HomeMy WebLinkAbout6205 EL CAMINO REAL; ; AS140011; PermitCity of Carlsbad
Sprinkler Permit
Permit No: AS1400II
6205 EL CAM INO
Job Address:
REAL
Permit Type: SPRINK
Parcel No: 2131001600
Lot #: 0
Status: ISSUED
Applied 1/24/2014
Approved: 3/5/2014
Reference No.: Issued: 3/5/2014
PC #: Inspector:
Project Title SGCA TI-1ST FLOOR NEW OFFICE PARTITION & 2ND FL
MEZZANINE (9) SPRINKLER HEADS MODEL FIFR300
Applicant:
FIRE WATCH
437 EL CAJON BL
EL CAJON, CA
619-2993473
Owner:
MYJJLLC
C/O EMILY H M LIN
6205 EL CAM INO REAL
CARLSBAD CA
Fees ($) Add'l Fees ($) Total ($) Balance ($)
268 0 268 0
Bulletin 159
ble Model Fl FR - 300 CD
Quick Response Extended
Coverage Sprinklers
300 psi 120,7 bar) Rated
Model Fl FR - 300 QREC
300 psi (20,7 bar) Rated
Sprinkler Types
Extended Coverage Pendent (QREC)
Extended Coverage Horizontal Sidewall
(QREC-9)
Extended Coverage Recessed Pendent
(QREC)
Extended Coverage Recessed
Horizontal Sidewall (QREC-9) QREC Pendent Recessed
QREC Pendent
Product Description
Reliable Models F1FR-300 QREC and F1FR-300
QREC-9 pendent and horizontal sidewall sprinklers are
high pressure rated automatic sprinklers which can
handle a maximum service pressure of 300 psi (20,7
bar).
These Models are quick response sprinklers which
utilize a 3.0mm frangible glass bulb. These sprinklers
have demonstrated response times in laboratory tests
which are five times faster than standard response
sprinklers. This quick response enables Model
F1 FR-300 QREC and QREC-9 sprinklers to apply
water to a fire much faster than standard sprinklers of
the same temperature rating.
The glass bulb contains an accurately controlled
amount of special fluid hermetically sealed inside a
precisely manufactured glass capsule. This glass bulb is
specially constructed to provide fast thermal response.
Other sprinkler parts are made of brass, copper or
beryllium nickel.
At normal temperatures, the glass bulb contains fluid
in both the liquid and vapor phases. The vapor phase
can be seen as a small bubble. As heat is applied, the
liquid expands, forcing the bubble smaller and smaller as
the liquid pressure increases. Continued heating forces
the liquid to push out against the bulb, causing the glass
to shatter, operating the waterway and allowing the
deflector to distribute the discharging water.
The temperature rating of the sprinkler is identified
by the color of the glass bulb.
QREC-9 Horizontal Recessed QREC-9
Sidewall Horizontal Sidewall
Application
The most common applications for Model Fl FR-300
QREC and QREC-9 Sprinklers will be in fire protection
systems for high rise buildings where a quick response
rating is required and the pressure entering the sprinkler
system is in excess of 175 psi (12 bar). The Use of these
sprinklers will provide the opportunity to reduce or
eliminate the need for pressure reducing valves.
The Reliable Automatic Sprinkler Co, Inc. 525 North MacQuesten Parkway, Mount Vernon, New York 10552
OREC Pendent
Model Fl FR-300 Quick Response Extended Coverage Pendent Sprinkler
Deflector: QREC
Installation Wrench: Model D Sprinkler Wrench
Approval Type: Quick Response Extended Coverage - Light Hazard Occupancy
Installation Date:
Nominal e Thread "K" Factor Sprinkler Approval Temperature Sprinkler
Identification
Size- Size US Metric Length Organizations Rating Number (SIN)
Vi' ½" NPT 5.62 81.0 22' 1,2 135-F (57-C) R5945 (15mm) (R1/2) (56.1mm)
3/4"NPI 8.0 115.3
155°F(68°c)
17/3 l 2.4" 1,2 T 135°F(57°C) R5942 (20mm) (R3/4) (61mm)
Model Fl FR-300 Quick Response Extended Coverage Recessed Pendent Sprinkler
Deflector: OREC
Installation Wrench: Model RC1 Sprinkler Wrench
Approval Type: Quick Response Extended Coverage - Light Hazard Occupancy
Installation Data:
Fe oils M
00
Nominal "K" Factor Sprinkler
Office Thread Sprinkler Approval Temperature Identification
Size
Size US I Metric Length Organizations Rating Number (SIN)
Vi' ½" NFl 5 62 . I 81.0 2.2" 1,2 135°F(57°c) R5945 (15mm) (R1/2) (56mm) 155°F (68°C)
32, 3/4"NPT 17/ ,.4" 8.0 1115.3 2 1,2 135°F (57°C) R5942 (2C)mm) (2 (R3%) (61mm)
Coverage Area
Flow Rate Pressure Max. Coverage Area
Width x Length
K=8.O(1153) K=5.62(81.0) gpm Umin ftxft. bar
mxm psi I bar psi
26 98.4 10.6 0,7 I 21.6 I 1,5 16x16 4.9x4.9
33 I 124.9 17.0 I 1,2 I 34,7 I 2,4 18x18 5.5x5.5
40 I 151.5 25.0 I 1,7 I 51.0 I 3,5 , 20x2d 6.0x6.d
'"135°F only.
(')Refer to escutcheon data table for approvals and dimensions.
Model Fl FR-300 Quick Response Extended Coverage Horizontal Sidewall Sprinkler
Deflector: QREC-9
Installation Wrench: Model D Sprinkler Wrench
Approval Type: Quick Response Extended Coverage - Light Hazard Occupancy
Installation Data:
Nominal
I Orifice
Thread
I Size
"K" Factor Sprinkler!
Length
Approval
I Organizations
Temperature Rating
I Sprinkler I I Identification I
Number US Metric
17/333/e,NPT 80 1153 2.95" 1,2 135°F (57°C) R5962 I (20mm) (R (75mm) ' 155°F (68°C)
2.
QREC-9 Horizontal Sidewall
,Model,Fl FR-300 Quick Response Extended Coverage Recessed Horizontal Sidewall Sprinkler
Deflector: QREC-9
Installation Wrench: Model GFR1 Sprinkler Wrench
Approval Type: Quick Response Extended Coverage - Light Hazard Occupancy
Installation Data:
Nominal
Orifice
Thread
Size
"K" Factor I I Sprinkler
I Length
Approval 11
Organizations
Temperature
1 Rating°F
I Sprinkler I I identification
(SIN) US Metric
11/3211
(20mm)
31W'NPT8.0 (R34) 115.3 2.95"
I (75mm) I 1,2 135°F (57°C)
155°F (68°C) R5962
"'Refer to Escutcheon Data Table for approvals and dimensions.
Coverage Area
Rate Pressure Width
Coverage DeflectorMaximum DimeFlow x Length Mm.
il
gpm L/min psi bar ft. x ft. mxm
98.4 10.6
in.
26 0,7 16x16 4.9x4.9 12 29 109.8 13.1 0,9 16x16 4.9x4.9 4-12 102-305 29 109.8 13.1 0,9 16x18 4.9x5.5 4-12 102-305
32 121.1 16.0 1,1 16x20 4.9x6.0 4-12 102-305 36 136.3 20.2 1,4 16x22 4.9x6.7 4-12 102-305 39 1 147.6 23.8 1,6 1 16x24 4.9x7.3 4-12 102-305
PACE OP PITTING roT2
4 To 12
COILING DIMENSION
1/8 TURN SPRING COLLAR UNTIL TIGHT AGAINST I I
ROSS.
SPRINKLER WRENCH
__j
II5/I6
2 27/32 014.
L RECOMMENDED
.l:J___r
WALL HOLE I ______ 2) ______ 2 I/4 DIAME1ER E
159P002 I I ADJUSTMENT (2) 48FGO2
Installation
Quick response sprinklers are intended for
installation as specified in NFPA 13. Quick response
sprinklers and standard response sprinklers should
not be intermixed.
The Model F1FR-300 QREC and QREC-9 Recessed
Sprinklers are to be installed as illustrated. The Model Fl
or F2 escutcheons illustrated are the only recessed
escutcheons to be used with the these sprinklers. The
use of any other recessed escutcheon will void all
approvals and negate all warranties.
When installing Model Fl FR-300 QREC Pendent and
QREC-9 Horizontal Sidewall Sprinklers, use the Model 0
Sprinkler Wrench. When installing Model F1FR-300
QREC-9 Recessed Horizontal Sidewall Sprinklers, use
the Model OFR1 Sprinkler Wrench. Use the Model AOl
Wrench for installing F1FR-300 QREC Recessed
Pendent Sprinklers. Any other type of wrench may
damage these sprinklers.
Maintenance
Model Fl FR-300 Extended Coverage Sprinklers
should be inspected quarterly and the sprinkler
system maintained in accordance with NFPA 25. Do
not clean sprinklers with soap and water, ammonia or
any other cleaning fluids. Remove dust by using a
soft brush or gentle vacuuming. Remove any
sprinkler that has been painted (other than factory
applied) or damaged in any way. A stock of spare
sprinklers should be maintained to allow quick
replacement of damage or operated sprinklers. Prior
to installation, sprinklers should be maintained in the
original cartons and packaging until used to minimize
the potential for damage to sprinklers that would
cause improper operation or non-operation.
Approval Organizations
Underwriters Laboratories Inc.
UL Certified for Canada
ULI Listing Category
Sprinklers, Automatic & Open
Quick Response Sprinklers
Temperature Ratings
Classification
Sprinkler
Temperature
Maximum Ambient
Temp. Bulb
Color
OF °c °F °C
Ordinary 135 57 100 I 38 Orange
Ordinary 155 I 68 100 I 38 Red
Intermediate 175 I 79 150 I 66 Yellow
ULI Guide Number
VNIV
Sprinkler Types
Pendent (QREC)
Horizontal Sidewall (QREC-9)
Recessed Pendent (QREC)
Recessed Horizontal Sidewall (QREC-9)
3.
Finishes,"'
Standard Finishes
Sprinkler Escutcheon
Bronze Brass
Chrome Chrome
White Polyester Coated White Painted
Special Application Finishes
Sprinkler Escutcheon
Bright Brass Bright Brass
Black Plated Black Plated
Black Paint Black Paint
Off White Off White
Satin Chrome Satin Chrome
Other colors and finishes are available on special order.
Consult factory for details
Escutcheon Data
Sprinkler Type Escutcheon
Model Approvals Adjustment "A" Dimension
Face of Fitting to
Ceiling or Wall
Dimensions
Fl FR-300 OREC
Pend Fl 1 2 ~" (19mm) s/i' (19mm) /6" (5mm) to
15 /is (24mm)
F1FR-3000REC-9
HSW F2 1,2 31W, (19 3 /6" 1%"(35mm) (5mm) to
%"(l8mm)
Ordering Information
Specify:
Sprinkler Model
Sprinkler Type.
Orifice Size
Deflector Type
Temperature Rating
Sprinkler Finish
Escutcheon Type
Escutcheon Finish (where applicable)
Note: When Recessed sprinklers are ordered, the
sprinklers and escutcheons are packaged
separately.
The equipment presented in this bulletin is to be installed in accordance with the latest published Standards of the National Fire Protection Association, Factory Mutual
Research corporation, or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable.
Products manufactured and distributed by Reliable have been protecting life and property for over 80 years, and are installed and serviced by the most highly qualified
and reputable sprinkler contractors located throughout the United States, Canada and foreign countries.
Manufactured by
The Reliable Automatic Sprinkler Co., Inc.
800.431.1588 Sales Offices Reliable 800.848.6051 Sales Fax
914.668.3470 Corporate Offices
w.reliablesprinker.com Internet Address
®Rd paw
Revision lines indicate updated or new data.
E.G. Printed in USA 01/01 P/N 999990164