HomeMy WebLinkAbout3257 CAMINO DE LOS COCHES; 202; AS110035; Permit10/29/2020 AS 110035 Permit Data
City of Carlsbad
Sprinkler Permit
Permit No: AS110035
3257 CAMINO DE LOS
Job Address: Status: ISSUED
COCHES
Permit Type: SPRINK Applied 3/7/2011
Parcel No: 2550313200 Approved: 3/7/2011
Lot #: 0
Reference No.: Issued: 3/7/2011
PC #: Inspector:
Project Title: VIBRA HEALTHCARE T.I. FIRE SPRINKLER PLAN CHECK &
INSPECTIONS
Applicant:
TOTAL FIRE PROTECTION, INC.
STE. 244
1611-AS. MELROSE DR.
VISTA, CA
760-525-4329
Owner:
P S F H LOS COCHES L L C
401 BST#1200
SAN DIEGO CA
Fees ($) Add'l Fees ($) Total ($) Balance ($)
130 0 130 0
1/1
4611 OO"
TrFeP
MATERIAL DATA SUBMITTAL
Vibra Healthcare Ti.
3257 Camino De Los Coches, Suite 202
Carlsbad, CA 92009
Page Description Manufacturer
1-2 Sprinkler Piping
3-10 Sprinkler Piping
11-12 Sprinkler Piping
13-19 Sprinkler
20 Pipe Hangers & Supports
21 Pipe Hangers & Supports
22-24 Pipe Hangers & Supports
ALLIED Dyna Thread Pipe
TYCO Ductile Iron Fittings
TYCO Mechanical Tee
TYCO TY-FRB Q.R. SSP
AFCON Fig 300 Ring
AFCON Fig 655 All Thread Rod
HILTI HDI Drop in Anchor
Total Fire Protection, Inc.
1611A S. Melrose Dr. #244
Vista, Ca 92081.
(760)525-4329 fax (877) 724-4329
C16-955387
tfpjohnc@gmail.com
APt!ED AS SUBITTED
CARLSBAD FIRE DEPARTMENT
=411
Full Line Sch-40 Replacement
DynaThreada offers the life expectancy of Sch4O with superior hydraulics and greater value
Dyna-Thread sprinkler pipe represents an engineering advancement for the sprinkler pipe industry. It combines the safety
and longevity of traditional Sch-40 pipe with quality and superior hydraulic advantages.
Dyna-Thread's inside diameter is up
to 3.6% larger than Sch-40 giving it
superior hydraulics. And, when used
in combination with Dyna-Flow pipe,
down sizing often occurs.
Dyna-Thread is fully listed and
approved by UL, ULC, and FM for
fire sprinkler applications.
The life expectancy of Dyna-Thread
and Sch-40 are equal based on the
calculated wall thicknesses per UL.
The consistent quality of steel used to
make Dyna-Thread facilitates smooth
threading and lower maintenance
costs.
The exterior of Dyna-Thread is
protected by a clean, durable mill
coating for extended shelf life and
easy paint application.
0 <~> @
Listed Approved Listed
With its increased strength and lighter
weight, Dyna-Thread reduces
installation fatigue and is ideal for
retro-fit applications.
Corrosion Resistance Ratio (CRR) is a
UL (Underwriters Laboratory) term for
the estimated life expectancy of a pipe
joint. This is based on the calculated
wall thickness at the base of the first
exposed thread, assumed to be the
weakest point of the pipe length. Dyna-
Thread and Sch-40 have the same
calculated wall thicknesses at this point
and are both assigned the same CRR of
1.00.
The internal surface of all black Allied
Tube & Conduit Fire Sprinkler pipe
products up to 4.5000" in diameter is
coated with our new Antibacterial
Formula, "ABF'. In scientific laboratory
test, ABS proved to have superior
resistance to microbial colonization of
pipe walls, thereby delaying or possibly
preventing the onset of
Microbiologically Influenced corrosion
(MIC) when the First Sprinkler System
is first installed.
More wall thickness at the thread
(CRR=l .00) gives Dyna-Thread
better life expectancy than lightwall
threadable pipe joints.
Unlike lightwall threadable pipe,
Dyna-Thread has no thread gauge
warning.
Dyna-Thread is approved for
standard hanger spacing (15 ft.
O.C.), can be used as earthquake
sway bracing, and is safe to use as
drops.
Dyna-Thread is safer to weld on.
Dyna-Thread is more widely
accepted than lightwall threadable
where Sch-40 is specified.
Specifications &Approvals
Super 40/Dyna-Thread pipe is
manufactured to meet: ASTM A-135,
Grade A and is in compliance with
NFPA-13. All sizes of Super 40/Dyna-
Thread are rated at 300 psi working
pressure. Super 40/Dyna-Thread is UL
and ULC Listed for wet, thy deluge and
pre-action sprinkler systems and FM
Approved for use in wet systems. Super
40/Dyna-Thread can be "hot-dip"
galvanized to meet FM requirement for
thy systems. Super 40/Dyna-Thread is
approved for all threaded couplings and
welded outlets and is suitable for all
roll-grooved, and plain-end fittings.
(See listing information).
Specifications
NPS Nominal I.D. Wt. WI. (H20 Filled) Pc WI/Lift (21') WI/LIft (24') Wi/lift (25')
In; mm in; mm Lbs/Ft; Kg/in Lbs/Ft, Kg/ni Lift Lbs; Kg Lbs; Kg Lbs; Kg
V 1.080 1.330 1.75 70 1955 2234 232
25 27.4 2.0 2.60 70 887 1013 1051
1W 1.408 1.870 2.54 51 2002 2288 2384
32 35.8 2.8 3.78 51 908 1038 108
1W 1.639 2.290 3.22 44 2115 2418 2519
40 41.6 3.4 4.79 44 959 1097 114
2 2.104 3.050 4.57 30 1921 2196 228
50 53.4 4.5 6.80 30 871 996 103
tqco/Flow Control 9 cihecJ 16100 S. Lathrop' Harvey, IL 60426
11350 Norcom Rd. ' Philadelphia, PA 19154
TUBE & CONDUIT 2525 N. 27 th Ave. Phoenix, AZ 85009
Customer Service:
(800) 882-5543
Fax 708-339-180"----"
S3-3
Submittal Data Sheet Dyna"ThreadG
Full Line Sch-40 Replacement
Dyna-Thread sprinkler pipe represents an engineering advancement for the sprinkler
pipe industry. It combines the safety and longevity of traditional Sch-40 pipe with
quality and superior hydraulic advantages.
Comparison to Schedule 40 Dyna-Threads inside diameter is up to 3.6% larger than
Sch-40 giving it superior hydraulics. Also, when used in combination with Dyna-Flow
pipe, down sizing often occurs. Dyna-Thread is fully listed and approved UL, ULC,
and FM for fire sprinkler applications. The life expectancy of Dyna-Thread and Sch-40
are equal based on the calculated wall thicknesses per UL. The consistent quality of
steel used to make Dyna-Thread facilitates smooth threading and lower maintenance
costs. The exterior of Dyna-Thread is protected by a clean, durable mill coating for
extended shelf life and easy paint application. With its increased strength and lighter
weight, Dyna-Thread reduces installation fatigue and is ideal for retro-fit applications.
Corrosion Resistance Ratio (CRR) is a UL (Underwriters Laboratory) term for the
estimated life expectancy of a pipe joint. This is based on the calculated wall thickness
at the base of the first exposed thread, assumed to be the weakest point of the pipe
length. Dyna-Thread and Sch-40 have the same calculated wall thicknesses at this
point and are both assigned the same CRR of 1.00.
Comparison to L.W.T. Pipe More wall thickness at the thread (CRR= 1.00) gives
Dyna-Thread better life expectancy than lightwall threadable pipe joints. Unlike
lightwall threadable pipe Dyna-Thread has no thread gauge warning. Dyna-Thread is
approved for standard hanger spacing (15 ft. O.C.), can be used as earthquake sway
bracing, and is safe to use as drops. Dyna-Thread is safer to weld on than many zinc-
coated lightwall threadable pipe products. Dyna-Thread is more widely accepted than
lightwall threadable where Sch-40 is specified.
Stamp Here
Specifications & Approvals Super 40/
Dyna-Thread pipe is manufactured to
meet: ASTM A 135, Grade A and is in
compliance with NFPA-13. All sizes of
Super 40/Dyna-Thread are rated at 300
psi working pressure. Super 40/ Dyna-
Thread is UL and ULC Listed for wet,
dry and pre-action sprinkler systems and
FM Approved for use in wet systems.
Super 40/Dyna-Thread can be "hot-dip"
galvanized to meet FM requirement for
dry systems. Super 40/Dyna-Thread is
approved for all threaded couplings and
welded outlets and is suitable for all roll-
grooved, and plain-end fittings. (See
listing information).
The internal surface of all black Fire
Sprinkler pipe up to 4.5000" in diameter
shall be coated with Allied Tube &
Conduit Antibacterial Formula "ABF".
NPS Nominal I.D. WI. Wt. (H20 Filled) Pcsl Wtfl.iIt (21') Wt/Ult (24') Wt,tifl (25')
In; mm in; mm Lbs/Ft; Kg/rn Lbs/Ft Kg/rn Lift Lbs; Kg Lbs; Kg Lbs; Kg
1.080 1.330 1.75 70 1955 2234 232
25 27.4 2.0 2.60 70 887 1013 105
1¼' 1.408 1.870 2.54 51 2002 2288 2384
32 35.8 2.8 3.78 51 908 1038 108
1W 1.639 2.290 3.22 44 2115 2418 2511
40 41.6 3.4 4.79 44 959 1097 114
2.104 3.050 4.57 30 1921 2196 228
50 53.4 4.5 6.80 30 871 996 103
American Tube and Pipe was acquired by Allied Tube and Conduit on February I,
1997. The engineered lightwall and standard wall family of products although they
have different names are the same in all respects with regard to strength, weight,
bundle count, listings and approvals. For example,
Dyna-Flow and Super Flo are the same product as
are Dyna Thread and Super 40. XL is manufactured Us (jj) <j> 9
with Exterior galvanized coating. BLT is
manufactured with Black lacquer coating. Listed Approved Listed
Project: Sprinkler Contractor: Date:
Engineer: Specification Reference: System Type:
Locations: Comments: (I) S3-4
tqC0 /Fire & Building
/ Products
Technical Services: Tel: (800) 381-9312 I Fax: (800) 791-5500
Pipe Fittings
NPT Threaded,
Ductile Iron
General
Description
The TycoO Series 800 Threaded Pipe
Fittings and California Tees & Elbows
are manufactured from ductile iron.
They are stronger and more corrosion
resistant than cast iron fittings. The
additional strength is provided by the
ductile properties and by adding mag-
nesium while the iron is being poured
into the final cast shape. Although
lighter than standard cast iron, the fit-
tings have an added advantage of be-
ing less susceptible to cracking due to
their added strength.
The Series 800, California, and Figure
719 Threaded Pipe Fittings are a re-
designation for the Central Series 800,
California, and Figure 719 Threaded
Pipe Fittings.
WARNINGS
The Threaded Pipe Fittings described
herein must be installed and main-
tained in compliance with this docu-
ment, as well as with the applicable
standards of the National Fire Pro-
tection Association, in addition to the
standards of any other authorities hav-
ing jurisdiction. Failure to do so may
impair the performance of these
devices.
The owner is responsible for maintain-
ing their fire protection system and de-
vices in proper operating condition.
The installing contractor or sprinkler
manufacturer should be contacted
with any questions.
Technical
Data
Approvals: UL Usted and FM Approved
Maximum Working Pressure:
Series 800 and California Fittings:
250 psi (17,2 bar)
Figure 719 Plug:
250 psi (17,2 bar)
Material:
Series 800 and California Fittings:
Ductile Iron
Figure 719 Plug:
Cast Iron
Pipe Thread:
NPT per ANSI B1.20.1
Installation
Apply Teflont tape or high quality pipe
joint compound on male pipe threads
and tighten two to three turns beyond
hand tight.
NOTE
Installers who have not used ductile
iron threaded fittings should be in-
structed that the fittings are stron-
ger than the pipe and overtightening
the fitting can create leaks and cause
damage to pipe threads. In general,
there is about one-half turn difference
between cast iron and ductile iron fit-
tings. Apply Teflon tape or high qual-
ity pipe joint compound on the male
pipe threads and tighten two to three
turns beyond hand tight. If an auto-
matic make-on machine is being used,
please exercise caution in setting the
machine to the proper parameters pri-
or to tightening fittings onto the male
pipe threads.
Limited
Warranty
Products manufactured by Tyco Fire
& Building Products (TFBP) are war-
ranted solely to the original Buyer for
ten (10) years against defects in mate-
rial and workmanship when paid for
and properly installed and maintained
under normal use and service. This
warranty will expire ten (10) years from
date of shipment by TFBP. No warran-
ty is given for products or components
manufactured by companies not af-
filiated by ownership with TFBP or for
products and components which have
been subject to misuse, improper in-
stallation, corrosion, or which have not
been installed, maintained, modified or
repaired in accordance with applicable
Standards of the National Fire Protec-
tion Association, and/or the standards
of any other Authorities Having Juris-
diction. Materials found by TFBP to be
defective shall be either repaired or re-
placed, at TFBP's sole option. TFBP
neither assumes, nor authorizes any
person to assume for it, any other ob-
ligation in connection with the sale of
products or parts of products. TFBP
shalt not be responsible for sprinkler
system design errors or inaccurate or
incomplete information supplied by
Buyer or Buyer's representatives.
In no event shall TFBP be liable, in
contract, tort, strict liability or under
any other legal theory, for incidental,
indirect, special or consequential dam-
ages, including but not limited to labor
charges, regardless of whether TFBP
was informed about the possibility of
such damages, and in no event shall
TFBP's liability exceed an amount
equal to the sales price.
The foregoing warranty is made in lieu
of any and all other warranties. ex-
oress or implied, including warranties
of merchantability and fitness for a
particular ourpose,
This limited warranty sets forth the ex-
clusive remedy for claims based on
failure of or defect in products, materi-
als or components, whether the claim
is made in contract, tort, strict liability
or any other legal theory.
This warranty will apply to the full ex-
tent permitted by law. The invalidity,
in whole or part, of any portion of this
warranty will not affect the remainder.
Ordering
Procedure
When placing an order, indicate the
full product name. Please specify the
quantity, figure number, wall thickness,
and size.
Page 1 of 10 JANUARY, 2008
tregistered trademark of E. I. du Pont de Nemours and Company or its affiliates. 0 TFPI7IO
Page 2oflO TFPI7I0
gure 813
86780
86781
86280
86281
86282
86283
86782
FIGURE 811 FIGURE 813
900 ELBOW 450 ELBOW
Nominal Pipe
Size Figure 811 Fi
ANSI A B Approx. A B Approx.
Inches Inches Inches Weight Part Ines Inches Weight Part
DN (mm) (mm) Lbs. Number (mm) (mm) Lbs. Number
(kg) (kg)
1/2 1.13 0.56 0.24 86206 0.88 0.38 0.22 DN15 (28,7) (14,2) (0111) (22,4) (9,7) (0,09)
3/4 1.31 0.75 0.40 86205 1.00 0.44 0.33
0N20 (33,3) (19,0) (0,18) (25,4) (11,2) (0,15)
I 1.50 0.81 0.64 86200 1.13 0.81 0.48
DN25 (38,1) (20,6) (0129) (28,7) (20,6) (0,21)
1-1/4 1.75 1.06 0.95 86201 1.31 0.63 0.73 DN32 (44,5) (26,9) (0,43) (33,3) (16,0) (0,33)
1-1/2 1.94 1.19 1.24 86202 1.44 0.69 0.93 0N40 (49,3) (30,2) (0,56) (36,6) (17,5) (0,42)
2 2.25 1.50 1.74 86203 1.68 0.94 1.55 0N50 (57,1) (38,1) (0179) (42,7) (23,9) (0,70) __
2-1/2 2.69 1.56 3.28 86204 1.94 1.00 2.70 0N65 1(68,3) (39,6) (1,49) (49,3) (25,4) (1,22)
TABLE 1 NOMINAL DIMENSIONS FIGURES 811 & 813
TFPI7IO Page 3of 10
FIGURE 812
90 REDUCING ELBOW
Nominal Pipe Figure 812 Size
ANSI A B C D Approx.
Inches Inches Inches Inches Inches Weight
Lbs.
Part
ON (mm) (mm) (mm) (mm) Number
(kg)
314x1/2 1.19 1.19 0.63 0.63 0.33 86342 DN20x 15 (30,2) (30,2) (16,0) (16,0) (0115)
1 x 1/2 1.25 1.38 0.56 0.81 0.44 86210 DN25 x 15 (31,8) (35,1) (14,2) (20,6) (0,20)
I x 3/4 1.38 1.44 0.69 0.88 0.53
DM25 x 20 (35,1) (36,6) (17,5) (22,4) (0,24) 86211
1-114x1/2 1.31 1.50 0.63 0.94 0.64 86212 DN32 x 15 (33,3) (38,1) (16,0) (23,9) (0,29)
1-1/4 x 3/4 1.44 1.63 0.75 1.06 0.75 86213 DM32 x 20 (36,6) (41,4) (19,0) (26,9) (0,34)
1-114x1 1.56 1.68 0.88 1.00 0.77 86214 DM32 x 25 (39,6) (42,7) (22,4 (25,4) (0135)
1-1/2x3/4 1.50 1.75 0.75 1.19 0.95 86221
DN40x20 (38,1) (44,4) (19,0) (30,2) (0,43)
1-1/2 x 1 1.63 1.81 0.88 1.13 0.99 86215 DN40 x 25 (41,4) (46,0) (22,4) (28,7) (0,45)
1-1/2x 1-1/4 1.81 1.88 1.13 1.19 1.14 86216 DM40 x 32 (4610) (47,8) (28,7) (30,2) (0,52)
2x314 1.63 1.94 0.88 1.38 1.39 86217 DM50 x 20 (41,4) (49,3) (22,4) (35,1) (0,63)
2x1 1.75 2.06 2.00 1.31 1.58 86218 DN50 x 25 (44,4) (52,3) (50,8) (33,3) (0,72)
2x 1-1/2 2.00 2.19 1.25 1.44 1.67 86220 DM50 x 40 (50,8) (55,6) (31,8) (36,6)
2-1/2 x 2 2.38 2.63 1.25 1.88 3.01 86262 DN65 x 50 (60,5) (66,8) (31,8) (47,8) (1136)
TABLE 2
NOMINAL DIMENSIONS FIGURE 812
(D
TFPI7I0 Page 5of 10
Nominal Pipe
Size
Approx.
ANSI Inches
DN
Weight
Lbs.
Part
Number
(kg)
1/2 0.18 72779 DN15 (0,08)
3/4 0.26 72778 DN20 (0,11)
1 0.44 72755 DN25 (0,20)
1-1/4 0.54 72754 DN32 (0,24)
1-1/2 0.71 72753 0N40 (0,32)
2 1.15 72752 DN50
2.29
0N65 (19,0)
Al J
L! UJii
FIGURE 814 FIGURE 818
IRON TEE STRAIGHT COUPLING
86340
TABLE 4
NOMINAL DIMENSIONS FIGURES 814 & 818
Figure 814 Figure 818
A B Approx. A B
Inches Inches Weight
Lbs.
Part
Number Inches Inches
(mm) (mm) (kg)
(mm) (mm)
1.13 0.56 0.33 1.38 0.31
(28,7) (14,2) (0,15) (35,1) (7,9)
1.31 0,75 0.50 86341 1.63 0.56
(33,3) (19,0) (0,23) (41,4) (14,0)
1.50 0.81 0.85 86230 175 0.38
(38,1) (20,6) (0,38) (44,4) (9,7)
1.75 1.06 1.30 86231 2.00 0.56
(44,4) (26,9) (0,59) (50,8) (14,0)
1.94 1.19 1.63 86232 2.19 0.75
(49,3) (30,2) (0,74) (55,6) (1910)
2.25 1.50 2.63 6233 2.63 1.13
(57,1) (38,1) (1,19) (66,8) (28,7) (0,52)
2-1/2 2.69 1.564.55 6234
E
3.00 0.75
(68,3) (39,6) (2,06)_____
(76,2)
TFPI7I0 Page GoflO
Page 7 of 10 TFPI7IO
—C7
FIGURE 815
REDUCING TEE
Nominal Pipe Size Figure 815
A B C D E F Approx.
ANSI Inches Inches Inches Inches Inches Inches Inches Weight Part
ON (mm) (mm) (mm) (mm) (mm) (mm) Lbs. Number
(kg)
1-1/2x1-1/4x112 1.44 1.31 1.69 0.69 0.63 1.13 1.03 86257 DN40 x 32 x 1 (36,6) (33,3) (42,9) (17.5) (16,0) (28,7) (0,47)
1.1/2x1-114x3/4 1.50 1.44 1.75 0.75 0.75 1.19 1.10 86258 0N40 x 32 x 20 (38.1) (36,6) (44,5) (19,0) (19.0) (30,1) (0.50)
1-1/2x 1-1/4x 1 1.63 1.56 1.81 0.88 0.88 1.13 1.31 86259 DN40 x 32 x 25 (41.4) (39.7) (46,0) (22,4) (22,4) (28.7) (0.59)
1-1/2x1-1/4x2 2.19 2.13 2.00 1.44 1.44 1.25 1.94 86260 0N40x 32 x 50 (55.6) (54,1) (50,8) (36,6) (36,6) (57,1) (0,88)
1-1/2x1-1/2x112 1.44 1.44 1.69 0.69 0.69 1.13 1.14 86261 0N40 x 40 x 15 (36,6) (36,6) (42,9) (17,5) (17,5) (28.7) (0,52)
1-112 x 1-1/2 x 3/4 1.50 1.50 1.75 0.75 0.75 1.19 1.23 86262 DN40x40x20 (38.1) (38,1) (44,4) (19.0) (19,0) (30.1) (0.56)
1-1/2x1-1/2x1 1.63 1.63 1.81 0.88 0.88 1.13 1.38 86263 0N40 x 40 x 25 (41,2) (41,2) (46,0) (22,4) (22,4) (28,7) (0,62)
1-1/2x1-1/2x1-114 1.81 1.81 1.88 1.06 1.06 1.19 1.50 86264 DN40 x 40 x 32 (46,0) (46,0) (476) (27.0) (27,0) (30.1) (0.68)
1-112x1-1I2x2 2.19 2.19 2.00 1.44 1.44 1.25 2.00 86265 DN40x40x50 (55,5) (55,5) (50,8) (36,6) (36.6) (31,7) (0.91)
2x1 x2 2.25 2.00 2.25 1.50 1.31 1.50 2.18 86266 DN50 x 25 x 50 (57,2) (50,8) (57,2) (38,1) (33,3) (38,1) (0,99)
2x1-1/4x2 2.25 2.13 2.25 1.50 1.44 1.50 2.31 86267 DN50 x 32 x 50 (57,2) (54,1) (57.2) (38,1) (36,6) (38,1) (1,05)
2x1-1/2x1/2 1.50 1.44 1.88 0.75 0.69 1.31 1.50 86268 DN50 x 40 x 15 (38.1) (36.6) (47,8) (19,0) (17,5) (33,3) (0,68)
2x1-1/2x314 1.63 1.50 1.94 0.88 0.75 1.38 1.61 86269 05040 x 20 (41,4) (38,1) (49,3) (22,4) (19,0) (35,0) (0,73)
2x1-112x1 1.75 1.63 2.00 1.00 0.88 1.31 1.65 86270 DN50x40x25 (44,5) (41,4) (50,8) (25,4) (22,4) (33,3) (0,75)
2x1-1I2x1-1/2 2.06 1.94 2.19 1.31 1.19 1.44 2.03 86272 DN50 x 40 x 40 (52,4) (49,2) (55.5) (33.3) (30,2) (36.6) (0.92)
2x1-1/2x2 2.25 2.19 2.50 1.50 1.44 1.50 2.37 86273 DN50x40x50 (57,1) (55.5) (63,5) (38,1) (36.6) (38,1) (1,07)
2x2x1/2 1.50 1.50 1.88 0.75 0.75 1.31 1.50 86222 DN50 x 50 x 1 (38,1) (38.1) (47.8) (19,0) (19,0) (33,3) (0.68)
2 x 2 x 314 1.63 1.63 1.94 0.88 0.88 1.38 1,67 86223 DN5O x 50 x 20 (41,4) (41,4) (49,3) (22,4) (22.4) (35,0) (0,76)
2x2x1 1.75 1.75 2.00 1.00 1.00 1.31 1.91 86224 DN50 x 50 x 25 (44.5) (44.5) (50.8) (25,4) (25.4) (33.3) (0,88)
2x2x1414 1,88 1.88 2.13 1.13 1.13 1.44 2.05 86225 DN50 x 50 x 32 (47,8) (47,8) (54,1) (28.7) (28.7) (36.6) (0,93)
2 x 2 x 1-1/2 2.00 2.00 2.19 1.25 1.25 1.50 2.11 86226 DN50x50x40 (50,8) (50,8) (55,6) (31,8) (3118) (38.1) (0.96)
2 x 2 x 2-1/2 2.63 2.63 2.38 1.75 1.88 1.44 3.67 86227 DN50 x 50 x 65 (66.8) (66,6) (60,5) (44,5) (47.8) (36.6) (1.66)
2-1/2 x 2 x 3/4 1.75 1.63 2.31 0.63 0.88 1.75 2.22 86274 0(465 x 50 x20 (44,5) (41,4) (58,7) (15,9) (22.4) (44,5) (1,01)
TABLE 5(2 0F2)
NOMINAL DIMENSIONS FIGURE 815
Page 8 of 10 TFPI7IO
1!!1lI
iiiiiiui
FIGURE 820 820
CAP
FIGURE 830
BRASS SEAT UNION
FIGURE 719
PLUG
Nominal Pipe Figure 820 Figure 830 Figure 719 Size
ANSI A Approx. A B Approx. A Approx.
Inches inches Weight
Lbs.
Part
Number Inches Inches Weight
Lbs.
Part
Number Inches Weight
Lbs.
Part
Number
DN (mm)
(kg)
(mm) (mm) (kg) (mm) (kg)
112 0.88 0.15 72776 1.88 0.81 0.47 68207 0.94 0.10 86292 DN15 (22.4) (0,06) (47,8) (20,6) (0,21) (23,9) (0,04)
3/4
0N20
1.00
(25,4)
0.22
(0,10) 72777 2.00
(50,8)
0.94
(23,9)
0.66
(0,30) 86275 1.13
(28,7)
0.18
(0,08)
86293
1 1.18 0.33 72824 2.19 0.81 1.08 86276 1.25 0.28 86294 DN25 (30,0) (0,15) (55,6) (20,6) (0,49) (31,7) (0,13)
1-114
DN32
1.31
(33,3)
0.54
(0,24) 72756 2.50
(63,5)
1.06
(26,9)
1.54
(0,70) 86277 86295
1
(35,1)
0.50
(0,23)
1-1/2
0N40
1.38
(35,1)
0.68
(0,31) 72822 2.63
(66.8)
1.19
(30,2)
2.03
(0,92) 86278 1.44
(36.6)
0.70
(0,32)
86296
2
DN50
1.50
(38,1)
0.96
(0,43) 72823 3.13
(79,5)
1.63
(41.4)
3.15
(1,43) 86279 1.50
(38,1)
0.90
(0,41)
86297
2-1/2 1.75 1.80 72825 - - - - - - - DN65 (44,5) (0,82)
TABLE 6
NOMINAL DIMENSIONS FIGURES 820,830 & 719
TFPI7I0 Page 9of 10
ii _
FIGURE 825 FIGURE 827 FIGURE 816
EXTENSION PIECE HEX BUSHING REDUCING COUPUNG
1.69
Nominal Pipe Figure 825 Figure 827 Figure 816
Size Extension Piece Hex Bushing Reducing Coupling
A Approx. A Approx. A B Approx.
ANSI inches inches Weight Part Inches Weight Part inches Inches Weight Part
ON
(mm)
Lbs. Number (mm) Lbs. Number (mm) (mm) Lbs. Number
(kg) (kg) (kg)
1/2x1/2 1.50 0.20 72751 - - - - - - - DN15x15 (38,1) (0109)
1/2x1/2 2.00 0.27 72980 - - - - - - - DN15 x 15 (5018) (0,12)
314 x 3/4 1.50 0.22 72981 - - - - - - - DN20x20 (38,1) (0,10)
3/4 x 3/4 2.00 0.31 73982 - - - - - - 0N20 x 20 (50,8) (0,14)
3/4 x 1/2
- - - -
1.75 0.69 0.38 86772 DN20 x 15 (43,2) (17,5) (0,17)
1 x1/2
- -
1.06 0.22 72726 0.50 0.38 86228 DN25x 15 (26,9) (0110) (42,9) (12,7) (0,17)
1 x3/4
- - -
1.06 0.18 72762 1.75 0.50 0.53 86229 0N25 x 20 (26,9) (0,08) (43,2) (12,7) (0,24)
1-1/4x1
- - -
1.19 0.31 72763 - - - - 0N32 x 25 (30,2) (0,14)
1-112x1
- -
1.25 0.53 72757 - - - - DN40 x 25 (31,7) (0,24)
1-1/2x1-114
- -
1.25 0.35 72764 - - - - DN40 x 32 (31,7) (0,10)
2x1
-
1.38 0.75 72759 - - - - DN50 x 25 (35,1) (034)
2x 1-1/4
- - -
1.38 0.69 72761 - - - - DN50x32 (35,1) (0,31)
2x1-1/2
-
1.38 0.62 72775 - - - - 0N50 x 40 (35,1) (0,28)
TABLE 7
NOMINAL DIMENSIONS FIGURE 825,827 & 816
tqCo /Fire & Building
I Products
Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500
www.tyco-fire.com
Grinnell Grooved Fire Protection Products
Figure 40-5
Strap
General
Description
(flj) () See Fire Protection
Submittal Sheet for FM Pressure Rating and
Listing/Approval Information
The Figure 40-5 Strap is an economical alternative
to welded pipe outlets on steel pipe.
The Figure 40-5 Strap may be used with full
lengths of pipe and eliminates threading and
welding, decreasing waste and installation time.
The 40-5 Strap may be used in wet, dry pipe and
deluge systems.
WARNING
The Figure 40-5 Strap described herein must be
installed and maintained in compliance with this
document, as well as withtheapplicable standards
of the National Fire Protection Association, in
addition to the standards of any otherautho titles
ha ving jurisdiction. Failure to do so mayimpair
the performance of this device.
The owner is responsible for maintaining their
fire protection system and devices in proper
operating condition. The installing contractor or
spr!nklarmanufacturershouldbe contacted with
any questions.
Technical
Data
Figure: 40-5
Outlet: Threaded
Approvals: UL, FM, ULC, and VdS;
See Fire Protection submittal Sheet for exact
Listing /Approval information.
Housing: Ductile iron conforming to
ASTM A-536, Grade 65-45-12
Protective Coatings:
'Clear rust inhibitive coating
'Zinc electroplated conforming to
ASTM B-633, Type Ill Service 2 (optional)
U-Bolt: Carbon steel conforming to
ASTM A-307, Grade A, Zinc electroplated
Nuts: Carbon steel conforming to
ASTM A-307, Grade A, Zinc electroplated
Gasket: (specify when ordering)
Grade "E" EPOM green color code.
(See Data Sheet 1FP1895 for aid in selecting
proper gasket)
Ordering
Procedure
When placing an order, indicate the full product
name. Please specifythe quantity, figure number,
type of gasket, Grade "E' EPOM, and size.
Grinnell Grooved Piping Products, valves,
accessories and other products are available
throughoutthe U.S., Canada, and internationally,
through a network of distribution centers. You
may write directly or call 215-362-0700 for the
distributor nearest you.
Care and
Maintenance
The owner Is responsible for the inspection,
testing, and maintenance of their fire protection
system and devices in accordance with the
applicablestandards of the National Fire Protection
Association (e.g., NFPA 25), in addition to the
standards of any authority having jurisdiction.
The installing contractoror product manufacturer
should be contacted relative to any questions.
Any impairment must be immediately corrected.
It is recommended that automatic sprinkler
systems be Inspected, tested, and maintained by
a qualified inspection Service.
Limited
Warranty
Products manufactured by Tyco Fire Products are
warranted solely to the original Buyer for ten (10)
years against defects in material and workmanship
when paid brand properly installed and maintained
under normal use and service. This warranty will
expire ten (10) years from date of shipment bylyco
Fire Products. No warranty is given for products or
components manufactured by companies not
affiliated by ownershipwith Tyco Are Products orfor
products and components which have been subject
to misuse, improperinstallation, corrosion, orwhich
have not been installed, maintained, modified or
repaired in accordance with applicable Standards of
the National Fire Protection Association (NFPA),
and/or the standards of any otherAuthorities Having
Jurisdiction. Materials found byTyco Fire Products
to be defective shall be either repaired or replaced, at
Tyco Fire Products' sole option. Tyco Fire Products
neither assumes, nor authorizes any person to
assumeforit,anyotherobligahoninconnectionwith
the sale of products or parts of products. Tyco Are
Productsshallnotberesponsibleforsprinklersystern
designerrorsorinaccurateorincompleteinfomiation
supplied by Buyer or Buyer's representatives.
IN NO EVENT SHALL TYCO FIRE PRODUCTS BE
LIABLE, IN CONTRACT, TORT, STRICT LIABILITY
OR UNDER ANY OTHER LEGAL THEORY, FOR
INCIDENTAL, INDIRECT, SPECIAL OR
CONSEQUENT1ALDAMES,INCLUDlNGBUTNOT
LIMITED TO LABOR CHARGES, REGARDLESS OF
WHETHER1YCOFIREPRODUCTSWASINFORMED
ABOUT THE POSSIBILITY OF SUCH DAMAGES,
AND IN NO EVENT SHALITYCO FIRE PRODUCTS'
LIABILITY EXCEED AN AMOUNT EQUAL TO THE
SALES PRICE.
Page 1 of 2 September 2004
(B
TFPI 720
Pipe Nominal Dimensions Hole Net
A B C D Size Size Wt.
Run x Inches Inches Inches Inches Inches Lbs.
Branch mm mm mm mm mm Kg.
11/4 ' x V2" 2.00 1.50 3.50 1.20 13A6 0.84
50.8 38.1 88.9 30.5 30.2 0.4
11/4' x 3/40 2.00 1.50 3.50 1.20 j3/ 0.88
50.8 38.1 88.9 30.5 30.2 0.4
11/40 X 1 2.31 1.68 3.50 1.20 1/16 1.13
58.7 42.7 88.9 30.5 30.2 0.5
11/20 X 1/20 2.12 1.62 3.50 1.32 13'16 0.84
53.8 41.1 88.9 33.5 30.2 0.4
11/20 x 3/" 2.12 1.62 3.50 1.32 1/16 0.88
53.8 41.1 88.9 33.5 30.2 0.4
1112" x 1" 2.43 1.80 3.50 1.32 1/16 1.13
61.7 45.7 88.9 33.5 30.2 0.5
2xW 2.36 1.86 3.74 1.55 1/i 0.88
59.9 47.2 95.0 39.4 30.2 0.4
2 x 3/40 2.36 1.86 3.74 1.55 i/16 0.95
59.9 47.2 95.0 39.4 30.2 0.4
20 x r 2.67 2.04 3.74 1.55 13M 1.16
67.8 51.8 95.0 39.4 30.2 0.5
21/2"X1/2 2.61 2.11 4.25 1.80 1346 0.90
66.3 53.6 108.0 45.7 30.2 0.4
21/20 x 3/0 2.61 2.11 4.25 1.80 VA6 0.99
66.3 53.6 108.0 45.7 30.2 0.4
2W 1" 2.92 2.29 4.25 1.80 1346 1.21
74.2 58.2 108.0 45.7 30.2 0.5
Item Description
1 Housing
2 Gasket
3 Flanged Nut
4 U-Bolt
Fitting
Size
Equivalent Length
(1 inch pipe)
1'/4"X 1" 8
1V20 x 1" 6
2'x 1" 6
21/20 x 1 4
The friction loss for these outlets is specified in
equivalent length of 1 inch Schedule 40 (C=120) pipe.
Page 2of 2 TFP1720
Figure 40.5 Strap
The 1 inch outlets can be used with a nipple leading Note: Outlet threads conforming to ISO 7-1 are available, contact
directly to a sprinkler. These fittings should be used Tyco Fire Products.
for hydraulically calculated systems only.
12 ()
General Notes: It is the Designer's responsibility to select products suitable for the intended service and to ensure ISO that pressure ratings and performance data is not exceeded. Always read and understand the installation 9001
instructions (lH-1 000). Never remove any piping component or corrector modify any piping deficiencies without
first depressurizing and draining the system. Material and gasket selection should be verified to be compatible
for the specific application. . Certified Company
TYCO FIRE PRODUCTS, 451 North Cannon Avenue, Lansdale, Pennsylvania 19946 Printed U.S.A.
tL,Cf3 /Fire & Building
I Products
Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500
Series TY-FRB — 2.8,4.2,56, and 8.0 K-factor
Upright, Pendent, and Recessed Pendent Sprinklers
Quick Response, Standard Coverage
General
Description
The Tyco® Series TY-FRB, 2.8, 4.2,
5.6, and 8.0 K-factor, Upright and Pen-
dent Sprinklers described in this data
sheet are quick response - standard
coverage, decorative 3 mm glass bulb
type spray sprinklers designed for use
in light or ordinary hazard, commercial
occupancies such as banks, hotels,
shopping malls, etc.
The recessed version of the Series
TY-FRB Pendent Sprinkler, where ap-
plicable, is intended for use in areas
with a finished ceiling. It uses either a
two-piece Style 10 (1/2 inch NPT) or
Style 40 (3/4 inch NPT) Recessed Es-
cutcheon with 1/2 inch (12,7 mm) of
recessed adjustment or up to 3/4 inch
(19,1 mm) of total adjustment from the
flush pendent position, or a two-piece
Style 20(1/2 inch NPT) or Style 30(3/4
inch NPT) Recessed Escutcheon with
1/4 inch (6,4 mm) of recessed adjust-
ment or up to 1/2 inch (12,7 mm) of
total adjustment from the flush pen-
dent position. The adjustment pro-
vided by the Recessed Escutcheon re-
duces the accuracy to which the fixed
pipe drops to the sprinklers must be
cut.
Corrosion resistant coatings, where
applicable, are utilized to extend the
life of copper alloy sprinklers beyond
that which would otherwise be ob-
IMPORTANT
Always refer to Technical Data
Sheet TFP 700 for the INSTALLER
WARNINGS that provides cautions
with respect to handling and instal-
lation of sprinkler systems and com-
ponents. improper handling and in-
stallation can permanently damage
a sprinkler system or its compo-
nents and cause the sprinkler to fall
to operate in a fire situation or cause
it to operate prematurely.
Page 1 of 10
tained when exposed to corrosive at-
mospheres. Although corrosion resis-
tant coated sprinklers have passed the
standard corrosion tests of the appli-
cable approval agencies, the testing is
not representative of all possible cor-
rosive atmospheres. Consequently, it
is recommended that the end user be
consulted with respect to the suitability
of these coatings for any given corro-
sive environment. The effects of ambi-
ent temperature, concentration of
chemicals, and gas/chemical velocity,
should be considered, as a minimum,
along with the corrosive nature of the
chemical to which the sprinklers will be
exposed.
An intermediate level versions of the
Series TY-FRB Pendent Sprinklers
are detailed in Technical Data Sheet
1FP356, and Sprinkler Guards are de-
tailed in Technical Data Sheet TFP780
WARNINGS
The Series TY-FRB Sprinklers de-
scribed herein must be installed and
maintained in compliance with this
document, as well as with the applica-
ble standards of the National Fire Pro-
tection Association, in addition to the
standards of any other authorities hav-
ing jurisdiction. Failure to do so may
impair the performance of these de-
vices.
The owner is responsible for maintain-
ing their fire protection system and de-
vices in proper operating condition.
The installing contractor or sprinkler
manufacturer should be contacted
with any questions.
AUGUST, 2007
Model/Sprinkler
Identification
Numbers
TYII3I - Upright 2.8K, 112"NPT
TY1231 - Pendent 2.81K, 112"NPT
TY2131 - Upright 4.2K, 112"NPT
TY2231 - Pendent 4.21K. 1/2'NPT
11Y3131 - Upright 5.6K, 112"NPT
lTV3231 - Pendent 5.6K. 112"NPT
TY4131 - Upright 8.01K, 3!4"NPT
TY4231 - Pendent 8.0K, 314'NPT
TY4831- Upright 8.01(. 112"NPT
1Y4931- Pendent 8.01K, 112"NPT
(B TFPI7I
TFPI7I
ESCUTCHEON 7/161 (11,1 mm)
PLATE SEATING NMINAL
SURFACE NPT fjAKE.IN
2-3/16" \
(55,6 mm)
1-1/2"
(38,11 mm)
SSP DEFLECTOR *
Page 3 of 10
STYLE 10or20
RECESSED SSU
ESCUTCHEON LflFLh.L.IUK
I
7/16"
(111,11 mm) I NOMINAL I 4
MAKE-IN
mm)
2-3116" 2
WRENCH
FLATS
-1 1/2" NPT 2-716" (73,0 mm) DIA.
PENDENT I RECESSED PENDENT UPRIGHT CROSS SECTION
Frame 3 - Sealing 4 - Bulb 6 - Deflector * Temperature rating is indicated on deflector or adjacent
2- Button Assembly 5- Compression orifice seat on frame.
Screw
FIGURE 3
QUICK RESPONSE SERIES TY-FRB UPRIGHT (TY3131) AND PENDENT (TY3231) SPRINKLERS
5.6 K-FACTOR, 112 INCH NPT
ESCUTCHEON 1/2" (12,1 mm)
PLATE SEATING NOMINAL
SURFACE MAKE-IN NPT
216"
(58, mm)
1-9/16"
i
(39.7 mm)
SSP DEFLECTOR 7/8"
PENDENT RECE
STYLE 30 or 40
RECESSED SSU* ESCUTCHEON DEFLECTOR
6*
AMEW
(1 mm)
OMINAL
MAKE IN
2-11W 2
mm) f V -
_LJ.1
im))D
PENDENT UPRIGHT CROSS SECTION
Frame 3 - Sealing - Bulb 6 - Deflector * Temperature rating is indicated on deflector or adjacent to
2- Button Assembly," 5-Compression orifice seat on frame. Screw
FIGURE 4
,-QUICK RESPONSE SERIES TY-FRB UPRIGHT (TY4131) AND PENDENT (TY4231) SPRINKLERS
8.0 K-FACTOR, 314 INCH NPT
(D
Page 4oflO TFPI7I
7/16"(11,1 mm)
NOMINAL SSU' 112' MAKE-IN DEFLECTOR NPT
I
fla",
5
2-1/4' 2-16
(57,2 mm)
F
1-9/16' WRE H (39,7 mm)
-. >_*SP*
.."DEFLECTOR CROSS
PE .tIeT {N UPRIGHT SECTION
- Frame 3 - Sealing 4 ulb 6 - Deflector * Temperature rating is indicated on deflector or adjacent to
2 - Button Assembly - Compression orifice seal on Frame. Screw
FIGURE 5
UICK RESPONSE SERIES TY-FRB UPRIGHT (TY4831) AND PENDENT (TY4931) SPRINKLERS
8.0 K-FACTOR, 1/2 INCH NP
Technical
Data
Approvals
UL and C-UL Listed.
FM, LPCB, and NYC Approved.
(Refer to Table A and B for Complete
approval information including corro-
sion resistant status.)
Maximum Working Pressure
Refer to Table C.
Discharge Coefficient
K = 2.8 GPM/psi1/2 (40,3 LPM/barl/2)
1< = 4.2 GPM/psi1/2 (60,5 LPM/barl12)
K = 5.6 GPM/ps1112 (80,6 LPM/bar112)
K = 8.0 GPM/ps1112 (115,2 LPMIbar1I2)
Temperature Ratings
Refer to Table A and B
Finishes
Sprinkler: Refer to Table A and B.
Recessed Escutcheon: White Coated,
Chrome Plated, or Brass Plated.
Physical Characteristics
Frame .............Bronze
Button .........Brass/Copper
Sealing Assembly ..........
Beryllium Nickel w/Teflorit
Bulb ...............Glass
Compression Screw .....Bronze
Deflector .......Copper/Bronze
Bushing (K=2.8) .......Bronze
The glass Bulb contains a fluid which
expands when exposed to heat. When
the rated temperature is reached, the
fluid expands sufficiently to shatter the
glass Bulb, allowing the sprinkler to
activate and water to flow.
The Series TY-FRB Pendent and Up-
right Sprinklers are intended for fire
protection systems designed in ac-
cordance with the standard installation
rules recognized by the applicable
Listing or Approval agency (e.g., UL
Listing is based on the requirements of
NFPA 13, and FM Approval is based
on the requirements of FM's Loss Pre-
vention Data Sheets ). Only the Style
10, 20, 30, or 40 Recessed Escutch-
eon, as applicable, is to be used for
recessed pendent installations.
Page 6 of 10 TFPI7I
SPRINKLER FINISH (See Note 8)
K TYPE TEMP. BULB NATURAL
BRASS
I CHROME
PLATED
I
LIQUID POLYESTER
WHITE* LEAD
COATED
5.6
1/2"
PENDENT
(TY3231)
and
135"F/57°C Orange
1,2,3,4,5,6,7 1,2,3,5 I -d I
175°F179"C Yellow
UPRIGHT
(TY3131) 200"F1930C Green
286"F/141"C Blue
NPT 135"F/57"C Orange
1,2,4,5 N/A
RECESSED
PENDENT
(TY3231)*
Figure 10
1155°F(68"C Red I
175°F179°C Yellow
2000F/93°C Green
135"F/57"C Orange
1,2,3,4,5 N/A
RECESSED
PENDENT
(TY3231)**
Figure 11
155"F(68°C Red
175°F/790C Yellow
200°F/93°C Green
8.0
3/40
PENDENT
(TY4231)
and
UPRIGHT
(TY4131)
135"F/570C Orange
1, 2, 3,4,5, 6,7
1,2,5
155"F/680C Red
175"F179°C Yellow
200"F/93°C Green
286"F/141°C Blue
NPT 135"F1570C Green
1,2,4,5 N/A
RECESSED
PENDENT
(TY4231)"
Figure 12
155"F168°C Orange
175"F/79"C Red
200"F193"C Yellow
135°F/57"C Orange
1,2,3,4,5 N/A
RECESSED
PENDENT
(1Y4231)**
Figure 13
155"F/68"C Red
175"F/79°C Yellow
200"F/930C Green
8.0
1/2"
NPT
PENDENT
(TY4931)
and
UPRIGHT
(TY4831)
135"F157"C Orange
1,2,4,5,6
1,2,5 155"F/68°C Red
175"F/79"C Yellow
200°F/93"C Green
1286'F/141-Cl Blue
NOTES:
Listed by Underwriters Laboratories, Inc. (UL) as Quick Response Sprinklers.
Listed by Underwriters Laboratories, Inc. for use in Canada (C-UL) as Quick Response Sprinklers.
Approved by Factory Mutual Research Corporation (FM) as Quick Response Sprinklers.
Approved by the Loss Prevention Certification Board (LPCB Ref. No. 007k/04) as Quick Response Sprinklers; however, the
LPCB does not rate the thermal sensitivity of recessed sprinklers.
Approved by the City of New York under MEA 354-01-E.
VdS Approved (For details contact Tyco Fire & Building Products, Enschede, Netherlands. Tel. 31-53428-4444/Fax 31-53-428-3377).
Approved by the Loss Prevention Certification Board (LPCB Ref. No. 094a106) as Quick Response Sprinklers.
B. Where Polyester Coated and Lead Coated Sprinklers are noted to be UL and C-UL Listed, the sprinklers are UL and C-UL Listed as
Corrosion Resistant Sprinklers. Where Lead Coated Sprinklers are noted to be FM Approved, the sprinklers are FM Approved as a
Corrosion Resistant Sprinklers.
0 Installed with Style 10 (1/20 NPT) or Style 40 (3/4" NPT) 3/4" Total Adjustment Recessed Escutcheon, as applicable.
Installed with Style 20 (1/2" NPT) or Style 30 (3/40 NPT) 1/2" Total Adjustment Recessed Escutcheon, as applicable.
*0* Frame and Deflector only. Listings and approvals apply to color (Special Order).
N/A: Not Available
TABLE B
LABORATORY LISTINGS AND APPROVALS
5.6 AND 8.0 K-FACTOR SPRINKLERS
TFPI7I Page 7 of 10
SPRINKLER FINISH
K TYPE NATURAL CHROME WHITE LEAD
BRASS PLATED
I
POLYESTER COATED
PENDENT (TY3231)
and
2.8 UPRIGHT (TY3131) 175 PSI (12,1 BAR) N/A
1/2 RECESSED PENDENT NPT (TY323)
PENDENT (TY4231)
and
4.2 UPRIGHT (TY4131) 175 PSI (12,1 BAR) N/A
RECESSED PENDENT NPT (TY4231)
PENDENT(TV3231)
and 250 PSI (17,2 BAR) 175 PSI (12,1 BAR)
5.6 OR UPRIGHT (TY3131)
1/2' 175 PSI (12,1 BAR) RECESSED PENDENT NPT (ry'3231) (SEE NOTE 1) N/A
- PENDENT (TY4231)
and 175 P81(12,1 BAR) 175 PSI (12,1 BAR)
8.0 UPRIGHT (TY4131)
RECESSED PENDENT NPT (TY4231) N/A
8.0 PENDENT(TY4931)
1/2' and 175 PSI (12,1 BAR) 175 PSI (12,1 BAR)
NPT UPRIGHT (TY4831)
NOTES:
1. The maximum working pressure of 250 psi (17,2 bar) only applies to the Listing by Underwriters Laboratories Inc. (UL), the Listing by
Underwriters Iaboratories,lnc. for use in Canada (C-UL); and the Approval by the City of New York.
TABLE C, MAXIMUM WORKING PRESSURE
Installation
The Series TY-FRB Sprinklers must
be installed in accordance with the fol-
lowing instructions:
NOTES
Do not install any bulb type sprinkler if
the bulb is cracked or there is loss of
liquid from the bulb. With the sprinkler
held horizontally, a small air bubble
should be present. The diameter of the
air bubble is approximately 1/16 inch
(1,6 mm) for the 135°F/57°C to 3/32
inch (2,4 mm) for the 286°F/141C
temperature ratings.
A leak tight 1/2 inch NPT sprinklerjoint
should be obtained with a torque of 7
to 14 ft.Ibs. (9,5 to 19,0 Nm). A maxi-
mum of 21 ft. lbs. (28,5 Nm) of torque
may be used to install sprinklers with
1/2 NPT connections. A leak tight 3/4
inch NPT sprinkler joint should be ob-
tained with a torque of 101020 ft.Ibs.
(13,4 to 26,8 Nm). A maximum of 30
ft.lbs. (40,7 Nm) of torque is to be used
to install sprinklers with 3/4 NPT con-
nections. Higher levels of torque may
distort the sprinkler inlet and cause
leakage or impairment of the sprinkler.
Do not attempt to make-up for insuffi-
cient adjustment in the escutcheon
plate by under- or over-tightening the
sprinkler. Readjust the position of the
sprinkler fitting to suit.
The Series TY-FRB Pendent and Up-
right Sprinklers must be installed in
accordance with the following instruc-
tions.
Step 1. Pendent sprinklers are to be
installed in the pendent position, and
upright sprinklers are to be installed in
the upright position.
Step 2. With pipe thread sealant ap-
plied to the pipe threads, hand tighten
the sprinkler into the sprinkler fitting.
Step 3. Tighten the sprinkler into the
sprinkler fitting using only the W-Type
6 Sprinkler Wrench (Ref. Figure 14).
With reference to Figures 1, 2, 3, 4,
and 5, the W-Type 6 Sprinkler Wrench
is to be applied to the sprinkler wrench
Oats.
The Series TY-FRB Recessed Pen-
dent Sprinklers must be installed in
accordance with the following instruc-
tions.
Step A. After installing the Style 10.
20, 30, or 40 Mounting Plate, as appli-
cable, over the sprinkler threads and
with pipe thread sealant applied to the
pipe threads, hand tighten the sprin-
kler into the sprinkler fitting.
Step B. Tighten the sprinkler into the
sprinkler fitting using only the W-Type
7 Recessed Sprinkler Wrench (Ref.
Figure 15). With reference to Figure 1,
2, 3, and 4, the W-Type 7 Recessed
TFPI7I
2-7/8' DIA. -
5/8*1/4' (73,0 mm) I 3/4'(19,1 mm
(15,9±6,4 mm) 2-1/4' DIA. I 1/4" (6,4
FACE OF (57,2 mm) MO TING
SPRINKLER PLATE FITTING
I /8'
(3,
1
2 mm)
MOUNTING $
1
SURFACE
SERIES 1-1/4'(31,8 mm) I CLOSURE TVFRB 3/4' (19.1 mm)
FIGURE 10
RJES TY-FRB RECESSED PENDENT
WIT TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT
STYLE 10 RECESSED ESCUTCHEON
5.6 K-FACTOR, 1/2 INCH NPT
- 2-718' DIA.
(73,0 mm) 3/4'(19.1 mm)
(15,9±6,4 mm) t 2-1/4" DIA, __....I 1/4" (6,4 m
(57,2 mm) FACE OF MO U ING
SPRINKLER TE
FITTING
/ 1/8"
I . (3,2 mm)
MOUNTING
SURFACE
CLOSURE SERIES 1-5/18"
TY..FRB 13/16' (20.6 mm)
FIGURE 12
S IES TY-FRB RECESSED PENDENT
WIT 0-PIECE 3/4 INCH TOTAL ADJUSTMENT
STYLE 40 RECESSED ESCUTCHEON
8.0 K-FACTOR, 3/4 INCH NPT
Page 9 of 10
2-7/8' DIA.
(73,0 mm) 1/2±1/8' 10"(12,7 m r (12,7±3,2 mm) - 2-1/4' DIA 1/4' (6,4 m)
FACE OF MM MO TING I SPRINKLER PLATE
FITTING
I 1/8' (3,2
1
mm)
\ ft MOUNTING
SURFACE
CLOSU SERIES .1-1/4(31,8 mm) I RE TY-FRO 1' (25,4 mm)
FIGURE 11
RiES TY-FRB RECESSED PENDENT
WI TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 20 RECESSED ESCUTCHEON
5.6 K-FACTOR, 1/2 INCH NPT
. 2-7/8* DIA. - (73.0 mm) 1/2'(12,7 mm)
(12,7*3,2 mm) - 2-1/4' DIA. j 1/4 (6.4
(57,2 mm)
FACE OF MO TING
SPRINKLER LATE
FITTING
I 116"
I - (3,2 mm)
\
MOUNTING
SURFACE
CLOSURE SERIES 1-5/16'(33.3 mm)
TYFRB 1-1116' (27.0 mm)
FIGURE 13
RIES TY-FRB RECESSED PENDENT
WIT TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 30 RECESSED ESCUTCHEON
8.0 K-FACTOR, 314 INCH NPT
pleted, to verify the integrity of the cor-
rosion resistant coating. Thereafter,
annual inspections per NFPA 25
should suffice; however, instead of in-
specting from the floor level, a random
sampling of close-up visual inspec-
tions should be made, so as to better
determine the exact sprinkler condi-
tion and the long term integrity of the
corrosion resistant coating, as It may
be affected by the corrosive conditions
present.
The owner is responsible for the in-
spection, testing, and maintenance of
their fire protection system and de-
vices in compliance with this docu-
ment, as well as with the applicable
standards of the National Fire Protec-
tion Association (e.g, NFPA 25), in
addition to the standards of any other
authorities having jurisdiction. The in-
stalling contractor or sprinkler manu-
WRENCH RECESS
(END 'A' USED FOR
1/2" NPT MODELS)
WRENCH RECESS
(END 'B" USED FOR
314' NPT MODELS)
FIGURE 14
W-TYPE 6 SPRINKLER
WRENCH
facturer should be contacted relative
to any questions.
It is recommended that automatic
sprinkler systems be inspected,
tested, and maintained by a qualified
WRENCH
RECESS
PUSH WRENCH
IN TO ENSURE
ENGAGEMENT
WITH SPRINKLER
WRENCHING AREA
FIGURE 15
W-TYPE 7 RECESSED
SPRINKLER WRENCH
Inspection Service in accordance with
local requirements and/or national
codes.
8
Page 10 of 10 TFPI7I
P/N 57-XXX-X-XXX
I L
I MODEL/SIN
330 2.8K UPRIGHT (1I2NPT) TY1131
331 2.8K PENDENT (1/2"NPT) TY1231
340 4.2K UPRIGHT (1I2NPT) TY2131
341 4.2K PENDENT (1/2"NPT) TY2231
j370 5.61< UPRIGHT (1/2NPT) TV3131
371 5.6K PENDENT (1/2NPT) TY3231
390 8.0K UPRIGHT (3/4'NPT) 1V4131
391 8.0K PENDENT (314"NPT) TY4231
360 8,0K UPRIGHT (1/2"NPT) TY4831*
361 8.0K PENDENT (112"NPT) 1Y4931
I
I SPRINKLER I
135
155
175
200
286
RATING
135*F/5C
1 NATURAL BRASS 155*F/68*C
4 WHITE POLYESTER 175°F/79°C
3 WHITE (RAL9010)
1
200°F/93C
1 9 CHROME PLATED 286*F/141*C
7 I LEAD COATED
* Eastern Hemisphere sales only.
TABLED
PART NUMBER SELECTION
SERIES TY-FRB PENDENT AND UPRIGHT SPRINKLERS
Limited
Warranty
Products manufactured by Tyco Fire &
Building Products (TFBP) are war-
ranted solely to the original Buyer for
ten (10) years against defects in mate-
rial and workmanship when paid for
and properly installed and maintained
under normal use and service. This
warranty will expire ten (10) years
from date of shipment by TFBP. No
warranty is given for products or com-
ponents manufactured by companies
not affiliated by ownership with TFBP
or for products and components which
have been subject to misuse, improper
installation, corrosion, or which have
not been installed, maintained, modi-
fied or repaired in accordance with ap-
plicable Standards of the National Fire
Protection Association, and/or the
standards of any other Authorities
Having Jurisdiction. Materials found
by TFBP to be defective shall be either
repaired or replaced, at TFBP's sole
option. TFBP neither assumes, nor
authorizes any person to assume for it,
any other obligation in connection with
the sale of products or parts of prod-
ucts. TFBP shall not be responsible for
sprinkler system design errors or inac-
curate or incomplete information sup-
plied by Buyer or Buyer's repre-
sentatives.
In no event shall TFBP be liable, in
contract, tort, strict liability or under
any other legal theory, for incidental,
indirect, special or consequential darn-
ages, including but not limited to labor
charges, regardless of whether TFBP
was informed about the possibility of
such damages, and in no event shall
TFBP's liability exceed an amount
equal to the sales price.
The foregoing warranty is made in lieu
of any and all other warranties, ex-
press or imolied. including warranties
of merchantability and fitness fora Dar-
ticular purpose.
This limited warranty sets forth the ex-
clusive remedy for claims based on
failure of or defect in products, materi-
als or components, whether the claim
is made in contract, tort, strict liability
or any other legal theory.
This warranty will apply to the full ex-
tent permitted by law. The invalidity, in
whole or part, of any portion of this
warranty will not affect the remainder.
When placing an order, indicate the
full product name. Refer to the Price
List for complete listing of Part Num-
bers.
Contact your local distributor for avail-
ability.
Sprinkler Assemblies with NPT
Thread Connections:
Specify: (Specify Model/SIN), Quick
Response, (specify K-factor), (specify
temperature rating), Series TY-FRB
(specify Pendent or Upright) Sprinkler
with (specify type of finish or coating),
P/N (specify from Table 0).
Recessed Escutcheon:
Specify: Style (10, 20, 30, or 40) Re-
cessed Escutcheon with (specify*) fin-
ish, P/N (specify).
* Refer to Technical Data Sheet TFP770.
Sprinkler Wrench:
Specify: W-Type 6 Sprinkler Wrench,
P/N 56-000-6-387.
Specify: W-Type 7 Sprinkler Wrench,
P/N 56-850-4-001.
TYCO FIRE & BUILDING PRODUCTS, 451 North Cannon Avenue, Lansdale, Pennsylvania 19446
300
RING HANGER
<a> C®US l thru l Inch pipe 112 and 314 Inch pipe S thru 8 Inch pipe
SIZE - 1/2 thru 8 inch pipe.
MATERIAL - Carbon Steel, Mil. Galvanized to G-90 specification.
FINISH - Mi!. Galvanized and Stainless Steel.
LISTING - UL in US and CANADA.
APPROVAL - Factory Mutual Research.
CONFORMS WITH: Federal Specification WW-H-171(Type 10),
Manufacturers Standardization Society ANSI/MSS-SP-58 (Type 10); install
in accordance with ANSI/MSS- SP-69.
MAXIMUM TEMPERATURE - 650°F.
FUNCTION - For fire sprinkler and general piping purposes.
Swivel nut permits hanger adjustment after installation.
FEATURES -
1 thru 4 inch:
* Offset edge for EASY pipe insertion.
1 thru8inch:
* Full length knurl on swivel nut for better grip.
UNIQUE FEATURES
1 thru 3 inch:
* UL listed to accept AFCON #310 Surge Restrainer.
* Swivel nut
Retained in ring to keep the assembly intact prior to installation.
Removed easily if needed.
* UL listed for use on CPVC pipe.
ORDERING - Part # and pipe size.
Index
02/01
IMPERIAL MAX REC.
LOAD LBS.
METRIC
PIPE ROD PIPE ROD
318 400 10
314 3f8 400 20 to
3/8 400 25 10
11/4 3/8 400 32 10
fli 400 40 1 in
2 3/8 400 60 10
21/2 3/8 600 65 tO
3 318 600 so 10
31/2 600 10
4 3/8 1000 100 in
5 112 1250 126 12
8 112 1250 150 12
8 1250
Order Part d300m
Note: 1t2' Ring Hanger not <FM> appmvcd
655
ALL THREADED ROD CUT TO LENGTH
ROD
SIZE
MAX. REC. LOAD LBS.
FOR SERVICE TEMP.
65OF 75OF
3/8 610 540
1/2 1130 1010
5/8 1810 1610
3/4 2710 1 2420
7/8 3770 1 3360
NOTE; maximum Temperature: 750SF
SIZE - 3/8 thru 7/8 inch rod in linch
increments.
MATERIAL - Carbon Steel.
FINISH - Plain, Electro-Galvanized and
Stainless Steel.
ORDERING - Part #, rod diameter, rod
length and finish.
2/00 (B
Listincls/ADDrovals
City of Los Angeles
Research Report No. 23709 (HDI Only)
FM (Factory Mutual)
Pipe Hanger Components for Automatic
Sprinkler Systems (3/8' - 3/4')
(HDI and HDI-L)
UL (Underwdters Laboratories)
UL 203 Pipe Hanger Equipment for Fire
Protection Services (3/8' - 3I4"
r: .1I-L Drop-I Anchor
4.3.8.1 Product Description
4.3.8.2 Material Specifications
4.3.8.3 Technical Data
4.3,8.4 Installation Instructions
4.3.8.5 Ordering Information
4.3.8.1 Product Description
The Hilti HDI/HDI-L Drop-In anchor is an • Intelligent expansion section
internally threaded, flush mounted adapts to the base material and
expansion anchor for use in concrete. reduces number of hammer blows
up to 50% (HDI-L)
Product Features Guide Specifications
HDI
Anchor, setting tool and Hilti drill bit
form a matched tolerance system
to provide reliable fastenings
Allows shallow embedment without
sacrificing performance
Up provides flush installation,
consistent anchor depth, and easy
rod alignment (HDI-L)
Up allows accurate flush
surface setting, independent
of hole depth (HDI-L)
Ideal for repetitive fastenings with
threaded rods of equal length
Expansion Anchor Expansion anchors
shall be flush or shell type and zinc
plated in accordance with ASTM B 633,
SC 1, Type Ill. Anchors shall be Hilti
HDVHDI-L anchors as supplied by Hilti.
Installation Install shell or flush type
anchors in holes drilled with Hilti carbide
tipped drill bits. Install anchors as per
manufacturer's recommendations.
4.3.8.2 Material Specifications
HDI/HDI-L, 114', 3/8", 1/2", and HDI 5/8" and 3/4" are manufactured from mild
carbon steel which is plated with a zinc finish for corrosion protection in
accordance with ASTM B 633, SC 1, Type Ill
HDI Stainless Steel material meets the requirements of AlSI 303
4.3.8.3 Technical Data
HDI/HDl-L Specification Table
Anchor HDIIHDI-L HUt
1/4 3/8 1/2 5/8 3/4 Size in.
De~(MM) .4) (9.5) (12.7) (15.9) (19.1)
dbft Nominal Bit diameter in. 3/8 1/2 5/8 27/32 1
h,om Std. depth of embed. In. 1 1-9/16 2 2-9/16 3-3/16
Anchor length (mm) (25) (40) (51) (65) (81)
h1 Hole depth
fth Useable thread in. 7/16 5/8 11/16 7/8 1-3/8
length (mm) (11) (15) (17) (22) (34)
Threads per inch 20 16 13 11 10
h mm. base material in. 3 3-1/8 4 5-1/8 6-3/8
thickness (mm) (76) (79) (102) (130) (162)
Tm max. tightening ft-lb 4 11 22 37 80
torque (Nm) 1 (5.4) (14.9) 1 (29.8) 1 (50.2) 1 (108.5)
Combined Shear and Tension Loading
(Nd
+
1'__ Y3 1.0 (Ref. Section 4.1.2.7)
362 Hilti. Inc. (US) 1-800-879.8000 1 wwW.us.hdti.com I an españot 1-800-879-5000 1 Hilti (Canada) Corp. 1-800-363-4458 1 www.hillLca I Product Technical Guide 2008
HDI & HDI-L Drop-In Anchor 4.3.0
Carbon Steel HDI Allowable Loads in Concrete
Anchorsize 2000 psi (13.8 MPa) 4000 psi (27.6 MPa) 6000 psi (41.4 MPa)
kL(mm) Tension lb (kN) Shear lb (kN) Tension lb (kN) Shear lb (kN) Tension lb (kN) Shear lb (kN)
HIM HDI-L HDI HDl-L HDI HDl-L HIM I HDI-L HIM HIM-I 1101 HDI-L
1/4 6.4) 500(2.2) 500(2.2) 450(8.0) 460(8.0) 570(2.5) 570(2.5) 625(2.8) 625(2.8) 790) 3.5) 790(3.5) 700(3.1) 700(3.1)
3/8(0.5) 1 890) 4.0) 890(4.0) 965) 4.3) 965(4.3) 1115( 5.0) 1115(5.0) 1250)5.5) 1250(5.5) 1 1360) 6.0) 1360) 6.0) 1500) 6.7) 1500) 6.1)
1/2(12.7) 1120( 5.0) 1120(5,0) 1500( 6.7) 1500(6.7) 1785) 7.9) 1785(7.9) 2125( 9.5) 1940(8,5) 2345(10.4) 2345(10.4) 2500(11.1) 2500(11.1)
518 (15.9) 1875) 8.3) - 2500(11.1) - 2920(13.0) - 3250(14.5) - 3715 (16.5) - 3750(16.7) -
3/4 (19.1) 2500(11.1) - 3875(17.2) - 4065(18.1) - 5000(22.2) - 5565 (243) - 5500(24.5) -
Note: The ultimate shear and allowable shear values are based on the use of SAE Grade 5 bolts, (f = 85 ksi, F,, = 120 ksi) with the exception of the 1/4 HDI/HDI-L in I'. = 6000 psi
concrete which is based upon the use of a SAE Grade 8 boll (l = 120 ksi, F, = 150 ksi).
Carbon Steel HDI Ultimate Loads in Concrete
Ambor sin 2000 psi (13.8 MPa) 4000 psi (27.6 MPa) 6000 psi (41.4 MPa)
In.(rnm) Tension lb (kfifl Shear lb (kN) Tension lb (kN) Shear lb cN) Tension lb (kN) I Shear lb (kN)
1101 1101-I. 1101 HDI-L 1101 I HDI-L HIM HDI-L HDI HDI-I 1101 I HDI-L
1/4 ( 6.4) 1995) 8.9) 1995( 8.9) 1800( 8.0) 1800( 8.0) 2270(10.1) 2270(10,1) 2500(11.1) 2500(11.1) 3150(14.0) 3150(14.0) 2800(12.5) 2800(12.5)
3/8 ( 9.5) 3555(15.8) 3555(15.8) 3850(17.1) 3850(17.1) 4460(19.8) 4460(19.8) 5000(22.2) 5000(22.2) 5430(24.2) 5430(24.2) 6000(26.7) 6000(26.7)
1/2 (12.7) 4470(19.9) 4470(19.9) 6000(26.7) 6000(26.7) 7140(31.8) 7140(31.8) 8500(37.8) 7750(34.4) 9375(41.7) 9375(41.7) 10000(44.5) 0000(44.5)
7500(33.4) - 0000(44.5) - 11685(52.0) - 13000(57.8) - 4865 (66,1) - 15000(66.7) -
10000(44.5) - 5500(69.0) - 6260(72.3) - 0000 (89.0) - 2250(99.0) - 22000(97.9) -
Carbon Steel HDI Allowable Loads in Lightweight Concrete and
Lightweight Concrete over Metal Deck1'2
Anchor
Size
in. (mm)
Anchor Installed In 3000 psi (20.7 MPa)
It. WI. Concrete3
Anchor Installed Through Steel Deck Upper Auto
Into 3000 psi (20.7 MPa) Lt WI. Concrete4
Anchor Installed Through Steel Deck Lower Flute
Into 3000 psi (20.7 MPa) U. WI. Concrete4
Tension, lb (k1 Shea lb (kN) Tension, lb (kN) Shear, lb (kN) Tension, lb (kN) Shear, lb (kN)
1/4(6.4) 465(2.1) 340(1.5) 530(2.4) 335(1.5) 375(1.7) 250(1.1)
3/8(9.5) 755 (3.4) 940 (4.2) 880 (3.9) 1010 (4.5) 500 (2.2) 500 (2.2)
1/2(12.1) 1135(5.0) 1700(7.6) 1105(4.9) 1755(7.8) 625(2.8) - 750(3.3)
5/8(15.9) 1465(6.5) 2835(12,6) - - 875(3.9) 875 (3.9)
3/4(19.1) 2075 (9.2) 3680(16.4) - - 1250(5.5) 1000(4.4)
1 The allowable values are based on the use of SAE Grade 2 bolts installed in the
anchors.
2 Based on using a safety factor of 4.0.
Stainless Steel HDI Allowable Loads in Concrete
3 The tabulated shear and tensile values are for anchors installed in structural light-
weight concrete having the designated ultimate compressive strength at the time of
installation. The concrete must comply with ASTM C 330-77.
4 The tabulated shear and tensile values are for anchors installed through 20 gauge
intermediate decking into structural lightweight concrete having the designated
ultimate strength at the time of Installation. The concrete must comply with ASTM
C 330-77.
Anchor size
in. (mm)
4000 psi (27.6 MPa) 6000 psi (41.4 MPa)
Tension lb (kN) Shear lb (kN) Tension lb (kN) Shear lb (kN)
SS HDI - 1/4 (6.4) 480 (2.1) 600 (2.7) 740 (3.3) 600 (2.7)
SS HDl- 3/8 (9.5) 1040 (4.6) 1230 (5.5) 1460 (6.5) 1230 (5.5)
SS HDI -1I2 (12.7) 1840 (8.2) 2760 (12.4) 2410 (10.7) 2160 (12.3)
SS HDI -5I8 (15.9) 2630(11.7) 4510 (20.1) 3770 (16.8) 4510 (20.1)
SS HDI - 3/4 (19.1) 3830 (17.0) 5580 (24.8) 5030 (22.4) 5580 (24.8)
Note The ultimate and allowable shear values are based on the use of Type 18-8 bolts,
Stainless Steel HDI Ultimate Loads in Concrete
Anchor size
in. (mm)
4000 psi (27.6 MPa) 6000 psi (41.4 MPa)
Tension lb (kN) Shear lb (kN) Tension lb (kN) Shear lb (kN)
SS MDI - 1/4 (6.4) 1930 (8.6) 2400 (10.7) 2950 (13.1) 2400 (10.7)
SS 1101-3/8 (9.5) 4170 (18.5) 4920 (21.9) 5850 (26.0) 4920 (21.9)
S Hill - 1/2 (12.7) 730 (32.7) llfldfl (491) QWtfl (42.8) 11040 (491)
SS HDI -
SS HDI - 3/4 (19.1) 15340 (68.2) 22320 (99.3) 20130 (89.5) 22320 (99.3) 2 3
Hitti, Inc. (US) 1.800.879-8000 1 www.us.hBti.com I an español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 1 www.hlitl.ca I Product Technical Guide 2008 363
Anchor Spacing Adjustment Factors
s = Actual Spacing
s,, = 2.0
= 3.5 h,
Edge Distance Adjustment Factors
c = Actual edge distance
Cflfl - 2.0hnom
Ca = 3.0 h,,,
43.8 HDII & HDI-L Drop-In Anchor
Anchor Spacing and Edge Distance Guidelines (See Anchoring Technology Section 4.1.3)
Sc1
3.0- Shear& I - Ccr
Shear
2.0- ;:.
1.0
I I
01 • I I I
0 ii 0 .2 .4 .6 .8 1.0
0 .2 .4 .6 .8 1.0 Edge Distance Adjustment Factor
Anchor Spacing Adjustment Factor (Rv InN)
(IA)
Influence of Anchor Spacing &
Edge Distance fA, R
Anchor Size
in. (mm)
h.
In. (mm)
1/4(6.4) 1(25)
3/8(9.5) 1-9/16(40)
1/2(12.7) 2(51)
5/8(15.8) 2-9/16(65)
3/4(19.1) 3-3/16(81)
= standard embedment depth
Load Adjustment Factors (Anchor Spacing) fA Load Adjustment Factors (Edge Distance) f
Tension/Shear Loads Tension, l, Shear, fily
Spacing
S
In. (MM)
Anchor Diameter Edge Distance
C
ln.(mm)
Anchor Diameter Anchor Diameter
1/4 318 1/2 5/8 314 1/4 318 1/2 5/8 3/4 1/4 3/8 1/2 5/8 3/4
2 ( 51) .50 - - - 2 (fl .80 - - - - .65 - -
3 3 .50 - - - _3 tO £0 - - - tO £5 - - -
4 (102) .69.50 4 (102) 91.80 .85.65
4-1/2 (114) .79 .58 - 4-1/2 (114) - .98 .85 - - - .96 .74 - -
5 (127) .90.67.50 5 (127) 1.090.80 1.0.8365
5-1/2 (140) 1.0 .75 .55 5-1/2 (140) - - .95 .83 - - .91 .70 1 -
6 (152) .83.61.50 6 (152) 1.0.87 1.0.77
7 (178) - - 1.0 .74 1 .57 6-1/2 (165) - - - .91 1 .80 - - .84 .65
8 (203) - - .87 .67 7 (178) - .95 1 .84 - - - .91 .72
9 (229) 1.0 .77 8 (203) 1O 10 83
10 (254) .88 9 (229) - - - - .96 - - - - .94
11 (279) 10 (254) 1.0 1.0
12 (305) 1.0
Srpj= 2.0hnom,8c1 3.5hn0m
A= 0.33 s-O.17
h,,
for se> S> S 1,
C, = 2.0h,,CD 3.0hl,,
fRw 0.2c+0.4
h
for c> c > c
C,1, =
flvv = 0.35 c-O.05
for ce > c > Cmin
364 HilLi, Inc. (US) 1.800.879-8000 1 wwwus.hiIti.com I an esp&io? 1-800-879-5000 1 Hilt, (Canada) Corp. 1-800-363-4458 1 www.hfttLca I Product Technical Guide 2008
lent,
.13-190 INSTALLATION OF SPRINKLER SYSTEMS
Contractor's Material and Test Certificate for Aboveground Piping
PROCEDURE
Upon completion of work, Inspection and tests shall be made by the rector's representative and witnessed by an owner's
representative. All defects shall be corrected and system left In service before contractor's personnel finally leave the job.
A certificate shall be filled out and signed by both representatives. Copies shall be prepared for approving authorities owners, and
contractor. It is understood the owner's representative's signature In no way prejudices any claim against contractor for faulty material, poor
workmanship, or faflureto comply with approving authority's requirements or local ordinances.
Property name i 1 Vl4 l4/
Date
Property address 2-o2
•
Accepted by approving authorities (names)
Lf41
Plans
Address
Installation conforms to accepted plans Er Yes El No
Equipment used is approved Yes 0 No
If no, explain deviations
Has person In charge of fire equipment been Instructed as El Yes El No to caon of control valves and care and maintenance
of this new equipment?
If no, explain
Instructions Have copies of the following been left on the premises? El Yes El No
System components instructions', J Yes El No
Care and maintenance Instructions El Yes El No
NFPA25 El Yes El No
Ion
o
f
system
Supplies buildings
Year of Orifice Temperature
Make Model manufacture size Quantity rating
Sprinlders
Pipe and Type of pipe S&A. (/3 'lie iei- .
fittings Type of fittings (T S#iae.-I Air ig
Alarm
valve or
flow
Alarm device
Maximum time to operate
through test connection
Type Male Modal Minutes Seconds
Indicator
Dry valve Q 0. D.
Make .mom 'Soriano. Make
Dry pipe
operating
test
through test Water
pISilI
Mr
pressure
jrip,öñt
—air pressure
: test MMI.2
AJ51Th
operated
property
Minutesi Seconds psi psI Minutes Seconds Yes No
Without
In
'Measured from time Inspectors test connection Is opened
2NFPA 13 only requires the 60-second limitation In specific sections
FIGURE 16.1 Contractor's Material and Test Certificate for Aboveground Piping.
2002 Edition '
SYSTEMS ACCEPTANCE
on D Pneumatic 0 ElectrIc 0 Hydraulics
P71P~jng'is-u*vk9,d 0 Yes 0 No Detecting media supervised 3-1 El No Does valve operate fmthrnanual trip, remote, or both - Yes 0 No control stations?
Deluge and
Is there an .tile facility In each>< ci 1 If no, explain. valves
preaction for testing?
Yes
each circuit operate Does as operate Maximum time to Make Model supervision loss alarm? valve mIeãeL operate release Yes No Yes No
j
!JSeconds
tion Make and Setting Static pressure Residual late Pressure and floor
reducing
_____________ valve test
owing)
niet (psi) Outlet 4ps1) Flow (gpm)
mats . ydrostatictestsshallbemadeatnotlessthan200psi(13.6barfor2hours
o
r
5
0
p
s
I
(
3
.
4
b
a
r
)
pressure In excess of 150 psi (102 bar) for 2 hours. Differential dry-pipe valve clappers shall be left open during the test to prevent damage. All aboveground piping leakage shall be stopped. TOM
description Pneumallc. Establish 40 psi (2.7 bar) air pressure and measure drop, which shall not exceed 1½ psi (0.1 bar) In 24 hours. Test pressure tanks at normal water level and air pressure and measure air pressure drop, which shall not exceed 1½ psi (0.1 bar) In 24 hours.
34$ All piping hydrostatically tested at psi (___ bar) for &. tours it no, state reason Dry piping pneumatically tested 0 Yes No Equipment operates properly es 0 No
Do you certify as the sprinkler contractor that addItives and corrosive chemicals, sodium silicate or derivatives of sodium silicate, brine, or other corrosive chemicals were not used for test
i
n
g
s
y
s
t
e
m
s
o
r
s
t
o
p
p
i
n
g
l
e
a
k
s
?
£:Jves No
rain I Reading of gauge located near water Residual pressure with valve In test Tests test u test connection: ____ psi (_ bar) connection open wide:____ psi Underground mains actions to system risers flushed before conn to sprinkler piping
VefflW by copy f the CosMaterial 0 No Other Explain Certificate for Underground Piping.
Flushed by Installer of underg or piping D ves-[:10
powder-drIyejJast are used In concrete, 0 Yes 0 No explain
•
Lhasreee11[ative sample testing been atisctodfy completed?
Blanktesting 14ui ___4cafions —&removed gaskets
- . _
• —_—+_— — Welding piping 0 Yes ,'1ã
It yes.
certify as the sprinkler contractor that welding procedures
with the ofatleastAWSB2.1?
Do you certify that the welding was perfo welders qualIfiedeIdin compliance with the requirements of at leastAWS <1 0
Do you certify that the w canted out In compliance with documented quality cpn procure to ensure that all discs are ropenings in pip1ng1re smooth, that slag and other welding residuethat the internal diameters of piping are not penetrat
Cutouts Do you certify that you have a control feature to ensure that J:56"Yes 0 No (discs) all cutouts (discs) are retrieved?
FIGURE 16.1 Continued
2002 Edition
13-192 INSTALLATION OF SPRINKLER SYSTEMS
Additional explanations and notes
lu
FIGURE 16.1 Continued
16.2.1.2 Portions of systems normally subjected to system working pressures in excess of 150 psi (10.4 bar) shall be S ,~ted as described in 16.2.2.1atapressure of 50psi(&5:bar)
excess of system working pressure.
16.2.1.3 Where cold weather wiWnotpei'thit tëstiiigwith wa-ter, an interim air test shall -be permitted to be conducted as described in 16.2.3.
16.2.1.4 Modifications affecting 20 or fewer sprinklers shall
not require testing in excess of system working pressure.
16.2.1.5 Where addition or modification is made to an exist-ing system affiiig more tban.W spthlders,tbe new portion shall be isolated and tested atnot less than 200 psi (13.8 bar)
for 2 hours.
16.2.1.6 Modiictions that cannot be isolated, iuèh as reló-cated drops, shall not require testing in excess of system work-
- ing pressure
16.2.1.7 Loss. shai1 be determined by a drop in gauge pres-
sure or visual leakage.
16.2.1.8 The test pressure shall be read from a gauge located
at the low elevation point of the system or portion being
tested.
16.2.19 Additives, corrosive'chemicals such as sodium -sili'
cate, or derivatives of sodium silicate, brine or othei` chenu-cals shall not be used while hydrostatically testing systems or for stopping leaks.
16.2.1.10 Piping between the exterior fire department con-nection and the check valve in the fire department inlet pipe
shall be hydruitaticaliy-tested in-the-same-in. an er--asihe-bal-
e of the system.
.1.11 When deluge systems are being hydrostatically tested, plugs shall be installed in fittings and replaced with
open sprinklers after the test is completed, or the operating
elements of automatic sprinklers shall be removed after th
e
test is completed.
16.2.1.12* The trench shall be backfilled between joints be-
fore testing to prevent movement of pipe.
16.2.1.13 Where required for safety measures presented by the hazards of open trenches, the pipe and joints shall be per-mitted to be backfihled provided the installing contractor
takes the responsibility for locating and correcting leakage in excess of that permitted in 16.2.1.8.
16.2.1.14 Provision shall be made for the proper disposal of water used for flushing or testing.
16.2.1.15* Test Blanks.
16.2.1.15.1 Test blanks shall have painted lugs protruding in such a way as to clearly indicate their presence.
16.2.1.152 The test blanks shall Be numbered, and the in-stalling contractor shall have a recirdkeeping method en
s
u
r
-
ing their removal after work is completed.
16.2.1.16 When subject ito hydrostatic test pressures, the clap-per of a differential-type valve shall be held off its seat to pre-vent damaging the valve.
16.2.2 Day Pipe and Double Interlock System(s) Mr Test.
16.2.2.1 In addition to the standard hydrostatic test, an air pressure leakage test at 40 psi (2.8 bar) shall be conducted for
24 hours. Any leakage that results in a loss of pressure in excess of 1 V2 psi (0.1 bar) for the 24 hours shall be corrected.
16.2.2.2 Where systems are installed in spaces that are ca-pable of being operated at temperatures below 32°F (0°C), air pressure leakage tests required in 16.2.2 shall be cnducted at the lowest nominal temperature of the space.
2002 EditIon