HomeMy WebLinkAbout1781 SKIMMER CT; ; CBR2021-1547; PermitPERMIT REPORT
Residential Permit
Print Date: 07/25/2022
Job Address: 1781 SKIMMER CT, CARLSBAD, CA 92011-3609
Permit Type:
Parcel#:
Valuation:
Occupancy Group:
#of Dwelling Units:
Bedrooms:
Bathrooms:
Project Title:
BLDG-Residential
2150505700
$12,758.80
Work Class:
Track#:
Lot#:
Project#:
Plan#:
Construction Type:
Orig. Plan Check#:
Plan Check#:
Description: HILAL: DETACHED TRELLIS (485 SF)/ !RETAINING WALL
Applicant: Property Owner:
Patio
ANTONIO E MONTI JR
ANTONIO MONTI JR
525 W BOBIER DR
VISTA, CA 92083-1811
(951) 448-3302
CO-OWNERS HILAL BASIM AND POOLJANINE
1781 SKIMMER CT
CARLSBAD, CA 92011
FEE
SB1473 -GREEN BUILDING STATE STANDARDS FEE
SWPPP PLAN REVIEW FEE TIER 1 -Medium
SWPPP INSPECTION FEE TIER 1 -Medium BLDG
STRONG MOTION -RESIDENTIAL (SMIP)
PATIO -FRAME WITH COVER
DETACHED ACCESSORY & UTILITY USES
Total Fees: $958.86 Total Payments To Date: $958.86
(city of
Carlsbad
Permit No: CBR2021-1547
Status: Closed -Finaled
Applied: 05/27/2021
Issued: 12/01/2021
Fina led Close Out: 07/12/2022
Inspector:
Final Inspection:
TKers
07/12/2022
Contractor:
JOEY TAM BORELLI
3326 WILD OAK LN
ESCONDIDO, CA 92027-6508
{760) 802-7040
Balance Due:
AMOUNT
$1.00
$64.00
$271.00
$1.66
$100.00
$521.20
$0.00
Please take NOTICE that approval of your project includes the "Imposition" of fees, dedications, reservations, or other exactions hereafter
collectively referred to as "fees/exaction." You have 90 days from the date this permit was issued to protest imposition of these
fees/exactions. If you protest them, you must follow the protest procedures set forth in Government Code Section 66020{a), and file the
protest and any other required information with the City Manager for processing in accordance with Carlsbad Municipal Code Section
3.32.030. Failure to timely follow that procedure will bar any subsequent legal action to attack, review, set aside, void, or annul their
imposition.
You are hereby FURTHER NOTIFIED that your right to protest the specified fees/exactions DOES NOT APPLY to water and sewer connection
fees and capacity changes, nor planning, zoning, grading or other similar application processing or service fees in connection with this
project. NOR DOES IT APPLY to any fees/exactions of which you have previously been given a NOTICE similar to this, or as to which the
statute of limitation has previously otherwise expired.
1635 Faraday Avenue I Carlsbad, CA 92008-7314 I 442-339-2719 I 760-602-8560 f I www.carlsbadca.gov
Ccityof
Carlsbad
Job Address 1781 SKIMMER CT
RESIDENTIAL
BUILDING PERMIT
APPLICATION
B-1
Plan Check C{2;/l,2ft?I-Jstf7
Est. Value
PC Deposit ----.------=----
Date ---=-5l~P-k'----=-l-12-----'-I_
Suite: APN: 215-050-57-00 -----
CT/Project#: _________________ Lot#: ___ _
Fire Sprinklers: 0 YES 0 NO
BRIEF DESCRIPTION OF WORK:
Air Conditioning: 0 YES 0 NO Electrical Panel Upgrade: 0 YES 0 NO
PROPOSE DETACHED WOOD/ ALUMINUM TRELLIS COVE~ 10'-6" HIGH 55 FT OF 5 FT HIGH RET WALL ~~o
~ Addition/New: _____ Living SF, ___ Deck SF, 485 Patio SF, ___ Garage SF
Is this to create an Accessory Dwelling Unit? 0 Y 0 N New Fireplace? 0 Y 0 N, if yes how many? __
D Remodel: ____ SF of affected area Is the area a conversion or change of use ? 0 Y ON
0 Pool/Spa: ____ SF Additional Gas or Electrical Features? STUB GAS TO BBQ, HEATERS
□solar: ___ KW, __ Modules, Mounted:0Roof QGround, Tilt:O YO N, RMA: 0 YON,
Battery:OY ON, Panel Upgrade: OY ON
D Reroof: __________________________________ _
0 Plumbing/Mechanical/Electrical Only: 2 CIRCUITS FOR LIGHTS, FANS, outlets
D Other:----------------------------------
APPLICANT (PRIMARY CONTACT)
Name: ANTONIO MONTI
Address: 525 W BOBIER DR
City: VISTA State:._C_A_...;Zip: 92083
Phone: 442-33-8173
Email: DRAW4U2@GMAIL.COM
DESIGN PROFESSIONAL
Name: SERVIN ENGINEERING INC
Address: 2647 GATEWAY RD
City: CARLSBAD
Phone: 760-931-1792
State:_C_A_...;Zip: 92009
Email: NICKSERVIN@GMAIL.COM
PROPERTY OWNER
Name: BASIM & JENINE HILAL
Address: 1781 SKIMMER CT
City: CARLSBAD
Phone: 858-284-9415
State: CA Zip: _9_20_1_1 __ _
Email: ___________________ _
CONTRACTOR BUSINESS
Name: TAMBORELLI CONST co.
Address: 3326 WILD OAK LN
City: ESCONDIDO State:_C_A_zlp: 92027
Phone: 760-802-7040
Email: PHILIP@TEAMG7.COM
Architect State License: _3_3_53_8__________ State License:_34_51_9_0 ___ Bus. License: ______ _
(Sec. 7031.S Business and Professions Code: Any City or County which requires a permit to construct, alter, improve, demolish or ~a\~si~eii~~s I
issuance, also requires the applicant for such permit to file a signed statement that he/she is licensed pursuant to the provisions of the Contractor's License law
{Chapter 9, commending with Section 7000 of Division 3 of the Business and Professions Code} or that he/she is exempt therefrom, and the basis for the alleged
exemption. Any violation of Section 7031.S by any applicant for a permit subjects the applicant to a civil penalty of not more than five hundred dollars {$500}).
1635 Faraday Ave Carlsbad, CA 92008 Ph: 760-602-2719 Fax: 760-602-8558 Email: Building@carlsbadca.gov
8-1 Page 1 of2 Rev. 06/18
( OPTION A ): WORKERS'COMPENSATION DECLARATION:
I hearby affirm under penalty of perjury one of the following declarations: 0 I have and will maintain a certificate of consent to self-insure for workers' compensation provided by Section 3700 of the Labor Code, for the performance of the
work which this permit is issued.
01 have and will maintain worker's compensation, as required by Section 3700 of the Labor Code, for the performance of the work for which this permit is issued.
My workers' compensation insurance carrier and policy number are: Insurance Company Name: INSURANCE COMPANY OF THE WEST
Polley No. WSD5040771 Expiration Date: _04_1_1312_0_2_2 ______ _
D Certificate of Exemption: I certify that in the performance of the work for which this permit is issued, I shall not employ any person in any manner so as to be come
subject to the workers' compensation Laws of California. WARNING: Failure to secure workers compensation coverage Is unlawful, and shall subject an employer to
criminal penalties and civil fines up to $100,000.00, In addition the to the cost of compensation, damages as provided for In Section 3706 of the Labor Code,
Interest and attorney's fees.
CONTRACTOR SIGNATURE: _Jo_E_Y_TAM_e_oR➔Ci7----'L'-"" .... =---11/-/\. ..... " .... -'-::i_,_Q...,..~=\:\::_-~_:-__ D AGENT DATE: _o_S12_112_0_21 ___ _
( OPTION B ): OWNER-BUILDER DECLARATION:
I hereby affirm that I am exempt from Contractor's license Law for the following reason:
DI, as owner of the property or my employees with wages as their sole compensation, will do the work and the structure is not intended or offered for sale (Sec.
7044, Business and Professions Code: The Contractor's License Law does not apply to an owner of property who builds or improves thereon, and who does such work
himself or through his own employees, provided that such improvements are not intended or offered for sale. If, however, the building or improvement is sold within
one year of completion, the owner-builder will have the burden of proving that he did not build or improve for the purpose of sale).
0 I, as owner of the property, am exclusively contracting with licensed contractors to construct the project (Sec. 7044, Business and Professions Code: The
Contractor's License Law does not apply to an owner of property who builds or improves thereon, and contracts for such projects with contractor(s) licensed
pursuant to the Contractor's License Law).
DI am exempt under Section _______ Business and Professions Code for this reason:
1. I personally plan to provide the major labor and materials for construction of the proposed property Improvement. QYES Q NO
2. I (have/ have not) signed an application for a building permit for the proposed work.
3. I have contracted with the following person (firm) to provide the proposed construction (include name address/ phone/ contractors' license number):
4. I plan to provide portions of the work, but I have hired the following person to coordinate, supervise and provide the major work (include name/ address/ phone/
contractors' license number):
5. I will provide some of the work, but I have contracted (hired) the following persons to provide the work indicated (include name/ address/ phone / type of work):
OWNER SIGNATURE: □AGENT DATE: ______ _ --------------------------
CONSTRUCTION LENDING AGENCY, IF ANY:
I hereby affirm that there Is a construction lending agency for the performance of the work this permit is issued (Sec. 3097 (i) Civil Code).
Lender's Name: NA Lender's Address: ____________________ _
ONLY COMPLETE THE FOLLOWING SECTION FOR NON-RESIDENTIAL BUILDING PERMITS ONLY:
Is the applicant or future building occupant required to submit a business plan, acutely hazardous materials registration form or risk management and prevention
program under Sections 25505, 25533 or 25534 ofthe Presley-Tanner Hazardous Substance Account Act? Yes/ No
Is the applicant or future building occupant required to obtain a permit from the air pollution control district or air quality management district? Yes / No
Is the facility to be constructed within 1,000 feet of the outer boundary of a school site? Yes / No
IF ANY OF THE ANSWERS ARE YES, A FINAL CERTIFICATE OF OCCUPANCY MAY NOT BE ISSUED UNLESS THE APPLICANT HAS MET OR IS MEETING THE
REQUIREMENTS OF THE OFFICE OF EMERGENCY SERVICES AND THE AIR POLLUTION CONTROL DISTRICT.
APPLICANT CERTIFICATION:
I certify that I have read the application and state that the above information is correct and that the information on the plans is accurate. I agree to comply with all
City ordinances and State laws relating to building construction.
I hereby authorize representative of the City of carlsbad to enter upon the above mentioned property for inspection purposes. I ALSO AGREE TO SAVE, INDEMNIFY AND KEEP
HARMLESS THE CITY OF CARLSBAD AGAINST ALL UABIUTIES, JUDGMENTS, COSTS AND EXPENSES WHICH MAY IN ANY WAY ACCRUE AGAINST SAID CITY IN CONSEQUENCE OF
THE GRANTING OF THIS PERMIT.OSHA: An OSHA permit is required for excavations over 5'0' deep and demolition or construction of structures over 3 stories in height.
EXPIRATION: Every permit issued by the Building Official under the provisions of this Code shall expire by limitation and become null and void if the building or work authorized
by such permit is not commenced within 180 days from the date of such permit or if the building or work authorized by such permit is suspended or abandoned at any time
after the work is commenced for a period of 180 days (Section 106.4.4 Uniform Building Code).
APPLICANT SIGNATURE: _P_H_Iu_P_uZAR __ RA_G_o __________________ DATE: 0512112021
1635 Faraday Ave Carlsbad, CA 92008
B-1
Ph: 760-602-2719 Fax: 760-602-8558
Page 2 of2
Email: Building@carlsbadca.gov
Rev. 06/18
Building Permit Inspection History Finaled
{city of
Carlsbad
PERMIT INSPECTION HISTORY for (CBR2021-1547)
Permit Type: BLDG-Residential Application Date: 05/27/2021 Owner: CO-OWNERS HILAL BASIM AND POOL
Work Class: Patio
Status: Closed -Finaled
JANINE
Issue Date: 12/01/2021 Subdivision:
Expiration Date: 08/23/2022
IVR Number: 33656
Address: 1781 SKIMMER CT
CARLSBAD, CA 92011-3609
Scheduled
Date
Actual Inspection Type
Start Date
Inspection No. Inspection Primary Inspector Reinspection Inspection
12/07/2021
12/21/2021
12/07/2021 BLDG-SW-Pre-Con
Checklist Item
172008-2021
COMMENTS
Status
Passed Tim Kersch
BLDG-Building Deficiency
12/21/2021 BLDG-11 173130-2021 Partial Pass Tim Kersch
Foundatlon/Ftg/Piers
(Rebar)
Checklist Item
BLDG-Building Deficiency
COMMENTS
Requested confirmation location of
footings.
02/24/2022 02/24/2022 BLDG-11 177181-2022 Passed Tim Kersch
Foundation/Ftg/Piers
(Rebar)
Checklist Item
BLDG-Building Deficiency
COMMENTS
Requested confirmation location of
footings.
07/12/2022 07/12/2022 BLDG-Final Inspection 186724-2022 Passed Tim Kersch
Monday, July 25, 2022
Checklist Item
BLDG-Building Deficiency
BLDG-Plumbing Final
BLDG-Mechanical Final
BLDG-Structural Final
BLDG-Electrical Final
COMMENTS
Complete
Passed
Yes
Re inspection Incomplete
Passed
Yes
Complete
Passed
Yes
Complete
Passed
Yes
Yes
Yes
Yes
Yes
Page 1 of 1
DATE: October 20, 2021
JURISDICTION: Carlsbad
• 1W
INTERWEST
A SAF'Ebultt COMPANY
PLAN CHECK#.: CBR2021-1547 Rev 1
PROJECT ADDRESS: 1781 Skimmer Ct
SET: III
□ APPLICANT
□ JURIS.
PROJECT NAME: Hilas Residence -Proposed Detached Wood/ Aluminum Trellis Cover
and Retaining Wall
~ The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction's building codes.
D The plans transmitted herewith will substantially comply with the jurisdiction's codes
when minor deficiencies identified below are resolved and checked by building department staff.
D The plans transmitted herewith have significant deficiencies identified on the enclosed check list
and should be corrected and resubmitted for a complete recheck.
D The check list transmitted herewith is for your information. The plans are being held at lnterwest
until corrected plans are submitted for recheck.
D The applicant's copy of the check list is enclosed for the jurisdiction to forward to the applicant
contact person.
D The applicant's copy of the check list has been sent to:
~ lnterwest staff did not advise the applicant that the plan check has been completed.
D lnterwest staff did advise the applicant that the plan check has been completed .
Person contacted : (~A) Telephone#:
Date contacted : (by:'\f) Email:
Mail Telephone Fax In Person
0 REMARKS:
By: Abe Doliente
lnterwest
10/12/21
Enclosures: Original set of approved plans.
9320 Chesapeake Drive, Suite 208 ♦ San Diego, California 92123 ♦ (858) 560-1468 ♦ Fax (858) 560-1576
• lW
INTERWEST
DATE: October 2, 2021
JURISDICTION: Carlsbad
PLAN CHECK#.: CBR2021-1547 Rev 1
PROJECT ADDRESS: 1781 Skimmer Ct
SET: II
0 APPLICANT
□ JURIS.
PROJECT NAME: Hilas Residence -Proposed Detached Wood/Aluminum Trellis Cover
and Retaining Wall
D The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction's building codes.
D The plans transmitted herewith will substantially comply with the jurisdiction's codes
when minor deficiencies identified below are resolved and checked by building department staff.
D The plans transmitted herewith have significant deficiencies identified on the enclosed check list
and should be corrected and resubmitted for a complete recheck.
~ The check list transmitted herewith is for your information. The plans are being held at lnterwest
until corrected plans are submitted for recheck.
D The applicant's copy of the check list is enclosed for the jurisdiction to forward to the applicant
contact person.
~ The applicant's copy of the check list has been sent to:
Antonio Monti
D lnterwest staff did not advise the applicant that the plan check has been completed.
D lnterwest staff did advise the applicant that the plan check has been completed.
Person contacted: Antonio Monti Telephone#: no info
Date contacted:
Mail Telephone
0 REMARKS:
By: Abe Doliente
lnterwest
(by: ) Email: draw4u2@gmail.com
Fax In Person
Enclosures:
9/24/21
9320 Chesapeake Drive, Suite 208 ♦ San Diego, California 92 123 ♦ (858) 560-1468 ♦ Fax (858) 560-1576
DATE: 8 -4-2021
JURISDICTION: Carlsbad
• 1W
INTERWEST
A SAFEbullr COMi .!lr,l'r'
PLAN CHECK#.: CBR2021-1547.RC1
PROJECT ADDRESS: 1781 Skimmer Ct
SET: II
□ APPLICANT
□ JURIS.
PROJECT NAME: Hilal Res -Proposed detached wood/aluminum trellis cover and
retaining wall
D The plans transmitted herewith have been corrected where necessary and substantially comply
w ith the jurisdiction's codes.
[2J The plans transmitted herewith will substantially comply with the jurisdiction's building codes
when minor deficiencies identified below are resolved and checked by building department staff.
D The check list transmitted herewith is for your information. The plans are being held at lnterwest
until corrected plans are submitted for recheck.
D The applicant's copy of the check list is enclosed for the jurisdiction to forward to the applicant
contact person.
D The applicant's copy of the check list has been sent to:
[2J lnterwest staff did not advise the applicant that the plan check has been completed.
D lnterwest staff did advise the applicant that the plan check has been completed.
Person contacted: Telephone#:
Date contacted: (by: Email:
Mail Te lephone Fax In n
[2J REMARKS: Sheets A-2 and SD-1, must be stamped and signed by Nick Servin,
P .E. C33538 before permit can be issued. All other sheets must just be
signed by designer.
By: Erich A. Kuchar, P.E.
lnterwest
Enclosures:
9320 Chesapeake Drive, Suite 208 ♦ San Diego, California 92 123 ♦ (858) 560-1468 ♦ Fax (858) 560-1576
Carlsbad CBR2021-154 7 Rev 1
October 2, 2021
NOTE: The items listed below are from the previous correction list. These remaining
items have not been adequately addressed. The numbers of the items are from the
previous check list and may not necessarily be in sequence. The notes in bold font are
current.
GENERAL PLAN CORRECTION LIST
JURISDICTION: Carlsbad
1
PROJECT ADDRESS: 1781 Skimmer Ct
DATE PLAN RECEIVED BY
ESGIL: 9/24/21
REVIEWED BY: Abe Doliente
FOREWORD (PLEASE READ):
PLAN CHECK#.: CBR2021-1547 Rev
DATE REVIEW COMPLETED:
October 2, 2021
This plan review is limited to the technical requirements contained in the International Building
Code, Uniform Plumbing Code, Uniform Mechanical Code, National Electrical Code and state
laws regulating energy conservation, noise attenuation and disabled access. This plan review is
based on regulations enforced by the Building Department. You may have other corrections
based on laws and ordinances enforced by the Planning Department, Engineering Department
or other departments.
The following items listed need clarification, modification or change. All items must be satisfied
before the plans will be in conformance with the cited codes and regulations. The approval of
the plans does not permit the violation of any state, county or city law.
• Please make all corrections, as requested in the correction list. Submit FOUR new complete
sets of plans for commercial/industrial projects (THREE sets of plans for residential projects).
For expeditious processing, corrected sets can be submitted in one of two ways:
1. Deliver all corrected sets of plans and calculations/reports directly to the City of Carlsbad
Building Department, 1635 Faraday Ave., Carlsbad, CA 92008, (760) 602-2700. The City will
route the plans to lnterwest and the Carlsbad Planning, Engineering and Fire Departments.
2. Bring TWO corrected set of plans and calculations/reports to lnterwest, 9320
Chesapeake Drive, Suite 208, San Diego, CA 92123, (858) 560-1468. Deliver all
remaining sets of plans and calculations/reports directly to the City of Carlsbad Building
Department for routing to their Planning, Engineering and Fire Departments.
NOTE: Plans that are submitted directly to lnterwest only will not be reviewed by the City
Planning, Engineering and Fire Departments until review by lnterwest is complete.
• To facilitate rechecking, please identify, next to each item, the sheet of the plans upon
which each correction on this sheet has been made and return this sheet with the
revised plans.
Carlsbad CBR2021-154 7 Rev 1
October 2, 2021
• Please indicate here if any changes have been made to the plans that are not a result of
corrections from this list. If there are other changes, please briefly describe them and where
they are located on the plans. Have changes been made not resulting from this list?
□ Yes □ No
ONLY ITEM NO. 4 IS RESOLVED AS A RESULT OF SET II SU BM ITT AL. THERE WERE NO
RESPONSES FOR ITEMS 1 THRU 3. PLEASE READ THE INSTRUCTIONS BEFORE YOU
RESUBMIT SET Ill TO SAVE SOME TIME.
1. Please submit a copy of the building permit application for this revision.
2. Submit a summary of the changes that are made from the original set of approved plans.
3. All sheets of the revised plans must be signed by the person responsible for their
preparation.
The jurisdiction has contracted with EsGil, located at 9320 Chesapeake Drive, Suite 208, San
Diego, California 92123; telephone number of 858/560-1468, to perform the plan review for your
project. If you have any questions regarding these plan review items, please contact Abe
Doliente at Esgil. Thank you.
...
DATE: 6-14-2021
JURISDICTION: Carlsbad
• 1W
IN TE RW E ST
A SAFEbu,ll COMPANV
PLAN CHECK#.: CBR2021-1547
PROJECT ADDRESS: 1781 Skimmer Ct
SET: I
□ APPLICANT
□ JURIS.
PROJECT NAME: Hilal Res -Proposed detached wood/aluminum trellis cover and
retaining wall
D The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction's codes.
D The plans transmitted herewith will substantially comply with the jurisdiction's codes
when minor deficiencies identified below are resolved and checked by building department staff.
cg] The check list transmitted herewith is for your information. The plans are being held at lnterwest
until corrected plans are submitted for recheck.
D The applicant's copy of the check list is enclosed for the jurisdiction to forward to the applicant
contact person .
D The applicant's copy of the check list has been sent to:
D lnterwest staff did not advise the applicant that the plan check has been completed.
cg] lnterwest staff did advise the applicant that the plan check has been completed.
Person contacted: Antonio Monti
Date contacted : (by:
Telephone#: not provided
) Email: draw4u2@gmail.com
Mail Telephone Fax In Person
0 REMARKS:
By: Erich A. Kuchar, P.E.
lnterwest
5-28-2021
Enclosures:
9320 Chesapeake Drive, Suite 208 ♦ San Diego, California 92123 ♦ (858) 560-1468 ♦ Fax (858) 560-1576
Carlsbad CBR2021-1547
6-14-2021
PLAN REVIEW CORRECTION LIST
SINGLE FAMILY DWELLINGS AND DUPLEXES
PLAN CHECK#.: CBR2021-1547
PROJECT ADDRESS: 1781 Skimmer Ct
FLOOR AREA: 485 sqft patio cover
220 sqft of wall
REMARKS:
DATE PLANS RECEIVED BY
JURISDICTION:
DATE INITIAL PLAN REVIEW
COMPLETED: 6-14-2021
FOREWORD (PLEASE READ):
JURISDICTION: Carlsbad
STORIES: 1
HEIGHT: 10'-6"
DATE PLANS RECEIVED BY
ESGIL CORPORATION: 5-28-2021
PLAN REVIEWER: Erich A. Kuchar, P.E.
This plan review is limited to the technical requirements contained in the California Residential
Code, California Building Code, California Plumbing Code, California Mechanical Code,
California I Electrical Code and state laws regulating energy conservation, noise attenuation and
access for the disabled. This plan review is based on regulations enforced by the Building
Department. You may have other corrections based on laws and ordinance by the Planning
Department, Engineering Department, Fire Department or other departments. Clearance from
those departments may be required prior to the issuance of a building permit.
Present California law mandates that construction comply with the 2019 edition of the California
Code of Regulations (Title 24), which adopts the following model codes: 2019 CRC, 2019 CBC,
2019 CPC, 2019 CMC and 2019 CEC.
The above regulations apply, regardless of the code editions adopted by ordinance.
The following items listed need clarification, modification or change. All items must be satisfied
before the plans will be in conformance with the cited codes and regulations. Per Sec. 105.4 of
the 2019 California Building Code, the approval of the plans does not permit the violation of any
state, county or city law.
To speed up the recheck process, please note on this list (or a copy) where each
correction item has been addressed, i.e., plan sheet number, specification section, etc.
Be sure to enclose the marked up list when you submit the revised plans.
Carlsbad CBR2021-1547
6-14-2021
PLANS
1. Please make all corrections, as requested in the correction list. Submit FOUR new
complete sets of plans for commercial/industrial projects (THREE sets of plans for
residential projects). For expeditious processing, corrected sets can be submitted
in one of two ways:
1. Deliver all corrected sets of plans and calculations/reports directly to the City of
Carlsbad Building Department, 1635 Faraday Ave., Carlsbad, CA 92008, (760)
602-2700. The City will route the plans to lnterwest and the Carlsbad Planning,
Engineering and Fire Departments.
2. Bring TWO corrected set of plans and calculations/reports to lnterwest, 9320
Chesapeake Drive, Suite 208, San Diego, CA 92123, (858) 560-1468. Deliver all
remaining sets of plans and calculations/reports directly to the City of Carlsbad
Building Department for routing to their Planning, Engineering and Fire
Departments.
NOTE: Plans that are submitted directly to lnterwest only will not be reviewed by
the City Planning, Engineering and Fire Departments until review by lnterwest is
complete.
2. A reminder that due to Covid-19, the City will not permit counter corrections.
Please make sure all the items are satisfied; otherwise, another round of
corrections will be necessary.
3. All sheets of plans must be signed by the person responsible for their
preparation. (California Business and Professions Code).
4. Sheets A-2 and SD-1, and any other structural sheets that will be added·are
required to be stamped and signed by Nick Servin, P.E. C33538.
STRUCTURAL
5. Update plan call outs to have wood columns embedded in concrete to specify
pressure-preservative treated wood. (Section R317.1).
6. Update all beam calcs and plans for correct 20 psf live load. Cales are currently
using 10 psf live load which is incorrect.
7. Update plans and calcs for using correct dead load in lateral analysis to match
that of gravity loading. Dead load should be 10 psf not 5 psf as used in cal cs on
page L3. Wx should equal 464 sqft x 10 psf = 4,640 lbs.
8. Provide complete retaining wall analysis and structural details for max height of
5'-0" retaining wall. Keep in mind that not only does it need to resist the soil loads
but also that of the dead load of the new patio slab on grade and live load
Carlsbad CBR2021-1547
6-14-2021
surcharge. Wall calcs must show this 60 psf live load and 50 psf dead load (for 4"
slab on grade) surcharge.
9. Update detail 1 & 2/SD-1 to show correct reinforcement spacing, size, and hook
detail. Sheet A-2 calls out for #4's at 12"OC EW? How can caisson reinforcement
go each way? Is this supposed to be #4 ties at 12" OC? Provide detail and
update plans and calcs as rewired with new loading from comment #7.
MECHANICAL
10. Please provide listing information for the outdoor cooking appliance to verify
clearance to combustibles and overhead protection. If this is an unlisted
appliance, it cannot be installed beneath a combustible overhead. CMC Section
921 .0.
MISCELLANEOUS
11 . To speed up the review process, note on this list (or a copy) where each
correction item has been addressed, i.e., plan sheet, note or detail number,
calculation page, etc.
12. Please indicate here if any changes have been made to the plans that are not a
result of corrections from this list. If there are other changes, please briefly
describe them and where they are located in the plans.
• Have changes been made to the plans not resulting from this correction list?
Please indicate:
Yes □ No □
13. The jurisdiction has contracted with lnterwest, located at 9320 Chesapeake
Drive, Suite 208, San Diego, California 92123; telephone number of
858/560-1468, to perform the plan review for your project. If you have any
questions regarding these plan review items, please contact Erich A. Kuchar,
P.E. at lnterwest. Thank you.
Carlsbad CBR2021-1547
6-14-2021
[DO NOT PAY -THIS IS NOT AN INVOICE]
VALUATION AND PLAN CHECK FEE
JURISDICTION: Carlsbad
PREPARED BY: Erich A. Kuchar, P.E.
BUILDING ADDRESS: 1781 Skimmer Ct
BUILDING OCCUPANCY: R-3
BULDING AREA
PORTION (Sq.Ft.)
patio cover 485
retiaring wal 220
Air Conditioring
Fire Sprinklers
TOTAL VALUE
Jurisdiction Code cb
j 1997 UBC Building Ptrmit Ftt iJ
l J"\I ~":
I 1997 UBC Plan Chtck Fet
I :.4\1 }it:
i.l
Vabltion
~
15.41
24.65
By Ordinance
Type of Review: P Complete Review
r Repetitive Fee -,
~ Repeats
r Other
r t-tomy
EIIGIFee
~
Reg.
Mod.
PLAN CHECK#.: CBR2021-1547
DATE: 6 -14-2021
VALUE ($)
7,474
5,423
12,897
1 ,
r Structural Only
$91.78,
Sheet 1 of 1
Structural Calculations
For
Project:
Hilal Patio
1781 Skimmer Court
Carlsbad, CA 92009
c/o
G7 Landscape
Phillip Lizarraga
3129 Tiger Run Court
Carlsbad, CA 92010
760-305-3122
Nick Servin
Servin Engineering, Inc.
2647 Gateway Road, Suite 105-500
Carlsbad, CA 92009
(760) 931-1792, FAX: (760) 931-1892
nickservin@imail.com C'-f'i
JOB NUMBER: 22667 I\ \
May 15, 2021
RCE 33,538
Engineer does not take any responsibility for construction, or control of the job. Engineer's responsibility is solely limited
to the design of the structural members included herein. Any changes to design, structural members or configuration shall
void calculations. Supervision may be contracted for assurance of proper construction.
SHEET INDEX
No. DESCRIPTION SHEETS
Engineering Assumptions
2 Framing Calculations Fl-F8
3 Foundation calculation Pl
4 Lateral Calculations Ll-L6
, __
ENGINEERING ASSUMPTIONS
LOADS:
ROOF:
DEAD LOADS:
TILE
FRAMING
DRYWALL
MISC.
PLYWOOD
TOTAL
LIVE LOADS:
SLOPE <4:12
SLOPE >4:12
FLOOR:
DEAD LOADS:
FRAMING
PLYWOOD
CARPET/PAD
CEILING
MISCELLANEOUS
WALLS:
LIVE LOADS:
FLOOR
DECK
TOTAL
12 PSF SHINGLES
3.0 PSF
2.5 PSF
1.0 PSF
Ll PSF
20.0 PSF
20 PSF
16 PSF
6 PSF
3 PSF
1 PSF
3 PSF
2 PSF
15 PSF
12 PSF
40 PSF
60 PSF
2.0 PSF
3.0
2.5
1.0
1.5 PSF
10 PSF
SOILS INVESTIGATION BY: None Available 1,500 PSF SOIL BEARING PRESSURE
FRAMING:
2X , 4X FRAMING DFL #2 MIN U. N. 0.
6X & LARGER DFL #1 MIN U. N. 0.
P ARALLAMS 2.0E WS
CONCRETE:
STEEL:
Fv
PSI
95
85
290
Fb
PSI
875
1,350
2,900
2,500 AT 28 DAYS
40,000 PSI
E
PSI
1,600,000
1,600,000
2,000,000
BUILDING DESIGN CRITERIA
The design criterion for development in the project City or County is based on the 2019 California Building
Code. The design criteria are minimum standards and must be supported by structural calculations and
geothechnical reports when used in the design of structures within the city. Basis is CBC Chapter 16 and
ASCE 7.
ADOPTED CODES
2019 California Building Code
2019 California Energy Code
2019 California Electrical Code
2019 California Plumbing Code
2019 California Mechanical Code
2019 California Fire Code
Roof Live Load =
Floor Live Load =
Deck Live Load =
SEISMIC DESIGN
Seismic Importance = l
20 psf Reducible
40 psf
60 psf
Seismic Design Category "D" for Occupancy Categories I, II, and III
Seismic Design Coefficients and factors per ASCE
Ss = 0.993 Fa = 1.2
Sds = 0.794 Sdl = null
Assume site soil Class "D"
WIND DESIGN
Basic wind speed 96 at 3-second gust
Basic wind pressure 17.05 psf
Exposure "D" for most areas
Sl = 0.361
Sms = 1.192
Rainfall 3 inches per hour for design of roof drains
Fv = null
Sml = null
R = 1.50
V =0.53w
Servin Engineering, Inc.
2647 Gateway Road# 105-500
Carlsbad, CA 92009
Nick Servin, PE
760-533-6532
nickservin mail.com
Project Title:
Engineer:
Project ID:
Project Descr:
Printed 14 MAY 2021 4 32PM
Wood Beam Software copyright ENERc.ALC, INC. 1983-2020, Buid:12.20.8.24
1 ,1
DESCRIPTION: RB-1 TRELLIS BEAM
CODE REFERENCES
Calculations per NOS 2018, IBC 2018, CBC 2019, ASCE 7-16
Load Combination Set : ASCE 7-16
Material Pro erties
Analysis Method : Allowable Stress Design Fb +
Load Combination ASCE 7-16 Fb -
Fe-Prll
Wood Species : Douglas Fir-Larch Fe -Perp
Wood Grade : No. 1 Fv
Ft
Beam Bracing : Beam is Fully Braced against lateral-torsional buckling
' D(0.05) Lr(0.05)
' f 6x10
Span= 13.0 ft
1,000.0psi
1,000.0psi
1,500.0psi
625.0psi
180.0psi
675.0psi
E : Modulus of Elasticity
Ebend-xx 1,700.0 ksi
Emlnbend -xx 620.0ksi
Density 31 .210pcf
' t
~
A lied Loads Service loads entered Load Factors will be applied for calculations
Uniform Load : D = 0.010, Lr= 0.010 ksf, Tributary Width = 5.0 ft, (Trellis)
DESIGN SUMMARY
Maximum Bending Stress Ratio
Section used for this span
fb: Actual
Fb: Allowable
Load Combination
Location of maximum on span
Span # where maximum occurs
Maximum Deflection
Max Downward Transient Deflection
Max Upward Transient Deflection
Max Downward Total Deflection
Max Upward Total Deflection
Overall Maximum Deflections
Load Combination
+O+lr
Vertical Reactions
Load Combination
Overall MAXimum
Overall MINimum
DOnly
+D+Lr
+D+0.750Lr
+0.60D
Lr Only
Span
=
=
=
=
=
0.24S 1 Maximum Shear Stress Ratio
6x10 Section used for this span
306.42psi fv: Actual
1,250.00 psi Fv: Allowable
+D+Lr Load Combination
6.500ft Location of maximum on span
Span# 1 Span # where maximum occurs
0.048 in Ratio = 3224 >=360
0.000 in Ratio= 0<360
0.097 in Ratio= 1612>=180 0.000 in Ratio= 0<180
Max.•-· Deft Location in Span Load Combination
0.0968 6.547
Support notation : Far left is #1
Support 1
0.650
0.325
0.325
0.650
0.569
0.195
0.325
Support 2
0.650
0.325
0.325
0.650
0.569
0.195
0.325
Desi n OK
= 0.073: 1
6x10
16.48 psi
= 225.00 psi
+D+Lr
= 12.241 ft
Span# 1
Max. '+' Deft Location In Span
0.0000 0.000
Values in KIPS
Fl
Servin Engineering, Inc.
2647 Gateway Road# 105-500
Carlsbad, CA 92009
Nick Servin, PE
760-533-6532
nickservin mail.com
Project Title:
Engineer:
Project ID:
Project Descr:
Pnnled 14 MAY 2021 4 37PM
FIie: Wood Beam Software copyright ENERCALC, INC. 1983-2020, Bu
1 ,1
DESCRIPTION: RB-2 TRELLIS BEAM
CODE REFERENCES
Calculations per NOS 2018, IBC 2018, CBC 2019, ASCE 7-16
Load Combination Set : ASCE 7-16
Material Pro erties
Analysis Method : Allowable Stress Design
Load Combination ASCE 7-16
Wood Species : Douglas Fir-Larch
Wood Grade : No.1
Fb+
Fb-
Fc -Prll
Fe -Perp
Fv
Ft Beam Bracing : Beam is Fully Braced against lateral-torsional buckling
♦ ♦ D(O 05) Lr(0.05)
I l • 6x10
Span= 15.50 ft
1,000.0psi
1,000.0psi
1,500.0psi
625.0psi
180.0psi
675.0psi
E: Modulus of Elasticity
Ebend-xx 1,700.0ksi
Eminbend -xx 620.0ksi
Density 31.210pcf
A lied Loads Service loads entered. Load Factors will be applied for calculations
Uniform Load : D = 0.010, Lr= 0.010 ksf, Tributary Width= 5.0 ft, (Trellis)
DESIGN SUMMARY
Maximum Bending Stress Ratio
Section used for this span
fb: Actual
Fb: Allowable
Load Combination
Location of maximum on span
Span # where maximum occurs
Maximum Deflection
Max Downward Transient Deflection
Max Upward Transient Deflection
Max Downward Total Deflection
Max Upward Total Deflection
Overall Maximum Deflections
Load Combination
+D+Lr
Vertical Reactions
Load Combination
Overall MAXimum
overall MINimum
DOnly
+D+Lr
+D-+-0.750Lr
-+-0.600
Lr Only
Span
=
= =
= =
0.348 1 Maximum Shear Stress Ratio
6x10 Section used for this span
435.61 psi fv: Actual
1,250.00psi Fv: Allowable
+D+Lr Load Combination
7.750ft Location of maximum on span
Span# 1 Span # where maximum occurs
0.098 in Ratio= 1902>=360
0.000 in Ratio= 0<360
0.196 in Ratio= 951 >=180 0.000 in Ratio= 0<180
Max.'." Defl Location in Span Load Combination
0.1955 7.807
Support notation : Far left Is # 1
Support 1
0.775
0.388
0.388
0.775
0.678
0.233
0.388
Support2
0.775
0.388
0.388
0.775
0.678
0.233
0.388
Desi n OK
= 0.090 : 1
6x10
= 20.14 psi
= 225.00 psi
+D+Lr = 14.765ft
= Span# 1
Max.•+• Defl Location in Span
0.0000 0.000
Values in KIPS
Servin Engineering, Inc.
2647 Gateway Road# 105-500
Carlsbad, CA 92009
Nick Servin, PE
760-533-6532
nickservin mail.com
Project Title:
Engineer:
Project ID:
Project Descr:
Prrnted 14 MAY 2021 4 36PM
Wood Beam Software copyright ENERCALC, INC. 1983-2020, Build:12.20.8.24 ,:.
DESCRIPTION: RB-3 TRELLIS BEAM
CODE REFERENCES
Calculations per NOS 2018, IBC 2018, CBC 2019, ASCE 7-16
Load Combination Set : ASCE 7-16
Material Pro ertles
Analysis Method : Allowable Stress Design
Load Combination ASCE 7-16
Wood Species
Wood Grade
: Douglas Fir-Larch
: No.1
Fb+
Fb-
Fc-Prll
Fe -Perp
Fv
Ft Beam Bracing : Beam is Fully Braced against lateral-torsional buckling
' 0(0.08) Lr(0.08)
6x10
Span= 13.0 ft
1,000.0psi
1,000.0psi
1,500.0 psi
625.0 psi
180.0 psi
675.0 psi
E : Modulus of Elasticity
Ebend-xx 1,700.0ksi
Eminbend -xx 620.0ksi
Density 31 .210pcf
♦
A lied Loads Service loads entered Load Factors will be applied for calculations
Uniform Load : D = 0.010, Lr = 0.010 ksf, Tributary Width = 8.0 ft, (Trellis)
DESIGN SUMMARY
Maximum Bending Stress Ratio
Section used for this span
fb: Actual
Fb: Allowable
Load Combination
Location of maximum on span
Span # where maximum occurs
Maximum Deflection
Max Downward Transient Deflection
Max Upward Transient Deflection
Max Downward Total Deflection
Max Upward Total Deflection
Overall Maximum Deflections
Load Combination
+D+lr
Vertical Reactions
Load Combination
Overall MAXimum
Overall MINimum
DOnly
+D+lr
+D..0.750Lr
..0.60D
Lr Only
Span
=
=
=
=
=
0.392 1 Maximum Shear Stress Ratio
6x10 Section used for this span
490.27psi fv: Actual
1,250.00psi Fv: Allowable
+D+Lr Load Combination
6.500ft Location of maximum on span
Span# 1 Span # where maximum occurs
0.077 in Ratio= 2015>=360
0.000 in Ratio= 0<360
0.155 in Ratio= 1007>=180 0.000 in Ratio= 0<180
Max.·-· Oefl Location in Span Load CombinaUon
0.1548 6.547
Support notation : Far left is # 1
Support 1
1.040
0.520
0.520
1.040
0.910
0.312
0.520
Support 2
1.040
0.520
0.520
1.040
0.910
0.312
0.520
Design OK
= 0.117 : 1
6x10
= 26.37 psi
= 225.00 psi
+D+Lr
= 12.241 ft
= Span# 1
Max. • +' Defl Location in Span
0.0000 0.000
Values in KIPS
Servin Engineering, Inc. Project Title:
Engineer: 2647 Gateway Road # 105-500
Carlsbad, CA 92009
Nick Servin, PE
Project ID:
Project Descr:
760-533-6532
nickservin mail.com
Wood Beam ,.,
DESCRIPTION: RB-4 TRELLIS BEAM
CODE REFERENCES
Calculations per NOS 2018, IBC 2018, CBC 2019, ASCE 7-16
Load Combination Set : ASCE 7-16
Material Properties
Analysis Method : Allowable Stress Design
Load Combination ASCE 7-16
Wood Species : Douglas Fir-Larch
Wood Grade : No.1
Fb+
Fb-
Fc -Prll
Fe -Perp
Fv
Ft
Beam Bracing : Beam is Fully Braced against lateral-torsional buckling
9 0(0 08) Lr(0.08)
6x10
Span= 15.50 It
Software
1,000.0psi
1,000.0psi
1,500.0psi
625.0psi
180.0psi
675.0psi
Printed 14 MAY 2021, 4.37PM
File: as1m Patio.
ht ENERCALC, INC. 1983-2020, Bulld:12.20.8.24
• .. !
E : Modulus of Elasticity
Ebend-xx 1,700.0ksi
Eminbend -xx 620.0ksi
Density 31.210pcf
Ap lied Loads Service loads entered Load Factors will be applied for calculations.
Uniform Load : D = 0.010, Lr= 0.010 ksf, Tributary Width= 8.0 ft, (Trellis)
DESIGN SUMMARY
Maximum Bending Stress Ratio
Section used for this span
fb: Actual
Fb: Allowable
Load Combination
Location of maximum on span
Span# where maximum occurs
Maximum Deflection
Max Downward Transient Deflection
Max Upward Transient Deflection
Max Downward Total Deflection
Max Upward Total DeOectlon
Overall Maximum Deflections
Load Combination
+D+Lr
Vertical Reactions
Load Combination
Overall MAXlmum
Overall MINimum
DOnly
+D+Lr
+D+0.750lr
+0.60D
Lr Only
Span
=
=
= =
o.ssa 1 Maximum Shear Stress Ratio
6x10 Section used for this span
696.97psi fv: Actual
1,250.00 psi Fv: Allowable
+D+Lr Load Combination
7.750ft Location of maximum on span
Span# 1 Span # where maximum occurs
0.156 in Ratio= 1189 >=360
0.000 in Ratio= 0<360
0.313 in Ratio= 594>=180 0.000 in Ratio= 0<180
Max. • -• Defl Location in Span Load Combination
0.3129 7.807
Support nolation : Far left is #1
Support 1
1.240
0.620
0.620
1.240
1.085
0.372
0.620
Support 2
1.240
0.620
0.620
1.240
1.085
0.372
0.620
=
=
= =
Design OK
0.143:1
6x10
32.22 psi
225.00psi
+D+Lt 14.765ft
Span# 1
Max. • +' Defl Location in Span
0.0000 0.000
Values in KIPS
Servin Engineering, Inc.
2647 Gateway Road# 105-500
Carlsbad, CA 92009
Nick Servin, PE
760-533-6532
nickservin mail.com
Project Title:
Engineer:
Project ID:
Project Descr:
Printed 15 MAY 2021 6 31AM
ile: asim atio. Wood Beam Software copyright ENERCALC, INC. 1983-2020, BuDd:12.20.8.24
1,1
DESCRIPTION: RB-5 TRELLIS BEAM
CODE REFERENCES
Calculations per NDS 2018, IBC 2018, CBC 2019, ASCE 7-16
Load Combination Set: ASCE 7-16
Material Pro erties
Analysis Method : Allowable Stress Design
Load Combination ASCE 7-16
Wood Species : Douglas Fir-Larch
Wood Grade : No.1
Fb+
Fb •
Fe-Prll
Fe• Perp
Fv
Ft
Beam Bracing : Beam is Fully Braced against lateral-torsional buckling
0.01) Lr(O 01} 6
D(0.52~rl0.52\
&10
Span = 16.0 ft
1,000.0psi
1,000.0psi
1,500.0psi
625.0psi
180.0psi
675.0 psi
E : Modulus of Elasticity
Ebend-xx 1,700.0ksi
Eminbend • xx 620.0ksi
Density 31.210pcf
~ 6)(10
Span = 2.50 ft
A lied Loads Service loads entered. Load Factors will be applied for calculatrons.
Load for Span Number 1
Uniform Load : D = 0.010, Lr= 0.010 ksf, Tributary Width= 1.0 ft, (Trellis)
Point Load : D = 0.520, Lr = 0.520 k@7.0 ft, (RB-3)
Load for Span Number 2
Uniform Load : D = 0.010, Lr= 0.010 ksf, Tributary Width = 1.0 ft, (Trellis)
Point Load : D = 0.520, Lr = 0.520 k@ 2.50 ft, (RB-3)
DESIGN SUMMARY
Maximum Bending Stress Ratio = 0.412 1 Maximum Shear Stress Ratio
Section used for this span
fb: Actual
Fb: Allowable
Load Combination
Location of maximum on span
Span # where maximum occurs
Maximum Deflection
Max Downward Transient Deflection
Max Upward Transient Deflection
Max Downward Total Deflection
Max Upward Total Deflection
Overall Maximum Deflections
Load Combination
+D+lr
Vertical Reactions
Load Combination
Overall MAXlmum
Overall MINimum
DOnly
+D+lr
+D+0.750Lr
Span
1
2
=
=
=
6x10
514.63psi
1,250.00 psi
Max.•.• Oefl
0.1634
0.0000
+O+Lr
6.972ft Span# 1
0.082 in Ratio=
-0.009 in Ratio=
0.163 in Ratio=
-0.018 in Ratio=
Location In Span
7.151
7.151
Section used for this span
fv: Actual
Fv: Allowable
Load Combination
Location of maximum on span Span # where maximum occurs
2350 >=360
6836>=360
1175 >=180
3418>=180
Load Combination
+D+lr
Support notation : Far left Is #1
Support 1
0.579
0.289
0.289
0.579
0.506
Support 2 Support 3
1.871
0.936
0.936
1.871
1.637
=
=
=
Max.'+' Defl
0.0000
-0.0176
Values In KIPS
Design OK
0.137: 1
6x10
30.84 psi
225.00 psi
+D+Lr
16.000ft
Span# 1
Location in Span
0.000
2.500
Servin Engineering, Inc.
2647 Gateway Road# 105-500
Carlsbad, CA 92009
Nick Servin, PE
760-533~532
nickservin mail.com
Wood Beam
1,1
DESCRIPTION: RB-5 TRELLIS BEAM
Vertical Reactions
Load Combination
Lr Only
Support 1
.174
0.289
Project Title:
Engineer:
Project ID:
Project Descr:
Support notation : Far left Is #1
Support 2 Support 3
.56
0.936
Printed 15 MAY 2021 6 31AM
Software copyright ENERCALC, INC. 1983-2020, Build:12.20.8.24
Values in KIPS
Servin Engineering, Inc.
2647 Gateway Road# 105-500
Carlsbad, CA 92009
Nick Servin, PE
760-533-6532
nickservin mail.com
Wood Beam ,.,
DESCRIPTION: RB-6 TRELLIS BEAM
CODE REFERENCES
Calculations per NDS 2018, IBC 2018, CBC 2019, ASCE 7-16
Load Combination Set : ASCE 7-16
Material Pro erties
Analysis Method : Allowable Stress Design
Load Combi(lalion ASCE 7-16
Wood Species : Douglas Fir-Larch
Wood Grade : Select Structural
Project Title:
Engineer:
Project ID:
Project Descr:
Fb+
Fb-
Fc-Prtl
Fe -Perp
Fv
Ft
1,500.0psi
1,500.0 psi
1,700.0 psi
625.0 psi
180.0psi
1,000.0psi
Beam Bracing : Beam is Fully Braced against lateral-torsional buckling
a. Of Lr(O. 01) 6
D(0.52~r!O. Sfl
6x10
Span = 16.0 ft
E : Modulus of Elasticity
Ebend-xx 1,900.0ksi
Eminbend -xx 690.0ksi
Density 31.210pcf
D(O 01) 8H-8~l i'' '·0
'' ! i t 7 :
~ 6x10
Span = 2.50 ft
A lied Loads Service loads entered Load Factors will be applied for calculations
Beam self weight calculated and added to loads
Load for Span Number 1
Uniform Load : D = 0.010, Lr= 0.010 ksf, Tributary Width = 1.0 ft, (Trellis)
Point Load : D = 0.520, Lr= 0.520 k@ 7 .0 ft, (RB-3)
Point Load : D = 0.520, Lr= 0.520 k @7.0 ft, (RB-3)
Load for Span Number 2
Uniform Load : D = 0.010, Lr = 0.010 ksf, Tributary Width= 1.0 ft, (Trellis)
Point Load : D = 1.040, Lr= 1.040 k@ 2.50 ft, (RB-3 X 2)
DESIGN SUMMARY
Maximum Bending Stress Ratio = 0.52~ 1 Maximum Shear Stress Ratio
Section used for this span
fb: Actual
Fb: Allowable
Load Combination
Location of maximum on span
Span # where maximum occurs
Maximum Deflection
Max Downward Transient Deflection
Max Upward Transient Deflection
Max Downward Total Deflection
Max Upward Total Deflection
Overall Maximum Deflections
Load Combination
+D+Lr
Vertical Reactions
Load Combination
Overall MAXimum
Overall MINimum
DOnly
Span
1
2
=
=
6x10 Section used for this span
991 .37psi fv: Actual
1,875.00 psi Fv: Allowable
+O~ Load Combination
6.972ft Location of maximum on span
Span# 1 Span# where maximum occurs
0.128 in Ratio= 1503>=360
-0.007 in Ratio= 8686 >=360
0.276 in Ratio= 694>=180
-0.024 in Ratio= 2522 >=180
Max.•-• Defl Location in Span Load Combination
0.2763 7.151
0.0000 7.151 +D+Lr
Support notation : Far left Is #1
Support 1
1.089
0.501
0.589
Support 2 Support 3
3.650
1.764
1.886
=
=
=
=
Desi n OK
0.272: 1
6x10
61 .26 psi
225.00 psi
+0-+lr
16.000ft
Span# 1
Max.'+" Defl Location in Span
0.0000 0.000
-0.0238 2.500
Values in KIPS
Servin Engineering, Inc.
2647 Gateway Road# 105-500
Carlsbad, CA 92009
Nick Servin, PE
760-533-6532
nickservin mail.com
Wood Beam ,.,
DESCRIPTION: RB-6 TRELLIS BEAM
Vertical Reactions
Load Combination
~4.r
-+0-+-0.750Lr
-+-0.60D
Lr Only
Project Title:
Engineer:
Project ID:
Project Descr:
Support notation : Far left is #1
Support 1 Support 2 Support 3
1.089
0.964 3.209
0.353 1.131
0.501 1.764
Printed 15 MAY 2021. 6 37AM
ile: Basim atio.ec6
Software copyright ENERCALC, INC. 1983-2020, Build:12.20.8.24
Values in KIPS
Servin Engineering, Inc. Project Name: Basim Patio
2647 Gateway Road,# 105-500 Flagpole Footing Design v\ddress: 1781 Skimmer Court
Carlsbad, CA 92009 Program -Constrained ~N: 22667
760-533-6532 By: NS
Email: nickservin@gmail.com Date: 5/21/2021
Criteria:
dA2= 4.25*Ph/S3/b Units
b Diameter of footing Feet
d Footing depth Feet
h Height of applied load Feet
p Lateral load Lbs
S3 Lateral bearing pressure PSF/ft
Input: b 1.50 Feet d 2.90 Feet
h 9.00 Feet Initial Guess
p 282 Lbs
S3 100 PSF/ft S3 adj 290.00 PSF/ft
Output: d= 2.92 Feet deep, minimum
ff
L\TC Hazards by Location
Search Information
Address:
Coordinates:
Bevation:
Times tamp:
Hazard Type:
Reference
Document:
Risk Category:
Site Class:
,a Island
1781 Skimmer Ct, Carlsbad, CA92011, USA ential ~abitat...
33.10942500000001, -117 .2714465
279 ft
2021 -03-03T02:08:21.702Z
Seismic
ASCE7-16
II
O-default
Go gle
Basic Parameters
Name Value Description
Ss 0.993 MCER ground motion (period=0.2s)
S1 0.361 MCER ground motion (period=1.0s)
SMs 1.192 Site-modified spectral acceleration value
SM1 • null Site-modified spectral acceleration value
Sos 0.794 Numeric seismic design value at 0.2s SA
So1 • null Numeric seismic design value at 1.0s SA
"See Section 11 .4.8
•Additional Information
Name Value Description
soc • null Seismic design category
Fa 1.2 Site amplification factor at 0.2s
Fv • null Site ampllflcaUon factor at 1.0s
CRs 0.897 Coefficient of risk (0.2s)
CR1 0.908 Coefficient of risk (1.0s)
PGA 0.435 MCEG peak ground acceleration
FPGA 1.2 Site amplification factor at PGA
PG~ 0.521 Site modified peak ground acceleration
I
l
CD
®
Temecula
0
279 ft · Cleveland Borrego
Springs
0 Ocean.w National Forest
0 scondido Anza-Bc 0 Dese
State f
Mt Laguna
0
San Diego O 0 ,_ Map data ~2021 Google, INEGI
.I
I
I
i
L\TC Hazards by Location
Search Information
Address:
Coordinates:
Elevation:
Tlmestamp:
Hazard Type:
ASCE 7-16
MRI 10-Year
MRI 25-Year
MRI 50-Year
MRI 100-Year
Risk Category I
Risk Category II
Risk Category Ill
Risk Category IV
1781 Skimmer Ct, Carlsbad, CA92011, USA
33.10942500000001, -117.2714465
279 ft
2021-03-03T02:07:23.254Z
Wind
ASCE 7-10
67 mph MRI 10-Year
72 mph MRI 25-Year
77 mph MRI 50-Year
82 mph MRI 100-Year
89 mph Risk Category I
96 mph Risk Category II
102 mph Risk Category Ill-IV
107 mph
,a Island
ential
labitat ...
Go gle
72 mph
79 mph
85 mph
91 mph
100 mph
110 mph
115 mph
Temecula 0
279 ft · Cleveland Borrego
•
~ Spr~ngs Ocean National Forest
0 scondido Anza-Bc 0 Dese
State F
Mt L!guna
San Diego O 0 ,. Map data @2021 Google, INEGI
ASCE 7-05
ASCE 7-05 Wind Speed 85 mph
The results indicated here DO NOT reflect any state or local amendments to the values or any delineation lines made during the building
code adoption process. Users should confirm any output obtained from this tool with the local Authority Having Jurisdiction befo,e
proceeding with design.
Disclaimer
Hazard loads are interpolated from data prolAded in ASCE 7 and rounded up to the nearest whole integer. Per ASCE 7, islands and
coastal areas outside the last contour should use the last wind speed contour of the coastal area -in some cases, this website will
extrapolate past the last wind speed contour and therefore, prolAde a wind speed that is slightly higher. NOTE: For queries near wind-
borne debris region boundaries, the resulting determination is sensitive to rounding which may affect whether or not it is considered to
be within a wind-borne debris region.
Mountainous terrain, gorges, ocean promontories, and special wind regions shall be examined for unusual wind conditions.
While the information presented on this website is believed to be correct, ATC and its sponsors and contributors assume no
responslbilityor liability for its accuracy. The material presented in the report should not be used or relied upon for any specific
applicaUon without competent examination and verification of Its accuracy, suitability and applicability by engineers or other licensed
professionals. ATC does not intend that the use of this information replace the sound judgment of such com petent professionals,
ha'lling experience and knowledge in the field of practice, nor to substitute for the standard of care required of such professionals in
Interpreting and appl~ng the results of the report prolAded by this website. Users of the information from this website assume all liability
arising from such use. Use of the output of this website does notimplyapproval by the governing building code bodies responsible for
Project Name:
ddress:
Basim Patio Servin Engineering, Inc.
2647 Gateway Road
Carlsbad, CA 92009 SEISMIC DISTRIBUTION TABLE N:
1781 Skimmcer Court
22667
60-931-1792, 1892 Fax
Email: nickservin@gmail.com
Base Shear Calculation: Patio Lateral
V= Sos• W where: Sos = 2/3"SMs =
(R/1) S,,s = F."Ss =
s. =
Site Class=
F, =
Vmu= S01 "W where: S01 = 2/3"SM, =
T"(R/1) sM, = F;s, =
S,=
Site Class=
F. =
v_ = o.01·w or v..,.. = co.5·s,1cR11J)'W
0.79
1.19
0.993
D
1.20
0.24
0.36
0.361
D
1.00
If S1 ~ 0.6g
I V = 0.53"W I I v,. .. = 1.48'W I v,.,,, = o.01·w I
USE: V • 0.53'W
Story Force Distribution:
(From USGS Mapped S8 & S1)
(Defaull Class D)
(From USGS Mapped Ss & S,)
(From USGS Mapped S8 & S1)
(Default Class D)
(From USGS Mapped S5 & S,)
F, D1stnbu11on -Verhcal Elemenls (Shea,walls) V = 1 239 lbs
Story Unit DL (psf) w,(lbs) h, (ft)
Roof 464 5 2320 9.5 22040
Wall 4 5 20 4 80
I:w,= 2340 I: w,"h, = 22120
F,, D1slnbu1,on • Honzonial Elemenis (Diaphragms)
Story Unit DL (psf) w,(lbs) I:w, (lbs)
Roof 464 5 2320 2320 1.000
2320
By: ns
Date: 5/21/2021
Occupancy Category: II
I = Importance Factor:
Seismic Design Category: D
Basic Buildin S stem:
G. Cantilevered Column S stem
7. Timber Frames
R = Response ModiflCStion Factor: 1.5
Building Period T :
T = o.02o·t,,.075 = 0.11
h,. = 9.5 ft
w,'h/I:wx"hx F, (lbs) V Redistribution F /sq ft (psf)
0.996 1235 1237 2.67
0.004 4
I:F, (lbs) F 0/sqft (psf)
1237 1237 2.67
L 3
Seniin Engineering, Inc.
2647 Gateway Road
Carlsbad, CA 92009 SEISMIC STORY FORCE DISTRIBUTION
760-93 1-1792, 1892 Fax
Email: nicksen,in@gmail.com
Seismic Force Distribution @Story Level:
Line Width To Left of Length Along
Line ft
A 14.50 1 .00
B 14.50 16.00
C 14.50 16.00
1 16.00 29.00
2 16.00 29.00
14.50 16.00
Line Width To Left of Length Along Width To Right Length Along
Line ft) Line ft of Line (ft Line (fl)
Shear F,lfl" = psi 0'
Line Width To Left of Length Along Width To Righi Length Along
Line (Ill Line lftl of Line lftl Line (fl)
Trib. Area (tt2) p•F, (psi)
116 3.47
232 3.47
116 3.47
232 3.47
232 3.47
Trib. Area (112) p•F, (psi)
Trib. Area (tt2) p•F, (psi)
Project Name:
ddress:
Basim Patio
1781 Skimmer Court
226l,7 N:
By:
Date:
Vu= F (lbs)
402
804
402
804
804
Vu= F (lbs)
Vu= F (lbs)
ns
5/21/2021
V = 0.7"VU
(lbs, ASO
281
563
281
563
563
V = 0.7°VU
(lbs, ASO)
V = 0.7°VU
/lbs, ASOl
Controls half to ea
column, v=282 lbs
L4
Servin Engineering. Inc. Project Name:
ddress:
Basim Patio
2647 Gateway Road
Ci!rlsbad, CA 92009
760-931-1792. 1892 Fax
Email: nickservin@gmail.com
WIND ANALYSIS -ANALYTICAL PROCEDURE N:
1781 Skimmer Cou"
22667
Design Wind Pressure:
(Enclosed and Partially Enclosed Buildings • Low-Rise Building)
Where:
qh = 0.00256°K,,°K11°K.,"V2'1
K,, = velocity pressure exposure coefficients evaluated at mean roof height, h
K,. = topographic factor evaluated at mean roof height, h
K., = wind directionality factor
V = Basic Wind Speed
I = Importance Factor
Qh'" 17.05 psf
Q. = 1705 psi 8= 184
Building
Surface
2
3
4
5
6
1E
2E
3E
4E
Ge,.
0.51
-0.69
-0.47
-0.41
-0.45
-0.45
o.n
-1.07
-0.87
-0.61
Story Force Distribution: ...
Story Trib. Wall Ht.
Roof 1.0
Gcpi (+)
0.16
0.16
0.18
0.18
0.16
0.18
0.18
0.18
0.18
0.18
p(psf) Gcpi (·)
5.67 -0.18
-14.83 ·0.18
·11 .00 -0.18
-10.08 -0.18
-10.74 -0.18
-10.74 -0.18
10.14 -0.18
-21.31 -0.18
-14.47 -0.18
-13.50 -0.18
p (psf)
11.61
-8.69
-4.86
-3.94
-4.80
-4.60
16.27
-15.17
-8.33
-7.36
By:
Date:
Total Building Height: 9.5
Eave Height: 9.5
Mean Roof Height, h: 10
For Wind Exposure D:
K,, = 0.85
K.,=
K., = 0.85
V = 96 mph with 3 second gust
Occupancy Category: II
I= Importance Factor.
Design Wind Pressure:
Roof Height:
11S
S/21/2021
Max Interior Zone Pressure: 14.83 psf
Max End Zone Pressure: 21.31 psf
Wall Height:
Max Interior Zone Pressure: 11.81 psf
Max End Zone Pressure: 16.27 psf
211
,....., •UNIFO!tM WIND l'OttCE IN END ZONE
,.; ,. L
"'Im: •UNIFORM WIND FO!tCE IN
INTEltlOlt ZONE
L 5
Servin Engineering, Inc.
2647 Gateway Road
Carlsbad, CA 92009
760-93 J.I 792. 1892 Fax
Email: nickservin@gmail.com
Wind Force Distribution @ Story Level:
Line Diaphragm
Width #1 ft
A 14.50
B 14.50 14.50
C 14.50
1 16.00
2 16.00
• Shear w,..,= pit
WIND STORY FORCE DISTRIBUTION
line Receive End 2a (ft) v .. .,.,,,(lbs) Exterior/ Intermediate Zone Shear
Exterior Yes 3.20 108
Exterior Yes 3.20 215
Exterior Yes 3.20 108
Exterior Yes 3.20 119
Exterior Yes 3.20 119
a = lesser of 0.4h.,..0 or 0.1 b
b = Least Horizontal Building Dimension
... , = plf
Line Width To Left of Width To Right Wall Type Una Receive End 2a (ft) v,.,..,.,,(lbs) Line (ft) of Line (ftl Exterior I lnlennedlltl Zone Shear
a = lesser of 0.4h,,,. •• or 0.1 b
b = Least Horizontal Building Dimension
Line line Receive End
~•rlor I lnterm1di111 Zone Shear _ 2a (ft) v..._ (lbs)
a = lesser of 0.4hm .. n or 0.1 b
b = Least Horizontal Building Dimension
L ., ....
Project Name:
ddress:
Basim Patio
1781 Skimmer Coun
22667 N:
By: 11S
Date: sn112021
v.,.,, ... (lbs) V(lbs)
18 126
18 233
18 126
19 137
19 137
a• 1.60 ft
b = 16.0 ft
V.,.,,... (lbs) V(lbs)
a .. 0.00 ft
b = 0.0 ft
v.,__(lbs) V(lbs)
a = 0.00 ft
b • ft
L6