Fixed Systems Permit
Permit No: FS130018
1890 RUTHERFORD
Job Address:
RD
Permit Type: FIXSYS
Parcel No: 2121203500
Lot #: 0
Reference No.:
PC #:
Status: APPROVED
Applied 7/18/2013
Approved: 7/22/2013
Issued: 7/22/2013
Inspector:
Project Title: GENOPTIX CTCE INSTALL FULLY AUTO ANSUL, INERGEN (IC-
541) FIRE SUPPRESSION SYSTEM WITH BATTER BACKUP IN
SERVER ROOM 1902
Applicant:
JAM FIRE PROTECTION INC
8254 RON SON RD
SAN DIEGO CA
858-495-2328 858-495-2335
Owner:
PDG CARLSBAD 47&48 L P
1825 GILLESPIE WAY #102
EL CAJON CA
Fees ($) Add'I Fees ($) Total ($) Balance ($)
370 0 370 0
Fire Protection, Inc.
8254 Ronson Rd.
San Diego, CA. 92111
Phone (858) 495-2335, Fax (858) 496-3820
Project Info:
,i Genoptix - CTCE
1890 Rutherford Rd.
Carlsbad, CA. 92008
Scope of Work:
Installation of an Ansul, Inergen (IG-541), Inert Gas Fire Suppression System
in Server Room 1902. The Inergen system will utilize an Autopulse. Z-10,
agent release control panel for the detection and control functions.
Design By:
Steve Wylie
858-495-2335
StevewyIiejamfire.com
BLANK PAGE
S
0
Hydraulic Flow CaIcs
for the
Ansul, Inergen System
C
S
0
ANSUL
INERGEN DESIGNER
UL listed EX4510, FMRC Approved (J.I.)2Y0A9.AF. ULC listed CEx1151
Version 2.1.2
File: Data file name: C:\Bruce DeushaneJAM\Active Projects1 -JAM SDGenoptix\Genoptix FIXED.inr
Job Number 13SRW2859F for Genoptix - CTCE
Address: 1890 Rutherford Rd.
Carlsbad CA 92008
Country: USA
Agent Storage Conditions
Storage pressure is 2175 psia at 70 degrees Fahrenheit.
439 cubic feet of INERGEN stored in each of 3 cylinders.
Total agent in storage is 1317 cubic feet.
Time to discharge 1185 cubic feet (90% of INERGEN) is 68.4 seconds
Maximum pressure downstream of manifold orifice is 1226 psia
Concentrations
95% Maximum Minimum Requested
Time Cu Ft Concentration Concentration Concentration
Area Volume (sec) INERGEN at Max. Temp. at Mm. Temp. at Min Temp.
Server Room 2495.5 46 1317.0 41.4% at 75°F 40.5% at 60°F 34.2% at 60°F
Sea level equivalent oxygen: 12.3% at 75°F
Concentrations are based on altitude of 100 ft mean sea level.
0 Free Vent Calculation
Peak Maximum Wall Minimum Free
Area Rate Strength Vent Area
Server Room 2795.6 cfm 5.0 lbs./sq.ft. 107 sq. in.
Pressure Drop Results
Sec Sec Nominal Length Equiv Elev Tee! Start Term Flow
Start End Pipe Size (ft) Length(ft) (ft) Mfld psia psia (cfm)
1 2 1!2 40T 0.0 38.0 0.0 MFLD 1033 999 501.6
2 3 1 80T 1.0 2.6 0.0 MELD 999 999 1003.2
3 4 1 80T 1.0 2.6 0.0 MFLD 999 995 1504.8
4 5 1 80T 1.5 5.5 0.5 MFLD 995 991 1504.8
5 6 ORIFICE .344 INCHES DRILL NO. 11/32 991 423 1504.8
6 7 1 40T 3.5 3.5 3.5 423 574 1504.8
7 8 1 40T 4.4 7.0 0.0 574 567 1504.8
8 301 1 40T 1.0 6.2 -1.0 SIDE 567 565 752.1
1 (Continued)
ANSUL
INERGEN DESIGNER
• UL listed EX4510, FMRC Approved (J.l.) 2Y0A9.AF. ULC listed CEx1151
Version 2.1.2
File: Data file name: C:\Bruce Deushane\JAM\Active Projects\1-JAM SDGenoptix\Genoptix FIXED.inr
Job Number: 13SRW2859F
Pressure Drop Results (Continued)
Sec Sec Nominal Length Equiv Elev Tee! Start Term Flow
Start End Pipe Size (if) Length(ft) (if) Mfld psia psia (cfm)
8 9 1 40 T 7.8 9.5 0.0 THRU 567 568 752.7
9 302 1 401 1.0 3.6 -1.0 568 567 752.7
Calculation based on 70 degree Fahrenheit pre-discharge Pipeline Temperature
Pipe and Fittings
Sec Sec Nominal Length Side Thru Unions! EqI
Start End Pipe Size (if) 90's Tee Tee Cplgs (if)
1 2 1/2 40T 0.0 0 0 0 0 Cyl Valve 38 ft
2 3 1 801 1.0 0 0 1 0
3 4 1 801 1.0 0 0 1 0
S 4 5 1 801 1.5 1 0 1 0
5 6 1 801 0 0 0 0 Man. Orifice
6 7 1 401 3.5 0 0 0 0
7 8 1 401 4.4 1 0 0 0
8 301 1 401 1.0 0 1 0 0
8 9 1 401 7.8 0 0 1 0
9 302 1 40T 1.0 1 0 0 0
Nozzle Performance Summary
Nozzle Nominal Drill Drill Quantity (cu if) Area
Number Pipe Size Number Diameter Discharged Name
301 1 40 T S 0.348 659.3 Server Room
302 1 40 T S 0.348 657.7 Server Room
Messages/Errors
ANSUL 150 bar INERGEN DESIGNER Version number 2.1.2
Calculation based on fixed nozzle and pipe sizes.
0 2 (Continued)
ANSUL
INERGEN DESIGNER
UL listed EX4510, FMRC Approved W.I.) 2Y0A9.AF. ULC listed CEx1151
Version 2.1.2
File: Data file name: C:\Bruce DeushaneJAM'Active Projects1-JAM SDGenoptixGenoptix FIXED.inr
Job Number: 13SRW2859F
Messages/Errors (Continued)
Calculation done on 7/16/2013 at 11:56:04 AM
Concentrations are based on an altitude of 100 ft above mean sea level.
Altitude correction factor is 1.00
Pipe schedule selected for pipe sizes downstream of the manifold orifice is based on the maximum
pipe pressure for Grade A-53B, A-I 06B Seamless. To determine if other grades are acceptable,
verify that the maximum pipe pressures for other grades are equal to or greater than the maximum
anticipated downstream pressure.
Calculation by JAM Fire Protection
Bruce Deushane
1930 S. Myrtle Ave.
Monrovia CA 91016 USA
Telephone: 626-256-4400
Fax: 626-256-4401
S
0
3 End of Printout
ANSUL
INERGEN DESIGNER
Version 2.1.2
File: Data file name: C:\Bruce Deushane\JAM\Active Projects1 -JAM SD\GenoptixGenoptix FIXED.inr
Job: 13SRW2859F
Customer: Genoptix - CTCE
Address: 1890 Rutherford Rd.
Carlsbad CA 92008
Country: USA
Hazard Area Information
Area: Server Room
Design concentration 34.2% at 600 Fahrenheit
Estimated maximum concentration 41.3% at maximum hazard temperature 75° Fahrenheit
Net volume of enclosure 2495.5 cubic feet
Minimum INERGEN required 1065.6 cubic feet
Approximate INERGEN supplied 1317. cubic feet
Flooding factor .427 cubic feet of INERGEN per cubic feet of enclosure volume
Maximum allowable wall strength 5.0 lbs./sq.ft.
Area consists of one volume
Volume 1: Length 17.5ftWidth 15.5 ft Height 9.2ft
2 nozzles. Nozzle identifiers: 301, 302
Agent Storage Conditions
Number of cylinders: 3 each containing 439 cubic feet of INERGEN.
agent 1317 cubic feet
•
Total
Engineering units (ft, cu ft, psia) are specified
Calculation based on 70 degree Fahrenheit pre-discharge Pipeline Temperature
Calculation based on fixed nozzle and pipe sizes
Pipe Data Input
Sec Sec Nominal Length Elev 90's Side Thru Union! Noz EqI
Start End Pipe Size (ft) (ft) Tee Tee Cplg Dia (ft)
1 2 1/2-40T 0.01 0.00 0 0 0 0 38.00
2 3 1 - 80 1 1.00 0.00 0 0 1 0 2 cyl 0.00
3 4 1 - 80 1 1.00 0.00 0 0 1 0 3 cyl 0.00
4 5 1 - 80 T 1.50 0.50 1 0 1 0 3 cyl 0.00
5 6 1-801 0.00 0.00 0 0 0 0 Orifice
6 7 1 -401 3.50 3.50 0 0 0 0 0.00
7 8 1 - 40 T 4.40 0.00 1 0 0 0 0.00
8 301 1-40T 1.00 -1.00 0 1 0 0 0.348 0.00
8 9 1 - 40 T 7.80 0.00 0 0 1 0 0.00
9 302 1-401 1.00 -1.00 1 0 0 0 0.348 0.00
0
1 (End of Data Input File Printout)
S
S
BLANK PAGE
Ansul, Inergen (IG-541
150 Bar
INERT GAS FIRE SUPPRESSION SYSTEM
DATA SHEETS
S
S
0
BLANK PAGE