HomeMy WebLinkAbout2251 FARADAY AVE; 150; CBC2022-0066; PermitBuilding Permit Finaled
Commercial Permit
Print Date: 05/03/2023
Job Address: 2251 FARADAY AVE, # 150, CARLSBAD, CA 92008-7209
Permit Type: BLDG-Commercial Work Class:
Parcel#: 2120610400 Track#:
Valuation: $10,000.00 Lot#:
Occupancy Group:
#of Dwelling Units:
Bedrooms:
Bathrooms:
Occupant Load:
Code Edition:
Sprinkled:
Project Title:
Project#:
Plan#:
Construction Type:
Orig. Plan Check#:
Plan Check It
Description: ABBOTT: EMERGENCY GENERATOR REPLACEMENT
Applicant:
C2 BUILDING GROUP
107 S CEDROS AVE, # STE 220
SOLANA BEACH, CA 92075-1994
(858) 232-0213
FEE
BUILDING PLAN CHECK
Property Owner:
FARADAY PROPERTY LLC
11444 W OLYMPIC BLVD
LOS ANGELES, CA 90064
BUILDING PLAN REVIEW-MINOR PROJECTS {LDE)
BUILDING PLAN REVIEW -MINOR PROJECTS (PLN)
ELEC: GENERATOR OVER 100 kW
FIRE Special Equipment (Ovens, Dust, Battery)
SB1473-GREEN BUILDING STATE STANDARDS FEE
STRONG MOTION -COMMERCIAL (SMlP)
Tenant Improvement
Total Fees: $1,547.45 Total Payments To Date: $1,547.45
Permit No:
Status:
{Cityof
Carlsbad
CBC2022-0066
Closed -Finaled
Applied: 02/28/2022
Issued: 05/03/2022
Finaled Close Out: 05/03/2023
Final Inspection: 05/01/2023
INSPECTOR: Renfro, Chris
Balance Due:
AMOUNT
$312.65
$194.00
$98.00
$481.00
$458.00
$1.00
$2.80
$0.00
Please take NOTICE that approval of your project includes the "l mposition" of fees, dedications, reservations, or other exactions hereafter
collectively referred to as "fees/exaction." You have 90 days from the date this permit was issued to protest imposition of these
fees/exactions. If you protest them, you must follow the protest procedures set forth in Government Code Section 66020(a), and file the
protest and any other required information with the City Manager for processing in accordance with Carlsbad Municipal Code Section
3.32.030. Failure to timely follow that procedure will bar any subsequent legal action ta attack, review, set aside, void, or annu I their
imposition.
You are hereby FURTHER NOTIFIED that your right to protest the specified fees/exactions DOES NOT APPLY to water and sewer connection
fees and capacity changes, nor planning, zoning, grading or other similar application processing or service fees in connection with this
project. NOR DOES IT APPLY to any fees/exactions of which you have previously been given a NOTICE similar to this, or as to which the
statute of limitation has previously otherwise expired.
Building Division Page 1 of 1
1635 Faraday Avenue, Carlsbad CA 92008-7314 I 442-339-2719 I 760-602-8560 f I www.carlsbadca.gov
r
( :i tv (r[
C,1rlslJc1d
COMMERCIAL
BUILDING PERMIT
APPLICATION
B-2
l'Lm ll1,·rk (/'-~~,..4~)-{ __ :[14:-fr'.·
Job Address 2251 Faraday Ave, Carlsbad CA 92008
Tenant Name#: Abbou l<apid Diagno!itics
1_,;1, V<Jli.w
Suite: APN: 21;1.061-04-oo -----
Lot#: 010330 Lot 7 Year Built: -----------
Year Built:_~-Occupancy: 8, r-1~_ Construction Type:_11_1-R_~
n1mx Dl'SCR1P·1101\1 or wrnuc EMEt{GENcY GENrnAToR HF:P1Acr:Mrn1
REFEH TO PREVIOUS PERMIT II: CBC2021-0261
Fire sprinklers:0YESQ NO A/C:o,'YESQNO
0 Addition/New: _____________ New SF and Use, ____ _ New SF and Use
--~----SF Other (SpccifyL~-~-SF Deck, SF Patio Cover,
OTenant Improvement: _______ SF,
-~~~SF,
Existing Use: ________ Proposed Use:-----~-
Existing Use: Proposed Use: ______ _
Ii] Other: EMERGENCY GENERATOR Rl=PLACEMENT & SLAB EXTENSION TO ACCOMMODATE NO PROPOSED CHANGE IN USE.
PRJ i\flt},RY APPL!CAI\JT
Name: Andy Darragh
Address; ,1499 Ruffin l~oad, Suite /1300
PIWPERTY OWNrn
Name: Biosite lncorpornled
Address: 9975 Summers Ridge l~oad
City: San Diego State:_c_A __ Zip: 92123 City: San Diogo State:_c_A_ ..... Zip: 92121
Phone: 619-252-4226 Phone: Bss-sos.2124
Email: sseimer@fparch.com Email: _____________________ _
Dl'.SlGi\J PiWFESSION/\l COf\JTRACTO[{ OF f<ECOl{D
Name: Andy Darragh Business Name: C2 Building Group -----~------------Address: 4499 Ruffin Road, Suite 300 Address: 107 S. Cedros Ave, Suite 220
City: San Diego State:_c_A __ .Zip: 92123 City: Solana Beach State:_c_A __ Zip: 92075
Phone: 619-252-4226 Phone: 858-354.0911
Email: sseimer@fparch.com Email: james@Obuildinggroup.com
Architect State License: c 24431 CSLB License#: 996486 Class: B -------------------------------
Carlsbad Business License# (Required): BLOsooasso-09-2018
APPLICANT CERTIFICATION: I certify that I have read the application and state that the above information is correct and that the
information on the plans is accurate. I agree to comply with all City ordinances and State laws re I a ting to building
construction.
NAME {PRINT): Andy Darragh
i
· '.i· , 02/22/2022
SIGN: ------------DATE:-------
1635 Faraday Ave Carlsbad, CA 92008 Ph: 160-602-}.719 Fax: 160-60l•8558 Email: Building@carlsb~dca.gm,
REV. 10/21
THIS PAGE REQUIRED AT PERMIT ISSUANCE PLAN CHECK NUMBER:~~~~~~~
A BUJLD!NG f'EnMll C/\N BE l',SIJU) TO !Jlf llJt /\ ~; IAIT LICU\l'1FD cor~ ITi/W!(m (JR!\ iir:orun Y OV\11\IHL ti Ii !i l'I w;OI\!
SIGNII\JG TIHS FOHJVI lS AN !\GENT FOH [ff! Irn [NTlW f\i,J /.\U fl lOHllAI [O!\l HlrU\/1 OH u.·1 l rn IS l{LflUlflLf) l'Hl()H l()
PERIVllT ISS\Jf\l\lCF.
rr (OPTION A)= I.JCEI\JSEDCOf\j"f'Ri\CH)ll DECl/\f{~;.ltWJ; · -· -· · , · · ~
I hereby a[ firm underpenaltyof perjury that I am licensed under provisions of Chapter 9 (commencing with Section 7000)of Division 3 fl
of the Business and Professions Code, and my license is in full force and effect. I also affirm underpenaltyof pe1juryoneof the ~
foil owing declarations (CHOOSE ONE): 0
_ DI have and will maintain a certificate of consent to self-insure for workers' compcmation provided by Section 3"/00 of the Labor Code, for the performance of the jj
ti •1' M work which lh1s permit is issued Policy No._____ ___ _ ____ ___ _____ _ ____ --•--·----l,
It -OR-Ii
[i ■ I have and w1\I mamtam workers compcnsallon. as required by Section 3 /00 of the I abor Code, for the performance of the work for which this permit 1s issued, G fl My workers' compensation insurance carrier and policy number are-lnsuranceCompany Name: Travelers lnSllr.ance -·· ___________________ \:
Ii: Policy No. _ _lJ_B-2S741662-21-26-G Expiration Date: _06/18/2022 ____ -____ I
! -OR-i:
fi O Certificate of Exemption: I certify that in the performance of the work for which this permit is issued, I shall not employ any person in any manner so as to become (l !l subject to the workers' compensation Laws of California. WARNING: failure to secure workers compensation coverage is unlawful and shall subject an employ~, to )!
U criminal penalties and civil fines up to $100,000.00, in addition the to the cost of compensation, damages as provided for in Section 3706 of the Labor Cade, !!
f: interest and attorney's Ices. :)
!~ !'1 ~ COI\JSTIWCTION LENDING AGU\JCY,ff /\i\lY: j:
;, I hereby affirm that there is a construction lending agency for the performance of the work this permit is issued (Sec 3091 (i) Civil Code)_ \!
r' Lender's Name:_~~--~~-_____ _ _____ lender's Address:. :/ f ll CQNTRJ\CTOR CERT/Ff CJ\ T/ON; The applicant certifies that al/ dawmen/s ond pion, cJearly and occurotely show all exi,t,ng and propo;ed burl dings, structures. access mads, and
utilities/utility eoscrncms. 1111 proposed m-od1ficotions. and/or addftioM ate cfeo,Jy lribeled on t/ie site plan. Any potetitially e
opproved for cm1str11ction ond mny be required to be altered or removed. The city'"s opprovol of the opplicatian is bused on t
dtmem•ons -of, the property, buifdmgs, :, trvdifre.s Qnd t~eff set bucks from property lines and from one another; access rood5/,
a.i statt"d i-s tme and correct; a// ease-men ts ond other encumbrance~ to development hove beer, occvrotely 5hown and labeled
ex;.sting un the-property Wl!te completed tli -accotdcrnce with o/J te-gv!Qt1on5 m ex1stenc~ at the rune of therr constwction, unless othe-rw,se noted ~
NAME (PRINT): Kevin Stamer SIGNATURE:_L-.~~~=-------DATE: 04127/2022 !!
: ~', ~~~~~,_~~~~~~~:~~:~,~:~:~~:~:~~-~s,~~~:u~~o~~~~~,~.:c.~t for the c,o~~.Ttor,;;~;l,dcr!:t!~~'~,'.~ .. •v•,,_ .. ,"''' ,• "u, ,., . , .. . ,. ~,,.,c '. :.,
fl {OPTION B}: OWNER-BUILDER [1_ECLA!Y}I!ON: ·-~
~
1 I hereby affirm that I am exempt from Contractor's License Law for £he following reason: :1, D I, .,s owner of the property or my employees with wages as their sole compensation, will do the work and the structure is not intended or offered for sale (Sec. ,
7044, Business and Professions Code: The Contractor's License Law does not apply to an owner of property who builds or improves thereon, and who does such Ir, wor!, himself or through his own employees, provided that such improvements are not intended or offered for sail', If, however, the building or improvement is sold [i
within one year of completion, the owner~builder will have the burden of proving that he did not build or improve for the purpose of sale). 1.,
-OR-I
' ~ 0 I, as owner of the property, am exclusively contracting with licensed contractors to construct the project (Sec. 7044, Business and Professions Code: l he
Contractor's License Law does not apply to an owner of property who builds or improves thereon, and contracts for such projects with contractor(s) licensed rl
pursuant to the Contractor's License I aw}. ;!
lJ -OR-1 I □~::,"'"'"""'" ,.,,;acs; aod P,orcss;oos Code o;,;,;,., ,, °"''"' o, M:, foe'"'""""' _ __ _____ ____ __ _ _ -------•-----1
I O FORM B-61 "Owner Builder Acknowledgement and Verification form" is required for any permit issued to a property owner. H !! By my signature below I acknowledge that, except for niy per5onal residence in which\ must have resided for at lea5t one year prior to completion of the t/
~ in1provernents covered by this permit, I c,111110\ legally sell a ;tructure that I have built as an owner-builder if it has not been constructed in its entirety by license cl ~.
Jl contractors, I understand that a copy of the appl icoble law, Section 7014 of the Business and Professions Code, lsavailabteupon request when this application is ~
t! submitted or at the following Web site: http;/ twww,leginfo.ca,govlcotaw.html. ;
ijl' OWNER CERT/FICA T/ON: The applicant cerlifies that all document, and plans dearly anti accurately sltow all e,isting and proposed buildings, structures, occell roads, and uW,t,es/uti/ity H
· casemeors, All proposed modifications and/or additions are clearly labeled on the site p/an. Ar,y potentially ~1<isting detail within these pluns incon,istenl with the site plun ore not approved for f,.:
construction and may berequired to be altered or removed. The city', approval oftl,e opplicolion is bated on the premise lhot the submitted documents and p/ons show the correct dimensions of; ii
ij the ptoperty, bulfdings, structures and their setbocks from properly lines and from one another; access roads/eosements, and ur,1/ties. The existmg and proposed use of eoch building as stated is true ft Md correct; all easements and other enwm/Jronces to development have been accurately shown and /ubeled as we// as oil on-site grodingjs,te preparation. All improvement, exi<ting on tl,e property I ::::•;:::):• •"" •• """""oo•" '""-" ,,. "=of'""' ="•:::•ss "~••• oo<-' DA TE:----------!]
M Note: It the person signing above is an authorized agent for the propl!rtv owner include form B-62 signed by property owner. ij
P-~-,e-c...,i:.;'.:,.,':\!';::1«f",.'":(,l~!".;.'~.~~:; c;·;~~~;)Oi,:'4"'.;1~::r ~:;.,ff;:-;-::-:,1~~:.:,,.."'-r,.:,;._"'.': ;i·;!i,¼'P/, ,:r,-,r~.,;;~r;.:.tt!;1!f"fo~;-!'.;.;::·.·:rt,7;;::.:.."":'.£r.,;~;-.;'.,".~·1.·,...-.:-t:~;n::;::-_:::l'::t·-•~-;c.:,;-'.1(r.,•f11.;1',t,.'3li,i~!''r.'.f'.&c•-ir-.: .. ;1,~,~;ir,;,..,._.tt,t,:;!".~:;.1..-.•~:~.ff:;:.:;r.:":l;'~X1l,!'t.'1",k'IM~ ... J;._~ ,:..:--:•'"•"..:., .... '!.'::: .. -.~·,:.:.~,,,_I
1635 Farnday /we Carlsbad, CA 92008 Ph: 760-602-Z"/19 Fax: 760-602-8558 Email: Building@carlsbadca,gov
2 REV. 10/21
Building Permit Inspection History Finaled
{City of
Carlsbad
PER"'1IT INSPECTION ~ISTORY for (CBC2022-0066)
Application Date: 02/28/2022 Owner: FARADAY PROPERTY LLC Permit Type: BLDG-Commercial
Work Class: Tenant Improvement Issue Date: 05/03/2022 Subdivision: CARLSBAD TCT#81-10 UNIT#01
Status: Closed -Finaled Expiration Date: 10/30/2023
lVR Number: 38968
Address: 2251 FARADAY AVE, # 150
CARLSBAD, CA 92008-7209
Scheduled Actual Inspection Type Inspection No. Inspection Primary Inspector Reinspection Inspection
Date Start Date Status
04/10/2023 04/1012023 BLDG-11 207 494-2023 Passed Chris Renfro
Foundation/Ftg/P iers
(Rebar)
Checklist Item
BLDG-Building Deficiency
NOTES Created By
Angie Teanio
COMMENTS
Partial pass on extension of pad for larger
generator. Special inspection report
collected.
TEXT
760-685-6124 Wayne
05/01/2023 05/01/2023 BLDG-34 Rough 209583-2023 Passed Chris Renfro
Wednesday, May 3, 2023
Electrical
Checklist Item
BLDG-Building Deficiency
NOTES Created By
Becky Falk
COMMENTS
TEXT
PJ 916-712-8634
BLDG-Final Inspection 209653-2023 Passed
Checklist Item
BLDG-Building Deficiency
BLDG-Structural Final
BLDG-Electrical Final
COMMENTS
Chris Renfro
Complete
Passed
Yes
Created Date
04/07/2023
Complete
Passed
Yes
Created Date
04/28/2023
Complete
Passed
Yes
Yes
Yes
Page 1 of 1
A Universal
Engineering Construction Testing & Engineering, Inc.
Sciences
Company Inspection I Testing l Geotechnical 1 Environmental & Construction Engineering I Civil Engineering I Surveying
City of Carlsbad
INSPECTION REPORT APR 1 0 2023 PAGE 1 OF 1
RECORD COPY GTE JOB NO. 4810.2300068
BUILDING DIVISl~~ORT NO.
PROJECT NAME Abbott Generator Expansion 23-005 INSPECTION MATERIAL IDENTIFICATION
ADDRESS 2251 Faraday Avenue □ CONCRETE CONC. MIX NO. & lb/in2
Carlsbad, CA 92008 ~ REINF. STEEL GROUT MIX NO. & lblin2
ARCHITECT □ MASONRY MORT AR TYPE & lb/in2
ENGINEER □ PT CONCRETE REINF. STEEL GR/SIZE
CONTRACTOR C2 Building Group □ FIELD WELDING STRUCTURAL STEEL
OTHER D&D Concrete □ SHOP WELDING HIGH-STRENGTH BOLT
INSPECTION DATE 4/7/23 □ BATCH PLANT MASONRY BLOCK
PLAN FILE/OTHER ~ EXP.ANCHOR OTHER
BLDG. PERMIT/OTHER □ OTHER
MATERIAL SAMPLING
0 CONCRETE 0 MORTAR 0 GROUT 0 FIREPROOFING O MASONRY BLOCK
0 REINFORCING STEEL 0 STRUCTURALSTEEL 0 BOLTS O OTHER
INSPECTIONS PERFORMED, MATERIAL IDENTIFICATION, PROGRESS, WORK REJECTED, REMARKS
PLEASE NOTE ANY RE-INSPECTION, TESTING, OR OTHER PROJECT ISSUES.
Arrived on site as requested. Verified compaction of bottom of footing for the generator pad expansion area. Native material was
compacted using a whacker and probed firm and unyielding, indicating sufficient compaction was achieved. Verified epoxy holes were
cleaned and drilled to proper depth. Observed installation of #5 bars at 12" o/c top and bottom, with 6" embed, using Simpson Set-3G
epoxy (ICC-ES ESR-2508, expires 1/17/25) per details 3 and 4 on Sheet S-101. Verified installation of additional reinforcing steel per
details on Sheet S1. All work complies with applicable codes and approved plans.
Certification of Compliance: All work, unless otherwise noted, complies with applicable codes and the approved plans and specifications.
PRINTED NAME Shane Kepler
CERTIFICATION NO. 9960829 SIGNATURE --------------------------
1441 Montiel Road, Suite 115 I Escondido, CA 92026 I Ph (760) 746-4955 I Fax (760) 746-9806 I www.cte-inc.net
•
Structural Calculations for
Abbott
Generator Replacement
Carlsbad, CA
February 2022
'c, 2020 M,yamoto lritemat,onal, Inc. All rights reserved This document or any part thereof must not be re
CBC2022-0066
2251 FARADAY AVE #150
ABBOTT EMERGENCY GENERATOR REPLACEMENT
2120610400
2/28/2022
CBC2022-0066
3 -'< Q)
3
0 ,-+
0 •
m1yamoto .
~
Project: ~~ ~~«.IU'0''V _ Sheet No:_l _
Project No: -~1-~__.0J_,_,,O'-----Cale. By: f-'-=<:,'---Date: ,~
ll,o, &f c,fJG
lvUflft ·. e,,~I\., k~v-t~~vt; C h,Llo~ e
4 'vt-) 9 &( ·, {i)-; ,_, q,,-J flt hs,
\ ic>V vJ~ -"-~h?l-)'n· ( t,~~1 ~ )
Mtt ( 1411160 ~" 71-b 1 p,~
f ~c,u.> 'lfr.-, ~~ l ~ o l + v't~ .,, 'L S 'f;t \~ >
~ \'(.) l, ~ 7.-,, .; )
~--ro ... 1 't -1-f ~L., 1--1.o
~ r.-. 6 ,'? ~(l7 '1:r ~ o. ~
.../a,1 /} /J,,, ~ t iv II 0 I -' 1 ·1,, ' '/7 ll, b -r -4. ,<, 41{ .,,_· l} ,. ) i. ~
~-&7, 1, 1--+ «, 4:-~ i 1o t , 1 1v~ ,::,
~r( -:: t; , f.,1-'7,& v> (p~/1,, '/ b 1 c I>~ &1~ -9 ~0 "PL.> ft
J), ~ lo/, tJt C. t
..ttJ.> '"''t 7 1 ~. ¾ 'J. \~, ~,11 ~ '\'. 1>/ (p ~ ~
u7'f, ,,,,'{ J. ,, ft v:>( ~ ~ ?;rt)
ff,.~ f 'M ~
fl JI -!.-i ~"1 , 1r > ~ .:,0 d
~ p'7'h 1 .,,,, '"'·~/7..,,,,, ., "--~ 11,v r~1 ~ .VJ)( vv-4-~ 16"5\~ ~ ~ .,~ )i 1-~1 \f... ,,. t '" 11 /17 _,,._ ~♦tgt1 'e,, c.. T' -C:J
' .
, 0,-C Hazards by Location
•• Search Information
Address:
Coordinates:
Elevation:
Tlmestamp:
Hazard Type:
Reference
Document:
Risk Category:
Site Class:
2251 Faraday Ave, Carlsbad, CA 92008, USA
33.1336965, -117 .27734 79
300 ft
2021-07 -16T02:02: 17 .2502
Seismic
ASCE7-16
II
0-default
Basic Parameters
Name Value Description
Ss 0.971 MCER ground motion (perlod=0.2s)
s, 0.355 MCER ground motion (perlod=1 .0s)
SMs 1.165 Site-modified spectral acceleration value
SM1 * null Site-modified spectral acceleration value
Sos 0.777 Numeric seismic design value at 0.2s SA
So1 • null Numeric seismic design value at 1.0s SA
* See Section 11.4.8
... Additional Information
Name Value Description
SDC • null Seismic design category
Fa 1.2 Site amplification factor at 0.2s
Fv * null Site amplification factor at 1.0s
CRs 0.902 Coefficient of risk (0.2s)
CR1 0.911 Coefficient of risk (1.0s)
PGA 0.424 MCEG peak ground acceleration
FPGA 1.2 Site amplification factor at PGA
PGAM 0.508 Site modified peak ground acceleration
. "j' -Tem.ecula
l
ap data @2021 Google, INEGI
TL 8
... RT
~ 0.971
SsUH 1.077
SsD 1.5
S1RT 0.355
S1UH 0.389
S10 0.6
PGAd 0.5
* See Section 11.4.8
Long-period transition period (s)
Probabilistic risk-targeted ground motion (0.2s)
Factored uniform-hazard spectral acceleration (2% probability of
exceedance In 50 years)
Factored deterministic acceleration value (0.2s)
Probabilistic risk-targeted ground motion (1.0s)
Factored uniform-hazard spectral acceleration (2% probability of
exceedance in 50 years)
Factored determlnlstlc acceleration value (1.0s)
Factored deterministic acceleration value (PGA)
The results indicated here DO NOT reflect any state or local amendments to the values or any delineation lines made during the building
code adoption process. Users should confirm any output obtained from this tool with the local Authority Having Jurisdiction before
proceeding with design.
Disclaimer
Hazard loads are provided by the U.S. Geological Survey Seismic Desian Web Services.
While the information presented on this website is believed to be correct, ATC and its sponsors and contributors assume no responsibility
or liability for its accuracy. The material presented In the report should not be used or relied upon for any specific application without
competent examination and verification of its accuracy, suitability and applicability by engineers or other licensed professionals. ATC does
not Intend that the use of this information replace the sound judgment of such competent professionals, having experience and knowledge
in the field of practice, nor to substitute for the standard of care required of such professionals In interpreting and applying the results of the
report provided by this website. Users of the information from this website assume all liability arising from such use. Use of the output of
this website does not imply approval by the governing building code bodies responsible for building code approval and interpretation for the
building site described by latitude/longitude location in the report.
www.hilti.com
Company:
Specifier:
Address:
Phone I Fax:
E-Mail:
Specifier's comments:
1 Input data
Anchor type and diameter:
Effective embedment depth:
Material:
Evaluation Service Report:
Issued I Valid:
Proof:
Stand-off installation:
Anchor plate:
Profile:
Base material:
Installation:
Reinforcement:
Seismic loads (cat. C, D, E, or F)
Kwik Bolt TZ · SS 304 3/4 (3 3/41
het,act = 3.750 in., hnom = 4.313 in.
AISI 304
ESR-1917
11112020 I 51 112021
Design method ACI 318-14 / Mech.
eb = 0.000 in. (no stand-off); t = 0.500 in.
•=iiS•• Profis Anchor 2.9.4
Page:
Project:
Sub-Project I Pos. No.:
Date: 2/14/2022
Ix x ly x t = 3.000 in. x 3.000 in. x 0.500 in .; (Recommended plate thickness: not calculated
Round bars (AISC), 1/16; (L x W x T) = 0.063 in. x 0.063 in.
cracked concrete, 3000, fc' = 3,000 psi; h = 15.000 in.
hammer drilled hole, Installation condition: Dry
tension: condition B, shear: condition B; no supplemental splitting reinforcement present
edge reinforcement: none or < No. 4 bar
Tension load: yes (17.2.3.4.3 (d))
Shear load: yes (17.2.3.5.3 (c))
R -The anchor calculation is based on a rigid anchor plate assumption.
Geometry [in.] & Loading [lb, in.lb]
z
Input data and results must be cllecked ror agreement w~h the existing conditions and for plaus1b1lltyl
PROFIS Anchor ( c) 2003-2009 Hilti AG, FL-9494 Schaen Hilli is a registered Trademark of Hilti AG, Schaen
,:,,s.,
www.hilti.com Profis Anchor 2.9.4
Company: Page: 2
Specifier: Project:
Address: Sub-Project I Pas. No.:
Phone I Fax:
E-Mail:
2 Load case/Resulting anchor forces
Load case: Design loads
Anchor reactions [lb]
Tension force: (+ Tension, -Compression)
Date:
Anchor Tension force Shear force Shear force x Shear force y
1 1,000 1,000 0 1,000
max. concrete compressive strain: -[%o]
max. concrete compressive stress: -[psi]
resulting tension force in (x/y)=(0.000/0.000): 1,000 [lb]
resulting compression force in (x/y)=(0.000/0.000): 0 [lb]
Anchor forces are calculated based on the assumption of a rigid anchor plate.
3 Tension load
Load Nua [lb] Capacity ♦ Nn [lb]
Steel Strength* 1,000 18,041
Pullout Strength* 1,000 4,331
Concrete Breakout Strength** 1,000 4,249
* anchor having the highest loading **anchor group (anchors in tension)
3.1 Steel Strength
N,a = ESR value refer to ICC-ES ESR-1917
$ Nsa ~ Nua ACI 318-14 Table 17.3.1.1
Variables
A,e.N [in.2] futa [psi]
0.24 101,500
Calculations
Nsa [lb]
24,055
Results
N,a [lb] $ steel ~ nonductile $ N,a [lb] Nua [lb]
24,055 0.750 1.000 18,041 1,000
3.2 Pullout Strength
Npn,I, = Np,2500 A a (fc'/2500)05 refer to ICC-ES ESR-1917
$ Npn.(, ~ Nua ACI 318-14 Table 17.3.1.1
Variables
f~ [psi] "-a Ne.2500 [lb)
3,000 1.000 8,110
Calculations
(fc'/2500)0 5
1.095
Results
N~ni, [lb] $ concrete $ seismic $ nonductile $ N~nl, [lb]
8,884 0.650 0.750 1.000 4,331
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROF IS Anchor ( c) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilli AG, Schaan
2/14/2022
y
X
Utilization 13N = Nu.I♦ Nn Status
6 OK
24 OK
24 OK
Nua [lb]
1,000
\
~ 'www.hilti.com
Company:
Specifier:
Page:
Project:
Address: Sub-Project I Pos. No.:
Phone I Fax:
E-Mail:
3.3 Concrete Breakout Strength
Neb = (.:::) lj/ ed,N lj/ c,N ljl cp,N Nb
$ Neb ~ Nua
ANc see ACI 318-14, Section 17.4.2.1, Fig. R 17.4.2.1(b)
ANc0 = 9 h~f
lJI ec,N = ( 1 + ~ eN) $ 1.0
3 het
w ed.N = o. 7 + o.3 U~s~:J s 1.0
= MAX(ca,mm 1.5h0,) 1 O
\JI cp,N Cac ' Cac $ .
Nb = kc A a ~ h~r5
Variables
h81 [in.] ec,,N [in.]
3.750 0.000
Cac [in.] kc
7.000 24
Calculations
ANc [in.2] ANc0 [in.2]
119.53 126.56
Results
Neb [lb] cli concrete
8,715 0,650
ec2,N [in.]
0.000
J.. a
1.000
ljl ec1,N
1.000
$ se1sm1e
0.750
Date:
ACI 318-14 Eq. (17.4.2.1a)
ACI 318-14 Table 17.3.1.1
ACI 318-14 Eq. (17.4.2.1c)
ACI 318-14 Eq. (17.4.2.4)
ACI 318-14 Eq. (17.4.2.5b)
ACI 318-14 Eq. (17.4.2.7b)
ACI 318-14 Eq. (17.4.2.2a)
Ca,m,n [in.] \jl c,N
5.000 1.000
(C [psi]
3,000
IJI ec2,N lj/ ed,N
1.000 0.967
4> nonduct1le cj, Neb [lb]
1.000 4,249
Input data and results must be checked for agreement with the exlsltng conditions and for plaus,bilrtyl
PROFtS Anchor ( c) 2003-2009 Hilti AG, FL-9494 Schaan H1lt1 is a registered Trademark of Hilt, AG, Schaan
lj/ cp.N
1.000
Nua [lb]
1,000
1:115;.1
Profis Anchor 2.9.4
3
2/14/2022
Nb [lb]
9,546
• www.hilti.com
Company:
Specifier:
Page:
Project:
i=iiS~•
Profis Anchor 2.9.4
4
Address: Sub-Project I Pos. No.:
Phone I Fax: Date:
E-M ail:
4 Shear load
Load Vua [lb] Capacity ♦ Vn [lb]
Steel Strength* 1,000 8,379
Steel failure (with lever arm)* N/A NIA
Pryout Strength** 1,000 12,201
Concrete edge failure in direction •• N/A NIA
• anchor having the highest loading ••anchor group (relevant anchors)
4.1 Steel Strength
Vsa,eq = ESR value
$ Vsteel ~ Vua
refer to ICC-ES ESR-1917
ACI 318-14 Table 17.3.1.1
Variables
Ase.v [in.2]
0.24
Calculations
Vsa.eq [lb]
12,890
Results
Vsa.eq [lb)
12,890
4.2 Pryout Strength
futa [psi]
101 ,500
$ sleel
0.650
Vcp = kcp [ (t::) ljl ed.N \j/ c,N \II cp.N Nb]
$ Vcp ~ Vua
av,seis
0.820
$ nonductile
1.000
ANc see ACI 318-14, Section 17.4.2.1, Fig. R 17.4.2.1(b)
ANcO = 9 h~r
41 ec,N = ( 1 + ~ e~) ~ 1.0
3 her
\j/ ed,N = 0.7 + 0.3 ( ~S~:J ~ 1.0
= MAX(ca.min 1.5het) < 1 _0 \j/ cp,N Cac ' Cac -
Nb = kc t..a ~ h~;5
Variables
kcp
2
41 c,N
1.000
Calculations
ANc [in.2]
119.53
Results
Vcp [lb]
17,430
her [in.]
3.750
Cac [in.]
7.000
ANco [in.2]
126.56
4> concrete
0.700
ec1.N [in.]
0.000
kc
24
41 ec1.N
1.000
$ seismic
1.000
$ Vsa [lb] Vua [lb]
8,379 1,000
ACI 318-14 Eq. (17.5.3.1a)
ACI 318-14 Table 17.3.1.1
ACI 318-14 Eq. (17.4.2.1c)
ACI 318-14 Eq. (17.4.2.4)
ACI 318-14 Eq. (17.4.2.5b)
ACI 318-14 Eq. (17.4.2.7b)
ACI 318-14 Eq. (17.4.2.2a)
e02,N [in.] Ca,min [in.]
0.000 5.000
t,. a f~ [psi]
1.000 3,000
ljl ec2.N \j/ ed.N
1.000 0.967
~ nonductile $ Vcp [lb]
1.000 12,201
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c) 2003-2009 Hilti AG. FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
2/14/2022
Utilization Pv = Vual♦ Vn Status
12 OK
N/A N/A
9 OK
NIA N/A
ljl cp.N Nb [lb]
1.000 9,546
Vua [lb]
1,000
~
www.hilti.com
Company:
Specifier:
Address:
Phone I Fax:
E-Mail:
5 Combined tension and shear loads
Pv
0.235 0.119 5/3
6 Warnings
•=iiS•• Profis Anchor 2.9.4
Page: 5
Project:
Sub-Project I Pos. No.:
Date: 2/14/2022
Utilization PN.v [%] Status
12 OK
The anchor design methods in PROFIS Anchor require rigid anchor plates per current regulations (ETAG 001/Annex C, EOTA TR029, etc.). This
means load re-distribution on the anchors due to elastic deformations of the anchor plate are not considered -the anchor plate is assumed to be
sufficiently stiff, in order not to be deformed when subjected to the design loading. PROFIS Anchor calculates the minimum required anchor plate
thickness with FEM to limit the stress of the anchor plate based on the assumptions explained above. The proof if the rigid anchor plate
assumption is valid is not carried out by PROFIS Anchor. Input data and results must be checked for agreement with the existing conditions and
for plausibility!
Condition A applies when supplementary reinforcement is used. The <I> factor is increased for non-steel Design Strengths except Pullout Strength
and Pryout strength. Condition B applies when supplementary reinforcement is not used and for Pullout Strength and Pryout Strength. Refer to
your local standard.
• Refer to the manufacturer's product literature for cleaning and installation instructions.
Checking the transfer of loads into the base material and the shear resistance are required in accordance with ACI 318 or the relevant standard!
An anchor design approach for structures assigned to Seismic Design Category C, D, E or Fis given in ACI 318-14, Chapter 17, Section
17.2.3.4.3 (a) that requires the governing design strength of an anchor or group of anchors be limited by ductile steel failure. If this is NOT the
case, the connection design (tension) shall satisfy the provisions of Section 17.2.3.4.3 (b), Section 17.2.3.4.3 (c), or Section 17.2.3.4.3 (d). The
connection design (shear) shall satisfy the provisions of Section 17.2.3.5.3 (a), Section 17.2.3.5.3 (b), or Section 17.2.3.5.3 (c).
Section 17.2.3.4.3 (b) / Section 17.2.3.5.3 (a) require the attachment the anchors are connecting to the structure be designed to undergo ductile
yielding at a load level corresponding to anchor forces no greater than the controlling design strength. Section 17.2.3.4.3 (c) I Section 17.2.3.5.3
(b) waive the ductility requirements and require the anchors to be designed for the maximum tension/ shear that can be transmitted to the
anchors by a non-yielding attachment. Section 17.2.3.4.3 (d) I Section 17.2.3.5.3 (c) waive the ductility requirements and require the design
strength of the anchors to equal or exceed the maximum tension / shear obtained from design load combinations that include E, with E increased
by roo-
Hilti post-installed anchors shall be installed in accordance with the Hilti Manufacturer's Printed Installation Instructions (MPII). Reference ACI
318-14, Section 17.8.1.
Fastening meets the design criteria!
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG. Schaan
I ,•
www.hilti.com
Company:
Specifier:
Address:
Phone I Fax:
E-Mail:
7 Installation data
Anchor plate, steel: -
Profile: Round bars (AISC), 1 /16; (L x W x T) = 0.063 in . x 0.063 in.
Hole diameter in the fixture: d1 = 0.813 in.
Plate thickness (input): 0.500 in.
Recommended plate thickness: not calculated
Drilling method: Hammer drilled
Cleaning: Manual cleaning of the drilled hole according to instructions
for use is required.
7 .1 Recommended accessories
Drilling
Suitable Rotary Hammer
• Properly sized drill bit
Coordinates Anchor in.
Anchor x y
1 0.000 0.000
c .•
Cleaning
• Manual blow-out pump
y
1.500
-~
I \
)
1.500
C.
5.000
Input data and results must be checked for agreement with the existing conditions and for plausibility!
,:iis.,
Profis Anchor 2.9.4
Page: 6
Project:
Sub-Project I Pos. No.:
Date: 2/14/2022
Anchor type and diameter: Kwik Bolt TZ -SS 304 3/4 (3 3/4)
Maximum installation torque: 1,320.002 in.lb
Hole diameter in the base material: 0.750 in.
Hole depth in the base material: 4.500 in.
Minimum thickness of the base material: 8.000 in.
Setting
• Torque wrench
• Hammer
1.500
0 0 0 0 ~ ~
~ ~
-7 X
0 0 0 0 ~ ~
~ ~
1.500
PROFIS Anchor ( c) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
• •=iiS•• www.hilti.com Profis Anchor 2.9.4
Company: Page: 7
Specifier: Project:
Address: Sub-Project I Pos. No.:
Phone I Fax: Date: 2/14/2022
E-Mail:
8 Remarks; Your Cooperation Duties
• Any and all information and data contained in the Software concern solely the use of Hilti products and are based on the principles, formulas and
security regulations in accordance with Hilti's technical directions and operating, mounting and assembly instructions, etc., that must be strictly
complied with by the user. All figures contained therein are average figures, and therefore use-specific tests are to be conducted prior to using
the relevant Hilti product. The results of the calculations carried out by means of the Software are based essentially on the data you put in.
Therefore, you bear the sole responsibility for the absence of errors, the completeness and the relevance of the data to be put in by you.
Moreover, you bear sole responsibility for having the results of the calculation checked and cleared by an expert, particularly with regard to
compliance with applicable norms and permits, prior to using them for your specific facility. The Software serves only as an aid to interpret norms
and permits without any guarantee as to the absence of errors, the correctness and the relevance of the results or suitability for a specific
application.
You must take all necessary and reasonable steps to prevent or limit damage caused by the Software. In particular, you must arrange for the
regular backup of programs and data and, if applicable, carry out the updates of the Software offered by Hilti on a regular basis. If you do not use
the AutoUpdate function of the Software, you must ensure that you are using the current and thus up-to-date version of the Software in each case
by carrying out manual updates via the Hilti Website. Hilti will not be liable for consequences, such as the recovery of lost or damaged data or
programs, arising from a culpable breach of duty by you.
Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
..
IV DIESE[ GENERATOR SETS
•
frn,1gs:> shown mr1v not reflect .1ctw1I conligl1rat1on
BENEFITS & FEATURES
CAT® GENERATOR SET PACKAGE
Cat generator set packages have been fully prototype tested and
certified torsional vibration analysis reports are ava ilable. The
packages are designed to meet the NFPA 110 requ irement for loading,
conform to the ISO 8528-5 steady state and fill transient response
requirements.
CAT DIESEL ENGINES
The four-cycle Cat diesel engine combines consistent performance
with excellent fuel economy and transien t response that meets or
exceeds ISO 8528-5. The engines feature a reliable, rugged, and
durable design that has been field proven in thousands of app lications
worldwide in emergency standby installations.
COOLING SYSTEM
The cooling system has been designed and tested to ensure proper
genera tor set co oling, and includes the radiator, fan, bel ts, and all
guarding installed as standard. Contact your Cat dealer for specific
ambient and altitude capabilities.
GENERATORS
The generators used on Cat packages have been designed and
teste d to work with the Cat engine. The generators are built with
robust Class H insulation and provide industry-leading motor starting
capability and altitude capabi lities.
EMCP CONTROL PANELS
The EMCP controller features the reliability and durability you have to
come to expect from your Cat equipment. The EMCP 4 is a scalable
control platform designed to ensure reliable generator set operation,
providing extensive information about power output and engine
operation. EMCP 4 systems can be further customized to meet your
needs through programming and expansion modules.
LEHE1773-07
550 ekW -750 ekW
60 Hz
Standby
550 ekW
600 ekW
650 ekW
700 ekW
750 ekW
SPECIFICATIONS
ENGINE SPECIFICATIONS
Prime
500 ekW
545 ekW
600 ekW
635 ekW
680 ekW
Engine Model Cat® C18 ACERT In-line 6, 4-cycle diesel
Bore x Stroke 145mm x 183mm (5.7in x 7.2in)
Disp lacement 18.1 L (1106.3 in3)
Compression Ratio 14.5:1 (550-600 ekW);
14:1 (650-750 ekW)
Aspiration Turbocharged Air-to-Air Aftercooled
Fuel Injection System Electronic Unit Injection
Governor Electronic ADEM™ A4
Emission Certifications EPA TIER II
GENERATOR SET SPECIFICATIONS
Alternator Design Brushless Single Bearing, 4 Pole
Stator 2/3 Pitch
No. of Leads 6/12
Avai lable Voltage Options 600V/480V/240V/220V/208V
Frequency 60Hz
Alternator Voltage 24V
Alternator Insulation & IP Class H; IP23
Standard Temperature 125/130 Deg C Rise
Availab le Excitation Sel f-Excited, AREP Options
Voltage Regulation, ~1% Steady State+/-
1/9
DIESEi: GENERATOR SETS
' STANDARD EQUIPMENT OPTIONAL EQUIPMENT
Air inlet system Aftercooler core
Turbocharger Air inlet system Dual Element air cleaner
Heavy Duty Canister air filters
EMCP4.2B con trol panel EMCP 4.4
Control panels Standard breaker
• 3 Pole
Local Annunciator
Annunciators Box
• Right mounted power centre
Radiator and cooling fan with belt guards Control panels Remote E-Stop button
Discrete 1/0 Module
Thermostats and housing Volt Free Contact
Coolan t leve l sensor Ea rth (Ground) Fault Relay
Cooling system Coolant level sight gauge
Jacket water pump, gear driven
Remote Monitoring Software
CAT Connect Connectivity-Ethernet, Cellular, Satellite
Coolant drain valve; terminated on edge of base
Cooling system filled with Caterpillar Extended
Life Coolant
Telematics PL444 4G LTE
Telematics PLG601, PLG641
Single LSI motorised Circuit Breaker
Circuit Breakers External Paralleling
Auxiliary Contacts
Exhaust system Exhaust manifold; dry Neutral Bar (208V)
Primary fuel filter w/integral water separator & Sound Attenuated (SA)
secondary filter Enclosures Weather Protective
Fuel system Fuel cooler
Fuel priming pump
Flexible fuel lines
Engine fuel transfer pump
Aluminium Enclosure
Coolant Heater
Cooling system Jacket water heater with pump
Stone guards
Brushless, self-excited 2/3 pitch, random wound
Generators IP23 Protection
and generator Insulation Class H and temperature rise
attachments Power centre, IP22 bottom cable entry
Segregated low voltage wiring pane
Audio & Visual Fuel Alarm
Base/Fuel Tank Sub Base Dual Wall Fuel Tank: 660, 1000, 1900.
2200, 2640 gal
Fuel System Integral 8hr Tank Base
Sub Tank Bases: 24Hr & 48Hr
Narrow skid base
Mounting System Generator mounting & Duct Plate
Anti-vibration mounts (Non-captive)
Overspeed
Generators PMG, AAEP
Oversize and generator Coastal Protection (CIP) attachments Space Heater Control
Protection High coolant temperature shutdown
System Low oil pressure shutdown
Low Coolant level shu tdown
Starting/ Standard Battery Set
charging system Oversize Battery Set
UL2200 Listed
Starting/charging 24-Volt Electric Starting Motor
24V, 45 amp charging alternator system Battery rack & cab les
Certifications CSA 22.2
Certification of Compliance -IBC Seismic
Dua l IBC & OSHPO
Certifications EPA Stationary Emergency Use General Tool Set
WEIGHTS & DIMENSIONS
Standby Dim"A" Dim "B" Dim "C" Generator
Set Weight Ratings mm(in) mmlin) mm(inl l1g (lb)
550 ekW
600 ekW 3477 (137) 1628 (65) 2102 (83) 4431 (9769)
650 ekW
◄--e ~--► 700ekW 3512 (138) 1746 (69) 2322 (92) 4863 (10721)
Note: General configuration not to be used for installation. 750 ekW
See general dimension drawings for detail. Note: Weights & Dimensions are for open set on skid base.
LEHE1773-07 2/9
ATTACHMENTS
Picture shown may not represent actual package.
Features
C18 Sub-Base Fuel
Tanks
US Sourced
Diesel Generator Set
350 -750 ekW 60 Hz
• UL Listed for United States (UL 142) and Canada (CAN/ULC S601)
• Facilitates compliance with NFPA 30 code, NFPA 37 and 110 standards and CSA C282 code
• Dual wall
• Lockable fuel fill cap, 4" (101 .6 mm) NPT
• Low fuel level warning standard, customer configurable warning or shutdown
• Primary tank leak detection switch in containment basin
• Tank design provides capacity for thermal expansion of fuel
• Fuel supply dip tube is positioned so as not to pick up fuel sediment
• Fuel return and supply dip tube is separated by an internal baffle to prevent immediate re-supply of heated
return fuel
• Pressure washed with an iron phosphate solution
• Interior tank surfaces coated with a solvent-based thin-film rust preventative
• Heavy gauge steel gussets with internal lifting rings
• Primary and secondary tanks are leak tested at 20.7 kPa (3 psi) minimum
• Compatible with open packages and enclosures
• Gloss black polyester alkyd enamel exterior paint
• Welded steel containment basin (minimum of 110% of primary tank capacity)
• Direct reading fuel gauge with variable electrical output
• Emergency vents on primary and secondary tanks are sized in accordance with NFPA 30
Sub-Base
• The Sub-Base fuel tank mounts below the generator set wide base
Integral
• Integral diesel fuel tank is incorporated into the generator set base frame
• Robust base design includes linear vibration isolators between tank base and engine generator
Options
• Audio/visual fuel level alarm panel
• 5 gal (18 .9 L) spill containment
• 5 gal (18 .9 L) spill containment with fuel fill drop tube with in 6" (152 mm) from bottom of tank
• 5 gal (18.9 L) spill containment with overfill prevention valve and fuel fill drop tube with in 6" (152 mm) from
bottom of tank
• ULC Listed 7.5 gal (28.4 L) spill containment with vent extensions, vent whistle, and drop tube facilitating
compliance with CSA B 139-09
• ULC Listed 7.5 gal (28.4 L) spill containment with overfill prevention valve, vent extensions, vent whistle
and drop tube facilitating compliance with CSA 8139-09
LEHE0467-09 Page 1 of 5
ATTACHMENTS
Sub-Base Fuel Tank Base Useable Capacities with Fuel Tank
Dimensions & Weights
Sub-base -Width(W) 2056 mm (81 in)
Sub-base*-Width(W) 2357 mm (92.?in)
Sound Attenuated Enclosure
Total Useable Tank Only
Capacity Capacity Dry Weight Height 'H' Length 'L'
C13 Tank Feature
Design Code Liter Gallon Liter Gallon kg lb mm In mm in
Integral FTDW013 2646 699 2540 671 1569 3450 762 30.0 5461 215.0
Sub-Base FTDW0051 3941 1041 3876 1024 1659 3657 635 25.0 5550 218.5
Sub-Base FTDW006 6980 1844 6818 1801 2033 4483 889 35.0 6184 243.5
Sub-Base FTDW007 8339 2203 8244 2178 2292 5052 889 35.0 7074 278.5
Sub-Base FTDW011 2476 654 2435 643 1468 3236 635 25.0 3810 150.0
Total Useable Tank Only
Capacity Capacity Dry Weight Height 'H' Length 'L'
C15 Tank Feature
Design Code Liter Gallon Liter Gallon kg lb mm in mm In
Integral FTDW001 1283 339 1262 333 1015 2237 639 25.0 4746 186.9
Sub-Base FTDW0051 3941 1041 3876 1024 1659 3657 635 25.0 5550 218.5 FTDW016
Sub-Base FTDW006 6980 1844 6818 1801 2228 4912 889 35.0 6184 243.5
Sub-Base FTDW011 2476 654 2435 643 1468 3236 635 25.0 3810 150.0
Sub-Base FTDW034 10887 2876 9899 2615 2847 6277 914 36 7747 305
Total Useable Tank Only
Capacity Capacity Dry Weight Height 'H' Length 'L'
C18 Tank Feature
Design Code Liter Gallon Liter Gallon kg lb mm In mm in
Integral FTDW003 1446 382 1422 376 1015 2237 635 25.0 3814 150.1
Integral• FTDW030 2498 660 2381 629 1681 3703 762 30.0 4995 196.6
Integral' FTDW031 5175 1367 4997 1320 2046 4510 762 30.0 6737 265.3
Sub-Base FTDW005 3941 1041 3876 1024 1659 3657 635 25.0 5550 218.5
Sub-Base FTDW007 8339 2203 8244 2178 2150 4134 889 35.0 7074 278.5
Sub-Base FTDW011 2476 654 2435 643 1468 3236 635 25.0 3810 150.0
Sub-Base• FTDW032 10228 2702 9994 2640 2638 5816 889 35.0 7368 290
"For Ratings 650, 700 &750 ekW only
LEHE0467-09
Overall Package Height with
Tank
Open Enclosure
mm in mm in
NA NA 2743 108.0
NA NA 2955 116.3
NA NA 3209 126.3
NA NA 3209 126.3
NA NA 2955 116.3
Overall Package Height with
Tank
Open Enclosure
mm in mm In
NA NA 2619 103.0
NA NA 2955 116.3
NA NA 3209 126.3
NA NA 2955 116.3
NA NA 3233 127.3
Overall Package Height with
Tank
Open Enclosure
mm in mm In
NA NA 2560 100.8
2670 105 2675 105.3
NA NA 2675 105.3
NA NA 2905 114.3
NA NA 3209 126.3
NA NA 2905 114.3
NA NA 3132 123.3
Page 3 of 5
ATTACHMENTS CAJ®
, C,
00
lL JJ
The heights listed above do not include lumber used during manufacturing and shipping.
Estimated Run Times (Hours) at 100% Load
C13 Tank Standby Ratings (ekW) Prime Ratings (ekW)
Design Feature Code 400 350 --350 320 --
Integral Tank FTDW013 24 27 --25 29 --
Sub-Base FTDW005 / FTDW016 36 41 --38 43 --
Sub-Base FTDW006 65 72 --72 77 --
Sub-Base FTDW007 77 87 --81 93 --
Sub-Base FTDW011 23 25 --24 27 --
C15 Tank Standby Ratings (ekW) Prime Ratings (ekW)
Design Feature Code 500 450 400 350 455 410 365 320
Integral Tank FTDW001 / FTDW002 9 9 11 11 10 10 11 12
Sub-Base FTDW005 / FTDW016 28 29 32 36 30 31 35 38
Sub-Base FTDW006 50 52 57 63 54 56 62 67
Sub-Base FTDW008 / FTDW011 17 18 20 22 19 20 22 24
Sub-Base FTDW034 72 75 82 91 78 81 90 97
C18 Tank Standby Ratings (ekW) Prime Ratings (ekW)
Design Feature Code 750 700 650 600 550 680 635 600 545 500
Integral FTDW003 / FTDW004 ---8 g ---9 10
Integral* FTDW030 11 12 13 --12 13 14 --
Integral* FTDW031 24 25 27 --26 27 29 33 36
Sub-Base FTDW005 ---24 25 ---25 27
Sub-Base FTDW007 ---51 54 ---54 59
Sub-Base FTDW008 / FTDW011 ---15 16 ---16 17
Sub-Base• FTDW032 49 51 54 --53 55 58 --
•For Ratings 650, 700 &750 ekWonly
LEHE0467-09 Page 4 of 5
' , l evel 1 Sound Attenuated Enclosure (Steel) Sound Levels
Cooling Air Flow Rate Ambient Capability* Sound Pressure Levels
Model Standby eKW (dBA) at 7m (23 ft)
m3/s cfm "C 'F 100% Load
350 8.5 18010 57 135 74 C13 400 8.5 180 10 56 133 75
350 10.4 22072 59 138 73
400 10.4 22072 51 124 73 C15 450 10.4 22072 46 115 74
500 12.5 26415 48 118 75
550 8.1 17234 45 113 75
600 8.1 17234 43 109 75
C18 650 12.7 26909 51 123 75
700 12.7 26909 48 118 75
750 12.7 26909 48 118 75
Sound Attenuated Enclosure (Aluminum) Sound Levels
Cooling Air Flow Rate Ambient Capability* Sound Pressure Levels
Model Standby eKW (dBA) at 7m (23 ft)
m3/s cfm "C "F 100% Load
350 8.5 -57 135 75 C13 400 8.5 -56 133 75
350 10.4 22072 59 138 72
400 10.4 22072 51 124 73 C15 450 10.4 22072 46 115 74
500 12.5 26415 48 118 75
550 8.1 17234 45 113 76
600 8.1 17234 43 109 76
C18 650 12.7 26909 51 123 76
700 12.7 26909 48 118 76
750 12.7 26909 48 118 76
LEHE0465-08 2/7
lliii -.-u-■vvv■-vu--------------------------------,
~
Level 2 Sound Attenuated Enclosure (Steel) Sound Levels
Cooling Air Flow Rate Ambient Capability* Sound Pressure Levels
Model Standby eKW (dBA) at 7m (23 ft)
m3/s cfm oc OF 100% Load
350 7.2 15256 50 122 70 C13 400 7.2 15256 50 122 70
350 10.4 22071 50 122 72
400 10.4 22071 50 122 72 C15 450 10.4 22071 50 122 72
500 12.5 26415 50 122 72
*Cooling system performance at sea level. Consult your Ca dealer for site specifi c ambient and altitude capabilities.
Note: Sound level measurements are subject to instrumentation, installation and manufacturing variability, as we ll as ambient site conditions.
Component Weights to Calculate Package Weight
Narrow Skid Base Wide Skid Base Sound Attenuated Sound Attenuated Standby Enclosure (Steel) Enclosure (Aluminum) Model eKW
kg lb kg lb l<g lb kg lb
350 C13 253 578 579 1276 1245 2745 765 1687 400
350
400 C15 273 602 465 1025 1245 2745 765 1687 450
500
550 301 664 466 1027 1301 2868 817 1801 600
C18 650
700 286 630 637 1404 1393 3071 887 1955
750
Sound Attenuated Enclosure on Skid Base
Length "L" Width "W" Height "H"
Model Standby eKW mm in mm in mm in
350 C13 4948 194.8 2014 79.3 2320 91.3 400
350
400 C15 4948 194.8 2014 79.3 2320 91.3 450
500
550 5183 204.0 2014 79.3 2262 89.0 600
C18 650
700 5230 205.9 2315 91 .1 2253 88.7
750
LEHE0465-08 3/7
....--,-=,.-wu-■-v-..a,u ■-...,..,,-----------~------------------,
.,
ound Attenuated Enclosure on a UL Listed Integral Fuel Tank Base
--LlNC1H (LI
e.-----p.....J
,,-.--.....
ti t~ Ii
@ =
HllG
.. el ll fEl ! f El -iS .. ..
Hl (H\
-~ ~ 1~ t~
-= -
' . .
' ' ' '
-WIDTH (W)
Model Standby eKW Length "L" Width "W" Height "H"
mm in mm in mm in
350 C13 5461 215.0 2014 79 .3 2743 108.0 400
350
400 C15 4948 194.8 2014 79.3 2619 103.0 450
500
550 5187 204.2 2014 79.3 2561 101 .0 600
C18 650
700 6977 274.7 2315 91.1 2675 105.3
750
LEHE0465-08 4/7
, 6 ound Attenuated Enclosure on a UL Listed 660 Gallon Sub-Base Fuel Tank Base
LENGTH Ill
~
11.
Ill
I : I f lB I f lB : flB
""'"' It!)
I ~
c::, ' V ' I u ·I· '
1----Vll>THCW) ---J
Length "L" Width "W" Height "H" Model Standby eKW mm in mm in mm in
350 C13 4948 194.8 2056 80.9 2955 116.3 400
350
400 C15 4948 194.8 2056 80.9 2955 116.3 450
500
550 C18 5184 204.1 2056 80.9 2897 114.1 600
LEHE0465-08 5/7
... -.-..-.--u ■1-1DJ11c.-------------------------------,
,-•Sound Attenuated Enclosure on a UL Listed 1000 Gallon Sub -Base Fuel Tank Base
_...,.__.
.~
.1 ! ~
fol = " ~ ~ TEl e ~El " Tt:3 " ..
T (HJ
I
'--'-~ ( i II~
-~
~
I· , I . I ' '
~
I LENG1 H (l) --WOTH IWJ--
Length "L" Width "W" Height "H" Model Standby eKW mm in mm in mm in
350 C13 5751 226.4 2056 80.9 2955 116.3 400
350
400 C15 5751 226.4 2056 80.9 2955 116.3 450
500
550 C18 5747 226.3 2056 80.9 2897 114.1 600
LEHE0465-08 6/7
SAN DIEGO REGIONAL
HAZARDOUS MATERIALS
QUESTIONNAIRE
Abbott Rapid Diagnostics
Project Address (include suite)
2251 Faraday Ave, Carlsbad, CA 92008
Mailing Address (include suite)
2251 Faraday Ave, Car1sbad. CA 92008
Business Contact
Raymond Rice
City
San Diego
City
CMsbad
Applicant E-mail
RECORD ID#
PLAN CHECK#
State
CA
State
CA
OFFICE USE ONLY
BP DATE
Telephone#
442-339-07 49
Zip Code APN#
92008 212-061-04-00
Zip Code Plan File#
92006
Telephone# Project Contact
Abby Fan-ell alarrell@fpbarch.com 41 !>827-8504
Tho following questions represent the facility's activities, NOT the specific project description.
PART I: FIRE DEPARTMENT -HAZARDOUS MATERIALS DIVISION: OCCUPANCY CLASSIFICATION: (not required for projects within the City of San
Diego): Indicate by circling the item, whether your business will use, process, or store any of the following hazardous materials. If any of the items are circled,
applicant must contact the Fire Protection Agency with jurisdiction prior to plan submittal.
Occupancy Rating: B, F-1, S-1 Facility's Square Footage (including proposed project): 21,630 SF I Corrosives ffi Explosive or Blasting Agents A Organic Peroxides ~ Water Reactives
Compressed Gases (.£) Oxidizers 1 Cryogenics
Flammable/Combustible liquids 7. Pyrophorics 11 Highly TCIXic or Toxic Materials
4. Flammable Solids 8. Unstable Reactives 12. Radioactives
Other Health Hazards
None of These.
PART II: SAN DIEGO COUNTY DEPARTMENT OF ENVIRONMENTAL HEAL TH -HAZARDOUS MATERIALS DIVISION HMO : If the answer to any of the
questions is yes, applicant must contact the County o an Diego Hazardous Materials Division, 5500 verla Avenue, uite 170, San Diego, CA 92123.
Call (858) 505-6700 prior to the issuance of a building permit.
FEES ARE REQUIRED Project Completion Date: 3/4/2022 Expected Date of Occupancy: 3/25/2022
(for new construction or remodeling projects)
Is your business listed on the reverse side of this form? (check all that apply).
0 CalARP Exempt
'""'' I
1.
2.
3.
4.
5.
6.
7.
8.
YES NO ~ B □ l!I
Will your business dispose of Hazardous Substances or Medical Waste in any amount?
Will your business store or handle Hazardous Substances in quantities greater than or equal to 55 gallons, 500
pounds and/or 200 cubic feet?
Will your business store or handle carcinogens/reproductive toxins in any quantity?
Will your business use an existing or install an underground storage tank?
Will your business store or handle Regulated Substances (CalARP)?
Will your business use or install a Hazardous Waste Tank System (Title 22, Article 10)?
Will your business store petroleum in tanks or containers at your facility with a total facility storage capacity equal lo
or greater than 1,320 gallons? (California's Aboveground Petroleum Storage Act).
Date Initials
0 CalARP Required
I
Date \mtials
D CalARP Complete
t;llil/3Cll2021 /
Date Initials
PART 111: SAN DIEGO COUNTY AIR POLLUTION CONTROL DISTRICT (APCDl: The following questions are intended to identify the majority of air pollution
issues at the planning stage. Your project may require additional measures not identified by these questions. Some residential projects may be exempt from APCD
requirements. If yes is answered for either questions 1, 2 or 5 or for more comprehensive requirements, please contact APCD at apcdcomp@sdcounty.ca.gov;
(858) 586-2650; or 10124 Old Grove Road, San Diego, CA 92131.
1.
2.
3.
4.
5.
6.
YES NO
!::I □ □ lfl
Will the project disturb 100 square feet or more of existing building materials?
Will any load supporting structural members be removed?
□
□
□
(ANSWER ONLY IF QUESTION 1 or 2 IS YES) Has an asbestos survey been performed by an individual that has passed an EPA-approved
building inspector course?
I!) (ANSWER ONLY IF QUESTION 1 or 2 IS YES) Based on the survey results, will the project disturb any asbestos containing material? If yes. a
notification may be required at least 10 working days prior to commencing asbestos removal. Additionally, a notification may be required prior to
the removal of a load supporting structural member(s) regardless <if the presence of asbestos. l!I Will the project or associated construction equipment emit air contaminants? See the reverse side of this form for typical equipment requiring an
APCD permit. If yes, contact APCD prior to the issuance of a building permit. □ (ANSWER ONLY IF QUESTION 5 IS YES) Will the project or associated construction equipment be located within 1,000 feet of a school
bounda ?
Briefly describe business activities: Briefly describe proposed project:
I declare under penalty of perjury that to the best of my knowledge and belief I e responses made herein are true and correct.
""~'""""' 7tl44/4 6~ I • I=
Name of Owner or Authorized Agent Signature of Owner or Authorized Agent Date
FOR OFFICAL USE ONLY: FIRE DEPARTMENT OCCUPANCY CLASSIFICATION:, ____________________ -'-------------
BY· DATE· ___ / __ -/ __ _
EXEMPT OR NO FURTHER INFORMATION REQUIRED RELEASED FOR BUILDING PERMIT BUT NOT FOR OCCUPANCY RELEASED FOR OCCUPANCY
COUNTY-HMO* APCD COUNTY-HMO APCD COUNTY-HMO APCD
MJA approved 10/21/ 1
•A stamp in this box only exe111p1s ousinesses from completing or updating a Hazardous Matenals Business Plan. Other permitting requirements may sttll apply
HM-9171 (9/18) County of San Diego -DEH -Hazardous Materials Division