HomeMy WebLinkAbout6515 AMBROSIA LN; ; AS100100; Permit10/27/2020 AS100100 Permit Data
City of Carlsbad
Sprinkler Permit
Job Address: 6515 AMBROSIA LN
Permit Type: SPRINK
Parcel No: 2158410700
Lot#: 0
Reference No.:
Permit No: AS100100
Status: ISSUED
Applied 8/16/2010
Approved: 8/16/2010
Issued: 8/16/2010
PC #: Inspector:
Project Title: DAYBREAK CHURCH UNDERGROUND FIRE SPRINKLER PLAN
CHECK & 3 INSPECTIONS
Applicant: Owner:
INLAND VALLEY PIPELINE
P.O. BOX 1084
TEMECULA, CA
951-368-3903
Fees($)
260
Add'I Fees ($)
0
DAYBREAK COMMUNITY CHURCH OF
COASTAL NORTH COUNT
6515 AMBROSIA LN
CARLSBAD CA
Total($) Balance($)
260 0
1 /1
\ 0\00
INSTALIATION OF PRIVATE FIRE SERVICE MAINS AND THEIR APPURTENANCES
Contractor's Material and Test Certificate for Underground P.iping
PROCEDURE
Upon completion of work, inspection and tests shall be made by the contractor's representative and witnessed by an owner's
representative. All defects shall be corrected and system left in service before contractor's personnel finally leave the job.
A certificafe.shall be filled out and signed by both representatives. Copies shall be prepared for approving authorities, owners, and
contractor. It is understood the owner's representative's signature in no way prejudices any claim against contractor for faulty material, poor
workmanship, or failure to comply with approving authority's requirements or local ordinances.
Property name
Property address
Plans
.Instructions
Location
Underground
pipes and joints
Test
description
Flushing
tests
Installation conforms to accepted plans
Equipment used is approved
If no, state deviations
Has person in charge of fire equipment been instructed as to location of
control valves and care and maintenance of this new equipment?
If no, explain
Have copies of appropriate instructions and care and maintenance
charts been left on premises?
If no, explain
Supplies buildings
Pipe types and class
Pipe conforms to Fittings
conforms to
If no, explain
Joints needed anchorage clamped, strapped, or blocked in
accordance with /VF/JII standard
If no, explain
Type joint
Date -I D
Yes
Yes
Yes
~Yes
. Yes
D Yes
/('['Yes
D No
D No
D No
D No
D No
D No
D No
.El.Yfil:ling;_ Flow the required rate until water is clear as indicated by no collection of foreign material in burlap bags at
outlets such as hydrants and blow-offs. Flush at flows not less than 390 gpm (1476 Umin) for 4-in. pipe, 880 gpm (3331
Umin) for 6-in. pipe, -1560 ·gpm (5905 Umin) for 8-in. pipe, 2440 gpm (9235 Umin) for 10-in. pipe, and 3520 9pm (13,323
Umin) for 12-in. pipe. When supply cannot produce stipulated flow rates, obtain maximum available.
Hydrostatic: Hydrostatic tests shall be made at not less than 200 psi (13.8 bar) for 2 hours or 50 psi (3.4 bar) above
static pressure in excess of 150 psi (10.3 bar) for 2 hours.
Leakage: New pipe laid with rubber gasketed joints shall, if the workmanship is satisfactory, have little or no leakage at
the joints. The amount of leakage at the joints shall not exceed 2 quarts per hour (1.89 Uhr) per 100 joints irrespective
of pipe diameter. The leakage shall be distributed over all joints. If such leakage occurs at a few joints; the installation
shall be considered unsatisfactory and necessary repairs made. The amount of allowable leakage specified above can
be increased by 1 fluid ounce per inch valve diameter per hr. (30 mU25 mm/hr) for each metal seated valve isolating the
test section. If dry barrel hydrants are tested with the main valve open so the hydrants are under pressure, an additional
5 ounces per minute (1_50 mUmin) leakage is permitted for each hydrant.
New un,Jound piping flushed according to NF . standard by (company)
Yes D No
If no, explain
~lushing flow was obtained
~rublic water D Tank or reservoir D Fire pump
Through what type openi g
D Hydrant butt · Open pipe
Lead-ins flushed according to ~ standard by ( company) 0 No
If no, explain
~lushing flow was obtained ·
)'\:.., ~ ublic water D Tank or reservoir D Fire pump
Through.what type opening
Y connection to flange D Open pipe
and spigot (NFPA 24, 1 of 2)
FIGURE IO.IO.I Sample of Contractor's Material an:d Test Certificate for Underground Piping.
2002 Edition
ABOVEGROUND PIPE AND FITTINGS 24-17
Hydrostatic All ne~ underground piping hydrostatical~ested at Joints covered
test . aoo psi for hours D Yes D No
Total amount of leakage measured
Leakage D gallons a hours
test Allowable leakage
eJ gallons ~ hours
Number installed
I
Type and make I All operate satisfactorily
Hydrants ~ c/4~ gso D Yes D No
Water control valves left wide open ~Yes □ No
Control If no, state reason
valves
Hose threads of fire department connections and hydrants interchangeable with ~es D No
those of fire department answering alarm
Date left in service
Remarks
Name of inst~ contractor I',' --r; /11 IA lhAJ '/lt!J,:1,.1 -Signatures /7 Tests witnessed by
For property owner (signed)
I
For in~;=r (signed) I
Additional_:... ------~d notes
FIGURE 10.10.1 Continued
(1) *The amount of leakage at the joints shall not exceed
2 qt/hr (1.89 L/hr) per 100 gaskets or joints, irrespective
of pipe diameter.
(2) *The amo~nt ofleakage specified in 10.10.2.2.4(1) shall be
permitted to be increased by 1 fl oz (30 ml) per inch valve
diameter per hour for each metal-seated valve isolating
the test section.
(3) If dry barrel hydrants are tested with the main valve open
so the hydrants are under pressure, an additional 5 fl oz/
min (150 ml/min) ofleakage shall be permitted for each
hydrant.
(4) The amount of leakage in buried piping shall be mea-
sured at the specified test pressure by pumping from a
calibrated container.
Chapter 11 Hydraulic Calculations
11.1 * Calculations in English Units. Pipe friction losses shall
be determined based on the Hazen-Williams formula, as fol-
lows:
4.52Ql.85
P = c1.ssd•.s1
Title
1
Date
Title/, r;J I Dateo/ _ /7-/0
where:
p =· frictional resistance (psi/ft of pipe)
Q = flow (gpm)
C = friction loss coe:fficien t
d = actual internal diameter of pipe (in.)
(NFPA 24, 2 of 2)
11.2 Calculations in SI Units. Pipe friction losses shall be de-
termined based on the Hazen-:-Wtlliams formula in SI units, as
follows:
where:
Pm = frictional resistance (bar/m of pipe)
~ = flow (L/min)
C = friction loss coefficient
dm = actual internal diameter of pipe (mm)
Chapter 12 Aboveground Pipe and Fittings
12~1 General. Aboveground pipe and fittings shall comply
with the applicable sections of Chapters 6 and 8 of NFPA 13,
2002 Edition