HomeMy WebLinkAbout7040 AVENIDA ENCINAS; ; AS150117; Permit9/28/23, 10:37 AM
Job Address:
Permit Type:
Parcel No:
Lot#:
Reference No.:
PC#:
Project Title:
Applicant:
AS150117 Permit Data
City of Carlsbad
Sprinkler Permit
Permit No: AS150117
7040 AVENI DA
Status: ISSUED
ENCINAS
SPRINK Applied 4/27/2015
2144301400 Approved: 4/27/2015
0
Issued: 4/27/2015
Inspector:
CARLSBAD MASSAGE TWO HEAD Tl
Owner:
COSCO FIRE PROTECTION
4990 GREEN CRAIG LN
DONAHUE SCHRIBER REALTY GROUP L
p
C/O PARADIGM TAX GROUP SAN DIEGO, CA
858-444-2000
about:blank
Fees($)
70
Add'I Fees ($)
. 0
5694 MISSION CENTER RD #602-800
SAN DIEGO CA
Total($) T
70 __j_-
Balance($)
0 j
1 /1
•••••••• ··•····. •••••••• ••••••••
COSCO
Fire Protection
ASlSD\l-=t
San Diego Branch Office
4990 Greencraig Lane
San Diego, CA 92123
(858) 444-2000 fax: 444-2056
CA Lie.: C-16 #577621
www.coscofire.com
MATERIAL SUBMITTAL
Date: 4/30/15
Joy Massage
7040 A venida Encinas, # 106
Carlsbad, CA
JOB# 1504-2411
All material submitted, may be substituted
by material of equal performance & design, &
shall be deemed acceptable by purchaser.
Submitted by: Chris Eason
Los Angeles • San Francisco • Orange • Fresno • San Diego • Seattle
Bulletin 110 Rev. W
ModelG
Reliabld Automatic Sprinklers
Spray Upright,
Spray Pendent
And Conventional
Product Description
The Reliable Model G Automatic Sprinkler utilizes the
center strut solder in compression principle of construc-
tion. The fusible alloy is captured in the cylinder of the
solder capsule by a stainless steel ball. When the fusible
alloy melts, the ball moves into the cylinder allowing the
cylinder to fall away from the sprinkler. When this happens,
the lever is released to spring free from the sprinkler so
that all of the operating parts clear from the waterway al-
lowing the deflector to distribute the discharging water.
Except for the parts in the cylinder as mentioned above,
the sprinkler components are made from copper based
alloys for maximum corrosion protection. Lead plated, wax
coated or wax over lead plated sprinklers are available for
specially severe environments. Chrome plated sprinklers
are available for decorative purposes.
All sprinklers are individually hydrostatically tested. All
sprinklers are identified as to their fusing point by mark-
ings that appear on several of the operating parts and by
an identifying color that appears on the frame.
Sprinkler Types
Standard Upright -This deflector configuration is normal-
ly used with exposed piping installations. Water is distrib-
uted laterally and downward in a wide pattern approximat-
ing a hemisphere which is completely and uniformly filled
with water in the form of small drops or spray.
Standard Pendent -This deflector configuration is nor-
mally used where the space above the piping is limited
or where a concealed piping installation is employed. The
discharge characteristics of the standard pendent are
virtually identical to the standard upright as described
above.
Large and Small Orifice -By varying the orifice size, a
large or small orifice sprinkler is created that will distrib-
ute as much as 40% more water or 65% less water than
the normal ½" (15mm) orifice sprinkler.
Conventional -This deflector configuration is used pri-
marily in those countries where the LPC installation rules
have precedence. The sprinkler is designed to distribute
a portion of its water discharge upward against the ceil-
ing with the balance downward. It may be installed in
either the upright or the pendent position. Sprinklers with
conventional deflectors are available with orifice sizes
corresponding to light, ordinary and extra-high hazard
installations.
Upright Pendent
Small Orifice Upright Conventional
Application and Installation
Standard sprinklers are used in fixed fire protection sys-
tems: Wet, Dry, Deluge or Preaction. Care must be exer-
cised that the orifice sizes, temperature ratings, deflector
styles and sprinkler spacings are in accordance with the
latest published standards of the National Fire Protection
Association or the approving authority having jurisdiction .
The sprinklers must be installed with the Reliable Model
D Sprinkler Wrench. Any other type of wrench may dam-
age the sprinkler.
The approvals or listings of Reliable Automatic Sprin-
klers by major approving organizations are shown in the
tabulated list provided on the back of this bulletin.
Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York 10523
CD !;_
~ :::::,
--'
....J,
0
JJ ~
Tee;hnlcal .Data
"K" Factor Sprinkler Sprinkler Identification
Sprinkler Type Approvals Number (SIN)
us Metric Height ssu SSP
Standard-Upright (SSU) and Pendent (SSP)
Deflectors Marked to Indicate Position
½" (15 mm) Standard Orifice with ½" NPT (R '/2) Thread 5.62
7/,6'' (11 mm) Small Orifice with '/2'' NPT (R'/2) Thread 4.24
3/a'' ( 10 mm) Small Orifice with '/2" NPT (R'/2) Thread 2.82
5/,s" (8 mm) Small Orifice with '/2'' NPT (R'/2) Thread 1.98
17/32" (20 mm) Large Orifice with '/2'' NPT (R1/2) Thread 7.96
17/32'' (20 mm) Large Orifice with 3/," NPT (R3/,)Thread 8.20
20 mm XHH with 20 mm Thread 8.20
10 mm XLH with 10 mm Thread 4.10
Conventional-Installed in Upright or Pendent Position
10mm XLH with 10mm Thread 4.10
15mm Standard Orifice with (R'/2) Thread 5.62 20mm XHH with (R3/•) Thread 8.20
Temperature Ratings
Sprinkler Maximum
Ambient Frame m Classification Rating Temoerature Color
•F •c •F ·c
Ordinary 135 57 100 38 Black
Ordinary 165 74 100 38 Uncolored
Intermediate 212 100 150 66 White
Hioh 286 141 225 107 Blue
<1> Frame color does not apply to painted or plated sprinklers
-Use sprinkler rating as identified on operating parts.
Finishes <1>
Standard Finishes
Bronze -All Temperature Ratings
Chrome -All Temperature Ratings
White<2> -All Temperature Ratings
Onlv Frame and Deflector are Painted
Special Armlication Finishes
81.0 2 7/a'' (73mm) 1,2,3,4,5,6, 7 R1025 R1015
61.0 2 7/s''(73mm) 1, 5 R1023 R1013
40.6 2 7/s" (73 mm) 1, 2, 5 R1021 R1011
28.5 2 7/a'' (73 mm) 1, 5 R1022 R1012
114.7 2 7/a''(73 mm) 1, 2, 5 R1026 R1016
118.2 2 15/,6'' (75 mm) 1, 2, 5 R1027 R1017
118.2 75.4 mm 3,4,5 R1027 R1017
59.1 73 mm 3,4,5 R1024 R1014
59.1 73mm 4 R1074
81.0 73mm 3,4, 5, 7 R1075
118.2 75.4 mm 3,4 R1077
sprinklers with soap and water, ammonia or any other clean-
ing fluids. Remove any sprinkler that has been painted (other
than factory applied) or damaged in any way. A stock of spare
sprinklers should be maintained to allow quick replacement of
damaged or operated sprinklers. Prior to installation, sprinklers
should be maintained in the original cartons and packaging un-
til used to minimize the potential for damage to sprinklers that
would cause improper operation or non-operation. Use only the
Model D Sprinkler Wrench for sprinkler removal and installation.
Any other type of wrench may damage the sprinkler.
Approval Organizations
1. Underwriters Laboratories, Inc. and UL
Certified for Canada (cULus).
2. Factory Mutual Research Corporation
3. Loss Prevention Council
4. Pleniere Assemblee
5. VdS Schadenverhutung GmbH
Bright Brass Plated -Only frame, deflector and cap are plated. 135°F (57°C}, 165°F
6. N.Y.C. BS&A No. 587-75-SA or
N.Y.C. MEA 258-93-E
(74°C}, 212°F (100°C} Temp. Rating.
Black Plated -Only frame, deflector and cap are plated. All Temp. Ratings.
Polyester Coated <2K•> -Only frame and deflector are coated.
Lead Plated -165°F (74°C), 212°F (100°C} and 286°F (141°C} Temp. Ratings.
Wax-Coated 13> -165°F (74°C} Clear Wax, 212°F (100°C) Brown Wax.
Wax-Coated Over
Lead Plated <3> -165°F /74°C\ Clear Wax, 212°F r100°C) Brown Wax.
(1)
(2)
(3)
Other colors and finishes are available. Consult factory for details.
UL listed and NYC MEA Approved only.
14)
212°F (100°C) brown wax may be used on 286°F (141°C)
sprinklers when maximum ambient temperatures do not exceed 150°F
(66°C). UL Listed, FM Approved, NYC MEA 258-93-E.
FM Approved for R1027 only.
Maintenance
Model G Sprinklers should be inspected and the sprinkler
system maintained in accordance with NFPA 25. Do not clean
7. EC Certificate: 1438-CPD-0054 (R1015)
1438-CPD-0053 (R 1025)
1438-CPD-0052 (R1075)
1438-CPD-0056 (R 1077)
Ordering Information
Specify
1. Model G
2. Deflector
• Upright
• Pendent
• Conventional
3. Nominal Orifice
4. Inlet Thread
5. Temperature Rating
6. Finish
The equipment presented in this bulletin is to be installed in accordance with the latest published Standards of the National Fire Protection Association, Factory
Mutual Research Corporation, or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable.
Products manufactured and distributed by Reliable have been protecting life and property for over 90 years, and are installed and serviced by the most highly
qualified and reputable sprinkler contractors located throughout the United States, Canada and foreign countries.
Manufactured by
Reliable
Reliable Automatic Sprinkler Co., Inc.
(800) 431-1588 Sales Offices
(800) 848-6051 Sales Fax
(914) 829-2042 Corporate Offices
www.reliablesprinkler.com Internet Address
IS:\. Recycled ~ Paper
Revision lines indicate updated or new data.
EG Printed in U.S.A. 04/15 P/N 9999970005