HomeMy WebLinkAbout2230 NOB HILL DR; ; AS090080; Permit7/19/22, 2:32 PM AS090080 Permit Data
City of Carlsbad
Sprinkler Permit
Permit No: AS090080
Job Address: 2230. NOB HILL DR
Permit Type: SPRINK
Parcel No: 1671122700
Lot #: 0
Status: ISSUED
Applied 7/16/2009
Approved: 7/16/2009
Reference No.: Issued: 7/16/2009
PC #: Inspector:
Project Title: JOHNSON RESIDENCE T.I. FIRE SPRINKLER PLAN CHECK &
INSPECTIONS
Applicant:
WEST COAST FIRE PROTECTION
271 ROYMAR RD
SUITE F
OCEANSIDE, CA
(760)754-8472
Owner:
JOHNSON FAMILY TRUST 08-20-08
2230 NOB HILL DR
CARLSBAD CA
Fees ($) Add'I Fees ($) Total ($) Balance ($)
130 0 130 0
about:blank 1/1
Asoiooso
WEST COAST FIRE PROTECTION
271 ROYMAR ROAD SUITE F
OCEANSIDE,CA 92054
HYDRAULIC CALCULATIONS
FOR
Johnson Guesthouse
2230 Nob Hill Carlsbad CA
FILE NUMBER:
DATE: JUL 14, 2009
-DESIGN DATA-
OCCUPANCY CLASSIFICATION: RESIDENTIAL
DENSITY: N/A gpm/sq. ft.
AREA OF APPLICATION: Bed Room W/ flat ceiling
COVERAGE PER SPRINKLER: 16x16 sq. ft.
NUMBER OF SPRINKLERS CALCULATED: 1 sprinklers
TOTAL SPRINKLER WATER FLOW REQUIRED: 18.0 gpm
TOTAL WATER REQUIRED (including hose) : 23.0 gpm
FLOW AND PRESSURE (@ BOR) : 18 gpm @ 29.1 psi
SPRINKLER ORIFICE SIZE: 1/2 inch
NAME OF CONTRACTOR: WEST COAST FIRE PROTECTION
DESIGN/LAYOUT BY: DAN AMATO
AUTHORITY HAVING JURISDICTION: Carlsbad Fire Department
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 2
DATE: 7/14/2009 C:\HASS78\JOHNSONRES.SDF
JOB TITLE: JOHNSON RESIDENCE
WATER SUPPLY DATA
SOURCE STATIC RESID. FLOW AVAIL. TOTAL REQ'D
NODE PRESS. PRESS. @ PRESS. @ DEMAND PRESS.
TAG (PSI) (PSI) (GPM) (PSI) (GPM) (PSI)
SRCE 70.0 65.0 100.0 69.7 23.0 40.5
AGGREGATE FLOW ANALYSIS:
TOTAL FLOW AT SOURCE 23.0 GPM
TOTAL HOSE STREAM ALLOWANCE AT SOURCE 5.0 GPM
OTHER HOSE STREAM ALLOWANCES 0.0 GPM
TOTAL DISCHARGE FROM ACTIVE SPRINKLERS 18.0 GPM
NODE ANALYSIS DATA
NODE TAG ELEVATION NODE TYPE PRESSURE DISCHARGE
(FT) (PSI) (GPM)
1 15.0 K= 4.20 18.4 18.0
TOR 8.0 - - - - 24.6 - - -
BOR 0.5 - - - - 29.1 - - -
Ui -2.0 - - - - 31.4 - - -
Mi 8.0 - - - - 28.3 - - -
M2 8.0 - - - - 39.3 - - -
SRCE 8.0 SOURCE 40.5 18.0
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 3
DATE: 7/14/2009 C:\HASS78\JOHNSONRES.SDF
JOB TITLE: JOHNSON RESIDENCE
PIPE DATA
PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS.
END ELEV. NOZ. PT DISC. VEL(FPS) HW(C) (FT) SUM.
NODES (FT) (K) (PSI) (GPM) FL/FT (PSI)
Pipe: 1 -18.0 1.101 PL 23.00 PF 3.2
1 15.0 4.2 18.4 18.0 6.1 150 FTG 35.0 PE 3.0
TOR 8.0 0.0 24.6 0.0 0.056 TL 58.00 PV
Pipe: 2 -18.0 1.101 PL 11.58 PF 1.2
TOR 8.0 0.0 24.6 0.0 6.1 150 FTG 10.0 PE 3.2
BOR 0.5 0.0 29.1 0.0 0.056 TL 21.58 PV
Pipe: 3 -18.0 1.030 PL 5.00 PF 1.2
BOR 0.5 0.0 29.1 0.0 6.9 150 FTG 10.0 PE 1.1
Ui -2.0 0.0 31.4 0.0 0.077 TL 15.00 PV
Pipe: 4 -18.0 1.590 PL 130.00 PF 1.2
Ui -2.0 0.0 31.4 0.0 2.9 150 FTG 3.0 PE -4.3
Ml 8.0 0.0 28.3 0.0 0.009 TL 133.00 PV
Pipe: 5 FIXED PRESSURE LOSS DEVICE
M2 8.0 0.0 39.3 0.0 11.0 psi, 18.0 gpm
Ml 8.0 0.0 28.3 0.0
Pipe: 6 -18.0 1.025 PL 15.00 PF 1.2
M2 8.0 0.0 39.3 0.0 7.0 150 FTG ---- PE 0.0
SRCE 8.0 SRCE 40.5 (N/A) 0.079 TL 15.00 PV
NOTES (HASS)
Calculations were performed by the HASS 7.9 computer program
under license no. 27081246 granted by
HRS Systems, Inc.
4792 LaVista Road
Tucker, GA 30084
The system has been calculated to provide an average
imbalance at each node of 0.013 gpm and a maximum
imbalance at any node of 0.078 gpm.
Total pressure at each node is used in balancing the system.
Maximum water velocity is 7.0 ft/sec at pipe 6.
PIPE FITTINGS TABLE
Pipe Table Name: STANDARD.PIP
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 4
DATE: 7/14/2009 C:\HASS78\JOHNSONRES.SDF
JOB TITLE: JOHNSON RESIDENCE
PAGE: * MATERIAL: S40 HWC: 120
Diameter Equivalent Fitting Lengths in Feet
(in) E T L C B G A D N
Eli Tee LngEii ChkVlv BfyVlv GatVlv AimChk DPVlv NPTee
1.025 1.79 4.47 1.79 4.47 5.36 0.89 8.93 8.93 4.47
1.030 1.83 4.57 1.83 4.57 5.49 0.91 9.15 9.15 4.57
1.101 2.53 6.33 2.53 6.33 7.59 1.27 12.66 12.66 6.33
1.590 3.76 7.53 1.88 8.47 5.65 0.94 9.41 9.41 7.53
C C C
Alf
0
C
0 0
c)
0 0
C"
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 5 DATE: 7/14/2009 C:\HASS78\JOHNSONRES.SDF JOB TITLE: JOHNSON RESIDENCE
-1 ('1 '-'
r
C C C 0 C C 0 0 0
0 0 0 C 0 0 0 0 0 I C N k.0 Li_I C) C'J
—QU)d--
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 6
DATE: 7/14/2009 C:\HASS78\JOHNSONRES.SDF
JOB TITLE: JOHNSON RESIDENCE
WATER SUPPLY CURVE
72+
*
0
\
66\
1* <-65.0 psi @ 100 gpm
Flow Test Point
60+
54+
P 48+
R I
E I
S I
S 42+
U X
R I
E
36+
( I
P I
S I
I 30+
) I
24+
18+
12+ LEGEND
I X = Required Water Supply
40.45 psi @ 23.0 gpm
6+
I 0 = Available Water Supply
69.67 psi @ 23.0 gpm
'V
0++-+---+----+-----+ ------+--------+--------+---------+-----------+
200 300 400 500 600 700 800 900 1000
FLOW (GPM)
A 60 ~Dc) go
tqC102 /Fire & Building
I Products
Technical Services: Tel: (800) 381-9312 I Fax: (800) 791-5500
,a
rapid response
HOME FIRE SPRINKLER SYSTEM
Series LFII Residential
Concealed Pendent Sprinklers, Flat Plate
4.2 K-factor
General
Description
The Series LFII (TY2596) Residential
Concealed Pendent Sprinklers are
decorative, fast response, fusible sol-
der sprinklers designed for use in resi-
dential occupancies such as homes,
apartments, dormitories, and hotels.
The cover plate assembly conceals
the sprinkler operating components
above the ceiling. The flat profile of the
cover plate provides the optimum aes-
thetically appealing sprinkler design.
In addition, the concealed design of
the Series LFII (TY2596) provides 1/2
inch (12,7 mm) vertical adjustment.
This adjustment reduces the accuracy
to which the fixed pipe drops to the
sprinklers must be cut to help assure
a perfect fit installation.
The Series LFII are to be used in wet
pipe residential sprinkler systems for
one- and two-family dwellings and mo-
bile homes per NFPA 13D; wet pipe
residential sprinkler systems for resi-
dential occupancies up to and includ-
ing four stories in height per NFPA
13R; or, wet pipe sprinkler systems for
the residential portions of any occu-
pancy per NFPA 13.
The Series LFII (TY2596) has a 4.2
(60,5) K-factor that provides the re-
quired residential flow rates at reduced
IMPORTANT
Always refer to Technical Data
Sheet TFP 700 for the "INSTALLER
WARNING that provides cautions
with respect to handling and instal-
lation of sprinkler systems and com-
ponents. Improper handling and in-
stallation can permanently damage
a sprinkler system or its compo-
nents and cause the sprinkler to fail
to operate in afire situation or cause
it to operate prematurely.
Page 1 of 4
pressures, enabling smaller pipe sizes
and water supply requirements.
The Series LFII (TY2596) has been
designed with heat sensitivity and
water distribution characteristics
proven to help in the control of residen-
tial fires and to improve the chance for
occupants to escape or be evacuated.
The Series LFII (1Y2596) Residential
Concealed Pendent Sprinklers are
shipped with a Disposable Protective
Cap. The Protective Cap is temporarily
removed for installation, and then it
can be replaced to help protect the
sprinkler while the ceiling is being in-
stalled or finished. The tip of the Pro-
tective Cap can also be used to mark
the center of the ceiling hole into plas-
ter board, ceiling tiles, etc. by gently
pushing the ceiling product against the
Protective Cap. When the ceiling in-
stallation is complete the Protective
Cap is removed and the Cover Plate
Assembly installed.
WARNINGS
The Series LFII (TY2596) Residential
Concealed Pendent Sprinklers de-
scribed herein must be installed and
maintained in compliance with this
document, as well as with the applica-
ble standards of the National Fire Pro-
tection Association, in addition to the
standards of any other authorities hav-
ing jurisdiction. Failure to do so may
impair the performance of these de-
vices.
The owner is responsible for maintain-
ing their fire protection system and de-
vices in proper operating condition.
The installing contractor or sprinkler
manufacturer should be contacted
with any questions.
SprinklerNodel
Identification
Number
SIN 1Y2596
JANUARY, 2006
Technical
Data
Approvals:
UL and C-UL Listed. NYC Approved
under MEA 44-03-E.
Maximum Working Pressure:
175 psi (12,1 bar)
Discharge Coefficient:
K = 4.2 GPM/psill2 (60,5 LPM/bar112)
Temperature Rating:
160°F/71°C Sprinkler with
135°F/57°C Cover Plate
Vertical Adjustment:
1/2 inch (12,7 mm)
Finishes:
Cover Plate:
Flat White, Bright White, Chrome, or
Custom
Physical Characteristics:
Body ..............Brass
Cap ..............Bronze
Saddle .............Brass
Sealing Assembly ..........
Beryllium Nickel w/ Teflont
Soldered Link Halves .....Nickel
Lever .............Bronze
Compression Screw ......Brass
Deflector ...........Copper
TFP44O
F-
Page 2 of 4 TFP44O
Minimum Flow (i)) and Minimum Flow (b) and Minimum Flow ("I and
Maximum Maximum Residual Pressure Residual Pressure Residual Pressure
Coverage Spacing For Horizontal Ceiling For Sloped Ceiling For Sloped Ceiling
Area (a) Ft. (Max. 2 Inch Rise (Greater Than 2 Inch (Greater Than 4 Inch
Ft. x Ft. (m) for 12 Inch Run) Rise Up To Rise Up To
(m x m) Max. 4 Inch Rise
for 12 Inch Run)
Max. 8 Inch Rise
for 12 Inch Run)
160'FI7I°C 160°F171°C 160°F171°C
Sprinkler Sprinkler Sprinkler
12x12 12 13 GPM (49,2LPM) I8 GPM (68,1LPM) 1S GPM (68,1LPM)
(3,7 x 3,7) (3,7) 9.6 psi (0,66 bar) 18.4 psi (1,27 bar) 18.4 psi (1,27 bar)
14x 14 14 14 GPM (53,0 LPM) 18 GPM (68,1 LPM) 18 GPM (68,1 LPM)
(4,3 x 4,3) (4,3) 11.1 psi (0,77 bar) 18.4 psi (1,27 bar) 18.4 psi (1,27 bar)
16x 16 16 16 GPM (60,6 LPM) 18 GPM (68,1 LPM) 18 GPM (68,1 LPM)
(4,9 x4,9) (4,9) 14.5 psi (1,00 bar) 18.4 psi (1,27 bar) 18.4 psi (1,27 bar)
18x 18 18 20 GPM (75,7 LPM) 20 GPM (75,7 LPM) N/A
(5,5 x 5,5) (5.5) 22.7 psi (1,57 bar) 22.7 psi (1.57 bar)
20 x 20 20 24 GPM (90,8 LPM) 26 GPM (98,4 LPM) N/A
(6,1 x 6,1) (6,1) 327 psi (2,25 bar) 1 38.3 psi (2,64 bar)
For coverage area dimensions less than or between those indicated, it is necessary to use the minimum required flow for the
next highest coverage area for which hydraulic design criteria are stated.
Requirement is based on minimum flow in GPM (LPM) from each sprinkler. The associated residual pressures are calculated
using the nominal K-factor. Refer to Hydraulic Design Criteria Section for details.
TABLE A
NFPA 13D AND NFPA 13R WET PIPE HYDRAULIC DESIGN CRITERIA
FOR THE SERIES LFII (TY2596) RESIDENTIAL CONCEALED PENDENT SPRINKLER
Guide Pin Housing ......Bronze
Guide Pins ......Stainless Steel
Support Cup ..........Steel
Cover Plate ..........Copper
Retainer ............Brass
Cover Plate Ejection Spring .....
...Stainless Steel
tDuPont Registered Trademark
Operation
When exposed to heat from a fire, the
Cover Plate, which is normally sol-
dered to the Support Cup at three
points, falls away to expose the Sprin-
kler Assembly. At this point the Deflec-
tor supported by the Arms drops down
to its operated position. The fusible
link of the Sprinkler Assembly is com-
prised of two link halves that are sol-
dered together with a thin layer of sol-
der. When the rated temperature is
reached, the solder melts and the two
link halves separate allowing the sprin-
kler to activate and flow water.
Design
Criteria
The Series IFIl (TY2596) Residential
Concealed Pendent Sprinklers are UL
and C-UL Listed for installation in ac-
cordance with the following criteria.
NOTE
When conditions exist that are outside
the scope of the provided criteria, refer
to the Residential Sprinkler Design
Guide TFP490 for the manufacturer's
recommendations that may be accept-
able to the Authority Having Jurisdic-
tion.
System Type. Only wet pipe systems
may be utilized.
Hydraulic Design. The minimum re-
quired sprinkler flow rate for systems
designed to NFPA 13D or NFPA 13R
are given in Table A as a function of
temperature rating and the maximum
allowable coverage areas. The sprin-
kler flow rate is the minimum required
discharge from each of the total
number of "design sprinklers' as
specified in NFPA 130 or NFPA 13R.
For systems designed to NFPA 13, the
number of design sprinklers is to be
the four most hydraulically demanding
sprinklers. The minimum required dis-
charge from each of the four sprinklers
is to be the greater of the following:
The flow rates given in Table A for
NFPA 130 and 13R as a function of
temperature rating and the maxi-
mum allowable coverage area.
A minimum discharge of 0.1 gpm/sq.
ft. over the "design area" comprised
of the four most hydraulically de-
manding sprinklers for the actual
coverage areas being protected by
the four sprinklers.
Obstruction To Water Distribution.
Locations of sprinklers are to be in
accordance with the obstruction rules
of NFPA 13 for residential sprinklers.
Operational Sensitivity. The sprin-
klers are to be installed relative to the
ceiling mounting surface as shown in
Figure 3.
Sprinkler Spacing. The minimum
spacing between sprinklers is 8 feet
(2,4 m). The maximum spacing be-
tween sprinklers cannot exceed the
length of the coverage area (Ref. Ta-
ble A) being hydraulically calculated
(e.g., maximum 12 feet for a 12 ft. x
12 ft. coverage area, or 20 feet for a 20
ft. x 20 ft. coverage area).
installation
The Series LFll (TY2596) must be in-
stalled in accordance with the follow-
ing instructions:
NOTES
Damage to the fusible Link Assembly
during installation can be avoided by
handling the sprinkler by the frame
arms only (i.e., do not apply pressure
to the fusible link Assembly).
A leak tight 1/2 inch NPTsprinklerjoint
should be obtained with a torque of 7
to 14 ft.lbs. (9,5 to 19,0 Nm). A maxi-
.-J
TFP44O
BODY
(1/2" NPT) -
CAP
SADDLE
SUPPORT
CUP WITH
ROLL FORMED
THREADS
GUIDE
PIN
GUIDE PIN
HOUSING
DEFLECTOR -
THREAD INTO
SUPPORT CUP
UNTIL MOUNTING
SURFACE IS
FLUSH WITH
CEILING
SOLDER
TAB
SEALING
ASSEMBLY
SPRINKLER
WRENCHING
AREA
COMPRESSION
SCREW
LEVER
SOLDER LINK
ELEMENT
I' 'I I II I II I
DEFLECTOR
(OPERATED I
I POSITION) I
I SPRINKLER!SIJPPORT CUP
ASSEMBLY
I
I
I
I I
I RETAINER
H WITH THREAD H H - DIMPLES
EJECTION
SPRING
COVER PLATEIRETAINER
ASSEMBLY COVER
PLATE
FIGURE 1
SERIES LFII (TY2596) RESIDENTIAL
CONCEALED PENDENT SPRINKLER
Page 3 of 4
mum of 21 ft.lbs. (28,5 Nm) of torque
is to be used to install sprinklers.
Higher levels of torque may distort the
sprinkler inlet with consequent leak-
age or impairment of the sprinkler.
Do not attempt to compensate for in-
sufficient adjustment in an Escutcheon
Plate by under- or over-tightening the
Sprinkler. Readjust the position of the
sprinkler fitting to suit.
Step 1. The sprinkler must only be
installed in the pendent position and
with the centerline of the sprinkler per-
pendicular to the mounting surface.
Step 2. Remove the Protective Cap.
Step 3. With pipe thread sealant ap-
plied to the pipe threads, and using
the W-Type 18 Wrench shown in Fig-
ure 2, install and tighten the Sprink-
ler/Support Cup Assembly into the fit-
ting. The W-Type 18 Wrench will
accept a 112 inch ratchet drive.
WRENCH
RECESS
PUSH WRENCH
IN TO ENSURE
ENGAGEMENT
WITH SPRINKLER
WRENCHING AREA
FIGURE 2
W-TYPE 18
SPRINKLER WRENCH
2-1/2" DIA. SPRINKLER-
(63,5
ASSEMBLY 112" THREADED SPRINKLER
(63,5 mm 1/2" (12,7 mm) FACE OF
_/OPERAThD
___
NPT ADJUSTMENT FITTING
___ 7' SPRINKLER _____________
PLATE
- (49,2 mm RETAINER 1/8 GAP ±6,4 mm)
1-15/16"±114" COVER
1/2" (12,7 mm) I COVER- SPRINKLER- I RETAINER SUPPORT CUP •
MOUNTING
3/16 SURFACE
IDISPOSABLE
ASSEMBLY ASSEMBLY (4,8 mm)
,
V(254 mm)
3-3/16"DIA. DEFLECTOR IN
(81,0 mm) TIP PROTECTIVE CAP OPERATED POSITION
FIGURE 3
SERIES LFII (TY2596) RESIDENTIAL CONCEALED PENDENT SPRINKLER
INSTALLATION DIMENSIONS I PROTECTIVE CAP /ACTIVATED DEFLECTOR
Page 4 of 4 TFP440
Step 4. Replace the Protective Cap by
pushing it upwards until it bottoms out
against the Support Cup. The Protec-
tive Cap helps prevent damage to the
Deflector and Arms during ceiling in-
stallation and/or during application of
the finish coating of the ceiling. It may
also be used to locate the center of the
clearance hole by gently pushing the
ceiling material against the center
point of the Cap.
NOTE
As long as the protective Cap remains
in place, the system is considered to
be "Out Of Service".
Step 5. After the ceiling has been com-
pleted with the 2-1/2 inch (63 mm)
diameter clearance hole and in prepa-
ration for installing the Cover Plate As-
sembly, remove and discard the Pro-
tective Cap, and verify that the
Deflector moves up and down freely.
If the Sprinkler has been damaged and
the Deflector does not move up and
down freely, replace the entire Sprin-
kler assembly. Do not attempt to mod-
ify or repair a damaged sprinkler.
Step 6. Screw on the Cover Plate As-
sembly until its flange comes in con-
tact with the ceiling.
Do not continue to screw on the Cover
Plate Assembly such that it lifts a ceil-
ing panel out of its normal position.
If the Cover Plate Assembly cannot be
engaged with the Mounting Cup or the
Cover Plate Assembly cannot be en-
gaged sufficiently to contact the ceil-
ing, the Sprinkler Fitting must be repo-
sitioned.
Care and
Maintenance
The Series LFII (TY2596) must be
maintained and serviced in accord-
ance with the following instructions:
NOTES
Absence of an Escutcheon Plate may
delay the sprinkler operation in a fire
situation.
Before closing a fire protection system
main control valve for maintenance
work on the fire protection system
which it controls, permission to shut
down the affected fire protection sys-
tem must be obtained from the proper
authorities and all personnel who may
be affected by this action must be no-
tified.
Sprinklers which are found to be leak-
ing or exhibiting visible signs of corro-
sion must be replaced.
Automatic sprinklers must never be
painted, plated, coated, or otherwise
altered after leaving the factory. Modi-
fied or over heated sprinklers must be
replaced.
Care must be exercised to avoid dam-
age - before, during, and after instal-
lation. Sprinklers damaged by drop-
ping, striking, wrench twist/slippage,
or the like, must be replaced.
The owner is responsible for the in-
spection, testing, and maintenance of
their fire protection system and de-
vices in compliance with this docu-
ment, as well as with the applicable
standards of the National Fire Protec-
tion Association (e.g., NFPA 25), in
addition to the standards of any other
authorities having jurisdiction. The in-
stalling contractor or sprinkler manu-
facturer should be contacted relative
to any questions.
NOTE
The owner must assure that the sprin-
kiers are not used for hanging of any
objects and that the sprinklers are only
cleaned by means of gently dusting
with a feather duster; otherwise, non-
operation in the event of a fire or inad-
vertent operation may result.
It is recommended that automatic
sprinkler systems be inspected,
tested, and maintained by a qualified
Inspection Service in accordance with
local requirements and/or national
codes.
Limited
Warranty
Products manufactured by Tyco Fire &
Building Products (TFBP) are war-
ranted solely to the original Buyer for
ten (10) years against defects in mate-
rial and workmanship when paid for
and properly installed and maintained
under normal use and service. This
warranty will expire ten (10) years
from date of shipment by TFBP. No
warranty is given for products or com-
ponents manufactured by companies
not affiliated by ownership with TFBP
or for products and components which
have been subject to misuse, improper
installation, corrosion, or which have
not been installed, maintained, modi-
fied or repaired in accordance with ap-
plicable Standards of the National Fire
Protection Association, and/or the
standards of any other Authorities
Having Jurisdiction. Materials found
by TFBP to be defective shall be either
repaired or replaced, at TFBP's sole
option. TFBP neither assumes, nor
authorizes any person to assume for it,
any other obligation in connection with
the sale of products or parts of prod-
ucts. TFBP shall not be responsible for
sprinkler system design errors or inac-
curate or incomplete information sup-
plied by Buyer or Buyers repre-
sentatives.
In no event shall TFBP be liable, in
contract, tort, strict liability or under
any other legal theory, for incidental,
indirect, special or consequential dam-
ages, including but not limited to labor
charges, regardless of whether TFBP
was informed about the possibility of
such damages, and in no event shall
TFBP's liability exceed an amount
equal to the sales price.
of merchantability and fitness for a
This limited warranty sets forth the ex-
clusive remedy for claims based on
failure of or defect in products, materi-
als or components, whether the claim
is made in contract, tort, strict liability
or any other legal theory.
This warranty will apply to the full ex-
tent permitted bylaw. The invalidity, in
whole or part, of any portion of this
warranty will not affect the remainder.
Ordering
Procedure
When placing an order, indicate the
full product name. Contact your local
distributor for availability..
Sprinkler Assembly:
Series LFII (1Y2596), K4.2, Residen-
tial Concealed Pendent Sprinkler with-
out Cover Plate Assembly,
P/N 51-122-1-160.
Cover Plate Assembly:
Cover Plate Assembly having a (spec-
ify) finish for the Series LFII (1Y2596),
K4.2, Residential Concealed Pen-
dent Sprinkler, P/N (specify).
Chrome ..................PIN 56-122-9-135
Off White.................PIN 56-122-0-135
Bright White ............... P/N 56-122-4-135
Flat White ................PIN 56-122-5-135
White (RALSO1O) ........... P/N 56-122-3-135
Custom ..................PIN 56-122-X-135
*Eastern Hemisphere sales only.
Sprinkler Wrench:
Specify: W-Type 18 Sprinkler Wrench,
P/N 56-000-1-265.
TYCO FIRE & BUILDING PRODUCTS, 451 North Cannon Avenue, Lansdale, Pennsylvania 19446
many angles, reducing
assembly effort. This sprin-
kler is available in various
temperature ratings (see
chart on page 2) and fin-
ishes to meet many design
requirements.
The recessed pendent
should be utilized with a
Model V27 recessed
escutcheon which pro-
vides up to V4" (19 mm) of
adjustments.
Sprinkler Operation
The operating mechanism
is a frangible glass bulb
which contains a heat
responsive liquid. During a
fire, the ambient tempera-
ture rises causing the liquid
in the bulb to expand.
When the ambient temper-
ature reaches the rated
temperature of the sprin-
kler, the bulb shatters. As a
result, the waterway is
cleared of all sealing parts
and water is discharged
towards the deflector. The
deflector is designed to dis-
tribute the water in a pat-
tern that is most effective
in controlling the fire.
Coverage
For coverage area and
sprinkler placement, refer
to NFPA 13 standards.
4tE1UlIC
-I
AUTOMATIC SPRINKLERS
FIRE PROTECTION PROUTS
V27, K5.6
Models V2703, V2704, V2707 and V2708
Standard Spray
Upright, Pendent and Recessed Pendent
Standard and Quick Response
PRODUCT DESCRIPTION
These Model V27 standard
spray sprinklers are
designed to produce a
hemispherical spray pat-
tern for standard commer-
- cial applications. They are
707 available with either stan-
Recessed dard or quick response
Pendent bulbs. The design incorpo-
<> (fl () () rates state-of-the-art, heat
responsive, frangible glass
See vitc bulb design (standard or
publication 1001
V2707 details. quick response) for prompt,
V2708 precise operation.
The die cast frame is more
streamlined and attractive
hex
)J
than traditional sand cast
Pendent
v27T frames. It is cast with a
V2704
-shaped wrench boss to
(j allow easy tightening from
Upright
F-
TECHNICAL SPECIFICATIONS
Models: V2703, V2704, V2707
V2708
Style: Pendent, Upright or
Recessed Pendent
Nominal Orifice Size:
½' (13 mm)
K-Factor: 5.6 Imp. (8,1 SI.")
Nominal Thread Size:
½' NPT (15 mm)
Max. Working Pressure:
175 psi (1200 kPa)
Factory Hydrostatic Test:
100% @ 500 psi (3450 kPa)
Mn. Operating Pressure:
7 psi (48kPa)
Temperature Rating: See
chart on page 2.
MATERIAL
SPECIFICATIONS
Upright Deflector:
Bronze per UNS C22000
Pendent Deflector:
Bronze per UNS C51000
Bulb: Glass with glycerin solu-
tion.
Bulb Nominal Diameter:
U Standard: 5,0 mm
U Quick Response: 3,0 mm
Load Screw: Bronze per UNS
C65100
Pip Cap: Bronze per UNS
C65100
Spring: Beryllium nickel
Seal: Teflon* tape
Frame: Die cast brass 65-30
Lodgement Spring:
Stainless steel per UNS S30200
ACCESSORIES
Installation Wrench:
U Open End: V27
U Recessed: V38, V38-3
U Socket: V27
Finishes:
U Plain brass
U Chrome plated
U White painted**
U Custom painted**
0 Lead**
155, 200, 286SR Only -
Q Wax**
U Wax over lead**
For cabinets and other accesso-
ries refer to separate sheet.
NOTE: Weather resistant recessed
escutcheons available upon request.
For K-Factor when pressure is mea-
sured in Bar, multiply SA. units by
10.0.
Teflon is a registered trademark of
Dupont Co.
UL Listed for corrosion resistance in
all configurations.
VICTAULIC® IS AN ISO 9001 CERTIFIED COMPANY
Victaulic Company of America Victaulic Company of Canada Victaulic Europe Victaulic America Latina Victaulic Asia Pacific
Phone: 1-800-PICK-VIC (1-800-742-5842) Phone: 905-884-7444 Phone: 32-9-381-1500 Phone: 610-559-3300 Phone: 65-6235-3035
Fax: 610-250-8817 Fax: 905-884-9774 Fax: 32-9-380-4438 Fax: 610-559-3608 Fax: 65-6235-0535
e-mail:pickvic@victaulic.com e-mail: viccanada@victaulic.com e-mail: viceuro@victaulic.be e-mail: eical@victaulic.com e-mail: vicap@victaulic.com
2544 Rev.O 8/03 5 Registered Trademark of Victaulic 0 Copyright 2003 Victaulic Printed in U.S.A.
APPROVALSILISTINGS
Nominal Approved Temperature Ratings °FI°C
Orifice Size K-Factor
Inches Imperial Deflector
Model millimeters S.LA Response Type UL FM ULC NYCIMEAt CSFM §
V2703 ½ 5.6 Standard Upright 135-360 135-360 135-360 135-360 135-360
13 8.1 57-182 57-182 57-182 57-182 57-182
V2707 ½ 5.6 Standard Pendent 135-360 135-360 135-360 135-360 135-360
13 8,1 57-182 57-182 57-182 57-182 57-182
½5.6 Recessed Pendent 135-360 135-200 135-360 135 -360 135 -360 V2707 13 8,1 Standard Up to °R Adjustment 57-182 57-93 57-182 57-182 57-182
V2704 1h 5.6 Quick Upright 135-286 135-286 135-286 135-286 135-286
13 8,1 57- 141 57-141 57- 141 -----57-141 57 -141
V2708 1h 5.6 Quick Pendent 135-286 135-286 135-286 135-286 135-286
13 8,1 57-141 57-141 57-141 57-141 57-141
½ 5.6 Recessed Pendent 135-200 135-200 135-200 135-200 135-200 V2708 13 8,1 Quick Up tow Adjustment 57-93 57-93 57-93 57-93 57-93
½ 5.6 Recessed Pendent 135-200 135-200 135-200 135 -200 V2708 13 8,1 Quick Up to ~' Adjustment 1 57 -93 No 57 -93 57 -93 1 57 -93
t Listings and approval as of printrng. a All are approved open, except for areas designated N0.
For K-Factor when pressure is measured in Bar, multiply S.I. units by 10.
MEA #62-99-E. § CSFM #7690-0531:112
t
RATINGS
All glass bulbs are rated for
temperatures from -67°F
(-5 5°C) up to those shown
in adjacent table.
Temperature - °FI°C
Nominal Maximum Sprinkler Victaulic Glass
Temperature Part Temperature Ambient Temp. Bulb
Classification Identification Rating Allowed Color
Ordinary A 135
57
100
38 Orange
Ordinary c 55
168
100
38 Red
Intermediate E 175 150
79 65 Yellow
Intermediate F 200
93
150
65 Green
High J 286
141
225 -
107 Blue
Extra High t K 360
182
300
149 Purple
- I M Open = No Bulb
Standard response only.
All are approved open, except for areas designated No.
- 150/65 if wax coated.
E1
ORDERING INFORMATION
Please specify the following
when ordering: 0 Sprinkler Model Number U K-Factor 0 Sprinkler Finish
O Style 0 Thread Size 0 Escutcheon Finish
U Temperature Rating U Quantity U Wrench Model Number
A%W1TRNIJiG
Always read and understand installation, care, and maintenance instructions, supplied with each box of sprinklers, before proceeding with installation
of any sprinklers.
Always wear safely glasses and loot protection.
Depressurize and drain the piping system before attempting to install, remove, or adjust any Victaulic piping products. . 0 Installation rules, especially those governing obstruction, must be strictly followed.
Painting, plating, or any re-coating of sprinklers (other than that supplied by Victaulic) is not allowed.
Failure to follow these instructions could result in serious personal injury and/or property damage.
The owner is responsible for maintaining the fire protection system and devices in proper operating condition. For minimum maintenance and inspection requirements, refer to the
current National Fire Protection Association pamphlet that describes care and maintenance of sprinkler systems. In addition, the authority having jurisdiction may have additional
maintenance, testing, and inspection requirements that must be followed.
If you need additional copies of this publication, or if you have any questions about the safe installation of this product, contact Victaulic World Headquarters, P.O. Box 31, Easton,
Pennsylvania 18044-0031, 610-559-3300.
40.10 -2
17A6
(37 mm)
(66 1W
(41 mm) 2W
(60 mm)
DIMENSIONS
(25 MM) 1 k
Standard Pendent - V2707, V2708 Standard Upright- V2703, V2704
Recessed - V2707, V2708
(Drawing not to scale)
23W (60 mm)
Max. Hole
2(51 mm)
Mm. He
(33 mm) (24 mm) Typical Ceiling TO (149nm) _____
1,y . (24 mm)
Finished Surface (43 mm)
MAXIMUM RECESS
(75 mm)
MAXIMUM EXTENSION
3/4 Adjustment
Recessed - V2707, V2708
(Drawing not to scale)
I I
AVAILABLE WRENCHES
V27
Socket
V38 or V38-3
Recessed
V27
Open End
V270],V2]08Pendent / / /
V2707, V2708 Recessed Pendent
V2703, V2704 Upright
40.10-3
DISTRIBUTION PATTERNS
MODELS V2707, V2708
K5.6 STANDARD PENDENT AND RECESSED PENDENT
10'
3,0 m
8'
2,4m
6'
1,8 m
4,
1,2 m
2'
0,6 m
0
7 psi
48 kPa
15 psi
103 kPa
30 psi -------
207 kPa
2' 4' 6' 8' 10' 12' 14'
0,6 m 1,2 m 1,8 m 2,4 m 3,0 m 3,7 m 4,3 m
MODELS V2703, V2104
1(5.6 STANDARD UPRIGHT DISTRIBUTION PATTERNS - TRAJECTORY -- --
m
'
m --
\
-
--
"S \
m
\
m
--
2' 4' 6' 8' 10' 12' 14' 16'
0,6m 1,2rn 1,8m 2,4m 3,0m 3,7m 4,3m 4,9m
NOTES:
Data shown is approximate and can vary due to differences in installation.
These graphs illustrate approximate trajectories, floor-wetting, and wall-wetting patterns for these specific Victaulic FireLock Automatic Sprinklers. They are
provided as information for guidance in avoiding obstructions to sprinklers and should not be used as minimum sprinkler spacing rules for installation. Refer to
the appropriate NFPA National Fire Code and the authority having jurisdiction for specific information regarding obstructions, spacing limitations and area of
coverage requirements. Failure to follow these guidelines could adversely affect the performance of the sprinkler and will void all Listings, Approvals and War-
ranties.
All patterns are symmetrical to the centerline of the waterway.
I— I
WARRANTY Refer to the Warranty section
of the current Price List or
contact Victaulic for details.
This product shall be manufactured by Victaulic Company. All products to be installed in accordance nlh current Victaulic installation/assembly instructions.
Victaulic reserves the right to change product specifications, designs and standard equipment without notice and without incurring obligations.
40.10-4
10'
3,0 m
8
2,4
6'
1,8
4
1,2
2
0,6
0
7 psi
48 kPa
15 psi
103 kPa
30 psi
207 kPa