Project Title: TITLE BOXING TENANT IMPROVEMENT TO EXISTING FIRE
SPRINKLER SYSTEM
Applicant:
ARNOLD'S FIRE SPRINKLERS
13168 MAPLEVIEW ST
LAKESIDE CA
619-987-0295
Owner:
LOS GOGH ES PROPERTIES L L C
101 N WESTLAKE BLVD #201
WESTLAKE VILLAGE CA
Fees ($) Add'I Fees ($) Total ($) Balance ($)
0 0 0 0
1/1
3t7 C-J As [:~)o
GENERAL NOTES:
TYPICAL Up! DOWN GETAiL
— w000w
ERSEW&V
— AQAISTAaEAIPOOa
PROVIDE NEW UPRIGHT SPRINKLER PROTECTION FOR TENANT IMPROVEMENT OF EXISTING SPRINKLERED BUILDING.
SCOPE OF WORK:
UI
CC
—C
Ld
zo
z
Ffl)OIl11, C-1- . - #l1. 1BA LII
VICINITY MAP
FP-1
HANGER DETAIL 1111111111
I. THE FIRE SPRINKLER SYSTEM SHALL BE DESIGNED AND INSTALLED IN
ACCORDANCE WITH NFPA #13(2015) EDITION.
IT IS THE RESPONSIBILITY OF THE BUILDING OWNER TO MAINTAIN THE
INTEGRITY OF THE SPRINKLER SYSTEM.
THE SPRINKlER CONTRACTOR WILL PROVIDE THE OWNER WITH THE
NECESSARY INSTRUCTION MANUALS FOR THE UP KEEP OF THE SYSTEM AS
WELL AS A COPY OF NFPA #25 AT PROJECT CLOSE OUT IF APPUCABLE
ONLY NEW SPRINKLERS SHALL BE USED IN THE INSTALLATION OF THE
SPRINKlER SYSTEM.
SPRINKLER PLANS SHALL BE MAINTAINED AT ALL TIMES ON THE JOBSTTE.
AN APPOINTMENT SHALL BE MADE IN ADVANCE WITH THE APPROPRIATE
FIRE PREVENTION OFFICE FOR ALL INSPECTIONS AND TESTS,
ALL SYSTEM PIPING SHALL BE HYDROSTATIC
TESTED
AT 200 PSI FOR TWO
HOURS. OR AT SO PSI ABOVE THE SYSTEM OPERATING PRESSURE WHICH EVER IS GREATER IFAPPUCABLE.
ALL UNDERGROUND MAINS. AND LEAD-IN CONNECTIONS ARE DUSTING.
ALL VALVES SHALL HAVE A PERMENATELY AFFIXED SIGN INDICATING ITS
FUNCTION AND/OR AREA OF USE.
A STOCK OF SPARE SPRINKLERS OF EACH STYLE, TYPE, AND TEMPERATURE
RATING ALONG WITH A SPRINKLER WRENCH SHALL BE LOCATED NEXT TO THE
THE MAIN BUILDING RISER.
II. ANY PORTION OF THE SPRINKLER SYSTEM WHICH IS EXPOSED TOFREEZING
SHALL BE ADEQUATELY PROTECTED AGAINST EXPOSURE.
WHEN SERVING MORE THAN 105 SPRINKLERS AUTOMATIC SPRINKLER SYSTEM!
SHALL BE SUPERVISED BY AN APPROVED CENTRAL PROPRIEIORY OR REMOTE
STATION SERVICE AND/OR A LOCAL ALARM WHICH WILL GIVE AN AUDIBLE
SIGNAL AT A CONSTANTLY ATTENDED LOCATION.
ALL WALLS SHOWN ON PLANS ARE FULL HEIGHT WALLS (UNLESS NOTED
OTHERWISE).
TENANT IMPROVEMENT NOTES:
ALL WORK AND MATERIALS ARE DESIGNED TO BE IN ACCORDANCE WITH THE
NFPA 13 AND THE CARLSBAD FIRE DEPARTMENT REQUIREMENTS.
FIRE SPRINKLERS ARE SPACED PER LIGHT HAZARD OCCUPANCY WITH A
MAXIMUM SPACING OF 225 SQ. FT. ANY INCIDENTAL ORDINARY HAZARD
OCCUPANCIES ARE SPACED AT 130 SQ. FT.
ALL NEW PIPING TO BE SCHEDULE 30 BLACK STEEL PIPE WITH THREADABLE CAST OR DUCTILE IRON FiTTiNGS,
SUPPLY NEW PENDANT SPRINKLERS FROM EXISTING BRANCH LINES.
HANG ARMOVER PIPING TO ROOF! FLOOR STRUCTURE ABOVE WITH HANGERS
AS DETAILED.
B. FIELD VERIFY CEIUNG HEIGHTS AS INDICATED ON PLANS.
A.
GRAPHIC SCALE FIRE SPRINKLER LAYOUT PLAN