- SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 1.
DATE: -12117/2-00-9- -C:-\HASS-74\C4211-L1B.SDF-
JOB TITLE: OAK AVE. LOT-#1 RESIDENCE B TWO HEAD CALC-2nd FLOOR -- -
WATER SUPPLY DATA
SOURCE STATIC RESID. FLOW AVAIL. TOTAL REQ'D
NODE PRESS. PRESS. @ PRESS. 8 DEMAND PRESS.
TAG (PSI) (PSI) (G-PM) (PSI) -(GPM) (-PSI)
1 88.0 82.0 500.0 88.0 31.3 61.2
AGGREGATE FLOW ANALYSIS
TOTAL FLOW AT SOURCE 31.3 GPM
TOTAL HOSE STREAM ALLOWANCE AT SOURCE 0.0 GPM
OTHER HOSE STREAM ALLOWANCES 5.0 GPM
TOTAL DISCHARGE FROM ACTIVE SPRINKLERS 26.3 GPM
NODE ANALYSIS DATA
NODE TAG ELEVATION NODE TYPE PRESSURE DISCHARGE
(FT) (PSI) (GPM)
1 0.0 SOURCE 61.2 31.3
2 0.0 - - - - 46.6 - -
2A 0.0 - - - - 42.6 - - -
3A 10.0 HOSE STREAM 36.2 5.0
3 10.5 - - - - 33.7 -. - -
4 13.5 - - - - 30.7 - - -
5 26.5 - - - - 19.0
6 35.5 - - - - 13.3 - - -
7 35.5 - - - - 9.6 - - -
7A 35.0 K= 4.30 9.6 13.3
8A 35.0 K= 4.30 9.1 13.0
SPRINKLER SYSTEMHYDRAULIC'ANALYSIS Page
-DATE: 12117/2009 -- -- .- c:\HAs74\c4211-L1B.sDF --
JOB-TITLE OAK AVE LOT #1 RESIDENCE B TWO HEAD CALC-2nd FLOOR
PIPE DATA
PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS.
END ELEV. NOZ. PT DISC. VEL(FPS) HW(C) (FT) SUM.
NODES (FT) (K) (PSI) (GPM) FL/FT (PSI)
Pipe: 1 31.3 0.995 FL 45.00 PF 14.6
1 0.0 SRCE 61.2 (N/A) 12.9 150 FTG T2LG PE 0.0
2 0.0 0.0 46.6 0.0 0.256 TL 57.00 PV
Pipe: 2 FIXED PRESSURE LOSS DEVICE
2 0.0 0.0 46.6 0.0 4.0 psi, 31.3 gpm
2A 0.0 0.0 !12.6 0.0
Pipe: 3 31.3 1.590 PL 65.00 PF 2.1
2A 0.0 0.0 42.6 0.0 5.1 150 FTG 5L PE -4.3
3A 10.0 H.S. 36.2 5.0 0.026 TL 80.00 PV
Pipe: 4 26.3 1.265 FL 5.00 PF 2.3
3A 10.0 H.S. 36.2 5.0 6.7 150 FTG 2T3LC FE -0.2
3 10.5 0.0 33.7 0.0 0.057 TL 40.00 PV
Pipe: 5 26.3 1.049 PL 3.00 PF 1.7
3 10.5 0.0 33.7 0.0 9.8 120 FTG C PE -1.3
4 13.5 0.0 30.7 0.0 0.216 TL 8.00 PV
Pipe: 6 26.3 1.101 PL 27.50 PF 6.0
4 13.5 0.0 30.7 0.0 8.9 150 FTG 3E5R FE -5.6
5 26.5 0.0 19.0 0.0 0.113 TL 53.50 PV
Pipe: 7 26.3 1.101 PL 9.00 FE' 1.8
5 26.5 0.0 19.0 0.0 8.9 150 FTG T2R FE -3.9
6 35.5 0.0 13.3 0.0 0.113 TL 16.00 PV
Pipe: 8 26.3 1.101 PL 14.00 FE' 3.7
6 35.5 0.0 13.3 0.0 8.9 150 FTG E2T2R FE 0.0
7 35.5 0.0 9.6 0.0 0.113 TL 33.00 pv
Pipe: 9 13.3 1.101 PL 0.50 PF 0.2
7 35.5 0.0 9.6 0.0 4.5 150 FTG TR FE 0.2
7A 35.0 4.3 9.6 13.3 0.032 TL 6.50 pv
Pipe: 10 13.0 1.101 FL 12.00 FE' 0.6
7 35.5 0.0 9.6 0.0 4.4 150 FTG E2R FE 0.2
8A 35.0 4.3 9.1 13.0 0.031 TL 21.00 PV
NOTES (HASS)
(1) Calculations were performed by the HASS 8.0 computer program
under license no. 16080621 granted by
HRS Systems, Inc.
208 South Public Square
Petersburg, TN 37144
-
- -'
SPRINKLER SYSTEMHYDRAULIC ANALYSIS Page .3
DATE 12/17/2009 - C \HASS74\C4211L1B SDF *
JOB TITLE OAK AVE LOT #1 RESIDENCE BTWO HEAD CALC-2nd FLOOR
The system has been calculated to provide an average
imbalance at each nodd of 0.010 gpm and a maximum
imbalance at any node of 0.103 gpm. /
Total pressure at each node is used in balancing the system.
Maximum water velocity is 12.9 ft/sec at pipe 1.
PIPE FITTINGS TABLE
Pipe Table Name: FSS.PIP
PAGE: A MATERIAL: SCH40 HWC: 120
Diameter Equivalent Fitting Lengths in Feet
(in) E T L C B G A D
Eli Tee
1.049 2.00 5.00 2.00 5.00 6.00 1.00 1.00 1.00
PAGE: H MATERIAL: CPVC HC: 150
Diameter Equivalent Fitting Lengths in Feet
(in) E T R K C L B L
Eli Tee TEERUN COtJPLG EL45
1.101 7.00 5.00 1.00 0.00 1.00 1.00 0.00 1.00
PAGE: I MATERIAL: CPPR-L HWC: 150
Diameter Equivalent Fitting Lengths in Feet
(in) E T L C B G A D
Eli Tee
1.265 5.00 9.00 2.00 11.00 2.00 2.00 0.00 0.00
PAGE: J MATERIAL: S40PVC HWC: 150
Diameter Equivalent Fitting Lengths in Feet
(in) E T L C B G A D
Eli Tee
1.590 6.00 12.00 3.00 14.00 8.00 2.00 0.00 0.00
PAGE: K MATERIAL: CPPR-K HWC: 150
Diameter Equivalent Fitting Lengths in Feet
(in) E T L C B G A D
Eli Tee L
0.995 2.00 6.00 1.50 0.00 0.00 3.00 0.00 0.00
.SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 4
DATE: 12/17/2009 C:\HASS74\C4211-LlB.SDF -
JOB TITLE: OAK AVE. LOT #1 RESIDENCE B TWO HEAD CALC-2nd FLOOR
WATER SUPPLY ANALYSIS
Static: 88.00 psi Resid: 82.00 psi Flow: 500.0 gpm
100.0
1
:so
G
A
U
G
E 6023
P
R
E
S 400
S
U
R
E
LEGEND
1 Available pressure
87.96 psi @ 31.3 gpm
2 9 Required pressure
61.20 psi CA, 31.3 qp
Source Supply Curve
System Demand Curve
20.0
P
S
I
I
200300 400 500 600 700 800 900 1000
FLOW (GPM)
- - ----. __-
- ---- VV._V V 1t' _VVV V - -V.,_: -r r- • -
ANALYSIS Pa675'
DATE 12/17/200 . *VV. C \HASS74\C42i1LlB SDF
JOB TITLE:ÔAK -AVEtOT- #1. RESIDE-NC-t. B---TWO HEAD CALC-2nd FLOOR. - V
- •V - 'tl - -. -r-:.. V V - - - - V -
V - _VVVV.V__•VV_ VVV.V V V• :_V.__V.V_V_. ------- ---- V
WATER SUPPLY CURVE - V
96+ •V -V VVV • •V V • V V
\\\\\\
I \\\\\\
* <-82.0 psi @ 500 gpm
80+ Flow Test Point
72+
P 64+
R X
E I
S
S 56+
U I V
R I
E
48+
P
S
I 40+
32+
24+
16+ LEGEND
X = Required Water Supply
61.20 psi 8 31.3 gpm
8+
I 0 = Available Water Supply
87.96 psi 8 31.3 gpm
+------+--------+--------+ ---------+-----------+
200 300 400 500 600 700 800 900 1000
FLOW (GPM)
- - -±---- - - * - -• --
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 1
DATE: 12/17/2009 . .,- -. C:\HASS74\C4211L1.SDF
JOB TITLE: OAK AVE. LOT #1RE'SIDENCE-A TWO HEAD CALC-REC ROOM
WATER SUPPLY DATA
SOURCE STATIC RESID. FLOW
NODE PRESS. PRESS. @
TAG (PSI) (PSI) (GPM)
1 88.0 82.0 500.0
AVAIL. TOTAL REQ'D
PRESS. @ DEMAND PRESS.
(-PSI) (GPM) (PSI)
88.0 31.3 54.1
AGGREGATE FLOW ANALYSIS:
TOTAL FLOW AT SOURCE ,31.3 GPM
TOTAL HOSE STREAM ALLOWANCE AT SOURCE 0.0 GPM
OTHER HOSE STREAM ALLOWANCES 5.0 GPM
TOTAL DISCHARGE FROM ACTIVE SPRINKLERS 26.3 GPM
NODE ANALYSIS DATA
NODE TAG ELEVATION NODE TYPE PRESSURE DISCHARGE
(FT) (PSI) (GPM)
1 0.0 SOURCE 54.1 31.3
2 0.0 - - - - 39.6 - - -
2A 0.0 - - - - 35.6 - - -
3A 10.0 HOSE STREAM 29.2 5.0
3 10.5 - - - - 26.7 - - -
4 13.5 - - - - 23.6 - - -
5 26.5 - - - - 13.9 - - -
6 18.5 - - - - 9.9 - - -
6A 18.0 K= 4.30 9.5 13.3
7A 18.0 K= 4.30 9.1 13.0
- .,-. .-,_ .. .------ -- -----..-- - ----- - - -,'. -
- . SPRINKLER SYSTEM HYDRAtJLICANALYSIS Page 2
DATE: 12/17/2009 - -. C:\HASS74\C4211-L1.SDF -•••
JOB: TITLE: OAK AVE.LOT #1 RESIDENCE TWOJHEAD.CALC-RECROOM
PIPE DATA
PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS.
END ELEV. NOZ. PT DISC. VEL(FPS) HW(C) (FT) SUM.
NODES (FT) (K) (PSI) (GPM) FL/FT (PSI)
Pipe: 1 31.3 0.995 PL 45.00 PF 14.5
1 0.0 SRCE 54.1 (N/A) 12.9 150 FTG T2LG PE 0.0
2 0.0 0.0 39.6 0.0 0.255 TL 57.00 PV
Pipe: 2 FIXED PRESSURE LOSS DEVICE
2 0.0 0.0 39.6 0.0 4.0 psi, 31.3 gpm
2A 0.0 0.0 35.6 0.0
Pipe: 3 31.3 1.590 PL 65.00 PF 2.1
2A 0.0 0.0 35.6 0.0 5.1 150 FTG 5L PE -4.3
3A 10.0 H.S. 29.2 5.0 0.026 TL 80.00 PV
Pipe: 4 26.3 1.265 PL 5.00 PF 2.3
3A 10.0 H.S. 29.2 5.0 6.7 150 FTG 2T3LC PH -0.2
3 10.5 0.0 26.7 0.0 0.057 TL 40.00 PV
Pipe: 5 26.3 1.049 PL 3.00 PF 1.7
3 10.5 0.0 26.7 0.0 9.8 120 FTC C PE -1.3
4 13.5 0.0 23.6 0.0 0.215 TL 8.00 PV
Pipe: 6 26.3 1.101 PL 20.50 PF 4.1
4 13.5 0.0 23.6 0.0 8.9 150 FTG ET4R PH -5.6
5 26.5 0.0 13.9 0.0 0.113 TL 36.50 PV
Pipe: 7 26.3 1.101 PL 36.50 PF 7.5
5 26.5 0.0 13.9 0.0 8.9 150 FTG 3ET4R PE 3.5
6 18.5 0.0 9.9 0.0 0.113 TL 66.50 PV
Pipe: 8 13.3 1.101 PL 5.00 PF 0.6
6 18.5 0.0 9.9 00 4.5 150 FTG ETR PE 0.2
6A 18.0 4.3 9.5 13.3 0.032 TL 18.00 PV
Pipe: 9 13.0 1.101 PL 17.00 PF 1.0
6 18.5 0.0 9.9 0.0 4.4 150 FTC ET2R PE 0.2
7A 18.0 4.3 9.1 13.0 0.031 TL 31.00 PV
NOTES (HASS)
Calculations were performed by the HASS 8.0 computer program
under license no. 16080621 granted by
HRS Systems, Inc.
208 South Public Square
Petersburg, TN 37144
The system has been calculated to provide an average
imbalance at each node of 0.001 gpm and a maximum
imbalance at any node of 0.006 gpm.
- --'--.'VV-.-----
•VVV _VVVV•V VVV - V VV V VV;V_ -r'-r V V - V - '
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 3
DATE: 12/17/2009 . , - •- 6:\HSS74\C4211-Li.SDF
JOB TITLE:-MK AVE.' LOT-41-RESIDENCE A TWO HEAD -CALC-P.EC-ROOM V
Total pressure at each node is used in balancing the system.
Maximumwater velocity is 12.9 ft/sec at pipe 1.
PIPE FITTINGS TABLE
Pipe Table Name: FSS.PIP
PAGE: A MATERIAL: SCH40 HWC: 120 V
Diameter Equivalent Fitting Lengths' in Feet
(in) E T L C B G A D
Eli Tee
1.049 2.00 5.00 2.00 5.00 6.00 1.00 1.00 1.00
PACE: H MATERIAL: CPVC HWC: 150
Diameter Equivalent Fitting Lengths in Feet
(in) E T R K C L B L
Eli Tee TEEB.UN COUPLG EL45
1.101 7.00 5.00 1.00 0.00 1.00 1.00 0.00 1.00
PAGE: I MATERIAL: CPPR-L HWC: 150
Diameter Equivalent Fitting Lengths in Feet
(in) B T L C B G A D
Eli Tee
1.265 5.00 900 2.00 11.00 2.00 2.00 0.00 0.00
PAGE: J MATERIAL: S40PVC HWC: 150
Diameter Equivalent Fitting Lengths in Feet
(in) E T L C B G A D
Eli Tee V
1.590 6.00 12.00 3.00 14.00 8.00 2.00 0.00 0.00
PAGE: K MATERIAL: CPPR-K HWC: 150
Diameter Equivalent Fitting Lengths in Feet
(in)' B T L C B G A D
Eli Tee L
0.995 2.00 6.00 1.50 0.00 0.00 3.00 0.00 0.00
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Pae4
DATE: 42/17/2009 . : c:\HASS74\C4211-L1.SDF
JOB TITLE: OAK AVE. LOT-#1RES1DENCE A TWO HEAD CALC-REC ROOM
WATER SUPPLY ANALYSIS
Static: 88.00 psi Resid: 82.00 psi Flow: 500.0 gpm
100.0
LEGEND
1
11
G
A
U
G
E 60.0
2
R
E
S 400
S
U
R
E
1 Available pressure
87.96 psi @ 31.3 gpm
2 0 Required pressure
54.10 psi 8 31.3 qpnt
Source Supply Curve
System Demand Curve
20.0
p
S
1
JIM
200300 400 500 600 700 800 900 1000
FLOW (GPM)
-- - • - ;-
" -- ---
--SPRINKLER-SYSTEM HYDRAULICitANALYSIS Page 5
-.DATE -- c\nA8s74\c4211-L1 SDF
LOT #1 RESIDENCEATWQ,HEAD*CALC-REC-ROOM_
- - ---'--- ----- - _---_-- " - --
WATERSUPPLY CURVE . .. -
96+ -
- -
\\\\\\
I \\\\\\
* <-82.0 psi @ 500 gpm
80+ Flow Test Point
72+
P64+
R I
E I
S I
S 56+
U x
R
E I
48+
( I
P
S I
I 40+
) I
32+
24+
16+ LEGEND
I X = Required Water Supply "
I 54.10 psi 8 31.3 gpm
8+
0 = Available Water Supply
87.96 psi 8 31.3 gpm
+---------------+--------+ ---------+ -----------+
200 300 400 500 600 700 800 900 1000
FLOW (GPM)
-----
qT—
Bulletin l36Rev.0
Model F1 FR
n 1141bi Model F1 FR Recessed
Sprinklers
Model Fl FR Sprinkler Types
Standard Upright
Standard Pendent
Conventional
Vertical Sidewall
Horizontal Sidewall
- HSW 1 Deflector
Model Fl FR Recessed Sprinkler Types
Recessed Pendent
Recessed Horizontal Sidewall
- HSW 1 Deflector
Listings & Approvals
1 Listed by Underwriters Laboratories, Inc. (UL)
Listed by Underwriters Laboratories of Canada (ULC)
Certified by FM Approvals
Loss Prevention Council ([PC, UK)
NYC BS&A No. 587-75-SA
Meets MIL-S-901C and MIL-STD 167-1
Verband der Schadenversicherer (VdS, Germany)
NYC MEA 258-93-E
UL Listing Category
Sprinklers, Automatic & Open
Quick Response Sprinkler
Upright Pendent
Vertical Sidewall Conventional
UL Guide Number
VNIV
Patents: US Patent No. 6374,920 Applies to
Model F1 FIR Vertical Sidewall Sprinklers.
Product Description
Reliable Models F1FR and F1FR Recessed Sprinklers are
quick response sprinklers which combine the durability of a
standard sprinkler with the uir..ic;tve low profile of a decorative
sprinkler.
The Models F 1 FR and r l• Recessed automatic sprir iklcr
utilize a 3.0 mm frangible pis bulb. These sprinklers have
demonstrated response tn in laboratory tests whiCh are
five to ten times faster than st ndard response sprinklers. This
quick response enables the Jrfe F1FR and F1FR Recessed
sprinklers to apply water to .. fire much faster than standard
sprinklers of the same ternperuture rating.
The glass bulb consists of :in accurately controlled amount
of special fluid hermeticatN,' ealed inside a precisely manu-
factured glass capsule. Thrs glass bulb is specially con-
structed to provide fast thermal response. The balance of
parts are made of brass, copper and beryllium nickel.
At normal temperatures, the glass bulb contains the fluid
in both the liquid and vapor phases. The vapor phase can
be seen as a small bubble. As heat is applied, the liquid ex-
Horizontal Sidewall Recessed Pendent
HSW 1 Deflector (Model FP Shown)
pands, forcing the bubble 'aller and smaller as the liquid
pressure increases. Corny . ed heating forces the liquid to
push Out against the b ir .ausing the glass to shatter
opening the waterway an' r -i)wing the deflector to clist rib
ute the discharging watc'
Application
Quick response sprir:'c'; arc used in fixed fire proic
tion systems: Wet. Dry, Dce.ae or Preaction. Care must be
exercised that the orifice s'.' temperature rating, deflector
style and sprinkler type n accordance with the latest
published standards of InC National Fire Protection Asso
ciation or the approving Authority Having Jurisdiction
Quick response sprinklers are intended for installation as
specified in NFPA 13, FM Global Loss Prevention Data
Sheet 2-8N or other applicable standards. Quick response
sprinklers and standard response sprinklers should not be
intermixed.
The Reliable Automatic Sprinkler Co., Inc. 103 Fairview Park Drive, El msford, New York 10523
Conventional
H H
-77
I
i
r<r 01 ScU o
' /J2
J.61G0'_(
(0 lrff 10 11 & '2 (SCurC(011 I'll "Bt( foR .PPROR,,CS .0 0(fS,Off5
Model FIFR Quick Response Upright, Pendent & Conventional Sprinklers
Installation Wrench: Model D Sprinkler Wrench
IncflIitj,sri flf
Sprinkler Type
K Factor Sprinkler --
Organization
Approval Sprinkler Identification
Number (SIN) Height
US Metric
Standard-Upright (SSU) and Pendent (SSP) Deflectors Marked to Indicate Position
)7 (15mm) Standard Orifice with ,I' NPT (RJ Thread 5.6 - 80 27(56mm) 1.23.4.56,7 R3625 83615
(20mm) Large Orifice with NPT(83/4)Throad 8.0 115 2.3"(58mm) 1,2,3.4.7.8 R3622 83612
' (17mm) Small Orifice with ,i NPT (R) Thread 4.2 60 22(56mm) 128 R3623 83613
"(10mm) Small Orifice with) NPT(RY2) Thread 2.8 .40 2.2"(56mm) 1.2,8 R3621("R361
i0mm Orifice XLH with FIX" Thread 4.2 60 1 56mm 4,6,7 R3624 83614
Conventional-install in Upright or Pendent Position
10mm Orifice XLH with R% Thread 42 60 56mm R3674
15mm StandardOrifice with 'I,' NPT(RY) Thread 56 80 56mm 4,6.7 - 83675
20mm Large Orifice with~" NPT (1R3%)Thread 8.0 115 _58mm 4,7 R3672
Polyester coated upright UL and ULC listed corrosion resistant.
Upright Pendent
Model FIFR Quick Response Recessed Pendent Sprinkler
Installation Wrench: Model GFR1 Sprinkler Wrench
Installation Data:
Nominal Thread K Factor Sprinkler I Approvalt'
Orifice Size US Metric Height Organizations
r;'I5usTi) NPT (R 80 2'2'56mm) 1.22,4,518
NPT (R3/,) 8.0 115 1 23"(58mrn) 131______
NPT(R/?) 4 2 60 1 2 2' (3mtn) 20
NPT (R/2) 28 - .40 27(56mm 2.8
0mm 4.2 60 _56mrr1 47
('I Refer 0 escutcheon data table for approvals and dimensions
Sprinkler Identification
Number (SIN)
R36t5
R361 2
R36L
_R3611
R36t4
2.
Vertical Sidewall
US Patent No. 6,374,920
Model FIFR Quick Response Vertical Sidewall Sprinkler
Installation Wrench.: Model D Sprinkler Wrench
Installation Position: Upright or Pendent
Approval Type: Light Hazard Occupancy
l.e.,II..e;.
Nominal
Orifice .
Thread
Size
K Factor Sprinkler
Height
Approval
Organizations
Sprinkler
Identification
Number (SIN) us Metric
1/2 NPT(RV2) 5.6 80 2.2(56mm) 1.2,3.6,8
R3685
15mm NPT(RY2) 5.6 80 2.2(56mm) 4
(1) LPC Approval is for Pendent position only.
Orientation Deflector to Ceiling
Dimension (Mm. - Max.)
Uptight 4"- 1(102mm -305mm)
Pendent 6 - 12" (152mm -305mm)
Model FIFR Quick Response Horizontal Sidewall Sprinkler
Deflector: HSW 1
Installation Wrench: Model D Sprinkler Wrench
Installation Data:
Nominal
Orifice
Thread
Size
K Factor
Sprinkler
Length
Approval Organizations
and Type of Approval Sprinkler
Identification
Number (SIN) US Metric Light
Hazard
Ordinary
Hazard
,i (15mm) Y$' NPT(RY?) 5.6 80 23(67mm) 12.3.5.j 1.2,5.8 P3635
NOTE: UL. ULC and MEA Listing permits use with Ft or F2 recessed escutcheon
•• L:. A
;iiLuP
\;I
Horizontal Sidewall
.v OF Fill/Ni, LI - ----- —H
W-ILL DIMENSION
-H
"OLE 0/A
2 REDUCER '
- - -- --
-==
II -
I,,-, '- OLLAR Jft/111
[1,/ui .uOAINSr SPRINKLER
,IIRFNCH BOSS,
- —I - .l'J1J51M,vr
() REFER TO ESCUTHCEON DATA TABLE FOR APPROVALS AND DIMENSIONS
3.
-
.'" '-.----- - - -'----
4
I £ It £1ort—- .-..-.-- -.-- ,- .-.-...-------,--.-..----.,-----..--.--..--.------.-..--.-.-.----.-- - -S -.-..--.— -
Quick response spnnklers are int&ided for installaUon tie vacuuming Remove any.-spnnkler hich.-hasbeen
spéöified in NFPA 13, FM Global I ê'éñtión bata Sheet painted (other than factory applied) or dárnà'géd iàiy
2-8N or other applicable standards Quick response spnn- way. A stock of spare sprinklersshóüld be maintained to
kiers and standard response sprinklers shoUld not be inter- allow quick replacement of damaged or-operated sprin-
mixed. . kiers. Prior to installation, sprinklers should be maintained
The Model F1FR Recessed Quick Response Sprinklers are to in the original cartons and packaging until used tó'mini-
be installed as shown. The Model Fl or F2 Esc illus-
'
checns mize the potential for damage to sprinklers that would
trated are the only recessed escutcheons to be used with the cause improper operation or non-operation.
Model F1FR Sprinklers. The use of any other recessed esCUt()h Sprinkler Types eon will void all approvals and negate all warranties. Standard Upright WbeninstallingModelFlFRSprinkiers,usetheModelDSprin-
Icier Wrench. When installing Model F1FR Recessed Pendent or Standard Pendent
Sidewall Sprinklers, use the Model GFR1 Sprinkler Wrench. Any Conventional
other type of wrench may damage these sprinklers. Sidewall (Vertical, Horizontal HSW1)
Glass bulb sprinklers have orange bulb protectors to mihimize Recessed Pendent
bulb damage during shipping, handling and installation. Recessed Horizontal Sidewall HSW1
MOVE THIS PROTECTION AT THE TIME THE SPRINKLER
YTFMIV1 AflFflINJFRViflFFRRRFPROrFCTIONRe- Finishes .
----
rroval of the protectors before this time may leave the bulb vul-
nerable to damage. RASCO wrenches are designed to install
sprinklers when covers are in place. REMOVE PROTECTORS
BY UNDOING THE CLASP BY HAND. DO NOT USE TOOLS
TO REMOVE THE PROTECTORS.
Temperature Ratings
Classification
Sprinkler
Temperature Max. Ambient
Temp.
Bulb
Color "C
Ordinary 57 135 icxr"c Orange
Ordinary 68 iss 100°F(38"C) Red
Intermediate 79 175 150°F(66°C) Yellow
Intermediate 93 20) 150°F (66°C) Green
High W 141 286 2250F(107vC) Blue
Not available for recessed sprinklers.
Escutcheon Data
Escutcheon "A"
Model Appnvals t64usfment Dniension Face
of Ftthr
to Ceding or
'Wall Dimension
1% -
Fl 12.4,8 Max Recess (38.1mm) 5 - 6 '6
Min Recess 3<" (5nm - 24mm)
(19.1mm)
t "
F2 1.2,3,4,5.7 .8 Max Recess (38.1mm) 1" •' - .6 6
Min Recess 6 " (&nm - llrwn)
(24mm) ____________
FP 1.2 Max Recessed '< 1,iç(38.lrrm)
______ _______ (11mm) ______ Push
/6 thread-off 1,2 Min Recessed (24mm) _________
No Dimensional Figure for FP
Maintenance
The Models F1FR and F1FR Recessed Sprinklers
should be inspected quarterly and the sprinkler system
maintained in accordance with NFPA 25. Do not clean
sprinklers with soap and water, ammonia or any other
cleaning fluids. Remove dust by using a soft brush or gen-
Standard Finishes
Sprinkler Escutcheon
Bronze Brass
Chrome Plated Chrome Plated 13)
White Polyester Coated 4 White Painted
Special Application Finishes
Sprinkler Escutcheon
Bright Brass Bright Brass
Black Plated Black Plated
Black Paint Black Paint
Off White on White
Satin Chrome Satin Chrome
Itt Other finishes and colors are available on special order.
Consult the factory for details.
FM Approvals is limited to bronze and brass, chrome or black
plated finishes only.
FP Push-on/Thread-off escutcheon.
UL and ULC listed corrosion resistance.
SIN numbers: R362 t, R3622, R3623. R3625.
Note: For Y2" orifice pendent FM approved white
polyester coated and UL approved white polyester
corrosion resistant sprinklers refer to Bulletin 014.
Ordering Information
Specify.-
Sprinkler Model
Sprinkler Type
Orifice Size
Deflector Type
Temperature Rating
Sprinkler Finish
Escutcheon Type
Escutcheon Finish (where applicable)
Note: When Model F1FR Recessed sprinklers are
ordered, the sprinklers and escutcheons are packaged
separately.
The equipment presented in in,s bulletin is lobe instated in accordance with the latest pertinent Standards of the National Fire Protection Association. Factory Mutual Research
Corporation, or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable
Products manufactured and distributed by Reliable have been protecting life and property for over 80 years. and are installed and serviced by the most highly qualified and reputa-
ble sprinkler contractors located throughout the united States. Canada and foreign countries
Manufactured by
The Reliable Automatic Sprinkler Co., Inc. Recycled paw
(80C))431-1588 Sates Offices Reliabld (800)848-605 I Sales Fax Revision lines indicate updated or new data
(914)829-2042 Corporate Offices
ww.reliablesp((mlrier.ccnr Internet Address - [C P'inrcd in u.sA.3O Pft'49999970027
A Concealed Residential
Sprinkler engineered for a
minimum design density
of 0.05 gpm/ft2 with low GPM
requirements.
Features
Very low water flow requirements.
1/21 (13mm) Total adjustment;
Push-On/Thread-Off
cover attachment option.
Smooth aesthetic ceiling profile.
Available in brass, chrome and
black plated or painted finishes.
Listings & Approval
Listed by Underwriters Laboratories,
and certified by UL for Canada (cULus)
UL Listing Categories
Residential Automatic Sprinklers
UL Guide Number
VKKW
Bulletin 006 Rev:A
CD
Model RFC43 Concealed
Residential Sprinkler
(SIN RA0612)
Product Description
Model RFC43 Concealed Residential Sprinklers are fast
response residential fusible solder link automatic sprinklers.
Residential sprinklers differ from standard sprinklers primarily
in their response time and water distribution patterns.
Model RFC43 sprinklers discharge water in a
hemispherical pattern below the sprinkler deflector.
Residential distribution patterns are higher and generally
contain a finer droplet size than standard sprinkler patterns.
The combination of speed of operation and high discharge
pattern required for residential sprinklers has demonstrated,
in fire testing, an ability for controlling residential fires, and
thereby providing significant evacuation time for occupants.
The RFC43 Sprinkler provides the best form of fire
protection by combining an attractive appearance and 1/2
(13mm) of cover adjustment for ease of installation. The
small diameter cover plate is easily and positively attached
and blends into the ceiling, concealing the most dependable
fire protection available, an automatic sprinkler system.
The RFC43 is a UL Listed Residential Sprinkler to be
installed in the residential portions of any occupancy in
accordance with NFPA 13, 13R, & 13D.
The RFC43 can reduce the need for precise cutting of drop
nipples. The threaded cover plate assembly can be adjusted
without tools to fit accurately against the ceiling. The fire
protection system need not be shut down to adjust or remove
the cover plate assembly.
Application and Installation
The RFC43, for residential installations, uses a 165°F (74°C)
fusible solder link in a tuning fork style sprinkler frame with a
drop-down deflector. This assembly is recessed into the
ceiling and concealed by a flat cover plate. The cover plate is
attached to the skirt, using 135°F (57°C) ordinary temperature
classification solder. When the ceiling temperature rises, the
solder holding the cover plate releases the cover allowing the
deflector to drop into position and exposing the sprinkler
Tha PcIihIc Ajetnmntir qnrintclar (e mrs 7S F\Inrth NA 'r)iictn Iflci,r-,t \/crnrn F\IcA, Ynrk 1ncc9
inside to ceiling temperature. The subsequent operation of
the solder link opens the waterway and causes the deflector
to drop into position to distribute the discharging water in a
hemispherical pattern below the sprinkler deflector. Any
adjustment of thread engagement between the cover plate
and cup will assure that the drop-down deflector is properly
located below the ceiling. The residential distribution pattern
contains a finer droplet size than a standard sprinkler, and the
pattern produces significantly higher wall wetting.
After a 2 58 inch diameter hole is cut in the ceiling, the
sprinkler is to be installed with the Model FC Wrench. When
installing a sprinkler, the wrench is first positioned into the
sprinkler/cup assembly and around the hexagonal body of
the sprinkler frame. The Wrench must bottom out against the
cup in order to ensure proper, safe installation. The sprinkler
is then tightened into the pipe fitting. When inserting or
removing the wrench from the sprinkler/cup assembly, care
should be taken to prevent damage to the sprinkler. DO NOT
WRENCH ON ANY OTHER PART OF THE SPRINKLER/CUP
ASSEMBLY. MODEL RFC43 CONCEALED SPRINKLERS
MUST BE INSTALLED ONLY WITH 135°F RATED COVERS.
Cover assemblies provide up to )" (13mm) of adjustment
Turn the cover clockwise until the flange is in contact with the
ceiling. The optional push-on cover plate may require a final
adjusting turn to contact the ceiling. Cover removal requires
turning in the counter-clockwise direction.
In ceilings that have a plenum space above the sprinkler,
the plenum space may have neutral or negative
pressurization but must not be positively pressurized. Inspect
all sprinklers after installation to ensure that the gap between
the cover plate and ceiling and the 4 slots in the cup are all
open and free from any air flow impediment
Temperature Rating
Sprinkler Cover Plate
I
I I
Max. Ambient
I Temp. I I
165°F/74°C 135°F/57°C I 100°F/38°C
Installation Data
1 Minimum Required
Thread Size K Sprinkler Maximum Minimum Sprinkler Discharge
h' Factor Spacing Distance Distance between inc m, ft. (m) to Wall ft. (m) sprinkler ft. (m) Flow Press.
qpm (Lpm)1 psi (bar)
½" (15mm) 4.3 112 x 12 (3.6x3.6) 6 (1.83) 8(2 43) 12(45) 78(0 54)
1/2" (15mm) 4.3 14 x 14 (4.3x4.3) 7(2.13) 8(2.43) 13(49) 9.1 (0.63)
1/2" (15mm) 4.3 16 x 16 (4.9x4.9) 8(2.43) 8(2.43) 13(49) 1 9.1(0.63)
Y2" (15mm) 4.3 18 x 18 (5,56.5) 9(2.74) 8(2,43) 18(68) 17.5(1.21)
15mpj 4.3 2Ox2O(6.0x6.9J9j95L 8(2.43) j 21 (79) ._L2!6
Note: 1 bar = 100 Kpa
Model RFC 43 Pendent Flat Concealed installed below Sloped Ceiling.
Technical Data.----
Thread Sprinkler CoverplateJ Max.
Size Temp. Rating TernRating p. I Pressure
.L(XLL 165j4) ... .
Max. Actual Max Sprinkler
Ambient Temp. K Factor A men Identification i
-(metric) -
Number (SIN.)
_100 ) L .i012......
Table 3-Appr_
Max. Slope of 6/,2 (33.7) Pitch Max. Slope of 2 (18.4° - -- Pitch
Pressure Max. Sprinkler Spacing Along Slope Mm. Flow Per Sprinkler Head Pressure Mm. Flow Per Sprinkler Head
(W) Width x ( L) Length ft (m)
12 x 12(3) _1(I_........17.5(1,21) - i39)
17.5(1,21) l349) 14 x 14(4,3
3(49) 16x16(4.9x4, 17.5(1,21)
18x18 (5,5x5,5) - _________ 21(79) 23.8 1, 64
20 x 20(6.1 6.1) ________
21(79) 23.8 1.
2.
Maintenance
Model RFC43 Concealed Sprinklers should be inspected
quarterly and the sprinkler system maintained in accordance
With NFPA 25. Do not clean sprinklers with soap and water,
ammonia or any other cleaning fluids. Remove dust by using
a soft brush or gentle vacuuming. Remove any sprinkler
cover plate assembly which has been painted (other than
factory applied) or damaged in any way. A stock of spare
sprinklers should be maintained to allow quick replacement of
damaged or operated sprinklers. Prior to installation,
sprinklers should be maintained in the original cartons and
packaging until used to minimize the potential for damage to
sprinklers that would cause improper operation or
non-operation.
135°F (570C). Cover plate assembly shall consist of a brass
cover plate and copper alloy retainer flange having a
[thread-on] [push-on] and thread-off design, allowing a 1/2
cover plate adjustment Any secure engagement between
the cover plate and the cup will assure that the drop-down
deflector is properly located below the ceiling. A plastic
protective cap shall be provided and factory installed inside
the sprinkler cup to protect the drop-down sprinkler deflector
from damage, which could occur during construction before
the cover plate is installed. Standard cover finish: [Chrome]
[White] [Specialty-specify]. Residential concealed sprinklers
shall be Reliable Model RFC43, SIN RA0612 (Bulletin 006).
Model RFC43 Residential Concealed
Sprinkler Specification
Sprinklers shall be cULus Listed low flow residential
concealed sprinklers with drop-down deflector and
adjustable flat cover plate engineered for a minimum design
density of 0.05 gprrvt2. Sprinkler frame and deflector shall be
of bronze frame construction having a 1/2" NPT thread.
Thermal element shall consist of an approved black-painted
beryllium-nickel fusible solder link with symmetric lever
mechanism, maintaining a Teflon-coated Belleville spring
washer and machined brass cap water seal assembly
containing no plastic parts. Sprinkler K-factor shall be nominal
4.3 (62.4), having a 7/16" orifice. Temperature rating shall be
Ordinary 165°F (740C); cover plate temperature rating to be
Ordering Information
Specify:
Sprinkler Model
Cover Plate Finish
Thread-On or
Push-On cover
Cover Plate Finishes 01
Standard Finishes
Chrome
White
Special Application
Finishes
Bright Brass
Black Plating
Black Paint
Off White
Satin Chrome
"Other colors and finishes
available. Consult factory
for details.
Note: Paint or any other
coatings applied over the
factory finish will void all
approvals and warranties
r -
112 ' REDUCING
TEE OR ELBOW
LI [6. 7mm] 0/A.
ZJ - [58.7mm] 0/A - -1 HOLE IN CEILING
CUP .
2 [50.8mm] 1p14X.
FACE OF FirTING ro FACE OF CEILING
DIMENSION
CEILING
[12.7mm] MAX. I
COVER ADJUSTMENT 5116'
4.8mm 1 COVER PLATE
A
(84./ mm]
SSEMSLY SPRINKLER
COVER PLA TE: 1/2" [12.7mm 1 ADJusTMENT
3.