Loading...
HomeMy WebLinkAbout5800 ARMADA DR; ; AS140153; PermitCity of Carlsbad Sprinkler Permit Permit No: AS140153 Job Address: 5800 ARMADA DR Permit Type: SPRINK Parcel No: 2111000600 Lot #: 0 Reference No.: Status: ISSUED Applied 6/25/2014 Approved: 7/1/2014 Issued: 7/1/2014 PC #: Inspector: Project Title: HOMESTREET BANK TI OF EXISTING 3RD FLOOR OFFICE Applicant: PACIFIC FIRE SYSTEMS, INC. 13142 NELSON LANE POWAY, CA 858-722-9865 Owner: LOT 15 CARLSBAD RANCH L L C 5800 ARMADA DR #102 CARLSBAD CA Fees ($) Add'I Fees ($) Total ($) Balance ($) 268 0 268 0 CONTRACTOR'S MATERIAL & TEST CERTIFICATE FOR A BOVEGROUND PIPING PROCEDURE Upon completion of work, inspection and tests shall be made by the contractor's representative and witnessed by an owner's representative. AU defects shall be corrected and system left In service before contractor's personnel finally leave the job. A certificate shag be filled out and signed by both representatives. Copies shall be prepared for approving authorities, owners, and contractor. It is understood the owner's representative's signature In no way prejudices any claim against contractor for faulty material, poor workmanship, or failure to comply with approving authority's requirements or local ordinances. HOMESTREET BANK PROPERTY 5800 ARMADA DR.. SUITE 350, CARLSBAD, CA 92008 PLANS ACCEPTED BY APPROVING AUTHORITY(S) NAMES Carlsbad Fire Department ADDRESS 1635 Faraday Ave.. Carlsbad, CA 92008 INSTALLATION CONFORMS TO ACCEPTED PLANS EQUIPMENT USED IS APPROVED IF NO, EXPLAIN DEVIATIONS YES 0 NO YES 0 NO INSTRUCTIONS HAS PERSON IN CHARGE OF FIRE EQUIPMENT BEEN INSTRUCTED AS TO LOCATION OF CONTROL VALVES AND CARE AND MAINTENANCE OF THIS NEW EQUIPMENT? IF NO, EXPLAIN Building maintenance is in charge of building operations not the individual tennants. [:]YES NO HAVE COPIES OF THE FOLLOWING BEEN LEFT ON THE PREMISES: SYSTEM COMPONENTS INSTRUCTIONS CARE AND MAINTENANCE INSTRUCTIONS NFPA25 0 YES 0 NO DYES 0 NO DYEs 0 NO LOCATION OF SYSTEM SUPPLIES BUILDING: Fire riser is located in an exterior closet on the North side of the building. - MAKE MODEL YEAR OF MANUFACTURE KFACTOR QUANTITY TEMPERATURE RATING SPRINKLERS PIPE AND FITtiNGS Type of Pipe: Schd. 40 Type of Fittings: Cast iron 125# and ALARM VALVE OR FLOW INDICATOR ALARM DEVICE MAXIMUM TIME TO OPERATE THRU TEST CONNECTION TYPE MAKE MIN. T MODEL _SEC. • DRY PIPE OPERATING TEST DRY VALVE O.O.D. MAKE MODEL SERIAL NO. MAKE MODEL SERIAL NO. TIME TO TRIP THRU TEST CONNECTION WATER PRESSURE AIR PRESSURE TRIP POINT AIR PRESSURE TIME WATER REACHED TEST OUTLET ALARM OPERATED PROPERLY MIN. I SEC. PSI PSI PSI MIN. SEC. YES NO Without Q.O.D. 0 0 With O.O.D. 0 0 IF NO, EXPLAIN: *MEASURED FROM TIME INSPECTOR'S TEST CONNECTION OPENED. (OVER) t Cr OPERATION 0 PNEUMATIC 0 ELECTRIC 0 HYDRAULIC. PIPING SUPERVISED 0 YES 0 NO DETECTING MEDIA SUPERVISED 0 YES 0 NO DOES VALVE OPERATE FROM THE MANUAL TRIP AND/OR REMOTE CONTROL STATIONS 0 YES 0 NO DELUGE & PREACTION IS THERE AN ACCESSIBLE FACILITY IN EACH CIRCUIT FOR TESTING DYES 0 NO IF NO, EXPLAIN VALVES DOES EACH CIRCUIT OPERATE DOES EACH CIRCUIT OPERATE MAXIMUM TIME TO MAKE MODEL SUPERVISION LOSS ALARM? VALVE RELEASE? OPERATE RELEASE YES NO YES NO MIN. SEC. 0 HYDROSTATIC: Hydrostatic tests shall be made at not less than 200 psi (13.6 bars) for two hours or 50 psi (3.4 bars) above static pressure in excess of 150 psi TEST (102 bare) for two hours. Differential dry-pipe valve clappers shall be left open during test to prevent damage. All aboveground piping leakage shall be stopped. DESCRIPTION PNEUMATIC: Establish 40 par (2.7 bars) air pressure and measure drop which shall not exceed 1-112 psi (0.1 bars) in 24 hours Test pressure tanks at normal water level and air pressure and measure air pressure drop which shall not exceed 1-112 psi (0.1 bars) in 24 hours. ALL PIPING HYDROSTATICALLY TESTED AT PSI FOR - - HRS. IF NO, STATE REASON: DRY PIPING PNEUMATICALLY TESTED DYES 0 NO EQUIPMENT OPERATES PROPERLY DYES 0 NO DO YOU CERTIFY AS THE SPRINKLER CONTRACTOR THAT ADDITIVES AND CORROSIVE CHEMICALS, SODIUM SILICATE OR DERIVATIVES OF SODIUM SILICATE, BRINE, OR OTHER CORROSIVE CHEMICALS WERE NOT USED FOR TESTING SYSTEMS OR STOPPING LEAKS? TESTS DYES 0 N DRAIN READING OF GAGE LOCATED NEAR WATER SUPPLY TEST RESIDUAL PRESSURE WITH VALVE IN TEST TEST CONNECTION: PSI I CONNECTION OPEN WIDE PSI UNDERGROUND MAIN AND LEAD IN CONNECTIONS TO SYSTEM RISERS FLUSHED BEFORE CONNECTION MADE TO SPRINKLER PIPING OTHER EXPLAIN VERIFIED BY COPY OF THE U FORM NO. 859 0 YES D NO FLUSHED BY INSTALLER OF UNDER- GROUND SPRINKLER PIPING D YES 0 NO BLANK NUMBER USED LOCATIONS: NUMBER REMOVED TESTING 0 GASKETS WELDED PIPING 0 YES 0 NO IF YES... DO YOU CERTIFY AS THE SPRINKLER CONTRACTOR THAT WELDING PROCEDURES COMPLY WITH THE REQUIREMENTS OF AT LEAST AWS 010.9, LEVEL AR-3? DYES 0 NO DO YOU CERTIFY THAT THE WELDING WAS PERFORMED BY WELDERS QUALIFIED IN WELDING COMPLIANCE WITH THE REQUIREMENTS OF AT LEAST AWS DI0.9, LEVEL AR-3? DYES 0 NO DO YOU CERTIFY THAT WELDING WAS CARRIED OUT IN COMPLIANCE WITH A DOCUMENTED QUALITY CONTROL PROCEDURE TO INSURE THAT ALL DISCS ARE RETRIEVED, THAT OPENINGS IN PIPING ARE SMOOTH, THAT SLAG AND OTHER WELDING RESIDUE ARE REMOVED, AND THAT THE INTERNAL DIAMETERS OF PIPING ARE NOT PENETRATED? DYES 0 NO CUTOUTS (DISCS) DO YOU CERTIFY THAT YOU HAVE A CONTROL FEATURE TO ENSURE THAT ALL CUTOUTS (DISCS) ARE RETRIEVED? $'ES D NO HYDRAULIC NAME PLATE PROVIDED IF NO, EXPLAIN: DATA NAMEPLATE DYES 0 NO DATE LEFT IN SERVICE WITH ALL CONTROL VALVES OPEN: 7h 2, 2/+' REMARKS 'I NAME OF SPRINKLER CONTRACTOR: TESTS WITNESSED BY FOR PROPERTY OWNER (SIGNED) TITLE DATE SIGNATURES I I FO 9R (SIGNED) TITLE DATE FOR LOCAL FIRE MARSHAL (SIGNED) I TITLE DATE FOR RESPONSIBLE MANAGING EMPLOYEE (SIGNED) TITLE DATE ADDITIONAL EXPLANATION AND NOTE ' ie- z rrl (BACK)