Project Title: SPEC SUITE #101 T.I. FIRE SPRINKLER PLAN CHECK &
INSPECTIONS
Applicant:
SULLY FIRE PROTECTION
1975 SPANISH OAK WAY
VISTA, CA
760-727-3444
Owner:
HURLEY THOMAS J
1015 CHESTNUT AVE #F2
CARLSBAD CA
Fees ($) Add'I Fees ($) Total ($) Balance ()
L 130 0 130 0
Flow Control I Tyco Fire
Products 1%
\(Dl,--~ D
P~o -
Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500
Series TY-FRB and 80 K-factor
Upright and Pendent Sprinklers
Quick Response, Standard Coverage
General
Description
ThSeries TY-FRB, 2.8, 5.6, and 8.0
K-factor, Upright and Pendent Sprin-
klers described in this data sheet are
quick response - standard coverage,
decorative 3 mm glass bulb type spray
sprinklers designed for use in light or
ordinary hazard, commercial occupan-
cies such as banks, hotels, shopping
malls, etc.
The recessed version of the Series
TY-FRB Pendent Sprinkler, where ap-
plicable, is intended for use in areas
with a finished ceiling. It uses either a
two-piece Style 10 (1/2 inch NPT) or
Style 40 (3/4 inch NPT) Recessed Es-
cutcheon with 1/2 inch (12,7 mm) of
recessed adjustment or up to 3/4 inch
(19,1 mm) of total adjustment from the
flush pendent position, or a two-piece
Style 20 (1/2 inch NPT) or Style 30(3/4
inch NPT) Recessed Escutcheon with
1/4 inch (6,4 mm) of recessed adjust-
ment or up to 1/2 inch (12,7 mm) of
total adjustment from the flush pen-
dent position. The adjustment provided
by the Recessed Escutcheon reduces
the accuracy to which the fixed pipe
drops to the sprinklers must be cut.
Corrosion resistant coatings, where
applicable, are utilized to extend the
life of copper alloy sprinklers beyond
that which would otherwise be ob-
tained when exposed to corrosive at-
mospheres. Although corrosion resis-
tant coated sprinklers have passed the
standard corrosion tests of the appli-
cable approval agencies, :he testing is
not representative of all possible cor-
rosive atmospheres. Consequently, it
is recommended that the end user be
consulted with respect to the suitability
r these corrosion resistant coatings
for any given corrosive environment.
The effects of ambient temperature,
concentration of chemicals, and
gas/chemical velocity, should be con-
sidered, as a minimum, along with the
corrosive nature of the chemical to
which the sprinklers will be exposed.
An intermediate level version of the
Series TY-FRB Pendent Sprinkler can
be obtained by utilizing the Series TY-
FRB Pendent Sprinkler in combination
with the Model S2 Shield.
WARNINGS
The Series TY-FRB Sprinklers de-
scribed herein must be installed and
maintained in compliance with this
document, as well as with the applica-
ble standards of the National Fire Pro-
tection Association, in addition to the
standards of any other authorities hav-
ing jurisdiction. Failure to do so may
impair the integrity of these devices.
The owner is responsible for maintain-
ing their fire protection system and de-
vices in proper operating condition.
The installing contractor or sprinkler
manufacturer should be contacted
relative to any questions.
Model/Sprinkler
Identification
Numbers
TY1131 - Upright 2.8K, 1/2"NPT
TY1231 - Pendent 2.81K, 1/2"NPT
TY3131 - Upright 5.61K, 1/2"NPT
TY4131 - Upright 8.0K 3/4"NPT
TY4231 - Pendent 8.0K, 3/4"NPT
Technical
Data
Approvals
UL and C-UL Listed.
FM and LPC Approved.
(Refer to Table A for complete approval
information including corrosion resis-
tant status.)
Maximum Working Pressure
175 psi (12,1 bar)
Discharge Coefficient
K = 2.8 GPM/psi112 (40,3 LPM/barl/2)
K = 5.6 GPM/psi1/2 (80,6 LPM/barl/2)
K = 8.0 GPM/psi1/2 (115,2 LPM/barl/2)
Temperature Ratings
Refer to Table A
Finishes
Sprinkler: Refer to Table A
Recessed Escutcheon: White Coated
or Chrome Plated. (Other colors are
available on request.)
Physical Characteristics
Frame .............Bronze
Button .........Brass/Copper
Sealing Assembly ..........
Beryllium Nickel w/Teflonj-
Bulb ..............Glass
Compression Screw .....Bronze
Deflector ...........Copper
Bushing (K=2.8) .......Bronze
.4—
ESCUTCHEON
PLATE SEATING
SURFACE
7/16" (11,1 mm)
NOMINAL
-MAKE-IN 1/2" **
NPT
2-3/16"
(55,6 mm) i
Page 2 of 8
1/2" **
NPT
ESCUTCHEON
PLATE SEATING
SURFACE
2-1/4"
(57,2 mm)
1-9/16"
(39,7 mm)
—Li—]" — -.-;-J.
7/16" (11,1 mm)
NOMINAL SSU*
MAKE-IN DEFLECTOR
it(55,6
WRENCH ' 3
DEFLECTOR CROSS
uJJ;1[e1:I SECTION
- Frame
2 - Button
3 - Gaskeled 4 - Bulb 6- Deflector * Temperature rating is indicated on deflector or adjacent to
Spring 5 - Compression 7- Bushing orifice seat on frame.
Plate Screw **Pipe thread connections per ISO 7/1 can be provided on
special request.
FIGURE 1
QUICK RESPONSE SERIES TV-FRB IJPRIGHT(TY1I31) AND PENDENT(TY1231) SPRINKLERS
2.8 K-FACTOR, 112 INCH NPT
STYLE 100r20
ESCUTCHEON
RECESSED SSU*
DEFLECTOR
tJTJ 7/16
I II "
(11.1 mm)
:NOMINAL
E- IN
FLATS
_MAK 2-3/16"
(55,6 mm)
1/2NPT** I
UPRIGHT CAOSS SECTION
SSP DEFLECTOR* 1—"- 2-7/8" (73,0 mm) DIA.
PENDENT RECESSED PENDENT
1 - Frame 3 - Gasketed 4- Bulb 6- Deflector Temperature, rating is indicated on deflector or adjacent to
2- Button Spring 5 - CompressIon orifice seat on frame.
Plate Screw **Pipe thread connections per ISO ill can be proved on
special request.
FIGURE 2
OWCK RESPONSE SERIES TY-FRB UPRIGHT (TY3 13 1) AND PENDENT(7-V3231) SPRINKLERS
5.6 K-FA CTOR, 1/2 INCH NPT
SSU*
DEFLECTOR
6*
1/2 5
(12,7 mm)
NOMINAL 4
MAKE-IN
2 2-1/4
(57,2 mm)
'
314NPT** I
UPRIGHT CROSS SECTION
Page ioi8
ESCUTCHEON 1/2 (12,7 mm) STYLE 30 or 40
PLATE SEATING ** NOMINAL RECESSED
SURFACE MAKE-IN ESCUTCHEON NPT
2-5/16
S(58,7 mm) _______
1-9/16
(39,7 mm) WRENCH
FLATS
SSP DEFLECTOR 2-7/8 (73,0 mm) DIA.
PENDENT RECESSED PENDENT
1 • Frame - 3- Gasketed 4 - Bulb 6 - Deflector * Temperature rating is indicated on deflector or adjacent to
2 - Button Spring 5 - Compression 7 - Ejection orifice seat on frame, Plate Screw Spring
**Pipe thread connections per ISO 7/1 can be provided on
special request.
FIGURE 3
QUICK RESPONSE SERIES TY-FRB UPRIGHT (TY4131) AND PENDENT(TY4231) SPRINKLERS
8.0 K-FACTOR, 3/4 INCH NPT
Operation
The glass Bulb contains a fluid which
expands when exposed to heat. When
the rated temperature is reached, the
fluid expands sufficiently to shatter the
glass Bulb, which then allows the
sprinkler to activate and water to flow.
Design
Criteria
The Series TY-FRB Pendent and Up-
right Sprinklers are intended for fire
protection systems designed in ac-
cordance with the standard installation
rules recognized by the applicable
Listing or Approval agency (e.g., UL
Listing is based on NFPA 13 require-.
ments). Only the Style 10, 20, 30, or 40
Recessed Escutcheon, as applicable,
is to be used for recessed pendent
installations.
Page 4 of 8
SPRINKLER FINISH (See Note 5)
K TYPE TEMP. BULB
LIQUID
NATURAL
BRASS
I CHROME
PLATED
IPOLYESTER
COATED
LEAD
COATED
2.8
1/2'
NPT
PENDENT
(TY1231)
and
UPRIGHT
(TYI131)
135F/57°C Orange
1, 2,3 N/A 155°F/68C Red
175F/79°C Yellc..
200°F/93°C Green
286F/141°C Blue
1/2
PENDENT
(TY3231)
and
UPRIGHT
(TY3131)
135F/57°C Orange
1, 2, 3, 4 1, 2,3 155°F/68°C Red
175FT79°C Yellow
200°F193°C Green
286°F/141°C blue
NPT RECESSED
PENDENT
(TY3231)
Figure 4
135F/57C Orange
1,2,4 N/A ______
175F/79°C Yellow
200FI93°C Green
RECESSED
PENDENT
(TY3231)*
Figure 5
135F/57C Orange
12,3,4 N/A 155°F/68°C Red
175°F179°C Yellow
200°F/93°C Green
8.0
3/4w
PENDENT
(TY4231)
and
UPRIGHT
(TY4131)
135°F/57°C .Orange.
1, 2, 3, 4
1,2 155°F/68°C Red
175F/79°C Yellow
200°F/93°C Green
286°F/141°C Blue
NPT RECESSED
PENDENT
(TY4231)
Figure 6
135Ff57°C Green
12,4 N/A 155°FI68C Orange
175F/79°C Red
200°F/93C Yellow
RECESSED
PENDENT
(TY4231)**
Figure 7
1351F15710 Orange
1, 2, 3, 4 N/A 155°F/68°C Red
175°F179°C Yellow
200°F/93°C Green
NOTES:
Listed by Underwriters Laboratories, Inc. (UL) as Quick Response Sprinklers.
Listed by Underwriters Laboratories, Inc. for use in Canada (C-UL) as Quick Response Sprinklers.
Approved by Factory Mutual Research Corporation (FM) as Quick Response Sprinklers.
Approved by the Loss Prevention Council (LPC) as Quick Response Sprinklers; however, the LPC does not rate the thermal sensitivity
of recessed sprinklers.
5. Where Polyester Coated and Lead Coated Sprinklers are noted to be UL and C-UL Listed, the sprinklers are UL and C-UL Listed as
Corrosion Resistant Sprinklers. Where Lead Coated Sprinklers are noted to be FM Approved, the sprinklers are FM Approved as a
Corrosion Resistant Sprinklers.
* Installed with Style 10 (1/2' NPT) or Style 40 (3/4' NPT) 3/4' Total Adjustment Recessed Escutcheon, as applicable.
** Installed with Style 20 (1/2' NPT) or Style 30 (3/4' NPT) 1/2' Total Adjustment Recessed Escutcheon, as applicable.
White or Any Color (Frame and Detector only).
TABLE A
LABORA TORY LISTINGS AND APPROVALS
Page 5 of 8
2-7/8' DIA.
5/8±1/4' (73,0 mm) I 3/4' (19.1 mm)
(15,9±6,4 mm) 2-1/4' DIA. 1/4' (6,4 mm)
FACE OF42mMOUNTING
1/8"
SPRINKLE PLATE
FITTING
(3,2mm)
MOUNTIN
SURFACESERIES
1-1/4" (31,8 mm) CLOSURE TYFRB 3/4'(19,1 mm)
FIGURE
SERIES TY-FRB RECESSED PENDENT
SPRINKLER ASSEMBLY WITH TWO-PIECE
3/4 INCH TOTAL ADJUSTMENT
STYLE 10 RECESSED ESCUTCHEON
5.6K-FACTOR, 1/2 INCH NP
- 2-7/8' 01k
(73,0 mm) 1/2±1/4' 1/2"(12.7mm)
[(127±64mm) 2-1/4" DIA. 1/4"(6,4 mm)
FACE OF
PLATE SPRINKLER
FITTING
L,57'2 mm) MOUNTING
- 1/8' I. ____ (3,2 mm)
/ 11 MOUNTING
SURFACE
CLOSURE SERIES 1-1/4'(31,8mr
TYFRB 1'(25,4 mm)
FIGURE 5
SERIES TY-FRB RECESSED PENDENT
SPRINKLER ASSEMBLY WITH TWO-PIECE
1/2 INCH TOTAL ADJUSTMENT
STYLE 20 RECESSED ESCUTCHEON
5.6K-FACTOR, 1/2 INCH NPT
2-7/8" DIA.
5/8±1/4' (73,0 mm) 3/4"(19,11 mm)
(15,9±6,4mm) - 2-1/4'01A. 1/4" (6,4 mm)
FACE OF
*R l
(57,2 mm) MOUNTING
1/8'
PLATE SPRINKLE
FITTING
(3,2mm)
MOUNTIN
SURFACE
CLOSURE SERIES 1-5/16 (33,3j_________ TYFRB 13/16" (20,6 mm)
- 2-7/8' DIA.
1/2±1/4' (73,0 mm) 1/2' (12,7 mm)
(12,7±6,4 mm) _ 2-1/4' DIA. 1/4"(6,4 mm)
I
FACE OF (57,2 mm) MOUNTING
SPRINKLER
1/8'
R PLATE
FITTING
(3,2 mm)
\ MOUNTING I
SURFACE
CLOSURE SERIES 1-5/16'(33,3 mm)
TVFRB 1-1/16' (27,0 mm)
FIGURES
SERIES TY-FRB RECESSED PENDENT
SPRINKLER ASSEMBLY WITH TWO-PIECE
3/4 INCH TOTAL ADJUSTMENT
STYLE 40 RECESSED ESCUTCHEON
8.0 K-FACTOR, 314 INCH NP
FIGURE 7
SERIES TY-FRB RECESSED PENDENT
SPRINKLER ASSEMBLY WITH TWO-PIECE
1/2 INCH TOTAL ADJUSTMENT
STYLE 30 RECESSED ESCUTCHEON
8.0K-FACTOR, 3/4 INCH NPT
Installation
The Series TY-FRB Sprinklers must be
installed in accordance with the follow-
ing instructions:
NOTES
Do not install any bulb type sprinkler if
the bulb is cracked or there is a loss of
liquid from the bulb. With the sprinkler
held horizontally, a small air bubble
should be present. The diameter of the
air bubble is approximately 1/16 inch
(1,6 mm) for the 1350F/570C to 3/32
inch (2,4 mm) for the 286°F/141°C
temperature ratings.
A leak tight 1/2 inch NPT sprinkler joint
should be obtained with a torque of 7
to 14 ft.lbs. (9,5 to 19,0 Nm). A maxi-
mum of 21 ft. lbs. (28,5 Nm) of torque
may be used to install sprinklers with
1/2 NPT connections. A leak tight 3/4
inch NPT sprinkler joint should be ob-
tained with atorque of 10 to 20 ft.lbs.
(13,4 to 26,8 Nm). A maximum of 30
ft.lbs. (40,7 Nm) of torque is to be used
to install sprinklers with 3/4 NPT con-
nections. Higher levels of torque may
distort the sprinkler inlet with conse-
quent leakage or impairment of the
sprinkler.
Do not attempt to make-up for insuffi-
cient adjustment in the escutcheon
plate by under- or over-tightening the
sprinkler. Readjust the position of the
sprinkler fitting to suit.
The Series TY-FRB Pendent and Up-
right Sprinklers must be installed in
accordance with the following instruc-
tions.
Step 1. Pendent sprinklers are to be
installed on the pendent position, and
upright sprinklers are to be installed in
the upright position.
Step 2. With pipe thread sealant ap-
plied to the pipe threads, hand tighten
the sprinkler into the sprinkler filling.
Step 3. Tighten the sprinkler into the
sprinkler fitting using only the W-Type
6 Sprinkler Wrench (Ref. Figure 8).
With reference to Figures 1, 2, and 3,
the W-Type 6 Sprinkler Wrench is to be
applied to the sprinkler wrench flats.
The Series TY-FRB Recessed Pen-
dent Sprinklers must be installed in
accordance with the following instruc-
tions.
Step A. After installing the Style 10.
20, 30, or 40 Mounting Plate, as appli-
cable, over the sprinkler threads and
with pipe thread sealant applied to the
pipe threads, hand tighten the sprin-
kler into the sprinkler fitting.
Step B. Tighten the sprinkler into the
sprinkler fitting using only the W-Type
7 Recessed Sprinkler Wrench (Ref.
Figure 9). With reference to Figure 2 or
3, the W-Type 7 Recessed Sprinkler
Wrench is to be applied to the sprinkler
wrench flats.
Step C. After the ceiling has been in-
stalled or the finish coat has been ap-
plied, slide on the Style 10, 20, 30, or
40 Closure over the Series TY-FRB
Sprinkler and push the Closure over
the Mounting Plate until its flange
comes in contact with the ceiling.
Care and
Maintenance
The Series TY-FRB Sprinklers must be
maintained and serviced in accord-
arice with the following instructions:
NOTES
Before closing a fire protection system
main control valve for maintenance
work on the fire protection system
which it controls, permission to shut
down the affected fire protection sys-
tem must be obtained from the proper
authorities and all personnel who may
be affected by this action must be no-
tified.
Absence of an escutcheon, which is
used to cover a clearance hole, may
delay the time to sprinkler operation in
a fire situation.
Sprinklers which are found to be leak-
ing or exhibiting visible signs of corro-
sion must be replaced.
Automatic sprinklers, must never be
shipped or stored where their tempera-
ture will exceed 100°F/380C and they
must never be painted, plated, coated
or otherwise altered after leaving the
factory. Modified sprinklers must be re-
placed. Sprinklers that have been ex-
posed to corrosive products of com-
bustion, but have not operated, should
be replaced if they cannot be com-
pletely cleaned by wiping the sprinkler
with a cloth or by brushing it with a soft
bristle brush.
Care must be exercised to avoid dam-
age to the sprinklers - before, during,
and after installation. Sprinklers dam-
aged by dropping, striking, wrench
twist/slippage, or the like, must be re-
placed. Also, replace any sprinkler that
has a cracked bulb or that has lost
liquid from its bulb. (Ref. Installation
Section).
Frequent visual inspections are rec-
ommended to be initially performed for
corrosion resistant coated sprinklers,
after the installation has been com-
pleted, to verify the integrity of the cor-
rosion resistant coating. Thereafter,
WRENCH RECESS
(END A' USED FOR
1/2' NPT MODELS)
WRENCH RECESS
(END 'B' USED FOR
3/4' NPT MODELS)
FIGURE 8
W-TYPE 6 SPRINKLER
WRENCH
WRENCH
RECESS
PUSH WRENCH
IN TO ENSURE
ENGAGEMENT
WITH SPRINKLER
WRENCHING AREA
FIGURE 9
W-TYPE 7 RECESSED
SPRINKLER WRENCH
annual inspections per NFPA 25
should suffice; however, instead of in-
specting from the floor level, a random
sampling of close-up visual inspec-
tions should be made, so as to better
determine the exact. sprinkler condi-
tion and the long term integrity of the
corrosion resistant coating, as it may
be affected by the corrosive conditions
present.
The owner is responsible for the in-
spection, testing, and maintenance of
their fire protection system and de-
vices in compliance with this docu-
ment, as well as with the applicable
standards of the National Fire Protec-
tion Association (e.g., NFPA 25), in
addition to the standards of any other
authorities having jurisdiction. The in-
stalling contractor or sprinkler manu-
facturer should be contacted relative
to any questions.
It is recommended that automatic
sprinkler systems be inspected,
tested, and maintained by a qualified
Inspection Service.
Page 7 of B
Limited
Warranty
Products manufactured by Tyco Fire
Products are warranted solely to the
original Buyer for ten (10) years
against defects in material and work-
manship when paid for and properly -
installed and maintained under normal
use and service. This warranty will ex-
pire ten (10) years from date of ship-
ment by Tyco Fire Products. No war-
ranty is given for products or
components manufactured by compa-
nies not affiliated by ownership with
Tyco Fire Products or for products and
components which have been subject
to misuse, improper installation, corro-
sion, or which have not been installed,
maintained, modified or repaired in ac-
cordance with applicable Standards of
the National Fire Protection Associa-
tion, and/or the standards of any other
Authorities Having Jurisdiction. Mate-
rials found by Tyco Fire Products to be
defective shall be either repaired or
replaced, at Tyco Fire Products' sole
option. Tyco Fire Products neither as-
sumes, nor authorizes any person to
assume for it, any other obligation in
connection with the sale of products or
parts of products. Tyco Fire Products
shall not be responsible for sprinkler
system design errors or inaccurate or
incomplete information supplied by
Buyer or Buyer's representatives.
IN NO EVENT SHALL TYCO FIRE
PRODUCTS BE LIABLE, IN CON-
TRACT, TORT, STRICT LIABILITY OR
UNDER ANY OTHER LEGAL THE-
ORY, FOR INCIDENTAL, INDIRECT,
SPECIAL OR CONSEQUENTIAL
DAMAGES, INCLUDING BUT NOT
LIMITED TO LABOR CHARGES, RE-
GARDLESS OF WHETHER TYCO
FIRE PRODUCTS WAS INFORMED
ABOUT THE POSSIBILITY OF SUCH
DAMAGES, AND IN NO EVENT
SHALL TYCO FIRE PRODUCTS' LI-
ABILITY EXCEED AN AMOUNT
EQUAL TO THE SALES PRICE.
THE FOREGOING WARRANTY IS
MADE IN LIEU OF ANY AND ALL
OTHER WA RRANTIES EXPRESS OR
IMPLIED. INCLUDING WARRANTIES
OF MERCHANTABILITY AND FIT-
NESS FOR A PARTICULAR PUR-
POSE.
Page 8 of 8
P/N 57 - XXX - X - XXX
I
MODEL/SIN I
1
1.
7
9
7
SPRINKL ER
NATURAL BRASS
WHITE POLYESTER
CHROME PLATED
LEAD COATED
I I _L_
135
155
175
200
286
TEMPERATURE
RATING
___________
135°F157°C
155°F/68°C
175°F/79°C
200°F/93C
286°F/141°C
330 2.8K UPRIGHT (1/2NPT) TY1131
331 2.8K PENDENT (1/2NPT) TY1231
370 5.6K UPRIGHT (1/2"NPT) 1Y3131
371 5.6K PENDENT (1/2NPT) TY3231
390 8.OK UPRIGHT (3/4NPT) 1Y4131
391 8.0K PENDENT (314"NPT) TY4231
TABLE B
PART NUMBER SELECTION
SERIES TV-FRB PENDENT AND UPRIGHT SPRINKLERS
4
Ordering Recessed Escutcheon:
Procedure Specify: Style (specify) Recessed Es-
finish), PIN .- cutcheon with (specify
(specify). When placing an order, indicate the full
product name. Refer to the Price List .1/2 (15 mm)
for complete listing of Part Numbers.
pr Plated ......... P/N 56-7Ol'-10 Contact your local distributor foc avail- 1/2',,.(15,!1rn)
' ability. /
$tvje1.6.
Color'
Sprinkler Assemblies with NPT Coated-i P/N 56-70174-010 1/2 (15 mm). - Thread Connections: Style 20
Specify: (Specify MddellSlN), Quick Chrome Plated .........PIN 56-705-9-010
Response, (specify K-factor), (specify 25
m)
tyle~ 20 temperature rating),- Serie TYFRB White Color (specify Pendent or Uprigti) Sprinkler, Coated ................ P/N 56-705-4-010 with (specify type of finish or coating), 3/4 (20 mm)
PN (specify from Table B). Style 30
Chrome Plated .........P/N 56-705-9-011 • 3/4' (20 mm)
Style 30
- White Color
Coated ...............P/N 56-705-4-011
3/4 (20 mm) • Style 40
Chrome Plated .........P/N 56-700-9-010
3/4 (20 mm)
Style 40
White Color
Coated ...............P/N 56-700-4-010
Sprinkler Wrench: -.
Specify: W-Type 6 Sprinkler Wrench,
P/N 56-000-6-387.
Specify: W-Type 7 Sprinkler Wrench,
- P/N 56-850-4-001.