HomeMy WebLinkAbout6860 AVENIDA ENCINAS; ; AS160214; PermitCity of Carlsbad
Sprinkler Permit
Permit No: AS160214
6860 AVEN IDA
Job Address:
ENCINAS
Permit Type: SPRINK
Parcel No: 2144501900
Lot #: 0
Reference No.:
PC #:
Status: ISSUED
Applied 7/19/2016
Approved: 8/5/2016
Issued: 8/5/2016
Inspector:
Project Title: NURSE CLINIC REMODEL T.I.: ADD/RELOCATE NEW FIRE
SPRINKLERS FOR TI IN EXISTING SPRINKLERED BLDG. THE
EXISTING FIRE SPRINKLER COVERAGE OUTSIDE THE AREA
OF WORK WILL REMAIN AND WILL NOT BE AFFECTED BY
THE SCOPE OF WORK.
Applicant:
SCHMIDT FIRE PROTECTION CO INC
4760 MURPHY CANYON RD
SAN DIEGO, CA 92123
858-279-6122
Owner:
KAISER FOUNDATION HEALTH PLAN
INC
393 E WALNUT ST
PASADENA CA
Fees ($) Add'I Fees ($) Total ($) Balance ($)
303 0 303 0
Bulletin 111 Rev. P
CJ C
ct Reflab Model C Recesse
d Automatic Sprinkler
The Most Compact Attractive
and Easily Installed Sprinkler
Ever Designed!
Features
11/;_," (38mm) Total adjustment provided by
adjustable inlet versions.
1/2" (13mm) Total adjustment provided by
economical standard inlet version.
Adjustable inlet version available with either
1" NPT male or female threads eliminating
costly reducing coupling.
Small diameter escutcheon.
Available in brass, chrome or white finish.
Multiple orifice sizes for design flexibility.
Listed by Underwriters Laboratories Inc. &
Underwriters' Laboratories of Canada. Ap-
proved by Factory Mutual Research Corp.
& Loss Prevention Council, NYC BS&A No.,
587-75-SA.
Product Description
Today's modern buildings demand that a sprinkler not
only provide the best fire protection but also achieve an
attractive appearance. Reliable's Model G Recessed
Sprinkler meets both criteria. It combines the fire fighting
capability of a proven sprinkler with the smallest practi-
cable recessing unit. Its small profile does not disrupt the
overhead aesthetics, and yet one vertical glance upward
gives a visual assurance of the finest in fire protection, an
automatic sprinkler system.
The Model G Recessed Sprinkler's threaded two-piece
construction makes initial field installation a very easy
task. It allows ceilings panels to be removed without
shutting down the fire protection thus facilitating main-
tenance of above ceiling services. The adjustable one
inch NPT inlet versions have one and one half inches of
adjustment which eliminates both the normally required
reducing coupling and the need to accurately cut drop
nipples. This sprinkler can be adjusted after the ceil-
ing is in place and even while the system is pressurized
eliminating the final corrections to pipe hangers or ceil-
ings that might otherwise be required.
The Reliable Model G Automatic Sprinkler is the heart
of the Recessed Sprinkler. This sprinkler utilizes the cen-
ter strut solder in compression principle of construction.
The fusible alloy, captured in the cylinder of a small sol-
der capsule by a stainless steel ball, acts as the trigger of
the sprinkler. When the fusible alloy melts, the sprinkler
operating parts spring free from the sprinkler clearing the
waterway and allowing the deflector to distribute the dis-
charging water.
ASi 60214
6860 AVENIDA ENCINAS
Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York 10523
Product Description and Installation
The Reliable Model G Recessed Sprinkler has been de-
signed with ease of installation in mind. A choice of three
inlets with up to one inch adjustment coupled with the ½"
(13mm) escutcheon adjustment enables most systems
to be installed using pro-cut drop nipples. The adjust-
ment can be accomplished after the ceiling installation
and while the system is pressurized thereby providing
sprinkler protection before construction is completed.
The Non-Adjustable inlet version (Figure 1) Consists
of the Reliable Model G Sprinkler with an attached cup
recessed in the ceiling. A ceiling hole of 2 14" (57mm)
diameter is recommended.
The Adjustable inlet version uses the same sprinkler as
the Non-Adjustable inlet version except the 1" of addi-
tional adjustment is provided by a telescoping sprinkler
inlet section that threads in or out of a stationary Coupling
Reducer (either 1 male or 1 'female) as shown in figures
2 or 3. The Sprinkler-Cup assembly comes attached to
the inlet Coupling Reducer and is retained from separa-
tion past its maximum adjustment length by a snap ring.
This combination is simply installed after the system drop
nipple, elbow or tee has been 'roughed in" to the dimen-
sions shown in figures 2 or 3. Wrenching means are pro-
vided by hex flats on the coupling reducer as depicted in
the figures-do not wrench on any other part of the sprin-
kler. After the ceiling tiles have been cut and installed in
place (a 2 1/4" {57mm}hole is recommended), the sprin-
kler can be adjusted using the RC-1 Concealed Wrench.
When using the wrench in this application, however, do
not over-torque beyond the adjustment stops.
Figure 4 shows a ½" NFl non-adjustable inlet sprin-
kler, with the attached sprinkler cup combination inserted
into the special Reliable Model RC-1 Installation Wrench.
This wrench must he used. The wrenching pads of the
sprinkler easily slip into the rectangular cut-outs of the
wrench as the outside diameter locates the threaded
cup. A ½" (13mm) drive ratchet can then be used for
installation and tightening.
Figure 5 shows the removal of the wrench. Care should
be taken during this procedure to avoid hitting the de-
flector with the wrench. The wrench should be lowered
until it clears the sprinkler. The installation completed
by threading the escutcheon on until it contacts the coil-
ing. To avoid leaving smudge marks on the ceiling, the
Reliable Model FEA Flush Sprinkler Escutcheon Wrench
should be used.
Note:
Use hex wrench on Coupling Reducer to tighten
Adjustable Sprinkler into fittings. Do not use RC-1
Wrench for this purpose.
Do not install the Model G Recessed Sprinkler in
ceilings which have positive pressure in the space
above.
Maintenance
The Model G Recessed Pendent Sprinklers should be
inspected and the sprinkler system maintained in accor-
dance with NFFA 20. Do not clean sprinklers with soap
and water, ammonia or any other cleaning fluid. Remove
any sprinkler that has been painted (other that factory
applied) or damaged in any way. A stock of spare sprin-
klers should be maintained to allow quick replacement
of damaged or operated sprinklers. Prior to installation,
sprinklers should be maintained in the original cartons
and packaging until used to minimize the potential for
damage to sprinklers that would cause improper opera-
tion or non-operation.
½' NPT Non—Adjustable Inlet
Figure 1
11,IFL_ lJ.)
"-ax-
N
-- j
- --------I '
8
1" NPT Male—Adjustable Inlet
Figure 2
V
f ,I
xx
'1 ''
1" NPT Female—Adjustable Inlet
Figure 3
11
Technical Data
Sprinkler Inlet Total
Adjustment
Nominal
Orifice
"K" Factor
Thread
Sprinkler Approval Identification Organizations U.S. Metric Number (SIN)
Non-Adjustable ½" (13mm) ½' (15mm 562 81.0 ½' NPT (R½) 1, 2. 3 4. 5. 7 R1015
Non-Adjustable ½" (13mm) Ar," (11mm) 4.24 61.0 ½" NPT (R½) 1,3,4 R1013
Non-Adjustable ½" (13mm) /" (10mm) 2,82 40.6 ½" NPT (R½) 1. 3, 4 131011
Non-Adjustable ½" (13mm) 17/12" (20mm) 7.96 114.7 ½" NFl (R½) 1.3 R1016
Adjustable 1½" (.38mm) ½"(5mm) 5.53 79.7 1" NPT Male or Female 1,2,3.4 191118
Adjustable 11/2' (38mm) 7A1" (1 1. mm) 4.24 61.0 1" NPT Male or Female 1, 3, 4 All 13
Adjustable 111/2" (38mm) 2/1"(10mm) 2.75 39.2 1" NPT Male or Female 1.3,4 R1117
Adjustable 1½" (38mm) 15mm 5.53 79.7 RI Male or Female 5 R1118
Note: Sprinkler escutcheon provides ½" (131nm) of the total adjustment. Adjustable inlets, when used, provide 1" (2511-11TI) of the total adjustment.
Temperature Ratings
Sprinkler Rating Maximum Ambient Classification Temperature
OF I °COF oc
Ordinary 135 57 100 38
Ordinary 165 74 100 I 38
Intermediate 212 100 150 66
Approval Organizations
Underwriters Laboratories Inc.
Factory Mutual Research Corp.
Light Hazard Occupancies - No limitations
Ordinary Hazard Occupancies - Groups 1 &
2, Wet Systems Only
Underwriters Laboratories of Canada
NYC BS & A No. 587-75-SA
Loss Prevention Council
XLH, CHI and OHll Occupancies Only
NYC MEA 258-93-F
EC Certificate: 1438-CPD-0054 (R1015)
Note: Unless otherwise indicated, Ordinary hazard ap-
provals are without limitations. 7/;/' (1 1mm) and /" (10mm)
orifice sprinklers are limited to light hazard occupancies.
Ordering Information
Specify:
Temperature Rating
Nominal Orifice
Sprinkler Finish
Escutcheon Finish
Sprinkler Type: Either Non-Adjustable Inlet (Fig. 1) 1"
male Adjustable Inlet (Fig. 2)1" Female Adjustable
Inlet (Fig. 3)
Finishes (1)
Standard Finishes
Sprinkler Escutcheon
Bronze Brass
Chrome Chrome
White Painted White Fainted
Special Application
Sprinkler Escutcheon
Bright Brass 2' Bright Brass
Black Plated Black Plated
Satin Satin
Polyester Coated Polyester Coaled
(1) Other color Finishes available upon request. Consult Factory for details.
' Only frame, deflector and cap are plated
Only frame and deflector are painted or coated. Operating parts
are chrome plated. UL Listed and MEA Approved only.
igure 4 Figure 5 F
3,
F]
Reliable...For Complete Protection
Reliable offers a wide selection of sprinkler components. Following are some of the many
precision-made Reliable products that guard life and property from fire around the clock.
Automatic sprinklers
Flush automatic sprinklers
Recessed automatic sprinklers
Concealed automatic sprinklers
Adjustable automatic sprinklers
Dry automatic sprinklers
Intermediate level sprinklers
Open sprinklers
Spray nozzles
Alarm valves
Retarding chambers
Dry pipe valves
Accelerators for dry pipe valves
Mechanical sprinkler alarms
Electrical sprinkler alarm switches
Water flow detectors
Deluge valves
Detector check valves
Check valves
Electrical system
Sprinkler emergency cabinets
Sprinkler wrenches
Sprinkler escutcheons and guards
Inspectors test connections
Sight drains
Ball drips and drum drips
Control valve seals
Air maintenance devices
Air compressors
Pressure gauges
Identification signs
Fire department connection
The equipment presented in this bulletin is to be installed in accordance with the latest published Standards of the National Fire Protection Association, Factory
Mutual Research Corporation, or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable.
Products manufactured and distributed by Reliable have been protecting life and property for over 90 years, and are installed arid serviced by the most highly
qualified and reputable sprinkler contractors located throughout the United States, Canada and foreign countries.
Manufactured by
Reliable Automatic Sprinkler Co, Inc. Recycled
ReliabILA (800) 431-1588 Sales Offices Paper
(800) 848-6051 Sales Fax
(914) 829-2042 Corporate Offices Revision lines indicate updated or new data.
www.reliablesprinkler.com Internet Address EG. Printed in U.S.A. 03115 P/N 9999970006