HomeMy WebLinkAbout1940 CAMINO VIDA ROBLE; ; FPC2018-0173; PermitcJity of PERMIT REPORT Carlsbad Print Date: 05/11/2022 Permit No: FPC2018-0173 Job Address: 1940 CAMINO VIDA ROBLE, CARLSBAD, CA 92008-6516 Status: Closed - Finaled Permit Type: FIRE-Construction Commercial Work Class: Fire Sprinklers Parcel #: 2120921300 Track #: Applied: 06/06/2018 Valuation: $74,416.00 Lot #: Issued: 06/13/2018 Occupancy Group: Project #: Finaled Close Out: 03/24/2021 #of Dwelling Units: Plan #: Bedrooms: Construction Type: Final Inspection: Bathrooms: Orig. Plan Check U: INSPECTOR: Wong, Cindy Plan Check #: Project Title: Description: CAL-COMP USA (CCSD) -SPRINKLER TI (48 HEADS) TI FOR 3D PRINTER ROOM WITHIN EXISTING OFFICE SPACE Applicant: FPContractor: AMERICAN AUTOMATIC FIRE SUPPRESSION AMERICAN AUTOMATIC FIRE SUPPRESSION INC INC JAZZMIN DEEKEN 9925 PROSPECT AVE, USTE B 9925 PROSPECT AVE, # B SANTEE, CA 92071 SANTEE, CA 92071 (619) 562-3010 (619) 562-3010 FEE AMOUNT FIRE NFPA 13 or 13R System 7 - 100 heads $536.00 Total Fees: $536.00 Total Payments To Date: $536.00 Balance Due: $0.00 Fire Department Page 1 of 1 1635 Faraday Avenue, Carlsbad CA 92008-7314 1760-602-4665 1760-602-8561 f I www.carlsbadca.gov 00 tqco Fire Protection Products Worldwide Contacts www.tyco-fire.com Series TY-FRB, 56 K-factor Upright, Pendent, and Recessed Pendent Sprinklers Quick Response, Standard Coverage General Description The TYCO Series TY-FRB, 5.6 K-factor, Upright (TY313) and Pendent (TY323) Sprinklers described in this data sheet are quick response, standard coverage, decorative 3 mm glass bulb-type spray sprinklers designed for use in light or ordinary hazard, commercial occupan- cies such as banks, hotels, and shop- ping malls. The recessed version of the Series TY- FRB Pendent Sprinkler, where applica- ble, is intended for use in areas with a finished ceiling. This recessed pendent sprinkler uses one of the following: A two-piece Style 15 Recessed Escutcheon with recessed adjust- ment up to 5/8 inch (15,9 mm) from the flush pendent position. A two-piece Style 20 Recessed Escutcheon with recessed adjust- ment up to 1/2 inch (12,7 mm) from the flush pendent position. The adjustment provided by the Recessed Escutcheon reduces the accuracy to which the fixed pipe drops to the sprinklers must be cut. Intermediate level versions of Series TY-FRB Sprinklers are described in Technical Data Sheet TFP357. Sprin- kler guards and shields are described in Technical Data Sheet TFP780. IMPORTANT Always refer to Technical Data Sheet TFP 700 for the "INSTALLER WARNING" that provides cautions with respect to handling and instal- lation of sprinkler systems and com- ponents. Improper handling and installation can permanently dam- age a sprinkler system or its compo- nents and cause the sprinkler to fall to operate in a fire situation or cause it to operate prematurely. Page 1 of 4 [NoTIcE The TYCO Series TY-FRB Sprinklers described herein must be installed and maintained in compliance with this doc- ument, as well as with the applicable standards of the National Fire Protec- tion Association, in addition to the stan- dards of any other authorities having jurisdiction. Failure to do so may impair the performance of these devices. The owner is responsible for maintain- ing their fire protection system and devices in proper operating condition. The installing contractor or sprinkler manufacturer should be contacted with any questions. Sprinkler Identification Number (SIN) TY313 .......Upright 5.6K, 1/2" NPT TY323 ......Pendent 5.6K, 1/2" NPT Technical Data Approvals UL and C-UL Listed FM, LPCB, and VdS Approved CE Certified Sprinklers with Polyester Finish are UL and C-UL Listed as Corrosion-Resis- tant Sprinklers. Maximum Working Pressure 175 psi (12.1 bar) 250 psi (17.2 bar)* *The maximum working pressure of 250 psi (17.2 bar) only applies to the listing by Un- derwriters Laboratories, Inc. (UL). Discharge Coefficient K=5.6 GPM/psi112 (80,6 LPM/barl'2) FEBRUARY 2014 Temperature Rating 135°F (57°C) 155°F (68°C) 175°F (79°C) 200°F (93°C) 286°F (141°C) Finishes Sprinkler: Refer to Table A Recessed Escutcheon: White Coated, Chrome Plated, or Brass Plated Physical Characteristics Frame ...................Bronze Button..............Brass/Copper Sealing Assembly .........Stainless Steel w/TEFLON Bulb ......................Glass Compression Screw........Bronze Deflector.................Bronze TFPI72 TFPI72 Page 2 of 4 Components: * Temperature rating is ** Pipe thread connections per ISO 7-1 1 - Frame 4 - Bulb indicated on Deflector. can be provided on special request. 2 - Button 5 - Compression STYLE 15 or 20 3 - Sealing Screw ESCUTCHEON PLATE 1/2 7/16 (11,1 mm) RECESSED Assembly 6 - Deflector* DEFLECTOR * SEATING SURFACE NPT** NOMINAL MAKE-IN ESCUTCHEON 2" (50,8 mm) CROSS SECTION 1 7/16 (11,1 mm) I NOMINAL MAKE-IN 2" (50,8 mm) 1/2 NPT** UPRIGHT WRENCH FLATS DEFLECTOR * b...— 2-7/8" (73,0 mm) DIA. PENDENT RECESSED PENDENT FIGURE 1 SERIES TY-FRB UPRIGHT (TY313) AND PENDENT (TY323) SPRINKLERS 5.6 K-FACTOR, 1/2 INCH NPT, QUICK RESPONSE / CH RECESS (USE ONLY ND FIGURE 2 W- TYPE 6 SPRINKLER WRENCH WRENCH RECESS PUSH WRENCH IN TO ENSURE ENGAGEMENT WITH SPRINKLER WRENCHING AREA FIGURE 3 W- TYPE 7 RECESSED SPRINKLER WRENCH Operation The glass bulb contains a fluid which expands when exposed to heat. When the rated temperature is reached, the fluid expands sufficiently to shatter the glass bulb, allowing the sprinkler to activate and water to flow. Design Criteria The TYCO Series TY-FRB, 5.6 K-factor, Upright (TY313) and Pendent (TY323) Sprinklers are intended for fire protec- tion systems designed in accordance with the standard installation rules rec- ognized by the applicable Listing or Approval agency (such as, UL Listing is based on the requirements of NFPA 13, and FM Approval is based on the requirements of FM's Loss Prevention Data Sheets). Only the Style 15 or Style 20 Recessed Escutcheon is to be used for recessed pendent installations. Installation The TYCO Series TY-FRB, 5.6 K-factor, Upright (TY313) and Pendent (TY323) Sprinklers must be installed in accor- dance with this section. General Instructions Do not install any bulb-type sprinkler if the bulb is cracked or there is a loss of liquid from the bulb. With the sprin- kler held horizontally, a small air bub- ble should be present. The diameter of the air bubble is approximately 1/16 inch (1,6 mm) for the 135°F (57°C) and 3/32 inch (2,4 mm) for the 286°F (141°C) temperature ratings. A leak-tight 1/2 inch NPT sprinkler joint should be obtained by applying a min- imum to maximum torque of 7 to 14 ft.-lbs. (9,5 to 19,0 Nm). Higher levels of torque can distort the sprinkler Inlet with consequent leakage or impairment of the sprinkler. Do not attempt to compensate for insufficient adjustment in the Escutch- eon Plate by under- or over-tightening the sprinkler. Re-adjust the position of the sprinkler fitting to suit. Upright and Pendent Sprinklers The Series TY-FRB Upright and Pen- dent Sprinklers must be installed in accordance with the following instructions. Step 1. Install Pendent sprinklers in the pendent position. Install upright sprin- klers in the upright position. Step 2. With pipe-thread sealant applied to the pipe threads, hand- tighten the sprinkler into the sprinkler fitting. TFPI72 Page 3 of 4 Step 3. Tighten the sprinkler into the sprinkler fitting using only the W-Type 6 Sprinkler Wrench (Figure 2). With ref- erence to Figure 1, apply the W-Type 6 Sprinkler Wrench to the wrench flats. Torque sprinklers 7 to 14 ft.-lbs. (9,5 to 19,0 Nm). Recessed Pendent Sprinklers The Series TY-FRB Recessed Pendent Sprinklers must be installed in accor- dance with the following instructions. Step A. After installing the Style 15 or Style 20 Mounting Plate over the sprin- kler threads, and with pipe-thread sealant applied to the pipe threads, hand-tighten the sprinkler into the sprinkler fitting. Step B. Tighten the sprinkler into the sprinkler fitting using only the W-Type 7 Recessed Sprinkler Wrench (Figure 3). With reference to Figure 1, apply the W-Type 7 Recessed Sprinkler Wrench to the sprinkler wrench flats. Torque sprinklers 7 to 14 ft.-lbs. (9,5 to 19,0 Nm). Step C. After ceiling installation and fin- ishing, slide on the Style 15 or Style 20 Closure over the Series TY-FRB Sprin- kler and push the Closure over the Mounting Plate until its flange comes in contact with the ceiling. Care and Maintenance The TYCO Series TY-FRB, 5.6 K-factor, Upright (TY313) and Pendent (TY323) Sprinklers must be maintained and ser- viced in accordance with this section. Before closing a fire protection system main control valve for maintenance work on the fire protection system that it controls, obtain permission to shut down the affected fire protection systems from the proper authorities and notify all personnel who may be affected by this action. Absence of the outer piece of an escutcheon, which is used to cover a clearance hole, can delay sprinkler operation in a fire situation. The owner must assure that the sprin- klers are not used for hanging any objects and that the sprinklers are only cleaned by means of gently dusting with a feather duster; otherwise, non- operation in the event of a fire or inad- vertent operation may result. Sprinklers which are found to be leak- ing or exhibiting visible signs of corro- sion must be replaced. Automatic sprinklers must never be painted, plated, coated, or other- wise altered after leaving the factory. Modified sprinklers must be replaced. Sprinklers that have been exposed to corrosive products of combustion, but have not operated, should be replaced if they cannot be completely cleaned by wiping the sprinkler with a cloth or by brushing it with a soft bristle brush. Care must be exercised to avoid dam- age to the sprinklers before, during, and after installation. Sprinklers damaged by dropping, striking, wrench twist/ slippage, or the like, must be replaced. Also, replace any sprinkler that has a cracked bulb or that has lost liquid from its bulb. (Ref. Installation Section.) The owner is responsible for the inspection, testing, and maintenance of their fire protection system and devices in compliance with this document, as well as with the applicable standards of the National Fire Protection Associa- tion (e.g., NFPA 25), in addition to the standards of any other authorities hav- ing jurisdiction. Contact the installing contractor or sprinkler manufacturer regarding any questions. Automatic sprinkler systems are rec- ommended to be inspected, tested, and maintained by a qualified Inspec- tion Service in accordance with local requirements and/or national codes. 2-7/8 DIA. (73,0 mm) - 2-1/4 DIA. FACE OF (57,2 mm) SPRINKLER FITTING 5/8 (15,9 mm) _____ _____________ FLUSH 3/8±5/16" (9,5±7,9 mm) MOUNTING (3 1/8 J 2 mm) SURFACE _____ CLOSURE SERIES MOUNTING 1-3/8" (34,9 mm) TYFRB PLATE 3/4" (19,1 mm) FIGURE 4 SERIES TY-FRB RECESSED PENDENT SPRINKLER ASSEMBLY 'TY323) WITH TWO PIECE 5/8 INCH TOTAL ADJUSTMENT STYLE 15 RECESSED ESCUTCHEON 2-7/8" DIA. (73,0 mm) FACE OF SPRINKLER - 2-1/4" DIA. FITTING (57,2 mm) 5/16±1/4" 1/2 (12,7 mm) (7,9±6,4 mm) FLUSH MOUNTING / 1/8' J / / SURFACE / \ (3,2 mm) CLOSURE SERIES MOUNTING 1-3/8 (34,9 mm) TY-FRB PLATE 7/8 (22,2 mm) FIGURE 5 SERIES TY-FRB RECESSED PENDENT SPRINKLER ASSEMBLY (TY323) WITH TWO PIECE 1/2 INCH TOTAL ADJUSTMENT STYLE 20 RECESSED ESCUTCHEON TFPI72 Page 4 of 4 PIN* 77 - XXX - X - XXX SPRINKLER TEMPERATURE FINISH RATINGS SIN 370 5.6K UPRIGHT (1/2 NPT) TY313 371 5.6K PENDENT (112 NPT) TY323 * Use suffix "I" for ISO 7-1 connection; 1 NATURAL BRASS 3 PURE WHITE (RAL9010)** POLYESTER SIGNAL WHITE (RAL9003) POLYESTER 9 CHROME PLATED for example, 77-370-4-175-I - ** Eastern Hemisphere sales only 135 135-F (57-C) 155 155°F(68°C) 175 175°F(79°C) 200 200°F (93°C) 286 286°F :(1:41°C) TABLE A SERIES TY-FRB UPRIGHT AND PENDENT SPRINKLERS PART NUMBER SELECTION Limited Warranty For warranty terms and conditions, visit www.tyco-fire.com. Ordering Procedure Contact your local distributor for avail- ability. When placing an order, indicate the full product name and Part Num- ber (P/N). Sprinkler Assemblies with NPT Thread Connections Specify: Series TY-FRB Upright or Pen- dent (specify) Sprinkler, SIN (specify), K=5.6, Quick Response, (specify) tem- perature rating, (specify) finish, P/N (specify, refer to Table A). Recessed Escutcheon Specify: Style 15 Recessed Escutcheon with (specify*) finish, P/N (specify*) Specify: Style 20 Recessed Escutch- eon with (specify*) finish, P/N (specify*) Refer to Technical Data Sheet TFP770 Sprinkler Wrench Specify: W-Type 6 Sprinkler Wrench, P/N 56-000-6-387 Specify: W-Type 7 Sprinkler Wrench, P/N 56-850-4-001 GLOBAL HEADQUARTERS 11400 Pennbrook Parkway, Lansdale, PA 19446 1 Telephone +1-215-362-0700 Copyright © 2014 Tyco Fire Products, LP. All rights reserved. tqco TEFLON is trademark of The DuPont Corporation. Fire Protection Products tqcci Ffre Protection Products Worldwide Contacts www.tyco-fire.com Ultra K17 - 168 K-factor Upright Control Mode Specific Application Sprinkler Standard Response, 155°F (68°C) & 200°F (93°C) General Description The TYCO 16.8 K-factor, Ultra K17, Standard Response, Upright Control Mode Specific Application Sprinkler (Ref. Figure 1) is an automatic sprinkler of the frangible bulb type. It is intended for use with National Fire Protection Association Control Mode Specific Application" installation criteria for the protection of high piled storage. It may also be utilized as a 16.8 K-factor, upright, standard response "Storage Sprinkler" in accordance with Factory Mutual Loss Prevention Data Sheets. (See FM 2-0 and 8-9 for specific design and installation criteria.) The Ultra K17 Sprinkler can provide a higher level of protection than other standard spray sprinklers and, in some cases, it can provide an economi- cal advantage by eliminating in-rack sprinklers. Applications for the Ultra K17 Upright Control Mode Specific Application Sprinkler are expanding beyond the current "specific application" listings! approvals. For information regard- ing research fire tests which may be acceptable to an authority having juris- diction, please contact the Technical Services Department. IMPORTANT Always refer to Technical Data Sheet TFP700 for the "INSTALLER WARNING" that provides cautions with respect to handling and instal- lation of sprinkler systems and com- ponents. Improper handling and installation can permanently damage a sprinkler system or its compo- nents and cause the sprinkler to fail to operate in a fire situation or cause it to operate prematurely. Page 1 of 4 NOTICE The Ultra K17, Standard Response, Upright Control Mode Specific Applica- tion Sprinkler described herein must be installed and maintained in compliance with this document and with the appli- cable standards of the National Fire Protection Association, in addition to the standards of any authorities having jurisdiction. Failure to do so may impair the performance of these devices. The owner is responsible for main- taining their fire protection system and devices in proper operating con- dition. Contact the installing contrac- tor or product manufacturer with any questions. Sprinkler Identification Number (SIN) TY7153 TY7153 is a redesignation for C7153, G1887, and S8042. MAY 2017 Technical Data Approvals UL and C-UL Listed FM and NYC Approved Specific details for laboratory listings and approvals given in Table A. The approvals apply to the service conditions indicated in the Design Criteria section. Maximum Working Pressure 175 psi (12,1 bar) Pipe Thread Connection 3/4 inch NPT Discharge Coefficient K = 16.8 GPM/p5i112 (241,9 LPM/bar"2) Temperature Ratings Refer to Table A Finish Natural Brass Physical Characteristics Frame ............................Bronze Button ............................Bronze Sealing Assembly. . Beryllium Nickel w/TEFLON Bulb (5 mm).........................Glass Compression Screw ..................Brass Deflector ..............Chrome Plated Brass TFP33O TFP33O Page 2 of 4 SPRINKLER FINISH TYPE TEMPERATURE BULB NATURAL BRASS WITH LIQUID CHROME DEFLECTOR 155°F (68°C) Red 3,4 UPRIGHT K = 16.8 (TY7153) 200°F (93°C) Green 1,2,3,4 NOTES: Listed by Underwriters Laboratories, Inc. (UL Listed) Listed by Underwriters Laboratories, Inc. for use in Canada (C-UL Listed) Approved by Factory Mutual Research Corporation (FM Approved) Approved by the City of New York under MEA 177-03-E TABLE A LABORATORY LISTINGS AND APPROVALS (REFER TO THE DESIGN CRITERIA SECTION) Design Criteria UL and C-UL Listing Requirements The TYCO 16.8 K-factor, Ultra K17, Standard Response, Upright Control Mode Specific Application Sprin- kler may be installed in accordance with NFPA 13 "Control Mode Spe- cific Application Sprinkler (for Storage Use)" requirements to provide ceiling only protection (that is, no in-rack sprinklers) for high piled storage occu- pancies (Solid-piled, palletized and rack storage including but not limited to Class l-IV and Group A plastics) using the criteria from NFPA 13. FM Approval Requirements The TYCO 16.8 K-factor, Ultra K17 (1Y7153) Sprinklers may be installed with the applicable "storage sprinkler" guidelines provided by Factory Mutual. (FM guidelines may differ from UL and C-UL Listing criteria.) Operation The glass bulb contains a fluid that expands when exposed to heat. When the rated temperature is reached, the fluid expands sufficiently to shatter the glass bulb, allowing the sprinkler to activate and flow water. Installation The TYCO 16.8 K-factor, Ultra K17, Standard Response, Upright Control Mode Specific Application Sprinkler must be installed in accordance with this section. General Instructions Do not install any bulb type sprinkler if the bulb is cracked or there is a Toss of liquid from the bulb. With the sprin- kler held horizontal, a small air bubble should be present. The diameter of the air bubble is approximately 1/16 inch (1 16 mm). IL.1tLg Obtain a 3/4 inch NPT sprinkler joint by applying a minimum to maximum torque of 7 to 14 ft.-lbs. (9,5 to 19,0 Nm). Higher levels of torque can distort the sprinkler Inlet with consequent leakage or impairment of the sprinkler. Step 1. With pipe thread sealant applied to the pipe threads, hand tighten the Ultra K17 Sprinkler into the sprinkler fitting. Step 2. Using the W-Type 8 Sprinkler Wrench (Ref. Figure 2) applied to the sprinkler Wrench Flats (Ref. Figure 1), tighten the Ultra K17 Sprinkler into the sprinkler fitting. Care and Maintenance The TYCO 16.8 K-factor, Ultra K17, Standard Response, Upright Control Mode Specific Application Sprinkler must be maintained and serviced in accordance with this section. Before closing a fire protection system main control valve for maintenance work on the fire protection system that it controls, permission to shut down the affected fire protection systems must be obtained from the proper authorities and all personnel who may be affected by this action must be notified. Sprinklers that are found to be leaking or exhibiting visible signs of corrosion must be replaced. Automatic sprinklers must never be painted, plated, coated, or other- wise altered after leaving the factory. Modified sprinklers must be replaced. Sprinklers that have been exposed to corrosive products of combustion, but have not operated, should be replaced if they cannot be completely cleaned by wiping the sprinkler with a cloth or by brushing it with a soft bristle brush. Care must be exercised to avoid damage to the sprinklers - before, during, and after installation. Sprin- klers damaged by dropping, striking, wrench twist/slippage, or the like, must be replaced. Also, replace any sprin- kler that has a cracked bulb or that has lost liquid from its bulb. (Ref. Installa- tion Section). CROSS SECTION UPRIGHT 1/2 12,7 mm) IOMINAL 4AKE-IN 511 WRENCH 3/4° FLAT NPT TFP33O Page 3 of 4 1 - Frame 2 - Button 3 - Sealing Assembly 4 - Bulb 5 - Deflector 6 - Compression Screw * Temperature rating is indicated on deflector. The owner is responsible for the inspec- tion, testing, and maintenance of their fire protection system and devices in compliance with this document, as well as with the applicable standards of the National Fire Protection Asso- ciation (e.g., NFPA 25), in addition to the standards of any other authorities having jurisdiction. Contact the install- ing contractor or product manufacturer with any questions. Automatic sprinkler systems are rec- ommended to be inspected, tested, and maintained by a qualified Inspec- tion Service in accordance with local requirements and/or national codes. FIGURE 1 ULTRA 1(17, 155°F (68°C) & 200°F (93°C), UPRIGHT SPRINKLER (TY7153) Limited Warranty For warranty terms and conditions, visit www.tyco-fire.com. Ordering Procedure Contact your local distributor for avail- ability. When placing an order, indicate the full product name and Part Number (P/N). Sprinkler Assemblies with NPT Thread Connections Specify: Ultra K17 (TY7153), K = 16.8, Upright Control Mode Specific Appli- cation Sprinkler, Standard Response, (specify) temperature rating. Upright (SIN TY7153) 155°F (68°C) ..................51-887-1-155 200'F(93-0) ..................51-887-1-200 Sprinkler Wrench Specify: W-Type 8 Sprinkler Wrench, P/N 56-892-1-001 TFP33O Page 4 of 4 GLOBAL HEADQUARTERS 11400 Pennbrook Parkway, Lansdale, PA 19446 1 Telephone +1-215-362-0700 Copyright © 2017 Tyco Fire Products, LP. All rights reserved. ttjco TEFLON is a registered trademark of DuPont Fire Protection Products 7 Malleable Iron Threaded Pipe Unions Pressure - Temperature Ratings Temperature Pressure Class 150 Class 250 Class 300 (°F) (°C) psi bar psi bar psi bar .200 to 1500 -28.90 to 300 20.7 65.60 500 34.5 600 41.4 2000 93.30 265 18.3 455 31.4 550 37.9 2500 121.10 225 15.5 405 27.9 505 34.8 3000 148.90 185 12.8 360 24.8 460 31.7 3500 176.70 150 10.3 315 21.7 415 28.6 4000 204.40 110 7.6 270 18.6 370 25.5 4500 232.20 75 5.2 225 15.5 325 22.4 5000 260.00 - - 180 12.4 280 19.3 5500 287.80 - - 130 9.0 1 230 15.9 Note: Unions with Copper or Copper Alloy seats are not intended for use where temperature exceedo 5O°F c®Us APPROVED For Listings/Approval Details and Limitations, visit our website @ www.anvilintl.com or contact an Anvil/AnvilStar Sales Representative. Malleable Iron Threaded Fittings Pressure Temperature Ratings Temperature Pressure Class 150 Class 300 __________ Sizes '/4"-1" (6-25 mm) Sizes 114_2 (32-51 mm) Sizes 21/2 -3" (64-76 mm) (°F) (°C) psi bar psi bar psi bar psi bar -200 to 1500 -28.90 to 300 20.7 2,000 65.60 137.9 1,500 103.4 1,000 68.9 2000 93.3 265 18.3 1,785 123.1 1,350 93.1 910 62.7 250° 121.1 225 15.5 1,575 108.6 1,200 82.7 825 56.9 300° 148.9 185 12.8 1,360 93.8 1,050 72.4 735 50.7 3500 176.7 150 10.3 1,150 79.3 900 62.1 650 44.8 400° 204.4 - - 935 64.5 750 51.7 560 38.6 4500 232.2 - - 725 50.0 600 41.4 475 32.8 5000 260.0 - - 510 35.2 450 31.0 1 385 26,5 5500 287.8 - - 300 20.7 300 20.7 1 300 20.7 Anvil Class 150/300 Malleable Iron Fittings conform to ASME B16.3 and Unions conform to ASME B16.39. ALL ELBOWS & TEES 3/ (10 ON) and LARGER ARE 100% GAS TESTED AT A MINIMUM OF 100 PSI. (6.9 bar) www.anvilintl.com 17J TO spr md c®us LISTED I BULL MOOSE TUBE COMPANY APPROVED [] A0 NFSA NFPA UL-VA" I U aim U • ..• *• -- S. V VV • - -V.V.S V S - c®us LISTED APPROVED no z 0 NFSA NFPA 2 Bull Moose Tube® is a customer focused, growth oriented manufacturer and marketer of tubular products, where success is based on a commitment to meeting the customer's perception of quality. Our strength resides in our people working together to satisfy customers and to promote business growth by achieving superior financial performance. www.BullMooseTube.com sales@bullmoosetube.com 800.325.4467 BULL. MOOSE TUBE COMPANY c®us LISTED <> APPROVED NFPA i. ADVANTAGES OF BULL MOOSE TUBE® EDDY PIPE® FAMILY All pipe products are UL Listed (for U.S. and Canada), and have been approved by Factory Mutual. Excellent production and coating capabilities, tighter tolerances, and our unique steel properties make our pipe excellent for roll grooving, welding, threading, and plain end fittings. All products are certified to ASTM Al 35 and A795 Type E, Grade A. Available in specific cut to order lengths from regular mill rollings. More popular sizes available with coating or bare. Ultra Eddy®, Eddy Flow®, Eddylite®, and Eddythread 40® offer cost savings along with superior hydraulics without compromising service life. Sprinkler pipe inventory stocked in Masury, Ohio; Gerald, Missouri; Casa Grande, Arizona; Kent, Washington; and Dallas, Texas. All Bull Moose (black) sprinkler pipe includes our exclusive EDDY GUARD Il® MIC preventative coating. Bull Moose Tube® sprinkler pipe is FBCTM compatible. PRODUCTS Schedule 10 and Schedule 40: FM approved and UL lstcd sprinkler pipe. Lddythrcad 40®: Light threadable Schedule 40 repIrmnt with corrosion resistance ratio of 1.0. Eddylite®: Lightwall threadable with standard outside diameter. Eddy Flow®: Cost effective replacement for Schedule 10. Ultra Eddy®: Lightwall roll groovable pipe. Bull Moose galvanized steel sprinkler pipe is hot dipped galvanized to meet ASTM Al 23 standards. All products are stencilled to meet FM & UL specifications. PROTECTION Eddy Guard Il®: Bull Moose Tube® is producing product that can resist bacteriological growth even after multiple rinse-outs. You know MIC corrosion can impact your installation and your property. Specify Bull Moose Tube® "Eddy Guard Il®" and feel comfortable knowing that you are getting Eddy Pipe® product you trust with the bacteria resistance you need. Eddy Guard Il® is NFPA 13 and NFPA 13R system compatible for use in hybrid systems as well as FM approved. All information contained herein is accurate as known at the time of publication. Bull Moose Tube reserves the right to change product specifications without notice and without incurring obligation. 71 El - dli Mdose Tube'sSchedule: 0d Schedule 4darFM .Approved and UL Ustdd (foU.ST: : rdCaida), entFugh hes . products do not require separate approvals and listings: Bull Moose Tube® madethe decision to have themappro'Jed and listed. Our Schedule.1O and Schedule 40 have a pressure rating of 300 PSI and have been-through the same rigorous testin6 as our other fine pipe proddcts. Schedule 1 0-can' he supplied roll groovedor plain end. Bull MooséTube'sSchedule 10 and Schedule 40pipes are hot dipped galvanized to meet ASTM A123 standards. All 5roduds are stencilled to meet FM & UL specifications. r c®us LISTED <9> APPROVED C;] A ONFSA A,,..dc.a F.,. NFPA s--. 4 SCHEDULE 10 PIPE SPECIFICATIONS NOMINAL PIPE O.D. I.D. WATER FILLED BUNDLE SIZE (IN) (IN) (IN) CRR** WEIGHT/FT WEIGHT SIZE 1 1.315 _1.°9T 15.27_L _.IJ. sLft.__. - .10 _L 41 1/4 42 _1 8ji 2 518___ fl6JI L11/2 - 1.906 '1682 776 2 09 lbs/ft 1 3.053 61 2 1 57 2.641l b7ft 2 1/2 2875 2635 [492 _353 I/ft 1 5893 301 43E3 500 ____260 34 l7ftT1 _7 957 ___i 19 I 4 - 4500 4260 250 L562l/ft 1 11796 19 SCHEDULE 40 PIPE SPECIFICATIONS NOMINAL PIPE O.D. I.D. WATER FILLED BUNDLE SIZE (IN) (IN) (IN) CRR** WEIGHT/FT WEIGHT SIZE _1 -- -1.315 - 1.049 i__00_Ji__1.68 lbs/ft - _J 2.055 70 - 1_1I4 _i6011=30__.918 11/2 1.900 1610 'L 100 2721bs/ftj 3.602 44 - L_2 ILI Q67 J_1 3 '5.114 _ r 21/2* 2875 - 2.468 dL iO0 580 lbs/f 7875 30 J fl3 -7- .500 [ 3068 J flioO_7Ibs/f 10 783J Th 4* 45OC 4O26 100 lO8Oths/ft 16 -- 19 - *Only available in Casa Grande, AZ **Corrosion Resistance Ratio per latest UI Directory Listing PIPE PREPARATION For proper operation, all pipe surfaces should be cleaned prior to installation. In order to provide a leak-tight seat for the gasket, pipe surfaces should be free from indentations and projections from the end of the pipe to the groove. All loose paint, scale, dirt, chips, grease, and rust must be removed prior to installation. Failure to take these important steps may result in improper coupling assembly, causing leakage. Also, check the manufacturer's instructions for the specific fitting used. V For Additional Information Contact (800) 325-4467 www.buIlmoosetube.com Or From Canada Call: (800) 882-4666 sales@buIlmoosetube.com - 1819 Clarkson Road I -- chesterfield, MO Gerald, MO Kent. WA Casa Grande, AZ Dallas TX Masurt OH BULL MOOSE TUBE COMPANY 63017 I FireLock® Outlet-T ® ILPCBI SEE VICTAULIC PUBLICATION 10.01 FOR DETAILS STYLE 922 The Style 922 Outlet-T provides a convenient method of incorporating ½, 3%, and 1/15, 20 and 25mm outlets for directly connecting sprinklers, drop nipples, sprigs, gauges, drains and other outlet products. Available for 1'A through 76.1 mm/32 to 76.1 mm piping systems, Style 922 outlets are UL/ULC Listed, LPCB and FM Approved for branch connections and VdS Approved for direct sprinkler connection only on wet and dry systems. The locating collar engages into the hole prepared in the pipe. When tightened, the assembly compresses the gasket onto the OD of the pipe. The Style 922 Outlet-T is UL/FM rated up to 300 psi/2068 kPa and VdS rated up to 16 bar at the ambient temperatures typical for fire protection systems. Style 922 is suitable for use on standard, lightwall, Schedule 5 and other specialty pipes.* Contact Victaulic for other optional coatings. *Consult Section 10.01 for specific listings/approvals. MATERIAL SPECIFICATIONS Housing: Ductile iron conforming to ASTM A-536, grade 65-45-12. Ductile iron conforming to ASTM A-395, grade 65-45-15, is available upon special request. Gasket: Grade "E" EPDM - Type A (Violet color code). FireLock products have been Listed by Underwriters Laboratories Inc. and Approved by Factory Mutual Research for wet and dry (oil free air) sprinkler services up to the rated working pressure using the Grade "E" Type A Gasket System. Bolts/Nuts: Heat-treated plated carbon steel, trackhead meeting the physical and chemical requirements of ASTM A-449 and physical requirements of ASTM A-183. Housing Coating: Orange enamel (North America, Latin America, Asia Pacific) Red enamel (Europe) JOB/OWNER CONTRACTOR ENGINEER System No. Submitted By Spec Sect Para Location Date Approved www.victaulic.com vIcTAULIC IS REGISTERED TRADEMARK OF vIcTAuLIc COMPANY. © 2009 VIcTAULIC COMPANY. ALL RIGHTS RESERVED. REV ( 4tauIic Norni nal Size I nches/mm Hole Diameter ___________Ernensions - inches/millimeters Approx. Weight Each FPTt -0.00/-0.0 -. 1 1/4 1h 11/16 1.30 1.83 1.10 3.87 2.56 1 x 32 15 30.2 33.0 46.5 27.9 98.3 65.0 0.45 Y~ 1 3A6 1.28 1.83 1.10 3.87 2.56 1.1 20 30.2 32.5 46.5 27.9 98.3 65.0 0.50 1 13A6 1.52 2.18 1.10 3.87 2.56 1.2 25 30.2 38.6 55.4 27.9 98.3 65.0 0.54 11/2 ½ 1 3Ao 1.42 1.95 1.22 4.08 2.56 1.2 x 40 15 30.2 36.1 49.5 31.0 103.6 65.0 0.54 '/4 1 /16 1.40 1.95 1.22 4.08 2.56 1.2 20 30.2 35.6 49.5 31.0 103.6 65.0 0.54 1 1 1.64 2.30 1.22 4.08 2.56 1.3 25 30.2 41.2 58.4 310 1016 65.0 0.59 2 P/t6 1.66 2.19 1.46 4.60 2.56 1.3 x 50 15 30.2 42.2 55.6 37.1 116.8 65.0 0.59 3/4 13/i6 1.64 2.19 1.46 4.60 2.56 1.4 20 30.2 41.7 55.6 37.1 116.8 65.0 0.64 1 1/io 1.88 2.54 1.46 4.60 2.56 1.5 25 30.2 47.8 64.5 1 37.1 116.8 65.0 0.68 2½ ½ 1i16 1.91 2.44 1.71 5.40 2.56 1.6 65 15 30.2 48.5 62.0 43.4 137.2 65.0 0.73 '/4 1/l6 1.89 2.44 1.71 5.40 2.56 1.6 20 30.2 48.0 62,0 43.4 137.2 65.0 0.73 1 l'/16 2.13 2.79 1.71 5.40 2.56 1.6 25 30.2 54.1 1 70.9 43.4 137.2 65.0 0.73 ½ 1/16 1.91 2.44 1.71 5.50 2.56 1.6 76.1 mm X 15 30.2 48.5 62.0 43.4 139.7 650 0.73 1/4 13A6 1.89 2.44 1.71 5.50 2.56 1.6 20 30.2 48.0 62.0 43.4 139.7 65.0 0.73 13A6 2.13 2.79 1.71 5.50 2.56 1.7 25 30.2 54.1 70.9 43.4 139.7 65.0 0.80 DIMENSIONS I-. IPS CARBON STEEL PIPE - HOLE CUT PRODUCTS FireLock® Outlet-I STYLE 922 t Victaulic female threaded products are designed to accommodate standard NPT or BSPT (optional) male pipe threads only. Use of male threaded products with special features, such as probes, dry pen- dent sprinklers, etc., should be verified as suitable for use with this Victaulic product. Failure to verify suitability in advance may result in assembly problems or leakage. *Center of run to engaged pipe end for NPT threads (dimensions are approximate). www.victaulic.com VICTAULIC IS REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2009 VICTAuLIC COMPANY. ALL RIGHTS RESERVED. 10.52 2 JtauIicr REV r, IPS CARBON STEEL PIPE - HOLE CUT PRODUCTS FireLock® Outlet-T STYLE 922 PERFORMANCE Run Size x Outlet Size Equivalent Length of 1 Inch Schedule 40 Steel Pipe (per UL 213, Section 16) (C=120)*, FT 1 1/4 Inches/mm 1 Feet/meters 32 25 11/2 x 1 40 25 21/2 x 1 65 25 bluaii,,1 * Hazen-Williams coefficient of friction is 120 www.victaulic.com VICTAULIC IS REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2009 VICTAULIC COMPANY. ALL RIGHTS RESERVED. X.-A—C —ta _U1 i C~ RFV ( in-52 3 V FireLock® Outlet-I STYLE 922 INSTALLATION Reference should always be made to the 1-100 Victaulic Field Installation Handbook for the product you are installing. Handbooks are included with each shipment of Victaulic products for complete installation and assembly data, and are available in PDF format on our website at www.victaulic.com. WARRANTY Refer to the Warranty section of the current Price List or contact Victaulic for details. NOTE This product shall be manufactured by Victaulic or to Victaulic specifications. All products to be installed in accordance with current Victaulic installation/assembly instructions. Victaulic reserves the right to change product specifications, designs and standard equipment without notice and without incurring obligations. For complete contact information, visit www.victaulic.com 10.52 3355 REV G UPDATED 12/2009 VIcTAuLIc IS A REGISTERED TRADEMARK OF viclAuLic COMPANY. © 2009 VICTAULIC COMPANY. ALL RIGHTS RESERVED. x Aic-ta-uiic~ 10.52 P.O. Box 3365 South El Monte, CA 91733 626.444.0541 Fax 626.444.3887 www. Afcon.org 300 RING HANGER I thru 4 inch pipe LISTED FOR STEEL/CPVC 1/2 & 3/4 inch pipe 5 thru 8 inch pipe SIZE - ROD- 3/8" or 1/2" SIZE - SYSTEM PIPE - 1/2" thru 8" MATERIAL - Carbon Steel, Mu. Galvanized to G-90 spec. LISTING/APPROVAL - USTEn 203-EX 25511"- 8" <13> Approval guide - 1"- 8" OSHPD OPA-0601 See Website. CONFORMS WITH: Federal Specification WW-Fl-171E, Type 10. Manufacturers Standardization Society ANSI/MSS-SP-58 Type 10. MAXIMUM TEMPERATURE - 650°F. FUNCTION - Pipe hanger component of an AFCON hanger. To support steel, CPVC or copper pipe. INSTALLATION - Per NFPA 13, 13R, 13D, these instructions and the CPVC or copper pipe manufacturers instructions. FEATURES - * Sized and listed exclusively for use with #310 Surge Restrainer. * Band edge is offset for EASY pipe insertion. * Custom fit swivel nut for better retention in ring. ORDERING - Part #, pipe size. NFPA 13 PIPE ROD I WT. 5 WT.+250 UL TEST LOAD 1 3/8 30.75 403.75 750 11/4 3/8 43.95 469.75 750 11/2 3/8 54.15 520.75 750 2 3/8 76.95 634.75 750 21/2 3/8 118.35 841.75 850 3 3/8 162.30 1061.50 1050 4 3/8 246.00 1480.00 1500 5 1/2 349.45 1998.75 2000 6 1/2 476.35 2631.75 2650 8 1/2 1 711.00 3805.00 4050 11/09 Restraint SIZE - One size fits 3/4 thru 2 inch AFCON #300 Ring Hanger. 551 P.O. Box 3365 South El Monte, CA 91733 626.444.0541 Fax 626.444.3887 www. Afcon.org 310 RING RESTRAINER S MATERIAL - Carbon Steel. FINISH - Mil. Galvanized. LISTINGS - c us 203-EX 2551 Listed only for use with AFCON #300 Ring Hanger. FUNCTION - To restrain movement of sprinkler pipe toward the knurl nut of the ring hanger. To prevent upward movement of pipe that supplies a pendent sprinkler below the ceiling. INSTALLATION - Per NFPA 13 and CPVC manufacturers instructions on steel, CPVC, or copper pipe. Snap into locking position on swivel nut of AFCON #300 Ring Hanger. SPECIAL NOTE: When installing on CPVC sprinkler system pipe: Verify that all assembly components are cleaned of any surface oil. FEATURES - * Listed only for use with AFCON #300 Ring Hanger. ORDERING - Part # and size. Specific AFCON products are exclusively designed to be compatible ONLY with other AFCON products including parts and fasteners, resulting in a listed sway brace, restrainer or hanger assembly. Be advised the following warranty restriction will apply. DISCLAIMER - AFCON will NOT warrant against the failure of its products when used in combination with other products, parts or systems not manufactured or sold by AFCON. AFCON shall NOT be liable under any circumstances whatsoever for any director indirect, incidental or consequential damages of any kind, including but not limited to toss of business or profit, when non-AFCON products have been, or are used. 1/08 Not less than Wood Flooring 2 nominal width Product Features No pre-drilling required. lip - Not less than Quick to install using the Sammy 3° nominal Nut Driver with an 18V cordless thickness (2-1/2°) ,i i-i drill/driver. river. (depth or side Wood Joist of vertical member) -. - I F - - Saves time from traditional Double Sheebock methods. Ceiling Reduces installation cost Composite I Truss • Consult truss manufacturer for recommended installation point. Made in the U.S.A. *Pre-driffing may be required for GSj 25-380. Too/ av GS0 1 _ H ill ' (72flfl i 4 1 r 25 F ITI 3/81,4 1 i1 iFiri 1 I 3/ TJU-bs 1/4 Fir iFiri 3/ GST6O 1/4 . . Fi 1 - 113 n___ 14925 12.5-1 i - 1 11 F 1 . P4 1 180 (Fr 25 125 25 12~ A #14 Black Nut Driver Part# 8113910 I #14 SW Red Nut Driver art #8114910 Product Features Eliminates distortion of threaded rod. • Saves time from traditional methods. Accommodates up to 3 W x 12 pitch roof. • Reduces installation cost Allows 17° deflection from vertical. • Made in the U.S.A. 1I/7iFir 055' 3/8° 8141957 SH-GST30 1/4x3 1720 (Fir) 1500 1475 25 125 #14 Black Nut Driver SPECIAL NUT DRIVER SYSTEM: The nut drivers were designed with a unique spin-off feature which provides a fast and safe installation each time. When the face of the driver comes into Part# 8113910 contact with the material you are installing into, continue drilling until nut driver spins free. Installation is then complete. Warranty requires the use of the appropriate nut driver for installations. Flour Joist Product Features No pre-drilling required. 'Quick to install using the Sammy Nut Driver with an 18V cordless drill/driver. 'Saves time from traditional methods. Reduces installation cost Made in the U.S.A. Not less than 2' nominal width (1.1/2') up to 3-1/2' pipe; not less than 3' (2-1/2') nominal width 4' & 5' pipe 4 Minimum 2-1/2' from bottom for branch lines. Minimum 3' from bottom for main lines. Exception: This requirement shall not apply to 2' or thicker nailing ships resting on top of steel beams. 114' 8019957 SWG 200 114 x 2' 1725 (Fir) 25 125 378 -8020957 8WGI[0 Lc). vg' v021n7 SW(' 20 1/4 u 2' 1725 (Fir) 1050 25 125 #14 SW Red Nut Driver Part # 8114910 Insert the appropriate nut driver into a 3/8" or 1/2" portable drill. Insert the SAMMYS into the #14 (black) nut driver (p/n 8113910). Drill should be in a vertical position. Push the face of the nut driver tight to the member. When the nut driver spins freely on the SAMMYS, stop drill and remove. The SAMMYS is now ready to receive 1/4", 3/8", 1/2" or metric all thread rod, bolt stock. (The 1/2" requires the #I4SW red nut driver) Note: When installing DSTR, follow the above instructions, then add retainer nut and torque to 20 foot lbs. for maximum pullout in purlin steel. Insert the appropriate nut driver into a 3/8" or 1/2"portable drill. Insert the SAMMYS into the #I4SW (red) nut driver (p/n 8114910). With drill unit in a horizontal position and at a right angle to the structural member, begin installation. When the nut driver spins free on the SAMMYS, stop the drill and remove. The unit is now ready to receive 1/4", 3/8" or metric all thread rod or bolt stock. Note: When installing SWDR, follow the above instructions, then add retainer nut and torque to 20 foot lbs. for maximum pullout in puriin steel. SPECIAL NUT DRIVER SYSTEM: The nut drivers were designed with a unique spin-off feature which provides a fast and safe installation each time. When the face of the driver comes into contact with the material you are installing into, continue drilling until nut driver spins free. Installation is then complete. Warranty requires the use of the appropriate nut driver for installations.