HomeMy WebLinkAbout3239 CAMINO DE LOS COCHES; 100; FPC2019-0232; Permitäty of
PERMIT REPORT Carlsbad
Print Date: 05/11/2022 Permit No: FPC2019-0232
Job Address: 3239 CAMINO DE LOS COCHES, # 100, CARLSBAD, CA 92009-8966 Status: Closed - Finaled
Permit Type: FIRE-Construction Commercial Work Class: Fire Sprinklers
Parcel #: 2550313000 Track #: Applied: 10/04/2019
Valuation: $126,925.79 Lot #: Issued: 10/21/2019
Occupancy Group: Project #: Finaled Close Out: 11/14/2019
#of Dwelling Units: Plan #:
Bedrooms: Construction Type: Final Inspection:
Bathrooms: Orig. Plan Check #: INSPECTOR: Salcedo, Felix
Plan Check #:
Project Title:
Description: YOFIT -SPRINKLER TI (10 HEADS)
Applicant: FPContractor:
AMERICAN AUTOMATIC FIRE SUPPRESSION AMERICAN AUTOMATIC FIRE SUPPRESSION
INC INC
JAZZMIN DEEKEN 9925 PROSPECT AVE, #STE B
9925 PROSPECT AVE, U B SANTEE, CA 92071
SANTEE, CA 92071 (619) 562-3010
(619) 562-3010
FEE AMOUNT
FIRE NFPA 13 or 13R System 7 - 100 heads $553.00
Total Fees: $553.00 Total Payments To Date: $553.00 Balance Due: $0.00
Fire Department Page 1 of 1
1635 Faraday Avenue, Carlsbad CA 92008-7314 1 760-602-4665 1 760-602-8561 f I www.carlsbadca.gov
cci Worldwide i
Fire Protection Contacts www.tyco-fire.com tq
Products
Series TY-FRB, 56 K-factor
Upright, Pendent, and Recessed Pendent Sprinklers
Quick Response, Standard Coverage
General
Description
The TYCO Series TY-FRB, 5.6 K-factor,
Upright (TY313) and Pendent (TY323)
Sprinklers described in this data sheet
are quick response, standard coverage,
decorative 3 mm glass bulb-type spray
sprinklers designed for use in light or
ordinary hazard, commercial occupan-
cies such as banks, hotels, and shop-
ping malls.
The recessed version of the Series TY-
FRB Pendent Sprinkler, where applica-
ble, is intended for use in areas with a
finished ceiling. This recessed pendent
sprinkler uses one of the following:
A two-piece Style 15 Recessed
Escutcheon with recessed adjust-
ment up to 5/8 inch (15,9 mm) from
the flush pendent position.
A two-piece Style 20 Recessed
Escutcheon with recessed adjust-
ment up to 1/2 inch (12,7 mm) from
the flush pendent position.
The adjustment provided by the
Recessed Escutcheon reduces the
accuracy to which the fixed pipe drops
to the sprinklers must be cut.
Intermediate level versions of Series
TY-FRB Sprinklers are described in
Technical Data Sheet TFP357. Sprin-
kler guards and shields are described
in Technical Data Sheet TFP780.
IMPORTANT
Always refer to Technical Data
Sheet TFP700 for the "INSTALLER
WARNING" that provides cautions
with respect to handling and instal-
lation of sprinkler systems and com-
ponents. Improper handling and
installation can permanently dam-
age a sprinkler system or its compo-
nents and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
Page 1 of 4
NOTICE
The TYCO Series TY-FRB Sprinklers
described herein must be installed and
maintained in compliance with this doc-
ument, as well as with the applicable
standards of the National Fire Protec-
tion Association, in addition to the stan-
dards of any other authorities having
jurisdiction. Failure to do so may impair
the performance of these devices.
The owner is responsible for maintain-
ing their fire protection system and
devices in proper operating condition.
The installing contractor or sprinkler
manufacturer should be contacted with
any questions.
Sprinkler
Identification
Number (SIN)
TY313 .......Upright 5.6K, 1/2" NPT
TY323 ......Pendent 5.6K, 1/2" NPT
Technical
Data
Approvals
UL and C-UL Listed
FM, LPCB, and VdS Approved
CE Certified
Sprinklers with Polyester Finish are UL
and C-UL Listed as Corrosion-Resis-
tant Sprinklers.
Maximum Working Pressure
175 psi (12.1 bar)
250 psi (17.2 bar)*
*The maximum working pressure of 250 psi
(17,2 bar) only applies to the listing by Un-
derwriters Laboratories, Inc. (UL).
Discharge Coefficient
K=5.6 GPM/psi112 (80,6 LPM/bar1/2)
FEBRUARY 2014
Temperature Rating
135°F (57°C)
155°F (68°C)
175°F (79°C)
200°F (93°C)
286°F (141°C)
Finishes
Sprinkler: Refer to Table A
Recessed Escutcheon: White Coated,
Chrome Plated, or Brass Plated
Physical Characteristics
Frame ...................Bronze
Button..............Brass/Copper
Sealing Assembly.........Stainless
Steel w/TEFLON
Bulb ......................Glass
Compression Screw........Bronze
Deflector.................Bronze
TFPI72
TFPI72
Page 2 of 4
Components:
1 - Frame
2 - Button
3 - Sealing
Assembly
* Temperature rating is ** Pipe thread connections per ISO 7-1 4 - Bulb indicated on Deflector. can be provided on special request. 5 - Compression
Screw ESCUTCHEON PLATE 1/2 7/16 (11,1 mm)
6 - Deflector* DEFLECTOR * SEATING SURFACE NPT** NOMINAL MAKE-IN
STYLE 15or20
RECESSED
ESCUTCHEON
2'
(50,8 mm)
7/16"
(11,1 mm)
I NOMINAL
MAKE-IN
(50,8 mm)
1/2" NPT**
CROSS SECTION UPRIGHT
WRENCI-
FLATS
DEFLECTOR * f-.-- 2-7/8' (73,0 mm) DIA.
PENDENT RECESSED PENDENT
FIGURE 1
SERIES TY-FRB UPRIGHT (TY313) AND PENDENT (TY323) SPRINKLERS
5.6 K-FACTOR, 1/2 INCH NPT, QUICK RESPONSE
Operation
The glass bulb contains a fluid which
expands when exposed to heat. When
the rated temperature is reached, the
fluid expands sufficiently to shatter the
glass bulb, allowing the sprinkler to
activate and water to flow.
Design
Criteria
The TYCO Series TY-FRB, 5.6 K-factor,
Upright (TY313) and Pendent (TY323)
Sprinklers are intended for fire protec-
tion systems designed in accordance
with the standard installation rules rec-
ognized by the applicable Listing or
Approval agency (such as, UL Listing
is based on the requirements of NFPA
13, and FM Approval is based on the
requirements of FM's Loss Prevention
Data Sheets). Only the Style 15 or Style
20 Recessed Escutcheon is to be used
for recessed pendent installations.
Installation
The TYCO Series TY-FRB, 5.6 K-factor,
Upright (1Y313) and Pendent (TY323)
Sprinklers must be installed in accor-
dance with this section.
General Instructions
Do not install any bulb-type sprinkler if
the bulb is cracked or there is a loss
of liquid from the bulb. With the sprin-
kler held horizontally, a small air bub-
ble should be present. The diameter
of the air bubble is approximately 1/16
inch (1,6 mm) for the 135°F (57°C) and
3/32 inch (2,4 mm) for the 286°F (141°C)
temperature ratings.
A leak-tight 1/2 inch NPT sprinkler joint
should be obtained by applying a min-
imum to maximum torque of 7 to 14
ft.-lbs. (9,5 to 19,0 Nm). Higher levels
of torque can distort the sprinkler Inlet
with consequent leakage or impairment
of the sprinkler.
Do not attempt to compensate for
insufficient adjustment in the Escutch-
eon Plate by under- or over-tightening
the sprinkler. Re-adjust the position of
the sprinkler fitting to suit.
Upright and Pendent Sprinklers
The Series TY-FRB Upright and Pen-
dent Sprinklers must be installed
in accordance with the following
instructions.
Step 1. Install Pendent sprinklers in the
pendent position. Install upright sprin-
klers in the upright position.
Step 2. With pipe-thread sealant
applied to the pipe threads, hand-
tighten the sprinkler into the sprinkler
fitting.
/ WRENCH RECESS
/(USE ONLY
FIGURE 2
W- TYPE 6
SPRINKLER WRENCH
WRENCH
RECESS
PUSH WRENCH
IN TO ENSURE
ENGAGEMENT
WITH SPRINKLER
WRENCHING AREA
FIGURE 3
W- TYPE 7 RECESSED
SPRINKLER WRENCH
TFPI72
Page 3 of 4
Step 3. Tighten the sprinkler into the
sprinkler fitting using only the W-Type
6 Sprinkler Wrench (Figure 2). With ref-
erence to Figure 1, apply the W-Type 6
Sprinkler Wrench to the wrench flats.
Torque sprinklers 7 to 14 ft.-lbs. (9,5 to
19,0 Nm).
Recessed Pendent Sprinklers
The Series TY-FRB Recessed Pendent
Sprinklers must be installed in accor-
dance with the following instructions.
Step A. After installing the Style 15 or
Style 20 Mounting Plate over the sprin-
kler threads, and with pipe-thread
sealant applied to the pipe threads,
hand-tighten the sprinkler into the
sprinkler fitting.
Step B. Tighten the sprinkler into the
sprinkler fitting using only the W-Type
7 Recessed Sprinkler Wrench (Figure
3). With reference to Figure 1, apply the
W-Type 7 Recessed Sprinkler Wrench
to the sprinkler wrench flats. Torque
sprinklers 7 to 14 ft.-lbs. (9,5 to 19,0
Nm).
Step C. After ceiling installation and fin-
ishing, slide on the Style 15 or Style 20
Closure over the Series TY-FRB Sprin-
kler and push the Closure over the
Mounting Plate until its flange comes in
contact with the ceiling.
Care and
Maintenance
The TYCO Series TY-FRB, 5.6 K-factor,
Upright (TY313) and Pendent (TY323)
Sprinklers must be maintained and ser-
viced in accordance with this section.
Before closing a fire protection system
main control valve for maintenance
work on the fire protection system
that it controls, obtain permission to
shut down the affected fire protection
systems from the proper authorities
and notify all personnel who may be
affected by this action.
Absence of the outer piece of an
escutcheon, which is used to cover
a clearance hole, can delay sprinkler
operation in a fire situation.
The owner must assure that the sprin-
klers are not used for hanging any
objects and that the sprinklers are only
cleaned by means of gently dusting
with a feather duster; otherwise, non-
operation in the event of a fire or inad-
vertent operation may result.
Sprinklers which are found to be leak-
ing or exhibiting visible signs of corro-
sion must be replaced.
Automatic sprinklers must never be
painted, plated, coated, or other-
wise altered after leaving the factory.
Modified sprinklers must be replaced.
Sprinklers that have been exposed to
corrosive products of combustion, but
have not operated, should be replaced
if they cannot be completely cleaned
by wiping the sprinkler with a cloth or
by brushing it with a soft bristle brush.
Care must be exercised to avoid dam-
age to the sprinklers before, during, and
after installation. Sprinklers damaged
by dropping, striking, wrench twist/
slippage, or the like, must be replaced.
Also, replace any sprinkler that has a
cracked bulb or that has lost liquid from
its bulb. (Ref. Installation Section.)
The owner is responsible for the
inspection, testing, and maintenance of
their fire protection system and devices
in compliance with this document, as
well as with the applicable standards
of the National Fire Protection Associa-
tion (e.g., NFPA 25), in addition to the
standards of any other authorities hav-
ing jurisdiction. Contact the installing
contractor or sprinkler manufacturer
regarding any questions.
Automatic sprinkler systems are rec-
ommended to be inspected, tested,
and maintained by a qualified Inspec-
tion Service in accordance with local
requirements and/or national codes.
2-7/8 DIA.
(73,0 mm)
- 2-1/4 DIA.
FACE OF (57,2 mm)
SPRINKLER
FITTING 5/8 (15,9 mm)
FLUSH
3/8±5/16
(9,5±7,9 mm)
MOUNTING
I
SURFACE (3,2 mm)
/8" J
CLOSURE SERIES MOUNTING 1-3/8 (34,9 mm)
TY-FRB PLATE 3/4' (19,1 mm)
FIGURE 4
SERIES TY-FRB RECESSED PENDENT SPRINKLER ASSEMBLY (TY323)
WITH TWO PIECE 5/8 INCH TOTAL ADJUSTMENT STYLE 15
RECESSED ESCUTCHEON
2-7/8" DIA.
(73,0 mm)
FACE OF
SPRINKLER 2-1/4" DIA.
FITTING - (57,2 mm)
5/16±1/4"
\ I
1/2(12,7mm) (7,9±6,4 mm)
F
FLUSH
17,
SURFACE
CLOSURE
mm)
1/8" MOUNTING
CLOSURE SERIES MOUNTING 1-3/8" (34,9 mm)
TYFRB PLATE 7/8" (22,2 mm)
FIGURE 5
SERIES TY-FRB RECESSED PENDENT SPRINKLER ASSEMBLY (TY323)
WITH TWO PIECE 1/2 INCH TOTAL ADJUSTMENT STYLE 20
RECESSED ESCUTCHEON
TFPI72
Page 4 of 4
P/N*77_XXX_X_XXX
I SPRINKLER I TEMPERATURE I FINISH J- RATINGS
SIN 1 NATURAL BRASS
I 370 I 5.6K UPRIGHT (1/2NPT) TY313 3 PURE WHITE (RAL9010)** POLYESTER
371 5.6K PENDENT (1/2" NPT) TY323 POLYESTER SIGNAL WHITE (RAL9003)
Use suffix "I" for ISO 7-1 connection; 9 CHROME PLATED for example, 77-370-4-175-I - ** Eastern Hemisphere sales only
TABLE A
SERIES TY-FRB UPRIGHT AND PENDENT SPRINKLERS
PART NUMBER SELECTION
135 135°F (57°C)
155 155°F (68°C)
175 175°F(79°C)
200 200° F (93°C)
286 286°F (141°C)
Limited
Warranty
For warranty terms and conditions, visit
www.tyco-fire.com.
Ordering
Procedure
Contact your local distributor for avail-
ability. When placing an order, indicate
the full product name and Part Num-
ber (P/N).
Sprinkler Assemblies with NPT
Thread Connections
Specify: Series TY-FRB Upright or Pen-
dent (specify) Sprinkler, SIN (specify),
K=5.6, Quick Response, (specify) tem-
perature rating, (specify) finish, P/N
(specify, refer to Table A).
Recessed Escutcheon
Specify: Style 15 Recessed Escutcheon with (specify*) finish, P/N (specify*)
Specify: Style 20 Recessed Escutch- eon with (specify*) finish, P/N (specify*)
* Refer to Technical Data Sheet TFP770
Sprinkler Wrench
Specify: W-Type 6 Sprinkler Wrench,
P/N 56-000-6-387
Specify: W-Type 7 Sprinkler Wrench,
P/N 56-850-4-001
GLOBAL HEADQUARTERS 11400 Pennbrook Parkway, Lansdale, PA 194461 Telephone +1-215-362-0700
Copyright © 2014 Tyco Fire Products, LP. All rights reserved. tqco TEFLON is trademark of The DuPont Corporation. Fire Protection Products
Worldwide I tqC170 Contacts www.tyco-fire.com
Series TYFRB - 56 K-factor
Horizontal and Vertical Sidewall Sprinklers
Quick Response, Standard Coverage
General
Description
The Series TY-FRB, 5.6 K-factor, Hori-
zontal and Vertical Sidewall Sprinklers
described in this data sheet are quick
response -standard coverage, dec-
orative 3 mm glass bulb type spray
sprinklers designed for use in light and
ordinary hazard, commercial occu-
pancies such as banks, hotels, shop-
ping malls, etc. They are designed for
installation along a wall or the side of
a beam and just beneath a smooth
ceiling. Sidewall sprinklers are com-
monly used instead of pendent or
upright sprinklers due to aesthetics or
building construction considerations,
where piping across the ceiling is not
desirable.
The recessed version of the Series
TY-FRB Horizontal Sidewall Sprinkler
is intended for use in areas with a fin-
ished wall. It uses a two-piece Style
10 Recessed Escutcheon with 1/2 in.
(12,7 mm) of recessed adjustment or up
to 3/4 in. (19,1 mm) of total adjustment
from the flush sidewall position, or a
two-piece Style 20 Recessed Escutch-
eon with 1/4 in. (6,4 mm) of recessed
adjustment or up to 1/2 in. (12,7 mm)
of total adjustment from the flush side-
wall position. The adjustment provided
by the Recessed Escutcheon reduces
the accuracy to which the fixed pipe
nipples to the sprinklers must be cut.
Corrosion resistant coatings, where
applicable, are utilized to extend the life
IMPORTANT
Refer to Technical Data Sheet
TFP2300 for warnings pertaining to
regulatory and health information.
Always refer to Technical Data
Sheet TFP700 for the "INSTALLER
WARNING" that provides cautions
with respect to handling and instal-
lation of sprinkler systems and com-
ponents. Improper handling and
installation can permanently damage
a sprinkler system or its compo-
nents and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
Page 1 of 6
of copper alloy sprinklers beyond that
which would otherwise be obtained
when exposed to corrosive atmo-
spheres. Although corrosion resistant
coated sprinklers have passed the
standard corrosion tests of the appli-
cable approval agencies, the testing is
not representative of all possible cor-
rosive atmospheres. Consequently,
it is recommended that the end user
be consulted with respect to the suit-
ability of these coatings for any given
corrosive environment. The effects of
ambient temperature, concentration of
chemicals, and gas/chemical velocity,
should be considered, as a minimum,
along with the corrosive nature of the
chemical to which the sprinklers will be
exposed.
NOTICE
The Series TY-FRB Sprinklers
described herein must be installed
and maintained in compliance with
this document, as well as with the
applicable standards of the National
Fire Protection Association, in addition
to the standards of any other authori-
ties having jurisdiction. Failure to do so
may impair the performance of these
devices.
The owner is responsible for main-
taining their fire protection system
and devices in proper operating con-
dition. Contact the installing contrac-
tor or product manufacturer with any
questions.
Sprinkler
Identification
Numbers
TY3331................Horizontal
1Y3431 .................. Vertical
JULY 2018
Technical
Data
Approvals
UL and C-UL Listed
FM Approved
LPCB Approved
NYC Approved
(Refer to Table A for complete approval
information including corrosion resistant
status.)
Maximum Working Pressure
Refer to Table B
Discharge Coefficient
K=5.6 GPM/ps1112 (80,6 LPM/bar112)
Temperature Ratings
Refer to Table A
TFPI76
* Temperature rating is
indicated on Deflector
** Pipe thread connections I
per ISO 7-1 can be
provided on special 2-7/8 IDA.
request (73,0 mm)
TFPI76
Page 2 of 6
1 - Frame DEFLECT(
HAT 2 - Button
3 - Sealing
Assembly
4 - Bulb
5 - Compression
Screw
6 - Deflector*
DEFLECT( 1 - Frame HAT 2 - Button
3 - Sealing
Assembly
4 - Bulb
5 - Compression
Screw
6 - Deflector*
0
9/16 WRENCH 1/2** 9/16 WRENCH 1/2
(14,3 mm) FLATS NPT (14,3 mm) FLATS NPT
1 ,
\77 -
1-13/16" 7/16'
(46,0 mm) (11,1 mm)
CENTERLINE NOMINAL
OF SPRINKLER MAKE-IN
WATERWAY 1-1/2
(38,1 mm)
ESCUTCHEON
PLATE SEATING ______ 2-3/16"
SURFACE (556 m)
STYLE 1Oor2O
RECESSED
ESCUTCHEON
ALL FINISHES EXCEPT POLY-STAINLESS
Tj
1-13/16" 7/16"
(46,0 mm) (11,1 mm)
CENTERLINE NOMINAL
OF SPRINKLER MAKE-IN
WATERWAY 1-1/2'
(38,1 mm)
ESCUTCHEON
PLATE SEATING ______ 2-3/16'
SURFACE (55,6 mm)
POLY-STAINLESS FINISH ONLY
STYLE 10
RECESSED
ESCUTCHEON
*Temperature rating is
indicated on Deflector
FIGURE 1
5.6 K-FACTOR QUICK RESPONSE
SERIES TY-FRB HORIZONTAL SIDEWALL (TY3331) SPRINKLERS
Finishes
Sprinkler: Refer to Table C
Recessed Escutcheon: Signal or Pure
White, Jet Black, Grey Aluminum, Chrome
Plated, or Brass Plated
Physical Characteristics
Frame ............................Bronze
Button ......................Brass/Copper
Sealing Assembly. . Beryllium Nickel w/TEFLON
Bulb...............................Glass
Compression Screw.................Bronze
HSW Deflector .....................Bronze
VSW Deflector.....................Copper
Poly-Stainless
Physical Characteristics
Frame ............................Bronze
Button ................L316 Stainless Steel"
Bulb ...............................Glass
Compression Screw .....L316 Stainless Steel"
HSW Deflector ..............Copper/Bronze
Sealing Assembly. Gold Plated Beryllium Nickel
w/TEFLON
*Type L316 stainless steel (UNS 31603) per ASTM
A479/479M or BS EN 1008 WN1.4404.
Operation
The glass bulb contains a fluid which
expands when exposed to heat. When
the rated temperature is reached, the
fluid expands sufficiently to shatter the
glass bulb, allowing the sprinkler to
activate and water to flow.
Design
Criteria
The Series TY-FRB, 5.6 K-factor, Hor-
izontal and Vertical Sidewall Sprin-
klers are intended for fire protection
systems designed in accordance with
the standard installation rules rec-
ognized by the applicable Listing or
Approval agency (e.g., UL Listing is
based on the requirements of NFPA
13, and FM Approval is based on the
requirements of FM's Loss Prevention
Data Sheets). Only the Style 10 or 20
Recessed Escutcheon, as applicable,
is to be used for recessed horizontal
installations.
7/16'
(11,1 mm)
NOMINAL
MAKE-IN 1/2**
NPT
RENC
LATE
TFPI76
Page 3 of 6
Installation
The Series TY-FRB, 5.6 K-factor, Hori-
zontal and Vertical Sidewall Sprinklers
must be installed in accordance with
this section.
General Instructions
Do not install any bulb type sprinkler
if the bulb is cracked or there is a loss
of liquid from the bulb. With the sprin-
kler held horizontally, a small air bubble
should be present. The diameter of the
air bubble is approximately 1/16 in.
(1,6 mm) for the 135°F (57°C) to
3/32 in. (2,4 mm) for the 286°F (141°C)
temperature ratings.
A leak tight 1/2 in. NPT sprinkler joint
should be obtained with a torque of
7 to 14 lb-ft (9,5 to 19,0 N'm). Higher
levels of torque may distort the sprin-
kler and cause leakage or impairment
of the sprinkler.
Do not attempt to make-up for insuf-
ficient adjustment in the escutcheon
plate by under-or over-tightening the
sprinkler. Readjust the position of the
sprinkler fitting to suit.
Series TY-FRB Horizontal and
Vertical Sidewall Sprinkler
Installation
The Series TY-FRB Horizontal and
Vertical Sidewall Sprinklers must be
installed in accordance with the fol-
lowing instructions.
Step 1. Horizontal sidewall sprinklers
are to be installed in the horizontal
position with their centerline of water-
way perpendicular to the back wall and
parallel to the ceiling. The word "TOP"
on the Deflector is to face towards the
ceiling.
Vertical sidewall sprinklers are to be
installed in the pendent or upright
position with the arrow on the Deflec-
tor pointing away from the wall.
Step 2. With pipe thread sealant
applied to the pipe threads, hand
tighten the sprinkler into the sprinkler
fitting.
Step 3. Tighten the sprinkler into the
sprinkler fitting using only the W-Type
6 Sprinkler Wrench (Ref. Figure 5), With
reference to Figure 1 or 2, the W-Type
6 Sprinkler Wrench is to be applied to
the wrench flats.
* Temperature ** Pipe thread
rating is connections
indicated on per ISO 7-1 can
Deflector, be provided on
special request.
ESCUTCHEON
PLATE SEATING
SURFACE
F -
2-3/16
(55,6 mm)
1-1/2
(38,1 m
Series TY-FRB Recessed
Horizontal Sidewall Sprinkler
Installation
The Series TY-FRB Recessed Horizon-
tal Sidewall Sprinklers must be installed
in accordance with this section.
Step A. Recessed horizontal sidewall
sprinklers are to be installed in the hori-
zontal position with their centerline of
waterway perpendicular to the back
wall and parallel to the ceiling. The
word "TOP" on the Deflector is to face
towards the ceiling.
Step B. After installing the Style 10 or
20 Mounting Plate over the sprinkler
threads, hand tighten the sprinkler into
the sprinkler fitting.
Step C. Tighten the sprinkler into the
sprinkler fitting using only the W-Type
7 Recessed Sprinkler Wrench (Ref.
Figure 6). With reference to Figure
1, the W-Type 7 Recessed Sprinkler
Wrench is to be applied to the sprin-
kler wrench flats.
Step D. After the ceiling has been
installed or the finish coat has been
applied, slide on the Style 10 or 20
Closure over the Series TY-FRB Sprin-
kler and push the Closure over the
Mounting Plate until its flange comes
in contact with the ceiling.
1 - Frame 4 - Bulb 7 - Ejection
2 - Button 5 - Compression Spring
3 - Sealing Screw
Assembly 6 - Deflector*
ARROW MUST
POINT AWAY
FROM AND BE
J@
Care and
Maintenance
The Series TY-FRB, 5.6 K-factor, Hori-
zontal and Vertical Sidewall Sprinklers
must be maintained and serviced in
accordance with this section.
Before closing a fire protection system
main control valve for maintenance
work on the fire protection system that
it controls, permission to shut down the
affected fire protection system must be
obtained from the proper authorities
and all personnel who may be affected
by this action must be notified.
Absence of an escutcheon, which is
used to cover a clearance hole, may
delay the time to sprinkler operation in
a fire situation.
Sprinklers that are found to be leaking
or exhibiting visible signs of corrosion
must be replaced.
Automatic sprinklers must never be
painted, plated, coated or other-
wise altered after leaving the factory.
Modified sprinklers must be replaced.
Sprinklers that have been exposed to
corrosive products of combustion, but
have not operated, should be replaced
if they cannot be completely cleaned
by wiping the sprinkler with a cloth or
by brushing it with a soft bristle brush.
Care must be exercised to avoid
damage to the sprinklers before,
during, and after installation. Spriklers
PERPENDICULAR
TO THE BACK
WALL SURFACE
SHOWN SHOWN CROSS
PENDENT UPRIGHT SECTION
FIGURE 2
5.6 K-FACTOR QUICK RESPONSE
SERIES TY-FRB VERTICAL SIDEWALL (TY3431) SPRINKLERS
TFPI76
Page 4 of 6
- 5/8±1/4
(15,9±6,4 mm)
MOUNTING
FACE OF
SURFACE SPRINKLER
FITTING
CLOSURE
2-7/8" DIA.
SERIES
(73,0 mm)
TY-FRB 2-1/4" DIA.
(57,2 mm)
MOUNTING
-
PLATE
1/8" I (3,2 mm)
1-1/4(31,8mm) 3/4(19,1 mm)
3/4' (19,1 mm) 1/4" (6,4 mm)
FIGURE 3
SERIES TY-FRB RECESSED HORIZONTAL SIDEWALL SPRINKLER
WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT
STYLE 10 RECESSED ESCUTCHEON
-
- 1/2±1/8"
(12,7±3,2 mm)
MOUNTING FACE OF
SURFACE SPRINKLER
FITTING
CLOSURE
2-7/8 DIA.
SERIES
(73,0 mm)
TY-FRB 2-1/4" DIA.
MOUNTING
(57,2mm)
PLATE
1/8"
(3,2 mm)
1-1/4(31,8mm) 1/2(12,7mm)
1(25,4mm) 1/4(6,4mm)
FIGURE 4
SERIES TY-FRB RECESSED HORIZONTAL SIDEWALL SPRINKLER
WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 20 RECESSED ESCUTCHEON
/ WRENCH RECESS
/ (END 'A' USED FOR
60
1/2' NPT MODELS)
FIGURE 5
W-TYPE 6
SPRINKLER WRENCH
WRENCH
RECESS
)
I
I
PUSH WRENCH
IN TO ENSURE
ENGAGEMENT
WITH SPRINKLER
WRENCHING AREA
FIGURE 6
W-TYPE 7 RECESSED
SPRINKLER WRENCH
TFPI76
Page 5 of 6
SPRINKLER FINISH (See Note 11)
K TYPE TEMP. BULB
LIQUID
NATURAL
BRASS PLATED POLYESTERC POLY-
STAINLESSC
LEAD
COATED
135°F (57°C) Orange
155°F (68°C) Red HORIZ.
175-F (79'C) Yellow SIDEWALL 1,2, 3,4,9, 10 1,2,3,9 1,2 1,2,3,9
(TY3331) 200°F (93°C) Green
286°F (141°C) Blue
5.6 RECESSED 135°F (57°C) Orange
155°F (68°C) Red 1/2 in.
NPT
HORIZ.
SIDEWALL (TY3331)a
1, 2,4,9,10 1,2,9 1,2 N/A
175°F (79°C) Yellow
Figure 3 Green 200°F (93°C)
RECESSED 135°F (57°C) Orange
155°F (68°C) Red HORIZ.
SIDEWALL (TY3331)b
1, 2, 3, 4, 9 N/A N/A
175°F (79°C) Yellow
Figure 4 Green 200°F (93°C)
VERTICAL 135°F (57°C) Orange
155°F (68°C) Red 5.6
SIDEWALL
175°F (79°C) Yellow 1/2 in. Installed 5, 6, 7, 8, 9 N/A 5, 6, 7, 9
NPT Pendent
or 200°F(93°C) Green
Upright Blue 286°F (141°C)
NOTES:
Listed by underwriters Laboratories, Inc. (UL) as Quick Response Sprinklers for use in Light and Ordinary Hazard Occupancies at a 4 to 12 in. (100 to 300 mm) top of deflec-
tor to ceiling distance.
Listed by Underwriters Laboratories Inc. for use in Canada (C-UL) as Quick Response Sprinklers for use in Light and Ordinary Hazard Occupancies at a 4 to 12 in. (100 to
300 mm) top of deflector to ceiling distance.
Approved by Factory Mutual Research Corporation (FM) as Quick Response Sprinklers for use in Light Hazard Occupancies at a 4 to 12 in. (100 to 300 mm) top of deflector to
ceiling distance.
Approved by the Loss Prevention Certification Board (LPCB Ref. No. 007a/04) at a4 to in. (100 to 150 mm) top of deflector to ceiling distance. The LPC does not rate the
thermal sensitivity of horizontal sidewall sprinklers.
Listed by Underwriters Laboratories, Inc. as Quick Response Sprinklers for use in Light and Ordinary Hazard Occupancies.
Listed by Underwriters Laboratories for use in Canada (C-UL) as Quick Response Sprinklers for use in Light and Ordinary Hazard Occupancies.
Approved by Factory Mutual Research Corporation (FM) as Quick Response Sprinklers for use in Light Hazard Occupancies.
Approved by the Loss Prevention Certification Board (LPCB Ref. No. 094a/06 & 007a/04) as Quick Response Sprinklers.
Approved by the City of New York under MEA 354-01-E.
10.Approved by the Loss Prevention Certification Board )LPCB Ref. No. 094a/06) at a 4 to 6 in. (100 to 150 mm) top of deflector to ceiling distance. The LPC does not rate the
thermal sensitivity of horizontal sidewall sprinklers.
11. Where Polyester Coated and Lead Coated Sprinklers are noted to be UL and C-UL Listed, the sprinklers are UL and C-UL Listed as Corrosion Resistant Sprinklers.
Whore Lead Coated Sprinklers are noted lobe FM Approved, the sprinklers are FM Approved as Corrosion Resistant Sprinklers.
Installed with Style 10)1/2 in. NPT) 3/4 in.Total Adjustment Recessed Escutcheon.
Installed with Style 20(1/2 in. NPT) 1/2 in. Total Adjustment Recessed Escutcheon.
Frame and deflector only.
TABLE A
LABORATORY LISTINGS AND APPROVALS
damaged by dropping, striking, wrench
twist/slippage, or the like, must be
replaced. Also, replace any sprikter
that has a cracked bulb or that has lost
liquid from its bulb. (Ref. Installation
Section).
The owner must assure that the sprin-
klers are not used for hanging any
objects and that the sprinklers are only
cleaned by means of gently dusting
with a feather duster; otherwise, non-
operation in the event of a fire or inad-
vertent operation may result.
Frequent visual inspections are rec-
ommended to be initially performed
for corrosion resistant coated sprin-
klers, after the installation has been
completed, to verify the integrity
of the corrosion resistant coating.
Thereafter, annual inspections per
NFPA 25 should suffice; however,
instead of inspecting from the floor
level, a random sampling of close-up
visual inspections should be made, so
as to better determine the exact sprin-
kler condition and the long term integ-
rity of the corrosion resistant coating,
as it may be affected by the corrosive
conditions present.
The owner is responsible for the
inspection, testing, and maintenance of
their fire protection system and devices
in compliance with this document, as
well as with the applicable standards
of the National Fire Protection Asso-
ciation (e.g., NFPA 25), in addition to
the standards of any other authorities
having jurisdiction. Contact the install-
ing contractor or product manufacturer
with any questions.
It is recommended that automatic
sprinkler systems be inspected, tested,
and maintained by a qualified Inspec-
tion Service in accordance with local
requirements and/or national codes.
TFPI76
Page 6 of 6
SPRINKLER FINISH
K TYPE NATURAL BRASS CHROME PLATED POLYESTER LEAD COATED
250 PSI (17,2 BAR) HORIZONTAL SIDEWALL (1Y3331) or
175PS1 (12,1 BAR)
RECESSED HORIZ.
SIDEWALL (TY3331)
5.6
1/2 in. (SEE NOTE 1)
NPT ___________________________
VERTICAL SIDEWALL 175 PSI (12,1 BAR) (TY3431)
NOTES:
1. The maximum working pressure of 250 psi (17,2 bar) only applies to the Listing by Underwriters Laboratories, Inc. (UL); the Listing by Underwriters Laboratories, Inc. for use in
Canada (C-UL); and, the Approval by the City of New York.
TABLE B
MAXIMUM WORKING PRESSURE
P/N 57 — XXX — X — XXX
SIN SPRINKLER I I FT EMPERATURE I
FINISH I I RATINGS
378 I HORIZONTAL SIDEWALL I TY3331
375 I VERTICAL SIDEWALL I TY3431
1 NATURAL BRASS
- POLY-STAINLESS GREY
2 ALUMINUM (RAL9007)1
POLYESTER
PURE WHITE (RAL9010)2
POLYESTER
SIGNAL WHITE (RAL9003)
POLYESTER
- JET BLACK (RAL9005)3
POLYESTER
7 LEAD COATED
9 CHROME PLATED
135 135°F(57°C)
155 155-F (68-C)
175 175-F (79-C)
200 200°F (93°C)
286 286°F(141°C)
NOTES:
Available for TY3331 only.
Eastern Hemisphere sales only.
Available in 155°F (68CC) or 200°F (93CC
temperature rating only.
TABLE C
PART NUMBER SELECTION
SERIES TY-FRB HORIZONTAL AND VERTICAL SIDEWALL SPRINKLERS
Limited
Warranty
For warranty terms and conditions, visit
www.tyco-fire.com
Ordering
Procedure
Contact your local distributor for avail-
ability. When placing an order, indicate
the full product name and Part Number
(P/N).
Sprinkler Assemblies with NPT
Thread Connections:
Specify: Series TY-FRB (specify SIN),
(specify K-factor), (specify) Horizontal
Sidewall or Vertical Sidewall Sprinkler,
Standard Response, Standard
Coverage, (specify) temperature
rating, (specify) finish or coating, P/N
(specify from Table C)
Recessed Escutcheon
Specify: Style (10 or 20) Recessed
Escutcheon with (specify*) finish, P/N
(specify*)
Refer to Technical Data Sheet TFP770
Sprinkler Wrench
Specify: W-Type 6 Sprinkler Wrench,
P/N 56-000-6-387
Specify: W-Type 7 Sprinkler Wrench,
P/N 56-850-4-001
1400 Pennbrook Parkway, Lansdale, PA 19446 Telephone +1-215-362-0700
C 2018 Johnson Controls. All rights reserved. All specifications and other Information shown Were current ansi document revision data and are subject to change Without notice. Johnson
NATIONAL FIRE PROTECTION ASSOCIATION and NFPA are resist e,ed trademarks at NaSvr,cl Fire Prvlevtivn Association: Controls
TEFLON is n registered IrodemaAc olOuPanI
Worldwide tqciclo Contacts www.tyco-fire.com
Series EC-11 and EC-14 Sprinklers,
11.2 K and 140 K Upright and Pendent
Extended Coverage Light and Ordinary Hazard
General
Description
TYCO Series EC-11 and EC-14
Extended Coverage Upright and
Pendent Sprinklers are decorative
glass-bulb sprinklers designed for use
in light or ordinary hazard occupancies.
They are intended for use in automatic
sprinkler systems designed in accor-
dance with standard installation rules,
such as NFPA 13, for a maximum cov-
erage area of 400 ft2 (37,2 m2) as com-
pared to the maximum coverage area
of 130 ft2 (12,1 m2) for standard cover-
age sprinklers used in ordinary hazard
occupancies, Series EC-11 and EC-14
Extended Coverage Sprinklers feature
a UL and C-UL Listing that permits their
use with unobstructed or non-combus-
tible obstructed ceiling construction as
defined and permitted by NFPA 13, as
well as a specific application listing for
use under concrete tees.
Series EC-11 and EC-14 Extended Cov-
erage Sprinklers have been fire tested
to compare their performance to that
of standard coverage spray sprinklers.
These tests have shown that the pro-
tection provided is equal to or more
effective than standard coverage spray
sprinklers.
Corrosion-resistant coatings, where
applicable, help extend the life of
copper alloy sprinklers beyond that
which occurs when exposed to
corrosive atmospheres. Although
corrosion-resistant coated sprinklers
IMPORTANT
Refer to Technical Data Sheet
TFP2300 for warnings pertaining to
regulatory and health information.
Always refer to Technical Data
Sheet TFP700 for the "INSTALLER
WARNING" that provides cautions
with respect to handling and instal-
lation of sprinkler systems and com-
ponents. Improper handling and
installation can permanently damage
a sprinkler system or its compo-
nents and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
Page 1 of 8
passed standard corrosion tests of
the applicable approval agencies, this
testing is not representative of all pos-
sible corrosive atmospheres. Conse-
quently, it is recommended that the end
user be consulted with respect to the
suitability of these corrosion-resistant
coatings for any given corrosive envi-
ronment. The effects of ambient tem-
perature, concentration of chemicals,
and gas/chemical velocity should be
considered, along with the corrosive
nature of the chemical to which the
sprinklers will be exposed.
LL.1tL.I
Series EC-11 and EC-14 Extended Cov-
erage Sprinklers described herein must
be installed and maintained in compli-
ance with this document, as well as
with the applicable standards of the
NFPA, in addition to the standards of
any other authorities having jurisdiction.
Failure to do so may impair the perfor-
mance of these devices.
The owner is responsible for main-
taining their fire protection system
and devices in proper operating con-
dition. Contact the installing contrac-
tor or product manufacturer with any
questions.
Sprinkler
Identification
Numbers
TY5137 ............Upright, 11.2K
TY5237 ............ Pendent, 11.2K
1Y6137 ............Upright, 14.0K
TY6237...........Pendent, 14.0K
TY5137 is re-designation for C5137, G1894. and S2510
TY5237 is re-designation for C5237, G1893, and S2511
TY6137 is a re-designation for C6137, G1896, and S2610
TY6237 is a re-designation for C6237, G1895, and S2611
OCTOBER 2018
Technical
Data
Approvals
TYCO Series EC-11 and EC-14
Extended Coverage Upright and
Pendent Sprinklers are UL and C-UL
Listed. Refer to Table A for complete
sprinkler approval information including
corrosion-resistant status. The approv-
als apply to the service conditions indi-
cated in the Design Criteria section.
Series EC-11 and EC-14 Extended Cov-
erage Sprinklers are FM Approved.
Refer to Table A for complete sprinkler
approval information including corro-
sion-resistant status. The approvals
apply to the service conditions indi-
cated in the Design Criteria section.
TFP22O
2-7/16"
(61,9 mm)
UPRIGHT &
PENDENT
I-
1/2"(12,7mm) J NOMINAL MAKE-IN
UPRIGHT
TFP22O
Page 2 of 8
WRENCH
FLAT
3/4" ESCUTCHEON PLATE NPT** SEATING SURFACE
16"
1 6*
nm)
- 5
CROSS
PENDENT SECTION
Components:
1 - Frame
2 - Button
3 - Sealing Assembly
4 - Bulb
5 - Compression Screw
6 - Deflector
* Temperature rating is
indicated on Deflector.
** Pipe thread connections per
ISO 7-1 can be provided on
special request.
FIGURE 1
SERIES EC-11 AND EC-14 EXTENDED COVERAGE SPRINKLERS
11.2 K-FACTOR UPRIGHT (TY5137) AND PENDENT (TY5237)
14.0 K-FACTOR UPRIGHT (TY6137) AND PENDENT (TY6237)
ASSEMBLY
The Style 60 Two-Piece Flush Escutch-
eon (Figure 4) is UL Listed for use with
the Series EC-11 and EC-14 Pendent
Sprinklers.
Maximum Working Pressure
175 psi (12,1 bar)
Pipe Thread Connection
3/4 in. NPT
Discharge Coefficients
K = 11.2 GPM/p5i½ (161,3 LPM/bar"")
K = 14.0 GPM/p5i½ (201,6 LPM/bar½)
Temperature Ratings
Refer to Table A
Finish
Sprinkler:
Refer to Table A
Recessed or Flush Escutcheon:
White-Coated, Chrome-Plated, and
Brass-Plated
Physical Characteristics
Frame ............................Bronze
Button............................Bronze
Sealing Assembly . Beryllium Nickel w/TEFLON
Bulb ........................Glass (3 mm)
Compression Screw ................Bronze
Deflector ...........................Brass
Operation
The glass bulb contains a fluid that
expands when exposed to heat. When
the rated temperature is reached, the
fluid expands sufficiently to shatter
the glass bulb, which- then allows the
sprinkler to activate and flow water.
Design
Criteria
TYCO Series EC-11 and EC-14
Extended Coverage Upright and
Pendent Sprinklers must only be
installed in accordance with the appli-
cable UL and C-UL Listing or FM
Approval requirements as indicated
below. Only Style 30 or 40 Recessed
Escutcheons are to be used for
recessed installation, as applicable.
Refer to Tables A, B, and C, for more
information.
UL and C-UL
Listing Requirements
Series EC-11 and EC-14 Extended
Coverage Sprinklers may be used
for the coverage areas shown in
Table D, based on maintaining the
minimum specified flow rate as a
function of coverage area and haz-
ard group for all sprinklers in the
design area.
Series EC-11 and EC-14 Extended
Coverage Sprinklers are permitted
to be used with unobstructed or
non-combustible obstructed ceil-
ing construction as defined and
permitted by NFPA 13; for example:
Unobstructed, combustible or
noncombustible, ceiling con-
struction with a deflector to
ceiling/roof deck distance of
1 t 12 in. (25 to 300 mm).
Obstructed, non-combusti-
ble, ceiling construction with a
deflector location below struc-
tural members of 1 to 6 in.
(25 to 150 mm) and a maximum
deflector to ceiling/roof deck dis-
tance of 22 in. (550 mm).
Series EC-11 and EC-14 Extended
Coverage Sprinklers, specifically
tested and listed for non-combus-
tible obstructed construction, are
permitted to be used within truss-
es or bar joists having non-com-
bustible web members greater
than 1 in. (25.4 mm) when apply-
ing the 4 times obstruction crite-
ria rule defined under "Obstruc-
tions to Sprinkler Discharge Pattern
Development".
To prevent cold soldering, the
minimum allowable spacing be-
tween Series EC-11 and EC-14 Ex-
tended Coverage Sprinklers is 8 ft
(2,4 m) for upright sprinklers and 9 ft
(2,7 m) for pendent sprinklers.
Series EC-ii and EC-14 Extended
Coverage Sprinklers are to be in-
stalled in accordance with all oth-
er requirements of NFPA 13 for
extended coverage upright and
pendent sprinklers; For exam-
ple, obstructions to sprinkler dis-
charge, obstructions to sprinkler
pattern development, obstructions
to prevent sprinkler discharge from
reaching hazard and clearance to
storage.
TFP22O
Page 3 of 8
Hazard Type Temperature Bulb
Liquid
Sprinkler Finish (See Note 5)
Natu ral
Brass
I Chrome
Plated
I Polyester* Lead
Coated
135°F (57°C) Orange
Upright
K=11.2 (TY5137) 1, 2, 3, 4 155°F (68°C) Red
175°F (79°C) Light Pendent Yellow
200°F (93°C) Green 1, 2, 4 1, 2,4 Table B describes
UL and C-UL
K11.2 (TY5237)
K=14.0 (1Y6237)
286°F (141°C) Blue
Recessed Pendent
K=11.2 (TY5237)
K=14.0 (TY6237)
135°F (57°C) Orange 1, 2, 3,4
N/A
Sensitivity Rating
Table C describes
FM
Sensitivity Rating
155°F (68°C) Red
175°F (79°C) Yellow
With Style 30
Escutcheon 1, 2, 4 200°F (93°C) Green
286°F (141°C) Blue
Ordinary
Table B describes
Upright
K11.2 (TY5137)
K14.0 (TY6137)
Pendent
K=11.2 (TY5237)
135°F (57°C) Orange
1, 2, 3, 4
Red
1, 2, 3, 4
155°F (68°C)
175°F (79°C) Yellow
1, 2, 4 200°F (93°C) Green
UL and CUL
Sensitivity Rating
K=14.0 (TY6237) Blue 286°F (141°C)
Recessed Pendent 135°F (57°C) Orange Table C describes
155°F (68°C) Red FM
Sensitivity Rating K=11.2 (TY5237)
K=14.0 (TY6237)
With Style 30 or 40
1, 2, 4 N/A
Di75°F (79°C) Yellow
Escutcheon 200°F (93°C) Green
NOTES
Listed by Underwriters Laboratories, Inc. (UL)
Listed by Underwriters Laboratories, Inc., for use in Canada (C-UL)
Approved by Factory Mutual Research Corporation (FM)
Approved by the City of New York under MEA 177-03-E
Where Polyester Coated or Lead Coated Sprinklers are noted to be UL and C-UL Listed, the sprinklers are UL and C-UL Listed as Corrosion Resistant Sprinklers
N/A = Not Available
Frame and Deflector only
Pendent only
TABLE A
LABORATORY LISTINGS AND APPROVALS
Light Hazard Ordinary Hazard Area Style ftxft 135°F 155°F 175°F 200°F 286°F 135°F 155°F 175°F 200°F 286°F
(57°C) (68°C) (79°C) (93°C) (141°C) (57°C) (68°C) (79°C) (93°C) (141°C)
Upright or Pendent - - - - - OR OR OR OR OR
14 x 14 Style 30 Recessed - - - - - OR OR OR OR OR
Style 40 Recessed - - - - - OR OR OR OR OR
Upright or Pendent OR* QR* OR* OR* QR* SR SR SR SR SR
16 x 16 Style 30 Recessed QR* QR* QR* OR* OR* SR SR SR SR SR
Style 40 Recessed N/A N/A N/A N/A N/A SR SR SR SR SR
Upright or Pendent QR* QR* OR* OR* OR* SR SR SR SR SR
18 x 18 Style 30 Recessed QR* OR* OR* OR* OR* SR SR SR SR SR
Style 40 Recessed N/A N/A N/A N/A N/A SR SR SR SR SR
Upright or Pendent QR* QR* OR' SR* SR* SR SR SR SR SR
20 x 20 Style 30 Recessed QR* QR* QR' SR* SR* SR SR SR SR SR
Style 40 Recessed N/A N/A N/A N/A N/A SR SR SR SR SR
NOTES
OR = Quick Response
SR = Standard Response
N/A =Not Applicable
Does not apply to Upright K=14.0
TABLE B
SENSITIVITY RATING FOR UL AND C-UL LISTING OF SERIES EC-11 OR EC-14 SPRINKLERS
(REFER TO TABLE D FOR PERMITTED K-FACTOR/AREA COMBINATIONS)
TFP22O
Page 4 of 8
HC-1
Linear Spacing Area Spacing
ft ft Ceiling Height
ft Ceiling Type K-factor Style Response
Min Max Min Max
Noncombustible Unobstructed, 11.2 EC Pendent or 10 20 100 400 Up to 30 Noncombustible Obstructed, or 14.0 EC Upright Combustible Unobstructed
Noncombustible Unobstructed, 11 2 EC . Pendent
10 20 100 400 Up to 30 Noncombustible Obstructed, or 14.0 EC Recessed
Combustible Unobstructed Style 30
Quick 10 20 100 400 Up to 30 Combustible Obstructed 11.2 EC
EC
Pendentor
14.0 Upright
11 2 EC . Pendent
10 20 100 400 Up to 30 Combustible Obstructed 14.0 EC Recessed
Style 30
10 20 100 400 Over 30 and
upt045 Noncombustible Unobstructed 11.2 EC
14.0 EC Upright
HC-2
Linear Spacing Area Spacing
ft ft Ceiling Height
ft Ceiling Type K-factor Style Response
Min Max Min Max
10 20 100 400 Up to 30
Noncombustible Unobstructed,
11.2 EC Upright
10 20 100 400 Upto30 14.0 EC Pendent or
Upright
Combustible Unobstructed Quick
10 16 100 256 Over 30 and 11.2 EC 14.0 Upright upt045 EC
HC-3
Linear Spacing Area Spacing
ft ft Ceiling Height
ft Ceiling Type K-Factor Style Response
Min Max Min Max
10 16 100 256 Up to 30 11.2 EC Upright
10 20 100 400 Upto30 14.0 EC Pendent or Upright
______ Noncombustible Unobstructed,
Combustible Unobstructed Quick
10 16 100 256 Over 30 and
upt045
11.2 EC,
14.0 EC Upright
NOTES
The design for K 11.2 SC (K 160 EC) sprinklers should not include fewer than six sprinklers or have a design pressure of less than 12 psi (0,8 bar); similarly the design for K 14.0
EC (K 200 EC)sprinklers should not include fewer than four sprinklers or have a design pressure of less than 18 psi (1,2 bar).
For flow criteria, refer to FM Loss Prevention Data Sheet 3-26.
Refer to FM Loss Prevention Data Sheet 2-0 for permitted K-Factor/Area Combinations.
TABLE C
SENSITIVITY RATING FOR FM APPROVAL OF SERIES EC-11 OR EC-14 SPRINKLERS
UL and C-UL Specific Application
Listing Requirements for
Installation under Concrete Tees
Series EC-11 and EC-14 Extended Cov-
erage Upright and Pendent Sprinklers
(TY5137, TY5237, TY6137 and TY6237)
have a UL and C-UL Specific Applica-
tion Listing for use under concrete tees
when installed as follows:
1. Stems of the concrete tee con-
struction must be spaced at less
than 7.5 ft (2,3 m) on center but
more than 3 ft (0,9 m) on center. The
depth of the concrete tees must not
exceed 30 in. (762 mm). The maxi-
mum permitted concrete tee length
is 32 ft (9,8 m). However, where the
concrete tee length exceeds 32 ft
(9,8 m), non-combustible baffles,
equal in height to the depth of the
tees, can be installed so that the
space between the tees does not
exceed 32 ft (9,8 m) in length.
2. The sprinkler deflectors are to be
located in a horizontal plane at or
above 1 in. (25,4 mm) below the
bottom of the concrete tee stems.
3. When the sprinkler deflectors are
located higher than a horizontal
plane 1 in. (25,4 mm) beneath the
bottom of the concrete tee stems,
the obstruction to sprinkler dis-
charge criteria requirements of
NFPA 13 for extended coverage
upright and pendent sprinklers
applies.
TFP22O
Page 5 of 8
Description Area
ft x ft
Light Hazard
0.10 GPM/ft2
Group
Ordinary Hazard
0.15 GPM/ft2
Group 11
Ordinary Hazard
0.20 GPM/ft2
____________
GPM
___________
PSI GPM
___________
PSI GPM PSI
14x14 30 7.2 30 7.2 39 12.1
TY5137
16x16 30 7.2 39 12.1 51 20.7
18x18 33 8.7 49 19.1 65 33.7 (K=11.2) Upright
20 x 20 40 12.8 60 28.7 80 51.0
14 x 14 30 7.2 30 7.2 39 12.1
16 x 16 30 7.2 39 12.1 51 20.7
TY5237
18 x 18 33 8.7 49 19.1 65 33.7 (K=11.2) Pendent
20x20 40 12.8 60 28.7 80 51.0
14 x 14 N/A N/A 39 7.8 1 51 13.3
16x16 N/A N/A 39 7.8 51 13.3 TY6137
18x18 N/A N/A 49 12.3 65 21.6 (K=14.0) Upright
20x20 N/A N/A 60 18.4 80 32.7
14 x 14 37 7.0 39 7.8 51 13.3
TY6237 16 x 16 37 7.0 39 7.8 51 13.3
18 x 18 37 7.0 49 12.3 65 21.6 (K=14.0) Pendent
20 x 20 40 8.2 60 18.4 80 32.7
NOTES
1 ft=0.3048 m
1 W = 0.093 m2
1 GPM = 3.785 LPM
1 psi = 0.06895 bar
1 GPM/ft2 = 40.74 mm/mm
TABLED
FLOW CRITERIA FOR UL AND C-UL LISTING OF SERIES EC-11 AND EC-14 SPRINKLERS
FM Approval Requirements
Series EC-11 and EC-14 Extended
Coverage Upright and Pendent Sprin-
klers are to be installed in accor-
dance with the applicable FM Loss
Prevention Data Sheet for limited use
in buildings of specific roof construc-
tion and for the protection of certain
specific ordinary hazard (non-storage
and/or non-flammable or combustible
liquid) occupancies. Information pro-
vided in the FM Loss Prevention Data
Sheets relates to, but is not limited to,
hydraulic design, ceiling slope, and
obstructions, minimum and maximum
allowable spacing, and deflector-to-
ceiling distance.
These criteria may differ from UL
and/or NFPA criteria. Therefore, the
designer should review and become
familiar with FM requirements before
proceeding with design.
Installation
TYCO Series EC-11 and EC-14
Extended Coverage Upright and
Pendent Sprinklers must be installed
in accordance with this section.
General Instructions
Do not install any bulb-type sprinkler
if the bulb is cracked or there is a loss
of liquid from the bulb. With the sprin-
kler held horizontally, a small air bubble
should be present. The diameter of the
air bubble is approximately 1/16 in.
(1,6 mm) for the 135°F (57°C) to
3/32 in. (2,4 mm) for the 286'F (141°C)
temperature ratings.
A leak-tight 3/4 in. NPT sprinkler
joint should be obtained by apply-
ing a minimum-to-maximum torque of
10 to 20 ft-lb (13,4 to 26,8 Nm). Higher
levels of torque may distort the sprin-
kler inlet with consequent leakage or
impairment of the sprinkler.
Do not attempt to compensate for
insufficient adjustment in an Escutch-
eon Plate by under or over-tightening
the Sprinkler. Re-adjust the position of
the sprinkler fitting to suit.
Step 1. Install the sprinkler with the
deflector parallel to the mounting
surface. Install pendent sprinklers in
the pendent position; install upright
sprinklers in the upright position.
Step 2. After installing the Style 30, 40,
or 60 mounting plate (or other applica-
ble escutcheon) over the sprinkler pipe
threads and with pipe-thread sealant
applied to the pipe threads, hand-
tighten the sprinkler into the sprinkler
fitting.
Step 3. For upright or pendent sprin-
klers, wrench-tighten using only the
W-Type 3 (End A) Sprinkler Wrench.
For the pendent sprinkler installed
with Style 30, 40, or 60 Escutcheon,
wrench-tighten the sprinkler using only
the W-Type 22 Sprinkler Wrench.
Apply the wrench recess of the appli-
cable sprinkler wrench (Figure 5 and 6)
to the sprinkler wrench flats (Figure 1).
TFP22O
Page 6 of 8
2-7/8 DIA.
1/2±1/8 (73,0 mm) 1/2' (12,7 mm)
(12,7±3,2 mm) 2-1/4' DIA. 1/4" (6,4 mm)
FACE OF (57,2 mm)
S
FITTING
R
'E1
(3,2 mm)
=///_li5
MOUNTING
JT
PLATE
CLOSURE ____________ .
1-3/8" (34,9 mm)
1-1/8" (28,6 mm)
FIGURE 2
SERIES EC-11 AND EC-14 RECESSED
PENDENT SPRINKLER ASSEMBLY
WITH TWO-PIECE 1/2 IN. TOTAL ADJUSTMENT
STYLE 30 RECESSED ESCUTCHEON
2-7/8" DIA.
5/8±1/4" - (73,0 mm) - 3/4' (19,1 mm)
(15,9±6,4 mm) 2-1/4' DIA. 1/4" (6,4 mm)
FACE OF (57,2 mm)
SPRINKLER 1/8'
FITTING (3,2 mm)
MIA
MOUNTING MOUNTING
SURFACE PLATE
CLOSURE
1-3/8"(3 mm)
7/8" (22,2 mm)
FIGURE 3
SERIES EC-11 AND EC-14 RECESSED
PENDENT SPRINKLER ASSEMBLY
WITH TWO-PIECE 3/4 IN. TOTAL ADJUSTMENT
STYLE 40 RECESSED ESCUTCHEON
2-7/8' DIA.
(73,0 mm)
INTERNAL 2-1/4' DIA. I I DIMENSIONS OF (57,2 mm) I STYLE 60 ESCUTCHEON
I I CLASS15OMALLEABLE
FACE OF IRON REDUCING
SPRINKLER FITTING: I SPRINKLER FITTING
3/8 (9,5 mm) ABOVE
TO 1/8" (3,2 mm) BELOW MOUNTING
MOUNTING SURFACE 1/8" SURFACE JTh\
I
ACCOMMODATE
(3,2 mm)
/ ESCUTCHEON PLATE
SEATING SURFACE:
1/4' (6,4 mm) ABOVE CLOSURE
5/16(587mm_ TO 1/2' (12,7 mm) BELOW 3/4,, NPT
MOUNTING SURFACE; MOUNTING 1-13/16" (46,0 mm)
3/4" (19,1 mm) TOTAL PLATE
ADJUSTMENT
FIGURE 4
SERIES EC-11 AND EC-14 PENDENT SPRINKLER ASSEMBLY
WITH 3/4 IN. TOTAL ADJUSTMENT
STYLE 60 TWO-PIECE FLUSH ESCUTCHEON
"FITTING SIDE"
TOWARDS SPRINKLER
FITTING
/\
WRENCH
RECESS /
(END "A")
FIGURE 5
W-TYPE 3 SPRINKLER
WRENCH
WRENCH
RECESS -_ -
WRENCH
HEX
FIGURE 6
W-TYPE 22 RECESSED
SPRINKLER WRENCH
TFP22O
Page 7 of 8
PIN 51 - XXX -X -XXX
SIN j SPRINKLER TEMPERATURE
FINISH1 RATING
893 11.2K Pendent TY5237 1 NATURAL BRASS 135 135°F (57°C)
894 11.2K Upright TY5137 SI? LITE 155 155°F (68°C)
- POLYESTER
895 14.0K Pendent TY6237 JET BLACK (RAL9005) 175 175°F (79°C)
- POLYESTER
896 14.0K Upright TY6137 200 200°F (93°C)
7 LEAD COATED
- 286 286°F(141°C)
9 CHROME-PLATED
- 000 OPEN2
NOTES:
Escutcheon ordered separately.
OPEN indicates the sprinkler assembly without glass bulb, button, and sealing assembly.
TABLE
SERIES EC-11 AND EC-14 UPRIGHT AND PENDENT SPRINKLERS
PART NUMBER SELECTION
Care and
Maintenance
TYCO Series EC-11 and EC-14
Extended Coverage Upright and
Pendent Sprinklers must be maintained
and serviced in accordance with this
section.
Before closing a fire protection system
main control valve for maintenance
work on the fire protection system
that it controls, obtain permission to
shut down the affected fire protection
systems from the proper authorities
and notify all personnel who may be
affected by this action.
Sprinklers which are found to be
leaking or exhibiting visible signs of
corrosion must be replaced.
Automatic sprinklers must never be
painted, plated, coated, or other-
wise altered after leaving the factory.
Modified sprinklers must be replaced.
Sprinklers that have been exposed to
corrosive products of combustion, but
have not operated, should be replaced
if they cannot be completely cleaned
by wiping the sprinkler with a cloth or
by brushing it with a soft bristle brush.
Care must be exercised to avoid
damage to the sprinklers before,
during, and after installation. Sprin-
klers damaged by dropping, striking,
wrench twist/slippage, or the like, must
be replaced. Also, replace any sprinkler
that has a cracked bulb or that has lost
liquid from its bulb. Refer to the Instal-
lation section, for more information.
Frequent visual inspections are rec-
ommended to be initially performed
for corrosion resistant coated sprin-
klers, after the installation has been
completed, to verify the integrity of the
corrosion resistant coating. Thereafter,
annual inspections per NFPA 25 should
suffice; however, instead of inspecting
from the floor level, a random sampling
of close-up visual inspections should
be made, so as to better determine the
exact sprinkler condition and the long
term integrity of the corrosion resistant
coating, as it may be affected by the
corrosive conditions present.
The owner is responsible for the
inspection, testing, and maintenance
of their fire protection system and
devices in compliance with this doc-
ument, as well as with the applicable
standards recognized by the Approval
agency, such as NFPA 25, in addition to
the standards of any authorities having
jurisdiction. Contact the installing con-
tractor or product manufacturer with
any questions.
Automatic sprinkler systems are rec-
ommended to be inspected, tested,
and maintained by a qualified Inspec-
tion Service in accordance with local
requirements and/or national codes.
Limited
Warranty
For warranty terms and conditions, visit
www.tyco-fire.com.
Ordering
Procedure
Contact your local distributor for
availability. When placing an order,
indicate the full product name and Part
Number (P/N).
Sprinkler Assemblies with
NPT Thread Connections
Specify: Series EC-11 or EC-14
(specify) Sprinkler, SIN (specify),
(specify) K-factor, Pendent or Upright
(specify) Extended Coverage, (specify)
temperature rating, (specify) finish, P/N
(from to Table E)
Recessed Escutcheon, Two-Piece
Specify: Style (30 or 40) Two-Piece
Recessed Escutcheon with (specify)
finish, P/N (specify*)
Refer to Technical Data Sheet TFP770
Flush Escutcheon, Two-Piece
Specify: Style 60 Two-Piece Flush
Escutcheon with (specify) finish, P/N
(specify**)
**Refer to Technical Data Sheet TFP778
Sprinkler Wrenches
Specify: W-Type 3 Sprinkler Wrench,
P/N 56-895-1-001
Specify: W-Type 22 Recessed Sprinkler,
Wrench, P/N 56-665-7-001
TFP22O
Page 8 of 8
1400 Pennbrook Parkway Lansdale, PA 194461 Telephone +11-215-362-0700
02019 Johnson Controls. All rights reserved. All specifications and other Information shown were current as of document revision data and are subject to change without notice. Johnson .1
NATIONAL FIvE PROTECTION ASSOCIATION and NFPA ore registered trademarks of Nations l Fire Protection Acoeviatiorri
TEFLON iso reglntnrad trademark 01 DuPont Controls
11
Malleable Iron Threaded Pipe Unions
Pressure - Temperature Ratings
Temperature Pressure Class 150 Class 250 Class 300
'psi .I: :bar psi bar p5 oar
200
to
1500
-28.9°
to 300 20.7
65.60
500 34.5 €OC 4.4
2000 93.30 265 18.3 455 31.4 55C 37.9
2500 121.10 225 15.5 405 27.9 50F 34.3
3000 148.9° 185 12.8 360 24.8 LEO 517
3500 176.70 150 10.3 315 21.7 415 28.6
4000 204.40 110 7.6 270 18.6 370 25.5
4500 232.20 75 5.2 225 15.5 325 22.4
5000 260.00 - - 180 12.4 2E0 19.3
5500 287.80 - - 130 9.0 230 15.9
Note: Unions with Copper or Copper Alloy seats are not intended for use where temeruture exces
450°F
c®us APPROVED
Malleable Iron Threaded Fittings
Pressure - Temperature Ratings
Temperature
Pressure
Class 150
Class 300 __________ Sizes Yr-i
(6-15 mm)
Sizes 11,/V-2' Sizes 21/u _30
(32-51 mm) 64-76 mm)
(F bar psi' hà' pi pitr
200
to
1500
-28.9
to
65.60
300 20.7 2,003 137.9 1,500 103.4 ,000 68.9
200° 93.3 255 18.3 1,785 123.1 1,350 93.1 910 62.7
250° 12 1. 1 225 15.5 1,575 108.6 1,200 82.7 325 56.9
3000 148.9 135 12.8 1,360 93.6 1,050 724 735 50.7
350° 176.7 150 10.3 1,150 79.3 900 62.1 350 44.8
4000 204.4 - - 935 64.5 750 51.7 560 38.6
4500 232.2 - - 725 50.0 600 41.4 475 32.8
500° 260.0 1 - - 510 35.2 450 37.011 385 26.5
5500 287.e, - - 300 20.7 300 20.7 300 20.7
Anvil Class 153/300 Malleable Iron Fittings conform to ASME
B16.3 and Unions conform to ASME B16.39.
For Listings/Approval Details and Limitations, visit our vebsite @
www.anvilintl.com or contact an Anvil/AnvilStar Sales Representative. ALL ELBOWS & EES N" (10 DN ard LARGER ARE 130% GAS TESTED AT
A MINIMUM CF 100 PSI. (6.9 bar)
~~) twww.anvilintl.com 17
PF-11.10
=1 =2 •i . i.
SPRINKLER
CATALOG
1Ii
\\\
4:
. .-
1, •;' '. i-::
I.
r
c®us LISTED
<s>
APPROVED
L NFPA
;•;
t
LMI=LJI
JDYTHF
I=nr-w I
Wim 1SIIIYAIJA
Bull Moose Tube® is a customer focused,
growth oriented manufacturer and
marketer of tubular products, where
success is based on a commitment
to meeting the customer's perception
of quality.
Our strength resides in our people
working together to satisfy customers
and to promote business growth by
achieving superior financial performance.
www.BullMooseTube.com
sales@bullmoosetube.com
800.325.4467
BULL MOOSE TUBE COMPANY
ran sprin Ii iprcedto r-. ® - rlleet'I rir r iitiestandrI iriI-
Trt .
!* '
-''• - :-' I
?.'
I
-- -
-.-
:':
•
?ç
): - •:-
c®us LISTED I
H
APPROVED I
[] A. OAFSA 4: NFPA I
ADVANTAGES OF BULL MOOSE TUBE® EDDY PIPE® FAMILY
All pipe products are UL Listed (for U.S. and Canada), and have been approved by Factory Mutual.
Excellent production and coating capabilities, tighter tolerances, and our unique steel properties make our pipe excellent for
roll grooving, welding, threading, and plain end fittings.
All products are certified to ASTM Al 35 and A795 Type E, Grade A.
Available in specific cut to order lengths from regular mill rollings.
More popular sizes available with coating or bare.
Ultra Eddy®, Eddy Flow®, Eddylite®, and Eddythread 40® offer cost
savings along with superior hydraulics without compromising service life.
Sprinkler pipe inventory stocked in Masur Ohio; Gerald, Missouri;
Casa Grande, Arizona; Kent, Washington; and Dallas, Texas.
All Bull Moose (black) sprinkler pipe includes our exclusive EDDY GUARD
Il® MIC preventative coating.
Bull Moose Tube® sprinkler pipe is FBCTM compatible.
PRODUCTS
Schedule 10 and Schedule 40: FM approved and UL listed
sprinkler pipe.
Eddythread 40®: Light threadable Schedule 40 replacement
with corrosion resistance ratio of 1.0.
Eddylite®: Lightwall threadable with standard outside diameter.
Eddy Flow®: Cost effective replacement for Schedule 10.
Ultra Eddy®: Lightwall roll groovable pipe.
Bull Moose galvanized steel sprinkler pipe is hot dipped
galvanized to meet ASTM Al 23 standards. All products are
stencilled to meet FM & UL specifications.
PROTECTION
Eddy Guard Il®: Bull Moose Tube® is producing product that can resist
bacteriological growth even after multiple rinse-outs. You know
MIC corrosion can impact your installation and your property. Specify
Bull Moose Tube® "Eddy Guard Il®" and feel comfortable knowing
that you are getting Eddy Pipe® product you trust with the bacteria
resistance you need. Eddy Guard Il® is NFPA 13 and NFPA 13R system
compatible for use in hybrid systems as well as FM approved.
All information contained herein is accurate as known at the time of publication.
Bull Moose Tube® reserves the right to change product specifications without notice
and without incurring obligation.
ano drid(la), CVflTfl(
productsrdo notThi4ui
approvals andlistings
' •t Moose Tube made th
to have them approve
OurSrhed ne 1 Oand
have a pressure ratinc
and, have been throug
rigorous testing as ou
pipe products. Schedu
suppIiedroHqroovm
.Bull MooTube's Sc
- .andSchedLile 44ipes
dipped galvanized to n
Al 23 standardsAlI pr
st icillid to meet FM
sfic3ubns.
45
,
tASTM
J(ts are
.-
S LI S
SCHEDULE 10 PIPE SPECIFICATIONS
NOMINAL PIPE O.D. I.D. WATER FILLED BUNDLE
SIZE (IN) (IN) (IN) CRR** WEIGHT/FT WEIGHT SIZE
1.097 JL157L11.4iiLft J .80 JL :J!iij
l FEW 9J 5L
11/2 1fli900T1682 77 [2091bs/ft 3031
-.
jIff
21I2 - _ [2635 492 I53IbtftjE893l
350Q 260
________ 341iift 957k
41L _4500 4260 ll25OJ 562 ifL
SCHEDULE 40 PIPE SPECIFICATIONS
NOMINAL PIPE O.D. I.D. WATER FILLED BUNDLE
SIZE (IN) (IN) (IN) CRR** WEIGHT/FT WEIGHT SIZE
L i 315 1-049 10 11,68 lbs/ft[ 2.055 IL 70
j660 a 380 10Q 2Jft E2Th1TL
12 [Th 900 ] i6 100 Till
23i5 r 2 06] ' rThoL7L 366ft Ei i4L=30=
fl21/2*_T2.875 2 468 100 80I/ft j
3L1 io 3Q68 8[bftI b3
- 4* r 4500 1 4026 100 10.80-16 T3i]r19 i
*Only available in Casa Grande, AZ
**Corrosion Resistance Ratio per latest UI Directory Listing
c®us LISTED
<>
APPROVED
ONFSA
NFPA -
--
PIPE PREPARATION
For proper operation, all pipe surfaces should be cleaned prior to installation. In order to provide a leak-tight seat for the gasket,
pipe surfaces should be free from indentations and projections from the end of the pipe to the groove. All loose paint, scale, dirt,
chips, grease, and rust must be removed prior to installation. Failure to take these important steps may result in improper coupling
assembly, causing leakage. Also, check the manufacturer's instructions for the specific fitting used.
For Additional Information Contact (800) 325-4467 www.buIlmoosetube.com
-
, Or From Canada Call (800) 882-4666 sales@builmoosetube.com
1819 Clarkson Road
Chesterfield, MO Gerald, MO Kent WA Casa Grande. AZ Dallas TX Masury, OH
BULL MOOSE TUBE cosr,jy 63017
FireLock® Outlet-I ILPCBI
SEE VICTAULIC PUBLICATION 10.01 FOR DETAILS
STYLE 922
The Style 922 Outlet-T provides a convenient method of incorporating ½, 3/4, and 1/15, 20
and 25 mm outlets for directly connecting sprinklers, drop nipples, sprigs, gauges, drains and
other outlet products. Available for P14 through 76.1 mm/32 to 76.1 mm piping systems, Style
922 outlets are UL/ULC Listed, LPCB and FM Approved for branch connections and VdS
Approved for direct sprinkler connection only on wet and dry systems.
The locating collar engages into the hole prepared in the pipe. When tightened, the assembly
compresses the gasket onto the OD of the pipe. The Style 922 Outlet-T is UL/FM rated up
to 300 psi/2068kPa and VdS rated up to 16 bar at the ambient temperatures typical for fire
protection systems.
Style 922 is suitable for use on standard, lightwall, Schedule 5 and other specialty pipes.*
Contact Victaulic for other optional coatings.
*Consult Section 10.01 for specific listings/approvals.
MATERIAL SPECIFICATIONS Housing: Ductile iron conforming to ASTM A-536, grade 65-45-12. Ductile iron conforming to
ASTM A-395, grade 65-45-15, is available upon special request.
Gasket:
Grade "E" EPDM - Type A
(Violet color code). FireLock products have been Listed by Underwriters Laboratories Inc. and
Approved by Factory Mutual Research for wet and dry (oil free air) sprinkler services up to the
rated working pressure using the Grade "E" Type A Gasket System.
Bolts/Nuts: Heat-treated plated carbon steel, trackhead meeting the physical and chemical
requirements of ASTM A-449 and physical requirements of ASTM A-183.
Housing Coating:
Orange enamel (North America, Latin America, Asia Pacific)
Red enamel (Europe)
JOB/OWNER CONTRACTOR ENGINEER
System No Submitted By Spec Sect Para
Location Date Approved
Date
www.victaulic.com
vIcTAuLIc IS REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2009 VICTAULIC COMPANY. ALL RIGHTS RESERVED.
REV G
Ai tauIicr
U152 1
DIMENSIONS
IPS CARBON STEEL PIPE - HOLE CUT PRODUCTS
FireLock® Outlet-T
STYLE 922
Nominal Size
i nchesimm
Hole
Diameter Dimensions - i nc hes/milli meters
Approx.
Weight Each
Run X Branch +0 * 0641.5
V
1 1/4 ½ 1 3A6 130 1.83 1.10 3.87 2.56 1.0 x 32 15 30.2 33.0 46.5 27.9 98.3 65.0 0.45
3/4 11/16 1.28 1.83 1.10 3.87 2.56 1.1
20 30.2 32.5 46.5 27.9 98.3 65.0 0.50
1 1 3A6 1.52 2.18 1.10 3.87 2.56 1.2
25 30.2 38.6 55.4 27.9 98.3 65.0 0.54
11/3 ½ 1 3A6 1.42 1.95 1.22 4.08 2.56 1.2 x 40 15 30.2 36.1 49.5 1 31.0 103.6 65.0 0.54
3/4 1 3A6 1.40 1.95 1.22 4.08 2.56 1.2
20 30.2 35.6 49.5 31.0 103.6 65.0 0.54
1 1'/16 1.64 2.30 1.22 4.08 2.56 1.3
25 302 41.7 58.4 31.0 1 103.6 65.0 0.59
2 ½ 1'/16 1.66 2.19 1,46 4.60 2.56 1.3 x 50 15 30.2 1 42.2 55.6 37.1 116.8 65.0 0.59
3% 1 3/16 1.64 2.19 1.46 4.60 2.56 1.4
20 30.2 41.7 55.6 37.1 116.8 65.0 0.64
1 1 3/16 1.88 2.54 1.46 4.60 2.56 1.5
25 30.2 47.8 64.5 37.1 1 116.8 65.0 0.68
2½ ½ 1 3/16 1.91 2.44 1.71 5.40 2.56 1.6 x 65 15 30.2 48.5 62.0 43.4 137.2 65.0 0.73
3% 1 3/16 1.89 2.44 1.71 5.40 2.56 1.6
20 30.2 48.0 62.0 43.4 137.2 65.0 0.73
1 1 3Ao 2.13 2.79 1.71 5.40 2.56 1.6
25 30.2 54.1 70.9 1 43.4 137.2 65.0 0.73
/2 1/l6 1.91 2.44 1.71 5.50 2.56 1.6 X 76.1 mm 15 30.2 48.5 62.0 43.4 139.7 65.0 0.73
3% 13A6 1.89 2.44 1.71 5.50 2.56 1.6
20 30.2 48.0 620 43.4 139.7 65.0 0.73
1 1 3A6 2.13 2.79 1.71 5.50 2.56 1.7
25 30.2 54.1 70.9 43.4 139.7 65.0 1 0.80
f Victaulic female threaded products are designed to accommodate standard NPT or BSPT (optional)
male pipe threads only. Use of male threaded products with special features, such as probes, dry pen-
dent sprinklers, etc., should be verified as suitable for use with this Victaulic product. Failure to verify
suitability in advance may result in assembly problems or leakage.
Center of run to engaged pipe end for NPT threads (dimensions are approximate).
www.victaulic.com
VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2009 VICTAULIC COMPANY. ALL RIGHTS RESERVED.
10.52 2
Aictaulicr
REV C,
IPS, CARBON STEEL PIPE - HOLE CUT PRODUCTS iU.ZL
PERFORMANCE
Run Size x Outlet Size
Equivalent Length of 1 inch
Schedule 40 Steel Pipe (per UL
213, Section 16) (C=120)*, FT
Inches/mm Feet/meters
x 40 25
1
¶1 A.
21/2
65 4.
1.1•iiii
Hazen-Williams coefficient of friction is 120
FireLock® Outlet-I
STYLE 922
www.victaulic.com
,s$(c;:tauIic.f'
VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2009 VICTAULIC COMPANY. ALL RIGHTS RESERVED.
RflI r 10V;9 3
FireLock® Outlet-I
STYLE 922
INSTALLATION Reference should always be made to the 1-100 Victaulic Field Installation Handbook for the product
you are installing. Handbooks are included with each shipment of Victaulic products for complete
installation and assembly data, and are available in PDF format on our website at www.victaulic.com.
WARRANTY Refer to the Warranty section of the current Price List or contact Victaulic for details.
NOTE This product shall be manufactured by Victaulic or to Victaulic specifications. All products to be
installed in accordance with current Victaulic installation/assembly instructions. Victaulic reserves the
right to change product specifications, designs and standard equipment without notice and without
incurring obligations.
For complete contact information, visit www.victaulic.com
'j4'ctauiic. 10.52 3355 REV G UPDATED 12/2009
vlcTAuLlc IS REGISTERED TRADEMARK OF vICTAULIC COMPANY. © 2009 VICTAULIC COMPANY. ALL RIGHTS RESERVED.
1052
P.O. Box 3365 South El Monte, CA 91733 626.444.0541 Fax 626.444.3887 www. Afcon.org
300
RING HANGER
I thru 4 inch pipe
LISTED FOR STEELJCPVC
1/2 & 3/4 inch pipe
5 thru 8 inch pipe
SIZE - ROD- 3/8" or 1/2"
SIZE - SYSTEM PIPE - 1/2" thru 8"
MATERIAL - Carbon Steel, Mil. Galvanized to G-90 spec.
LISTING/APPROVAL -
C®U8TDUs2 03-EX 2551 1"- 8"
4e> Approval guide - 1"- 8"
OSHPD OPA-0601 See Website.
CONFORMS WITH: Federal Specification WW-H-171E, Type 10.
Manufacturers Standardization Society ANSI/MSS-SP-58 Type 10.
MAXIMUM TEMPERATURE - 650°F.
FUNCTION - Pipe hanger component of an AFCON hanger.
To support steel, CPVC or copper pipe.
INSTALLATION - Per NFPA 13, 13R, 13D, these instructions and
the CPVC or copper pipe manufacturers instructions.
FEATURES -
* Sized and listed exclusively for use with #310 Surge Restrainer.
* Band edge is offset for EASY pipe insertion.
* Custom fit swivel nut for better retention in ring.
ORDERING - Part #, pipe size.
NFPA 13
PIPE ROD
I WT. 5 WT.+250
UL TEST LOAD
1 3/8 30.75 403.75 750
11/4 3/8 43.95 469.75 750
11/2 3/8 54.15 520.75 750
2 3/8 76.95 1 634.75 750
21/2 3/8 118.35 841.75 850
3 1 3/8 162.30 1061.50 1050
4 3/8 246.00 1460.00 1500
5 1/2 349.45 1996.75 2000
6 1/2 476.35 2631.75 2650
8 1/2 1 711.00 3805.00 4050
11/09
551
P.O. Box 3365 South El Monte, CA 91733 626.444.0541 Fax 626.444.3887 www. Afcon.org
310
RING RESTRAINER
Restraint
SIZE - One size fits 3/4 thru 2 inch AFCON#300 Ring Hanger.
MATERIAL - Carbon Steel.
FINISH - Mu. Galvanized.
LISTINGS -
Sus 203-EX 2551
Listed only for use with AFCON #300 Ring Hanger.
FUNCTION - To restrain movement of sprinkler pipe toward the knurl nut of the
ring hanger. To prevent upward movement of pipe that supplies a pendent
sprinkler below the ceiling.
INSTALLATION - Per NFPA 13 and CPVC manufacturers instructions
on steel, CPVC, or copper pipe.
Snap into locking position on swivel nut of AFCON #300 Ring Hanger.
SPECIAL NOTE: When installing on CPVC sprinkler system pipe:
Verify that all assembly components are cleaned of any surface oil.
FEATURES -
* Listed only for use with AFCON #300 Ring Hanger.
ORDERING - Part # and size.
Specific AFCON products are exclusively designed to be compatible ONLY with other AFCONproducts including parts and fasteners, resulting in a listed sway brace, restrainer or hanger assembly.
Be advised the following warranty restriction wilt apply. DISCLAIMER - AFCON will NOT warrant against the failure of its products when used in combination with other products, parts or systems
not manufactured or sold by AFCON AFCON shall NOT be liable under any circumstances whatsoever for any direct or indirect, incidental or consequential damages of any kind, including but not
limited to loss of business or profit, when non-AFCON products have been, or are used.
1/08
Not less than Wood Flooring 2' nominal width Product Features
No pre-drilling required.
Not less than ! I:
ir
Quick to install using the Sammy 3' nominal Nut Driver with an 18V cordless thickness (2-1/2')
(depth or side Wood Joist drill/driver.
of vertical member)
- - - 'Saves time from traditional
Double Sheebock methods. Ceiling
Reduces installation cost
_________Composite i Truss
Consult truss manufacturer for
recommended installation point
*Pre-driffing maybe required for G
25-380. Tool available on page I
IT
Made in the U.S.A.
__
1/4' 8003957 GST 200 114x2 1760 (Fir) 25 125
1'T480097GSj100-'/47x'3" 206j) 2512
3/8 8006957 GST.75 114x3/4 564 (3/4' Ply) 25 125
887957GS,ffi l74 3{oo 2525
3/8' 8008957 GST 20 1/4 x 2' 1760 (Fir) 850 1475 25 125
3180689251 2 1760 850 252
kilo 3/8 8009925 GST 25-380 3/8x2-112' 213 (Fir) 1500 25 125 #14 lack 7_4 1500 14Z5 2
3/8' 8069925 GST 30-SS 1/4x3 2060 (Fir) 25 125 Nut Driver
Part# 8113910
1i44 2,1802fr) 25125
3/8" 8012925 GST 60 1/4 x 6" 2230 (Fir) 25 125
112013925SJ2 1]42 l76J(//) 25f2
1/2" 8014925 GST 2.5-380 3/8 x 2-1/2" 2113 (Fir) 25 125
172825GT313 1/43 2275JEJr1 251
1/2' 8016925 GST4 1/4x4' 2180 (Fir) 25 125
i728017925TI6 1/46' 23IirJ 2b12 #14 SW Red
Nut Driver
Part# 8114910
Product Features
Eliminates distortion of threaded rod. • Saves time from traditional methods.
'Accommodates up to 3 'Ia" x 12 pitch roof. • Reduces installation cost.
'Allows 17" deflection from vertical. • Made in the U.S.A.
3/8' 8141957 SH-GST 30 1/4x 3' 1720 (Fir) 1500 1475 25 125
SPECIAL NUT DRIVER SYSTEM: The nut drivers were designed with a unique spin-off feature which provides a fast and safe installation each time. When the face of the driver comes into
contact wi;h the material you are installing into, continue drilling until nut driver spins free. Installation is then complete. Warranty requires the use of the appropriate nut driver for installations.
ARL
For the most up to date information, visit www.sammysuperscrew.coin 47' Lamm --- \w
- •"I-
4 #14 Black
Nut Driver
Part# 8113910
I
Floor Joist
Product Features
No pre-drilling required.
Quick to install using the Sammy
Nut Driver with an 18V cordless
drill/driver.
Saves time from traditional
methods.
Reduces installation cost
Made in the U.S.A.
Not less than 2' nominal width / (1-1/2') up to 3-1/2' ripe; not less than
3' (2-1/2') nominal width 4' & 5' pipe
.4
I
Minimum 2-1/2' from bottom for
branch lines. Minimum 3' from
bottom for main linen. Exception: This
requirement shall not apply to 2' or
thicker nailing strips resting on top of
steel beams.
Insert the appropriate nut driver into a 3/8" or 1/2" portable drill.
Insert the SAMMYS into the #I4SW (red) nut driver (p/n 8114910). With drill
unit in a horizontal position and at a right angle to the structural member,
begin installation.
When the nut driver spins free on the SAMMYS, stop the drill and
remove.
The unit is now ready to receive 1/4' 3/8" or metric all thread rod or
bolt stock.
Note: When installing SWDR, follow the above instructions, then add retainer nut
and torque to 20 foot lbs. for maximum pullout in purlin steel.
-' 114' 8Cfj WG00 74i' 6221iEJi) 25 t25
1/4' 8019957 SWG 200 1/4x2' 1725 (Fir) 25 125 - 37ll ——BO07 SW0 171 622r(id 300 25 12#
X 3/8" 8021957 SWG 20 1/4x2' 1725 (Fir) 1050 25 125
218807.392 SWG 850 12
#14 SW Red XSjl. 3/8'
L
8022925 SWG 25-380 3/8 X 2-1/2" 2249 (Fir) 1500 25 125
Not Driver 3/8'8023925 SWG'30 1j43 188(EJr) 25 12
Part#8114910
Insert the appropriate nut driver into a .3/8' or 1/2" portable drill
Insert the SAMMYS into the #14 (black) nut driver (p/n 8113910). Drill
should be in a vertical position.
Push the face of the nut driver tight to the member When the
nut driver spins freely on the SAMMYS, stop drill and remove.
The SAMMYS is now ready to receive 1/4", 3/8", 1/2" or metric
all thread rod, bolt stock. (The 1/2" requires the #14S W red nut driver)
Note: When installing DSTR, follow the above instructions,
then add retainer nut and torque to 20 foot lbs. for maximum
pullout in purlin steel.
mpj
on EXISHIM
ER , I Fol!'11
SPECIAL NUT DRIVER SYSTEM: The nut drivers were designed with a unique spin-off feature which provides a fast and safe installation each time. When the face of the driver comes into
contact with the material you are installing into, ::ontinoe drilling until nut driver spins free. Installation is then complete. Warranty requires the use of the appropriate nut driver for installations.