Genoptix CTCE Alarms Review Comments. Page 2
Review Comments
Genoptix CTCE Alarms, 1890 Rutherford Road, Carlsbad, CA
We strongly recommend the following operational tests be performed once the system installation
has been completed.
A "power off' test, where the normal power supply is shut off, and the system is left to
function on battery power alone for a period of 24 hours, at which time the system should still
be functioning and operational.
At the end of the end of the above test, prior to the primary power being restored, the system
should be placed in an "alarm" condition for a period of not less than five minutes, during
which time all notification appliances, including the off-station notification, are to function as
designed.
Once the two prior tests have been completed, the current level in the batteries should be
checked, the primary power restored, and at the end of 48 hours the current level checked
again to verify that the charging function of the panel is both operational, and able to recharge
the batteries within the time period specified by NFPA-72.
Once the test in item "c" has been completed, one of the leads to the battery should be
disconnected, to determine that the system will provide notification of an "off-normal" power
condition to the monitoring company.