Technical Services: Tel: (800) 381-9312/ Fax: (800) 791-5500
Series TY-FRB - 28,42,56, and 8.0 K-factor
Upright, Pendent, and Recessed Pendent Sprinklers
Quick Response, Standard Coverage
General
Description
The Series TY-FRB, 2.8, 4.2, 5.6, and
8.0 K-factor, Upright and Pendent
Sprinklers described in this data sheet
are quick response - standard cover-
age, decorative 3 mm glass bulb type
spray sprinklers designed for use in
light or ordinary hazard, commercial
occupancies such as banks, hotels,
shopping malls, etc.
The recessed version of the Series
TY-FRB Pendent Sprinkler, where ap-
plicable, is intended for use in areas
with a finished ceiling. It uses either a
two-piece Style 10 (1/2 inch NPT) or
Style 40 (3/4 inch NPT) Recessed Es-
cutcheon with 1/2 inch (12,7 mm) of
recessed adjustment or up to 3/4 inch
(19,1 mm) of total adjustment from the
flush pendent position, or a two-piece
Style 20 (1/2 inch NPT) or Style 30 (3/4
inch NPT) Recessed Escutcheon with
1/4 inch (6,4 mm) of recessed adjust-
ment or up to 1/2 inch (12,7 mm) of
total adjustment from the flush pen-
dent position. The adjustment provided
by the Recessed Escutcheon reduces
the accuracy to which the fixed pipe
drops to the sprinklers must be cut.
Corrosion resistant coatings, where
applicable, are utilized to extend the
life of copper alloy sprinklers beyond
that which would otherwise be ob-
tained when exposed to corrosive at-
IMPORTANT
Always refer to Technical Data
Sheet TFP 700 for the "INSTALLER
WARNING" that provides cautions
with respect to handling and instal-
lation of sprinkler systems and com-
ponents. Improper handling and in-
stallation can permanently damage
a sprinkler system or its compo-
nents and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
Page 1 of 8
mospheres. Although corrosion resis-
tant coated sprinklers have passed the
standard corrosion tests of the appli-
cable approval agencies, the testing is
not representative of all possible cor-
rosive atmospheres. Consequently, it
is recommended that the end user be
consulted with respect to the suitability
of these coatings for any given corro-
sive environment. The effects of ambi-
ent temperature, concentration of
chemicals, and gas/chemical velocity,
should be considered, as a minimum,
along with the corrosive nature of the
chemical to which the sprinklers will be
exposed.
An intermediate level versions of the
Series TY-FRB Pendent Sprinklers are
detailed in Technical Data Sheet
TFP356, and Sprinkler Guards are de-
tailed in Technical Data Sheet TFP780
WARNINGS
The Series TY-FRB Sprinklers de-
scribed herein must be installed and
maintained in compliance with this
document, as well as with the applica-
ble standards of the National Fire Pro-
tection Association, in addition to the
standards of any other authorities hav-
ing jurisdiction. Failure to do so may
impair the performance of these de-
vices.
The owner is responsible for maintain-
ing their fire protection system and de-
vices in proper operating condition.
The installing contractor or sprinkler
manufacturer should be contacted
with any questions.
Model/Sprinkler
Identification
Numbers
TY1131 - Upright 2.81K, 1/2NPT
TY1231 - Pendent 2.81K, 1/2'NPT
TY2131 - Upright 4.2K, 1/2'NPT
TY2231 - Pendent 4.21K, 1/2NPT
TY3131 - Upright 5.6K, 1/2 NPT
JULY, 2004
TY3231 - Pendent 5.61K, 1/2NPT
TY4131 - Upright 8.0K, 3/4'NPT
TY4231 - Pendent 8.01K, 3/4'NPT
Technical
Data
Approvals
UL and C-UL Listed.
FM, LPCB, and NYC Approved.
(Refer to Table A for complete approval
information including corrosion resis-
tant status.)
Maximum Working Pressure
175 psi (12,1 bar)
Discharge Coefficient
K = 2.8 GPM/psi1/2 (40,3 LPM/bar112)
K = 4.2 GPM/psi112 (60,5 LPM/bar112)
K = 5.6 GPM/psi112 (80,6 LPM/bar112) K = 8.0 GPM/psi112 (115,2 LPM/barl'2)
Temperature Ratings
Refer to Table A and B
TFPI7I
Page 2 of 8 TFPI7I
ESCUTCHEON
PLATE SEATING
SURFACE
-r—
— 2-1/4
(57,2 mm)
1-9/16"
(39,7 mm)
SSP DEFLECTOR * 2-7/8 (73,0 mm) DIA.
SSU *
DEFLECTOR
7/16"
(11,1 mm)
NOMINAL
MAKE-IN
2-3/16' WRENCH (55,6 mm)
FLATS
1/2" NPT
7/16(11,1 mm) STYLE 10 or 20
1/2" ** NOMINAL RECESSED
MAKE-IN ESCUTCHEON NPT i
PENDENT RECESSED PENDENT UPRIGHT CROSS SECTION
1 - Frame 3 - Sealing 4- Bulb 6 - Deflector * Temperature rating is indicated on deflector or adjacent to 2- Button Assembly 5 - Compression 7- Bushing orifice seat on frame. Screw **Pipe thread connections per ISO 7/1 can be provided on
special request.
FIGURE 1
QUICK RESPONSE SERIES TY-FRB UPRIGHT (TY1I31) AND PENDENT (TY123 1) SPRINKLERS
2.8 K-FACTOR, 1/2 INCH NPT
ESCUTCHEON
PLATE SEATING
SURFACE
-r-
2-3/16"
(55,6 mm)
1-1/2"
(38,1 mm)
cm
2-7/8" (73,0 mm) DIA.
SSU *
DEFLECTOR
iik11"1i\ (11,1mm) I 1 7/160
MAKE-IN
2-3/16"
NOMINAL I
WRENCH __ (55,6 mm)
FLATS
1/2" NPT ** Ii'
SSP DEFLECTOR*
7/16" (11,1 mm) STYLE 10cr 20
1/2" ** NOMINAL RECESSED
MAKE-IN ESCUTCHEON NPT
PENDENT RECESSED PENDENT UPRIGHT CROSS SECTION
1 - Frame 3 - Sealing 4 - Bulb 6- Deflector * Temperature rating is indicated on deflector or adjacent to 2 - Button Assembly 5 - Compression orifice seat on frame. Screw **Pipe thread connections per ISO 7/1 can be provided on
special request.
FIGURE 2
QUICK RESPONSE SERIES TY-FRB UPRIGHT (TY2131) AND PENDENT (TV2231) SPRINKLERS
4.2 K-FACTOR, 1/2 INCH NPT
Finishes Bulb ..............Glass
Sprinkler: Refer to Table A and B Compression Screw .....Bronze
Recessed Escutcheon: White Coated, Deflector .......Copper/Bronze
Chrome Plated, or Brass Plated Bushing (K=2.8) .......Bronze
Physical Characteristics
Frame .............Bronze
Button .........Brass/Copper
Sealing Assembly ..........
Beryllium Nickel w/Teflonj -
Operation
The glass Bulb contains a fluid which
expands when exposed to heat. When
the rated temperature is reached, the
fluid expands sufficiently to shatter the
glass Bulb, allowing the sprinkler to
activate and water to flow.
.4-
TFPI7I Page 3 of 8
ESCUTCHEON 7/16(11,1 mm) STYLE 100r20
PLATE SEATING 1/2 ** NOMINAL RECESSED SSU* SURFACE MAKE-IN ESCUTCHEON NPT DEFLECTOR
2-3/16" __ (1
7/16"
1,1 mm)
NOMINAL
16"
(55,6 mm)
(38,1 mm)
W
H $ (55,6 mm)
MAKE-IN 7T
1-1/2" I 2-3/
WRENC _______ FLATS
SSP DEFLECTOR * 2-7/8" (73,0 mm) DIA. 1/2" NPT ** I
PENDENT RECESSED PENDENT UPRIGHT CROSS SECTION
1 - Frame 3 - Sealing 4 - Bulb 6- Deflector * Temperature rating is indicated on deflector or adjacent to 2 - Button Assembly 5 - Compression orifice seat on frame. Screw **Pipe thread connections per ISO 7/1 can be provided on
special request.
FIGURE 3
QUICK RESPONSE SERIES TY-FRB UPRIGHT (TY3131) AND PENDENT (TY3231) SPRINKLERS
5.6 K-FACTOR, 1/2 INCH NPT
ESCUTCHEON 1/2" (12,7 mm) STYLE 30 or 40
PLATE SEATING ** NOMINAL RECESSED
SURFACE 3/4"MAKE-IN ESCUTCHEON SSU*
NPT DEFLECTOR T__
1/2" 2-5/16"
NOMINAL
(39,7 mm) W 1 HI
(58,7 mm)
1-9/16
MAKE-IN 2 1
WRENC (57,2 mm) 3
SSP DEFLECTOR* 2-7/8 (73,0 mm) DIA. 3/4 NPT
PENDENT RECESSED PENDENT UPRIGHT CROSS SECTION
1 - Frame 3 - Seating 4 - Bulb 6- Deflector * Temperature rating is indicated on deflector or adjacent to 2 - Button Assembly 5 - Compression orifice seat on frame. Screw **Pipe thread connections per ISO 7/1 can be provided on
special request.
FIGURE 4
QUICK RESPONSE SERIES TY-FRB UPRIGHT (TV4131) AND PENDENT (TV4231) SPRINKLERS
8.0 K-FACTOR, 3/4 INCH NPT
Design
Criteria
The Series TY-FRB Pendent and Up-
right Sprinklers are intended for fire
protection systems designed in ac-
cordance with the standard installation
rules recognized by the applicable
Listing or Approval agency (e.g., UL
Listing is based on the requirements of
NFPA 13, and FM Approval is based
on the requirements of FM's Loss Pre-
vention Data Sheets ). Only the Style
10, 20, 30, or 40 Recessed Escutch-
eon, as applicable, is to be used for
recessed pendent installations.
Installation
The Series TY-FRB Sprinklers must be
installed in accordance with the follow-
ing instructions:
NOTES
Do not install any bulb type sprinkler if
the bulb is cracked or there is a loss of
liquid from the bulb. With the sprinkler
Page 4 of 8
SPRINKLER FINISH (See Note 7)
K TYPE TEMP. BULB NATURAL I CHROME I WHITE
LIQUID BRASS PLATED POLYESTER
135°F/57°C Orange
PENDENT
(TY1231)
and 1,2,3,5
155°F/68°C Red
175°F/79°C Yellow
UPRIGHT 200°F/93°C Green
2.8
1/2'
(TY1131)
286°F/141°C Blue
NPT 135°F/57°C Orange
RECESSED
PENDENT
155°F/68°C Red
175°F/79°C Yellow (TY1231)*
Figure 5 1, 2, 5 200°F/93°C Green
135°F/57°C Orange
RECESSED
PENDENT
155°F/68°C Red
1750F/790C Yellow (TY1231)**
Figure 6 200°F/93°C Green
135°F/57°C Orange
PENDENT
(TY2231) 155°F/68°C Red
175°F/79°C Yellow and
UPRIGHT 200°F/93°C Green
4.2
1/2"
(TY2131)
1,2 286°F/141C Blue
135°F/57°C Orange NPT
RECESSED
PENDENT
155°F/68°C Red
1750F/791C Yellow (TY2231)*
Figure 7 200°F/930C Green
135°F/57°C Orange
RECESSED
PENDENT
1551F/681C Red
175°F/79°C Yellow (TY2231)**
Figure 8 200F/93°C Green
NOTES:
Listed by Underwriters Laboratories, Inc. (UL) as Quick Response Sprinklers.
Listed by Underwriters Laboratories, Inc. for use in Canada (C-UL) as Quick Response
Sprinklers.
Approved by Factory Mutual Research Corporation (FM) as Quick Response Sprin-
klers.
5. Approved by the City of New York under MEA 354-01 -E.
7. Where Polyester Coated Sprinklers are noted to be UL and C-UL Listed, the sprin-
klers are UL and C-UL Listed as Corrosion Resistant Sprinklers.
* Installed with Style 10 (1/2" NPT) or Style 40 (3/4" NPT) 3/4' Total Adjustment
Recessed Escutcheon, as applicable.
** Installed with Style 20 (1/2" NPT) or Style 30 (3/4" NPT) 1/2" Total Adjustment
Recessed Escutcheon, as applicable.
Frame and Deflector only. Listings and approvals apply to color (Special Order).
N/A: Not Available
TABLE A
LABORATORY LISTINGS AND APPROVALS
2.8 AND 4.2 K-FACTOR SPRINKLERS
held horizontally, a small air bubble A leak tight 1/2 inch NPT sprinkler joint
should be present. The diameter of the should be obtained with a torque of 7
air bubble is approximately 1/16 inch to 14 ft.lbs. (9,5 to 19,0 Nm). A maxi-
(1,6 mm) for the 1350F/57°C to 3/32 mum of 21 ft. lbs. (28,5 Nm) of torque
inch (2,4 mm) for the 286°F/1410C may be used to install sprinklers with
temperature ratings. 112 NPT connections. A leak tight 314
TFPI7I
inch NPT sprinkler joint should be ob-
tained with a torque of 10 to 20 ft.lbs.
(13,4 to 26,8 Nm). A maximum of 30
ft. lbs. (40,7 Nm) of torque is to be used
to install sprinklers with 3/4 NPT con-
nections. Higher levels of torque may
distort the sprinkler inlet and cause
leakage or impairment of the sprinkler.
Do not attempt to make-up for insuffi-
cient adjustment in the escutcheon
plate by under- or over-tightening the
sprinkler. Readjust the position of the
sprinkler fitting to suit.
The Series TY-FRB Pendent and Up-
right Sprinklers must be installed in
accordance with the following instruc-
tions.
Step 1. Pendent sprinklers are to be
installed in the pendent position, and
upright sprinklers are to be installed in
the upright position.
Step 2. With pipe thread sealant ap-
plied to the pipe threads, hand tighten
the sprinkler into the sprinkler fitting.
Step 3. Tighten the sprinkler into the
sprinkler fitting using only the W-Type
6 Sprinkler Wrench (Ref. Figure 13).
With reference to Figures 1, 2, 3, and
4, the W-Type 6 Sprinkler Wrench is to
be applied to the sprinkler wrench
flats.
The Series TY-FRB Recessed Pen-
dent Sprinklers must be installed in
accordance with the following instruc-
tions.
Step A. After installing the Style 10.
20, 30, or 40 Mounting Plate, as appli-
cable, over the sprinkler threads and
with pipe thread sealant applied to the
pipe threads, hand tighten the sprin-
kler into the sprinkler fitting.
Step B. Tighten the sprinkler into the
sprinkler fitting using only the W-Type
7 Recessed Sprinkler Wrench (Ref.
Figure 14). With reference to Figure 1,
2, 3, and 4, the W-Type 7 Recessed
Sprinkler Wrench is to be applied to
the sprinkler wrench flats.
Step C. After the ceiling has been in-
stalled or the finish coat has been ap-
plied, slide on the Style 10, 20, 30, or
40 Closure over the Series TY-FRB
Sprinkler and push the Closure over
the Mounting Plate until its flange
comes in contact with the ceiling.
TFPI7I Page 5 of 8
SPRINKLER FINISH (See Note 8)
K TYPE TEMP. BULB
LIQUID
NATURAL I
BRASS
CHROME
PLATED I
WHITE***
POLYESTER
LEAD
COATED
5.6
1/2"
PENDENT
(TY3231)
and
UPRIGHT
(TY3131)
135°F/57°C Orange
1,2,3,4,5,6,7 1,2,3,5
155°F/68°C Red
175°F/79°C Yellow
200°F/93°C Green
286'F/1 41'C Blue
NPT
RECESSED
PENDENT
(TY3231)*
Figure 9
135°F/57°C Orange
1, 2, 4, 5 N/A
155°F/68"C Red
175°F/79"C Yellow
200°F/93"C Green
RECESSED
PENDENT
(TY3231)"
Figure 10
135°F/57°C Orange
1,2,3,4,5
I I I I 1,2,4, 5 I
Green
N/A
155"F/68°C Red
175°F/79°C Yellow
200°F/93°C
8.0
3/4,'
PENDENT
(TY4231),
and
UPRIGHT
(TY4131)
135°F/57°C Orange
1,2,3,4,5,6,7
1,2,5
155°F/68°C Red
175°F/79"C Yellow
200°F/93°C Green
286°F/141°C Blue
NPT RECESSED
PENDENT
(TY4231)*
Figure 11
135"F/57"C Green
1,2,4, 5 N/A
155°F/68°C Orange
175°F/79°C Red
200°F/93°C Yellow
L
RECESSED
PENDENT
(TY4231)**
Figure 12
-
135°F/57°C Orange
1, 2, 3, 4,5 N/A
I I
155°F/68"C Red
175" F/79°C Yellow
200"F/93°C Green
NOTES:
Listed by Underwriters Laboratories, Inc. (UL) as Quick Response Sprinklers.
Listed by Underwriters Laboratories, Inc. for use in Canada (C-UL) as Quick Response Sprinklers.
Approved by Factory Mutual Research Corporation (FM) as Quick Response Sprinklers.
Approved by the Loss Prevention Certification Board (LPCB Ref. No. 007k/04) as Quick Response Sprinklers; however, the
LPCB does not rate the thermal sensitivity of recessed sprinklers.
Approved by the City of New York under MEA 354-01-F.
VdS Approved (For details contact Tyco Fire & Building Products, Enschede, Netherlands, Tel. 31-53-428-4444/Fax 31-53-428-3377).
Approved by the Loss Prevention Certification Board (LPCB Ref. No. 094a/06) as Quick Response Sprinklers.
Where Polyester Coated and Lead Coated Sprinklers are noted to be UL and C-UL Listed, the sprinklers are UL and C-UL Listed as
Corrosion Resistant Sprinklers. Where Lead Coated Sprinklers are noted to be FM Approved, the sprinklers are FM Approved as a
Corrosion Resistant Sprinklers.
* Installed with Style 10 (1/2' NPT) or Style 40 (3/4" NPT) 3/4" Total Adjustment Recessed Escutcheon, as applicable.
** Installed with Style 20 (1/2' NPT) or Style 30 (3/4' NPT) 1/2' Total Adjustment Recessed Escutcheon, as applicable.
Frame and Deflector only. Listings and approvals apply to color (Special Order).
N/A: Not Available
TABLE B
LABORATORY LISTINGS AND APPROVALS
5.6 AND 8.0 K-FACTOR SPRINKLERS
Page 6 of 8
2-7/8' DIA.
5/8±1/4' (73,0 mm) I 3/4' (19,1 mm)
(15,9±6,4 mm) - 2-1/4' DIA. 1/4' (6,4 mm) I
FACE OF 57,2 MOUNTING
SPRINKLER PLATE
FITTING
,
1/8'
(3.2mJ
/
MOUNTING /
,!LIII
6'
SURFACE//
(33,3 mm) CLOSURE SERIES
TY-FRB 13/16"(20,6 mm)
FIGURE 5
SERIES TV-FRB RECESSED PENDENT
WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT
STYLE 10 RECESSED ESCUTCHEON
2.8 K-FACTOR, 1/2 INCH NPT
- 2-7/8' DIA. -
5/8±1/4' (73,0 mm) 3/4'(19,1 mm)
(15,9±6,4 mm) 2-1/4' DIA. 1/4' (6,4 mm)
;
FACE OF MOUNTING(57,2
SPRINKLER PLATE I
FITTING
1/8'
(3,2 mm)
MOUNTING
SURFACE
SERIES 1-1/4'(31,8 mm) CLOSURE TYFRB 3/4'(19,1 mm)
FIGURE 7
SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT
STYLE 10 RECESSED ESCUTCHEON
4.2 K-FACTOR, 1/2 INCH NPT
TFPI7I
2-7/8' DIA.
1/2±1/8' (73,0 mm) 1/2' (12,7 mm) r (12,7±3,2 mm) 2-1/4' DIA. 1/4"(6,4 mm)
FACE OF 57,2 mm) MOUNTING
SPRINKLER PLATE
FITTING
/~(3,2 mm)
____________
MOUNTING /
I16,
71 t t
SURFACE/
(33,3 mm) CLOSURE SERIES
TY-FRB 1-1/16"(27,0 mm)
FIGURE 6
SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 20 RECESSED ESCUTCHEON
2.8 K-FACTOR, 1/2 INCH NPT
- 2-7/8' DIA.
(73,0 mm) 1/2±1/8' 1/2'(12,7mm)
E (12,7±3,2 mm) 2-1/4' DIA. j 1/4" (6,4 mm)
FACE OF (57,2 mm) MOUNTING
1/8'
SPRINKLER I PLATE
FITTING
(3,2 mm)
/ _
f \ ll
MOUNTING
SURFACE
SERIES 1-1/4' (31,8 CLOSURE TY-FRB 1' (25,4 mm)
FIGURE 8
SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 20 RECESSED ESCUTCHEON
4.2 K-FACTOR, 1/2 INCH NPT
Care and
Maintenance
The Series TY-FRB Sprinklers must be
maintained and serviced in accord-
ance with the following instructions:
NOTES
Before closing a fire protection system
main control valve for maintenance
work on the fire protection system that
it controls, permission to shutdown the
affected fire protection system must be
obtained from the proper authorities
and all personnel who maybe affected
by this action must be notified.
Absence of an escutcheon, which is
used to cover a clearance hole, may
delay the time to sprinkler operation in
a fire situation.
Sprinklers that are found to be leaking
or exhibiting visible signs of corrosion
must be replaced.
Automatic sprinklers must never be
painted, plated, coated or otherwise
altered after leaving the factory. Modi-
fied sprinklers must be replaced.
Sprinklers that have been exposed to
corrosive products of combustion, but
have not operated, should be replaced
if they cannot be completely cleaned
by wiping the sprinkler with a cloth or
by brushing it with a soft bristle brush.
Care must be exercised to avoid dam-
age to the sprinklers - before, during,
and after installation. Sprinklers dam-
aged by dropping, striking, wrench
twist/slippage, or the like, must be re-
placed. Also, replace any sprinkler that
has a cracked bulb or that has lost
liquid from its bulb. (Ref. Installation
Section).
Frequent visual inspections are rec-
ommended to be initially performed for
corrosion resistant coated sprinklers,
after the installation has been com-
pleted, to verify the integrity of the cor-
rosion resistant coating. Thereafter,
annual inspections per NFPA 25
should suffice; however, instead of in-
specting from the floor level, a random
sampling of close-up visual inspec-
tions should be made, so as to better
determine the exact sprinkler condi-
TFPI7I
- 2-7/8' DIA. -
5/8±1/4" (73,0 mm) I 3/4'(19,1 mm)
(15,9±6,4 mm) - 2-1/4" DIA. 1/4" (6,4 mm)
FACE OF (57,2 mm) MOUNTING SPRINKLER PLATE FITTING
1/8"
(3,2 mm)
MOUNTING
SURFACE
SERIES 1-1/4"(31,8 mm) CLOSURE TYFRB 3/4"(19,11 mm)
FIGURE 9
SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT
STYLE 10 RECESSED ESCUTCHEON
5.6 K-FACTOR, 1/2 INCH NPT
2-7/8' DIA.
5/8±1/4" (73,0 mm) I 3/4"(19,1 mm)
(15,9±6,4mm) - 2-1/4" DIA. 1/4" (6,4 mm)
FACE OF (572 mm) MOUNTING
PLATE SPRINKLER
FITTING
________ 1/8"
__ __________ (3,2 mm)
//,U/;:1 ___ __ ____
MOUNTING
SURFACE
CLOSURE SERIES 1-5/16"(33,3 mm)
TYfRB 13/16"(20,6 mm)
FIGURE 11
SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT
STYLE 40 RECESSED ESCUTCHEON
8.0 K-FACTOR, 3/4 INCH NPT
Page 7 of 8
- 2-7/8' DIA.
1/2±1/8' 1/2' (12,7 mm) (73,0 mm)
[(12,7±3,2 mm) - 2-1/4" DIA. 1/4' (6,4 mm)
I FACE OF (57,2 mm) MOUNTING I # 1/8"
I SPRINKLER PLATE I I FITTING
(32m m) I
/ ________________
\
MOUNTING
SURFACE
SERIES 1-1/4"(31,8 mm) CLOSURE TYFRB 1" (25,4 mm)
FIGURE 10
SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 20 RECESSED ESCUTCHEON
5.6 K-FACTOR, 1/2 INCH NPT
2-7/8' DIA.
1/2±1/8' (73,0 mm) 1/2"(12,7 mm)
E (12,7±3,2 mm) - 2-1/4" DIA. -I 1/4" (6,4 mm) I
FACE OF (57,2 mm) I MOUNTING I
SPRINKLER PLATE I
1/8
FITTING
I
_ 2 ___
t \
MOUNTING
SURFACE
CLOSURE SERIES 1-5/16"(33,3 mm)
TYFRB 1-1/16'(27,0 mm)
FIGURE 12
SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 30 RECESSED ESCUTCHEON
8.0 K-FACTOR, 3/4 INCH NPT
tion and the long term integrity of the
corrosion resistant coating, as it may
be affected by the corrosive conditions
present.
The owner is responsible for the in-
spection, testing, and maintenance of
their fire protection system and de-
vices in compliance with this docu-
ment, as well as with the applicable
standards of the National Fire Protec-
tion Association (e.g., NFPA 25), in
addition to the standards of any other
authorities having jurisdiction. The in-
stalling contractor or sprinkler manu-
facturer should be contacted relative to
any questions.
It is recommended that automatic
sprinkler systems be inspected,
tested, and maintained by a qualified
Inspection Service in accordance with
WRENCH RECESS
(END "A" USED FOR
1/2" NPT MODELS)
WRENCH RECESS
(END "B" USED FOR
3/4" NPT MODELS)
FIGURE 13
W-TYPE 6 SPRINKLER
WRENCH
local requirements and/or national
codes.
WRENCH
RECESS
PUSH WRENCH
IN TO ENSURE
ENGAGEMENT
WITH SPRINKLER
WRENCHING AREA
FIGURE 14
W-TYPE 7 RECESSED
SPRINKLER WRENCH
Page 8 of 8 TFPI7I
P/N 57 - XXX - X - XXX
I L
MODEL/SIN
330 2.8K UPRIGHT (1/2'NPT) 1Y1131
331 2.8K PENDENT (1/2'NPT) 1Y1231
340 4.2K UPRIGHT (1/2NPT) TY2131
341 1 4.2K PENDENT (1/2"NPT) TY2231
370 5.6K UPRIGHT (1/2'NPT) TY3131
371 5.6K PENDENT (1/2NPT) 1Y3231
390 8.0K UPRIGHT (3/4'NPT) TY4131
391 8.0K PENDENT (3/4NPT) TY4231
I
L1 135
SPRINKLER
155
175
200
286
RATING
1 NATURAL BRASS 155°F/68°C
4 WHITE POLYESTER 1750F/79°C
3 WHITE (RAL9010)" 200*F/93*C
9 CHROME PLATED 286°F/141°C
7 LEAD COATED
* Eastern Hemisphere sales only.
TABLE C
PART NUMBER SELECTION
SERIES TY-FRB PENDENT AND UPRIGHT SPRINKLERS
Limited
Warranty
Products manufactured by Tyco Fire
Products are warranted solely to the
original Buyer for ten (10) years
against defects in material and work-
manship when paid for and properly
installed and maintained under normal
use and service. This warranty will ex-
pire ten (10) years from date of ship-
ment by Tyco Fire Products. No war-
ranty is given for products or
components manufactured by compa-
nies not affiliated by ownership with
Tyco Fire Products or for products and
components which have been subject
to misuse, improper installation, corro-
sion, or which have not been installed,
maintained, modified or repaired in ac-
cordance with applicable Standards of
the National Fire Protection Associa-
tion, and/or the standards of any other
Authorities Having Jurisdiction. Mate-
rials found by Tyco Fire Products to be
defective shall be either repaired or
replaced, at Tyco Fire Products' sole
option. Tyco Fire Products neither as-
sumes, nor authorizes any person to
assume for it, any other obligation in
connection with the sale of products or
parts of products. Tyco Fire Products
shall not be responsible for sprinkler
system design errors or inaccurate or
incomplete information supplied by
Buyer or Buyer's representatives.
IN NO EVENT SHALL TYCO FIRE
PRODUCTS BE LIABLE, IN CON-
TRACT, TORT, STRICT LIABILITY OR
UNDER ANY OTHER LEGAL THE-
ORY, FOR INCIDENTAL, INDIRECT,
SPECIAL OR CONSEQUENTIAL
DAMAGES, INCLUDING BUT NOT
LIMITED TO LABOR CHARGES, RE-
GARDLESS OF WHETHER TYCO
FIRE PRODUCTS WAS INFORMED
ABOUT THE POSSIBILITY OF SUCH
DAMAGES, AND IN NO EVENT
SHALL TYCO FIRE PRODUCTS' LI-
ABILITY EXCEED AN AMOUNT
EQUAL TO THE SALES PRICE.
THE FOREGOING WARRANTY IS
MADE IN LIEU OF ANY AND ALL
OTHER WARRANTIES EXPRESS OR
Ordering
Procedure
®statatur 1ica1 distributor for avail-
ab,.indicate the
full product
name. Refer to
the Price List for
complete listing
of Part Numbers.
Sprinkler Assemblies with NPT
Thread Connections:
Specify: (Specify Model/SIN), Quick
Response, (specify K-factor), (specify
temperature rating), Series TY-FRB
(specify Pendent or Upright) Sprinkler
with (specify type of finish or coating),
P/N (specify from Table C).
Recessed Escutcheon:
Specify: Style (specify) Recessed Es-
cutcheon with (specify finish), P/N
(specify).
1/2 (15 mm)
Style 10
Chrome Plated ............P/N 56-701-9-010
White Coated .............P/N 56-701-4-010
White RAL90I0" ...........P/N 56-701-3-010
Brass Plated ..............P/N 56-701-2-010
1/2 (15 mm)
Style 20
Chrome Plated ............P/N 56-705-9-010
White Coated .............P/N 56-705-4-010
White RAL9010" ...........P/N 56-705-3-010
Brass Plated ..............P/N 56-705-2-010
3/4 (20 mm)
Style 30
Chrome Plated ............P/N 56-705-9-011
White Coated .............P/N 56-705-4-011
White RAL9010*P/N 56-705-3-011
Brass Plated ..............P/N 56-705-2-011
3/4" (20 mm)
Style 40
Chrome Plated ............P/N 56-700-9-010
White Coated .............P/N 56-700-4-010
White RAL9010*P/N 56-700-3-010
Brass Plated ..............P/N 56-700-2-010
* Eastern Hemisphere sales only.
Sprinkler Wrench:
Specify: W-Type 6 Sprinkler Wrench,
P/N 56-000-6-387.
Specify: W-Type 7 Sprinkler Wrench,
P/N 56-850-4-001.
TYCO FIRE PRODUCTS, 451 North Cannon Avenue, Lansdale, Pennsylvania 19446
-Is
tqc0 /Fire & Building
I Products
Technical Services: Tel: (800) 381-9312/ Fax: (800) 791-5500
Series EC-8 - 80 K-factor
Extended Coverage (Light Hazard)
Pendent and Recessed Pendent Sprinklers
General
Description
The Series EC-8 Extended Coverage
Pendent Sprinklers are decorative
glass bulb sprinklers designed for use
in light hazard occupancies. They are
intended for use in automatic sprinkler
systems designed in accordance with
standard installation rules (e.g., NFPA
13) for a maximum coverage area of
400 ft2 (37,2 m2), as compared to the
maximum coverage area of 225 ft2
(20,6 m2) for standard coverage sprin-
klers used in light hazard occupancies.
The recessed version of the EC-8, in-
tended for use in areas with a finished
ceiling, uses either the two-piece Style
30 or 40 Recessed Escutcheon. The
Style 30 Recessed Escutcheon pro-
vides up to 1/2 inch (12,7 mm) of total
adjustment from the flush pendent po-
sition, whereas, the Style 40 provides
3/4 inch (19,1 mm) of vertical adjust-
ment from the flush pendent position.
The adjustment provided by the Re-
cessed Escutcheons reduces the ac-
curacy to which the fixed pipe drops to
the sprinklers must be cut.
Corrosion resistant coatings, where
applicable, are utilized to extend the
life of copper alloy sprinklers beyond
that which would otherwise be ob-
tained when exposed to corrosive at-
mospheres. Although corrosion resis-
IMPORTANT
Always refer to Technical Data
Sheet TFP 700 for the "INSTALLER
WARNING" that provides cautions
with respect to handling and instal-
lation of sprinkler systems and com-
ponents. Improper handling and in-
stallation can permanently damage
a sprinkler system or its compo-
nents and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
Page 1 of 6
tant coated sprinklers have passed the
standard corrosion tests of the appli-
cable approval agencies, the testing is
not representative of all possible cor-
rosive atmospheres. Consequently, it
is recommended that the end user be
consulted with respect to the suitability
of these corrosion resistant coatings
for any given corrosive environment.
The effects of ambient temperature,
concentration of chemicals, and
gas/chemical velocity, should be con-
sidered, as a minimum, along with the
corrosive nature of the chemical to
which the sprinklers will be exposed.
WARNINGS
The Series EC-8 Extended Coverage
Sprinklers described herein must be
installed and maintained in compli-
ance with this document, as well as
with the applicable standards of the
National Fire Protection Association,
in addition to the standards of any
other authorities having jurisdiction.
Failure to do so may impair the per-
formance of these devices.
The owner is responsible for maintain-
ing their fire protection system and de-
vices in proper operating condition.
The installing contractor or sprinkler
manufacturer should be contacted
with any questions.
Model/Sprinkler
Identification
Number
TY4232 - Pendent, 8.0K
TY4232 is a redesignation for C4232
JANUARY, 2005
Technical
Data
Approvals
UL and C-UL Listed. FM and NYC Ap-
proved. (Refer to Table A for complete
approval information including corro-
sion resistant status. The approvals
apply to the service conditions indi-
cated in the Design Criteria section.)
Maximum Working Pressure
175 psi (12,1 bar)
Pipe Thread Connection
3/4 inch NPT
Discharge Coefficients
K = 8.0 GPM/psi112
(115,2 LPM/bar112)
TFP223
4-
Page 2 of 6 TFP223
Components: 3/4 ** ESCUTCHEON PLATE
1 - Frame NPT SEATING SURFACE
2 - Button
Sealing Assembly
Bulb 2
i/8. Compression 2
Screw 3 (54,0 mm)
6 - Deflector*
indicated on Deflector.1
,(12,7
1/2
Temperature rating is
mm) /16OMINAL
MAKE-IN (36,5 mm
** Pipe thread
connections per ISO
7/1 can be provided 6*
on special request.
FIGURE 1
SERIES EC-8 (TY4232) EXTENDED COVERAGE PENDENT SPRINKLERS
SPRINKLER FINISH (See Note 4)
HAZARD TYPE TEMP. BULB NATURAL
BRASS
I CHROME
PLATED
WHITE
LIQUID [POLYESTER
LIGHT
Refer to Table B for UL and C-UL
Sensitivity Rating
and
Sensitivity Rating
PENDENT 135*F/57*C Orange
1,2,3,5 155*F/68*C Red
_______________
REC. PENDENT
w/ Style 30 Esc.
135*F/57*C Orange
1,2,3,5
Refer to Table C for FM 155°F/68°C Red
REC. PENDENT
WI Style 40 Esc.
135°F/57°C Orange
1, 2, 5 155°F/68°C Red
NOTES:.
Listed by Underwriters Laboratories, Inc. (UL).
Listed by Underwriters Laboratories, Inc. for use in Canada (C-UL).
Approved by Factory Mutual Research Corporation (FM).
Where Polyester Coated Sprinklers are noted to be UL and C-UL Listed, the sprinklers are UL and C-UL Listed as Corrosion
Resistant Sprinklers.
Approved by the City of New York under MEA 113-04-E.
Frame and Deflector only. Listings and approvals apply to color (Special Order).
TABLE A
LABORATORY LISTINGS AND APPROVALS
(Refer to the Design Criteria Section)
Temperature Ratings
135°F/57°C and 1550F/680C
Finish
Sprinkler: Refer to Table A
Recessed Escutcheon: White Coated,
Chrome Plated, and Brass Plated
Physical Characteristics
Frame .............Bronze
Button ..............Bronze
Sealing Assembly ..........
Beryllium Nickel w/Teflont
Bulb ........Glass (3 mm dia.)
Compression Screw .........
.......Bronze
Deflector ............Brass
t Registered trademark of DuPont
Operation
The glass bulb contains a fluid that
expands when exposed to heat. When
the rated temperature is reached, the
fluid expands sufficiently to shatter the
glass bulb, allowing the sprinkler to
activate and flow water.
Design
Criteria
The Series EC-8 Extended Coverage
Pendent Sprinklers must only be in-
stalled in accordance with the applica-
ble UL and C-UL Listing or FM Ap-
proval requirements as indicated
below. Only the Style 30 or 40 Re-
cessed Escutcheon is to be used for
recessed installation, as applicable
(Ref. Table A, B, and C)..
UL and C-UL Listing
Requirements
The Series EC-8 Sprinklers may be
used for the coverage areas shown
in Table D, based on maintaining the
minimum specified flow rate as a
function of coverage area and haz-
ard group for all of the sprinklers in
the design area.
With respect to heat sensitivity, the
Series EC-8 Sprinklers can be used
with unobstructed construction con-
sisting of flat, smooth ceilings (in-
cluding bar joists) with a maximum
pitch of one in six as defined and
permitted by NFPA 13.
The minimum allowable spacing be-
TFP223
135°F 155°F
AREA STYLE
16x16 Pendent OR OR
16 x 16 Style 30 Recessed OR OR
16 06 Style 40 Recessed OR OR
18x18 Pendent OR OR
18 x 18 Style 30 Recessed OR SR
18 x 18 Style 40 Recessed OR SR
20 x 20 Pendent OR SR
20 x 20 Style 30 Recessed OR SR
20 x 20 Style 40 Recessed SR SR
OR: Quick Response
SR: Standard Response
N/A: Not Applicable
TABLE B
SENSITIVITY RATING FOR UL AND C-UL LISTING
OF SERIES EC-8 SPRINKLERS
135°F 155°F
AREA STYLE
16x16 Pendent OR OR
16 x 16 Style 30 Recessed OR N/A
16 x 16 Style 40 Recessed N/A N/A
18x18 Pendent OR OR
18 x 18 Style 30 Recessed OR N/A
18 x 18 Style 30 Recessed N/A N/A
20 x 20 Pendent OR OR
20 x 20 Style 30 Recessed OR N/A
20 x 20 Style 40 Recessed N/A N/A
OR: Quick Response
SR: Standard Response
N/A: Not Applicable
TABLE C
SENSITIVITY RATING FOR FM APPROVAL
OF SERIES EC-8 SPRINKLERS
Page 3 of 6
Installation
The Series EC-8 Sprinklers must be
installed in accordance with the follow-
ing instructions:
NOTES
Do not install any bulb type sprinkler if
the bulb is cracked or there is a loss of
liquid from the bulb. With the sprinkler
held horizontally, a small air bubble
should be present. The diameter of the
air bubble is approximately 1/16 inch
(1,6mm).
A leak tight 3/4 inch NPT sprinkler joint
should be obtained with a torque of 10
to 20 ft.!bs. (13,4 to 26,8 Nm). A maxi-
mum of 30 ft. lbs. (40,7 Nm) of torque
is to be used to install sprinklers.
Higher levels of torque may distort the
sprinkler inlet with consequent leak-
age or impairment of the sprinkler.
Do not attempt to compensate for in-
sufficient adjustment of an Escutcheon
Plate by under- or over-tightening the
Sprinkler. Readjust the position of the
sprinkler fitting to suit.
Step 1. The sprinkler must be installed
with the deflector parallel to the mount-
ing surface. Pendent sprinklers must
be installed in the pendent position.
Step 2. After installing the Style 30 or
40 mounting plate (or other escutch-
eon, as applicable) over the sprinkler
pipe threads, and with pipe thread
sealant applied to the pipe threads,
hand tighten the sprinkler into the
sprinkler fitting.
Step 3. Wrench tighten pendent sprin-
klers using only the W-Type 3 (End A)
Sprinkler Wrench. Wrench tighten the
recessed pendent sprinklers using
only the W-Type 4 Sprinkler Wrench.
The wrench recess of the applicable
sprinkler wrench (Ref. Figure 4 and 5)
is to be applied to the sprinkler wrench
flats (Ref. Figure 1).
tween the Series EC-8 Sprinklers, to
prevent cold soldering, is 8 feet (2,4
m).
4. The Series EC-8 Sprinklers are to be
installed in accordance with all other
requirements of NFPA 13 for ex-
tended coverage pendent sprin-
klers.
FM Approval
Requirements
The Series EC-8 Extended Coverage
Sprinklers are to be installed in ac-
cordance with the applicable Factory
Mutual Loss Prevention Data Sheet.
Information provided in the FM Loss
Prevention Data Sheets relate to, but
are not limited to, hydraulic design,
ceiling slope and obstructions, mini-
mum and maximum allowable spacing,
and deflector-to ceiling distance.
'-a
Page 4 of 6 TFP223
DESCRIPTION AREA GPM PSI
TY4232 (K=8.0) PENDENT 16 x 16 26 10.6
18x18 33 17.0
20x20 40 25.0
1 ft. = 0.3048 m
1 ft2 = 0.093 m2
1 gpm = 3.785 1pm
1 psi = 0.06895 bar
1 gpm/ft2 = 40.74 mm/mm
TABLED'
FLOW CRITERIA FOR UL AND C-UL LISTING
OF SERIES EC-8 SPRINKLERS
_ 2-7/8' DIA.
1/2±1/8 (73,0 mm) 1/2 (12,7 mm) r (12,7±3,2 mm) - 2-1/4" DIA. 1/4(6,4mm) I
FACE OF (57,2 mm)
SPRINKLER
FITTING (3,2 mm)
MOUNTING MOUNTING SURFACE PLATE
CLOSURE
1-1/4" (31 .8 mm)
1" (25,4 mm)
FIGURE 2
SERIES EC-8 RECESSED PENDENT SPRINKLER ASSEMBLY
WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 30 RECESSED ESCUTCHEON
• 2-7/8" DIA.
9/16±1/4" (73,0 mm) 3/4(19,1 mm) r (14,3±6,4 mm) - 2-1/4 DIA. 1/4k (6,4 mm) I
FACE OF "l (57,2 mm) I
SPRINKLER 1/8 I
FITTING _______ (32mm)
MOUNTING
SURFACE,/MOUNTING
PLATE
CLOSURE
1-5/16'(33,3 mm)
13/16"(20,6 mm)
FIGURE 3
SERIES EC-8 RECESSED PENDENT SPRINKLER ASSEMBLY
WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT
STYLE 40 RECESSED ESCUTCHEON
"FITTING SIDE"
TOWARDS SPRINKLER
FITTING
/ WRENCH
(
RECESS
(END
FIGURE 4
W-TYPE 3 SPRINKLER
WRENCH
WRENCH
RECESS
I
WRENCH
LUGS
FIGURE 5
W-TYPE 4 RECESSED
SPRINKLER WRENCH
Care and
Maintenance
The Series EC-8 Sprinklers must be
maintained and serviced in accord-
ance with the following instructions:
NOTE
Before closing a fire protection system
main control valve for maintenance
work on the fire protection system that
it controls, permission to shut down
the affected fire protection systems
must be obtained from the proper
authorities and all personnel who may
be affected by this action must be no-
tified.
Sprinklers that are found to be leaking
or exhibiting visible signs of corrosion
must be replaced.
Automatic sprinklers must never be
painted, plated, coated, or otherwise
altered after leaving the factory. Modi-
fied sprinklers must be replaced.
Sprinklers that have been exposed to
-.4
TFP223 Page 5 of 6
corrosive products of combustion, but
have not operated, should be replaced
if they cannot be completely cleaned
by wiping the sprinkler with a cloth or
by brushing it with a soft bristle brush.
Care must be exercised to avoid dam-
age to the sprinklers - before, during,
and after installation. Sprinklers dam-
aged by dropping, striking, wrench
twist/slippage, or the like, must be re-
placed. Also, replace any sprinkler that
has a cracked bulb or that has lost
liquid from its bulb. (Ref. Installation
Section).
Frequent visual inspections are rec-
ommended to be initially performed for
corrosion resistant coated sprinklers,
after the installation has been com-
pleted, to verify the integrity of the cor-
rosion resistant coating. Thereafter,
annual inspections per NFPA 25
should suffice; however, instead of in-
specting from the floor level, a random
sampling of close-up visual inspec-
tions should be made, so as to better
determine the exact sprinkler condi-
tion and the long term integrity of the
corrosion resistant coating, as it may
be affected by the corrosive conditions
present.
The owner is responsible for the in-
spection, testing, and maintenance of
their fire protection system and de-
vices in compliance with this docu-
ment, as well as with the applicable
standards of the National Fire Protec-
tion Association (e.g., NFPA 25), in
addition to the standards of any other
authorities having jurisdiction. The in-
stalling contractor or sprinkler manu-
facturer should be contacted relative to
any questions.
It is recommended that automatic
sprinkler systems be inspected,
tested, and maintained by a qualified
Inspection Service in accordance with
local requirements and/or national
codes.
Limited
Warranty
Products manufactured by Tyco Fire
Products are warranted solely to the
original Buyer for ten (10) years
against defects in material and work-
manship when paid for and properly
installed and maintained under normal
use and service. This warranty will ex-
pire ten (10) years from date of ship-
ment by Tyco Fire Products. No war-
ranty is given for products or
components manufactured by compa-
nies not affiliated by ownership with
Tyco Fire Products or for products and
components which have been subject
to misuse, improper installation, corro-
sion, or which have not been installed,
maintained, modified or repaired in ac-
cordance with applicable Standards of
the National Fire Protection Associa-
tion, and/or the standards of any other
Authorities Having Jurisdiction. Mate-
rials found by Tyco Fire Products to be
defective shall be either repaired or
replaced, at Tyco Fire Products' sole
option. Tyco Fire Products neither as-
sumes, nor authorizes any person to
assume for it, any other obligation in
connection with the sale of products or
parts of products. Tyco Fire Products
shall not be responsible for sprinkler
system design errors or inaccurate or
incomplete information supplied by
Buyer or Buyer's representatives.
IN NO EVENT SHALL TYCO FIRE
PRODUCTS BE LIABLE, IN CON-
TRACT, TORT, STRICT LIABILITY OR
UNDER ANY OTHER LEGAL THE-
ORY, FOR INCIDENTAL, INDIRECT,
SPECIAL OR CONSEQUENTIAL
DAMAGES, INCLUDING BUT NOT
LIMITED TO LABOR CHARGES, RE-
GARDLESS OF WHETHER TYCO
FIRE PRODUCTS WAS INFORMED
ABOUT THE POSSIBILITY OF SUCH
DAMAGES, AND IN NO EVENT
SHALL TYCO FIRE PRODUCTS' LI-
ABILITY EXCEED AN AMOUNT
EQUAL TO THE SALES PRICE.
THE FOREGOING WARRANTY IS
MADE IN LIEU OF ANY AND ALL
Ordering
Procedure
When placing an order, indicate the full
product name. Please specify the
Sprinkler Identification Number (SIN),
quantity, and temperature rating. Refer
to the Price List for complete listing of
Part Numbers.
Contact your local distributor for avail-
ability.
Sprinkler Assemblies with NPT
Thread Connections:
Specify: TY4232, (specify temperature
rating), Extended Coverage Pendent
Sprinkler with (specify finish), P/N
(specify).
135F/57C
Natural Brass .............PSN 50-801-1-135
White Coated .............PSN 50-801-4-135
White (RAL9O1O). .......... PSN 50-801-3-135
Chrome Plated ............PSN 50-801-9-135
155F/68°C
Natural Brass .............PSN 50-801-1-155
White Coated .............PSN 50-801-4-155
White (RAL9O1O). .......... PSN 50-801-3-155
Chrome Plated ............PSN 50-801-9-155
*Eastern Hemisphere sales only.
Recessed Escutcheon:
Specify: Style (30 or 40) Recessed
Escutcheon with (specify finish), P/N
(specify).
Style 30 Recessed Escutcheon
Chrome Plated ............PSN 56-705-9-011
White Color Coaled ........PSN 56-705-4-011
White (RAL9O1O). .......... PSN 56-705-3-011
Brass Plated ..............PSN 56-705-2-011
Style 40 Recessed Escutcheon
Chrome Plated ............PSN 56-700-9-010
White Color Coated ........PSN 56-700-4-010
White (RAL9O1O). .......... PSN 56-700-3-010
Brass Plated ..............PSN 56-700-2-010
*Eastern Hemisphere sales only.
Sprinkler Wrench:
Specify: W-Type 3 Sprinkler Wrench,
P/N 56-895-1-001
Specify: W-Type 4 Recessed Sprinkler
Wrench, P/N 56-875-4-001
gdw1ri1pJ;i7J;
Page 6 of 6 TFP223
TYCO FIRE PRODUCTS, 451 North Cannon Avenue, Lansdale, Pennsylvania 19446