HomeMy WebLinkAbout140 ACACIA AVE; # 5; CBR2020-2762; PermitPrint Date: 11/28/2022 Permit No: CBR2020-2762
Building Permit Finaled
Residential Permit
Job Address:
Permit Type:
Parcel #:
Valuation:
Occupancy Group:
140 ACACIA AVE, # 5, CARLSBAD, CA 92008-3204
BLDG-Residential
2042332400
$0.00
Work Class:
Lot #:
Project #:
P/M/E
Status:
Applied:
Issued:
10/27/2020
10/28/2020
Finaled Close Out:11/28/2022
#of Dwelling Units:
Track #:
Plan #:
Closed - Finaled
Plan Check #:
Orig. Plan Check #:Bathrooms:
Final Inspection:04/01/2022Bedrooms:Construction Type:
Occupant Load:
Code Edition:
Sprinkled:
INSPECTOR:Burnette, Paul
Alvarado, Tony
RE-PIPE // FRAMING & DRYWALL REPAIR // PLUMBING & ELECTRICAL // REPLACE 1 WINDOW TO MEET CURRENT CODE
(SUBJECT TO FIELD VERIFICATION OF SCOPE) (E-REVIEW)
Description:
Project Title:
Property Owner:
CO-OWNERS JAMSHID KHATIB AND BAHJAT
ZANJANI140 ACACIA AVE
CARLSBAD, CA 92008
AMOUNTFEE
BUILDING INSPECTION FEE $117.00 BUILDING INSPECTION FEE $117.00
PLUMBING, ELECTRICAL, AND MECHANICAL PERMIT $175.00
Total Fees:$409.00 Total Payments To Date:$409.00 Balance Due:$0.00
Please take NOTICE that approval of your project includes the "Imposition" of fees, dedications, reservations, or other exactions hereafter
collectively referred to as "fees/exaction." You have 90 days from the date this permit was issued to protest imposition of these
fees/exactions. If you protest them, you must follow the protest procedures set forth in Government Code Section 66020(a), and file the
protest and any other required information with the City Manager for processing in accordance with Carlsbad Municipal Code Section 3.32.030. Failure to timely follow that procedure will bar any subsequent legal action to attack, review, set aside, void, or annul their
imposition.
You are hereby FURTHER NOTIFIED that your right to protest the specified fees/exactions DOES NOT APPLY to water and sewer connection fees and capacity changes, nor planning, zoning, grading or other similar application processing or service fees in connection with this
project. NOR DOES IT APPLY to any fees/exactions of which you have previously been given a NOTICE similar to this, or as to which the
statute of limitation has previously otherwise expired.
1635 Faraday Avenue, Carlsbad CA 92008-7314 ï 442-339-2719 ï 760-602-8560 f ï www.carlsbadca.gov
Building Division Page 1 of 1
{"Cityof
Carlsbad
CBR2020-276210/27/2020{cityof Carlsbad RESIDENTIAL BUILDING PERMIT APPLICATION B-1 Plan Check _______ _ Est. Value PC Deposit Date _______ _ Job Address 140 Acacia Ave. Carlsbad, CA Sulte:5 APN: 204-233-24-00 -----CT/Project #: ________________ .Lot#: B &9 Year Built: _1_9_7_2 ______ _ Fire Sprinklers: ()ves@No Air Condltioning:Q YES® NO Electrical Panel Upgrade: Oves® NO BRIEF DESCRIPTION OF WORK: Remodel the unit by changing plumbing pipeline and fixtures, floor covering, paint, kitchen cabinets, celing can lights 0 Addition/New:N/A Living SF, ____ Deck SF, ____ Patio SF, ____ Garage SF __ Is this to create an Accessory Dwelling Unit? Ov ® N New Fireplace? Qv ® N, if yes how many? __ li!Remodel:._9_80 ____ SF of affected area Is the area a conversion or change of use? Ov ®N 0 Pool/Spa:. ____ SF Additional Gas or Electrical Features? N/A ------------osolar:. ___ KW,. ___ Modules, Mounted:0Roof 0Ground, Tilt: OvO N, RMA: Ov ON, Batterv:Ov ON, Panel Upgrade: Ov ON D Reroof:N/A -----------------------------------Iii Plumbing/Mechanical/Electrical Ii] Only: Other: re-pipe plumbing; kitchen/bathroom faucet and toilet, can celing light floor covering, paint, termit repair, kitchen cabinet This permit Is to be Issued In the name of the Property Owner as Owner-Builder, licensed contractor or Authorized Agent of the owner or contractor. The person listed as the Applicant below will be the main pofnt of contact throughout the permit process. PROPERTY OWNER APPLICANT Ii PROPERTY OWNERS AUTHORIZED AGENT APPLICANT 0 Name: Jamshid Khatib & Behjat Zanjani Address:2091 Salt Air Dr. Name: __________________ _ Address: _________________ _ City:Santa Ana State:CA Zip:92705 City: _________ .State: ____ Zip:. ____ _ Phone: (714) 488-3056 Phone: _________________ _ Email: bzaniani~iemcm.com Email: __________________ _ DESIGN PROFESSIONAL APPLICANT O CONTRACTOR OF RECORD APPLICANT 0 Name: ________________ _ Name: __________________ _ Address:. _______________ _ Address: _________________ _ City: _______ state: ___ .Zip: ___ _ City:. _______ .State: ___ .Zlp: _____ _ Phone: _______________ _ Phone: _________________ _ Email: bzanjani@iemcm.com Email: __________________ _ Architect State License: __________ _ State License/class:. _____ Bus. License: ___ _ 1635 Faradav Ave Carlsbad, CA 92008 Ph: 760-602-2719 Fax: 760-602-8558 Email: Buildlng@carlsbadca.gov REV,0B/20
IDENTIFY WHO WILL PERFORM THE WORK BY COMPLETING {OPTION A) OR {OPTION B) BELOW:
{OPTION A): LICENSED CONTRACTOR DECLARATION:
I hereby affirm under penalty of perjury that I am licensed under provisions of Chapter 9 (commencing with Section 7000) of Division 3
of the Business and Professions Code, and my license is in full force and effect. I also affirm under penalty of perjury one of the
following declarations:
01 have and will maintain a certificate of consent ta self•lnsure far workers' compensation provided by Section 3700 of the Labor Code, for the performance of the
work which this permit is Issued. Polley No., _____________________________________ _
0 I have and will maintain worker's compensation, as required by Section 3700 of the Labar Code, for the performance of the work for which this permit Is Issued.
My workers' compensation Insurance carrier and policy number are: lruuranceCompanv Name: ____________________ _
Polley No., __________________________ Explratlon Date: ______________ _
0 Certificate of Exemption; I certify that In the performance of the work for which this permit is issued, I shall not employ any person In any manner so as to become
subject to the workers' compensation Laws of California. WARNING: Failure to secure workers compensation coverage Is unlawful and shall subject an employer to
almlnal penalties and dvll fines up to $100,000.00, In addition the to the cost of compensation, dama1es as provided for In Section 3706 of the Labor Code,
Interest and attorney's fees.
CONSTRUCTION LENDING AGENCY, IF ANY:
I hereby affirm that there Is a construction lending agency for the performance of the work this permit ls Issued {Sec. 3097 (i) Ovil Code).
Lender's Name: ____________________ Lender's Address: ___________________ _
CONTRACTOR PRINT: _________ SIGN: _________ DATE: _____ _
(OPTION B): OWNER-BUILDER DECLARATION:
I hereby affirm that I am exempt from Contractor's License Law for the following reason:
Ii] I, as owner of the property or my employees with wages as their sole compensation, will do the work and the structure Is not Intended or offered for sale {Sec.
7044, Business and Professions Code: The Contractor's License Law does not apply to an owner of property who builds or Improves thereon, and who does such work
himself or through his own employees, provided that such Improvements are not Intended or offered for sale. If, however, the building or Improvement is sold within
one year of completion, the owner•bulider will have the burden of proving that he did not build or Improve for the purpose of sale).
0 I, as owner of the property, am exclusively contracting with licensed contractors to construct the project (Sec. 7044, Business and Professions Code: The
Contractor's License law does not apply to an owner of property who builds or improves thereon, and contracts for such projects with contractor(s) licensed
pursuant to the Contractor's License Law).
DI am exempt under Business and Professions Code Division 3, Chapter 9, Article 3 for this reason:
liJ•owner BuUder acknowledgement and verification form" has been filled out, signed and attached to this application.
0 Owners "Authorized Agent Form• has been filled out, signed and attached to this application giving the agttlt authority ta obtain the permit an the owner's behalf,
By my signature below I acknowledge that, except for my personal residence In which I must have resided for at least one year prior to completion of the
improvements covered by this permit, I cannot legally sell a structure that I have built as an owner•bullder if it h;M not been constructed In Its entirety by licensed
contractors. I understand that a copy of the applicable low, Section 7044 af the Business and Profess/ans Cade, Is available upon request when this application is
submitted ar at the following ~eb site: htt~://~.leglnfa.cu.gov/ct1law.html. /7 ~
OWNER PRINT: BehJat ZanJam SIGN: ~ ,:Z'E: 10/27 /20
APPLICANT CERTIFICATION: SIGNATURE REQUIRED AT THE TIME OF SUBMITTAL/
By my signature below, I certify that: I am the property owner or State of California Licensed Contractor or authorized to act on the property
owner or contractor's behalf. I certify that I have read the application and state that the above information is correct and that the information on
the plans is accurate. I agree to comply with all City ordinances and State laws relating to building construction.
I hereby authorize representative of the City of Carlsbad to enter upon the above mentioned property for Inspection purposes. I ALSO AGREE TO SAVE,
INDEMNIFY AND KEEP HARMLESS THE QTY OF CARLSBAD AGAINST AU LIABILmES, JUDGMENTS, COSTS AND EXPENSES WHIQ-1 MAY IN ANY WAY ACCRUE
AGAINST SAID CITY IN CONSEQUENCE OF THE GRANTING OF THIS PERMIT. OSHA: An OSHA permit Is required for excavations over S'O' deep and
demolition or construction of structures over 3 stories in height. , ~ z
APPLICANT PRINT: Behjat Zanjani SIGN: d ~ CZoATE: 10/27 /20
__., C 7
163S Faraday Ave carlsbad, CA 92008 Ph: 760-602-2719 FaK: 760•602•8558 Email: Building@ca!lsbadca.gov
2 REV. 08/20
(cityof
Carlsbad
OWNER-BUILDER
ACKNOWLEDGEMENT
FORM
B-61
Development Services
Building Division
1635 Faraday Avenue
760-602-2719
www.carlsbadca.gov
OWNER-BUILDER ACKNOWLEDGMENT FORM
Pursuant to State of California Health and Safety Code Section 19825-19829
To: Property Owner
An application for construction permit(s) has been submitted in your name listing you as the owner-builder of the
property located at:
Site Address 140 Acacia Ave., Carlsbad, CA 92008
The City of Carlsbad ("City") is providing you with this Owner-Builder Acknowledgment and Verificatlon form
to inform you of the responsibilities and the possible risks assoclated with typical construction activities issued
in your name as the Owner-Builder.
The City will not issue a construction permit until you have read and initialed your understanding of each
provision in the Property Owner Acknowledgment section below and sign the form. An agent of the owner
cannot execute this notice unless you, the property owner, complete the Owner's Authorized Agent form and
It Is accepted by the City of Carlsbad.
INSTRUCTIONS: Please read and initial each statement below to acknowledge your understanding and
verification of this Information by signature at the bottom of the form. These are very important construction
related acknowledgments designed to inform the property owner of his/her obligations related to the requested
permit activities.
t. _x __ l understand a frequent practice of unlicensed contractors is to have the property owner obtain an "Ow ner·
Builder" building permit that erroneously implies that the property owner is providing his or her own la bor and
material personatly. I, as an Owner-Builder, may be held liable and subject to serious financial risk for any injuries
sustained by an unlicensed contractor and his or her employees while working on my property. My homeowner's
insurance may not provide coverage for those injuries. I am willfully acting as an Owner-Builder and am aware of
the limits of my insurance coverage for injuries to workers on my property.
II. _x __ l understand building permits are not required to be signed by property owners unless they are responsible
for the construction and are not hiring a licensed contractor to assume this responsibility.
111. _x __ l understand as an "Owner•Bullder" I am the responsible party of record on the permit. I understand that I
may protect myself from potential financial risk by hir~ng a licensed contractor and having the permit filed in his
or her name instead of my own.
IV. _x __ l understand contractors are required by law to be licensed and bonded in California and to list their license
numbers on permits and contracts.
V. _X __ I understand If I employ or otherwise engage any persons, other than California licensed contractors, and
the total value of my construction is at least five hundred dollars ($500), including labor and materials, I may be
considered an "employer" under state and federal law.
1 REV.08/20
Owner-Builder Acknowledgement Continued
VI. _x __ l understand if I am considered an "employer" under state and federal law, I must register with the state
and federal government, withhold payroll taxes, provide workers' compensation disability insurance, and
contribute to unemployment compensation for each "employee." I also understand my failure to abide by these
laws may subject me to serious financial risk.
VII. _x __ I understand under California Contractors' State License Law, an Owner-Builder who builds single-family
residential structures cannot legally build them with the intent to offer them for sale, unless all work is performed
by licensed subcontractors and the number of structures does not exceed four within any calendar year, or all of
the work is performed under contract with a licensed general building contractor.
VIII. _x __ 1 understand as an Owner-Builder if I sell the property for which this permit is issued, I may be held liable
for any financial or personal injuries sustained by any subsequent owner(s) which result from any latent
construction defects in the workmanship or materials.
IX. _x __ I understand I may obtain more information regarding my obligations as an "employer" from the Internal
Revenue Service, the United States Small Business Administration, the California Department of Benefit
Payments, and the California Division of Industrial Accidents. I also understand I may contact the California
Contractors' State License Board (CSLB) at 1-800-321-CSLB (2752) or www.cslb.ca.gov for more information
about licensed contractors.
X. _x __ l am aware of and consent to an Owner-Builder building permit applied for in my name, and understand
that I am the party legally and financially responsible for proposed construction activity at the following address:
Our plumber, tile Installer, and flooring contractors are licensed and bonded except but our electrician and termite repair are not.
XI. _x __ l agree that, as the party legally and financially responsible for this proposed construction activity, I will abide
by all applicable laws and requirements that govern Owner-Builders as well as employers.
XII. _x __ l agree to notify the issuer of this form immediately of any additions, deletions, or changes to any of the
information I have provided on this form.
Licensed contractors are regulated by laws designed to protect the publlc. If you contract with someone who
does not have a license, the Contractor's State License Board may be unable to assist you with any financial loss
you may sustain as a result of a complaint. Your only remedy against unlicensed Contractors may be in civil court.
It is also Important for you to understand that if an unlicensed Contractor or employee of that individual or firm
is Injured while working on your property, you may be held liable for damages. If you obtain a permit as Owner-
Builder and wish to hire contractors, you will be responsible for verifying whether or not those contractors are
properly licensed and the status of their workers' compensation coverage.
Before a building permit can be issued, this form must be completed, signed by the property owner and returned
to the City of Carlsbad Building Division.
/ declare under penalty of perjury that I have read and understand all of the lnfarmatlon provided on this form and that my respotues, Including my
authority to sign this form, is true and correct. I am aware that I have the option to consult with legal counsel prior to signing this form, and I have
either (1} consulted with /ego/ counsel prior to signing this form or (2} have waived this right In signing this form without the advice of legal counsel.
Behjat Zanjani
Property Owner Name (PRINT)
2
10/27/20
Date
REV. 08/20
Building Permit Inspection History Finaled
PERMIT INSPECTION HISTORY for (CBR2020-2762)
BLDG-Residential 10/27/2020Application Date:Permit Type:Owner:COOWNER JAMSHID KHATIB & BAHJAT
ZANJANI
P/M/E 10/28/2020Work Class:Issue Date:Subdivision:PARCEL MAP NO 02616
11/23/2021Expiration Date:Status:
IVR Number: 29627
Closed - Finaled 140 ACACIA AVE, # 5
CARLSBAD, CA 92008-3204
Address:
Scheduled
Date
Inspection Type Inspection No. Inspection
Status
Primary Inspector Reinspection InspectionActual
Start Date
10/29/2020 10/29/2020 BLDG-84 Rough
Combo(14,24,34,44)
142358-2020 Failed Paul Burnette Reinspection Incomplete
COMMENTS PassedChecklist Item
BLDG-Building Deficiency No
BLDG-14
Frame-Steel-Bolting-Welding
(Decks)
No
BLDG-24 Rough-Topout No
BLDG-34 Rough Electrical No
BLDG-44
Rough-Ducts-Dampers
No
11/16/2020 11/16/2020 BLDG-27 Shower
Pan/Tubs
143423-2020 Cancelled Tony Alvarado Reinspection Incomplete
BLDG-84 Rough
Combo(14,24,34,44)
143424-2020 Cancelled Tony Alvarado Reinspection Incomplete
11/17/2020 11/17/2020 BLDG-14
Frame/Steel/Bolting/We
lding (Decks)
143861-2020 Failed Tony Alvarado Reinspection Incomplete
COMMENTS PassedChecklist Item
BLDG-Building Deficiency November 17, 2020:
1. Rough frame combination inspection –
not ready for all units. Scope of rough
frame, plumbing, electrical, mechanical
scope of work incomplete.
2. Structural alterations were made by
owner builder Jay, remodel/alteration has
compromised structural integrity of exterior
bearing walls at two locations.
3. Informed owner that structural engineer
needs to provide a solution and structural
engineers detail for a cut let-in brace and
double top plates severed.
No
01/19/2021 01/19/2021 BLDG-27 Shower
Pan/Tubs
148540-2021 Passed Tony Alvarado Complete
BLDG-84 Rough
Combo(14,24,34,44)
148541-2021 Partial Pass Tony Alvarado Reinspection Incomplete
Friday, April 1, 2022 Page 1 of 8
{cityof
Carlsbad
PERMIT INSPECTION HISTORY for (CBR2020-2762)
BLDG-Residential 10/27/2020Application Date:Permit Type:Owner:COOWNER JAMSHID KHATIB & BAHJAT
ZANJANI
P/M/E 10/28/2020Work Class:Issue Date:Subdivision:PARCEL MAP NO 02616
11/23/2021Expiration Date:Status:
IVR Number: 29627
Closed - Finaled 140 ACACIA AVE, # 5
CARLSBAD, CA 92008-3204
Address:
Scheduled
Date
Inspection Type Inspection No.Inspection
Status
Primary Inspector Reinspection InspectionActual
Start Date
COMMENTS PassedChecklist Item
BLDG-14
Frame-Steel-Bolting-Welding
(Decks)
January 19, 2021:
1. Rough framing, scope of work to
illuminate dry-rot /termite damage wood
studs (typical), and reinforce existing
loadbearing walls, per structural engineers
plans and detail specifications – partial
pass.
2. Pending letter from structural
engineer–for deviation to structural
engineers load bearing wall removal of
lead in brace detail, located at exterior
loadbearing wall Living room location.
3. Shower pans, scope of work-approved.
4. Insulation at all bathroom, kitchen and
exterior wall locations – approved.
5. Relocated existing sub-Standard
electrical panels from existing closet
locations, to approved new bedroom
location-approved.
6. Bathroom locations, outdoor living area,
moisture resistive-cement board-approved.
7. Rough mechanical, scope of
work-approved.
Yes
BLDG-24 Rough-Topout January 19, 2021:
1. Rough framing, scope of work to
illuminate dry-rot /termite damage wood
studs (typical), and reinforce existing
loadbearing walls, per structural engineers
plans and detail specifications – partial
pass.
2. Pending letter from structural
engineer–for deviation to structural
engineers load bearing wall removal of
lead in brace detail, located at exterior
loadbearing wall Living room location.
3. Shower pans, scope of work-approved.
4. Insulation at all bathroom, kitchen and
exterior wall locations – approved.
5. Relocated existing sub-Standard
electrical panels from existing closet
locations, to approved new bedroom
location-approved.
6. Bathroom locations, outdoor living area,
moisture resistive-cement board-approved.
7. Rough mechanical, scope of
work-approved.
Yes
Friday, April 1, 2022 Page 2 of 8
PERMIT INSPECTION HISTORY for (CBR2020-2762)
BLDG-Residential 10/27/2020Application Date:Permit Type:Owner:COOWNER JAMSHID KHATIB & BAHJAT
ZANJANI
P/M/E 10/28/2020Work Class:Issue Date:Subdivision:PARCEL MAP NO 02616
11/23/2021Expiration Date:Status:
IVR Number: 29627
Closed - Finaled 140 ACACIA AVE, # 5
CARLSBAD, CA 92008-3204
Address:
Scheduled
Date
Inspection Type Inspection No.Inspection
Status
Primary Inspector Reinspection InspectionActual
Start Date
BLDG-34 Rough Electrical January 19, 2021:
1. Rough framing, scope of work to
illuminate dry-rot /termite damage wood
studs (typical), and reinforce existing
loadbearing walls, per structural engineers
plans and detail specifications – partial
pass.
2. Pending letter from structural
engineer–for deviation to structural
engineers load bearing wall removal of
lead in brace detail, located at exterior
loadbearing wall Living room location.
3. Shower pans, scope of work-approved.
4. Insulation at all bathroom, kitchen and
exterior wall locations – approved.
5. Relocated existing sub-Standard
electrical panels from existing closet
locations, to approved new bedroom
location-approved.
6. Bathroom locations, outdoor living area,
moisture resistive-cement board-approved.
7. Rough mechanical, scope of
work-approved.
Yes
BLDG-44
Rough-Ducts-Dampers
January 19, 2021:
1. Rough framing, scope of work to
illuminate dry-rot /termite damage wood
studs (typical), and reinforce existing
loadbearing walls, per structural engineers
plans and detail specifications – partial
pass.
2. Pending letter from structural
engineer–for deviation to structural
engineers load bearing wall removal of
lead in brace detail, located at exterior
loadbearing wall Living room location.
3. Shower pans, scope of work-approved.
4. Insulation at all bathroom, kitchen and
exterior wall locations – approved.
5. Relocated existing sub-Standard
electrical panels from existing closet
locations, to approved new bedroom
location-approved.
6. Bathroom locations, outdoor living area,
moisture resistive-cement board-approved.
7. Rough mechanical, scope of
work-approved.
Yes
02/10/2021 02/09/2021 BLDG-14
Frame/Steel/Bolting/We
lding (Decks)
150142-2021 Partial Pass Paul Burnette Reinspection Incomplete
Friday, April 1, 2022 Page 3 of 8
PERMIT INSPECTION HISTORY for (CBR2020-2762)
BLDG-Residential 10/27/2020Application Date:Permit Type:Owner:COOWNER JAMSHID KHATIB & BAHJAT
ZANJANI
P/M/E 10/28/2020Work Class:Issue Date:Subdivision:PARCEL MAP NO 02616
11/23/2021Expiration Date:Status:
IVR Number: 29627
Closed - Finaled 140 ACACIA AVE, # 5
CARLSBAD, CA 92008-3204
Address:
Scheduled
Date
Inspection Type Inspection No.Inspection
Status
Primary Inspector Reinspection InspectionActual
Start Date
COMMENTS PassedChecklist Item
BLDG-Building Deficiency November 17, 2020:
1. Rough frame combination inspection –
not ready for all units. Scope of rough
frame, plumbing, electrical, mechanical
scope of work incomplete.
2. Structural alterations were made by
owner builder Jay, remodel/alteration has
compromised structural integrity of exterior
bearing walls at two locations.
3. Informed owner that structural engineer
needs to provide a solution and structural
engineers detail for a cut let-in brace and
double top plates severed.
Yes
03/29/2021 03/29/2021 BLDG-18 Exterior
Lath/Drywall
153671-2021 Passed Paul Burnette Complete
COMMENTS PassedChecklist Item
BLDG-Building Deficiency Yes
03/30/2021 03/30/2021 BLDG-17 Interior
Lath/Drywall
153866-2021 Passed Tony Alvarado Complete
COMMENTS PassedChecklist Item
BLDG-Building Deficiency March 29, 2021: (virtual inspection).
1. No Building Deficiencies.
2. Bathroom shower enclosure areas-
new moisture resistive cement
Dens-Shield/Hardy-backer/fiber-rock
board, type and nailing pattern, scope of
work per plan-approved.
Yes
05/27/2021 05/27/2021 BLDG-14
Frame/Steel/Bolting/We
lding (Decks)
158296-2021 Partial Pass Tony Alvarado Reinspection Incomplete
COMMENTS PassedChecklist Item
BLDG-Building Deficiency May 27, 2021: Partial Pass.
No multi-family/building deficiencies.
1. Newframed in windows, with new sill
plate heights-(reframed) typical.
2. New window framed sill heights (type V
light wood frame construction, 2x studs at
every 16 inches on center), per building
code specifications-for window egress sill
height requirements and window fall
protection requirements-(IRC chapter-3)
Yes
03/03/2022 03/03/2022 BLDG-Final Inspection 177635-2022 Partial Pass Tony Alvarado Reinspection Incomplete
Friday, April 1, 2022 Page 4 of 8
PERMIT INSPECTION HISTORY for (CBR2020-2762)
BLDG-Residential 10/27/2020Application Date:Permit Type:Owner:COOWNER JAMSHID KHATIB & BAHJAT
ZANJANI
P/M/E 10/28/2020Work Class:Issue Date:Subdivision:PARCEL MAP NO 02616
11/23/2021Expiration Date:Status:
IVR Number: 29627
Closed - Finaled 140 ACACIA AVE, # 5
CARLSBAD, CA 92008-3204
Address:
Scheduled
Date
Inspection Type Inspection No.Inspection
Status
Primary Inspector Reinspection InspectionActual
Start Date
COMMENTS PassedChecklist Item
BLDG-Structural Final March 3, 2022:
1. Apartment unit and condominium
complex handrails, guard rails
Inspection-Partial pass.
Yes
03/08/2022 03/08/2022 BLDG-Final Inspection 177989-2022 Failed Tony Alvarado Reinspection Incomplete
COMMENTS PassedChecklist Item
BLDG-Building Deficiency March 8, 2022:
1. Apartment/condominium complex
remodel, installing new handrails, guard
rails-(typical) Inspection-Not ready, failed,
does not meet 42" inch high guard rail min.
requirements, per residential code specs.
No
BLDG-Structural Final March 3, 2022:
1. Apartment unit and condominium
complex handrails, guard rails
Inspection-Partial pass.
Yes
03/25/2022 03/25/2022 BLDG-Final Inspection 178973-2022 Partial Pass Tony Alvarado Reinspection Incomplete
Friday, April 1, 2022 Page 5 of 8
PERMIT INSPECTION HISTORY for (CBR2020-2762)
BLDG-Residential 10/27/2020Application Date:Permit Type:Owner:COOWNER JAMSHID KHATIB & BAHJAT
ZANJANI
P/M/E 10/28/2020Work Class:Issue Date:Subdivision:PARCEL MAP NO 02616
11/23/2021Expiration Date:Status:
IVR Number: 29627
Closed - Finaled 140 ACACIA AVE, # 5
CARLSBAD, CA 92008-3204
Address:
Scheduled
Date
Inspection Type Inspection No.Inspection
Status
Primary Inspector Reinspection InspectionActual
Start Date
COMMENTS PassedChecklist Item
BLDG-Plumbing Final March 25, 2022: partial final pass.
1. Final inspection incomplete:
2. Pending:
a) light fixtures not installed.
b) label electrical subpanel in master
bedroom.
c) mechanical hood duct-exhaust not
connected.
3. Rest of work – OK.
Yes
BLDG-Mechanical Final March 25, 2022: partial final pass.
1. Final inspection incomplete:
2. Pending:
a) light fixtures not installed.
b) label electrical subpanel in master
bedroom.
c) mechanical hood duct-exhaust not
connected.
3. Rest of work – OK.
Yes
BLDG-Structural Final March 25, 2022: partial final pass.
1. Final inspection incomplete:
2. Pending:
a) light fixtures not installed.
b) label electrical subpanel in master
bedroom.
c) mechanical hood duct-exhaust not
connected.
3. Rest of work – OK.
Yes
BLDG-Structural Final March 3, 2022:
1. Apartment unit and condominium
complex handrails, guard rails
Inspection-Partial pass.
Yes
BLDG-Electrical Final March 25, 2022: partial final pass.
1. Final inspection incomplete:
2. Pending:
a) light fixtures not installed.
b) label electrical subpanel in master
bedroom.
c) mechanical hood duct-exhaust not
connected.
3. Rest of work – OK.
Yes
04/01/2022 04/01/2022 BLDG-Final Inspection 179545-2022 Passed Tony Alvarado Complete
Friday, April 1, 2022 Page 6 of 8
PERMIT INSPECTION HISTORY for (CBR2020-2762)
BLDG-Residential 10/27/2020Application Date:Permit Type:Owner:COOWNER JAMSHID KHATIB & BAHJAT
ZANJANI
P/M/E 10/28/2020Work Class:Issue Date:Subdivision:PARCEL MAP NO 02616
11/23/2021Expiration Date:Status:
IVR Number: 29627
Closed - Finaled 140 ACACIA AVE, # 5
CARLSBAD, CA 92008-3204
Address:
Scheduled
Date
Inspection Type Inspection No.Inspection
Status
Primary Inspector Reinspection InspectionActual
Start Date
COMMENTS PassedChecklist Item
BLDG-Plumbing Final April 4, 2022: final-pass.
1. Final inspection incomplete-approved.
2. No Pending items:
a) light fixtures-installed, and protective
plate covers installed until light fixture
arrives.
b) label electrical subpanel in master
bedroom-approved.
c) mechanical hood duct-exhaust
connected-approved.
3. Rest of work – Approved.
Yes
BLDG-Mechanical Final April 4, 2022: final-pass.
1. Final inspection incomplete-approved.
2. No Pending items:
a) light fixtures-installed, and protective
plate covers installed until light fixture
arrives.
b) label electrical subpanel in master
bedroom-approved.
c) mechanical hood duct-exhaust
connected-approved.
3. Rest of work – Approved.
Yes
BLDG-Structural Final April 4, 2022: final-pass.
1. Final inspection incomplete-approved.
2. No Pending items:
a) light fixtures-installed, and protective
plate covers installed until light fixture
arrives.
b) label electrical subpanel in master
bedroom-approved.
c) mechanical hood duct-exhaust
connected-approved.
3. Rest of work – Approved.
Yes
BLDG-Electrical Final March 25, 2022: partial final pass.
1. Final inspection incomplete:
2. Pending:
a) light fixtures not installed.
b) label electrical subpanel in master
bedroom.
c) mechanical hood duct-exhaust not
connected.
3. Rest of work – OK.
Yes
BLDG-Electrical Final April 4, 2022: final-pass.
1. Final inspection incomplete-approved.
2. No Pending items:
a) light fixtures-installed, and protective
plate covers installed until light fixture
arrives.
b) label electrical subpanel in master
bedroom-approved.
c) mechanical hood duct-exhaust
connected-approved.
3. Rest of work – Approved.
Yes
Friday, April 1, 2022 Page 7 of 8
PERMIT INSPECTION HISTORY for (CBR2020-2762)
BLDG-Residential 10/27/2020Application Date:Permit Type:Owner:COOWNER JAMSHID KHATIB & BAHJAT
ZANJANI
P/M/E 10/28/2020Work Class:Issue Date:Subdivision:PARCEL MAP NO 02616
11/23/2021Expiration Date:Status:
IVR Number: 29627
Closed - Finaled 140 ACACIA AVE, # 5
CARLSBAD, CA 92008-3204
Address:
Scheduled
Date
Inspection Type Inspection No.Inspection
Status
Primary Inspector Reinspection InspectionActual
Start Date
Friday, April 1, 2022 Page 8 of 8