
of each communication path and
failure of any communications
path shall be annunciated at the
supervising station and at the
protected premises within not more
than 24 hours of the failure.
How it Works
The 3G401OCF can be used as
either a Sole Communicator or as a
Backup Communicator. When being
used as a Sole Communicator the
3G4O1OCF will replace the phone
line connection on the panel and
as soon as it detects that an alarm
needs to be transmitted it will send
the alarm across the Cellular network
immediately. When being used as a
backup the communicator assesses
the connection to the PSTN phone
line, and only in the event of a phone
line failure will it send all alarm traffic
across the Cellular network to the
monitoring station.
In instances where the control panel
does not support Contact ID or
SIA (300 baud), the 3G401OCF has
inputs pre-set to transmit fire alarm,
fire supervisory or system trouble.
Alarm signals are transmitted directly
without the need of a clearinghouse
to the IP linecard of the monitoring
station receiver (Sur-Gard® System
I -I Pill/Ill/i V/5).
From Tyco Security Products
Activating & Initializing the Unit
Activating and initializing the 3G4010CF can be done using
the automated telephone activation system (VRU), mobile
interface or web-user interlace provided by
C24 Communications. No special tools are required.
Mobile Site for Easy Installation and
Comprehensive Maintenance
C24 Communications mobile site (m.connect24.com)
makes the installation a simple process and offers intuitive
trouble-shooting features, cutting down on time and cost
allocated to maintenance.
UL Listing
The 3G4010CF is UL listed under File 54019, Usting guide
UOXX, as a sole or backup communicator for Commercial Fire
monitoring installations. When used as a sole communicator
under NFPA72 2010 guidelines the 3G401OCF will send
its heartbeat once every 97 seconds ensuring that three
heartbeats will be received at the supervising station within
the 300 second window. When used as a sole communicator
under NFPA72 2013 guidelines the 3G40100F will send its
heartbeat once every 5 minutes to monitor connectivity with
the supervising station within the 1 hour window. When used
as a backup communicator the 3G401OCF will monitor the
other communication method (DACT) and send a daily test
transmission to the supervising station.
CSFM Listing
The 3G401OCF has been approved by the California State Are
Marshal (CSFM) pursuant to Section 13144.1 of the California
Health and Safety Code.
Ordering Information:
3G4O1OCF-USA .......... Universal Wireless Commercial
Are IJarrn Communicator
(U.S. ModeVSlM Card Included)
Rate Plan
Cost-effective rate plans have been negotiated and are
available through authorized master resellers. Contact your
monitoring station or visit www.connect24.com to find a
master reseller. When used as a sole communicator, the
3G401OCF requires use of the 4MB (NFPA72 2010) or
500kB (NFPA72 2013) rate plans to support the supervision
requirements.
Specifications
Dimensions ................................................ 11-1/2 x 10' x3'
(290 mm x 254 mm x 75 mm)
InputVoltage.............................................................120 VAC
Current Draw ............................................... 200 mA (standby)
400 mA (transmitting)
Operating Environment ................32° to 120° F (00 to 49° C)
Weight...........................................................12.8 lbs (5.8 kg)
Optional Acessories
Model Description
GS-1 5ANT 15 ft extension antenna (internal use)
GS-25ANT 25 ft extension antenna
(internal/external use)
GS-50ANT 50 ft extension antenna
(internal/external use)
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION ...
OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM
LISTING SERVICE
LISTING No. 7300-1273:0161 Page 1 of 1
CATEGORY: p7300— FIRE ALARM CONTROL UNIT ACCESSORIES/MISC. DEVICES
LISTEE: Digital Security Controls95 Bridgeland Ave, Toronto, Ontario M6A 1Y7 Canada
Contact: Dan Nita (905) 760-3000 Fax (905) 760-3020
Email: dnita@tycoint.com
DESIGN: Model 3G4010CF RF Communicator (GSM-GPRS/3G) signaling device. It is intended for
use as a standalone communication technology (standalone unit). It may also be used as a
backup communication technology in conjunction with a DACT. Refer to listee's data sheet
for additional detailed product description and operational considerations.
RATING: 120 V, 50/60 Hz, 0.3 A
INSTALLATION: In accordance with listee's printed installation instructions, applicable codes and ordinances
and in a manner acceptable to the authority having jurisdiction.
MARKING: Listee's name, model number, electrical rating, and UL label.
APPROVAL: Listed as communicator signaling device for use with a separately listed fire alarm control
unit. Refer to listee's Installation Instruction Manual for details.
06-03-15 gt
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed
the test results and/or other data but does not make an independent verification of any claims. This listing is not
an endorsement or recommendation of the item listed. This listing should not be used to verify correct
operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other
Date Issued: July 01, 2016 ListingExpires :June 30, 2017
Authorized By: DAVID CASTILLO, Program Coordinator
Fire Engineering Division
Remote Diagnostics
Panel Format Detection
SMS Command and Control
Phone number call direction
Easy enrollment with C24 Communications via VRU, web or mobile interface
NOTE: The 3G4010CF is designed to work with the Contact ID communication format as described in SIA DC-05 Standard or
the SIA communication format as described in SIA DC-03 Standard. Before completing the field installation of the alarm mon-
itoring system, please ensure communication with the supervising station is successful by sending several events and con-
firming that they have been received.
Technical Specifications
Ratings
Power Supply Ratings
Input Voltage: 120 V/60HzJ0.3A
Standby Voltage: 12V17AH
Standby Time: 24h (NSC) plus 5 minutes alarm
Low Battery Trouble
Indication Threshold: 11.5 VDC
Battery Deep Discharge
Protection (cut-off): 9.5VDC
Battery Type: sealed, rechargeable type, rated 12V/7Ah
(for 24hr standby time)
Battery charging voltage: 13.75 Vdc
Battery charge current 700mA (maximum)
NOTE: Battery must be replaced every 3-5 years.
Operating frequency - 2G
(GSM/GPRSIEDGE): 850/1900MHz
Operating frequency - 3G
(UMTSIHSPA): 850/1900MHz
Antenna gain: 2.0dBi
Environmental
Specifications
Operating temperature: 0°C49°C (32°F-i 20°F)
Humidity. 93%RH Maximum (non-condensing)
Mechanical Specifications
Endosure Type metal, red, hardwired transformer and high voltage connection box included
Endosure Dimensions: 290mm x 254mm x 75mm (11.5"x 1 0° x 3")
Weight 5.8Kg (12.8 Ibs) (including standby battery)
Simulated Telco Loop specifications (TIP/RING)
On-Hook Voltage: 12Vdc
Off-Hook Voltage
(Maximum): 22Vdc
Loop Current: 25mA
Loop Resistance: 600 Ohms
Standard Battery Capacity
The calculation for battery capacity is based on 200mA standby current for 24 hours plus a five minute alarm at 400mA or
600mA (if the 4 PGM outputs are also activated)
The requirements are as follows:
200mA x 24h = 4800mAh capadty for standby
400mA x5/60h 33.33mAh capacity for alarm condition
Total = 4833.33 mAh needed for 24h and five minutes alarm transmission. The supplied battery is W.
4
2co?O)I
SYSTEM RECORD OF COMPLETION
This form is to be completed by the system installation contractor at the time ofsystem acceptance and approvaL It shall be permitted to modify thisform as needed to provide a more complete and/or clear record
Insert NM in all unused lines.
Attach additional sheets, data, or calculations as necessary to provide a complete record.
Form Completion Date: Supplemental Pages Attached:
I. PROPERTY INFORMATION
Name of property;
Address: M
Description of property- .-
Name of property representative: (Vtttt 5 '
Address: S c 6 i- F
Phone: (,(4 4) Fax: E-mail: llc.1t A ' ptp
INSTALLATION, SERVICE, TESTING, AND MONITORING INFORMATION
Installation contractor:
Address: I 4'4O
Phone: Fax: E-mail: Service organ zatiorn L
Address: ç i01s4 /A %i t (
Phone: 11 —( I -5Qu Fax: E-mail: a kirv'-i IQq I Testing .organization:
Address:
Phone: Fax:
Effective date for test and inspection contract 1 1 c Ic
Monitoring organization: rt
Address:. %tP MY,o JO
Phone: fl I Fax: E-maiF Accountnumber , Phone line 1: Phoneline2: I Means of transmission I)SL. 45o1
Entity to to which alarms are retransmitte& f)L.4e.L ((..d. Phone:
DOCUMENTATION
On-site location of the required record documents and site-specific software:
DESCRIPTION OF SYSTEM OR SERVICE
This is a: 0 New system Modificafionto existing system Pemitnumber NFPA 72 edition: -
4.1 Control Unit
Manufacturer: Model number: )I 0f
4.2 Software and Firmware
Firmware revision number:
43 Alarm Verification N This system does not incorporate alarm verification. Number of devices subject to alarm verification: Alarm verification set for seconds
Copyright § 2012 National Fire Protection Assodation. This form may be copied for- indhtdu5l use other than for resale. It may not be copied for comroprrial sate or rsVibuton.
(p.1 of 2)
SYSTEM RECORD OF COMPLETION (continued)
S. SYSTEM POWER
5.1 Control Unit
5.1.1 Primary Power
Input voltage of control panel: U ( - Control panel amps: 6 t4)
Overcunent protection: Type: c + ()t€st Amps: 1
Branch circuit disconnecting means location: QML Number:
5.1.2 Secondary Power
Type of secondary power.
Location, if remote from .the plant:
Calculated capacity of secondary power to chive the system:
In standby mode (hours):.
5.2 Control Unit
This system does not have power extender panels
[j Power extender panels are listed on supplementary sheet A
In alarm mode (minutes):
b. CIRCUITS AND PATHWAYS
Pathway Type Dual Media Pathway Separate Pathway Class Survivability Level
Signaling Linc
Device Power
Initiating Device
Notification Appliance
Other (specify): -
REMOTE ANN
Location
INITIATING DEVICES
Type Quantity
Addressable or
Conventional Alarm or Supervisory Sensing Technology
Manual Pull Stations t
Smoke Detectors
Duct Smoke Detectors - WA fti/t
HeatDetectors
___NA _______
Gas Detectors M /\ - N A
Waterfiow Switches
_________
Tamper Switches
__
copyilqhte 2012 Naijonal Fire Proteclion Assodation. This form maybe onpied forindtedual use other than for resale. It may not be copied for commerdal sale or distribution.
(p. 2 of 2)
AHJ representative:
SYSTEM RECORD OF COMPLETION (con tlnued)
0 Mt%TIItATIfltJ
SYSTEM CONTROL FUNCTIONS
Type Quantity
Hold-Open Door Releasing Devices
HVAC Shutdown
Fire/Smoke Dampers
Door Unlocking
Elevator Recall
Elevator Shunt Trip
INTERCONNECTED SYSTEMS
This system does not have interconnected systems.
0 Interconnected systems are listed on supplementary sheet
CERTIFICATION AND APPROVALS
121 System Installation Contractor
This system as speied herein has been installed according to all NFPA standards cited herein.
Signed: Printed name: ()4 Date:
Organization: Title: z) L._ Phone:
122 System 0 eratlonal Test
This system as'fled herein has tested according to all NFPA standards cited herein.
Signed: Printed name: ('A4 Date:
Organization: tIvu- 0 Title: Phone:
12.3 Acceptance Test
Date and time of acceptance test: I I 3D? (•\
Installing contractor representative:
Testing contractor representative:
Property representative:
iot'? L1)s4ç
Copyright @2012 National Pim protection Association. This form may be copied for iridhadual use other than for resale. It may not be copied for commercial sale or distilbulion.
- (p.30f3)