HomeMy WebLinkAbout1480 TARA CT; ; CB121092; PermitCity of Carlsbad
1635 Faraday Av Carlsbad, CA 92008
08-21-2012 Residential Permit Permit No: CB121092
Job Address:
Building Inspection Request Line (760) 602-2725
1480 TARA CT CBAD
Permit Type:
Parcel No:
Valuation:
Occupancy Group:
# Dwelling Units:
Bec1rooms:
RESDNTL
2074400300
$43,734.00
0
0
Sub Type: RAD
Lot#: 0
Constuction Type: 5B
Reference #:
Structure Type:
Bathrooms: 0
Orig PC#:
Status: ISSUED
Applied: 06/12/2012
Entered By: RMA
Plan Approved: 08/21/2012
Issued: 08/21/2012
Inspect Area:
Plan Check#:
Project Title: PETTIT RES-ADD 192 SF
TO EXISTING MASTER BEDROOM //ADD 140 SF FOR BATHROOM &
CLOSET TO BEDROOM #3 (NEAR LIVING ROOM)
Applicant:
PETTIT DALE D&CAROL A
1480 TARA CT
CARLSBAD CA 92008
760 730-1462
Building Permit
Add'I Building Permit Fee
Plan Check
Add'I Plan Check Fee
Plan Check Discount
Strong Motion Fee
Park in Lieu Fee
Park Fee
LFM Fee
Bridge Fee
Other Bridge Fee
BTD #2 Fee
STD #3 Fee
Renewal Fee
Add'I Renewal Fee
Other Building Fee
HMP Fee
Pot. Water Con. Fee
Meter Size
Add'I Pot. Water Con. Fee
Reel. Water Con. Fee
Green Bldg Stands (SB1473) Fee
Green Bldg Stands Plan Chk Fee
$408.20
$0.00
$285.74
$0.00
$0.00
$4.37
$0.00
$0.00
$0.00
$0.00
$0.00
$0.00
$0.00
$0.00
$0.00
$0.00
$0.00
$0.00
$0.00
$0.00
$1.00
$0.00
Owner:
PETTIT DALE D&CAROL A
1480 TARA CT
CARLSBAD CA 92008
Meter Size
Add'I Reel. Water Con. Fee
Meter Fee
SDCWA Fee
CFO Payoff Fee
PFF (3105540)
PFF (4305540)
License Tax (3104193)
License Tax (4304193)
Traffic Impact Fee (31 05541)
Traffic Impact Fee (4305541)
Sidewalk Fee
PLUMBING TOTAL
ELECTRICAL TOTAL
MECHANICAL TOTAL
Housing Impact Fee
Housing lnlieu Fee
Housing Credit Fee
Master Drainage Fee
Sewer Fee
Additional Fees
Fire Sprinkler Fees
TOTAL PERMIT FEES
Total Fees: $877.31 Total Payments to Date: $877.31 Balance Due:
Inspector:
FINAL APPROVAL
Date: .;J.. ~ 8' · 1 7 Clearance:
$0.00
$0.00
$0.00
$0.00
$0.00
$0.00
$0.00
$0.00
$0.00
$0.00
$0.00
$86.00
$40.00
$52.00
$0.00
$0.00
$0.00
$0.00
$0.00
$0.00
$0.00
$877.31
$0.00
NOTICE: Please take NOTICE that approval of your proJect includes the "Imposition· of fees. dedications, rese111ations, or other exactions hereafter collectively
referred to as 'fees/exactions." You have 90 days from the date this permit was issued to protest imposition of these fees/exactions If you protest them, you must
follow the protest procedures set forth in Government Code Section 6602D(a), and file the protest and any other required information with the City Manager for
processing 1n accordance with Car1sbad Municipal Code Section 3.32.030. Failure to timely follow that procedure will bar any subsequent legal action to attack.
review, set aside, void, or annul their imposition.
You are hereby FURTHER NOTIFIED that your right to protest the specified fees/exactions DOES NOT APPLY to water and sewer connection fees and capacity
changes, nor planning, zoning, grading or other similar application processing or service fees in connection with this project. NOR DOES IT APPLY to any
City of Carlsbad
1635 Faraday Av Carlsbad, CA 92008
08-21-2012
Storm Water Pollution Prevention Plan (SWPPP) Permit
Permit No:SW120248
Job Address:
Permit Type:
Parcel No:
Reference #:
CB#:
1480 TARA CT CBAD
SWPPP
2074400300
CB121092
Status:
Lot#: 0 Applied:
Entered By:
Issued:
Inspect Area:
Project Title: PETTIT ADDITION/2ND DWELLING U Tier:
Applicant:
PETTIT DALE D&CAROL A
1480 TARA CT
CARLSBAD CA 92008
760 730-1462
Emergency Contact:
CAROL PETTIT
760 730-1462
SWPPP Plan Check
SWPPP Inspections
Additional Fees
TOTAL PERMIT FEES
Priority:
Owner:
PETTIT DALE D&CAROL A
1480 TARA CT
CARLSBAD CA 92008
ISSUED
06/12/2012
RMA
08/21/2012
1
L
$45.00
$55.00
$0.00
$100.00
Total Fees: $100.00 Total Payments To Date: $100.00 Balance Due:
FINAL A.PPROVAL
$0.00
~ «(•~ ~ CITY OF
CARLSBAD
Building Permit Application
1635 Faraday Ave., Carlsbad, CA 92008
760-602-2717 / 2718 / 2719
Fax: 760-602-8558
www. ca rlsba dca.gov
-0 3
CT/PROJECT# LOT# CONSTR. TYPe: OCC GROUP
DESCRIPTION OF WORK: Include Square F&et
: ci L "a( +-~ \~~~~ . )-ec..~f co ,n
EXISTING USE PROPOSED us~ . GARAGE (SF)
-::..,1~\f: \-,: ~z:.bYl.._l~ \\t')'\r\.C /1Jt ,\tt,t'\l,1.,'c<iM,1.\ &7("f"v
CONTACT NAME /If 0/fterent Fom App/leant)
ADDRESS
CITY STATE ZIP
PHONE FAX
EMAIL
CITY • C L-t1 \-s\) c¼\ STATE
.S\~
ZIP
97-Ctb
FAX N;~
STATE UC.#
DECKS (SF)
t--J/'.l-
FIREPLACE
YES I&-# _j_ NO □
c+
AIR CONDITIONING
YES O NO\L_
STATE(' f+
I+
ADORES , •
q--c,::,, S l·e+: Jt nc T nrJ1cu J
PHONE
7loD
EMAIL
~ IA 11-\.U
STATELIC.# Cl 1'I' BUS. UC.#
Lf;:>'?(X_> l
FIRE SPRINKLERS
YES~ NOD
(Sec. 7031.5 Business and Professions Code: Any City or County which requires a permit to construct, alter. improve, demolish or repair any structure. prior to its issuance. also requires the applicant for such permit to file a signed statement that he is licensed pursuant to the provisions of the Contractor's License law (Chapter 9, commending with Section 7000 of Division 3 of the Business and Professions Code) or (hat he is exempt therefrom, and the basis for the alleged exemption. Any violation of Section 7031.5 by any appl,cant for a permit subjects the applicant to a civil penalty of not more than five hundred dollars ($500)).
Workers' Compensation Declaration: I hereby affirm under penelty of p,;IJUl'f (1110 of Iha following declarations:
~I have and will maintain a certificate of consent to self-Insure for workers' compensatioo as provided by Section 3700 of the Labor Code, for the performance of the work for whlCh this permit is iswed.
0 I have and will maintain workers' compensation, as required by Section 3700 of the Labor Code, for the performance of the work for which this permit is issued. My workera' compensation insurance carrier and policy
number are: Insurance Co. ____________________ Policy No. ______________ Expiration Date _________ _
~ecbon need not be completed if the permit is for one hundred dollars ($100) or less. A Certificate of Exemption: I certify that in the performance of the work for which this permit is issued, I shall not employ any persoo in any manner so as to become subject to the Workers' Compensation Laws of
California. WARNING: Failure to secure workers' compensation coverage is unlawful, and shall subject an employer to criminal penalties and civil fines up to one huMred thousand dottart (&100,000), In
addhion to the cost of compensation a ges as provkled for in Section 3706 of the Labor code, interest and attorney's lees.
,J!S CONTRACTOR SIGNATURE
I hflfflby afflrm that I am exempt from Contractor's U=e Law for ths following reason:
□ I, as o'Mler of the property or my employees wilh wages as their sole compensation, will do the work and the structure is nol inlended or offered for sale (Sec. 7044, Busine5$ and Professions Code: The Conlracklr's
License Law does not apply to an 0W11er of property who builds or improves thereon, and who does such work himself or lhrough his Dl'ln employees, provided lhat such improvements are not intended or offered for
'\. /" sale. If, however. the building or improvement is sold within one year of completion, the Ol'lfler-builder will have the burden of proving that he did not build or improve for the pu,pose of sate).
l!I I, as owner of the property, am exclusively contracting with licensed contractors lo C011struct the project (Sec. 7044, Business aoo Professions Code: The Conlraelor's License law does not apply to an owner ol
• property who builds or improves !hereon, and conlracts for such projects with contractor(s) licensed pursuant to the ContractOfs Licerise law).
□ I am exempt under Section ____ Buslness and Professions Code for this reason:
1~atlyplanto providelhemajorlaborandmaterialsforconstructionoflheproposed prope,tyimprovement. □ Yes l{No . . _11 I .. _.,,-HI I
2 (have have not) signed an application for a building permit for the proposed work. ~IC~ "'cu,1tfl.e\T }3U.(flLL\ L Ol<.6T •
3. contracted with the following person (firm) lo provide the proposed cooslruction (include name address I phooe I oonlractors' license number): 1 110 . 4 \ q-~ 3 D L.
4. I plan to provide portions of lhe wDlk, but I have hired the rollowing person to coordinate, supervise and provide lhe meiorwtN"k (include name/ address I phone /conlracton;' Hcense number):
5. I will provide some DI the l'IOlk, but I have contracted (hired) the following persons to provide the work indicated (inciude name/ address I phone/ type of IMllk):
A.!PRO!'ERTYOWNERSIGNATURE '-Q.~ v iliJ · c{µ....t;-tt. □AGENT OATE /.c,-1/-(''}_
COMei.ETE THU SECTION FOi' NQN•RESIDENTIAL BUILDING PERMITS ONt.V ~ ... ..!t ". " ' ' ' ! •' ,;' ,.,,.·
Is tne applicant or future building occupant required lo submit a business plan, acutely hazardous materials registration tom, or risk management and prevention program under Sections 25506, 25533 or 25534 of lhe
Presley-Tanner Hazardous Substance Act0unt Act? □ Yes D No
Is the applicant or future building occupant required to obtain a permit from lhe air pollution control district or air quality management disbict? □ Yes Cl No
Is lha facility to be constructed within 1,000 feel of the outer boundary of a school site? □ Yes D No
IF ANY OF THE ANSWERS ARE YES, A FINAL CERTIFICATE OF OCCUPANCY MAY NOT BE ISSUED UNLESS THE APPLICANT HAS MET OR IS MEETING THE REQUIREMENTS OF THE OFflCE OF
EMERGENCY SERVICES AND THE AIR POLLUTION CONTROL DISTRICT.
I cerllfy that I have read the application and state thatllle above information is correct and lllatthe Information on llle plans ls accurate. I agioo to comply with all City ordinances and State laws relating to building constnK:lion.
I 1-ereby authorize rei;resenlative of lhe City of Cansbad to enter upon 1he above menooned property for i1spedi:)n purposes. I ALSO AGREE TO SAVE, INDEMNIFY AND KEEP HARMLESS THE CITY OF CARLSBAD
AGAINST ALL LIABILITl~S. JUDGMENTS, COSTS AND EXPENSES WHICH MAY IN ANY WAY ACCRUE AGAINST SAID CITY IN CONSEQUENCE Of THE GRANTING OF THIS PERMrT.
OSHA An OSHA penn~ is required b' excavations over 5'0' deep and clemciition or conslruclon of structures r:Ne/ 3 sb:lries n height.
EXPIRATION: Every penntt issued by lhe Suil:ling Official under !he provisons of this Code shall expire by lin~tion and become null and void if 1he lxlidng ord authorized by such permit is not~ Vtilhin
180 day.; from lhe date of such permit or if lral buidng or work aulhor2ed by suci1 permtt is suspended or aoandont,tany lire a r hi work is CX11T1menced for a perioo of 180 days(Sediln 106.4.4 Unibm &iilding Qxle) .
..es'APPLICANT'ss1GNATURE \._Q_c--t.i,. \?&_j-f (,L.v,f!__f], ~--J:ct> nAre Li,, l I · J ?-
Inspection List
Permit#: CB121092 Type: RESDNTL RAD PETTIT RES-ADD 192 SF
TO EXISTING MASTER BEDROOM I/ADD 1
Date Inspection Item Inspector Act Comments
02/07/2013 89 Final Combo RI
02/07/2013 89 Final Combo PD AP
12/14/2012 17 Interior Lath/Drywall PD AP
12/05/2012 17 Interior Lath/Drywall PB AP
12/05/2012 17 Interior Lath/Drywall PB AP
12/05/2012 18 Exterior Lath/Drywall PB AP
12/05/2012 18 Exterior Lath/Drywall PB AP
11/29/2012 16 Insulation PB AP
11/27/2012 84 Rough Combo PB AP
10/30/2012 13 Shear Panels/HD's PD AP
10/15/2012 15 Roof/Reroof PD AP
09/27/2012 11 Ftg/Foundation/Piers PD AP
09/21/2012 21 Underground/Under Floor PD AP
Friday, February 08, 2013 Page 1 of 1
EsGil Corporation
In <Partnersnip witli, <;;01Jernmentfor<Bui{tfin9 Safety
DATE: 8/17/2012
JURISDICTION: City of Carlsbad
PLAN CHECK NO.: 121092
PROJECT ADDRESS: 1480 Tara Ct.
SET II
PROJECT NAME: Pettit Residence Remodel & Addition
□ bPf'LICANT
~JURIS.
□ PLAN REVIEWER
□ FILE
[:8J The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction's building codes.
D The plans transmitted herewith will substantially comply with the jurisdiction's codes
when minor deficiencies identified below are resolved and checked by building department staff.
D The plans transmitted herewith have significant deficiencies identified on the enclosed check list
and should be corrected and resubmitted for a complete recheck.
D The check list transmitted herewith is for your information. The plans are being held at Esgil
Corporation until corrected plans are submitted for recheck.
D The applicant's copy of the check list is enclosed for the jurisdiction to forward to the applicant
contact person.
D The applicant's copy of the check list has been sent to:
~ EsGil Corporation staff did not advise the applicant that the plan check has been completed.
D EsGil Corporation staff did advise the applicant that the plan check has been completed.
Person contacted: Telephone#:
Date contacted: (by: ) Email: Fax #:
Mail Telephone Fax In Person
[SJ REMARKS: No second dwelling unit allowed.
By: David Yao Enclosures:
EsGil Corporation
0 GA O EJ O PC 8/13
9320 Chesapeake Drive, Suite 208 ♦ San Diego, California 92123 ♦ (858) 560-1468 ♦ Fax (858) 560-1576
EsGil Corporation
In (l'artnersnip witn government for (]Juiftfing Safety
DATE: 6/20/2012
JURISDICTION: City of Carlsbad
PLAN CHECK NO.: 121092
PROJECT ADDRESS: 1480 Tara Ct.
SET: I
PROJECT NAME: Pettit Residence Remodel & Granny Flat
~~~NT
~ □ PLAN REVIEWER
□ FILE
D The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction's codes.
D The plans transmitted herewith will substantially comply with the jurisdiction's
codes when minor deficiencies identified below are resolved and checked by building
department staff.
D The plans transmitted herewith have significant deficiencies identified on the enclosed check list
and should be corrected and resubmitted for a complete recheck.
t8J The check list transmitted herewith is for your information. The plans are being held at Esgil
Corporation until corrected plans are submitted for recheck.
D The applicant's copy of the check list is enclosed for the jurisdiction to forward to the applicant
contact person.
t8J The applicant's copy of the check list has been sent to:
Dale Pettit 1480 Tara Court Carlsbad, CA 92008
D EsGil Corporation staff did not advise the applicant that the plan check has been completed.
~ EsGil Corporation staff did advise the applicant that the plan check has been completed.
Person contacted: Dale Pettit (",J,..,,t) Telephone#: 760-730-1462
Date contacted: U>f 2., f 12. (by: ~) Email: clad1234@aol.com Fax #:
✓f Mail /Telephone_.., Fax In Person
0 REMARKS:
By: David Yao Enclosures:
EsGil Corporation
0 GA O EJ O PC 6/14
9320 Chesapeake Drive, Suite 208 ♦ San Diego, California 92123 ♦ (858) 560-1468 ♦ Fax (858) 560-1576
City of Carlsbad 121092
6/20/2012
PLAN REVIEW CORRECTION LIST
SINGLE FAMILY DWELLINGS AND DUPLEXES
PLAN CHECK NO.: 121092
PROJECT ADDRESS: 1480 Tara Ct.
FLOOR AREA:
Add living 322 sf
Add new entry 95 sf
REMARKS:
DATE PLANS RECEIVED BY
JURISDICTION:
DATE INITIAL PLAN REVIEW
COMPLETED: 6/20/2012
FOREWORD (PLEASE READ):
JURISDICTION: City of Carlsbad
STORIES: 1
HEIGHT:
DATE PLANS RECEIVED BY
ESGIL CORPORATION: 6/14
PLAN REVIEWER: David Yao
This plan review is limited to the technical requirements contained in the California version of
the International Residential Code, International Building Code, Uniform Plumbing Code,
Uniform Mechanical Code, National Electrical Code and state laws regulating energy
conservation, noise attenuation and access for the disabled. This plan review is based on
regulations enforced by the Building Department. You may have other corrections based on
laws and ordinance by the Planning Department, Engineering Department, Fire Department or
other departments. Clearance from those departments may be required prior to the issuance of
a building permit.
Present California law mandates that construction comply with the 2010 edition of the California
Code of Regulations (Title 24), which adopts the following model codes: 2009 IRC, 2009 IBC,
2009 UPC, 2009 UMC and 2008 NEC.
The above regulations apply, regardless of the code editions adopted by ordinance.
The following items listed need clarification, modification or change. All items must be satisfied
before the plans will be in conformance with the cited codes and regulations. Per Sec. 105.4 of
the 2009 International Building Code, the approval of the plans does not permit the violation of
any state, county or city law.
To speed up the recheck process, please note on this list (or a copy) where each
correction item has been addressed, i.e., plan sheet number, specification section, etc.
Be sure to enclose the marked up list when you submit the revised plans.
City of Carlsbad 121092
6/20/2012
Please make all corrections, as requested in the correction list. Submit FOUR new
complete sets of plans for commercial/industrial projects (THREE sets of plans for
residential projects). For expeditious processing, corrected sets can be submitted
in one of two ways:
1. Deliver all corrected sets of plans and calculations/reports directly to the City of
Carlsbad Building Department, 1635 Faraday Ave., Carlsbad, CA 92008, (760)
602-2700. The City will route the plans to EsGil Corporation and the Carlsbad
Planning, Engineering and Fire Departments.
2. Bring one corrected set of plans and calculations/reports to EsGil Corporation,
9320 Chesapeake Drive, Suite 208, San Diego, CA 92123, (858) 560-1468.
Deliver all remaining sets of plans and calculations/reports directly to the City of
Carlsbad Building Department for routing to their Planning, Engineering and Fire
Departments.
NOTE: Plans that are submitted directly to EsGil Corporation only will not be
reviewed by the City Planning, Engineering and Fire Departments until review by
EsGil Corporation is complete.
• PLANS
1. All sheets of plans must be signed by the person responsible for their
preparation. (California Business and Professions Code).
2. Provide a statement on the Title Sheet of the plans stating that this project shall
comply with the 2010 California Residential Code, which adopts the 2009 IRC,
2009 UMC, 2009 UPC and the 2008 NEC. Section R106.2.
• GENERAL RESIDENTIAL REQUIREMENTS
3. Bathrooms (defined as having a shower or tub), shall be provided with
mechanical ventilation (an openable window is not allowed). Energy Standards
150(0).
4. Glazing in the following locations should be shown on the plans as safety glazing
material in accordance with Section R308.4 (see exceptions):
a) Glazing adjacent to a door where the nearest exposed edge of the glazing
is within a 24-inch arc of either vertical edge of the door in a closed position
and where the bottom exposed edge of the glazing is less than 60 inches
above the walking surface. (window E next to door 3 at kitchen/dining ?
Unless comply with the exception 1 ?)Exceptions:
i) Glazing that is adjacent to the fixed panel of patio doors.
5. Wall assemblies separating main dwelling and granny flat shall be of one-hour
fire resistive construction. Provide details of the assemblies. Section R302.3.
Such wall assemblies shall extend to the underside of the roof sheathing, where
applicable. (5/8" type 'x' gypsum board on both sides of the 2x4 stud wall)
City of Carlsbad 121092
6/20/2012
Exceptions:
a) A fire-resistance rating of ½-hour shall be permitted in buildings equipped
throughout with an automatic sprinkler system installed in accordance with
NFPA 13.
b) Wall assemblies need not extend through attic spaces when the ceiling is
protected by not less than ¾-inch Type X gypsum board and an attic draft
stop constructed as specified in Section R302.12.1 is provided above and
along the wall assembly separating the dwellings. The structural framing
supporting the ceiling shall also be protected by not less than ½ -inch
gypsum board or equivalent.
6. Provide a note on the plans stating: "Penetrations of fire-resistive walls, floor--
ceilings and roof-ceilings shall be protected as required in CRC Section R302.4."
7. Walls separating main dwelling and granny flat shall have a sound transmission
class (STC) of not less than 50. CBC Section 1207.6. Show the location of and
provide details of the listed wall assemblies, and indicate the listing agency and
listing number for the tested ratings.
8. The Title Sheet or Site Plan should clearly indicate if any portion of the project is
in a noise critical area (CNEL contours of 60 dB) as shown on the City or County's
General Plan. If no portion of the project is within a noise critical area, provide a
note on the Title Sheet stating: "This project is not within a noise critical area
(CNEL contour of 60 dB) as shown on the General Plan". CBC Section 1207.11.
9. If the project is located in noise critical areas (CNEL contours of 60 dB) as shown
on the City or County's General Plan, then an acoustical analysis showing that the
proposed building has been designed to limit noise in habitable rooms to CNEL of
forty-five dB is required. Where windows must be closed to comply, it is
necessary to provide mechanical ventilation capable of providing at least two air
changes per hour. Provide design. CBC Section 1207 .11.
• ROOFING
10. Show the required ventilation for attics (or enclosed rafter spaces formed where
ceilings are applied directly to the underside of roof rafters). The minimum vent
area is 1/150 of attic area (or 1/300 of attic area if at least 50% (but not more
than 80%) of the required vent is at least 3 feet above eave vents or cornice
vents). Show on the plans the area required and area provided. Section R806.2.
11. Where eave vents are installed, insulation shall not block the free flow of air. A
minimum of 1" of air space shall be provided between the insulation and the roof
sheathing. To accommodate the thickness of insulation plus the required 1"
clearance, member sizes may have to be increased for rafter-ceiling joists.
Section R806.3.
City of Carlsbad 121092
6/20/2012
12. Note on the plans: "Attic ventilation openings shall be covered with
corrosion-resistant metal mesh with 1/8" minimum to¼" maximum openings.
Section R806.1.
• FOUNDATION REQUIREMENTS
13. Foundation anchorage in Seismic Design Categories C, Do, D1 and D2. In
addition to the requirements of Section R403.1.6, the following requirements
shall apply to wood light-frame structures in Seismic Design Categories Do, D1
and D2 and wood light-frame townhouses in Seismic Design Category C.
R403.1.6.1
1. Plate washers conforming to Section R602.11.1, 0.229"x3"x3". shall be
provided for all anchor bolts over the full length of required braced wall lines.
Properly sized cut washer shall be permitted for anchor bolts in wall lines not
containing braced wall panels.
• FRAMING
14. Detail E/4 the 2x4 support the 2x8 ridge shall be bearing at the truss joint where
web connect to top chord.
• MECHANICAL
15. Show on the plans the location, type and size (BTU's) of all heating and cooling
appliances or systems. The FAU for the main dwelling and granny flat shall be
separate unit.
• ELECTRICAL
16. Show on the plan the amperage of the electrical service, the location of the
service panel and the location of any sub-panels ..
17. Note on the plans that receptacle outlet locations will comply with CEC Article
210.52(A).
18. Include on the plans the following specifications for electrical devices installed in
dwellings: CEC Article 210 & 406
a) Tamper resistant receptacles for all locations described in 210.52 (i.e., all
receptacles in a dwelling).
b) Weather resistant type for receptacles installed in damp or wet locations
(outside).
c) Arc-fault protection for all outlets (not just receptacles) located in rooms
described in NEC 210.12(8): Family, living, bedrooms, dining, halls, etc.
d) GFCI protected outlets for locations described in NEC 210.8: Kitchens,
garages, bathrooms, outdoors, within 6' of a sink, etc.
City of Carlsbad 121092
6/20/2012
• PLUMBING
19. Dimension on the plans the 30" clear width required for the water closet
compartment and the 24" clearance required in front of the water closet. CPC
407.5.
20. Provide a note on the plans: The control valves in bathtubs, whirlpool bathtubs,
showers and tub-shower combinations must be pressure balanced or
thermostatic mixing valves. CPC Section 414.5 and 418.0.
21. Specify on the plans: Water conserving fixtures: New water closets shall use no
more than 1.28 gallons of water per flush, lavatories and kitchen faucets may not
exceed 2.2 GPM, and showers may not exceed 2.5 GPM of flow. CPC Section
402.0.
• MISCELLANEOUS
22. To speed up the review process, note on this list (or a copy) where each
correction item has been addressed, i.e., plan sheet, note or detail number,
calculation page, etc.
23. Please indicate here if any changes have been made to the plans that are not a
result of corrections from this list. If there are other changes, please briefly
describe them and where they are located in the plans.
• Have changes been made to the plans not resulting from this correction list?
Please indicate:
Yes □ No □
24. The jurisdiction has contracted with Esgil Corporation located at 9320
Chesapeake Drive, Suite 208, San Diego, California 92123; telephone number of
858/560-1468, to perform the plan review for your project. If you have any
questions regarding these plan review items, please contact David Yao at EsGil
Corporation. Thank you.
City of Carlsbad 121092
6/20/2012
[DO NOT PAY -THIS IS NOT AN INVOICE]
VALUATION AND PLAN CHECK FEE
JURISDICTION: City of Carlsbad
PREPARED BY: David Yao
BUILDING ADDRESS: 1480 Tara Ct.
BUILDING OCCUPANCY: R3/U
BUILDING AREA Valuation
PORTION ( Sq. Ft.) Multiplier
remodel & Add 332
Air Conditioning
Fire Sprinklers
TOTAL VALUE
Jurisdiction Code cb By Ordinance
Bldg. Permit Fee by Ordinance
Plan Check Fee by Ordinance
Type of Review: 0 Complete Review
D Repetitive Fee _ ___E] Repeats
Comments:
D Other
D Hourly
EsGil Fee
PLAN CHECK NO.: 121092
DATE: 6/20/2012
TYPE OF CONSTRUCTION: VB
Reg. VALUE
Mod.
per city
D Structural Only
($)
43,734
43,734
$408.201
$265.331
$228.591
Sheet 1 of 1
macvalue.doc +
~ ...
~ CITY OF
CARLSBAD
DATE: 06/25/12 PROJECT NAME:
PLAN CHECK
REVIEW
TRAN SM ITT AL
PLAN CHECK NO: 1 SET#: 1 ADDRESS: 1480 TARA CT
VALUATION: $43,734
Community & Economic
Development Department
1635 Faraday Avenue
Carlsbad CA 92008
www.carlsbadca.gov
PROJECT ID: CB 12-1092
APN: 207-440-03
✓ This plan check review is complete and has been APPROVED by the ENGINEERING
Division.
By: KATHLEEN LAWRENCE
A Final Inspection by the Division is required Yes ✓ No
This plan check review is NOT COMPLETE. Items missing or incorrect are listed on
the attached checklist. Please resubmit amended plans as required.
Plan Check Comments have been sent to:
You may also have corrections from one or more of the divisions listed below. Approval
from these divisions may be required prior to the issuance of a building permit.
Resubmitted plans should include corrections from all divisions.
For questions or clarifications on the attached checklist please contact the following reviewer as marked:
..
ENGIN~ERING; PLANNING .. ·•···. FIRE PREVENTION
760-602-4610 7~<M>02-2750 760-602-4665
Chris Sexton ✓ Kathleen Lawrence Greg Ryan
760-602-4624 760-602-2741 760-602-4663
Chris.Sexton@carlsbadca.gov Kathleen.Lawrence@carlsbadca.gov Gregory.Ryan@carlsbadca.gov
Gina Ruiz Linda Ontiveros Cindy Wong
760-602-4675 760-602-2773 760-602-4662
Gina.Ruiz@carlsbadca.gov Linda.Ontiveros@carlsbadca.gov Cynthia.Wong@i.:;arlsbadca.gov
Dominic Fieri
760-602-4664
Dominic.Fieri@carlsbadca.gov
Remarks:
/;~
"-' 4> .. ~ CITY OF
CARLSBAD
PLANNING DIVISION
BUILDING PLAN CHECK
REVIEW CHECKLIST
P~28
Development Services
Planning Division
1635 Faraday Avenue
(760) 602-4610
www.carlsbadca.gov
REVIEW#:
1 2 3
~ [8J □
Plan Check No. CB12-1092 Address 1480 Tara Ct Date 6/19/2012 Review# 2
Planner Chris Garcia Phone (760) 602-4622
APN: 207 -440-03-00
Type of Project & Use: Single Family Home Net Project Density:N/A DU/AC
Zoning: R-1 General Plan: RLM Facilities Management Zone: 1
CFO (in/out) #_Date of participation:OUT Remaining net dev acres:N/A
(For non-residential development: Type of land use created by this permit: N/A)
Legend: [8J Item Complete
Environmental Review Required:
DATE OF COMPLETION:
D Item Incomplete -Needs your action
YES O NO [8J TYPE
Compliance with conditions of approval? If not, state conditions which require action.
Conditions of Approval:
Discretionary Action Required: YES [8J NO O TYPE CDP 12-10 Approved
APPROVAL/RESO. NO. DATE
PROJECT NO.
OTHER RELATED CASES:
Compliance with conditions or approval? If not, state conditions which require action.
Conditions of Approval: --.
Coastal Zone Assessment/Compliance
Project site located in Coastal Zone? YES r8J. NOD
CA Coastal Commission Authority? YES D NO r8J.
If California Coastal Commission Authority: Contact them at -7575 Metropolitan Drive,
Suite 103, San Diego, CA 92108-4402; (619) 767-2370
Determine status (Coastal Permit Required or Exempt): Minor CDP Required
Habitat Management Plan
Data Entry Completed? YES □ NO [8J
If property has Habitat Type identified in Table 11 of HMP, complete HMP Permit application
and assess fees in Permits Plus
(A/P/Ds, Activity Maintenance, enter CB#, toolbar, Screens, HMP Fees, Enter Acres of
Habitat Type impacted/taken, UPDATE!)
lnclusionary Housing Fee required: YES D NO 12J
(Effective date of lnclusionary Housing Ordinance -May 21, 1993.)
Data Entry Completed? YES □ NO □
(A/P/Ds, Activity Maintenance, enter CB#, toolbar, Screens, Housing Fees, Construct
Housing YIN, Enter Fee, UPDATE!)
12J 12J D Housing Tracking Form (form P-20) completed: YES D NO D NIA [8J
P-28 Page 1 of 2 0711 1
· Site Plan:
□~□ Provide a fully dimensional site plan drawn to scale. Show: North arrow, property lines,
easements, existing and proposed structures, streets, existing street improvements, right-of-
way width, dimensional setbacks and existing topographical lines (including all side and rear
yard slopes). Provide legal description of property and assessor's parcel number.
City Council Policy 44 -Neighborhood Architectural Design Guidelines
1. Applicability: YES □ NO ~
2. Project complies: YES ~ NOD
Zoning:
1 . Setbacks:
Front:
Interior Side:
Street Side:
Rear:
Top of slope:
Required 20 Shown 37
Required _5 __ Shown ,,5 __
Required N/A Shown N/A
Required 1Q__ Shown ~1~6 __
Required N/A Shown N/A
2. Accessory structure setbacks: N/A
Front:
Interior Side:
Street Side:
Rear:
Structure separation:
3. Lot Coverage:
4. Height:
Required __ Shown
Required __ Shown
Required __ Shown
Required __ Shown __
Required __ Shown __
Required <40% Shown <40%
Required <30' Shown~
5. Parking: Spaces Required 2 covered Shown 3 covered
(breakdown by uses for commercial and industrial projects required)
Residential Guest Spaces Required 1 Shown 1
Additional Comments The site has been approved for a second dwelling unit. However, it
was communicated that the owner was going to remove the oven and just make a standard
addition without a second dwelling unit. The oven still shows on at least 1 page of the plans.
However, Planning is fine with the oven being there to create a second dwelling unit, or
having it removed to be a standard addition.
OK TO ISSUE AND ENTERED APPROVAL INTO COMPUTER Chris Garcia DATE 8/9/2012