HomeMy WebLinkAbout2810 CARIBOU CT; ; FPC2020-0006; PermitPERMIT REPORT
(äty of
Carlsbad
Print Date: 05/19/2022
Job Address: 2810 CARIBOU CT, CARLSBAD, CA 92010
Permit Type: FIRE-Construction Commercial Work Class: Fire Alarm
Parcel #: 2091200300 Track #:
Valuation: $4,775,784.50 Lot #:
Occupancy Group: Project U: DEV2018-0203
#of Dwelling Units: Plan #:
Bedrooms: Construction Type:
Bathrooms: Orig. Plan Check U:
Plan Check #:
Project Title: CARLSBAD OAKS LOT 4
Description: CARLSBAD OAKS INNOVATION PARK -LOT 4 SPRINKLER MONITORING
Applicant:
CHULA VISTA ALARM INC
TAYLOR BARDER
6175 PROGRESSIVE DR
SAN DIEGO, CA 92154-6649
(619) 585-9111
Permit No: FPC2020-0006
Status: Closed - Finaled
Applied: 01/09/2020
Issued: 02/04/2020
Finaled Close Out: 05/19/2020
Final Inspection:
INSPECTOR: Salcedo, Felix
Maldonado, Adalmira
FPContractor:
CHULA VISTA ALARM INC
6175 PROGRESSIVE AVE, U STE 400
SAN DIEGO, CA 92154-6647-SAN DIEGO
(619) 585-9111
FEE AMOUNT
FIRE Sprinkler Monitoring $383.00
Total Fees: $383.00 Total Payments To Date: $383.00 Balance Due: $0.00
Fire Department Page 1 of 1
1635 Faraday Avenue, Carlsbad CA 92008-7314 760-602-4665 1 760-602-8561 f I www.carlsbadca.gov
fft,202.o -000,
Potter IPA-60 Fire Alarm System Equipment
NEW EQUIPMENT LIST
Model # Description Mfg. CSFM#
IPA-60 Fire Alarm Control Panel Potter 7165-0328:0500
UD-2000 DACT Module Potter 7300-0328:0515
LE40 10CF Universal Communicator TYCO/DSC 7300-1273:0506
BW-DOCBOX Document Cabinet Mier N/A
PAD100-PSDA Manual Fire Alarm Box Potter 7150-0328:0201
(Manual Pull Station)
PAD 100-PD Photoelectric Smoke Potter 7272-0328:0504
Detector
PAD100-6DB Smoke Detector Base Potter 7300-0328:0502
PAD100-SIM Single Monitor Module Potter 7165-0328:0500
PAD100-MIM Mini Monitor Module Potter 7165-0328:0500
Central Station UL Certificate of Compliance
(E)POTTER
The Symbol of Protection
IPA-60
Fire Alarm Control Panel
Features
60 addresses available on this analog addressable system
Additional system capacity achieved via multi-point SLC modules
99 software zones
NFPA 72 Compliant Smoke Sensitivity Test Built-In
System Operates as Class A or Class B for SLC, P-Link and NACs
5 Amp Power Supply, Expandable to 310 amps
2 NACS, Regulated, Rated at 3 Amps each, expandable to 188
2 Input/Output (I/O) Circuits for system flexibility rated at I Amp each,
ideal for manual release and abort
Strobe Synchronization and System Wide Sync for Potter/AMSECO®,
Gentex®, Cooper Wheelock® and System Sensor® strobes
Dedicated Alarm, Supervisory and Trouble Relays
4,000 Event History Buffer
Cabinet will house up to 18 AU batteries
Optional two line DACT with UD-2000 that can report General, Zone or
Point Information
Built in IP Communicator
Ethernet Port for Programming and Network Connectivity
E-Mail System Status, Reports and Event Information <zE> () • Product includes 5 year warranty.
UUKL Listed for Smoke Control APPROVED LISTED
Description
The IPA-60 is an analog/addressable releasing fire alarm system with a
total system capacity of 60 addresses. Additional capacity on the system
is achieved using multi-point SLC modules. The control panel utilizes
the exclusive Potter protocol that includes a complete line of sensors and
modules. Each SLC may be comprised of any combination of smoke
sensor, heat detectors or modules and allows for a total of 50 ohms of
impedance and may use any wire compliant with the National Electrical
Code (NEC).
The IPA-60 has a 5 Amp power supply with two Notification Appliance
Circuits (NACs) and two Input/Output (I/O) circuits. The NACs are rated at
3 Amps each and the IIOs are rated at I Amp each. Each output is regulated
and power limited. In addition, each output is uniquely programmable and
may be configured for steady signal, strobe synchronization, constant
power, door holder power, or releasing. The strobe synchronization
includes Potter/AMSECO, Gentex, System Sensor and Cooper/Wheelock
and with the exclusive Quadrasync each output may have a unique brand
and all strobes will flash together. The IIOs are designed for inputs such as
manual release stations and abort switches that will not require polling and
react nearly instantaneously.
The IPA-60 is listed for releasing of fire suppression systems. The
software allows cross zones, counting zones, and timers for suppression.
The system is capable of multiple release outputs across multiple hazards.
In addition, the PSN-1000 may be used to extend releasing capability.
The NACs may be expanded using the PSN- 1000 series intelligent power
supplies. Each PSN-1000 adds another 10 Amps of power, 2 additional
input circuits and the IPA-60 will support up to 31 power supplies. The
system will synchronize the strobes system wide. In addition, the PSN-
1000E has space to allow the installation of up to six expansion cards.
The cards mount on a stacker bracket that allows access to all SLC circuit
connections.
Technical Specifications
Dimensions 16"W x 17H x 3 7/"D
AC Mains 3.0 Amps @ 120 VAC 50/60 HZ
2.0 Amps @240 VAC 50/60 HZ
Enclosure 16 gauge cold rolled steel with removable locked door with Lexan viewing window
Standby Current-130 mA
Alarm Current-200 mA
5 Amps power for NACs, I/O, and P-Link
Battery 3 Amps per NAC, regulated
I Amp per 1/0 circuit, regulated
Battery Charger range 8-55 Ah
Battery Charger voltage 27.3 VDC
P-Link maximum current of I Amp
Temperature and 32° to 120° (0°C to 49°C) with a maximum
Humidity Range humidity of 93% non-condensing.
NFPA 12, 12A, 13, 15, 16, 17, 17A, 70,
72, 750, and 2001
ANSI/UL 864 - Local (L), Remote Sta-
tion (RS), Central Station (CS), Propriety
(PPU), Auxiliary (AUX).Type of Service:
Standards Automatic (A), Manual (M), Water flow
(WF) Sprinkler Supervisory (SS) Type of
Signaling: Digital Alarm Communicator
(DAC), March Time (March), Non Coded
(NC), Reverse Polarity (Rev Pot), Other
Technologies (OT)
IBC 2000, 2003, 2006, 2009, 2012
Potter Electric Signal Company, LLC • St. Louis, MO • Phone: 800-325-3936 www.pottersignal.com
8830101-REVG • 9119 PAGE IOF4
(E)POTTER IPA-60
The Symbol of Protection Fire Alarm Control Panel
SLC Loop Accessories
The control panel may be connected with up to 60 addressable devices or modules in any combination. The SLC is not restricted by any special wire
requirements and may be wired with any wire that complies with the NEC.
SLC Loop Devices
Device Description
PAD 100-PD Analog Photo Electric Smoke Detector is a smoke detector with a listed obscuration of 1.02 to 3.83 percent per foot.
PAD 100-PHD Combination Analog Photo Electric Smoke/Heat Detector - a smoke detector with a listed obscuration of 1.02 to 3.83 percent
obscuration and a fixed temperature 135° Fahrenheit heat detector.
PAD 100-1-ID Analog Fixed Temperature Heat Detector that is selectable from 135° F to 185°F.
PAD 100-DUCTR Addressable Duct Smoke Detector with Form C Relay.
PAD 100-DUCT Addressable Duct Smoke Detector.
PADI00-613 6" round base that is mounted to an electrical box and wired for connection of one of the above sensors.
PADI00-413 4" round base that may be mounted to an electrical box and wired for connection to the above sensors.
PAD 100-113 Isolator base that interrupts a short in a SLC and prevents the short from affecting protected devices on the loop.
PADIOO-RB Addressable Relay Base that contains one relay controlled by the SLC. Relay is rated at rated at 2 amps at 30 VDC or 0.5A at 125 VAC.
PAD 100-SB Addressable Sounder Base that contains an addressable sounder module that may be configured for local, group and all call.
PAD100-CD Addressable CO gas detector.
PAD 100-DO Addressable photo electric smoke detector for use in DUCT/DUCTR enclosure.
PAD IOOLFSB Addressable Low Frequency Sounder Base that contains an addressable sounder module that may be configured for local, group and all
call. The LFSB complies with the Low Frequency Signal Requirements (520 Hz)
PADIOO-SPKB Speaker base is a wall or ceiling mount speaker capable of 25 or 70.7 VRMS and is field selectable from 1/8W to 4W.
Modules
Device Description
PAD 100-MIM Micro Input Module provides a small foot print contact module for mounting inside an enclosure.
PAD100-PSSA Single Action Addressable Pull Station.
PAD 100-PSDA Dual Action Addressable Pull Station.
PADIOO-SIM Single Input Module is a standard contact module with an LED that mounts into a 4" square electrical box.
PAD IOO-DIM Dual Input Module is a device that can monitor two distinct inputs with a single device or in a Class A mode.
PAD I00TRT1 Two Relay Two Input module provides two form C relays that are individually controlled by the control panel. Each relay is rated for 2
amps at 30VDC or 0.5 amps at 125 VAC. Also provides two contact inputs.
PAD100-NAC Notification Appliance Circuit module is an addressable remote appliance circuit controlled by the panel.
PAD 100-ZM Zone Module is used to connect conventional 2-wire smoke detectors to the system.
PADIOO-IM Module interrupts a short on the SLC and prevents the short from affecting protected devices on the loop.
PAD00-RM Relay Module that provides one form C relay controlled by the control panel. Relay is rated for 2 amps at 30VDC or 0.5 amps at I25VAC.
PADIOO-LED Module provides a single addressable LED that is controlled by the control panel.
PAD100-SM Speaker Module provides switching for two audio channels.
PAD100-LEDK Addressable LED and key switch that mounts in a single gang box.
PAD 100-DRTS DUCTR Remote Test Switch that mounts in a single gang box and optionally supervised.
PAD100-OROI One Relay One Input Module provides one form C relay and one input. The relay is rated at 2 amps at 30VDC or 0.5 amps at 125 VAC.
Potter Electric Signal Company, LLC St. Louis, MO Phone: 800-325-3936 www.pottersignal.com
8830101-REVG • 9/19 PAGE 2OF4
(E)POTTER IPA-60
The Symbol of Protection Fire Alarm Control Panel
SLC Features
The Potter protocol is a digital protocol with a proven design for
reliability and noise immunity. The system does not require special
cable or conductors for connection of the Signaling Line Circuit
as long as the cable is compliant with NFPA 70 and NFPA 72.
The system allows for Class A or Class B installations as well as
"T-Taps", with a max wiring distance of 10,000 Ft.
Sensor Features
The sensors through the fire alarm control panel provide a real
time status as to the condition of the system. The smoke detector
sensitivity, heat detector temperature level and drift compensation
are all programmable options. The system also allows for a day/night
mode where the panel automatically adjusts the sensitivity depending
on the time of day. To assist in the reduction of false alarms, the
smoke detectors also have a maintenance warning that sends a trouble
signal when a detector is dirty to the point that it can no longer
maintain the programmed sensitivity.
User Interface
The fire alarm control panel has a 2 x 16 LCD display to provide
information to the system status. The keypad has navigation keys
to allow manipulation of the Menu on board the panel. The panel is
shipped standard with the following LEDs:
AC Power - Green
Alarm - Red
Earth Fault - Amber
Supervisory - Amber
Silenced - Amber
Trouble - Amber
Pre-Release - Amber
Release - Red
The common buttons include a Silence, Reset, Acknowledge, and
Drill. All of the buttons are accessible once the locked door is
opened.
P-Link
The IPA-60 has a proprietary communication protocol that
communicates through a RS-485 connection to field devices. Up
to 64 devices may be connected to a single P-Link connection. The
P-Link includes the communication terminals and regulated 24 VDC
connection for the field devices. The field devices may be any of the
following:
RA-6075R —2 x 16 LCD annunciator with a key pad in a locked
metal enclosure.
RA-6500R(F) —4 x 40 LCD annunciator with a key pad in a locked
metal enclosure. Flush mount version available.
LED-16(F) - 16 LED annunciator with common indicators in a
locked metal enclosure. Flush mount version available.
PSN-1000(E) - 10 amp, remote intelligent power supply with
6 NACs, 2 Inputs and a P-Link repeater. This panel is listed in
conjunction with the IPA-60 as releasing circuits.
CA-6075 - Class A convertor that converts the SLC, NACs and
P-Link connection
UD-2000 - UL listed, Dual line telephone alarm communicator
DRV-50 - LED driver expander, used to connect up to 50 LEDs in a
graphic display
FCB-1000 - Fire communication bridge, provides remote mounting
of the Ethernet connection
FIB-1000 - Fiber interface module, used to extend P-Link to multi-
mode fiber (2 required)
RLY-5 - Relay module, provides 5 form C relay contacts rated at 3.0
amps 24VDC/125AC
SPG-1000 - Serial parallel gateway, allows for the connection to a
serial or parallel printer
The FIB-1000, FCB-1000 and the SPG-1000 may be installed in the
stacker bracket or ordered with the optional rack mount enclosure.
MC-1000 Multi-Connect allows up to sixty-three IPA series panels to
share a single reporting technology.
IDC-6 - Initiating device circuit provides 6 programmable inputs
AE-2 - Two card expansion cabinet
AE-8 - Eight card expansion cabinet
AE-14 - Fourteen card expansion cabinet
Ethernet/I.P. Connection
The IPA-60 is shipped standard with an Ethernet connection.
This connection is the programming port and may be connected
to a building Wide Area Network (WAN) or Local Area Network
(LAN). Once connected to the Internet, the panel may be selectively
programmed to e-mail alarm conditions, trouble conditions,
supervisory conditions, test, Event History and detector status. An
e-mail may be sent to the panel and the panel will e-mail the event
history, detector status, configuration file or server status to an
authorized E-mail account. In addition, reminders may be set to send
an e-mail for service, testing or other conditions.
In addition, the Ethernet connection is UL listed as an IP
communicator. The IP communicator is listed to report to the UL
listed Sur-Gard III IP receiver. The IP communicator replaces the
traditional less reliable alarm communicator transmitter that utilized
telephone lines. The IP communicator is an active method of
connection and communication to the monitoring station.
Potter Electric Signal Company, LLC St. Louis, MO Phone: 800-325-3936 www.pottersignal.com
8830101-REVG • 9/19 PAGE 3OF4
,0
RIGHT SIDE
(E)POTTER IPA-60
The Symbol of Protection Fire Alarm Control Panel
Dimensions
0 01
TOP •o DEPTH =3.75"
000R= 16.07"
BACKBOX = 15.77 DEPTH = 3.84
LEFT SIDE
o
BOTTOM
DWG #593-I
Ordering Information
Model Description Stock No.
IPA-60 Fire Alarm Releasing Control Panel 3992714
Replacement Board IPA-60 3992738
Compatible Releasing Devices
Note: For releasing applications please order the Potter EOLD
(3005012) for circuits connected to a releasing solenoid or actuator.
Brand Description
Skinner 732 18BN4U1'1LVN0C112CZ
732 I2BN4TNLVNOC322C2
Victaulic 753-E Series
Mini Max MX 123 & MX200 wl 8876677 & 889323
Viking 11591, 11601, 11602, 13843,& 13844
TLX PA0036
Potter Electric Signal Company, LLC St. Louis, MO • Phone: 800-325-3936 . www.pottersignal.com
8830101-REVG • 9/19 PAGE 4OF4
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
OFFICE OF THE STATE FIRE MARSHAL I Ila
FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM
LISTING SERVICE
LISTING No. 7165-0328:0500 Page 1 of I
CATEGORY: 7165 -- FIRE ALARM CONTROL UNIT (COMMERCIAL)
LISTEE: Potter Electric Signal Co1609 Park 370 Place, Hazelwood, 63042 United States
Contact: Bill Witherspoon (314) 595-6900 Fax (314) 595-6999
Email: biIIwpottersignal.com
DESIGN: Models IPA-60, IPA-1 00, and IPA-4000 fire alarm control units. Automatic, Manual, waterfiow
and sprinkler supervisory type device and local, auxiliary, releasing, remote station (PPU),
proprietary (PPU) and central station (PPU) services. Refer to listee's Installation Instruction
Manual for details. System components:
PAD100-DIM Dual Input Module
PAD 100-LED Addressable LED Module
PAD 100-OROl One Relay-One Input Module
PAD 100-RM Relay Module
PAD 100-SIM Single Input Module
PAD 100 TRTI Two Relay-Two Input Module
PAD 100-ZM Zone Module
PAD 100-IM lolator Module
PAD 100- NAC Notification Appliance Circuit Module
PAD 100-SM Speaker Module
PAD 100-MIM Micro Input Module
PAD 100-LEDK LED Key Switch Module
PAD 100-DRTS Duct Remote Test Switch
PAD 100-SLCE127 Point SLC Expander
MC-1000 Multi-Connect
PAD 100-DUCTR
AE-2 Enclosure
*5LCE127 Loop Expander
RATING: 24 VDC
INSTALLATION: In accordance with listee's printed installation instructions, applicable codes & ordinances
and in a manner acceptable to the authority having jurisdiction.
MARKING: Listee's name, model designation, rating and UL label.
APPROVAL: Listed as fire alarm control units when use with separately listed electrically and functionally
compatible initiating and indicating devices. Refer to listee's Installation Instruction Manual
for details.
01-14-2019 dcc
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed
the test results and/or other data but does not make an independent verification of any claims. This listing is not
an endorsement or recommendation of the item listed. This listing should not be used to verify correct
?V' operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other
Date Issued: July 01, 2019 Listing Expires June 30, 2020
Authorized By: DAVID CASTILLO, Program Coordinator
Fire Engineering Division
(E)POTTER UD-2000
The Symbol of Protection Digital Alarm Communicator
Features
Allows for communication to Monitoring Station
Communicates using SIA-DCS or Ademco Contact ID Protocols
For use with IPA, AFC, and ARC series Addressable Panels and
PFC-4064 Conventional Panel
Status LEDs indicate operation of DACT card
Installs with ease behind main panel LCD display via User
Interface bracket
Device address is set internally to address I
Includes two (2) RJ45 phone cords
Lxt
Description
The UD-2000 Digital Alarm Communicator Transmitter (DACT)
provides for up to two (2) phone lines for communication to a
monitoring station. The UD-2000 communicates using the SIA-
DCS or Ademco Contact ID protocols. When enabled, the DACT
automatically monitors each phone line or voltage and has the
ability to seize the line and connect with a remote receiver. Once the
communication is complete, the DACT will hang up.
The DACT is provided with terminal blocks for each phone line and
two RJ45 cords. In order for the DACT to work properly, it must be
installed on a plain old telephone service (POTS) line or equivalent
deemed by the authority having jurisdiction. The DACT must be
installed before any other equipment to ensure it can seize the phone
line.
Phone lines are high voltage and should be run in a separate conduit
from other circuits. The wire conductors connecting the DACT to the
phone system should be 26 AWG or larger.
Technical Specifications
Operating Voltage 22.0-24.OV
Standby Current I 6mA
Alarm Current 23mA
Max IJD-2000s per panel 1
Dimensions 4"W * 6"H * 1-5/8"D
Operating Tempuratures 0°C - 49°C (32°F- 120°F)
Operating Humidity Range 10% - 93% @ 30°C (86°F)
(non-condensing)
Mounting Options In FACP Behind keypad
Shipping Weight 0.47 lbs
Potter Electric Signal Company, LLC St. Louis, MO Tech Support: 866-956-1211 / Customer Service: 866-572-3005 www.pottersignal.com
8830146- REV B • 6/19 PAGE 10F3
(E)POTTER UD-2000
The Symbol of Protection DigitalAlarm Communicator
Out to Premises Phones
Line In From Telco
RD 1X Phone Jack to UD-2000
Plain Old Telephone (POTS) lines
Tip (Brown) Ring (Grey)
Out to Premises Phones
Line In From Telco
Installation
The UD-2000 DACT is connected to the control panel using the provided four-wire cable connection (P/N 5210514) between P4 and UD-2000 P1. The
connection is power limited and supervised.
Power system down.
Slide the UD-2000 into the card guides located under the User Interface bracket.
Secure the UD-2000 to the User Interface bracket using the provided #6-32x3/8" screw
Install the provided four-wire conductor jumper between UD-2000 P1 and P4.
Potter Electric Signal Company, LLC • St. Louis, MO Tech Support: 866-956-1211 / Customer Service: 866-572-3005 • www.pottersignal.com
8830146- REV B • 6/19 PAGE 2OF3
P Connector
on main board
T
Slides In guides under ,rein buurd.
Screw
RYU
H
-, - a
o DD
a • ODD ci
E) LEI
a
I
0
DWG #593.32A
P Connector on
small platform
control panel
0
cW)
(E)POTTER
The Symbol of Protection
U D-2000
Digital Alarm Communicator
UD-2000 DACT Installation on UD-2000 DACT Installation on
Small Platform Panel Large Platform Panel
Fig 1 Fig 2
Ordering Information
Model Description Stock No.
UD-2000 Digital Alarm Communicator 3992769
Potter Electric Signal Company, LLC • St. Louis, MO • Tech Support: 866-956.1211 / Customer Service: 866-572-3005 • www.pottersignal.com
8830146- REV H • 6/19 PAGE 3OF3
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM
LISTING SERVICE
LISTING No. 7300-0328:0515 Page 1 of 1
CATEGORY: 7300 -- FIRE ALARM CONTROL UNIT ACCESSORIES/MISC. DEVICES
LISTEE: Potter Electric Signal Co1609 Park 370 Place, Hazelwood, 63042 United States
Contact: Bill Witherspoon (314) 595-6900 Fax (314) 595-6999
Email: billw@pottersignal.com
DESIGN: Models UD-1000 and *UD..2000 Digital Alarm Communicator Transmitters (DACT).
Refer to listees data sheet for detailed product description and operational considerations.
INSTALLATION: In accordance with listees printed installation instructions, applicable codes & ordinances
and in a manner acceptable to the authority having jurisdiction.
MARKING: Listees name, model designation, rating and UL label.
APPROVAL: Listed as a digital alarm communicatior for use with listees separately listed fire alarm
control panels. Refer to listee's Installation Instruction Manual for details.
Rev 01 -09-19 gt
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed
the test results and/or other data but does not make an independent verification of any claims. This listing is not
an endorsement or recommendation of the item listed. This listing should not be used to verify correct VA operational requirements or installation criteria. Refer to listees data sheet, installation instructions and/or other
Date Issued: July 01, 2019 Listing Expires June 30, 2020
Authorized By: DAVID CASTILLO, Program Coordinator
Fire Engineering Division
Dec
From Tyco Security Products
Ensure your installations are
future-ready, with LTE
Features That
Make a Difference:
Uses LTE network for high-
speed, reliable and low-cost
communications to an IP
receiver
Automatically switches to 3G
(HSPAJHSPA+) if LIE service is
not available
Compatible with control panels
that communicate using Contact
ID or SIA (300 baud) formats
Full event reporting
4 on-board inputs with NC, NO
or SEOL supervision
4 on-board outputs (open
collector)
Activation and initialization
via website or mobile
interface provided by C24
Communications
View communicator status
directly from your mobile phone
to support on-site or remote
troubleshooting
Compatible with Sur-Gard®
System l-IP/11/111/IV/5 monitoring
station receivers
Includes UL listed power
supply, transformer and 7 Ah
rechargeable battery
UL 864 listed
CSFM listed
Due to rapidly-evolving cellular
technologies, 2G/3G network sunsets
are already on the horizon - with
some having already been completed.
Now's the time to adopt and adapt.
Switch to LTE today, to offer
customers long-lasting investment
protection, and reduce your future
truck rolls.
The LE401 OCF connects the alarm
control panel to the Cellular network
and reports alarm signals directly to
a monitoring station receiver
(Sur-Gard System 1-IP/11/I1 l/IV/5). The
LE401 OCF uses the Cellular network
to ensure low-cost, high-speed and
reliable alarm communications and is
compatible with control panels that
communicate using the Contact ID or
SIA (300 baud) format.
The LE401 OCF is compliant
with the latest requirements for
Communications Methods as per
UL864 and NFPA72 2010, 2013,
and 2016 editions. It can be used
in Fire Monitoring applications as a
single communications technology,
in which case any failure of the
communications path shall be
annunciated at the supervising station
within 5 minutes (NFPA72 2010)
or 1 hour (NFPA72 2013/2016)
of the failure, or it can be used as
part of a multiple communications
technologies (for example in
conjunction with a DACT). When
used as a back-up provision shall
be made to monitor the integrity of
each communication path and failure
of any communications path shall
be annunciated at the supervising
station and at the protected premises
within not more than 24 hours of the
failure.
How it Works
The LE401OCF can be used as
either a Sole Communicator or as a
Backup Communicator. When being
used as a Sole Communicator the
LE401 OCF will replace the phone
line connection on the panel and
as soon as it detects that an alarm
needs to be transmitted it will send
the alarm across the Cellular network
immediately. When being used as a
backup the communicator assesses
the connection to the PSTN phone
line, and only in the event of a phone
line failure will it send all alarm traffic
across the Cellular network to the
monitoring station.
From Tyco Security Products
In instances where the control panel does not support
Contact ID or SIA (300 baud), the LE401 OCF has inputs pre-
set to transmit fire alarm, fire supervisory or system trouble.
Alarm signals are transmitted directly without the need of
a clearinghouse to the IP linecard of the monitoring station
receiver (Sur-Gard® System l-IP/11/111/IV/5).
Activating & Initializing the Unit
Activating and initializing the LE40100F can be done using the
website interface provided by C24 Communications.
No special tools are required.
Mobile Site for Easy Installation and
Comprehensive Maintenance
C24 Communications mobile site (m.connect24.com)
makes the installation a simple process and offers intuitive
trouble-shooting features, cutting down on time and cost
allocated to maintenance.
-0
UL Listing
The LE401OCF is UL listed under File S4019, Listing guide
UOXX, as a sole or backup communicator for Commercial Fire
monitoring installations. When used as a sole communicator
under NFPA72 2010 guidelines the LE401OCF will send
its heartbeat once every 97 seconds ensuring that three
heartbeats will be received at the supervising station within
the 300 second window. When used as a sole communicator
under NFPA72 2013/2016 guidelines the LE401OCF will send
its heartbeat once every 5 minutes to monitor connectivity
with the supervising station within the 1 hour window. When
used as a backup communicator the LE401 OCF will monitor
the other communication method (DACT) and send a daily
test transmission to the supervising station.
CSFM Listing
The LE401 OCF has been approved by the California State Fire
Marshal (CSFM) pursuant to Section 13144.1 of the California
Health and Safety Code.
Ordering Information:
LE4O1OCF-AT .............. Universal Wireless Commercial
Fire Alarm Communicator
Rate Plan
Cost-effective rate plans have been negotiated and are
available through authorized master resellers. Contact your
monitoring station or visit www.connect24.com to find a
master reseller. When used as a sole communicator, the
LE401OCF requires use of the 4M (NFPA72 2010) or 500kB
(NFPA72 2013/2016) rate plans to support the supervision
requirements.
Specifications
Dimensions ................................................ 11-1/2 x 10 x3
(290 mm x 254 mm x 75 mm)
Input Voltage.............................................................120 VAC
Current Draw ..............................................200 mA (standby)
400 mA (transmitting)
Operating Environment ................32° to 120° F (00 to 49° C)
Weight...........................................................12.8 lbs (5.8 kg)
Optional Acessories
Model Description
LIE-i 5ANT 15 ft extension antenna
LTE-25ANT 25 ft extension antenna
LTE-50ANT 50 ft extension antenna
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
OFFICE OF THE STATE FIRE MARSHAL T -
FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM
LISTING SERVICE
LISTING No. 7300-1273:0506 Page 1 of 1
CATEGORY: 7300 -- FIRE ALARM CONTROL UNIT ACCESSORIES/MISC. DEVICES
LISTEE: Tyco Safety Products Canada Ltd.3301 Langstaff Rd., Concord, Ontario L4K 41_2 Canada
Contact: Dan Nita (905) 760-3000 Fax (905) 760-3020
Email: dnita@tycoint.com
DESIGN: Model LE4010CF LTE interface. Refer to listee's data sheet for additional detailed product
description and operational considerations.
RATING: 120 VAC
INSTALLATION: In accordance with listee's printed installation instructions, NFPA 72, applicable codes &
ordinances and in a manner acceptable to the authority having jurisdiction.
MARKING: Listee's name, model number, electrical rating, and UL label.
APPROVAL: Listed as a interface for use with a separately listed fire alarm control unit. Refer to listee's
Installation Instruction Manual for details.
NOTE: Burglary and other non-fire functions were not examined.
O1-11-l8gt
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed
the test results and/or other data but does not make an independent verification of any claims. This listing is not
an endorsement or recommendation of the item listed. This listing should not be used to verify correct
operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other
Date Issued: July 01, 2019 Listing Expires June 30, 2020
Authorized By: DAVID CASTILLO, Program Coordinator
Fire Engineering Division
WA
l;iJa3Taf
BW-DocBox (15"Wx 13"Hx 4"D)
includes:
Three labels:
"Fire Alarm Documents"
"As-B u It Permits"
"Test and Maintenance Documents"
An adjustable bungee allows you to
lit various sizes of binders,
documents, smoke-cans, etc.
A door bracket holds two CDs, three
sets of keys and more documents
A cam lock with two keys
BW-DocBox2 (1I"Wx 15"Hx4"D)
Smaller and more basic model without the door bracket
for CDs and key sets. However, it does have the three
labels, adljLlstable bungee and a lock with two keys.
)on't see the box you want? Customization, special colors, anchor silk-screening of logos are
:all us or visit our website available for quantities of 23 or more. (requires lead time(
800-473-0213 E-mail: infoitmierproducts.com
PADI 00-PSSNPSDA IDPOTTER Addressable Pull Station
The Symbol of Protection Single/Dual Action
Features
Single or Dual Action versions
Durable die-cast construction
Reset key matches the fire alarm control panels
Compatible with IPA Series panels
SLC Class A, Class X & Class B
Product includes a 5 year warranty
LISTED
Description
The PADIOO-PSSA (Single Action) is activated by simply pulling
the white "T" bar handle down. The PAD 100-PSDA (Dual Action)
is activated by lifting the front cover and then pulling the white "T"
bar handle down. Once activated, the "T" bar cannot be reset without
opening the front cover. Opening the front cover will also activate the
pull station. To reset the PAD 100-PS Series, use the Potter WS-93 key
to unlock and open the front cover. Once the cover is open, push the
"T" bar back into the normal position and re-secure the front cover.
Application
The PAD100-PSSAIPSDA is compatible with Potter's IPA series
addressable fire alarm control panels. It is a non-coded addressable
pull station available in either a single or dual action model and installs
on a single gang box or surface mounts using the P32-BB or P32-DBB
(deep) back box.
Technical Specifications
Operating Voltage 24.0 VDC
Max SLC Standby Current 200uA
Max SLC Alarm Current 200uA
32°F - 120°F (0° - 49°C) Environmental Limitations Indoor Only
Dimensions 4.75" H x 3.25" W x 1.75" D
Relative Humidity Range 0 - 93% (non-condensing)
Mounting Options Single gang box or
Potter P32-BB/DBB
Shipping Weight APS-SA- 1.22 lbs.
APS-DA - 1.46 lbs.
Potter Electric Signal Company, LLC • St. Louis, MO • Phone: 800-325-3936 • www.pottersignal.com
8830097 - REV A • 03/16 PAGE 1 OF 2
PAD 100-PSDA
Pull Station Back View and Wiring
Fig
Pra
PAD 100-PSSA
FACTORY WIRED CONTACTS
(E)POTTER PADI
Addressable Pull Station The Symbol of Protection Sin gle/DualAction
Setting the Address
The PAD 100-PS Series uses one SLC address assigned to the device. The address is set using the DIP switch located on the back of the PAD 100-PS
device.
Pull Station Front View
Fig -
Ii FROM FACPOR
PREVIOUS DEVICE
TO NEXT DEVICE
n
Ordering Information
Model Description Stock No.
PADIOO-PSSA Addressable Pull Station, Single Action 3992721
PAD 100-PSDA Addressable Pull Station, Dual Action 3992720
Potter Electric Signal Company, LLC St. Louis, MO Phone: 800-325-3936 • www.pottersignal.com
8830097 - REV A • 03/16 PAGE 2 OF 2
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM
LISTING SERVICE
LISTING No. 7150-0328:0201 Page 1 of I
CATEGORY: 7150-- FIRE ALARM PULL BOXES
LISTEE: Potter Electric Signal Co1609 Park 370 Place, Hazelwood, 63042 United States
Contact: Bill Witherspoon (314) 595-6900 Fax (314) 595-6999
Email: biIIwpottersignaI.com
DESIGN: Models APS-SA, *PAD100pSsA single action and APS-DA, *PADIOOPSDA dual action
addressable pull boxes. Refer to listee's data sheet for additional detailed product description
and operational considerations.
RATING: 22-24 VDC
INSTALLATION: In accordance with listee's printed installation, applicable codes & ordinances and in a
manner acceptable to the authority having jurisdiction.
MARKING: Listee's name, model designation, rating and UL label.
APPROVAL: Listed addressable pull boxes for use with separately listed and compatible fire alarm control
units. For indoor use only. Refer to listee's Installation Instruction Manual for details.
NOTE: These manual pull boxes meet the requirements of UL Standard 38, 1999 Edition with
California amendments.
*Revision 02-10-2017 dcc
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed
the test results and/or other data but does not make an independent verification of any claims. This listing is not
an endorsement or recommendation of the item listed. This listing should not be used to verify correct
operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other
Date Issued: July 01, 2018 Listing Expires June 30, 2019
Authorized By: DAVID CASTILLO, Program Coordinator
Fire Engineering Division
(E)POTTER PADI 00-PD
The Symbol of Protection Photoelectric Smoke Sensor
Features
Low profile, less than 2 inches with the base
Wide selectable sensitivity range of 1.0 to 3.70/o/foot
Sensor communicates sensitivity to control panel
UL listed smoke calibration and sensitivity
Optional locking tab to prevent unwanted removal
Simple DIP switch address setting, no programming tool
required
LED alarm indicator
Product includes a 5 year warranty
F11
LISTED
Description
The Photoelectric Smoke Sensor is a listed Analog Addressable smoke
sensor compatible with fire alarm control panels that utilize the Potter
Addressable Device (PAD) protocol. The PAD 100-PD is a low profile
smoke sensor with a wide sensitivity range. The sensor and base (not
included) are made of a durable plastic in an off-white color to blend
in with the ceiling.
The PAD100-PD has a sensitivity range of 1.0 to 3.7 % per foot and
is UL. The PADIOO-PD features drift compensation and has built in
dirty detector warning as well as. The PADIOO-PD and the control
panel communicate over a proven and robust digital communication
path and the system analyzes the information at the particular device.
The total polling speed is less than five (5) seconds, well under the UL
requirements.
The sensor is compatible with any of the PAD series sensor bases and
simply twists on. The PADIOO-PD is addressed using DIP switches
in the rear of the sensor and can be easily programmed in the field
without special tools.
Setting the Address
Each addressable device on the SLC loop must have a unique address
from 1 to 127 to function properly. The address is set using DIP
switches.
Before connecting a device to the SLC loop, take the following
precautions to prevent potential damage to SLC or device. Verify the
following:
Power to the device is removed
Field wiring is correctly installed.
Field wiring has no open or short circuits.
Technical Specifications
Operating Voltage 24 VDC
Alarm indicator 1 LED
Alarm set-point range 1.0 to 3.7%/ft 3.6-12 %/m
Installation temperature 32to 120 0 F/ 0to49°C range
Operating relative 0% to 93% (Non-condensing) humidity range
Start-up time Max. I sec.
Maximum number of 127 addresses per loop
Maximum number of
lighted indicators in 30
alarm per loop.
Color Eggshell White
Weight (without base) lOig (3.560z)
Dimensions (without Height: 1.35 in (34mm)
base) Diameter: 3.93 in (100 mm)
Potter Electric Signal Company, LLC • St. Louis, MO Phone: 800-325-3936 • www.pottersignal.com
8830108- REV A • 03/16 PAGE IOF2
(E)POTTER PADI 00-PD
The Symbol of Protection Photoelectric Smoke Sensor
Air Velocity Ratings
The PAD IOO-PD has an Open Area of Protection air velocity rating of 0 to 300 feet per minute.
The system has a maximum of 30 LEDs that can be turned on simultaneously. If the system already has 30 LEDs on, the PAD 100-PD will operate even
though the LED may not illuminate.
Operation
The PAD100-PD is an analog addressable sensor that uses one address on the Signaling Line Circuit (SLC) of a compatible fire alarm control panel.
The unit communicates with the control panel as it is polled. The LEDs flash every time the unit is polled and they will latch steady if the unit is in an
active status. The polling LED can be turned off if desired for less conspicuous operation.
The PAD IOO-PD with the PAD 100-4DB or PAD IOO-6DB has a low profile of less than two (2) inches to blend into the surrounding environment. The
sensor includes an insect screen to prevent foreign objects from reaching the chamber and the can be cleaned to restore operation of a dirty detector.
Sensor Sensitivity
The PADIOO-PD and the compatible control panel work in tandem to keep the sensitivity consistent. As the sensor is installed over time, the sensor
compensates for the dirt in the unit until it is out of range. At that time, the panel will indicate a dirty sensor. The sensor will then have to be cleaned
or replaced.
The PAD 100-PD can be programmed to provide a maintenance alert prior to reaching the dirty sensor level which will allow for intervention prior to
the sensor going into trouble. This allows for sensor replacement or cleaning prior to a nuisance trouble occurs.
NOTE: As required by NFPA, do not install the sensors until all construction is complete and the work area has been thoroughly cleaned. If the sensors
have been installed in a construction environment, they should be cleaned or replaced before the system is placed into service.
Spacing
The PAD 100-PD is UL listed with a recommended maximum spacing of 30 feet. Refer to NFPA 72 for specific information regarding detector spacing,
placement and special applications.
Compatible Bases
All bases will mount on a single gang, double gang, octagon, 4" square or mud ring electrical box.
Device Description Stock No.
PAD 100-41313 4" Standard Base 3992731
PAD 100-61313 6" Standard Base 3992732
PAD I00-113 6" base with an isolator module included. 3992730
PAD 100-RB 6" base with one Form-C relay contact. 2A @ 30VDC, 0.5A @ 125 VAC 13992728
PAD 100-SB 6" base with sounder module included. Sound pattern is provided from external source. 3992729
Ordering Information
Model Description I Stock No.
PADIOO-PD Photoelectric Smoke Sensor 13992733
Potter Electric Signal Company, LLC • St. Louis, MO • Phone: 800-325-3936 www.pottersignaI.com
8830108-REVA • 03/16 PAGE 2OF2
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
OFFICE OF THE STATE FIRE MARSHAL -
FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM
LISTING SERVICE
LISTING No. 7272-0328:0504 Page 1 of 1
CATEGORY: 7272 -- SMOKE DETECTOR-SYSTEM TYPE-PHOTOELECTRIC
LISTEE: Potter Electric Signal Co1609 Park 370 Place, Hazelwood, 63042 United States
Contact: Bill Witherspoon (314) 595-6900 Fax (314) 595-6999
Email: billwpottersignal.com
DESIGN: Models PAD100-PD, PAD100-DD and PAD100-PHD photoelectric smoke detector heads.
Model PAD 100-PHD has an intergral heat detector. Refer to Listee's data sheet for detailed
product description and operational considerations.
RATING: 24Vdc
INSTALLATION: In accordance with listee's printed installation instructions, applicable codes and ordinances
and in a manner acceptable to the authority having jurisdiction.
MARKING: Listee's name, model number, electrical rating, and UL label.
APPROVAL: Models PADIOO-PD and PAD100-PHD are listed as photoelectric smoke detector heads for
use with listee's detector base Models PADI00-4DB, PAD100-6DB, PAD100-RB,
PAD1 00-SB (CSFM#7300-0328:502) and Model PAD 100-lB (CSFM#7300-0328:501). Model
PADIOO-DD is listed as a photoelectric smoke detector head for use with Model
PAD100-DUCT (CSFM#3248-0328:0505). Refer to listee's Installation Instruction Manual for
details.
06-21-2017 dcc
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed
the test results and/or other data but does not make an independent verification of any claims. This listing is not
an endorsement or recommendation of the item listed. This listing should not be used to verify correct
operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other
Date Issued: July 01, 2019 Listing Expires June 30, 2020
Authorized By: DAVID CASTILLO, Program Coordinator
Fire Engineering Division
(E)POTTER
The Symbol of Protection
Features
Terminals Marked with Polarity to assist with installation
Duplicate terminals for in and out SLC wiring
Terminals accept 22 to 12 AWG wire sizes
Installs on single gang, double gang, octagon or 4" square box
Locking tab prevents unauthorized detector removal
Product includes 5 year warranty
PADI 00-4DB/6DB
4"/6"Addressable Detector Base
<a>
APPROVED LISTED
Application
The Potter PAD 100-6DB and PAD 100-4DB detector bases are used
to install Potter's addressable smoke and heat detectors. The PADIOO-
6DB will mount on a single gang, double gang, octagon or 4" square
electrical box.
Description
The PADI00-6DB and PAD100-4DB are low-profile, surface mount
bases used with Potter's addressable detectors. The base uses screw-
clamp terminals that accept wire ranging from 22 to 14 AWG. When
installed on recessed electrical boxes the PAD 100-6DB is wide enough
to completely cover the back box and the immediate surrounding area.
The base is equipped with a locking tab to deter unauthorized removal
of the attached detector.
Technical Specifications
Mounting Options Single gang, double gang, octagon, and 4"
square box
Terminals Screw-Clamp Type
Wire Guage 22 to 12 AWG
Diameter: 6.3 in (166 mm). Dimensions Height 0.72 in (18 mm)
Shipping Weight 87g (3.07 oz)
Material Durable Plastic
Potter Electric Signal Company, LLC St. Louis, MO • Phone: 800-325-3936 www.pottersignal.com
PRINTED IN USA 8830107- REV C • 12/18 PAGE I OF 2
(E)POTTER PADI 00-4DB/6DB
The Symbol of Protection 4 "/6 "Addressable Detector Base
Locking Feature
The PADI00-6DB and PAD100-413B include a locking feature that
prevents removal of the detector without using a tool.
To eliminate this feature, break off the locking tab (refer to Figure
1), and then install the detector.
Fig. 1
Break off tab (gray
area) in image to disable
locking feature.
To remove the detector from the base when the locking feature has
been enabled, insert a small screw driver into the slot on the base to
push the plastic tab while simultaneously turning the detector head
counter-clockwise.
Fig. 2
Wiring Diagram
Fig. 3
To FA(
Loop (
Ordering Information
Model Description Stock No.
PAD 100-6DB 6" Sensor Base 3992732
PADI004DB 4" Sensor Base 3992731
Insert small screwdr
into slot to remove
detector from base.
Potter Electric Signal Company, LLC St. Louis, MO . Phone: 800-325-3936 . www.pottersignal.com
PRINTED INUSA 8830107- REV C • 12/18 PAGE 2OF2
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM
LISTING SERVICE
LISTING No. 7300-0328:0502 Page 1 of 1
CATEGORY: 7300 -- FIRE ALARM CONTROL UNIT ACCESSORIES/MISC. DEVICES
LISTEE: Potter Electric Signal Co1609 Park 370 Place, Hazelwood, 63042 United States
Contact: Bill Witherspoon (314) 595-6900 Fax (314) 595-6999
Email: billwpottersignal.com
DESIGN: Models PAD100-4DB, PAD100-6DB, PADIOO-RB and PAD100-SB detector bases. Referto
Listee's data sheet for detailed product description and operational considerations.
RATING: 24Vdc
INSTALLATION: In accordance with listee's printed installation instructions, applicable codes and ordinances
and in a manner acceptable to the authority having jurisdiction.
MARKING: Listee's name, model number, electrical rating, and UL label.
APPROVAL: Listed as a addressable isolator base for use with separately listed compatible fire alarm
control units and listee's separately listed Models PAD-100-PD and PAD-100-PHD
(CSFM#7272-0328:0504), PAD-100-HD (CSFM#7270-0328:0503) and PAD-100-CD
(CSFM#5278-0328:0506) detector heads. Refer to listee's Installation Instruction Manual
for details.
06-21-2017 dcc
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed
the test results and/or other data but does not make an independent verification of any claims. This listing is not
an endorsement or recommendation of the item listed. This listing should not be used to verify correct
operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other
Date Issued: July 01, 2019 Listing Expires June 30, 2020
Authorized By: DAVID CASTILLO, Program Coordinator
Fire Engineering Division
(E)POTTER
PAD 1 00-SI M
The Symbol of Protection Single Input Module
Features
One (1) Class B monitoring input
SLC Class A, Class X & Class B
Mounts in a standard 4" or double gang box
Wiring terminals accessible when mounted in box
All wiring terminals accept 22 to 12 AWG
Product includes a 5 year warranty
NOTE: This addressable module does not support 2-wire smoke
detectors.
Description
The PAD 100-SIM uses one (1) SLC loop addresses when monitoring
one (1) Class B circuit. The module mounts on either a 4" square or
double gang box. The module is capable of monitoring one (1) Class
B circuit. The PAD100-SIM includes one red LED to indicate the
module's status. In normal condition, the LED flashes when the device
is being polled by the control panel. When the input is activated, the
LED will flash at a fast rate.
Application
The PAD100-SIM is compatible with Potter's IPA series addressable
fire alarm control panels. The PAD100-SIM is an interface module
used to monitor dry contact devices such as sprinkler waterfiow, valve
tamper switches, or conventional pull stations. The module is capable
of monitoring one Class B circuit.
Setting the Address
Each addressable SLC device must be assigned an address. The address
is set using the DIP switch located on the PAD 100-SIM.
Before connecting a device to the SLC loop, take the following
precautions to prevent potential damage to the panel or device:
Power to the device is removed.
Field wiring is correctly installed.
Field wiring has no open or short circuits.
to
LISTED
Technical Specifications
Operating Voltage 24.OV
Max SLC Standby 2401iA Current
Max SLC Alarm 240p.A Current
Max Wiring Resistance 1000
of IDC
Max Wiring I iF Capacitance of IDC
EOL Resistor 5.IK0
Operating Temperature
Range 32 to 120°F (0 to 49°C)
Operating Humidity
Range
0 to 93% (non-condensing)
Max no. of Module Per 127 units Loop
Dimensions 4.17" (106mm)L x 4.17"
(106mm)W x 1.14" (29mm)D
Mounting Options Standard 4" Square or
Double Gang Box
Shipping Weight 0.6 lbs
Potter Electric Signal Company, LLC St. Louis, MO • Phone: 800-325-3936 • www.pottersignal.com
8830083- REVA • 03/16 PAGE! OF 2
(E)POTTER PADI 00-SIM
The Symbol of Protection Single Input Module
Installation Using Compatible Electrical Box
Fig I
Wiring Diagram
PADJOO-SIM With Class B Circuit
Fig 2
Jku._1
pwt
.-p
Ordering Information
Model Description I Stock No.
PAD 100-SIM Single Input Module 3992704
Potter Electric Signal Company, LLC St. Louis, MO • Phone: 800-325-3936 . www.pottersignal.com
8830083- REVA • 03/16 PAGE 2 OF 2
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM
LISTING SERVICE
LISTING No. 7165-0328:0500 Page 1 of 1
CATEGORY: 7165-- FIRE ALARM CONTROL UNIT (COMMERCIAL)
LISTEE: Potter Electric Signal Co1609 Park 370 Place, Hazelwood, 63042 United States
Contact: Bill Witherspoon (314) 595-6900 Fax (314) 595-6999
Email: billw@pottersignal.com
DESIGN: Models IPA-60,IPA-100, and IPA-4000 fire alarm control units. Automatic, Manual, waterfiow
and sprinkler supervisory type device and local, auxiliary, releasing, remote station (PPU),
proprietary (PPU) and central station (PPU) services. Refer to listee's Installation Instruction
Manual for details. System components:
PAD100-DIM Dual Input Module
PAD 100-LED Addressable LED Module
PAD 100-OROI One Relay-One Input Module
PAD 100-RM Relay Module
PAD 100-SIM Single Input Module
PAD 100 TRTI Two Relay-Two Input Module
PAD 100-ZM Zone Module
PAD 100-IM lolator Module
PAD 100- NAC Notification Appliance Circuit Module
PAD 100-SM Speaker Module
PAD 100-MIM Micro Input Module
PAD 100-LEDK LED Key Switch Module
PAD 100-DRTS Duct Remote Test Switch
PAD 100-SLCE127 Point SLC Expander
MC-1000 Multi-Connect
PAD 100-DUCTR
AE-2 Enclosure
*SLCE 127 Loop Expander
RATING: 24 VDC
INSTALLATION: In accordance with listee's printed installation instructions, applicable codes & ordinances
and in a manner acceptable to the authority having jurisdiction.
MARKING: Listee's name, model designation, rating and UL label.
APPROVAL: Listed as fire alarm control units when use with separately listed electrically and functionally
compatible initiating and indicating devices. Refer to listee's Installation Instruction Manual
for details.
01-14-2019 dcc
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed
the test results and/or other data but does not make an independent verification of any claims. This listing is not
an endorsement or recommendation of the item listed. This listing should not be used to verify correct
operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other
Date Issued: July 01, 2019 Listing Expires June 30, 2020
Authorized By: DAVID CASTILLO, Program Coordinator
Fire Engineering Division
(E)POTTER
PAD 100-MI M
The Symbol of Protection Micro Input Module
Features
One Class B contact monitoring input
Small size allows mounting in most electrical boxes
SLC Class A, Class X & Class B
6" Pigtail wiring connections
Product includes a 5 year warranty
12
PAD 100-MIM (SLC Module)
II H
LISTED
Description
The PADIOO-MIM is used to monitor the status of an initiating
device(s) that contain a normally open set of dry contacts. The module
is enclosed in a plastic case to protect against inadvertent shorts and
ground faults. The case can be mounted using a single screw. The
PAD 100-MIM has a status indicator LED to indicate communication
and alarm condition. In normal condition, the LED flashes when the
device is being polled by the control panel. When the input is activated,
the LED will flash at a fast rate.
Application
The micro input module (PAD 100-MIM) is compatible with Potter's
IPA series addressable fire alarm control panels. Generally the
PADIOO-MIM is used to monitor pull stations and other devices
where the module is installed in an electrical box or enclosure behind
the device being monitored.
Technical Specifications
Operating Voltage 24.OV
Max SLC Standby 200A Current
Max SLC Alarm 20011A Current
IDC Input Circuit Class B Wiring
Max Wiring Resistance 100g2 of IDC
Max Wiring I gF Capacitance of IDC
EOL Resistor 5.1K9
Operating Temperature
Range 32 to 120°F (0 to 49°C)
Operating Humidity
Range
0 to 93% (non-condensing)
Max no. of Module Per 127 units Loop
Dimensions 1.75" (44.5mm)L x 1.36"
(34.5mm)Wx .43" (llmm)D
Mounting Options 2-1/2" (64mm) deep single-gang box
Shipping Weight 0.3 lbs
Potter Electric Signal Company, LLC • St. Louis, MO • Phone: 800-325-3936 www.pottersignal.com
8830079- REVA • 03/16 PAGE I OF 2
(E)POTTER PAD 100-MI M
The Symbol of Protection Micro Input Module
Setting the Address
Each addressable SLC device must be assigned an address. The address is set using the DIP switch located on the front of the PAD 100-MIM. Before
connecting a device to the SLC loop, take the following precautions to prevent potential damage to the panel or device:
Power to the device is removed.
Field wiring is correctly installed.
Field wiring has no open or short circuits.
Wiring Diagram
Fig I
FROM FACP OR PREVIOUS -
TO NORMALLY OPEN
DEVICE AND TO NEXT DEVICE MONITORED DEVICE
5.1K OHM REQUIRED
Part #3005013
Ordering Information
Model Description Stock No.
PAD 100-MIM Micro Input Module 3992700
Potter Electric Signal Company, LLC St. Louis, MO • Phone: 800-325-3936 • www.pottersignal.com
8830079- REV A • 03/16 PAGE 2 OF 2
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM
LISTING SERVICE
LISTING No. 7165-0328:0500 Page 1 of 1
CATEGORY: 7165-- FIRE ALARM CONTROL UNIT (COMMERCIAL)
LISTEE: Potter Electric Signal Co1609 Park 370 Place, Hazelwood, 63042 United States
Contact: Bill Witherspoon (314) 595-6900 Fax (314) 595-6999
Email: billw@pottersignal.com
DESIGN: Models IPA-60, IPA-100, and IPA-4000 fire alarm control units. Automatic, Manual, waterfiow
and sprinkler supervisory type device and local, auxiliary, releasing, remote station (PPU),
proprietary (PPU) and central station (PPU) services. Refer to listee's Installation Instruction
Manual for details. System components:
PAD 100-DIM Dual Input Module
PAD100-LED Addressable LED Module
PAD 100-OROI One Relay-One Input Module
PAD 100-RM Relay Module
PAD 100-SIM Single Input Module
PAD 100 TRTI Two Relay-Two Input Module
PAD 100-ZM Zone Module
PAD 100-IM lolator Module
PAD 100- NAC Notification Appliance Circuit Module
PAD 100-SM Speaker Module
PAD 100-MIM Micro Input Module
PAD 100-LEDK LED Key Switch Module
PAD 100-DRTS Duct Remote Test Switch
PAD 100-SLCE127 Point SLC Expander
MC-1000 Multi-Connect
PAD 100-DUCTR
AE-2 Enclosure
*5LCE127 Loop Expander
RATING: 24 VDC
INSTALLATION: In accordance with listee's printed installation instructions, applicable codes & ordinances
and in a manner acceptable to the authority having jurisdiction.
MARKING: Listee's name, model designation, rating and UL label.
APPROVAL: Listed as fire alarm control units when use with separately listed electrically and functionally
compatible initiating and indicating devices. Refer to listee's Installation Instruction Manual
for details.
01-14-2019 dcc
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed
the test results and/or other data but does not make an independent verification of any claims. This listing is not
an endorsement or recommendation of the item listed. This listing should not be used to verify correct
operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other
Date Issued: July 01, 2019 Listing Expires June 30, 2020
Authorized By: DAVID CASTILLO, Program Coordinator
Fire Engineering Division
U L
Applicant ID No: 892912-001 I
Service Center No: I I
Expires: 31-MAR-2020 I
CERTIFICATE OF COMPLIANCE
THIS IS TO CERTIFY that the Alarm Service ComDanv indicated below is included by Underwriters
Laboratories Inc. (UL) in its Product Directories as eligible to use the UL Listing Mark in connection with
Certificated Alarm Systems. The only evidence of compliance with UL's requirements is the issuance of a
UL Certificate for the Alarm System and the Certificate is current under UL's Certificate Verification Service.
This Certificate does not apply in any way to the communication channel between the protected property and
any facility that monitors signals from the protected property unless the use of a UL listed or Classified Alarm
Transport Company is specified on the Certificate.
Listed Service From: HUNTINGTON BEACH, CA (HUNTINGTON
Alarm Service Company: (892912-001) Service Center: (892912-001)
GENERAL MONITORING SERVICES INC GENERAL MONITORING SERVICES INC
17951 LYONS CIR 17951 LYONS CIR
HUNTINGTON BEACH CA 92647-7167 HUNTINGTON BEACH CA 92647-7167
The Alarm Service Company is Listed in the following Certificate Service Categories:
File - Vol No. CCN Listing Category
S7894i UUFX [Signal and Fire Alarm Equipment and Services] (Protective Signaling
/ Services) Central Station
***THIS CERTIFICATE EXPIRES ON 31MAR2020***
"LOOK FOR THE UL ALARM SYSTEM CERTIFICATE"
PROJECT: Shell Construction
Carlsbad Oaks Innovation Park
Lot 4
2810 Caribou Court
Carlsbad, CA 92108
SYSTEM: SPRINKLER MONITORING SYSTEM
INSTALLATION
SUBMITTED BY: CVA Security
6175 Progressive Avenue
Suite 400
San Diego, CA 92154
PHONE: (619) 585-9111
DATE SUBMITTED: December 30, 2019
FIRE ALARM SYSTEM RECORD OF COMPLETION
To be completed by the system installation contractor at the time of system acceptance and approval.
PROTECTED PROPERTY INFORMATION
Name of property: Carlsbad Oaks Innovation Park Lot 4 SHELL
Address: 2810 CARIBOU COURT, LOT 4 CARLSBAD CA 92010
Description of property: SHELL BUILDING
Occupancy type: B, 51
Name of property representative: BADIEE DEVELOPMENT
Address: 1261 PROSPECT ST. STE 9 LA JOLLA CA 92037
Phone: 7607170615 Fax: E-mail:
Authority having jurisdiction over this property: CITY OF CARLSBAD
Phone: 7606024663 Fax: E-mail:______________
FIRE ALARM SYSTEM INSTALLATION, SERVICE, AND TESTING INFORMATION
Installation contractor for this equipment: OVA SECURITY
Address: 6175 PROGRESSSIVE AVE STE 400
Phone: 6195859111 Fax: E-mail:.............
Service organization for this equipment: OVA SECURITY
Address: 6175 PROGRESSIVE AVE STE 400
Phone: 6195859111 Fax: E-mail:__________________
Location of as-built drawings: DOC BOX Location of historical test reports: DOC BOX
Location of system operation and maintenance manuals: DOCUMENT BOX
A contract for test and inspection in accordance with NFPA standards is in effect as of
MARCH 2020
Contracted testing company: CVA SECURITY
Address: 6175 PROGRESSIVE AVE STE 400 SAN DIEGO CA 92154
Phone: 6195859111 Fax: __________E-mail:_____________
Contract expires: Contract number: _______Frequency of routine inspections:
TYPE OF FIRE ALARM SYSTEM OR SERVICE
NFPA 72 Chapter Reference of System Type: FIRF SPRINKI FR SYSTFM
Name of organization receiving alarm signals with phone numbers (if applicable):
Alarm: GMS MONITORING Phone: 18886609111
Supervisory: Phone:
Trouble: Phone:
1
40
Entity to which alarms are retransmitted: Phone: -
TYPE OF FIRE ALARM SYSTEM OR SERVICE (CONTINUED)
Method of retransmission of alarms to that organization or location:
If Chapter. 8, note the means of transmission from the protected premises to the central
station:
Digital alarm communicator U McCulloh U Multiplex U 2-way radio U 1-way radio II
N/A
If Chapter 9, note the type of connection: LJ Local energy U Shunt EI N/A
3.1 System Software
Operating system (executive) software revision level: N/A
Site-specific software revision 'date: N/A Revision completed by: N/A
SIGNALING LINE CIRCUITS
Characteristics of signaling line circuits connected to this system (see NFPA 72, Table 6.6.1):
Quantity: I Style: y Class: B
ALARM-INITIATING DEVICES AND CIRCUITS
Characteristics of initiating device circuits connected to this system (see NFPA 72, Table 6.5):
Quantity: 3 Style: Y Class: B
5.1 Manual Initiating Devices
5.1.1 Manual Pull Stations Number of manual pull stations: 1
Type of devices: EAddressable U Conventional U Coded U Transmitter L N/A
5.2 Automatic Initiating Devices
5.2.1 Area Smoke Detectors Number of smoke detectors: 1
Type of coverage:)Q Complete area J Partial area U Nonrequired partial area L N/A
Type of devices: I Addressable U Conventional L Coded U Transmitter 11 N/A
Type of smoke detector sensing technology: CJ Ionization Photoelectric
5.2.2 Duct Smoke Detectors Number of duct smoke detectors:
Type of coverage:
Type of devices: U Addressable U Conventional 0 Coded D Transmitter U N/A
Type of smoke detector sensing technology: U Ionization U Photoelectric
5.2.3 Heat Detectors Number of heat detectors: N/A
Type of coverage: E1 Complete area U Partial area U Nonrequired partial area U N/A
5. ALARM-INITIATING DEVICES AND CIRCUITS (CONTINUED)
2
Type of devices: 121 Addressable U Conventional L Coded U Transmitter U N/A
5.2.4 Sprinkler Waterfiow Detectors Number of waterfiow detectors: I
Type of devices Addressable U Conventional U Coded U Transmitter Q N/A
5.2.5 Alarm Verification Number of devices subject to alarm verification:
Alarm verification on this system is: ID Enabled U Disabled U Set for seconds
SUPERVISORY SIGNAL-INITIATING DEVICES AND CIRCUITS
6.1 Sprinkler System Number of valve supervisory switches: 2
Type of devices: 121 Addressable D Conventional U Coded Q Transmitter U N/A
6.2 Fire PUMP N/A
Type of fire pump: C3 Electric Diesel
Type of fire pumps supervisory devices: U Addressable U Conventional
Coded U Transmitter U N/A
Fire Pump Functions Supervised
Fire pump power Q Fire pump running U Fire pump phase reversal
1 Selector switch not in auto D Engine or control panel trouble U Low fuel
Other:
6.3 Engine-Driven Generator
N/A
Type of generator supervisory devices: D Addressable Q Conventional U Coded
Transmitter Ll N/A
Engine or control panel trouble Generator running
Ll Selector switch not in auto Q Low fuel
Other:
ANNUNCIATORS' N/A
7.1 Annunciator I U Local D Remote
Type: 1J Addressable U Directory Graphic U N/A Location:
7.2 Annunciator 2 U Local Q Remote
Type: U Addressable U Directory U Graphic 11 N/A Location:
7.3 Annunciator 3 L Local U Remote
3
Type: U Addressable U Directory L Graphic U N/A Location:
8. ALARM NOTIFICATION DEVICES AND CIRCUITS
8.1 Emergency Voice Alarm Service N/A
Number of single voice alarm channels: Number of multiple voice alarm channels:
Number of speakers: Number of speaker zones:________________
8.2 Telephone Jacks N/A
Number of telephone jacks installed: Number of telephone handsets stored on site:
Type of telephone system installed: L Electrically powered II Sound powered U N/A
8.3 Nonvoice Audible System
Characteristics of notification device circuits connected to this system (see NFPA 72, Table
6.5):
Quantity: Style: _Class:________________
ALARM NOTIFICATION DEVICES AND CIRCUITS (continued)
8.4 Types and Quantities of Nonvoice Notification Appliances Installed
Bells: With visual device: Horns: With visual device:
Chimes: With visual device: Bells: With visual device:_______
Visual devices without audible devices: Other (describe):
EMERGENCY CONTROL FUNCTIONS ACTIVATED
Hold-open door releasing devices U Smoke management or smoke control
Door unlocking J Elevator recall U Other
SYSTEM POWER SUPPLY
10.1 Primary Power
Nominal voltage 120 Amps 20
Overcurrent protection: Type BREAK Amps20
Location (of primary supply panelboard): HPI CKTI
Disconnecting means location:
10.2 Secondary Power
Location: Type:_______ Nominal voltage: ________ Current rating:
Number of standby batteries: 2 Amp hour rating: 7 AMPS
Location of emergency generator:
Location of fuel storage:
Calculated capacity of secondary power to drive the system
In standby mode: 24HRS In alarm mode: 2HRS
II. RECORD OF SYSTEM INSTALLATION
Fill out after all installation is complete and wiring has been checked for opens, shorts, ground
faults, and improper branching, but before conducting operational acceptance tests.
The system has been installed in accordance with the following NFPA standards: (Note any
or all that apply.)
g1 NFPA 72 6 NFPA 70, National Electrical Code, Article 760
X1 Manufacturer's published instructions U Other (please specify):
System deviations from referenced NFPA standards:
Signed: Printed name: JESUS GOMEZ Date: 4/10/2020
Organization:CVA SECURITY Title: FA lNSTALLEhone: 6195859111
RECORD OF SYSTEM OPERATION
All operational features and functions of this system were tested by or inthe presence of the
signer shown below, on the date shown below, and were found to be operating properly in
accordance with the requirements of:
NFPA 72 NFPA 70, National Electrical Code, Article 760
Manufacturer's published instructions U Other (please specify):
Documentation in accordance with Inspection and Testing Form (Figure 10.6.2.3) is
attached
Signed: ___Printed name: JESUS GOMEZ Date: 04/10/2020
Organization: Title: FA INSTALLERhone:
CERTIFICATIONS AND APPROVALS
13.1 System Installation Contractor
This system as specified herein has been installed and tested according to all NFPA
standards cited herein. -
Signed: nted name: JESUS GOMEZ Date:411012020
Organization: Title: FA INSTALLEhone: 610559111
13.2 System Service Contractor
Wi
This system as specified herein has been installed and tested according to all NFPA
standards cited herein.
Signed: Printed name: JESUS GOMEZ Date: 4/10/2020
Organization: Title: FA INSPECTOhone: 6195859111
13.3 Central Station
This system as specified herein will be monitored according to all NFPA standards cited
herein.
Signed: Printed name: JESUS GOMEZ Date: 4/10/2020
Organization: Title: Phone: 6195859111
13.4 Property Representative
I accept this system as having been installed and tested to its specifications and all NFPA
standards cited herein.
Signed: _______________Printed name: Date:
Organization: Title: Phone:
13.5 Authority Having Jurisdiction
I have witnessed a satisfactory acceptance test of this system and find i: to be installed and
operating properly in accordance with its approved plans and specifications, its approved
sequence of operations, and with all NFPA standards cited herein.
Signed: Printed name: Date:
Organization: Title: Phone: