HomeMy WebLinkAbout2701 OCEAN ST; ; AS150138; PermitCity of Carlsbad
Sprinkler Permit
Permit No: AS 150138
Job Address: 2701 OCEAN ST
Permit Type: SPRINK
Parcel No: 2031403800
Lot #: 0
Reference No.:
PC #:
Project Title: DEAN RESIDENCE SFR
Status: APPROVED
Applied 5/12/2015
Approved: 5/13/2015
Issued: 5/13/2015
Inspector:
Applicant:
ALWAYS FIRE PROTECTION
1451 KENT AV.
ESCONDIDO, CA
760-294-4525
Owner:
DEAN TOMMY M TRUST 03-14-05
4517 ADAMS ST
CARLSBAD CA
Fees ($) Add'I Fees ($) Total ($) Balance ($)
280 0 280 0
AS 150138
HYDRAULIC DESIGN INFOF,1,.
Name: Dean Residence
Location: 2701 Ocean Street
Carlsbad, CA 92008
Building:
Contractor: Berry Smith & Associates
File Name: Dean Res 4-7-15.the
Construction: Z Combustible fl Noncombustible
Occupancy: Single Family Dwelling
AHJ: Carlsbad Fire Department
Date: April 07, 2015
System No:
Contract No.:
Drawing No.:
Calculated by: B. R.
Ceiling Height: 8'-1" ft
SYSTEM DESIGN
O NFPA 13: D Light Hazard fl Ordinary Hazard Group: fl Extra Hazard Group:
Figure: Curve:
nX Other (Specify): NFPA 13D
F1 Srecific Rullina:
- Made By: Date:
Area of Sprinkler Operation: 256 sqft System Type: EI Wet 0 Dry 0 Delugee-Action
Density: .05 gpm/sqft lf~
CW
Area per Sprinkler: 256 sqft SPRINKLER or NOZZLE
Hose Allowance Inside: gpm Make: Tyco Model L II l
Hose Allowance Outside: gpm Size: .5 in K-factor: 9
Rack Sprinkler Allowance: gpm Temperature Rating: 160 OF ) U) CALCULATION SUMMARY
Flow Required: 31.04 gpm Pressure Required: 55.23 psi At: SRC
"C" Factor Used: Overhead: 150 Underground: 150 L__1qJ
WATER SUPPLY
WATER FLOW TEST PUMP DATA TANK ORRESER1
Date: 4-2-15 Rated Capacity: gpm Capacity: gals
Time: 8:30 AM At: psi Elevation: ft
Static: 74 psi Elevation: ft
Residual: 73 psi WELL
Flowing: 52 gpm Proof Flow: gpm
Elevation: 41 ft
Location: 2701 Ocean Street Carlsbad, Ca 92008
Source of Information: Carldbad Municipal Water Linda 760-602-2750
COMMODITY STORAGE
Commodity: Class: Location:
Storage Height: Area: Aisle Width:
Storage Method: Solid Pile: % Palletized: % Rack: %
RACK STORAGE
O Single Row
O Double Row
El Multiple Row
FLUE SPACING
Longitudinal:
O Conventional Pallet
O Slave Pallet
in Transverse:
o Automatic Storage
O Solid Shelving
0 Open
O Encapsulated
0 Nonencapsulated
CLEARANCE FROM TOP OF STORAGE TO CEILING
in ft in
Horizontal Barriers Provided:
/
=
-
-
> -
- -1 -
:2 7
12.81 ft/sec in the pipe between Nodes: BFI and BF2
0.01 gpm
Fitting Type Legend
E = 90 degree elbow
I = Tee - Flow thru branch
H = Tee - Flow thru run
C = Check valve
U = Flow Indecater
N = 90 degree elbow
M = 45 degree elbow
File: Dean Res 4-7-15.the Page 1 of I
Hydraulic Summary
WATER SUPPLY INFORMATION
Static (psi): 66.60
Residual (psi): 65.70
© (gpm): 52.00
Hose (gpm): 0.00
System req. (gpm): 31.04
@ (psi): 55.23
Supply available: 66.25 psi
Safety margin: 11.02 psi
Maximum velbcity in the system is:
Continuity at all nodes satisfied to:
Pipe Type Legend
CP = Central - BlazeMaster CPVC
CL = Copper Type L
PP = PVC
CK = Copper Type K
NOTES
04/07/15 "THE" Sprinkler Program 2001
File: Dean Res 4-7-1 5.the Page 1 of I
Node Pressure Flow Hose Elevation K-factor Area Density
psi gpm gpm feet gpm/(psi)Y2 sqft gpm/sqft
1 7.05 13.00 57.650 4.90 25600 0.051
2 7.10 13.04 57.650 4.90 256.00 0.051
A 7.46 0.00 57.650
Al 7.51 0.00 57.650
A2 9.95 0.00 57.650
A3 8.07 0.00 57.650
A4 8.35 0.00 57.650
B 12.55 0.00 48.570
BI 12.82 0.00 48.570
82 14.11 0.00 48.570
TOR 14.53 0.00 48.570
BOR 19.59 5.00 5.00 40.400
BF1 42.36 0.00 43.000
BF2 29.01 0.00 41.000
UI 24.58 0.00 36.900
U2 42.82 0.00 43.000
SRC 55.23 31.04 41.000 Source
04/07/15 "THE" Sprinkler Program 2001
File Dean Res 4-7-1 5.the Page 1 of
Node Node Flow K-factor Elevation Pressure Diameter Length Fric Loss
Node Node Flow K-factor Elevation Pressure HWC Fittings Eqv Length Elev Loss
Pipe Flow Velocity itt Length itt FL
1 13.00 4.90 57.65 7.05 1.101 3.300 0.031
A 0.00 57.65 7.46 150 E I 10.000 0.00
13.00 4.38 13.300 0.41
2 13.04 4.90 57.65 7.10 1.101 3.300 0.031
Al 0.00 57.65 7.51 150 E I 10.000 0.00
13.04 4.40 13.300 0.41
A 0.00 57.65 7.46 1.101 11.650 0.002
Al 0.00 57.65 7.51 150 H 21 11.000 0.00
3.19 1.07 22.650 0.05
Al 0.00 57.65 7.51 1.101 30.690 0.046
A2 0.00 57.65 9.95 150 3E 2H I 22.000 0.00
16.23 5.47 52.690 2.44
A 0.00 57.65 7.46 1.101 24.800 0.018
A3 0.00 57.65 8.07 150 4H I 9.000 0.00
9.81 3.31 33.800 0.62
A3 0.00 57.65 8.07 1.101 10.370 0.018
A4 0.00 57.65 8.35 150 E 5.000 0.00
9.81 3.31 15.370 0.28
A2 0.00 57.65 9.95 1.101 9.080 0.046
TOR 0.00 48.57 14.53 150 I 5.000 3.93
- 16.23 5.47 14.080 0.65
A4 0.00 57.65 8.35 1.101 9.080 0.018
B . 0.00 48.57 12.55 150 E 5.000 3.93
9.81 3.31 14.080 0.26
B 0.00 48.57 12.55 1.101 8.890 0.018
BI 0.00 48.57 12.82 150 H I 6.000 0.00
9.81 3.31 14.890 0.27
Bl 0.00 48.57 12.82 1.101 56.790 0.018
B2 0.00 48.57 14.11 150 9H I 14.000 0.00
9.81 3.31 70.790 1.29
B2 0.00 48.57 14.11 1.101 17.240 0.018
TOR 0.00 48.57 14.53 150 H I 6.000 0.00
9.81 3.31 23.240 0.42
BOR 5.00 40.40 19.59 1.101 8.170 0.111
TOR 0.00 48.57 14.53 150 C U 5500 3.54
26.04 8.78 13.670 1.52
04/07/15 "THE" Sprinkler Program 2001
File: Dean Res 4-7-I5.the Page 2 of 2
Node Node Flow K-factor Elevation Pressure Diameter Length Fit Loss
Node Node Flow K-factor Elevation Pressure HWC Fittings Eqv Length Elev Loss
- Pipe Flow Velocity Ttl Length Ttl FL
UI 0.00 36.90 24.58 1.025 7.000 0.217
BOR 5.00 40.40 19.59 150 3N 9.000 1.52
31.04 12.07 16.000 3.48
BF2 0.00 41.00 29.01 1.101 27.000 0.153
Ui 0.00 36.90 24.58 150 2E 13.416 -1.78
31.04 10.46 40.420 6.20
BFI 0.00 43.00 42.36 0.995 7.170 0.251
BF2 0.00 41.00 29.01 150 3N 2C 17.000 -0.87
31.04 12.81 24.170 14.22
The Flow Dependent Pressure Loss Device in this pipe accounts for 8.14 psi of the total friction loss.
U2 0.00 43.00 42.82 0.995 1.830 0.251
BF1 0.00 43.00 42.36 150 0.000 0.00
31.04 12.81 1.830 0.46
SRC 31.04 Source 41.00 55.23 0.995 28.000 0.251
U2 0.00 43.00 42.82 150 2M 2.000 0.87
31.04 12.81 30.000 11.55
The Flow Dependent Pressure Loss Device in this pipe accounts for 4.01 psi of the total friction loss.
Units Legend
Flow = gpm Velocity = ft/sec Fric Loss = psi/ft
Elevation = feet Length, Elev Loss,
Presure = psi Eqv Length, Ttl FL = psi
Diameter = inches Ttl Length = feet
04/07/15 "THE" Sprinkler Program 2001
Water Supply vs. Sprinkler Demand
90 -
80
70
52 @66
31 @55
60
50
30
20
ic
0 20 40 60 80 100 120 140
Flow (gpm)
tqa~no
Fire Protection
Products
Worldwide
Contacts www.tyco-fire.com
RAPID RESPONSE Series LFII Residential Sprinklers
49 K-factor Pendent
Wet Pipe and Dry Pipe Systems
General
Description
The TYCO RAPID RESPONSE
Series LFII Residential Pendent
and Recessed Pendent Sprinklers
(TY2234) are decorative, fast
response, frangible bulb sprinklers
designed for use in residential occu-
pancies such as homes, apart-
ments, dormitories, and hotels. When
aesthetics and optimized flow charac-
teristics are the major consideration,
the Series LFII Residential Sprinklers
(TY2234) should be the first choice.
The Series LFII Residential Sprinklers
are intended for use in the following
scenarios:
wet and dry pipe residential sprin-
kler systems for one- and two-family
dwellings and mobile homes per
NFPA 13D
wet and dry pipe residential sprin-
kler systems for residential occu-
pancies up to and including four
stories in height per NFPA 13R
wet and dry pipe sprinkler systems
for the residential portions of any
occupancy per NFPA 13
The recessed version of the Series
LFII Residential Sprinklers is intended
for use in areas with finished ceilings.
It employs a two-piece Style 20
Recessed Escutcheon. The Recessed
Escutcheon provides 1/4 inch (6,4 mm)
of recessed adjustment or up to 1/2
inch (12,7 mm) of total adjustment
from the flush ceiling position. The
adjustment provided by the Recessed
IMPORTANT
Always refer to Technical Data
Sheet TFP700 for the "INSTALLEF?
WARNING" that provides cautions
with respect to handling and instal-
lation of sprinkler systems and
components. Improper handling and
installation can permanently damage
a sprinkler system or its components
and cause the sprinkler to fall to
operate in a fire situation or cause it
to operate prematurely.
Page 1 of 6
Escutcheon reduces the accuracy to
which the pipe drops to the sprinklers
must be cut.
The Series LFII Residential Sprinklers
have been designed with heat sensi-
tivity and water distribution charac-
teristics proven to help in the control
of residential fires and to improve the
chance for occupants to escape or be
evacuated.
Dry Pipe System Application
The Series LFII Residential Pendent
and Recessed Pendent Sprinklers
offers a laboratory approved option
for designing dry pipe residential
sprinkler systems, whereas, most
residential sprinklers are laboratory
approved for wet systems only.
Through extensive testing, it has been
determined that the number of design
sprinklers (hydraulic design area) for
the Series LFII Residential Pendent
and Recessed Pendent Sprinklers
(TY2234) need not be increased
over the number of design sprinklers
(hydraulic design area) as specified
for wet pipe sprinkler systems, as is
accustomed for density/area sprinkler
systems designed per NFPA 13.
Consequently, the Series LFII
Residential Sprinklers offer the
features of non-water filled pipe in
addition to not having to increase the
number of design sprinklers (hydraulic
design area) for systems designed to
NFPA 13,13D, or 13R.
NOTICE
The Series LFII Residential Pendent and•
Recessed Pendent Sprinklers (TY2234)
described herein must be installed and
maintained in compliance with this
document and the applicable stan-
dards of the National Fire Protection
Association, in addition to the stan-
dards of any authorities having jurisdic-
tion. Failure to do so may impair the
performance of these devices.
The owner is responsible for main-
taining their fire protection system and
devices in proper operating condi-
tion. Contact the installing contractor
or sprinkler manufacturer with
any questions.
FEBRUARY 2014
Sprinkler
Identification
Number (SIN)
TY2234
Technical
Data
Approvals
UL Listed for use with wet pipe and
dry pipe systems
C-UL Listed for use only with wet pipe
systems
NSF Certified to NSF/ANSI 61
For details on these approvals, refer
to the Design Criteria section.
Maximum Working Pressure
175 psi (12,1 bar)
Discharge Coefficient
K = 4.9 GPM/psi1/2 (70,6 LPM/bar112)
Temperature Rating
155°F (68°C) or 175°F (79°C)
Finishes
Natural Brass
Pure or Signal White
Chrome Plated
Physical Characteristics
Frame .............................Brass
Button............................Copper
Sealing Assembly ................Beryllium
Nickel w/TEFLON
Bulb (3 mm) ........................Glass
Compression Screw ................Bronze
Deflector .......................... Bronze Ejection Spring...............Stainless Steel
TFP400
TFP400
Page 2 of 6
7/16" (11,1 mm) 1/2 ESCUTCHEON
Components: NOMINAL NPT PLATE SEATING 2-7/8" DIA.________
1 - Frame
2 - Button
MAKE-IN SURFACE (73,0 mm)
4-Bulb
5 - Compression 2 2-1/4
Screw
6 - Deflector* (57,2 mm)
3 - Sealing Assembly 1
ESCUTCHEON
RENCH
1-5/8 I STYLE 20 (41,3 mm) w
3
—0 RECESSED
* Temperature :iii FLATS
rating is
indicated on
Deflector.
CROSS SECTION PENDENT RECESSED PENDENT
FIGURE 1
RAPID RESPONSE SERIES LFII RESIDENTIAL
PENDENT AND RECESSED PENDENT SPRINKLERS (TY2234)
7/16±1/8"
(11,1±3,2 mm)
FACE OF
SPRINKLER
FITTING
2-7/8 DIA.
(73,0 mm) I 1/2(12,7mm)
2-1/4 DIA. 1/4" (6,4 mm)
(57,2 mm)
MOUNTING
WR ENCH RECESS
(END "A' USED
FOR TY2234)
FIGURE 3
W-TYPE 6
SPRINKLER WRENCH
MOUNTING
SURFACE
CLOSURE TY2234
Operation
The glass bulb contains a fluid that
expands when exposed to heat. When
the rated temperature is reached, the
fluid expands sufficiently to shatter the
glass bulb, allowing the sprinkler to
activate and flow water.
Design
Criteria
The TYCO RAPID RESPONSE
Series LFIl Residential Pendent
and Recessed Pendent Sprinklers
(TY2234) are UL and C-UL Listed for
installation in accordance with this
section.
1/8
(3,2 mm)
1-3/8" (34,9 mm)
1-1/8 (28,6 mm)
Residential Sprinkler Design Guide
When conditions exist that are
outside the scope of the provided
criteria, refer to the Residential
Sprinkler Design Guide TFP490 for
the manufacturer's recommendations
that may be acceptable to the local
authority having jurisdiction.
System Types
Per the UL Listing, wet pipe and dry
pipe systems may be utilized. Per the
C-UL Listing, only wet pipe systems
may be utilized.
Refer to Technical Data Sheet TFP485
for the use of residential sprinklers in
residential dry pipe systems.
WRENCH
RECESS
PUSH WRENCH
IN TO ENSURE
ENGAGEMENT
WITH SPRINKLER
WRENCHING AREA
FIGURE 4
W-TYPE 7 RECESSED
SPRINKLER WRENCH
Ceiling Types
Smooth flat horizontal, or beamed, or
sloped, in accordance with the 2013
Edition of NFPA 13D, 13R, or 13 as
applicable.
Hydraulic Design
(NFPA 13D and 13R)
For systems designed to NFPA
13D or NFPA 13R, the minimum
required sprinkler flow rates are
FIGURE 2
STYLE 20 RECESSED ESCUTCHEON FOR USE WITH THE
RAPID RESPONSE SERIES LFII RESIDENTIAL PENDENT SPRINKLER
TFP400
Page 3 of 6
given in Tables A and B as a func-
tion of temperature rating and the
maximum allowable coverage areas.
The sprinkler flow rate is the minimum
required discharge from each of the
total number of "design sprinklers" as
specified in NFPA 13D or NFPA 13R.
The number of "design sprinklers"
specified in NFPA 130 and 13R for wet
pipe systems is to be applied when
designing dry pipe systems.
Hydraulic Design
(NFPA 13)
For systems designed to NFPA 13,
the number of design sprinklers is
to be the four most hydraulically
demanding sprinklers. The minimum
required discharge from each of the
four sprinklers is to be the greater of
the following:
The flow rates given in Tables A
or B as a function of temperature
rating and the maximum allowable
coverage area.
A minimum discharge of 0.1 gpm/ft2
over the "design area" comprised
of the four most hydraulically
demanding sprinklers for actual
coverage areas protected by the
four sprinklers.
The number of "design sprinklers"
specified in NFPA 13 for wet pipe
systems is to be applied when
designing dry pipe systems.
Dry Pipe System Water Delivery
When using the Series LFII Residential
Sprinklers (1Y2234) in dry pipe sprin-
kler systems, the time for water
delivery must not exceed 15 seconds
for the most remote operating
sprinkler.
Obstruction to Water Distribution
Sprinklers are to be located in accor-
dance with the obstruction rules
of NFPA 13D, 13R, and 13 as appli-
cable for residential sprinklers as
well as with the obstruction criteria
described within the Technical Data
Sheet TFP490.
Operational Sensitivity
Sprinklers are to be installed with a
deflector-to-ceiling distance of 1-1/4 to
4 inches.
Sprinkler Spacing
The minimum spacing between sprin-
klers is 8 feet (2,4 m). The maximum
spacing between sprinklers cannot
exceed the length of the coverage
area (Table A or B) being hydraulically
calculated (e.g., maximum 12 feet for a
12 ft. x 12 ft. coverage area, or 20 feet
for a 20 ft. x 20 ft. coverage area).
Installation
The TYCO RAPID RESPONSE
Series LFII Residential Pendent
and Recessed Pendent Sprinklers
(TY2234) must be installed in accor-
dance with this section:
General Instructions
Do not install any bulb type sprin-
kler if the bulb is cracked or there is a
loss of liquid from the bulb. With the
sprinkler held horizontally, a small air
bubble should be present. The diam-
eter of the air bubble is approximately
1/16 inch (1,6 mm).
A leak-tight 1/2 inch NPT sprinkler
joint should be obtained by applying
a minimum-to-maximum torque of 7
to 14 ft.-lbs. (9,5 to 19,0 Nm). Higher
levels of torque can distort the sprin-
kler Inlet with consequent leakage or
impairment of the sprinkler.
Do not attempt to compensate
for insufficient adjustment in an
Escutcheon Plate by under- or over-
tightening the sprinkler. Re-adjust the
position of the sprinkler fitting to suit.
Series LFII Residential Pendent
Sprinklers
The Series LFII Residential Pendent
Sprinklers must be installed in accor-
dance with the following instructions.
Step 1. Install pendent sprinklers in
the pendent position with the deflector
parallel to the ceiling.
Step 2. With pipe thread sealant
applied to the pipe threads, hand-
tighten the sprinkler into the sprinkler
fitting.
Step 3. Tighten the sprinkler into
the sprinkler fitting using only the
W-Type 6 Sprinkler Wrench (Figure
3). With reference to Figure 1, apply
the W-Type 6 Sprinkler Wrench to the
wrench flats.
Series LFII Residential Recessed
Pendent Sprinklers
The Series LFII Residential Recessed
Pendent Sprinklers must be installed
in accordance with the following
instructions.
Step A. Install recessed pendent
sprinklers in the pendent position with
the deflector parallel to the ceiling.
Step B. After installing the Style 20
Mounting Plate over the sprinkler
threads and with pipe thread sealant
applied to the pipe threads, hand-
tighten the sprinkler into the sprinkler
fitting.
Step C. Tighten the sprinkler into the
sprinkler fitting using only the W-Type 7
Recessed Sprinkler Wrench (Figure 4).
With reference to Figure 1, apply the
W-Type 7 Recessed Sprinkler Wrench
to the sprinkler wrench flats.
Step D. After the ceiling has been
installed or the finish coat has been
applied, slide on the Style 20 Closure
over the Series LFII Residential
Sprinkler and push the Closure over the
Mounting Plate until its flange comes in
contact with the ceiling.
TFP400
Page 4 of 6
WET PIPE SYSTEM
Minimum Flow and Residual Pressure(b, c)
Max.
Coverage Ordinary Temp. Rating Intermediate Temp. Rating Minimum
Area (a) 155°F (68°C) 175°F (79°C) Deflector to Installation Spacing
Flow Pressure Ft. x Ft. Flow Pressure Ceiling Type Ft.
(m x m) GPM PSI GPM PSI (m)
(L/min) (bar) (L/min) (bar)
12 x 12 13 7.0 13 7.0 Smooth
(3,7 x 3,7) (49,2) (0,48) (49,2) (0,48) Ceilings
1-1/4 to
4inches 14x14 13 7.0 13 7.0
(4,3 x 4,3) (49,2) (0,48) (49,2) (0,48)
Beamed
Recessed
using Style 20
16x16 13 7.0 13 7.0 Ceilings per Escutcheon or 8
(4,9 x 4,9) (49,2) (0,48) (49,2) (0,48) NFPA 13D
or 13R
non-recessed
per NFPA 13D,
13R, or 13
(2,4)
18x 18 17 12.0 17 12.0
(5,5x5,5) (64,3) (0,83) (64,3) (0,83) 1-1/4 to1-3/4
inches below
bottom of 20 x 20 20 16.7 20 16.7
(6,1 x 6,1) (75,7) (1,15) (75,7) (1,15) beam.
For coverage area dimensions less than or between those indicated, use the minimum required flow for the next highest coverage
area for which hydraulic design criteria are stated.
Requirement is based on minimum flow in GPM (LPM) from each sprinkler. The associated residual pressures are calculated using
the nominal K-factor. Refer to Hydraulic Design under the Design Criteria section.
For NFPA 13 residential applications, the greater of 0.1 gpm/ft2 over the design area of the flow in accordance with the criteria in
this table must be used.
TABLE A
WET PIPE SYSTEM
SERIES LFII RESIDENTIAL PENDENT AND RECESSED PENDENT SPRINKLERS (TY2234)
NFPA 13D, 13R, AND 13 HYDRAULIC DESIGN CRITERIA
DRY PIPE SYSTEM
Maximum Minimum Flow and Residual Pressure(b, c)
Ordinary Temp. Rating
______________________
Intermediate Temp. Rating Coverage
Area (a) 155°F (68°C) 175°F (79°C) Minimum
Ft. x Ft. Deflector to Installation Spacing
Flow Pressure Flow Pressure (m x m) Ceiling Type Ft.
GPM PSI GPM PSI (m)
(Limin) (bar) (L/min) (bar)
12x12 13 7.0 13 7.0 Smooth
(3,7 x 3,7) (49,2) (0,48) (49,2) (0,48) Ceilings
1-1/4 to
14 X 14
(4,3 x 4,3)
14
(53.0)
8.2
(0,57)
14
(53,0)
8.2
(0,57) 4 inches
Beamed
Recessed
using Style 20
16x16 15 9.4 15 9.4 Ceilings per Escutcheon or 8
(4,9 x 4,9) (56,8) (0,65) (56,8) (0,65) NFPA 13D
or13R
non-recessed
per NFPA 13D,
13R, or 13
(2,4)
18x18 18 13.5 18 13.5
(5,5 x 5,5) (68,1) (0,93) (68,1) (0,93) 1-1/4 to 1-3/4
inches below
bottom of 20 x 20 21 18.4 21 18.4
(6,1 x 6,1) (79,5) (1,27) (79,5) (1,27) beam.
For coverage area dimensions less than or between those indicated, use the minimum required flow for the next highest coverage
area for which hydraulic design criteria are stated.
Requirement is based on minimum flow in GPM (LPM) from each sprinkler. The associated residual pressures are calculated using
the nominal K-factor. Refer to Hydraulic Design under the Design Criteria section.
For NFPA 13 residential applications, the greater of 0.1 gpm/ft2 over the design area of the flow in accordance with the criteria in
this table must be used.
TABLE B
DRY PIPE SYSTEM
SERIES LFI1 RESIDENTIAL PENDENT AND RECESSED PENDENT SPRINKLERS (TY2234)
NFPA 13D, 13R, AND 13 HYDRAULIC DESIGN CRITERIA
TFP400
Page 5 of 6
Care and
Maintenance
The TYCO RAPID RESPONSE Series
LFII Residential Pendent and Recessed
Pendent Sprinklers (TY2234) must be
maintained and serviced in accordance
with this section:
Before closing afire protection system
main control valve for maintenance
work on the fire protection system that
it controls, permission to shut down
the affected fire protection system
must be obtained from the proper
authorities and notify all personnel
who may be affected by this action.
Absence of the outer piece of an
escutcheon, which is used to cover
a clearance hole, can delay sprinkler
operation in a fire situation.
The owner must assure that the
sprinklers are not used for hanging
any objects and that the sprinklers
are only cleaned by means of gently
dusting with a feather duster; other-
wise, non-operation in the event of
a fire or inadvertent operation may
result.
Sprinklers which are found to be
leaking or exhibiting visible signs of
corrosion must be replaced.
Automatic sprinklers must never be
painted, plated, coated, or other-
wise altered after leaving the factory.
Modified sprinklers must be replaced.
Sprinklers that have been exposed to
corrosive products of combustion, but
have not operated, should be replaced
if they cannot be completely cleaned
by wiping the sprinkler with a cloth or
by brushing it with a soft bristle brush.
Care must be exercised to avoid
damage to the sprinklers - before,
during, and after installation.
Sprinklers damaged by dropping,
striking, wrench twist/slippage, or the
like, must be replaced. Also, replace
any sprinkler that has a cracked bulb
or that has lost liquid from its bulb.
(Ref. Installation Section.)
The owner is responsible for the
inspection, testing, and mainte-
nance of their fire protection system
and devices in compliance with this
document, as well as with the appli-
cable standards of the National Fire
Protection Association (e.g., NFPA
25), in addition to the standards of any
authorities having jurisdiction. Contact
the installing contractor or sprinkler
manufacturer regarding any questions.
Automatic sprinkler systems are
recommended to be inspected,
tested, and maintained by a qualified
Inspection Service in accordance with
local requirements and/or national
codes.
Limited
Warranty
For warranty terms and conditions,
visit www.tyco-fire.com.
Ordering
Procedure
Contact your local distributor for
availability. When placing an order,
indicate the full product name and Part
Number (P/N).
Sprinkler Assembly
Specify: Series LFll (TY2234), K = 4.9,
Residential Pendent Sprinkler,
(specify) temperature rating, (specify)
finish, P/N (specify):
155°F (68°C)
Natural Brass ..............P/N 51-201-1-155
Pure White (RAL 9010)' ......P/N 51-201-3-155
Signal White (RAL 9003) .....P/N 51-201-4-155
Chrome Plated .............P/N 51-201-9-165
175°F (79°C)
Natural Brass ..............P/N 51-201-1-175
Pure White (RAL 9010)' ......P/N 51-201-3-175
Signal White (RAL 9003) .....P/N 51-201-4-175
Chrome Plated ...... ....... P/N 51-201-9-175
'Eastern Hemisphere sales only
Recessed Escutcheon
Specify: Style 20 Recessed
Escutcheon with (specify*) finish, P/N
(specify*)
'Refer to Technical Data Sheet TFP770
Sprinkler Wrench
Specify: W-Type 6 Sprinkler Wrench,
P/N 56-000-6-387
Specify: W-Type 7 Sprinkler Wrench,
P/N 56-850-4-001
TFP400
Page 6 of 6
GLOBAL HEADQUARTERS 11400 Pennbrook Parkway, Lansdale, PA 194461 Telephone +1-215-362-0700
Copyright © 2014 Tyco Fire Products, LP. All rights reserved. tqc TEFLON is trademark of The DuPont Corporation. Fire Protection Products
Ali
°Apo.Qivaives
SUBMITTAL
-Model DCLF 4A
flt-u shle Check Values
IX
STANDARD MATERIALS LIST
Part Name Material
Body, Caps, Ball Valve
5hutoffsjest cocks 910112e C89836 (lead Fcee)
Check Valve Cartridges Glass-Filled PPO
Springs 300 Series Stainless Steel
Seat Discs chloramine-resistant Silicone 1
0-rings (hloramine-resistant EPDM
Job Name:
Jobtocation:
Engineer
Coirtmctor
Tag:
110 Number
Representative:
Wholesale Distributon
DESCRIPTION
The Apolloe Model DCLF4A Lead Free* Double Check Valves prevent contamination of the potable
water supply due to back-siphonage or backpressure from substances that are objectionable
to the potable water supply, but non-health hazards. The top accessed modular check valve
cartridges provide captured springs, replaceable seats and reversible silicone seat discs. This
Made in America assembly features Apollo ball valves with stainless steel handles and nuts as
standard and carries the five-year Apollo' factory warranty.
FEATURES
Low pressure loss documented by
independent approval agencies
- Easily removable modular check valve
cartridge
Captured stainless steel springs
Apolloa ball valves W/ 55 handles & nuts
standard
Top-mounted test cocks for easy testing
No special tools required
Chloramine-resistant elastomers
Designed, cast, machined, assembled
and tested IN THE USA
PERFORMANCE RATING
Maximum Working Pressure 175 psi
Temperature Range 33 F —180°F
APPROVALS
ASSE 1015- Horizontal and Vertical
Flow Up (W'-2")
- CSA 8.64.5 - Horizontal and Vertical
Flow Up (W-2')
Approved by the Foundation for
Cross-Connection Control and
Hydraulic Research at the University
of Southern California - Horizontal and
Vertical Flow Up (W'-21
DIMENSIONS
Model
Number
Sire
(in.)
Dimensions (in.) Wt.
(lbs.) A IA,l B C D
4ALF-103-72F 1/2" 11-1/8 12-9132
114-9132
7-3/8 3-1/4 2-1/2 4.4
4ALF-104-12F 3/4" 12-3/4 8-1/2 3-1/2 3 60
4ALF-105-72F 1" 14-5/8 16-7/32 9-1/2 4 3-1/4 10.0
4ALF-106-72 1-1/4" r18-518 20-5/32 1-3/4 4-1/2 4-314 14.0
4ALF-107-72 1-1/2" 118-3/4 20-31132 11-5/8 4-1/2 4-314 17-0
4A1.F-108-72 r 21-1/8 22-13/16 12-3/4 5 5-3/8 25.4
-
B
* LEAD FREE: The wetted surfacesofthis product shall contain no more than 0.25% lead Apollo Valves, Manufactured by Conbraco Industries, Inc.
by weighted average. Complies with CA 481953. VTAct 193, MD 1413372, LAHB47I and 701 Matthews Mint-Hill Road, Matthews, NC 28105 USA
Federal Public Law 111-380. ANSI 3rd party approved and listed. www.apollovalves.com ) (704) 841-6000
Thespd&atwniuyiedfwafezenceon!y (snroco1nthuVia Inz.raava
ealcurw affaaemturthemalcwtis(wmgtrn
SS1206©03/14 Paael of 2
18
16
14
9 12
0
20
18
g 16
14
9 12
4
Apø&"aves
SUBMITTAL '
—Model DCLJF 4A
Double Check Valves
FACTORY CODE
Y-STRAINER I SIZE
4A = Standard 10 0= Standard ID 3= i!2'
4A[F= Lead Free ID 1= wlY-strainer 10 4= 3I4
(shipped loose) 0 5= r
D 6= 1-114
10 7= 1-1)2
D 8=2
FLOW CURVES
Meter Rated Flow
7.51p112' 7.5fps 314'
SHUT-OFF VALVES I OPTIONS (CAN BE COMBINED)
0 1= less hail valves (Uldassified 314"-21 0 F = SAEtlireadedtest cocks (standard 1/29I4 10)
El 2= w/ball valves (Standard) 0 11= locking (ever handles 0-1/4 1-1/2'. 27
El 4= w/union ball valves 0 U= locking tee handles (314"-11
O PR= Press
P = Push (3/4 -1')
.
- -
• /. 7 -.-
- --. --. -
. 314'
._-__-.------
-. -
10 20 30 40
RATE OF FLOW (GPM)
20
18
16
Cl) 14 U' 9 12
10
C4 8 (I) U)
04
7.5(psl 7.51ps1114'
--
—
0 10 20 30 40 50 60 70 80 90 100 110
RATE OF FLOW (GPM)
1.ipS111L I. 1p5
--
0 20 40 60 80 100 120 140 160 180 200 220 240
RATE OF FLOW (GPM)
Curves developed from independent approval
agencies actual tests —Consult factory fordetails
indicates rated (low as determined by approval
agencies. 7.5 ft/secis the typical maximum Plumbing
system flow rate.
Apollo Valves, Manufactured by Conbraco Industries, Inc.
701 Matthews Mint-Hill Road, Matthews, NC 28105 USA
www.apollavalves.com 1 (70-4) 941-6000
Thwbn(1ln5l)eJcEonIy n 5mth(1bwn2cponl)nofthl)inMffiuutnoIkeatheutuxumr4
ab1(g,lntomaththsEerbew *&flt'iOIti IeaevMaUrweife@www,,Un(orthrnnUwm,tñ1fwmatbm
551206003/14Page2 of 2