July 14, 2022
MTGL Project No.: 8139A14
Mr. Keith Pitts MTGL Log No.: 22-0401R1
Ryan Companies US, Inc. MTGL Branch: San Diego
533 South Third Street, Suite 100 Permit No.: GR2021-0021
Minneapolis, MN 55415
Subject: SOILS & ASPHALT COMPACTION REPORT
DGB6 Amazon
3266 Lionshead Ave
Carlsbad, CA 92010
References: 1. Nova Services Inc., (2017) Proposed Tilt-Up Commercial Structure
Carlsbad Raceway Lot 15, Lionshead Avenue- Carlsbad, California,
Nova Project No. 2016433, dated March 14th.
2.AECOM, (2021) Grading Plans for Carlsbad Raceway Lots 13-15 ADJ
06-07 (Lionshead Avenue), Drawing No. 501-3A, approved,
November 19th, 2021.
3.Standard Specifications for Public Works Construction, “Greenbook”
(2018).
Dear Keith Pitts,
This final report presents the results of compaction testing performed for the subject
project. We understand mass grading and initial site grading at the project site were
previously performed under observation by others. Observation and testing for this
project was performed for tenant improvements including pavements, utility trench
backfills, curb & gutters, a generator pad, and loading dock levelers. Compaction
tests were taken on the subject improvements on a periodic basis, as directed by
your field representative during the period of July 1st, 2021, through April 15th, 2022.
A field daily report was prepared by our soil’s technicians for each day of testing and
a copy was provided to the jobsite superintendent.
Field density testing was performed by first probing with T-handle steel probe, and
then using direct transmission nuclear methods, ASTM D6938/D2950. The maximum
density – optimum moisture relationship for the soil was established by our
laboratory in accordance with ASTM D1557 test methods. In-place density tests
indicated relative compaction was achieved in general conformance with the project
specifications and referenced geotechnical report.
Ryan Companies US, Inc. MTGL Project No. 8139A14
DGB6 Amazon MTGL Log No. 22-0401R1
Carlsbad, California July 14, 2022
Page 2
Where density testing indicated failing results, the areas were reworked until passing tests
were achieved.
Approximate locations of in-place density test are presented in Figure 1. Appendix A presents
the results of laboratory testing performed. Appendix B presents the results of field density
tests performed. This report does not constitute certification of compaction of the subject
improvements. We have performed the tests, as previously described, in accordance to
generally accepted soil testing practices. No other warranty, express or implied, is made.
MTGL, Inc. appreciates this opportunity to be of continued service to you on this project.
Should you have any questions regarding this report, please do not hesitate to contact us at
your convenience.
Respectfully Submitted,
MTGL, Inc.
Daniel Richardson, P.E.
Senior Engineer
Attachments: Figure 1 – In-Place Density Test Map
Appendix A – Laboratory Test Results Appendix B – Field Density Test Results
APPENDIX A
LABORATORY TEST RESULTS
Reference: AECOM (2021), Grading Plan for Carlsbad Raceway Lots 13-15 ADJ 06-07 (Lionshead Avenue) Drawing No. 501-3A, approvedNovember 11, 2021.
LEGEND
47 •
[lp ll ll r.r (IJ} /l' IY! fj (Qi fl l!4J
-Density Test Location
(Soil/ Aggregate Base)• AC-6 -Density Test Location
(Asphalt) MTGL Project No.:
8139A14
SATURATED SOILS
REMOVED,
AREAS REWORKED
r--"""""l�,.
r,J.lD�'# l/��"C\t#·m,11-,,,,.,"'"•""'-' ... ""• ,-----------/,� ----=--=··--·
IN-PLACE DENSITY TEST MAP DGB6 Amazon
Carlsbad, CA
SCALE
O'
Date: Author: April, 2022 TC
Note: All locations are approximate.
�t� I
Figure No.
60' 120' 1
Ryan Companies US, Inc MTGL Project No. 8139A14
DGB6 Amazon MTGL Log No. 22-0401R1
Carlsbad, CA July 2022
Page A1
APPENDIX A - LABORATORY TEST RESULTS
Maximum Density – Optimum Moisture Content
Lab
No.
Sample
Date
Sample
Location
Material
Description
Max Density
(pcf)
Opt Moist
(%)
171 3/8/22 Fireline -North Parking Lot Clayey Sand (SC), Tan 120.4 11.9
162 2/28/22 On-Site Existing Base, Gray 122.7 10.7
163 2/28/22 Import Class 2 Recycled Base, Gray 120.2 10.4
451 9/28/21 Import - Superior Class 2 Recycled Base, Gray 118.5 14.5
264 7/1/21 Loading Dock Levelers Sandy Clay (CL), Light Brown 120.3 12.7
Test Method: ASTM D1557 – Maximum Density – Optimum Moisture Content Relationship
Bulk Specific Gravity and Density Of Bituminous Mixtures
Lab
No.
Sample
Date
Sample
Location
Material
Description Bulk Sp Gr.
Unit Weight
(pcf)
231 4/15/22 Parking Lot Behind Warehouse 1/2" HMA Superior Ready Mix 2.4 150.2
Test Method: CTM 308 - Bulk Specific Gravity and Density of Compacted Hot Mix Asphalt
APPENDIX B
FIELD DENSITY TEST RESULTS
Ryan Companies US, Inc MTGL Project No. 8139A14
DGB6 Amazon MTGL Log No. 22-0401R1
Carlsbad, CA July 2022
APPENDIX B - FIELD DENSITY TEST RESULTS
Test
No. Date Location
Test Elev
or Depth
(ft)
Moist
Content
(%)
Dry Density
or Unit
Weight (pcf)
Max
No.
Rel
Comp
(%)
Req'd
Comp
(%)
Test
Type Remarks
Page B1
1 7/1/21 Loading Dock Levelers SG 15.3 110.4 264 92 90 NU
2 7/1/21 Loading Dock Levelers SG 15.1 109.0 264 91 90 NU
3 7/1/21 Loading Dock Levelers SG 16.0 108.3 264 90 90 NU
4 7/1/21 Loading Dock Levelers SG 16.4 108.7 264 90 90 NU
5 7/1/21 Loading Dock Levelers SG 16.1 108.1 264 90 90 NU
6 9/23/21 Electrical Trench for Generator at North Side of Building -1.0 15.7 108.8 264 90 90 NU
7 9/27/21 Generator Pad Northeast Side of Building SG 14.8 110.3 264 92 95 NU FAIL
8 9/27/21 Generator Pad Northeast Side of Building SG 13.3 104.1 264 87 95 NU FAIL
9 9/28/21 Generator Pad Northeast Side of Building SG 12.0 114.5 264 95 95 NU RT 2
10 9/28/21 Generator Pad Northeast Side of Building SG 14.5 115.1 264 96 95 NU RT 3
11 9/28/21 Generator Pad Northeast Side of Building AB 14.3 113.2 451 96 95 NU
12 9/28/21 Generator Pad Northeast Side of Building AB 16.0 114.1 451 96 95 NU
13 1/27/22 3/4" Electrical Conduit Trench at North Parking Lot. (Light poles) -0.5 14.0 114.3 264 95 95 NU
14 1/27/22 3/4" Electrical Conduit Trench at North Parking Lot. (Light poles) -0.5 13.0 115.4 264 96 95 NU
15 1/27/22 3/4" Electrical Conduit Trench at North Parking Lot. (Light poles) -0.5 14.1 114.5 264 95 95 NU
16 1/27/22 3/4" Electrical Conduit Trench at North Parking Lot. (Light poles) -0.5 12.8 114.3 264 95 95 NU
17 2/28/22 Parking Lot- PCC Area SG 14.8 111.5 264 93 95 NU FAIL
18 2/28/22 Parking Lot- PCC Area SG 16.1 110.2 264 92 95 NU FAIL
19 2/28/22 Parking Lot- PCC Area SG 16.0 112.2 264 93 95 NU FAIL
20 3/1/22 Parking Lot- PCC Area SG 13.0 115.0 264 96 95 NU RT 17
21 3/1/22 Parking Lot- PCC Area SG 11.9 116.0 264 96 95 NU RT 18
22 3/1/22 Parking Lot- PCC Area SG 10.8 118.0 264 98 95 NU RT 19
23 3/1/22 Parking Lot- PCC Area AB 14.0 117.7 163 98 95 NU
24 3/1/22 Parking Lot- PCC Area AB 12.6 116.9 163 97 95 NU
25 3/1/22 Parking Lot- PCC Area AB 14.2 117.2 163 98 95 NU
NU - Nuclear Gauge Test (ASTM D6938 / D2950) AB – Aggregate Base
SG - Subgrade AC – Asphalt Concrete
Ryan Companies US, Inc MTGL Project No. 8139A14
DGB6 Amazon MTGL Log No. 22-0401R1
Carlsbad, CA July 2022
APPENDIX B - FIELD DENSITY TEST RESULTS
Test
No. Date Location
Test Elev
or Depth
(ft)
Moist
Content
(%)
Dry Density
or Unit
Weight (pcf)
Max
No.
Rel
Comp
(%)
Req'd
Comp
(%)
Test
Type Remarks
Page B2
26 3/7/22 Irrigation Trenches at North Parking Lot AB 12.6 118.3 162 96 95 NU
27 3/7/22 Irrigation Trenches at North Parking Lot AB 11.5 116.1 451 98 95 NU
28 3/8/22 Fireline Trenches at North Parking Lot FG 22.7 94.3 171 78 95 NU FAIL
29 3/8/22 Fireline Trenches at North Parking Lot FG 23.6 96.7 171 80 95 NU FAIL
30 3/10/22 6" Hydrant Line at East End of Parking SG 16.1 114.8 171 95 95 NU RT 28
31 3/10/22 6" Hydrant Line at East End of Parking -2.0 15.8 109.5 171 91 90 NU RT 29
32 3/10/22 6" Hydrant Line at East End of Parking SG 16.3 110.6 171 92 90 NU
33 3/10/22 6" Hydrant Line at East End of Parking -1.0 16.8 108.5 171 90 90 NU
34 3/10/22 6" Hydrant Line at East End of Parking SG 14.5 114.3 171 95 90 NU
35 3/14/22 Curb & Gutter -North Parking Lot SG 16.8 103.8 451 88 90 NU FAIL- Soils Removed
36 3/14/22 Curb & Gutter -North Parking Lot SG 15.9 105.7 451 89 90 NU
37 4/5/22 Curb & Gutter at North Parking Lot SG 10.9 113.8 163 95 95 NU
38 4/5/22 Curb & Gutter at North Parking Lot SG 12.2 114.1 163 95 95 NU
39 4/5/22 Curb & Gutter at North Parking Lot SG 10.0 115.4 163 96 95 NU
40 4/6/22 Curb & Gutter at Northwestern Corner of Parking Lot AB 14.0 113.3 451 96 95 NU
41 4/6/22 Curb & Gutter at Northwestern Corner of Parking Lot AB 14.3 114.6 451 97 95 NU
42 4/6/22 Curb & Gutter at Northwestern Corner of Parking Lot AB 13.8 112.6 451 95 95 NU
43 4/15/22 Parking Lot Asphalt Behind Warehouse AB 14.0 115.0 451 97 95 NU
44 4/15/22 Parking Lot Asphalt Behind Warehouse AB 13.1 113.2 451 96 95 NU
45 4/15/22 Parking Lot Asphalt Behind Warehouse AB 13.8 112.7 451 95 95 NU
46 4/15/22 Parking Lot Asphalt Behind Warehouse AB 13.6 114.2 451 96 95 NU
47 4/15/22 Parking Lot Asphalt Behind Warehouse AB 14.2 113.3 451 96 95 NU
AC-1 4/15/22 Parking Lot Asphalt Behind Warehouse AC --- 145.0 231 97 95 NU
AC-2 4/15/22 Parking Lot Asphalt Behind Warehouse AC --- 144.4 231 96 95 NU
AC-3 4/15/22 Parking Lot Asphalt Behind Warehouse AC --- 147.5 231 98 95 NU
NU - Nuclear Gauge Test (ASTM D6938 / D2950) AB – Aggregate Base
SG - Subgrade AC – Asphalt Concrete
FAIL- Soils Removed
Ryan Companies US, Inc MTGL Project No. 8139A14
DGB6 Amazon MTGL Log No. 22-0401R1
Carlsbad, CA July 2022
APPENDIX B - FIELD DENSITY TEST RESULTS
Test
No. Date Location
Test Elev
or Depth
(ft)
Moist
Content
(%)
Dry Density
or Unit
Weight (pcf)
Max
No.
Rel
Comp
(%)
Req'd
Comp
(%)
Test
Type Remarks
Page B3
AC-4 4/15/22 Parking Lot Asphalt Behind Warehouse AC --- 146.8 231 98 95 NU
AC-5 4/15/22 Parking Lot Asphalt Behind Warehouse AC --- 143.8 231 96 95 NU
AC-6 4/15/22 Parking Lot Asphalt Behind Warehouse AC --- 143.6 231 96 95 NU
NU - Nuclear Gauge Test (ASTM D6938 / D2950) AB – Aggregate Base
SG - Subgrade AC – Asphalt Concrete