HomeMy WebLinkAbout2345 JEFFERS PL; ; CBR2022-3735; PermitPrint Date: 12/28/2022 Permit No: CBR2022-3735
Building Permit Finaled
Residential Permit
Job Address:
Permit Type:
Parcel #:
Valuation:
Occupancy Group:
2345 JEFFERS PL, CARLSBAD, CA 92008-3870
BLDG-Residential
2081615700
$6,400.00
Work Class:
Lot #:
Project #:
Cogen
Status:
Applied:
Issued:
10/07/2022
10/13/2022
Finaled Close Out:12/28/2022
#of Dwelling Units:
Track #:
Plan #:
Closed - Finaled
Plan Check #:
Orig. Plan Check #:Bathrooms:
Final Inspection:11/03/2022Bedrooms:Construction Type:
Occupant Load:
Code Edition:
Sprinkled:
INSPECTOR:de Roggenbuke, Dirk
GRANT; 5.84 KW ROOF MOUNTED PV SYSTEM WITH 16 MODULES(E-REVIEW)Description:
Project Title:
Contractor: SUNRUN INSTALLATION SERVICES INC
1225 PARK CENTER DR
VISTA, CA 92081-8353
(562) 503-5657
AMOUNTFEE
SB1473 – GREEN BUILDING STATE STANDARDS FEE $1.00
SOLAR–RESIDENTIAL: per kW $289.00
STRONG MOTION – RESIDENTIAL (SMIP)$0.83
Total Fees:$290.83 Total Payments To Date:$290.83 Balance Due:$0.00
Please take NOTICE that approval of your project includes the "Imposition" of fees, dedications, reservations, or other exactions hereafter
collectively referred to as "fees/exaction." You have 90 days from the date this permit was issued to protest imposition of these
fees/exactions. If you protest them, you must follow the protest procedures set forth in Government Code Section 66020(a), and file the protest and any other required information with the City Manager for processing in accordance with Carlsbad Municipal Code Section
3.32.030. Failure to timely follow that procedure will bar any subsequent legal action to attack, review, set aside, void, or annul their
imposition.
You are hereby FURTHER NOTIFIED that your right to protest the specified fees/exactions DOES NOT APPLY to water and sewer connection
fees and capacity changes, nor planning, zoning, grading or other similar application processing or service fees in connection with this
project. NOR DOES IT APPLY to any fees/exactions of which you have previously been given a NOTICE similar to this, or as to which the
statute of limitation has previously otherwise expired.
1635 Faraday Avenue, Carlsbad CA 92008-7314 ï 442-339-2719 ï 760-602-8560 f ï www.carlsbadca.gov
Building Division Page 1 of 1
{"Cityof
Carlsbad
( City of
Carlsbad
RESIDENTIAL
BUILDING PERMIT
APPLICATION
B-1
Plan Check
Est. Value
PC Deposit
Date
JobAddress. ____ 2_3_4_S_J_E_F_F_E_R_S_P_L _______ Unit: _____ .APN: __________ _
CT/Project#: Lot #: ____ Year Built: ________ _
BRIEF DESCRIPTION OF WORK: Roof mounted PV system
0 New SF : Living SF, ____ Deck SF, ___ Patio SF,. ____ Garage SF __ _
Is this to create an Accessory Dwell ing Unit? O Y O N New Fireplace? O YO N , if yes how many? ___ _
D Remodel: SF of affected area Is the area a conversion or change of use? O Y O N -----
□ Pool/Spa: ____ SF Additional Ga s or Electrical Features? ____________ _
iii Solar: 5.84 KW, 16 Modules, Mounted:.Roof 0Ground, Tilt: O v (x)N, RMA: OY ®N,
Battery:OY ®N, Panel Upgrade: OY ®N
Other:
PRIMARY APPLICANT PROPERTY OWNER
Name: Jamie Sager Name: DAN GRANT
Address: 1225 Park Center Dr Address: 2345 JEFFERS PL
City: Vjsta State: CA Zip: 92081 City: Carlsbad State: CA Zip: 92008
Phone: _________________ Phone: __________________ _
Email : __ j_a_m_ie_.s_a_g __ e_r_@_s_u_n_r_u_n_.c_o_m ______ Email: __________________ _
DESIGN PROFESSIONAL CONTRACTOR OF RECORD
Name: _________________ Business Name: Sunrun Installation Services
Address: Address: 1225 Park Center Dr
City:. _______ State: ___ Zip:____ City: Vista State: CA Zip: 92081
Phone: Phone: _________________ _
Email: Email: jamie.sager@sunrun.com
Architect State License: CSLB License#: 750184 Class: C 46 & C 10
Carlsbad Business License# (Required): BLOS1224843
APPLICANT CERT/FICA TION: I certify that I hove reod the applicotion and state thar the above informotion is correct and that the information ofche plans is accurate. I
agree ca comply with all City ordinances and Stote Jaws relating ta building constwction.~.
NAME {PRINT): Jamie Sager SIGN_ d DATE: 10/07/22
1635 Faraday Ave Carlsbad.CA 92008 Ph: 442-339-2719 Email: Buildlng@carlsbadca.gov
REV. 04122
THIS PAGE REQUIRED AT PERMIT ISSUANCE PLAN CHECK NUMBER: ______ _
A BUILDING PERMIT CAN BE ISSUED TO EITHER A STATE LICENSED CONTRACTOR OR A PROPERTY OWNER. IF THE PERSON SIGNING
THIS FORM IS AN AGENT FOR EITHER ENTITY AN AUTHORIZATION FORM OR LETTER IS REQUIRED PRIOR TO PERMIT ISSUANCE.
(OPTION A): LICENSED CONTRACTOR DECLARATION :
lherebyaffirmunderpenaltyofperjurythatlam/icensedunderprovisionsofChapter9(commencingwithSection7000)ofDivision3
of the Business and Professions Code, and my license is in full force and effect. I alsoaf firm under penalty of perjury one of the
following declarations (CHOOSE ONE):
D I have and will maintain a certificate of consent to self-insure for workers' compensation provided by Section 3700 of the Labor Code, for the performance of the
work which this permit Is issued. Policy No. ____________________________________________ _
-OR-
~I have and will maintain worker's compensation, as required by Section 3700 of the Labor Code, for the performance of the work for which this permit is issued.
My workers' compensation insurance carrier and policy number are: Insurance Company Name: American Zurich Insurance
Policy No. WC614287600 Expiration Date: ___J1...,.Q.,_/ .... 0'-'1.u/2'"'0"'-'2.._3,.,_ _______ 1 -OR-
D Certificate of Exemption: I certify that in the performance of the work for which this permit is issued, I shall not employ any person in any manner so as to become
subject to the workers' compensation Laws of California. WARNING: Failure to secure workers compensation coverage Is unlawful and shall subject an employer to
criminal penalties and civil fines up to $100,000.00, in addition the to the cost of compensation, damages as provided for in Section 3706 of the Labor Code,
interest and attorney's fees.
CONSTRUCTION LENDING AGENCY, IF ANY:
I hereby affirm that there is a construction lending agency for the performance of the work this permit is issued (Sec. 3097 (i) Civil Code).
Lender's Name: _______________________ lender's Address: _______________________ _
CONTRACTOR CERTIFICATION: The applicant certifies that all documents and plans clearly and accurately show all existing and proposed buildings, structures, access roads, and
utilities/utility easements. All proposed modifications and/or additions are clearly labeled on the site plan. Any potentially existing detail within these plans inconsistent with the site plan are
not approved for construction and may be required to be altered or removed. The city's approval of the application is based on the premise that the submitted documents and plans show
the correct dimensions of; the property, buildings, structures and their setbacks from property lines and from one another; access roads/easements, and utlllties. The existing and proposed
use of each building as stated Is true and correct: all e..isements and other encumbrances to development have been accurately shown and labeled as well as all on---site grading/site preparation.
All improvements existing on the property were completed In accordance with all regulations in existence ait the time of their construction, unless otherwise noted.
NAME {PRINT): Jamie Sager
Note: If the person signing above is an authorized agent for the cont
(OPTION B): OWNER-BUILDER DECLARATION:
I hereby affirm that I am exempt from Contractor's License Law for the following reason:
D I, as owner of the property or my employees with wages as their sole compensation, will do the work and the structure is not Intended or offered for sale (Sec.
7044, Business and Professions Code: The Contractor's License Law does not apply to an owner of property who builds or improves thereon, and who does such
work himself or through his own employees, provided that such improvements are not intended or offered for sale. If, however, the building or improvement is sold
within one year of completion, the owner-builder will have the burden of proving that he did not build or improve for the purpose of sale).
-OR-
DI, as owner of the property, am exclusively contracting with licensed contractors to construct the project (Sec. 7044, Business and Professions Code: The
Contractor's License Law does not apply to an owner of property who builds or improves thereon, and contracts for such projects with contractor(s) licensed
pursuant to the Contractor's License Law).
-OR-
D I am exempt under Business and Professions Code Division 3, Chapter 9, Article 3 for this reason:
AND.
D FORM B-61 "Owner Builder Acknowledeement and Verification Form" is required for any permit Issued to a property owner.
By my signature below I acknowledge that, except for my personal residence in which I must have resided for at least one year prior to completion of the
Improvements covered by this permit, I cannot legally sell a structure that I have built as an owner-builder 11 it has not been constructed In ,ts entirety by licensed
contractors./ understand that a copy of the applicable low, Section7044 of the Business and Professions Code, is available upon request when thisopplfcotion is
submitted arat the following Web site: http:/ l www.leginfo.co.govlcolaw.html.
OWNER CERTIFICATION: The applicant certifies that all documents and plans clearly and accurately show all existing and proposed buildings, structures, access roads, and uulities/utihty
easements. All proposed modifications and/or additions are clearly labeled on the site plan. Any potentially existing detall within these plans Inconsistent with the site plan are not approved
for construction and may be required to be altered or removed. The city's approval of the application is based on the premise that the submitted documents and plans show the. correct
dimensions of; the property, buildings, structures and their setbacks from property lines and from one another; access roads/easements, and utilities. The existing and proposed use of each
building as stated is true and correct: all easements and other encumbrances to development have been accurately shown and labeled as well as all on-site grading/site preparation. All
improvements existing on the property were completed in accordance with all regulations in ex1stence at the time of their construction, unless otherwise noted.
NAME {PRINT): SIGN: __________ DATE: ______ _
Note: If the erson si nln above is an authorized a ent for the ro ert owner include form 8-62 si ned b ro ert owner.
1635 Faraday Ave Carlsbad, CA 92008 Ph: 442-339-2719 Email: 8uild1ng@carlsbadca.gov
2
REV. 04/22
Building Permit Inspection History Finaled
PERMIT INSPECTION HISTORY for (CBR2022-3735)
BLDG-Residential 10/07/2022Application Date:Permit Type:Owner:
Cogen 10/13/2022Work Class:Issue Date:Subdivision:
05/02/2023Expiration Date:Status:
IVR Number: 43848
Closed - Finaled 2345 JEFFERS PL
CARLSBAD, CA 92008-3870
Address:
Scheduled
Date
Inspection Type Inspection No. Inspection
Status
Primary Inspector Reinspection InspectionActual
Start Date
11/03/2022 11/03/2022 BLDG-35 Solar Panel 195761-2022 Passed Dirk de Roggenbuke Complete
COMMENTS PassedChecklist Item
BLDG-Building Deficiency Yes
BLDG-Final Inspection 195760-2022 Passed Dirk de Roggenbuke Complete
COMMENTS PassedChecklist Item
BLDG-Building Deficiency Yes
BLDG-Structural Final Yes
BLDG-Electrical Final Yes
Thursday, November 3, 2022 Page 1 of 1
{cityof
Carlsbad
10/6/2022
RE: Structural Certification for Installation of Residential Solar
DAN GRANT:2345 JEFFERS PL, CARLSBAD,CA, 92008
Attn: To Whom It May Concern
Design Criteria
Code 2019 California Building Code (ASCE 7-16)
Risk category II Wind Load (component and Cladding)
Roof Dead Load Dr 15 psf V 97 mph
PV Dead Load DPV 3 psf Exposure C
Roof Live Load Lr 20 psf
Ground Snow S 0 psf
If you have any questions on the above, please do not hesitate to call.
Sincerely,
Eugene Munyanziza, P.E.
EV Engineering, LLC
projects@evengineersnet.com
http://www.evengineersnet.com
Exp: 06/30/2024
This Letter is for the existing roof framing which supports the new PV modules as well as the attachment of the
PV system to existing roof framing. From the field observation report, the roof is made of Tile roofing over roof
plywood supported by 2X4 Trusses at 24 inches. The slope of the roof was approximated to be 23 degrees.
After review and based on our structural capacity calculation, the existing roof framing has been determined to
be adequate to support the imposed loads without structural upgrades. Contractor shall verify that existing
framing is consistent with the described above before install. Should they find any discrepancies, a written
approval from SEOR is mandatory before proceeding with install. Capacity calculations were done in
accordance with applicable building codes.
projects@evengineersnet.com
http://www.evengineersnet.com
~EV
ENGINEERING
Structural Letter for PV Installation
Date: 10/6/2022
Job Address:2345 JEFFERS PL
CARLSBAD,CA, 92008
Job Name:DAN GRANT
Job Number:221006 DG
Scope of Work
Table of Content
Sheet 1 Cover2Attachment Uplift checks3Roof Framing Check
4 Seismic Check and Scope of work
Engineering Calculations Summary
Code 2019 California Building Code (ASCE 7-16)
Risk category II
Roof Dead Load Dr 15 psf
PV Dead Load DPV 3 psf
Roof Live Load Lr 20 psf
Ground Snow S 0 psf
Wind Load (component and Cladding)
V 97 mph
Exposure C
References
NDS for Wood Construction
Sincerely,
Eugene Munyanziza, P.E.
EV Engineering, LLC
projects@evengineersnet.com
http://www.evengineersnet.com Exp: 06/30/2024
This Letter is for the existing roof framing which supports the new PV modules as well as the attachment of the
PV system to existing roof framing. All PV mounting equipment shall be designed and installed per
manufacturer's approved installation specifications.
projects@evengineersnet.com
http://www.evengineersnet.com
-
~EV
ENGINEERING
Wind Load Cont.
97 mph ASCE 7-16 Figure 26.5-1B
C
1.0 ASCE 7-16 Sec 26.8.2
0.93 ASCE 7-16 Table 26.10-1
0.85 ASCE 7-16 Table 26.6-1
1.00 ASCE 7-16 Table 26.9-1
18.96 psf
23.0 Degrees
1.1
0.6 (Wind Tunnel value)
Uplift (W)Zone(1) Zone(2r) Zone(2e)Zone(3)
Fig. 30-3-2 GCp=-1.8 -2.2 -2.2 -2.1
Eq. 29.4-7 P=qh(GCp)(E)(a)=-22.53 -27.54 -27.54 -26.28
GCp=0.7 Figure 30.3-2
P=qh(GCp)(E)(a)=8.76 Equation 29.4-7
Rafter Attachments: 0.6D+0.6W (CD=1.6)
Connection Check
Attachement max. spacing=6 ft
5/16" Lag Screw Withdrawal Value= 266 lbs/in Table 12.2A - NDS
2.5 in DFL Assumed
Allowable Capacity= 760 lbs (Lag Bolt)
Zone Trib Width Area (ft) Uplift (lbs) Down (lbs)
Zone(1)6 16.5 252.7 194.1
Zone(2r)6 16.5 302.3 194.1
Zone(2e)6 16.5 302.3 194.1
Zone(3)6 16.5 289.9 194.1
Conservative Max=302.3 < 760
CONNECTION IS OK
Risk Category =
KZ =
Kd =
Ke =
2. Embedment is measured from the top of the framing member to the tapered tip of a lag screw.
Embedment in sheading or other material does not count.
II
V=
Exposure =
1. Pv seismic dead weight is negligible to result in significant seismic uplift, therefore the wind uplift
governs
E=
a=
KZt =
qh= 0.00256KzKztKdKeV2=
Pitch =
Lag Screw Penetration
projects@evengineersnet.com
http://www.evengineersnet.com
V
V
V V
V V
~EV
ENGINEERING
Vertical Load Resisting System Design
Roof Framing Trusses
Snow Load Fully Exposed
pg= 0 psf Ct =1.1
Ce =0.9 Is =1.0 ps = 0 psf
pf = 0 psf pfmin. = 0.0 psf 0 plf
Max Length, L = 7.3 ft
Tributary Width, WT =24 in
RLL = 20 psf 18.41 plf
Dr = 15 psf 30 plf
PvDL =3 psf 6 plf
Load Case: DL w= 28 plf
M= 116 lb-ft
Mallowable = Sx x Fb'= 309 lb-ft > 116 lb-ft OK
Load Case: DL+RLL DL+Lr= 40 plf
Mdown=167 lb-ft
Mallowable = Sx x Fb'= 429 lb-ft > 167 lb-ft OK
Load Case: DL+S DL+S= 36 plf
Mdown=149 lb-ft
Mallowable = Sx x Fb'= 412 lb-ft > 149 lb-ft OK
Load Case: DL+0.6W w= 46.5 plf
Mu=192 lb-ft
Mallowable = Sx x Fb' (wind)= 549 lb-ft > 192 lb-ft OK
Load Case: 0.6DL+0.6W w= 29.2 plf
Mu=121 lb-ft
Mallowable = Sx x Fb' (wind)= 549 lb-ft > 121 lb-ft OK
DL+0.45W+0.75(RLL or S)42 plf
Mdown=172 lb-ft
Mallowable = Sx x Fb'= 549 lb-ft > 172 lb-ft OK
Member Capacity
DF-L No.2
2X4 CL CF Ci CrFb =900 psi 1.0 1.3 1.0 1.15 1346 psi
Fv =180 psi N/A N/A 1.0 N/A 180 psi
E =1600000 psi N/A N/A 1.0 N/A 1600000 psi
Emin =580000 psi N/A N/A 1.0 N/A 580000 psi
Depth, d = 3.5 in
Width, b = 1.5 in
Cross-Sectonal Area, A = 5.25 in2
Moment of Inertia, Ixx =5.35938 in4
Section Modulus, Sxx =3.0625 in3
Allowable Moment, Mall = Fb'Sxx =343.4 lb-ft DCR=Mu/Mall =0.39 < 1 Satisfactory
Allowable Shear, Vall = 2/3Fv'A =630.0 lb DCR=Vu/Vall =0.37 < 1 Satisfactory
Design Value Adjusted Value
projects@evengineersnet.com
http://www.evengineersnet.com
~EV
ENGINEERING
------
Siesmic Loads Check
Roof Dead Load 15 psf
% or Roof with Pv 13.6%
Dpv and Racking 3 psf
Average Total Dead Load 15.4 psf
Increase in Dead Load 1.5%OK
Limits of Scope of Work and Liability
The increase in seismic Dead weight as a result of the solar system is less than 10% of the existing structure and
therefore no further seismic analysis is required.
We have based our structural capacity determination on information in pictures and a drawing set titled PV plans -
DAN GRANT. The analysis was according to applicable building codes, professional engineering and design
experience, opinions and judgments. The calculations produced for this structure's assessment are only for the
proposed solar panel installation referenced in the stamped plan set and were made according to generally
recognized structural analysis standards and procedures.
projects@evengineersnet.com
http://www.evengineersnet.com
~EV
ENGINEERING
I I