Description: RABABY: INSTALL MULTIP ORT MINI SPLIT W/ 3 INDOOR UNITS (E-REVIEW)
Applicant:
THE RIGHT CHOICE HEATING AND AIR INC
TOMER PERETZ
5351 GEYSER AVE
TARZANA, CA 91356-3308
(818) 435-7560
FEE
PLUMBING, MECHANICAL & ELECTRICAL PERMITS
Total Fees : $193.00 Total Payments To Date: $193.00
Permit No:
Status:
{city of
Carlsbad
CBR2022-1363
Closed -Finaled
Applied: 04/20/2022
Issued : 04/22/2022
Finaled Close Out: 03/09/2023
Final Inspection: 11/04/2022
INSPECTOR: Alvarado, Tony
Kersch, Tim
Contractor:
THE RIGHT CHOICE HEATING AND AIR INC
9825 INDEPENDENCE AVE
CHATSWORTH, CA 91311-4320
(818) 435-7560
Balance Due:
AMOUNT
$193.00
$0.00
Please take NOTICE that approval of your project includes the "Imposition" of fees, dedications, reservations, or other exactions hereafter
collectively referred to as "fees/exaction." You have 90 days from the date this permit was issued to protest imposition of these
fees/exactions. If you protest them, you must follow the protest procedures set forth in Government Code Section 66020(a), and file the
protest and any other required information with the City Manager for processing in accordance with Carlsbad Municipal Code Section
3.32.030. Failure to timely follow that procedure will bar any subsequent legal action to attack, review, set aside, void, or annul their
imposition.
You are hereby FURTHER NOTIFIED that your right to protest the specified fees/exactions DOES NOT APPLY to water and sewer connection
fees and capacity changes, nor planning, zoning, grading or other similar application processing or service fees in connection with this
project. NOR DOES IT APPLY to any fees/exactions of which you have previously been given a NOTICE similar to this, or as to which the
statute of limitation has previously otherwise expired.
Building Division Page 1 of 1
1635 Faraday Avenue, Carlsbad CA 92008-7314 I 442-339-2719 I 760-602-8560 f I www.carlsbadca.gov
; Cifyof
Carlsbad
RESIDENTIAL
BUILDING PERMIT
APPLICATION
8-1
Plan Check ________ _
Est. Va lue
PC Deposit
Date
JobAddress d-4'(6 ~ '3\-:· Unit: _____ .APN: __________ _
CT/Project #: _________________ Lot #: ____ Vear Built: ________ _
BRIEF 0EscRrPT10N oF woRK: \C'b:'0,\\ Vf\u.~ po-r..+ m't{)l ?fi·,k". ou+-&.c:0r ~ooo ITTu
3 Wo()r ( x.. ';;} Op)o ~ 1 \ ,,eooo B:s:µ,
□ New SF : Living SF, ____ Deck SF, ___ Patio SF, ____ Garage SF __ _
Is this to create an Accessory Dwelling Unit? O Y O N New Fireplace? O YO N, if yes how many? ___ _
D Remodel: _____ SF of affected area Is the area a conversion or change of use? O YO N
□ Pool/Spa:. _____ SF Additional Gas or Electrical Features? ____________ _
□Solar: ___ KW, ___ Modules, Mounted:QRoofOGround, Tilt: ('.)YON, RMA: OY ON,
Battery:OYO N, Panel Upgrade: OvON
Other:
PRIMARY APPLICANT PROPERTY OWNER
Name:ft?Q'Y::C ;t.bee.-\---==b-Name: :\Q('?f\:t t\_ L,~¢-P-A. ½o...lov)
Address: 53.:::i7 Oa::!?:Y ~ kv-€-. Address: a3:1-s ~A LA\ 5\::: . I
City: TM~ State: C ~ Zip: ot r:,s:ee City: C.&:&\6\co-.& Statel fr Zip: g :?:oo'.3
Phone: r£~-';-\ ~ S-3::Tu {) Phone: ~O -5 3 ~-'d \ 4 \
Email: \'{)A,\\ fil\\.;,un~cJ11..0t cgV\'0/lC..C..OW' Email: \Q\.o(},~'\ ® 'J;W:'O:+\ · tMV\
DESIGN PROFESSIONAL CONTRACTOR OF RECORD
Name: _______________ BusinessName: :fh.e. Q.,,:~ G½Q~l.€ t,\eAf,~i)A;,r
Address: Address: "\'Q;}S \ Q~~Ra:JU' p.-y.g -
City: _______ State: ___ Zip:_____ CityCh:s\;,;wo:6:½ State: (~ Zip:_°}_.__l~ ___ \_( __ _
Phone: Phone: 9-',1\'7'2::: 435-::::t§lpO
Email: Email: \,'X)Q.. ~ \ @)::--k&, ~ e¥'-\-(..\,t.b.'.c....<'.... \,\\.J&c.. · ~
Architect State License: CSLB License#: qee,OY,:::j:-Class: <2"d-b; 13
Carlsbad Business License# (Required): I?, L£J.5{ 3'-\3Ci f}S
APPLICANT CERT/FICA TION: I certify that I have read the application and state that the above information is correct and that the information of the plans is accurate. I
,,,., ro _,, _ ,11 c;::_""""' ,Ms1,~ /om ,e/WmJW b,H<P,g ro,nmctl~~??: 5,i'
NAME{PRINT): \c:m.e-r ?~~ SIG~=;....-:,-DATE: ~-15<2::~
1635 Faraday Ave Carlsbad, CA 92008 Ph: 442-339-2719 Email: Building@carlsbadca.gov
REV. 04/22
.. ····----·-------------
THIS PAGE REQUIRED AT PERMIT ISSUANCE PLAN CHECK NUMBER: ______ _
A BUILDING PERMIT CAN BE ISSUED TO EITHER A STATE LICENSED CONTRACTOR OR A PROPERTY OWNER. IF THE PERSON SIGNING
THIS FORM IS AN AGENT FOR EITHER ENTITY AN AUTHORIZATION FORM OR LETTER IS REQUIRED PRIOR TO PERMIT ISSUANCE.
(OPTION A): LICENSED CONTRACTOR DECLARATION:
lherebyaffirmunderpenaltyofperjurythatlamlicensedunderprovisionsofChapter9(commencingwithSection7000)ofDivision3
of the Business and Professions Code, and my license is in full force and effect. I also affirm under penal tyof perjury one of the
following declarations (CHOOSE ONE):
DI have and will maintain a certificate of consent to self-insure for workers' compensation provided by Section 3700 of the Labor Code, for the performance of the
work which this permit is issued. PolicyNo. ____________________________________________ _
-OR-
ial have and will maintain worker's compensation, as required by Section 3700 of the Labor Code, for the performance of the work for which this permit is issued.
My workers' compensation insurance carrier and policy number are: Insurance Company Name: "£a::r< Y\~ ~ \ ('f,u { Av"Le (~L:{
Policy No. l--5' !;31? 9-Z>~ 5 '.P;, Expiration Date: ~3---u=-----',g.=---3..__ _______ 1 -OR-
D Certificate of Exemption:! certify that in the performance of the work for which this permit is issued,! shall not employ any person in any manner so as to become
subject to the workers' compensation Laws of California. WARNING: Failure to secure workers compensation coverage is unlawful and shall subject an employer to
criminal penalties and civil fines up to $100,000.00, in addition the to the cost of compensation, damages as provided for in Section 3706 of the labor Code,
interest and attorney's fees.
CONSTRUCTION LENDING AGENCY, IF ANY:
I hereby affirm that there is a construction lending agency for the performance of the work this permit is issued {Sec. 3097 (i) Civil Code).
Lender's Name: _______________________ lender's Address: _______________________ _
CONTRACTOR CERT/FICA TION: The applicant certifies that all documents and plans clearly and accurately show all existing and proposed buildings, structures, access roads, and
utilities/utility easements. All proposed modifications and/or additions are clearly labeled on the site plan. Any potentially existing detail within these plans inconsistent with the site plan are
not approved for construction and may be required to be altered or removed. The city's approval of the application is based on the premise that the submitted documents and plans show
the correct dimensions of; the property, buildings, structures and their setbacks from property lines and from one another; access roads/easements, and utilities. The existing and proposed
use of each building as stated is true and correct; all easements and other encumbrances to development have been accurately shown and labeled as well as all on-site grading/site preparation.
All improvements existing on the property were completed in accordance with all regulations in existence at the time of their construction, unless otherwise noted.
n ~ ,1. NAME (PRINT): \ D:{l'Q,C y-?-("£+==b-SIGNATURE:c---:-< 2 __:::;:, DATE:_y-__ -__ 1 ..... 9: __ -0--o--_· __ _
Note: If the person signing above is an authorized agent for the contractor rovide a letter of authorization on contractor letterhead.
(OPTION B): OWNER-BUILDER DECLARATION:
I hereby affirm that I am exempt from Contractor's License Law for the following reason:
D I, as owner of the property or my employees with wages as their sole compensation, will do the work and the structure is not intended or offered for sale (Sec.
7044, Business and Professions Code: The Contractor's License law does not apply to an owner of property who builds or improves thereon, and who does such
work himself or through his own employees, provided that such improvements are not intended or offered for sale. If, however, the building or improvement is sold
within one year of completion, the owner-builder will have the burden of proving that he did not build or improve for the purpose of sale).
-OR-
□ I, as owner of the property, am exclusively contracting with licensed contractors to construct the project (Sec. 7044, Business and Professions Code: The
Contractor's License Law does not apply to an owner of property who builds or improves thereon, and contracts for such projects with contractor(s) licensed
pursuant to the Contractor's license Law).
-OR-DI am exempt under Business and Professions Code Division 3, Chapter 9, Article 3 forth is reason:
AND,
D FORM 8-61 "Owner Builder Acknowledgement and Verification Form" is required for any permit issued to a property owner.
By my signature below l acknowledge that, except for my personal residence in which I must have resided for at least one year prior to completion of t he
improvements covered by this permit, I cannot legally sell a structure that I have built as an owner-builder if it has not been constructed in its entirety by licensed
contractors. I understand that a copy of the applicable law, Section 7044 of the Business and Professions Code, is available upon request when this application is
submitted or at the following Web site: http:l l www.leginfo.ca.gov/ ca law.html.
OWNER CERTIFICATION: The applicant certifies that all documents and plans clearly and accurately show all existing and proposed buildings, structures, access roads, and utilities/utility
easements. All proposed modifications and/or additions are clearly labeled on the site plan. Any potentially existing detail within these plans inconsistent with the site plan are not approved
for construction and may be required to be altered or removed. The city's approval of the application is based on the premise that the submitted documents and plans show the correct
dimensions of; the property, buildings, structures and their setbacks from property lines and from one another; access roads/easements, and utilities. The existing and proposed use of each
building as stated is true and correct; all easements and other encumbrances to development have been accurately shown and labeled as well as aJI on-site grading/site preparation. All
improvements existing on the property were completed in accordance with all regulations in existence at the time of their construction, unless otherwise noted.
NAME (PRINT}: __________ SIGN: _________ DATE: _____ _
above is an authorized a ent for the ro e owner include form B-62 si ned b owner.
1635 Faraday Ave Carlsbad, CA 92008 Ph: 442-339-2719 Email: Building@carlsbadca.gov
2
REV. 04/22
Building Permit Inspection History Finaled
{city of
Carlsbad
PERMIT INSPECTION HISTORY for (CBR2022-1363)
Permit Type: BLDG-Residential Application Date: 04/20/2022 Owner: ATR PALOMAR MOBIL
Work Class: P/M/E Issue Date: 04/22/2022 Subdivision: LA COSTA MEADOWS #3
Status: Closed -Finaled Expiration Date: 05/03/2023 Address: 2715 ABEDUL ST
IVRNumber: 40114 CARLSBAD, CA 92009-5310
Scheduled Actual Inspection Type Inspection No. Inspection Primary Inspector Reinspection Inspection
Date Start Date Status
05/26/2022 05/26/2022 BLDG-43 Air 183573-2022 Passed Tim Kersch Complete
Cond./Furnace Set
Checklist Item COMMENTS Passed
BLDG-Building Deficiency Yes
BLDG-Final Inspection 183574-2022 Failed Tim Kersch Reinspection Incomplete
Checklist Item COMMENTS Passed
BLDG-Building Deficiency Yes
BLDG-Plumbing Final Yes
BLDG-Mechanical Final Yes
BLDG-Structural Final Yes
BLDG-Electrical Final Yes
06/06/2022 06/06/2022 BLDG-44 184251-2022 Cancelled Tony Alvarado Reinspection Incomplete
Rough/Ducts/Dampers
Checklist Item COMMENTS Passed
BLDG-Building Deficiency June 6, 2022: No
1. Reached out to owners representative
Lisa, regarding reinspection for new mini
split system, due to previous failure in
HVAC contractor installation practices of
new air conditioning mini split system
installed.
2. Owner will reschedule at later date on a
Thursday to accommodate owner and
contractor representative schedule.
06/16/2022 06/16/2022 BLDG-44 185039-2022 Failed Tony Alvarado Reinspection Incomplete
Rough/Ducts/Dampers
Friday, November 4, 2022 Page 1 of 5
PERMIT INSPECTION HISTORY for (CBR2022-1363)
Permit Type: BLDG-Residential
Work Class: P/M/E
Status: Closed -Finaled
Application Date: 04/20/2022 Owner: ATR PALOMAR MOBIL
Issue Date: 04/22/2022 Subdivision: LA COSTA MEADOWS #3
Expiration Date: 05/03/2023
IVRNumber: 40114
Address: 2715 ABEDUL ST
CARLSBAD, CA 92009-5310
Scheduled
Date
Actual Inspection Type
Start Date
Inspection No. Inspection
Status
Primary Inspector Reinspection Inspection
Checklist Item
BLDG-Building Deficiency
BLDG-Building Deficiency
COMMENTS
June 16, 2022:
1. Reinspection required due to mechanical
HVAC electrical equipment in attic and coil
systems. Packaged units.
2. required metal leak-proof pans under
attic units-required.
3. 30" x 30" minimal working platforms in
front of each hvac units in attic locations
required.
4. Total of (3) qty. electrical HVAC attic
units require working platforms.
5. Owner is requesting catwalk to be
installed, 1/2" or 5/8" inch plywood catwalk
18" wide up to 22" wide, from attic access
ceiling opening to all mechanical
HVAC/equipment units.
6. Owners requesting mechanical code
sections call-outs requirements for all the
following items:leak pans, catwalk, safety
switch installation and location, size of
mechanical HVAC metal pans.
7. Rest of (3)-attic mechanical HVAC
electrical units replaced, scope of
work-OK.
June 6, 2022:
1. Reached out to owners representative
Lisa, regarding reinspection for new mini
split system, due to previous failure in
HVAC contractor installation practices of
new air conditioning mini split system
installed.
2. Owner will reschedule at later date on a
Thursday to accommodate owner and
contractor representative schedule.
10/21/2022 10/21/2022 BLDG-44 194653-2022 Failed Tony Alvarado
Rough/Ducts/Dampers
Friday, November 4, 2022
Passed
No
No
Reinspection Incomplete
Page 2 of 5
PERMIT INSPECTION HISTORY for (CBR2022-1363)
Application Date: 04/20/2022 Owner: ATR PALOMAR MOBIL Permit Type: BLDG-Residential
Work Class: P/M/E Issue Date: 04/22/2022 Subdivision: LA COSTA MEADOWS #3
Status:
Scheduled
Date
11/04/2022
Closed -Finaled Expiration Date: 05/03/2023
IVRNumber: 40114
Address: 2715 ABEDUL ST
CARLSBAD, CA 92009-5310
Actual Inspection Type
Start Date
Inspection No. Inspection
Status
Primary Inspector Reinspection Inspection
Checklist Item
BLDG-Building Deficiency
BLDG-Building Deficiency
BLDG-Building Deficiency
COMMENTS
June 6, 2022:
1. Reached out to owners representative
Lisa, regarding reinspection for new mini
split system, due to previous failure in
HVAC contractor installation practices of
new air conditioning mini split system
installed.
2. Owner will reschedule at later date on a
Thursday to accommodate owner and
contractor representative schedule.
June 16, 2022:
1. Reinspection required due to mechanical
HVAC electrical equipment in attic and coil
systems. Packaged units.
2. required metal leak-proof pans under
attic units-required.
3. 30" x 30" minimal working platforms in
front of each hvac units in attic locations
required.
4. Total of (3) qty. electrical HVAC attic
units require working platforms.
5. Owner is requesting catwalk to be
installed, 1/2" or 5/8" inch plywood catwalk
18" wide up to 22" wide, from attic access
ceiling opening to all mechanical
HVAC/equipment units.
6. Owners requesting mechanical code
sections call-outs requirements for all the
following items:leak pans, catwalk, safety
switch installation and location, size of
mechanical HVAC metal pans.
7. Rest of (3)-attic mechanical HVAC
electrical units replaced, scope of
work-OK.
October 21, 2022:
(mechanical inspection failed).
1. Attic location, (3)-new condenser unit
installed, new drip pans/metal drip pans too
small, and do not cover entire condensate
unit dimensions in order to help reduce
water damage, if any future leaks.
2. Two new Condensate lines, required to
be supported more efficiently with metal
strap, located at two locations in attic area.
3. Informed owner Lisa Rababy,
Reinspection required.
4. The rest of the new (3)-mechanical units
installed in attic location, scope of work
appears to be-OK.
11/04/2022 BLDG-44 195843-2022 Passed Tony Alvarado
Rough/Ducts/Dampers
Passed
No
No
No
Complete
Friday, November 4, 2022 Page 3 of 5
PERMIT INSPECTION HISTORY for (CBR2022-1363)
Permit Type: BLDG-Residential
Work Class: P/M/E
Status:
Scheduled
Date
Closed -Finaled
Actual Inspection Type
Start Date
Checklist Item
Application Date: 04/20/2022 Owner: ATR PALOMAR MOBIL
Issue Date: 04/22/2022 Subdivision: LA COSTA MEADOWS #3
Expiration Date: 05/03/2023
IVRNumber:
Inspection No.
COMMENTS
40114
Inspection
Status
Address: 2715 ABEDUL ST
CARLSBAD, CA 92009-5310
Primary Inspector Reinspection Inspection
Passed
BLDG-Building Deficiency November 4, 2022: Yes
BLDG-Final Inspection
Friday, November 4, 2022
(Final mechanical inspection approved).
1. 2nd. Level Attic location, (3)-new
condenser mechanical units installed, with
new drip pans/metal drip pans do not
cover entire condensate unit perimeter
dimensions, in order for drip metal pans to
collect and help reduce water damage to
building structure.
2. The new attic mechanical unit-coil
locations, therefore Will be protected if
there is any sort of mechanical coil unit
water failure in the future. The 3-new
metal drip pans encompass the entire
condenser unit coil system locations, in
order to collect any possible water runoff.
3. The Building inspector and homeowner
Lisa Rababy were informed regarding the
three new metal drip pans installed will be
adequate and provide secondary water
leak protection, if there is a future
mechanical unit water leak failure, per
contractor representative Ruben who
addressed and completed all final
correction issues on behalf of the the Right
Choice company.
4. Two new Condensate lines, required to
be supported more efficiently with straps,
located at two locations in attic
area-approved.
5. Informed owner Lisa Rababy, Final
mechanical inspection -approved ..
6. The rest of the new (3)-mechanical units
installed in attic location, scope of work
appears to be-OK.
195969-2022 Passed Tony Alvarado Complete
Page 4of 5
PERMIT INSPECTION HISTORY for (CBR2022-1363)
Permit Type: BLDG-Residential
Work Class: P/M/E
Status:
Scheduled
Date
Closed -Finaled
Actual Inspection Type
Start Date
Checklist Item
BLDG-Mechanical Final
BLDG-Structural Final
Friday, November 4, 2022
Application Date: 04/20/2022 Owner: ATR PALOMAR MOBIL
Issue Date: 04/22/2022 Subdivision: LA COSTA MEADOWS #3
Expiration Date: 05/03/2023
IVRNumber: 40114
Address: 2715 ABEDUL ST
CARLSBAD, CA 92009-5310
Inspection No. Inspection
Status
Primary Inspector Reinspection Inspection
COMMENTS
November 4, 2022:
(Final mechanical inspection approved).
1. 2nd. Level Attic location, (3)-new
condenser mechanical units installed, with
new drip pans/metal drip pans do not
cover entire condensate unit perimeter
dimensions, in order for drip metal pans to
collect and help reduce water damage to
building structure.
2. The new attic mechanical unit-coil
locations, therefore Will be protected if
there is any sort of mechanical coil unit
water failure in the future. The 3-new
metal drip pans encompass the entire
condenser unit coil system locations, in
order to collect any possible water runoff.
3. The Building inspector and homeowner
Lisa Rababy were informed regarding the
three new metal drip pans installed will be
adequate and provide secondary water
leak protection, if there is a future
mechanical unit water leak failure, per
contractor representative Ruben who
addressed and completed all final
correction issues on behalf of the the Right
Choice company.
4. Two new Condensate lines, required to
be supported more efficiently with straps,
located at two locations in attic
area-approved.
5. Informed owner Lisa Rababy, Final
mechanical inspection -approved ..
6. The rest of the new (3)-mechanical units
installed in attic location, scope of work
appears to be-OK.
Passed
Yes
Yes
Page 5 of 5