HomeMy WebLinkAbout2625 WADSWORTH ST; ; CBR2021-3094; PermitPrint Date: 10/31/2022 Permit No: CBR2021-3094
Building Permit Finaled
Residential Permit
Job Address:
Permit Type:
Parcel #:
Valuation:
Occupancy Group:
2625 WADSWORTH ST, CARLSBAD, CA 92010-5603
BLDG-Residential
2081904000
$10,400.00
Work Class:
Lot #:
Project #:
Cogen
Status:
Applied:
Issued:
10/13/2021
10/17/2021
Finaled Close Out:10/31/2022
#of Dwelling Units:
Track #:
Plan #:
Closed - Finaled
Plan Check #:
CBR2021-3094Orig. Plan Check #:Bathrooms:
Final Inspection:11/10/2021Bedrooms:Construction Type:
Occupant Load:
Code Edition:
Sprinkled:
INSPECTOR:Alvarado, Tony
SELTSER; ROOF MOUNT PV 8.84KW/26 MODULES (E-REVIEW)Description:
Project Title:
Contractor: SOLAR POWER SUPPLY
1116 QUARRY ST
CORONA, CA 92879-1654
(714) 261-5180
AMOUNTFEE
SB1473 – GREEN BUILDING STATE STANDARDS FEE $1.00
SOLAR–RESIDENTIAL: per kW $268.00
STRONG MOTION – RESIDENTIAL (SMIP)$1.35
Total Fees:$270.35 Total Payments To Date:$270.35 Balance Due:$0.00
Please take NOTICE that approval of your project includes the "Imposition" of fees, dedications, reservations, or other exactions hereafter
collectively referred to as "fees/exaction." You have 90 days from the date this permit was issued to protest imposition of these
fees/exactions. If you protest them, you must follow the protest procedures set forth in Government Code Section 66020(a), and file the protest and any other required information with the City Manager for processing in accordance with Carlsbad Municipal Code Section
3.32.030. Failure to timely follow that procedure will bar any subsequent legal action to attack, review, set aside, void, or annul their
imposition.
You are hereby FURTHER NOTIFIED that your right to protest the specified fees/exactions DOES NOT APPLY to water and sewer connection
fees and capacity changes, nor planning, zoning, grading or other similar application processing or service fees in connection with this
project. NOR DOES IT APPLY to any fees/exactions of which you have previously been given a NOTICE similar to this, or as to which the
statute of limitation has previously otherwise expired.
1635 Faraday Avenue, Carlsbad CA 92008-7314 ï 442-339-2719 ï 760-602-8560 f ï www.carlsbadca.gov
Building Division Page 1 of 1
{"Cityof
Carlsbad
CBR2021-3094
10-13-2021
( City of
Carlsbad
RESIDENTIAL
BUILDING PERMIT
APPLICATION
8-1
Plan Check _______ _
Est. Value
PC Deposit
Date
Job Address SU '3' 0woS Unit: _____ APN: _________ _
CT/Project #: ________________ Lot #:. ____ Vear Built: ________ _
Fire Sprinklers:QvEsQNo Air Conditioning:@ YES Q No Electrica l Panel Upgrade:QYES~NO
BRIEF DESCRIPTION OF WORK :
0 New SF : _____ Living SF,~~-Deck SF, ____ Patio SF, ____ Garage SF __ _
Is this to create an Accessory Dwelling Unit? Q vQ N New Fireplace? Q vQ N, if yes how many? __
D Remodel: SF of affected area -----Is the area a conversion or change of use? Ov ON
D Pool/Spa: ____ SF Additional Gas or Electrical Features? ___________ _
ISZI..Solar: a.~'1 KW, 1'n Modules, Mounted:®oof~round, Tilt:O v®°N, RMA:O v ®N,
Batterv:0 v 0, Panel Upgrade: Qv ~
D Reroof: ________________________________ _
D Plumbing/Mechanical/Electrical
0 Only: Other:
PRIMARY APPLICANT PROPERTY OWNER
Name: Rv0c,:-J £\n v:es Name: AVA /0 s e,L ,~ :e¥?..
Address: , \\t,, G-t10,<'r\l S :\: Address: ·-i-0 i,G Wf>)S)S ,ticAsTu $-t
City:C.,OY"OY)b Stat~: 4', Zip:t\1l7~City:(,A\<L~BO\Q State:~ Zip:O\:Z,QIO
Phone: :J (4 · U I -? I 8 0 Phone: _________________ _
Email: Rer J >' fl, Sa\ 9'.Y'[',oowe:t:SvtnolY-M-tt:mail: _________________ _ r lie, I ,.,, .
DESIGN PROFESSIONAL CONTRACTOR OF RECORD
Name: _______________ Business Name:$oltM' ¥2J1Wt7r: Supr\:v I\. V\ (;
Address:. _______________ Address: .... \ .... \..._\_.C,__,.Q....__v ..... ca...,,c ........ r::➔¥-~--t,__ _______ _
City: _______ State: ___ .Zip: ____ City: fc:roo k'.' ") State: CJ/\, Zip: °1, "2. "6'7V\
Phone: _______________ Phone:_O/ __ &; ___ l -_.._'3-"!3,,...i?_~_g...,o.......,6_0 _________ _
Email: ________________ Email: 1:b ~Q ~~.S o\M:¥'4WffJ u.l? f I ;t • N-et
Architect State License: __________ CSLB License#: lQC) 8 ]l{ 6 Class: (2 J Ct ( 0
Carlsbad Business License# (Required): 0 /o ,' Cl O fl, 7
APPLICANT CERT/FICA TION: I certify that I have read the application and state that the above information is correct and that the
information on the plans is accurate. I agree to comply with all City ordinances and State laws relating to building
construction. / A
NAME (PRINT): RvAy t \ uv::e< SIGN: ~-z~ry"'---1.C.---DATE: U lo /1, I
1635 Faraday Ave Carlsbad, CA 92008 Ph: 760-602-2719 Fax: 1Zo2-~ Email: Building@carlsbadca.gov
REV. 07/21
THIS PAGE REQUIRED AT PERMIT ISSUANCE PLAN CHECK NUMBER: ---------
A BUILDING PERMIT CAN BE ISSUED TO EITHER A STATE LICENSED CONTRACTOR OR A PROPERTY OWNER. IF THE PERSON
SIGNING THIS FORM IS AN AGENT FOR EITHER ENTITY AN AUTHORIZATION FORM OR LETTER IS REQUIRED PRIOR TO
PERM IT ISSUANCE.
(OPTION A): LICENSED CONTRACTOR DECLARATION :
I herebyaffirm under penalty of perjury that I am licensed under provisions of Chapter 9 (commencing with Section 7000) of Division 3
of the Business and Professions Code, and my license is in full force and effect. I alsoaffirm under penalty of perjury one of the
following declarations (CHOOSE ONE}:
Q 1 have and will maintain a certificate of consent to self-insure for workers' compensation provided by Section 3700 of the Labor Code, for the performance of the
work which this permit is issued. Policy No. _____________________________________ _
-OR-
0)1 have and will maintain worker's compensation, as required by Section 3700 of the Labor Code, for the performance of the work for which this permit is issued.
lt;l;y ~orkers' compensation insurance carrier and olicy number are: Insurance Company Name: ~ °'(C O L[h = l~St/4tt"~ W[(l@AN~
Pohcy No. N 6 Exp1rat1on Date: ~<?:>~5..._{.._._6::j'-1'-~-<----.:2-E>~ .... ~.,,_~~-~~~---
-OR-0 Certificate of Exemption: I certify that in the performance of the work for which this permit is issued, I shall not employ any person in any manner so as to become
subject to the workers' compensation Laws of California. WARNING: Failure to secure workers compensation coverage is unlawful and shall subject an employer to
criminal penalties and civil fines up to $100,000.00, in addition the to the cost of compensation, damages as provided for in Section 3706 of the Labor Code,
interest and attorney's fees.
CONSTRUCTION LENDING AGENCY, IF ANY:
I hereby affirm that there is a construction lending agency for the performance of the work this permit is issued (Sec. 3097 (i) Civil Code).
Lender's Name: ____________________ ,Lender's Address: ___________________ _
CONTRACTOR CERT/FICA TION: I certify that I have read the application and state that the above information is correct and that
the information on the plans is accurate. I agree to comply with all City ordinances and State laws relating to building
construction. ~
NAME (PRINT): TvW\, G~¼ SIGNATURE: ~ DATE: KJ /1 $ ( 7-4
Note: If the person signing above is an authorized agent for the contractor provide&teroiauthorization on contractor letterhead.
-OR -
(OPTION B): OWNER-BUILDER DECLARATION:
I hereby affirm that I am exempt from Contractor's License Law for the following reason: Q I, as owner of the property or my employees with wages as their sole compensation, will do the work and the structure is not intended or offered for sale (Sec.
7044, Business and Professions Code: The Contractor's License Law does not apply to an owner of property who builds or improves thereon, and who does such
work himself or through his own employees, provided that such improvements are not intended or offered for sale. If, however, the building or improvement is sold
within one year of completion, the owner-builder will have the burden of proving that he did not build or improve for the purpose of sale).
-OR-O I, as owner of the property, am exclusively contracting with licensed contractors to construct the project (Sec. 7044, Business and Professions Code: The
Contractor's License Law does not apply to an owner of property who builds or improves thereon, and contracts for such projects with contractor(s) licensed
pursuant to the Contractor's License Law).
-OR-O I am exempt under Business and Professions Code Division 3, Chapter 9, Article 3 for this reason:
AND,
D FORM 8-61 "Owner Builder Acknowledgement and Verification Form" is required for any permit issued to a property owner.
By my signature below I acknowledge that, except for my personal residence in which I must have resided for at least one year prior to completion of the
improvements covered by this permit, I cannot legally sell a structure that I have built as an owner-builder if it has not been constructed in its entirety by licensed
contractors./ understand that a capyof the applicable law, Section 7044 of the Business and Professions Cade, is available upon request when this application is
submitted orat the following Web site: http:!/www.leginfo.ca.gov/calaw.html.
OWNER CERTIFICATION: /certify that I have read the applicationandstate that the above information is correct and that the
information on the plans is accurate. /agree to comply with all City ordinances and State laws relating to building
construction.
NAME (PRINT): SIGN: DATE: ----------------------Note: If the person signing above is an authorized agent for the property owner include form B-62 signed by property owner.
1635 Faraday Ave Carlsbad, CA 92008 Ph: 760-602-2719 Fax: 760-602-8558 Email: Building@carlsbadca.gov
2 REV. 07/21
, J
. '
Loyd W. Martin Professional Engineer, Inc.
9924 Universal Boulevard #224-406 Orlando, FL 32819 Tel:1.310.464.1804
Email: loydwmartin@gmail.com www.loydwmartin.com
Structural Calculations for a Roof Mounted Solar Photovoltaic System for:
Adam Seltser Residence
2625 Wadsworth St.,
Carlsbad, CA 92010
Applicable Codes:
2019 Ca lifornia Building Code , 20 19 California Electric Code,
2019 California Mechanical Code, American Society of Civil Engin eers
Standard ASCE 7-16 Minimum Design Loads for Buildings and Other
Structures, American Wood Council 2018 National Design Specification
for Wood Construction, Local Municipal Code , and all other codes which
are adopted by reference or enacted by law.
Assumed Design Parameters:
The existing structure has been built under a building permit and is in its
original condition. The existing roof structure is capable of its code
required live load and the ability of the roof structure to support live loads
has not been substantially reduced by the age of the structure , termites or
mold, or unauthorized modifications to the existing structure. Solar Energy
Contractor shall make an in spection of the existing roof framing system
prior to installation of the roof mounted solar energy system to verify that
the existing roof is capable of supporting minimum roof live loads.
Assumed Design Parameters:
All 2x members are grade Douglas Fir #2 or better
All 4X members are grade Douglas Fir #1 or better
All Roof Connectors are Simpson Strong-Tie or Equal
All Concrete Foundations are re = 2500 psi or stronger
Original Structure was built to the Type-V Wood Framed Standards
of the Applicable Building Code at the time of Construction.
Sht # 1 of 7
2021-4025 Solar Deployed Adam Seltser Residence Date: September 23, 2021
' I
Loyd W. Martin Professional Engineer, Inc.
9924 Universal Boulevard #224-406 Orlando, FL 32819 Tel:1.310.464.1804
Email: loydwmartin@gmail.com www.loydwmartin.com
Note to Building Official:
Based upon a review of the proposed plans and information, the
existing roof framing system is capable of safely supporting the additional
loads caused by the new solar photovoltaic energy system. The contractor
shall field verify that the existing roof structure is in its original permited
condition and verify that it can support the normal code required roof live
loads. Attached in this package are several calculations showing that the roof
members can support the additional weight of the solar array.
Furthermore, an analysis of the solar array's support for wind forces and a
seismic analysis of the existing structure are also included.
Check Existing 2x6 Roof Rafters @ 24" O.C.: *
W;;::JZZZZZZZZZZZZZZZZZZZZZZZI
w = 30 psf x 2 ft. = 60 plf R1 R2
7.7'
Total load on rafter = 60 plf x 7. 7 ft. = 462 lbs
*Note: Contractor to Field Verify Framing
Sht # 2 of 7
2021-4025 Solar Deployed Adam Seltser Residence Date: September 23, 2021
Loyd W. Martin Professional Engineer, Inc.
9924 Universal Boulevard #224-406 Orlando, FL 32819 Tel:1.310.464.1804
Email : loydwmartin@gmail.com www.loydwmartin .com
Check Existing 2x6 Roof Rafters @ 24" O.C.:
p
w LL ~ II I 1111111111 I 111111111111111111 I 111 I 11111
W oL tZZZZZZZZZZZZZZZZZZZZZZZZZZZZZ2l
w oL + LL = 30 psf x 2 ft. = 60 plf
R1 R2
7.7'
2.2' 5.5'
Total load on rafter = 60 plf X 5.5 + 28 plf X 2.2 ft + ( 6' X 2. 75' X 3 psf X 1 )
= 441 lbs < 462 lbs OK
Check attachment of Support to Existing Structure for Wind Uplift
CHECK SOLAR STRUCTURE ATTACHMENTS PER ASCE 7-16 WIND LOADS ON BU ILDING
APPURTENANCES AND OTHER STRUCTURES Section 29.4.4 THEREFORE CHECK
ATTACHMENT FOR TYPICAL CRITICAL LOAD WHICH IS THE EDGE ZONE -ZONE 2.
NOTE: PER DEFINITION ON SHEETS 246 & 247 OF ASCE 7-16 EFFECTIVE WIND AREA:
"FOR ROOFTOP SOLAR ARRAYS, THE EFFECTIVE WIND AREA IN FIG. 29.4-7 IS
EQUAL TO THE TRIBUTARY AREA FOR THE STRUCTURAL ELEMENT BEING
CONSIDERED, EXCEPT THAT THE WIDTH OF THE EFFECTIVE WIND AREA NEED NOT
BE LESS THAN ONE-THIRD ITS LENGTH."
EFFECTIVE AREA = 15 SQ FT
Sht # 3 of 7
2021-4025 Solar Deployed Adam Seltser Residence Date: September 23, 2021
Loyd W. Martin Professional Engineer, Inc.
9924 Universal Boulevard #224-406 Orlando, FL 32819 Tel:1.310.464.1804
Email: loydwmartin@gmail.com www.loydwmartin.com
Check attachment of Support to Existing Structure for Wind Uplift -Cont'd
Tributary Area to Each Solar Mount = 6 ft. x 2.75 ft.= 16.5 sq. ft. (Max )
Calculate Design Wind Pressure at each support (Wind Speed 110 mph Exposure C):
P = qh ( GCp) (YE) ( Ya)
qh = 0.00256 KzKz,KdKe \/2
Note:
Eq'n 29.4-7 ASCE 7-16
Eq'n 26.10-1 ASCE 7-16
Kz = velocity pressure coefficient Section 29.1 0.1 ASCE 7-16
Kz = 0.9 (Exposure C, Height = 20 ft or less)
Kz,= Topographical Factor= 1.0
Kd = Wind Directionality Factor = 0.85
Ka = Ground Elevation Factor = 1.0
V = 110 mph; VAss = 85 mph Table 1609.3.1 2019 CBC
qh = 0.00256 (0.9) (1.0) (0.85) (1.0) (8 5)2
qh = 14.15 psf
GCP = -2 .0 (Zone 2 ; Effective Area = 15 sq. ft. )
y E = Exposure Factor= 1.5
Ya = Solar Array Pressure Equalization Factor = 0. 7
p = qh( GCp)(YE)(Ya)
p = 14.15 psf (-2.0) (1 .5) (0.7) = 29.7 psf
Fig. 29.4-8 ASCE 7-16
Nominal (Unfactored) Uplift at each support = 29.7 psf x 16.5 sq. ft.= 490 lbs
Note: Section 2.4.1 of ASCE 7-16, Basic Load Combinations for All owable Stress
Design. Note: Applicable Load Combination #5 (D + 0.6W)
Dead Load = 3
Wind Load= 29.7
2021-4025 Solar Deployed Adam Seltser Resid ence
Sht # 4 of 7
Date: September 23, 202 1
. .
Loyd W. Martin Professional Engineer, Inc.
9924 Universal Boulevard #224-406 Orl and o, FL 32819 Tel:1 .3 10.464.1804
Email : loydwmartin @g mail.com www.loydwm artin .com
Check attachment of Support to Existing Structure for Wind Uplift -Cont'd
Design of (Factored) Load at each support:
3 psf + ( 0.6 x 29.7 psf ) = 20.82 psf
where:
Y = Distance between 2 lag screws
Y = 1.7"
Y' = Moment arm to 1st lag screw
Y' =8.9"
Moment due to load = ( 20.82 psf x 16.5 sq. ft. ) x 8.9 inches
= 3,057 in -lb
Load to lag screws = 3,057 in -lb / 1.7 in
= 1,798 lbs
Determine allowable load per 5/1 6" lag screw w/ 3.25" embedment into wood below
according to the 2018 NOS.
W' = W x Cd x Ct Table 10.3.1 2018 NOS
where:
W = 266 lbs I in. of embedment per Table 12.2a
Cd = 1.6 per Table 2.3.2 of 2018 NOS
Ct = 1.0 per Table 10.3.4 of 2018 NOS
W' = 266 lbs/ in. x 3.25 in. x 1.6 x 1.0 = 1,383 lbs === 1,798 lbs OK
OK. Use Tile Hooks with (2) 5/1 6" x 3.5" Lag Screws
with 3.25" min. embedment into wood, at 72" O.C. max,
as per Plans to Manufacturer's instructions.
2021 -4025 Solar Deployed Adam Seltser Resid ence
Sht # 5 of 7
Date: September 23, 2021
Loyd W. Martin Professional Engineer, Inc.
9924 Universa l Bo ulevard #224-406 Orlando, FL 32819 Tel:1.310.464.1804
Email : loydwmartin@gmail.com www.loydwmartin.com
Check Seismic load due to added dead load of photovoltaic system.
Determine Seism ic Weight of Existing Bu ilding:
Effective Existing Seismic Weight
= Approximately 3,100 Sq. ft. Area of (E) Buil ding
Approximate
Effective = 3,100 sq. ft. x 30 psf ave. = 93,000 LBS
Seismic Weight
DETERMINE BASE SHEAR
V =Cs W EQ'N 12.8-1 ASCE 7-16
Cs= (7.5] EQ'N 12.8-2 ASCE 7-16
R = THE RESPONSE MODIFICATION FACTOR IN TABLE 12.2-1
R = 6.5
18 = 1.0
WOOD SHEAR WALLS
IMPORTANCE FACTOR
Sos = 2/3 x SMs EQ'N 11.4-3 ASCE 7-16
SMs = FA x Ss EQ'N 11.4-1 ASCE 7-16
SMs = 1.2 X 1.5 = 1.8
Sos = 2/3 x 1.8 = 1.2
1.2 [6;5] =0.185 Cs = EQ'N 12.8-2 ASCE 7-16
2021-4025 Solar Deployed Adam Seltser Residence
Sht # 6.2 of 7
Date: September 23, 2021
Loyd W. Martin Professional Engineer, Inc.
9924 Un iversal Boulevard #224-406 Orlando, FL 32819 Tel:1.310.464.1804
Ema il: loydwmartin@gmail.com www.loydwmartin.com
EXISTING BASE SHEAR
V = 0.185 x 93,000 LBS = 17,205 LBS
DETERMINE NEW BASE SHEAR
EQ'N 12.8-1 ASCE 7-16
Determine Seismic Weight of Bu ilding with Solar Array:
EXISTING
SEISMIC
W EIGHT
NEW SOLAR
ARRAY
NEW
SEISMIC
WEIGHT
= 93,000 LBS
= 3 PSF x 26 PANELS x 3.3' x 5.5' = 1,416 LBS
= 93,000 LBS + 1,41 6 LBS = 94,4 16 LBS
THEREFORE NEW BA SE SHEAR:
V = 0.185 x 94,416 LBS = 17,467 LBS EQ'N 12.8-1 ASCE 7-16
% CHANGE = __ 1_7_,4_6_7_L_B_S_-_17_,2_0_5_L_B_S __
17,205 LBS x 100 =1.5 %<10% OK
OK. PER ASCE 7-16 SECTION 11.B.3 ALTERATIONS
EXI STING LATERAL FORCE RESISTIN G SYSTEM IS EXEMPT
FROM ANALYSIS SIN CE NEW SEISMIC FORCE IS
LESS THAN 10% GREATER THAN EXI STING SE ISMIC FORCE.
"Alterations are permitted to be made to any structure without requiring the
existing structure to comply with this standard provided the alterations comply
with the requirements for a new structure. Alterations that increase the
seismic force in any existing structural element by more than 10 percent or
decrease the design strength of any existing structural element to resist
seismic forces by more than 10 percent shall not be permitted unless the
entire seismic force-resisting system is determined to comply with this
standard for a new structure."
End of Calculations
2021-4025 Solar Deployed Adam Seltser Residence
Sht # 7 of 7
Date: September 23, 2021
Building Permit Inspection History Finaled
PERMIT INSPECTION HISTORY for (CBR2021-3094)
BLDG-Residential 10/13/2021Application Date:Permit Type:Owner:TRUST SELTSER FAMILY TRUST
12-17-18
Cogen 10/17/2021Work Class:Issue Date:Subdivision:
05/09/2022Expiration Date:Status:
IVR Number: 36435
Closed - Finaled 2625 WADSWORTH ST
CARLSBAD, CA 92010-5603
Address:
Scheduled
Date
Inspection Type Inspection No. Inspection
Status
Primary Inspector Reinspection InspectionActual
Start Date
11/10/2021 11/10/2021 BLDG-35 Solar Panel 170529-2021 Passed Tony Alvarado Complete
COMMENTS PassedChecklist Item
BLDG-Building Deficiency November 10, 2021: (Virtual inspection).
No PV Solar-building Deficiencies
1. New Low profile roof mounted PV solar
system, per engineered electrical
plan-approved.
2. Meter number-(6728890)-SDGE
Released.
Yes
BLDG-Final Inspection 170528-2021 Passed Tony Alvarado Complete
COMMENTS PassedChecklist Item
BLDG-Structural Final November 10, 2021: (Virtual inspection).
No PV Solar-building Deficiencies
1. New Low profile roof mounted PV solar
system, per engineered electrical
plan-approved.
2. Meter number-(6728890)-SDGE
Released.
Yes
BLDG-Electrical Final November 10, 2021: (Virtual inspection).
No PV Solar-building Deficiencies
1. New Low profile roof mounted PV solar
system, per engineered electrical
plan-approved.
2. Meter number-(6728890)-SDGE
Released.
Yes
Wednesday, November 10, 2021 Page 1 of 1