HomeMy WebLinkAbout6768 STRAWBERRY PL; ; FPR2017-0165; PermitPER][T REPORT
F4i:reiI3e:r1mit
Print Date: 08/15/2022
Job Address: 6768 STRAWBERRY PL, CARLSBAD, CA
Permit Type: FIRE-Construction Residential Work Class:
Parcel #: 2146312700 Track #:
Valuation: $656,025.00 Lot #:
Occupancy Group: Project #:
#of Dwelling Units: Plan #:
Bedrooms: Construction Type:
Bathrooms: Orig. Plan Check #:
Plan Check #:
Permit No: FPR2017-0165
Status: Closed - Finaled
Single Family Fire Sprinkli
Applied: 05/05/2017
Issued: 06/22/2017
DEV06075 Finaled Close Out: 04/13/2021
Final Inspection:
INSPECTOR: Stowe, Daniel
Wong, Cindy
Project Title: TABATA RANCH
Description: TABATA LOT 5 - SFD SPRINKLER <100 HEADS (48)
FPContractor:
INNOVATIVE FIRE PROTECTION INC
8779 COTTONWOOD AVE, # STE 101
SANTEE, CA 92071-4457
(619) 593-8200
FEE AMOUNT
FIRE NFPA 13D Single Family System (lnsp/Bldg) $121.00
FIRE NFPA 13D Single Family System (Plan Review) $239.00
Total Fees: $360.00 Total Payments To Date: $360.00 Balance Due: $0.00
Fire Department Page 1 of 1
1635 Faraday Avenue, Carlsbad CA 92008-7314 1 760-602-4665 760-602-8561 f I www.carlsbadca.gov
Cody O'Riley
From: Christopher Glassen <Christopher.Glassen@carlsbadca.gov>
Sent: Monday, November 21, 2016 12:48 PM
To: Cody O'Riley
Subject: RE: TABATA LOT 5 - WATER INFO
The static pressure for lot 5 is 118.6p51. The meter and lateral size are 1". Thank you,
(City of
Carlsbad
Christopher Glassen
Engineering Technician
City of Carlsbad
1635 Faraday Avenue
Carlsbad, CA 92008
www.carisbadca.gov
760-602-2784 1 760-602-1052 fax I christopher.glassen@carlsbadca.gov
NEW ENERGOV PERMITTING SYSTEM COMING TO CARLSBAD!
Appointment-Based Submittals and Resubmittals beginning October 17, 2016
Appointments can be made by phone: 760-602-2723
From: Cody O'Riley [mailto:Cody@ifpinc.net]
Sent: Monday, November 21, 2016 12:20 PM
To: Land Development Engineering <LandDev@CarlsbadCA.gov>; Linda Ontiveros <Linda.ontiveros@carlsbadca.gov>
Subject: TABATA LOT 5 - WATER INFO
Hello,
Would you please provide me with the following water info for the following project?
Tabata Lot 5
6768 Strawberry Place
Carlsbad, CA 92009
APN: 214-631-27
Lateral Size:
Meter Size:
Static Pressure:
Thank you for your time!
Cody O'Riley
1
INNOVATIVE FIRE PROTECTION, INC.
8779 COTTONWOOD AVENUE SUITE 101
SANTEE,CA 92071
HYDRAULIC CALCULATIONS
FOR
TABATA LOT 5
6768 STRAWBERRY PLACE
CARLSBAD, CA 92009
FILE NUMBER: 06472
DATE: MAY 4, 2017
-DESIGN DATA-
OCCUPANCY CLASSIFICATION:
DENSITY:
AREA OF APPLICATION:
COVERAGE PER SPRINKLER:
NUMBER OF SPRINKLERS CALCULATED:
S
TOTAL SPRINKLER WATER FLOW REQUIRED:
TOTAL WATER REQUIRED (including hose)
FLOW AND PRESSURE (8 BOR)
SPRINKLER ORIFICE SIZE:
NAME OF CONTRACTOR:
DESIGN/LAYOUT BY:
AUTHORITY HAVING JURISDICTION:
CONTRACTOR CERTIFICATION NUMBER:
RESIDENTIAL/LIGHT
.05 gpm/sq. ft.
205 sq. ft.
20' X 20'-400 sq. ft.
1 sprinkler
21.0 gpm
26.0 gpm
21.0 gpm 8 35.8 psi
1/2" inch
INNOVATIVE FIRE PROTECTION, INC.
JOE PLASSMEYER
CARLSBAD FIRE DEPARTMENT
C-16 711148
CALCULATIONS BY HASS COMPUTER PROGRAM (LICENSE # &CLICE&
HRS SYSTEMS, INC.
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 1
DATE: 5/4/2017 Y:\HASS CALCS 2017\TABATA LOT 5 (1HD) .SDF
JOB TITLE: TABATA LOT 2
0 0 0 (N • 0
(0 •
(0 lID (N 0
DW) 04U)-H--
(D
C
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 2
DATE: 5/4/2017 Y:\HASS CALCS 2017\TABATA LOT 5 (1HD) .SDF
JOB TITLE: TABATA LOT 2
NFPA MATER SUPPLY DATA
SOURCE STATIC RESID. FLOW AVAIL. TOTAL REQ'D
NODE PRESS. PRESS. 8 PRESS. @ DEMAND PRESS.
TAG (PSI) (PSI) (GPM) (PSI) (GPM) (PSI)
1 118.6 100.0 500.0 118.5 26.0 64.9
AGGREGATE FLOW ANALYSIS:
TOTAL FLOW AT SOURCE 26.0 GPM
TOTAL HOSE STREAM ALLOWANCE AT SOURCE 0.0 GPM
OTHER HOSE STREAM ALLOWANCES 5.0 GPM
TOTAL DISCHARGE FROM ACTIVE SPRINKLERS 21.0 GPM
NODE ANALYSIS DATA
NODE TAG ELEVATION NODE TYPE PRESSURE DISCHARGE NOTES
(FT) (PSI) (GPM)
1 0.0 SOURCE 64.9 26.0
2 0.0 - - - - 56.4 - - -
2A 0.0 - - - - 53.4 - - -
D 0.0 - - - - 53.1 - - -
C 0.0 - - - - 47.6 - - -
3A 10.0 - - - - 40.2 - - -
3B 12.0 HOSE STREAM 37.3 5.0
3 14.0 - - - - 35.8 - - -
4 16.0 - - - - 34.6 - - -
4A 16.0 - - - - 30.6 - - -
5 20.0 - - - - 26.9 - - -
6 20.0 - - - - 24.6 - -
7 20.0 - - - - 24.5 - - -
8 20.0 - - - - 24.6 - - -
9 30.0 - - - 21.8 - - -
10 30.0 - - - - 20.2 - - -
11 30.0 - - - - 20.0 - - -
12 30.0 - - - - 19.8 - - -
13 30.0 - - - - 19.6 - - -
101 30.0 - - - - 20.0 - - -
102 30.0 - - - - 20.0 - - -
103 30.0 K= 4.90 18.4 21.0
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 3
DATE: 5/4/2017 Y:\HASS CALCS 2017\TABATA LOT 5 (1HD).SDF
JOB TITLE: TAHATA LOT 2
NFPA2 PIPE DATA
Pipe Tag K-fac Add Fl Add Fl To Fit: L C (Pt) Frm Node El (ft) PT (q) Node/ Nom ID Eq.Ln. F (Pe) Not€ To Node El (ft) PT Tot. (Q) Disch Act ID (ft.) T Pf/ft. (Pf)
Pipe: 1 Source 0.0 40.00 150 64.9
1 0.0 64.9 26.0 2A K1.000 T: 6.0 7.00 0.0
2 0.0 56.4 26.0 0.995 G: 1.0 47.00 0.181 8.5
Pipe: 2 0.0 Fixed Pressure Loss Device
2 0.0 56.4 26.0 D 3.0 psi, 26.0 gpm
2A 0.0 53.4 26.0
Pipe: 3 0.0 0.0 2.00 150 53.4
2A 0.0 53.4 26.0 C L1.000 ---- 0.00 0.0
D 0.0 53.1 26.0 1.025 2.00 0.157 0.3
Pipe: 4 0.0 Fixed Pressure Loss Device
D 0.0 53.1 26.0 3A 5.5 psi, 26.0 gpm
C 0.0 47.6 26.0
Pipe: 5 0.0 0.0 50.00 150 47.6
C 0.0 47.6 26.0 33 P1.500 ---- 0.00 4.3
3A 10.0 40.2 26.0 1.244 50.00 0.061 3.0
Pipe: 6 H.S. 5.0 Disch 3.00 150 40.2
3A 10.0 40.2 21.0 3 L1.000 E: 3.0 10.00 0.9
33 12.0 37.3 26.0 1.025 T: 7.0 13.00 0.157 2.0
Pipe: 7 0.0 0.0 2.00 150 37.3
33 12.0 37.3 21.0 4 F1.000 E: 7.0 7.00 0.9
3 14.0 35.8 21.0 1.101 9.00 0.074 0.7
Pipe: 8 0.0 0.0 2.00 120 35.8
3 14.0 35.8 21.0 4A A1.000 ---- 0.00 0.9
4 16.0 34.6 21.0 1.049 2.00 0.142 0.3
Pipe: 9 0.0 Fixed Pressure Loss Device
4 16.0 34.6 21.0 5 4.0 psi, 21.0 gpm
4A 16.0 30.6 21.0
Pipe: 10 0.0 8.9 6 15.50 150 30.6
4A 16.0 30.6 12.1 9 F1.000 5: 7.0 12.00 1.7
5 20.0 26.9 21.0 1.101 T: 5.0 27.50 0.074 2.0
Pipe: 11 0.0 0.0 12.00 150 26.9
5 20.0 26.9 12.1 10 F1.000 2E:14.0 14.00 4.3
9 30.0 21.8 12.1 1.101 26.00 0.027 0.7
Pipe: 12 0.0 2.1 8 80.00 150 26.9
5 20.0 26.9 6.8 7 F1.000 8E:56.0 66.00 0.0
6 20.0 24.6 8.9 1.101 2T:10.0 146.00 0.015 2.2
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 4
DATE: 5/4/2017 Y:\HASS CALCS 2017\TABATA LOT 5 (1HD).SDF
JOB TITLE: TABATA LOT 2
Pipe Tag K-fac Add Fl Add Fl To Fit: L C (Pt)
Frm Node El (ft) PT (q) Node! Nom ID Eq.Ln. F (Pe)
To Node El (ft) PT Tot.(Q) Disch Act ID (ft.) T Pf/ft. (Pf)
Pipe: 13 0.0 8.9 12 5.00 150 24.6
6 20.0 24.6 -2.1 8 F1.000 T: 5.0 5.00 0.0
7 20.0 24.5 6.8 1.101 10.00 0.009 0.1
Pipe: 14 0.0 0.0 33.00 150 24.6
6 20.0 24.6 2.1 7 F1.000 E: 7.0 12.00 0.0
8 20.0 24.6 2.1 1.101 T: 5.0 45.00 0.001 0.0
Pipe: 15 0.0 13.7 13 14.00 150 24.5
7 20.0 24.5 -4.8 10 F1.000 E: 7.0 12.00 4.3
12 30.0 19.8 8.9 1.101 T: 5.0 26.00 0.015 0.4
Pipe: 16 0.0 8.9 12 29.00 150 24.6
8 20.0 24.6 -6.8 6 F1.000 2T:10.0 10.00 0.0
7 20.0 24.5 2.1 1.101 39.00 0.001 0.0
Pipe: 17 0.0 4.8 12 34.00 150 21.8
9 30.0 21.8 7.3 11 F1.000 3E:21.0 26.00 0.0
10 30.0 20.2 12.1 1.101 T: 5.0 60.00 0.027 1.6
Pipe: 18 0.0 0.0 14.00 150 20.2
10 30.0 20.2 7.3 13 F1.000 T: 5.0 5.00 0.0
11 30.0 20.0 7.3 1.101 19.00 0.010 0.2
Pipe: 19 0.0 13.7 13 54.00 150 20.2
10 30.0 20.2 -8.9 7 F1.000 E: 7.0 27.00 0.0
12 30.0 19.8 4.8 1.101 4T:20.0 81.00 0.005 0.4
Pipe: 20 0.0 21.0 103 0.50 150 19.8
12 30.0 19.8 -7.3 F1.000 T: 5.0 5.00 0.0
13 30.0 19.6 13.7 1.101 5.50 0.034 0.2
Pipe: 21 4.90 21.0 Disch 10.00 150 19.6
13 30.0 19.6 0.0 F1.000 E: 7.0 7.00 0.0
103 30.0 18.4 21.0 1.101 17.00 0.074 1.3
Pipe: 22 0.0 0.0 3.00 150 20.0
101 30.0 20.0 0.0 F1.000 E: 7.0 7.00 0.0
11 30.0 20.0 0.0 1.101 10.00 0.000 0.0
Pipe: 23 0.0 0.0 8.50 150 20.0
102 30.0 20.0 0.0 F1.000 E: 7.0 7.00 0.0
11 30.0 20.0 0.0 1.101 15.50 0.000 0.0
Pipe: 24 0.0 21.0 103 27.00 150 20.0
11 30.0 20.0 -13.7 F1.000 2T:10.0 10.00 0.0
13 30.0 19.6 7.3 1.101 37.00 0.010 0.4
NOtE
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 5
DATE: 5/4/2017 Y:\HASS CALCS 2017\TABATA LOT 5 (1HD) .SDF
JOB TITLE: TABATA LOT 2
NOTES (HASS)
Calculations were performed by the HASS 8.6 computer program
in accordance with NFPA13 (2016)
under license no. 16080621 granted by
HRS Systems, Inc.
208 Southside Square
Petersburg, TN 37144
(931) 659-9760
The system has been calculated to provide an average
imbalance at each node of 0.001 gpm and a maximum
imbalance at any node of 0.004 gpm.
Total pressure at each node is used in balancing the system.
Maximum water velocity is 10.7 ft/sec at pipe 1.
Items listed in bold print on the cover sheet
are automatically transferred from the calculation report.
PIPE FITTINGS TABLE
Pipe Table Name: STANDARD1.PIP
PAGE: A MATERIAL: S40 HWC: 120
Diameter Equivalent Fitting Lengths in Feet
(in) E T L C B G A D N
Eli Tee LngEll ChkVlv BfyVlv GatViv AlmChk DPVlv NPTee
1.049 2.00 5.00 2.00 5.00 6.00 1.00 10.00 2.00 5.00
PAGE: F MATERIAL: CPVC HWC: 150
Diameter Equivalent Fitting Lengths in Feet
(in) F E T R K C G
F45 El Tee RunT Kplg ChkVlv Gate
1.101 1.00 7.00 5.00 1.00 1.00 8.00 0.40
PAGE: K MATERIAL: CT-K HWC: 150
Diameter Equivalent Fitting Lengths in Feet
(in) E T F R K C G N
Ell Tee 45-Eli TeeRun Koupig ChkVlv GatViv NPTee
0.995 2.00 6.00 1.00 2.00 0.00 6.00 0.00 6.00
PAGE: L MATERIAL: CT-L HWC: 150
Diameter Equivalent Fitting Lengths in Feet
(in) E T F R K C G N
Ell Tee 45-Eli TeeRun Kouplg ChkVlv GatVlv NPTee
1.025 3.00 7.00 1.00 2.00 0.00 7.00 0.00 7.00
INNOVATIVE FIRE PROTECTION, INC.
8779 COTTONWOOD AVENUE SUITE 101
SANTEE,CA 92071
HYDRAULIC CALCULATIONS
FOR
TABATA LOT 5
6768 STRAWBERRY PLACE
CARLSBAD, CA 92009
FILE NUMBER: 06472
DATE: MAY 4, 2017
-DESIGN DATA-
OCCUPANCY CLASSIFICATION: RESIDENTIAL/LIGHT
DENSITY: .05 gpm/sq. ft.
AREA OF APPLICATION: 170 sq. ft.
COVERAGE PER SPRINKLER: 16' X 16'-256 sq. ft.
NUMBER OF SPRINKLERS CALCULATED: 2 sprinklers
5
TOTAL SPRINKLER WATER FLOW REQUIRED: 26.2 gpm
TOTAL WATER REQUIRED (including hose) : 31.2 gpm
FLOW AND PRESSURE (8 BOR) : 26.2 gpm @ 28.0 psi
SPRINKLER ORIFICE SIZE: 1/2" inch
NAME OF CONTRACTOR: INNOVATIVE FIRE PROTECTION, INC.
DESIGN/LAYOUT BY: JOE PLASSMEYER
AUTHORITY HAVING JURISDICTION: CARLSBAD FIRE DEPARTMENT
CONTRACTOR CERTIFICATION NUMBER: C-16 711148
CALCULATIONS BY HASS COMPUTER PROGRAM (LICENSE # &CLICE&
HRS SYSTEMS, INC.
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 1
DATE: 5/4/2017 Y:\HASS CALCS 2017\TABATA LOT 5 (2HD) .SDF
JOB TITLE: TABATA LOT 2
0 0 /- C- 0 0 0 0
00
(N • 0
00 n (N 0
(D 41 a4 Z i))&)c))i)1 —Q40)-H----
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 2
DATE: 5/4/2017 Y:\HASS CALCS 2017\TABATA LOT 5 (2HD) .SDF
JOE TITLE: TABATA LOT 2
NFPA WATER SUPPLY DATA
SOURCE STATIC RESID. FLOW AVAIL. TOTAL REQTD
NODE PRESS. PRESS. @ PRESS. 8 DEMAND PRESS.
TAG (PSI) (PSI) (GPM) (PSI) (GPM) (PSI)
1 118.6 100.0 500.0 118.5 31.2 65.5
AGGREGATE FLOW ANALYSIS:
TOTAL FLOW AT SOURCE 31.2 GPM
TOTAL HOSE STREAM ALLOWANCE AT SOURCE 0.0 GPM
OTHER HOSE STREAM ALLOWANCES 5.0 GPM
TOTAL DISCHARGE FROM ACTIVE SPRINKLERS 26.2 GPM
NODE ANALYSIS DATA
NODE TAG ELEVATION NODE TYPE PRESSURE DISCHARGE NOTES
(FT) (PSI) (GPM)
1 0.0 SOURCE 65.5 31.2
2 0.0 - - - - 53.6 - - -
2A 0.0 - - - - 49.6 - - -
D 0.0 - - - - 49.2 - - -
C 0.0 - - - - 42.2 - - -
3A 10.0 - - - - 33.6 - - -
3B 12.0 HOSE STREAM 29.9 5.0
3 14.0 - - - - 28.0 - - -
4 16.0 - - - - 26.7 - - -
4A 16.0 - - - - 21.2 - - -
5 20.0 - - - - 16.4 - - -
6 20.0 - - - - 13.4 - - -
7 20.0 - - - - 13.2 - - -
8 20.0 - - - - 13.3 - - -
9 30.0 - - - - 10.9 - - -
10 30.0 - - - - 8.4 - - -
11 30.0 - - - - 7.5 - - -
12 30.0 - - - - 8.4 - - -
13 30.0 - - - - 8.3 - - -
101 30.0 K= 4.90 7.2 13.2
102 30.0 K= 4.90 7.0 13.0
103 30.0 - - - - 8.3 - - -
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 3
DATE: 5/4/2017 Y:\HASS CALCS 2017\TABATA LOT 5 (2HD).SDF
JOB TITLE: TABATA LOT 2
NFPA2 PIPE DATA
Pipe Tag K-fec Add Fl Add Fl To Fit: L C (Pt)
Frm Node El (ft) PT (q) Node/ Nom ID Eq.Ln. F (Fe)
To Node El (ft) PT Tot. (Q) Disch Act ID (ft.) T Pf/ft. (Pf)
Pipe: 1 Source 0.0 40.00 150 65.5
1 0.0 65.5 31.2 2A K1.000 T: 6.0 7.00 0.0
2 0.0 53.6 31.2 0.995 G: 1.0 47.00 0.254 11.9
Pipe: 2 0.0 Fixed Pressure Loss Device
2 0.0 53.6 31.2 D 4.0 psi, 31.1 gpm
2A 0.0 49.6 31.1
Pipe: 3 0.0 0.0 2.00 150 49.6
2A 0.0 49.6 31.2 C L1.000 ---- 0.00 0.0
D 0.0 49.2 31.2 1.025 2.00 0.219 0.4
Pipe: 4 0.0 Fixed Pressure Loss Device
D 0.0 49.2 31.2 3A 7.0 psi, 31.1 gpm
C 0.0 42.2 31.1
Pipe: 5 0.0 0.0 50.00 150 42.2
C 0.0 42.2 31.2 33 P1.500 ---- 0.00 4.3
3A 10.0 33.6 31.2 1.244 50.00 0.085 4.3
Pipe: 6 H.S. 5.0 Disch 3.00 150 33.6
3A 10.0 33.6 26.2 3 L1.000 E: 3.0 10.00 0.9
3B 12.0 29.9 31.2 1.025 T: 7.0 13.00 0.219 2.8
Pipe: 7 0.0 0.0 2.00 150 29.9
3B 12.0 29.9 26.2 4 F1.000 E: 7.0 7.00 0.9
3 14.0 28.0 26.2 1.101 9.00 0.112 1.0
Pipe: 8 0.0 0.0 2.00 120 28.0
3 14.0 28.0 26.2 4A A1.000 ---- 0.00 0.9
4 16.0 26.7 26.2 1.049 2.00 0.214 0.4
Pipe: 9 0.0 Fixed Pressure Loss Device
4 16.0 26.7 26.2 5 5.5 psi, 26.1 gpm
4A 16.0 21.2 26.1
Pipe: 10 0.0 10.5 6 15.50 150 21.2
4A 16.0 21.2 15.6 9 F1.000 E: 7.0 12.00 1.7
5 20.0 16.4 26.2 1.101 T: 5.0 27.50 0.112 3.1
Pipe: 11 0.0 0.0 12.00 150 16.4
5 20.0 16.4 15.6 10 F1.000 2E:14.0 14.00 4.3
9 30.0 10.9 15.6 1.101 26.00 0.043 1.1
Pipe: 12 0.0 2.5 8 80.00 150 16.4
5 20.0 16.4 8.0 7 F1.000 83:56.0 66.00 0.0
6 20.0 13.4 10.5 1.101 2T:10.0 146.00 0.021 3.0
NotE
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 4
DATE: 5/4/2017 Y:\HASS CALCS 2017\TABATA LOT 5 (2HD).SDF
JOB TITLE: TABATA LOT 2
Pipe Tag K-fac Add Fl Add Fl To Fit: L C (Pt) Frm Node El (ft) PT (q) Node/ Nom ID Eq.Ln. F (Pe) To Node El (ft) PT Tot.(Q) Disch Act ID (ft.) T Pf/ft. (Pf)
Pipe: 13 0.0 10.5 12 5.00 150 13.4
6 20.0 13.4 -2.5 8 F1.000 T: 5.0 5.00 0.0 7 20.0 13.2 8.0 1.101 10.00 0.012 0.1
Pipe: 14 0.0 0.0 33.00 150 13.4
6 20.0 13.4 2.5 7 F1.000 E: 7.0 12.00 0.0
8 20.0 13.3 2.5 1.101 T: 5.0 45.00 0.001 0.1
Pipe: 15 0.0 10.3 13 14.00 150 13.2
7 20.0 13.2 0.3 10 F1.000 E: 7.0 12.00 4.3
12 30.0 8.4 10.5 1.101 T: 5.0 26.00 0.021 0.5
Pipe: 16 0.0 10.5 12 29.00 150 13.3
8 20.0 13.3 -8.0 6 F1.000 2T:10.0 10.00 0.0
7 20.0 13.2 2.5 1.101 39.00 0.001 0.1
Pipe: 17 0.0 0.0 34.00 150 10.9
9 30.0 10.9 15.6 11 F1.000 3E:21.0 26.00 0.0
10 30.0 8.4 15.6 1.101 T: 5.0 60.00 0.043 2.6
Pipe: 18 0.0 13.0 102 14.00 150 8.4
10 30.0 8.4 13.2 101 F1.000 T: 5.0 5.00 0.0
11 30.0 7.5 15.9 1.101 19.00 0.044 0.8
Pipe: 19 0.0 15.9 11 54.00 150 8.4
12 30.0 8.4 -15.6 9 F1.000 E: 7.0 27.00 0.0
10 30.0 8.4 0.3 1.101 4T:20.0 81.00 0.000 0.0
Pipe: 20 0.0 0.0 0.50 150 8.4
12 30.0 8.4 10.3 11 F1.000 T: 5.0 5.00 0.0
13 30.0 8.3 10.3 1.101 5.50 0.020 0.1
Pipe: 21 0.0 0.0 10.00 150 8.3
103 30.0 8.3 0.0 F1.000 E: 7.0 7.00 0.0
13 30.0 8.3 0.0 1.101 17.00 0.000 0.0
Pipe: 22 4.90 13.2 Disch 3.00 150 7.5
11 30.0 7.5 0.0 F1.000 E: 7.0 7.00 0.0
101 30.0 7.2 13.2 1.101 10.00 0.031 0.3
Pipe: 23 4.90 13.0 Disch 8.50 150 7.5
11 30.0 7.5 0.0 F1.000 E: 7.0 7.00 0.0
102 30.0 7.0 13.0 1.101 15.50 0.031 0.5
Pipe: 24 0.0 13.0 102 27.00 150 8.3
13 30.0 8.3 13.2 101 F1.000 2T:10.0 10.00 0.0
11 30.0 7.5 10.3 1.101 37.00 0.020 0.7
Not(
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 5
DATE: 5/4/2017 Y:\HASS CALCS 2017\TABATA LOT 5 (2HD).SDF
JOB TITLE: TABATA LOT 2
NOTES (HASS)
Calculations were performed by the HASS 8.6 computer program
in accordance with NFPA13 (2016)
under license no. 16080621 granted by
HRS Systems, Inc.
208 Southside Square
Petersburg, TN 37144
(931) 659-9760
The system has been calculated to provide an average
imbalance at each node of 0.009 gpm and a maximum
imbalance at any node of 0.190 gpm.
Total pressure at each node is used in balancing the system.
Maximum water velocity is 12.9 ft/sec at pipe 1.
Items listed in bold print on the cover sheet
are automatically transferred from the calculation report.
PIPE FITTINGS TABLE
Pipe Table Name: STANDARD1.PIP
PAGE: A MATERIAL: S40 HWC: 120
Diameter Equivalent Fitting Lengths in Feet
(in) E T L C B G A D N
Ell Tee LngEll ChkVlv BfyVlv GatVlv AlmChk DPViv NPTee
1.049 2.00 5.00 2.00 5.00 6.00 1.00 10.00 2.00 5.00
PAGE: F MATERIAL: CPVC HWC: 150
Diameter Equivalent Fitting Lengths in Feet
(in) F E T R K C G
F45 El Tee RunT Kplg ChkVlv Gate
1.101 1.00 7.00 5.00 1.00 1.00 8.00 0.40
PAGE: K MATERIAL: CT-K HWC: 150
Diameter Equivalent Fitting Lengths in Feet
(in) E T F R K C G N
Eli Tee 45-Eli TeeRun Kouplg ChkVlv GatVlv NPTee
0.995 2.00 6.00 1.00 2.00 0.00 6.00 0.00 6.00
PAGE: L MATERIAL: CT-L HWC: 150
Diameter Equivalent Fitting Lengths in Feet
(in) E T F R K C G N
Eli Tee 45-Ell TeeRun Koupig ChkVlv GatVlv NPTee
1.025 3.00 7.00 1.00 2.00 0.00 7.00 0.00 7.00
SPECIFICATION
FEATURES
Sizes: U3/4" U 1" U 1-1/4" U 1-1/2" 0 2"
Maximum working water pressure 175 PSI
Maximum working water temperature 180°F
Hydrostatic test pressure 350 PSI
End connections Threaded ANSI B1.20.1
OPTIONS
(Suffixes can be combined)
U - with full port QT ball valves (standard)
U L - less ball valves
U U - with union ball valves
U S - with bronze "Y" type strainer
U TCU - with test cocks "vertical" up
U V - with union swivel elbows (3/4" & 1")
U OSY - with OS & V gate valves
U FDC - with fire hydrant connection (2" only)
U FT - with integral male 450 flare SAE test fitting
APPLICATION
Designed for installation on potable water lines to protect
against both backsiphonage and backpressure of polluted
water into the potable water supply. Assembly shall provide
protection where a potential health hazard does not exist.
STANDARDS COMPLIANCE
(All sizes approved horizontal. Vertical approvals as
listed below.)
ASSE® Listed 1015 (vertical 3/4", 1 1/4", 1 1/2" & 2")
IAPMO® Listed (vertical I 114"-2")
CSA® Listed (vertical 3/4", 1 1/4", 1 1/2" & 2")
AWWA Compliant C510 (vertical 3/4")
UL® Classified (less shut-off valves only)
C-UL® Classified (less shut-off valves only)
Approved by the Foundation for Cross Connection
Control and Hydraulic Research at the University of
Southern California (vertical 3/4")
City of Los Angeles Approved (vertical 1-1/4-2")
NYC MEA 426-89-M VOL 3
MATERIALS
Main valve body Cast Bronze ASTM B 584
Access covers Cast Bronze ASTM B 584
Internals Stainless Steel, 300 Series
Elastomers Silicone (FDA approved)
Buna Nitrile (FDA approved)
Polymers NorylTM, NSF Listed
Springs Stainless steel, 300 series
DIJ
ACCESSORIES
U Repair kit (rubber only)
U Thermal expansion tank (Model WXTP) F U QT-SET Quick Test Fitting Set
U Test Cock Lock (Model TCL24)
DIMENSIONS & WEIGHTS (do not include pkg.)
____ B_________ A
G
DIMENSIONS (a proximate) WEIGHT
MODEL A UNION ° LESS BALL LESS WITH
SIZE A BALL C D E F G BALL BALL
VALVES VALVES VALVES VALVES
in. I mm in. mm in. Imm in. Imm in. Imm in. Imm in. mm in. I mm in. Imm lbs jkg lbs. I kg
3/4 20 111/4 286 121/2 318 7 178 11/2 38 3 76 31/2 89 1 3 76 15 381 5 2.3 7 3.2
1 25 121/4 311 137/8 353 7 178 1 1/2 38 3 76 31/2 89 173/4 451 8 3.6 12
32 151/2 419 181/2 470 109/16 268 2 51
5.
1/4 31/28941/2 114 4 211/254616 7.3 22 10
11/2 40 171/8435 191/8 486 109/16 268 2 51 31/289 41/2 114 4
C376
223/4 57816 7.3 22 10
2 50 181/44601 20 508 109/16 268 2 51 31/2 89 41/2 Il4 4 251/8 638116 j 7.3 i 28 l2.7
DOCUMENT#: REVISION:
_7112
Page 1 of 2 WILKINS a Zurn company, 1747 Commerce Way, Paso Robles, CA 93446 Phone: 805-238-7100 Fax:805-238-5766
In Canada: ZURN INDUSTRIES LIMITED, 3544 Nashua Dr., Mississauga, Ontario L4V 1L2 Phone: 905-405-8272 Fax:905-405-1292
Product Support Help Line: 877-BACKFLOW (877-222-5356) Website: http://www.zurn.com
FLOW CHARACTERISTICS
MODEL 950XL 3/4", 1", 11/4", 1 1/2" & 2" (STANDARD & METRIC)
FLOW RATES (Ifs)
• 0
ILJIÜliD
-
-•
I I 'I .1 1
FLOW RATES (GPM)
0 Rated Flow (Established by approval agencies)
TYPICAL INSTALLATION
Local codes shall govern installation requirements. To be
installed in accordance with the manufacturer's instructions
and the latest edition of the Uniform Plumbing Code. Unless
otherwise specified, the assembly shall be mounted at a
minimum of 12" (305mm) and a maximum of 30" (762mm)
above adequate drains with sufficient side clearance for
testing and maintenance. The installation shall be made
so that no part of the unit can be submerged.
Capacity thruSchedule 40 Pipe
Pipe size 5 ft/sec 7.5 ft/sec 10 ft/sec 15 ft/sec
1/8" 1 1 2 3
1/4" 2 2 3 5
3/8" 3 4 6 9
1/2 5 1 7 9 14
3/4" 8 12 17 25
13 20 27 40
1 1/4" 23 35 47 70
1 1/2" 32 48 63 95
52 78 105 167
DIRECTION OF FLOW
OUTDOOR INSTALLATION INDOOR INSTALLATION
SPECIFICATIONS
The Double Check Valve Backflow Preventer shall be ASSE® Listed 1015 approved, and supplied with full port ball
valves. The main body and access covers shall be bronze (ASTM B 584), the seat rings and all internal polymers shall
be NSF® Listed NorylTM and the seat disc elastomers shall be silicone. The first and second checks shall be acces-
sible for maintenance without removing the device from the line. The Double Check Valve Backflow Preventer shall be
a WILKINS Model 950XL.
WILKINS a Zurn company, 1747 Commerce Way, Paso Rabies, CA 93446 Phone: 805-238-7100 Fax:805-238-5766
IN CANADA: ZURN INDUSTRIES LIMITED, 3544 Nashua Dr., Mississauga, Ontario L4V 1L2 Phone:905-405-8272 Fax:905-405-1292
Product Support Help Line: 877-BACKFLOW (877-222-5356) Website: http://www.zurn.com Page 2of2
Item Description
1 Manifold Body, Male Thread x
Male Thread
2 Inline Check Valve, Spring
Loaded
3 Flow Switch with Retard
4 Drain Valve, with optional
pressure relief valve
5 Pressure Gauge, 0-300 psi
National Fire Products, LLC
R ES I - RISERTM
The RESI-RISERTM is a pre-assembled, compact, attractive fire sprinkler riser unit for residential
sprinkler systems in accordance with NFPA 13, 13R and 13D.
The RESI-RISERTM manifold is manufactured as a one-
piece casting that is air-tested for leaks.
Raised lettering on both sides allows the RESl-RISERTM
to be installed to the right or left and easily identifies
the flow direction and Test and Drain outlet.
Two mounting legs are molded onto the manifold
allowing for a secure right or left anchoring.
The flow switch has dual SPDT switches and a retard
of 0-90 seconds.
An optional "all in one" cost saving combination
Pressure Relief Valve/Test and Drain Valve is
available.
The RESI-RISERTM unique design gives the ability to be
installed within standard 2 x 4 frame construction.
Every size RESI-RISERTM fits within a 2 x 4 wall framed
at 16 inches on center.
Technical Data
Sizes: 1", 1W', 1W', and 2"
Style: Thread x Thread
Listing: Flow Switch and Pressure Gauge are UL
Listed
Finish (Riser Body): Cast Brass
Water Pressure Gauge: 0-300 psi
Optional Accessories: 175 psi Pressure Relief
Valve/Test and Drain
US Patent # 6,076,545
RESl-RISERTM Size Chart
___
Description 1" 11/4" 1Ya" 2"
Height* 13" 13" 13" 13"
Width** 10-3/4" 11-1/2" 12" 12-1/2"
Depth 3-1/2" 3-1/2" 3-1/2" 3-1/2"
Drain Size 1/2" 1" 1" 1"
Dimensions include all spacing needed to operate drain valve and
remove flow switch cover
* Without check valve
** With or without pressure relief valve
© National Fire Products, LLC (800) 528-7978
0 10 15 20 25 30 35 40 45 50 55 60
0 15 25 35 45 55 65 75 85 95
Pressure Loss Tables
Pressure Loss in 1" Resi-Riser
Pressure Relief/Test and Drain
How it Works
Normal Position -
Static Pressure
U
elieving Pressure
Exceeding 175 psi
J7
Manual Open - Drain
or Flow Switch Test
Locked Closed for
Hydrostatic Test H t
12
10
- 6
w
0.0
0 10 15 20 25 30 35 40
Flow (gpm)
Pressure Loss in 1-1/4" Resi-Riser
Flow (gpm)
Pressure Loss in 1-1/2" Resi-Riser
10
0 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80
Flow (gpm)
Pressure Loss in 2" Resi-Riser
Flow (gpm)
© National Fire Products, LLC (800) 528-7978
i or
SENJU SPRINKLER CO.,LTD.
Residential Lead Free Flat Concealed Sprinkler,
Pendent,
Model: RC-RES, K-Factor: 4.9, SIN: SS8464
GENERAL DESCRIPTION
The Model RC-RES Residential Flat Concealed Sprinklers are automatic sprinklers of the compressed fusible solder type. These
are decorative and fast response. The Cover Plate Assembly hides the Deflector, Heat Responsive Element etc., which is in turn
concealed above the ceiling. The cover plate has a flat profile, and its diameter is extremely small (2-5/8 inch, 68mm). The
push-on and/or thread-on, thread-off design of the concealed cover plate assembly allows easy installation of the cover plate.
Therefore, the Model RC-RES should be your first choice when aesthetics is the major consideration for ultimate appeal and
unbeatable performance is desired. The Model RC-RES is designed for the residential occupancies and it is perfect for use in
homes, hotels and other living quarters.
The Model RC-RES is to be used in wet pipe residential sprinkler systems for One- and Two- Family Dwellings and
Manufactured Homes per NFPA 13D; wet pipe residential sprinkler systems for Residential Occupancies up to and Including
Four Stories in Height per NFPA 13R; or, wet pipe sprinkler systems for the residential portions of any occupancies per NFPA 13.
The Model RC-RES has a 4.9 (70.6 LPM/bar1°) K-factor that meets the required residential flow rates with minimal residual
pressure, which allows for smaller pipe sizes and water supply requirements.
For extended installation flexibility, the Model RC-RES provides 1/2 inch (12.8mm) vertical adjustment. This adjustment in
installation decreases the need for precise cutting of the pipe that drops to the sprinkler and allows for a perfect fit with a range of
pipe lengths.
The heat sensitivity and water distribution design of Model RC-RES allows for an increased chance of residents' escape or
evacuation in case of fire. However, residential fire sprinkler systems are not a substitute for fire safety awareness or fire safety
construction required by building codes.
"Lead Free" is defined in the Reduction of Lead in Drinking Water Act (S.3874) endorsed by AWWA's Water Utility Council, and
California Assembly Bill #1953 as having less than or equal to a weighted average of 0.25% lead in wetted surface of pipes,
plumbing fittings and fixtures.
WARWINGS
The Mode! RC-RES must be installed and maintained in accordance with the rules stated herein as well as in
compliance with the applicable standards of the National Fire Protection Association regulations and the standards of
any other authorities ha ving jurisdiction.
In the event of this condition, consult the authorities ha ving jurisdiction for guidance and approval.
Failure to do so may impair the integrity of these devices.
It is the responsibility of the installing contractor to provide a copy of this document to the owner or his representative,
and in turn, it is the obligation of the owner to provide a copy of this document to a succeeding owner. The owner is
responsible for maintaining their fire protection system and devices in proper operating condition. The installing
contractor or sprinkler manufacturer should be contacted with any related questions.
Document No. U085160 Date Feb/09/2015
Page 2 of 8
OPERATION
2— )4u" ( 52mm)
NPT1/2 Marking
Lot No. Year of Manufacture
SIN SS8464
—K-factor K4.9
Temperature Rating 162T/72C
E UL MorN or 175F/79C
Control No. 6P07
U') NSF Mark NSF-61 —G
RESSPKR
0 Body (Capper Alloy)
0 Deflector (Phosphorus Bronze)
0 Gasket (PTFE)
0 Fusible Metal (Solder)
0 Heat Collector (Copper)
Cover Plate Assembly
or 3—j/" (83mm)
or 2- 5/u"square (068
FIGURE 1. Mode! RC-RES K-4.9
Color Code
SIN SS8464
k—factor 44.9
Temperature Rating
I62T/72C or I75F/79c
-UL Mork
CED
COVER PLATE SPRINKLER
(Top view) (Bottom View)
FIGURE 1-1. Marking (Color Code)
TECHNICAL DATA
Approvals: UL5 Listed, NSF-61-G
Sprinkler Identification Number (SIN): SS8464
Maximum Working Pressure: 175psi (12.1 bar)
Discharge Coefficient (Nominal K-Factor):
K=4.9 GPM/psi112 (70.6 LPM/bar112)
Temperature Rating:
1621 (72°C) Sprinkler with 1401 (60°C) Cover Plate
1751 (79°C) Sprinkler with 1621 (72°C) Cover Plate
Color Code (Sprinkler)
1621 (720C): Uncolored
1751 (79°C): White
Color Code (Cover Plate)
1401 (609C): No Mark
1621 (720C): White-Colored Mark
Vertical Adjustment: 1/2 inch (12.8 mm)
Cover Plate Finishes:
Standard Finishes-
White, Ivory, Beige, Brown, Black, Nickel,
Wood Grain
Custom Finishes-
Custom color and custom pattern cover plates are
available on special order. Contact a Senju
Sprinkler representative with any custom orders.
Please see chart on Page 8 for more detail.
Physical Characteristics: Ref. Figure 1
In case of fire, the solder component that holds together the Cover Plate and the Retainer melts. Then, the Cover Plate is
released at once. As a result, the Deflector drops down to the intended position. Two Heat Collectors are exposed to fire, and
when sufficient heat from the fire is recorded, internal components of the sprinkler to fall apart. This leads to allow the water flow
to be distributed on the affected by fire area. (Ref. Figure 2)
P L'IN i'uu P1P..O. _iiuiuU P. Ill I
Normal Condition =# Cover Plate Operation Ill Sprinkler Operation soll Water Discharge
FIGURE 2. OPERATION PROCESS (The figure is for illustrative purpose only)
Document No.U085160 Date : Feb/09/2015
Page 3 of 8
DESIGN CRITERIA
The herein stated rules for use and installation of Model RC-RES are provided by the manufacturer and must be strictly
implemented for safe and full results.
NOTES
Residential Fire Sprinkler Systems should only be designed and installed by individuals who are completely familiar
with automatic sprinkler system design, installation procedures, and techniques.
Several criteria may apply to the installation and usage of each sprinkler. Consequently, it is recommended that the
sprinkler system designer review and develop a working understanding of the complete list of criteria prior to initiating
the design of the sprinkler system.
Questions concerning sprinkler installation and usage criteria, which are not coverage by the following instructions,
should be submitted to Contact Company. Include sketches and technical details as appropriate.
In some instances, the requirements of this document may concern specifications which are more stringent and which
take precedence over those specified in NFPA 13, 13D, 13R, or by the authority ha ving jurisdiction.
The Model RC-RES must not be used in applications where the air pressure above the ceiling is greater than that below.
Inspect all sprinklers after installation to ensure that both the gap between the cover plate, ceiling and the 6 slots in the
cup are open and free from any air flow impediment.
The spray from the sprinkler is distributed radically outward and downward from the sprinkler deflector. Consequently,
the sprinklers must be located such that there will be no blind spaces shielded from spray by partitions, room dividers,
overhangs or other parts of the dwelling structure.
The number of sprinklers within each compartment (as defined by NFPA 13, 13D, or 13R) must be kept as small as
possible. Do NOT use more sprinklers than necessary to cover a particular space.
Use only the Cover Plate provided with the Model RC-RES. The sprinkler must be secured in place by firmly fastening
the sprinkler system piping to the structure. If the sprinkler is not properly secured in position, reaction forces
resulting from sprinkler operation could alter its orientation and its water distribution pattern.
Obstruction to Water Distribution
Locations of sprinklers must follow the obstruction rules of NFPA 13 for Residential Sprinklers.
General Service Conditions
The Model RC-RES must only be utilized in WET PIPE sprinkler systems.
Heat Source Criteria
Refer to NFPA 13D or 13R for the requirements relating to the prevention of possible activation of the Heat Responsive
Element of Model RC-RES, due to exposure to a heat sources other than an actual fire.
Precautionary Warnings for Corrosive Environments
The Model RC-RES should not be installed where they may be subjected to a corrosive environment including the following:
Chlorine ion and Chloride environment.
Stress corrosion cracking may be caused by exposure to environments with Chlorine ion and Chloride. Exposure to this
environment may result in sprinklers operating under Non-Fire conditions or Not Operating when exposed to an actual fire.
Sprinkler system piping with Copper.
Sprinkler systems should be constructed in compliance with the applicable standards and the requirements for the copper
piping when copper piping is used in the sprinkler system. (Reference standards NFPA 13, ASTM B813, B828, and CDA
(Copper Development Association) - Solder Joint)
All residual flux must be removed from the interior and exterior of copper piping by thoroughly flushing before installation of
the Sprinkler Heads. Otherwise, residues of flux may cause corrosion and leakage in the sprinkler system.
Hydraulic Design Criteria
The minimum required sprinkler flow rates for system designed to NFPA 13D or 13R are given in Table A as a function of
temperature rating and the maximum allowable coverage areas. The sprinkler flow rate is the minimum required discharge
from the most hydraulically demanding sprinkler from each of the total number of design sprinklers" as specified in NFPA 13D
or 13R.
For systems designed to NFPA 13, the number of designed sprinklers is to be the four most hydraulically demanding
sprinklers. The minimum required discharge from each of the four sprinklers is to be the greater of the followings;
The flow rates given in Table A for NFPA 13D and 13R as a function of temperature rating and maximum allowable
coverage area.
Document No.U085160 Date Feb/09/2015
Page 4 of 8
A minimum discharge 0.1GPM/sq.ft. [4.07LPMlsq.m] over the design area" comprised of the four most hydraulically
demanding sprinklers for the actual coverage areas being protected by the four sprinklers.
TABLE A. NFPA 13D & 13R WET PIPE HYDRAULIC DESIGN CRITERIA for Model SS8464
Maximum Ordinary Intermediate
Covera e Maximum Temperature Rating
162"F (72°C)
Temperature Rating
175'F (79°C) Deflector Installation
Minimum
Spacing
Area (W to
Flow(D)Pressure Flow Pressure Ft. x Ft Ft. Ceiling Type Ft.
(m xm)
. (m) GPM PSI GPM PSI (m)
(LPM) (bar) (LPM) (bar)
Smooth
12x12 12 13 7.0 13 7.0 Ceilings
(3.7x3.7) (3.7) (49.2) (0.48) (49.2) (0.48) 3/8 to 7/8
Inches.
14x14 14 13 7.0 13 7.0 Beamed
(4.3x4.3) (4.3) (49.2) (0.48) (49.2) (0.48) Ceilings
per NFPA
16x16 16 13 7.0 14 8.2 13D,13R Concealed 8
(4.9x4.9) (4.9) (49.2) (0.48) (53.0) (0.57) or 13 (2.4)
Installed
in beam
18x18 18 17 12.0 18 13.5 3/8 to
(5.5x5.5) (5.5) (64.3) (0.83) (68.1) (0.93) 7/8
inches
20x20 20 21 18.4 below
(6.1x6.1) (6.1) (79.5) (1.27) -
-
_]
bottom of
beam.
For coverage area dimensions less than the above mentioned, it needs to use the minimum required flow for the
Next Higher Coverage Area listed.
Requirement is based on minimum flow in GPM/LPM from each sprinkler. The associated residual pressures are
calculated using the nominal K-Factor. Refer to Hydraulic Design Criteria Section for details.
(C) For systems with ceiling types smooth flat horizontal, or beamed, or sloped, in accordance with the 2013 Edition of
NFPA 13D, 13R or 13 as applicable.
Sprinkler Spacin-g Criteria
The minimum spacing between sprinklers is 8 feet (2.4m). The maximum spacing between sprinklers cannot go beyond the
coverage area calculated by using the specific hydraulic factors. (Ref. Table A)
INSTALLATION
The Model RC-RES must be installed in accordance with the following instructions.
NOTES
Do not use any sprinklers which have been subjected to potential mechanical damage. Do not use any sprinklers which
show deformation or cracking in either the Sprinkler or the Protective Cap.
Prior to installation, sprinklers should be maintained in the original cartons and packaging until used to minimize the
potential for damage to sprinklers that would cause improper operation or non-operation.
The Protective Cap must remain on the sprinkler during installation and until the ceiling installation is completed. The
Protective Cap must be removed to place the sprinkler in service.
Document No.U085160 Date Feb/09/2015
Page 5 of 8
Use a torque of 7 to 14 ft.lbs (9.5 to 19.ONm) to achieve a 1/2 inch NPT sprinkler joint. If you exceed the recommended
maximum torque, this could result in damage to the sprinkler inlet, which may lead to leakage from the sprinkler.
In case of insufficient adjustment in Cover Plate installation, do not try to overly tighten, screw the sprinkler too loosely
or make any modification to the cover plate assembly. Readjust the sprinkler fitting for a better fit.
Installina Procedure
Step I
The installation requirements for the sprinkler are as follows: to be installed only in the pendent position with the waterway
perpendicular to the ceiling. Install the sprinkler fitting so that the distance from the face of the fitting to the mounting surface
will be nominally 2 inch (50.8mm) as shown in Figure 3.
Step 2
With pipe thread sealant applied to the threads, hand tighten the sprinkler into the sprinkler fitting. Then tighten it with the
Sprinkler Socket or Wrench & Socket Combination (Ref. Figure 4). The grooves of the Socket must fit perfectly with the
grooves on the Sprinkler for proper installation (Ref. Figure 4).
Step 3
If desired the Protective Cap may also be used to locate the center of the clearance hole by gently pushing the ceiling material
against the center point of the Protective Cap. Before the installation of the ceiling, the sprinkler installation can be started with
the 2-3/8 inch (60mm) diameter clearance hole (Ref. Figure 3). Use the "Tolerance Limit of Ceiling Level" indicator on the
Protective Cap to check for proper installation height (Ref. Figure 3).
Make a Space Here Do NOT Over-Tighten LGon_______________ the SprinklerAve. ,t" (6.4mm)
Mi )" (3.2mm)
eronce Limi e Cap____6 of Ceiling Levei
Mounting Surface the Socket
_
Mounting Surface /
2-(6Omm)W rench
Ceiling Hole Diameter /
CORRECT!
FIGURE 3. INSTALLATION FIGURE 4
Step 4
Use the Cap Remover RC to remove the Protective Cap (Ref. Figure 5), and then push or screw a Cover Plate Assembly on
the Cup of the Sprinkler by hand until its flange just comes in contact with the ceiling (Ref. Figure 6 and Figure 7). Stop
tightening the Cover Plate Assembly once the flange has come in contact with the ceiling. If the ceiling has been lifted from its
normal position in the process of tightening of the Cover Plate Assembly, readjust the cover plate assembly as necessary. If
the flange of the Cover Plate Assembly cannot come in contact with the ceiling sufficiently, readjust the sprinkler fitting as
necessary. When properly installed, there is a nominal 1/16 inch (1.6mm) air gap between the lip of the Cover Plate and the
ceiling, as shown in Figure 6
Document No. U085160 Date Feb/09/2015
Page 6 of
Sprinkler Head
Step 1
Protective Co
Cap Remover RC
Step
Hook by turning
Step 3 4
Pull down
FIGURE 5. PROTECTIVE CAP REMOVAL
Document No. U085160 Date Feb/09/2015
Page 7 of 8
CARE AND MAINTENANCE
The following instructions must be implemented for the maintenance and service of the Model RC-RES.
NOTES
Wet pipe sprinkler systems must be maintained at a minimum temperature of 40 F14 't to prevent freezing and bursting
of the pipe and/or sprinklers.
Automatic sprinklers are not to be tested with a heat source. Operation of the heat responsive element can result.
Absence of a Cover Plate Assembly may delay the response time of the sprinkler in case of fire.
Install the cover plate assembly properly, as shown in Figure 6. Improper installation of the cover plate assembly may
cause improper operation or non-operation.
If the ceiling is to be repainted after the installation of the Sprinkler, care must be exercised to ensure that the new paint
does not seal off any of the air gap.
Factory painted Cover Plates must not be repainted. They should be replaced, if necessary, by factory painted cover
plates. Non-factory applied paint may adversely delay or prevent sprinkler operation in case of a fire.
Do not pull the Cover Plate. Separation may result.
In preparation for maintenance of the fire protection system, permission to close the main control valve must be
obtained from the proper authorities and all affected by this action parties must be informed before the maintenance
session can commence.
Do NOT enclose any sprinklers within drapes, curtains, or valances.
Do NOT hang anything from the sprinklers.
Do NOT clean the sprinklers with soap and water, detergents, ammonia, cleaning fluids, or other chemicals. Remove
dust, lint, cobwebs, cocoons, insects, and larvae by gently brushing with a feather duster or gently vacuuming with a
soft bristle (i.e., dusting) brush attachment.
Exercise suitable safety precautions in the use and storage of highly flammable materials. The rapid rate of fire
development and spread of these materials can reduce the ability of the sprinkler systems to aid in the control of a fire
involving such hazards.
Leaking or corroded sprinklers must be replaced.
Automatic Sprinklers must never be shipped or stored where the temperature exceeds 1001/38°C.
Automatic sprinkler must never be physically altered, such as painted, plated, or coated, once shipped from the factory. If the
sprinklers have been in any way modified, they must be replaced.
Great caution must be applied to prevent damage to the sprinklers at all stages - before, during, and after installation. Damaged
units, as a result of dropping, hitting, over-tightening, or wrench slippage, must be replaced.
The Model RC-RES must only be replaced with pendent sprinklers which are listed for residential fire protection service and
which have the same nominal K-Factor, the same coverage area, and the same or lower flow ratings (as indicated under Table A
"Hydraulic Design Criteria").
When remodeling, such as by adding false beams or light fixtures or changing the location of compartment walls, first verity that
the new construction will not violate the installation requirements of the applicable standards of NFPA. Alter the new construction
and/or the sprinkler system to suit the requirements of this document and the applicable NFPA regulations.
The owner is responsible for the maintenance of the sprinkler system, including inspection and testing, its compliance with this
documents, as well as the standards of the National Fire Protection Association (e.g., NFPA 25), and the regulations of any other
authorities having jurisdiction. The owner should direct any questions regarding the above rules and regulations to the installing
contractors or the sprinkler manufacturer. It is recommended that automatic sprinkler systems be inspected, tested, and
maintained by a qualified Inspection Service in accordance with NFPA 25.
Document No. U085160 Date : Feb/09/2015
Page 8 of 8
ORDER PROCEDURE
When placing an order, please contact a local distributor with the following information (Model Name, Specify, Temp. and Finish).
Sprinkler:
Model: RC-RES
(SIN: SS8464, Residential Flat Concealed Sprinkler, Pendent, K4.9, Temperature: 162T (72°C) or 175'F (79°C))
Cover Plate Assembly:
2-5/8 inch (68mm) or 3-1/4 inch (83mm) or 2-5/8 inch square (068mm), Order Separately from Sprinkler
Please refer to the chart below for available sizes, temperature, and finishes.
Standard Finishes Custom Finishes
Mite Ivory Beige Brown Black Nickel Wood grain Custom Color Custom Pattern
2-5/8" Round, 140°F 0 0 - - - 0 - 0 0
3-1/4" Round, 140°F 0 0 0 0 0 0 0 0 0
2-5/8" Square, 140°F 0 - - - - - - 0 0
2-5/8" Round, 162°F 0 - - - - - - 0 0
3-1/4" Round, 162°F 0 - - - - - - 0 0
Tools for Installation of Model: RC-RES
Socket for Model RC-RES
Wrench & Socket for Model RC-RES
Cap Remover RC
Document No. U085160 Date Feb/09/2015
Fl Res 30, 49, 58 & 76 Fl Res 30, 49, 58 & 76
Recessed Pendent! Fl Recessed Pendent I FP
(7)
Fl Res 30,49,58&76 Fl Res 44&58 Fl Res 44 SWC
COP Pendent Recessed HSW/F2
Bulletin 135 Rev. M
Model Fl
Residential Sprinklers for
Design Density of .05 gpm/ft2 CD
Model Fl Res Sprinklers engineered for the lowest flows
to meet the minimum design density of .05 gpm/1t2
Types:
Fl Res 30Pendent
Fl Res 30 Recessed Pendent/F2
Fl Res 30 Recessed Pendent/FP
Fl Res 49 Pendent
Fl Res 49 Recessed Pendent/Fl
Fl Res 49 Recessed Pendent/FP
Fl Res 58 Pendent
Fl Res 58 Recessed Pendent/Fl
Fl Res 58 Recessed Pendent/FP
Fl Res 76 Pendent
Fl Res 76 Recessed Pendent/Fl
Fl Res 76 Recessed Pendent/FP
Fl Res 30 CCP Pendent
Fl Res 49 CCP Pendent
Fl Res 58 COP Pendent
Fl Res 76 CCP Pendent
Fl Res 44HSW
Fl Res 44 Recessed HSW/F2
Fl Res 58HSW
Fl Res 58 HSWX
21, KRes58HSWX
Fl Res 58 HSW Recessed HSW/F2
Fl Res 44 SWC
Listings & Approvals
1. Listed by Underwriters Laboratories Inc. and
UL Certified for Canada (cULus)
Sprinklers for .10 Density: Refer to Bulletin 176
UL Listing Category
Residential Automatic Sprinkler
UL Guide Number
VKKW
Patents
US Patent No. 6,516,893 applies to the Model Fl Res 49
& 58 Pendent Sprinklers
US Patent No. 7,353,882 applies to Model Fl Res 44 & 58
HSW Sprinklers
US Patent No. 7,784,555 applies to Model Fl Res 44 SWC
Sprinklers
Product Description
Model Fl Res Pendent sprinklers (Figs. 1, 2, 3, & 4) are fast
response sprinklers combining excellent durability, high sensitiv-
ity glass-bulb and low profile decorative design. The Fl Res
Horizontal Sidewall sprinklers (Figs. 5, 6 & 7) are equally attrac-
tive when above ceiling piping cannot be used.
The 3mm glass-bulb pendent sprinklers permit the efficient use
of residential water supplies for sprinkler coverage in residential
fire protection design.
The low flow Fl Res sprinklers are specially engineered for fast
thermal response to meet the sensitive fire protection applica-
tion needs of the latest residential market standards (UL 1626
Standard). Upon fire conditions, rising heat causes a sprinkler's
heat-sensitive element, glass bulb or link to actuate, releasing the
waterway for water flow onto the deflector, evenly distributing the
discharged water to control a fire.
Technical Data:
Thermal Sensor: Soldered Element (Link) or Nominal
3mm glass-bulb
Sprinkler Frame : Brass Casting
Sprinklers' Pressure Rating: 175 psi
Factory Hydrostatically Tested to 500 psi
Thread Size: ½" NPT (R½)
K-Factor: 3.0 (43.2) (Actual) - Fl Res 30 Pendent Sprinkler
4.9 (70.6) (Actual) - Fl Res 49 Pendent Sprinkler
5.8 (83.5) (Actual) - Fl Res 58 Pendent & HSW Sprinkler
7.6 (109)(Actual) - Fl Res 76 Pendent Sprinkler
4.4(63) (Actual) - Fl Res 44 HSW Sprinkler
Density: Minimum 0.05 gpm/ft2
Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York 10523
Application
Model Fl Res Sprinklers are used for Residential Fire Pro-
tection according to UL 1626 Standard*. For ceiling types:
Smooth Flat Horizontal, or beamed, or sloped, in accordance
with NFPA 13D, 13R, or 132013 editions. Be sure that orifice
size, temperature rating, deflector style and sprinkler type are
in accordance with the latest published standards of The Na-
tional Fire Protection Association or the approving authority
having jurisdiction.
Installation
Models Fl Res sprinklers are to be installed as shown.
Model Fl, F2 and FP Escutcheons, illustrated herewith, are
Escutcheon*, Fl or F2, Data:
the only recessed escutcheons to be used with Model Fl Res
sprinklers. Use of any other recessed escutcheon will void all
approvals and warranties. For installing Model Fl Res Pen-
dent sprinklers use only the Model D sprinkler Wrench; for
installing Models Fl Res Recessed Pendent, CCP & SWC
sprinklers use only the Model GFR2 sprinkler wrench; for in-
stalling Model Fl Res Recessed HSW sprinklers use only the
Model GFR2 Sprinkler Wrench. Use of wrenches other than
those specified may damage these sprinklers. Install Fl Res
44 with a ceiling to deflector distance of 4" - 12'. Flow arrow
on deflector must point away from near wall and "Top" mark-
ing must face ceiling.
Type Adjustment 'A" Face of fitting to ceiling Deflector Distance below bottom of beam Inch (mm) Inch (mm) Inch (mm) Inch (mm)
Fl 3/4 (19.0) Mm. Recessed = 1/e (41.3) 3/8 (9.5) 13/4(44.4) Max Recessed =7/s (22,2) 11/8 (28.6) 1(25.4)
F2 1/2 (12.7) Mm. Recessed = 1/o (41.3) 3/a(9,5) 1/4 (44.4) M. Recessed =11/8(28.6) 7/4 (22.2) 11A(31.7) * Note: Escutcheons Fl or F2 may be used with Model Fl Res 49, 58 & 76 Recessed Pendent Sprinkler -
Model Fl Res 30 Recessed Pendent / F2
Model Fl Res 30, 49, 58 & 76 Pendent • Mod i i-i iies 4, tm & lb iiecessea i-'en lent/Fl
Fl escutcheon, 3/4" (19mm) adjustment
2 I/4 HOLE 0/4.
...-[572m]-.
I I5/16 OH.
I [49.2mm]
1r
TURN COLLAR UNTIL I" 1/2' REDUCER
TIGHT AGAINST SPRINKLER FACE OF FITTING To
CEILING OIMENSIONr WRENCH BOSS. FAC E
1/8" (Fl ESCUTCHEON)
3/8-7/8 (F2 ESCUTCHEON)
ADJUSTMEN t
2 27/32 OIA.
[72.2mm]
Fig. 1 Fig. 2
Technical Data: Fl Res 30 Pendent and Recessed Pendent (SIN R351 1)
Thread
Size
I Nominal Orifice
Inch (mm)
Max. Pressure
psi (bar)
I Sprinkler Temp. Rating! Max. Ambient Temp.! Actual l<
Factor
I Sprinkler Length I
Inch (mm) OF I °C OF I e
½"NPT
(R1/2) 21/64" (8.2) I 175(12) 155
175
I 68
79 I I 100 38 3.0(43.2) 2.25 (57)
Max. Coverage area
Ft x Ft (m x m)
Max.
Spacing
Ft (m)
Ordinary Temp. Rating
(1550 80C)
Intermediate Temp. Rating
(175°F/790C) Top of Deflector to Ceiling
Inch (mm)
Minimum
Spacing
Ft (m)
Flow
GPM (Llmin)
Pressure
PSI (bar)GPM
Flow
(Llmin)
Pressure
PSI (bar)
12 x 12(3,6 x 3,6) 12(3,6) 8(30,3) 7.0 (0,48) 8(30,3) 7.0(0,48) Smooth ceilings 11/4 to 4(31.7 to 102)
using F2 escutcheon.
14 x 14 (4,3 x 4,3) 14(4.3) 10(37,8) 11(0,76) 10 (37,8) 11(0,76) Beamed Ceilings per NFPA 13D, 13R
or 13 installed in beams 11/4 to 13/4
(31.7 to 44.4) using F2 escutcheon
8(2,4)
16 X 16(4,9 X 4,9) 16(4,9) 13(49) 18.8(1,3) 13(49) 18.8(1,3)
For Ceiling types refer to NFPA 13, 13R or 13D
2.
Technical Data: Fl Res 49 Pendent and Recessed Pendent (SIN R3516)
Thread Nominal Orifice Max. Sprinkler Max. I Actual Sprinkler 1
Size Inch (mm) Pressure Temp. Rating Ambient Temp. K Length I
F I °C OF °C psi (bar) I Factor I Inch (mm)
½' NPT
(R½) /l6" (11) 175 (12) 155
175
68
79
100
150
I 38 I
I 66 4.9 (70.6) 2.25 (57) J
Ordinary Temp. Rating Intermediate Temp. Rating
Max. Coverage area Max. Spacing (l55°Fi8°C) (175°Fi790C) Top of Deflector Minimum
Ft x Ft (mx m) Ft (m) to Ceiling Spacing Flow I Pressure Flow Pressure
GPM(L/min) I PSI (bar) GPM(L/min) PSI (bar) Inch (mm) Ft (m)
12 x 12 (3,6 x 3,6) 12(3,6) 13 (49) 7.0(0,48) 13(49) 7.0(0,48) Smooth Ceilings 11/4 to 4(31.7 to
102) using F2 escutcheon.
14 x 14(4,3 x 4,3) 14(4,3) 13 (49) 7.0 (0,48) 13(49) 7.0 (0,48) 1 t 4(25.4 to 102) using Fl
escutcheon.
16 x 16(4,9 x 4,9) 16(4,9) 13(49) 7.0 (0,48) 13 (49) 7.0(0,48) Beamed Ceilings per NFPA
130, 13R or 13 installed in 8 (2,4)
18 x 18(5,5 x 5,5) 18(5,5) 17(64,3) 12(0,83) 17(64,3) 12(0,83) beams 11/4 to i/4 (31,7 to
44.4) using F2 escutcheon, 1
20 x 20(6,1 x 6,1) 20(6,1) 20(75,7) 16.7 (1,14) 20(75,7) 16,7(l.14) to 1/4 (25.4t044.4) using Fl
_____________ ____________ 'escutcheon
For Ceiling types refer to NFPA 13, 13A or 130
Ordinary Temp. Rating Intermediate Temp. Rating
Max. Coverage area Max. Spacing (1 55°Fi8°C) (175°F/790C) Top of Deflector Minimum
Ft x Ft (mx m) Ft (m) to Ceiling Spacing Flow Pressure Flow Pressure
GPM (Llmin) PSI (bar) GPM (1/min)PSI (bar) Inch (mm) Ft (m)
12 x 12 (3,6 x 3,6) 12(3.6) 15 (57) 9.4 (0,65) 15(57) 9.4 (0,65) Smooth Ceilings 4 to 8(100 to
203) using F2 escutcheon.
4 to 8(100 to 203) using Fl
escutcheon.
Beamed Ceilings per NFPA 13D,
13R or 13 installed in beams
4¼t0 8(108 to 203) using F2
escutcheon, 4 to 8(100 to 203)
using Fl escutcheon
8(2,4)
14 x 14(4,3 x 4,3) 14(4,3) 16(60,5) 10.6 (0,73) 16(60,5) 10.6 (0,73)
16 x 16 (4,9 x 4,9) 16(4,9) 17(64,3) 12.0(0,83) 17 (64,3) 12.0 (0,83)
18 x 18(5,5 x 5,5) 18(5,5) 19(72) 15.0 (1,0) 19(72) 15.0(1,0)
20 x 20(6,1 x 6,1) 20(6,1) 22(83,2) 20.2 (1,4) 22(83,2) 20.2 (1,4)
Technical Data: Fl Res 58 Pendent and Recessed Pendent (SIN R3513)
Thread Nominal Orifice Max. I Sprinkler I Max. I
Actual Sprinkler
Size Inch (mm) Pressure Temp. Rating I Ambient Temp. K Factor Length
I OF °C I OF I °C psi (bar) Inch (mm)
½" NPT
(R½) ½" (13) I I 175(12) 155
175
68
79
I 100
150
38
66 5.8 (83.5) I
2.25 (57)
Max. Coverage area Max. Spacing
Ordinary Temp. Rating
(1550Fi8°C)
Intermediate Temp. Rating
(1750F1790C) Top of Deflector Minimum
Ft x Ft (mx m) Ft (m) to Ceiling Spacing Flow Pressure Row Pressure
GPM (L/min) PSI (bar) GPM (11mm) PSI (bar) Inch (mm) Ft (m)
12 x 12(3,6 x 3,6) 12(3,6) 16(61) 7.6 (0,53) 16(61) 7.6 (0,53) Smooth Ceilings 11/4 to 4(31.7 to
102) using F2 escutcheon, 14 x 14(4,3 x 4,3) 14(4,3) 16 (61) 7.6 (0,53) 16(61) 7.6 (0,53) 1 t 4(25.4 to 102) using Fl
escutcheon, 16 x 16 (4,9 x 4,9) 16(4,9) 16 (61) 7.6 (0,53) 16 (61) 7.6 (0,53) Beamed Ceilings per NFPA 130,
13R or 13 installed in beams
8(2,4)
18 x 18(5,5 x 5,5) 18(5,5) 19(72) 10.8 (0,75) 19(72) 10.8 (0,75) 11A to 1/4 (31.7t0 44.4) using
F2 escutcheon, 1 t 13A (25.4 to 20 x 20(6,1 x 6,1) 20(6,1) 22(83,3) 14.4(1,0) 22(83,3) 14.4(1,0) 44.4) using Fl escutcheon
For Ceiling types refer to NFPA 13, 13R or 130
0
Technical Data: Fl Res 76 Pendent and Recessed Pendent (SIN R7618)
Thread Nominal Orifice Max. Sprinkler I Max. K I Sprinkler
Size Inch (mm) I Pressure Temp. Rating Ambient Temp. I Factor Length
j °F I °C psi (bar) Inch (mm)
/32"(13.5) 175 (12) I 155
175 I
68
j
I
79 I
100
150
38
I 66
I
I 7.6(109) 2.25(57)
Ordinary Temp. Rating Intermediate Temp. Rating 1 Max. Coverage area Max. Spacing (1 55°Fi8°C) (175°F/79°C) Top of Deflector to Ceiling Minimum
Ft x Ft (mx m) Ft (m) Inch (mm) Spacing Flow Pressure Flow GPM Pressure
GPM (1/mm) PSI (bar) (Lknin) PSI (bar)
Ft 'm
12 x 12 (3,6 x 3,6) 12(3,6) 21(79,5) 7.6 (0,53) 21(79,5) 7.6 (0,53) Smooth Ceilings 41/4 to 8 (108
o 203) using F2 escutcheon. 14 x 14(4,3 x 4,3) 14(4,3) 21 (79,5) 7.6 (0,53) 21(79,5) 7.6 (053) 4 to 8(100 to 203) using Fl
escutcheon. 16x 16(4,9x4,9) 16(4,9) 21(79,5) 7.6(0,53) 21(79,5) 7.6(0,53) Beamed Ceilings per NFPA
13D, 13R or 13 installed in
8(2,4)
18x 18(5,5x5,5) 18(5,5) 21(79,5) 7.6(0,53) 21(79,5) 7.6(0,53) beams 4%t08(108t0203)us-
ing F2 escutcheon, 4 to 8(100 20 x 20(6,1 x 6,1) 20(6,1) 23(87,1) 9.2(0,63) 23(87,1) 9.2(0,63) to 203) using Fl escutcheon
ror L.euIng types rerer to NI-t-A 1, 13K or 13L)
aei t-i Hes 50, 49, 55 & 16 CGP Per
>1
dent* • Model Fl Res 30, 49, 58 & 76
Recessed Pendent / FP
* Not listed for corrosion resistance.
2 5/8' [66.7mm] 0/A. 2 5/76" 0/A. HOLE IN CEILING [58.7mm]
CUP
lx 7/2" REDUCER
cup CEILING
/13 MAX.FITTING TO FACE OF CEILING DIMENSION
A I
i
"a"
T
COVER ADJUSTMENT HEIGHT
1J5FGO4E .mm
Fl RES 30, 49, 58 & 76 CCF PEND.
Fig. 3
Note: The Fl Res 76 will use a 1" x 3%" reducer.
CCP Cover Plate Data:
"A" "B" C
Cover Adjustment CCP Height Deflector Distance below bottom
Inch (mm) Inch (mm) of beam
Inch (mm)
1/2 (12.7) 15/16 (24) ½ (13) - 1(25.4)
/16 (7.9) I /4(19) ½ (13) - 1(25.4)
FP push-on/thread-off escutcheon
2 5/8" 0/A. [66.7mm]
HOLE IN CEILING -
2 5/16" 0/A.
- [58.7mm]
CUP
tp-
- 1" X 1/2" REDUCER
CEILING 1 7/2[38. 7mm] MAX.
FACE OF FITTING
TO FACE OF CEILING
ENS/ON
1/2" [13mm]
FP ADJUSTMENT
Fl RES 49 PENDENT-/FP
-
Fig. 4
FP Escutcheon Data:
"B"
FP Position "A" Deflector Distance below bottom
Inch (mm) of beam
Inch (mm)
Max, Recessed /i(11) I 1/2 (12,7)
Mm. Recessed /l6(24) 1(25.4)
Note: Sprinklers shown in Fig. 3 and Fig. 4 are not suitable for installation in ceilings which have positive pressure in
the space above.
4'
Technical Data: F1 Res 30 CCP Pendent and Recessed Pendent/FP (SIN R351 11
Thread Nominal Max. CCP Assembly Max. Sprinkler
Size O Orifice I Pressure Temp. Rating Ambient Temp. I K I Length
OF I OF °C j Inch (mm) psi (bar) Factor I Inch (mm)
½"NPT
(R½)
21/ (8.2) 175 (12) 135 57 100 38 3.0 (43.2) 2.25(57)
Ordinary Temp. Rating
(155°F/680C) lop of Deflector to Ceiling
Flow Pressure Inch (mm)
PM (1/mm) PSI (bar)
Smooth Ceilings ½ to 1(13 to 25.4) using COP. 8(30.3) 7,0 (0,48) ½ to 1(13 to 25.4) using FP escutcheon.
Beamed Ceilings per NFPA 13D, 13R or 13 installed in
14 x 14(4,3 x 4,3) 14(43) 11(37,8) 13.4 (0,92) beams ½ to 1(13 to 25.4) using COP.
½ to 1(13 to 25.4) using FP escutcheon,
For Ceiling types refer to NFPA 13, 13R or 130
Technical Data: F1 Res 49 CCP Pendent and Recessed Pendent/FP (SIN 3516)
Nominal cci I I Max.
Thread Orifice Max. Assembly Ambient K Sprinkler
Size Inch Pressure Temp. Temp . Factor Length
(mm) psi (bar) Rating ____ Inch (mm)
OF I °C OF I
½"NPT
(A½) /16" (11) 175 (12) 135 57 100 I 38 4.9 (70.6) 2.25 (57)
Max. Coverage Ordinary Temp. Rating Minimum
area Max. Spacing (155-17/680C) Top of Deflector to Ceiling Spacing
Ft x Ft (m x m) Ft (m) Flow Pressure Inch (mm) Ft (m) GPM (Um n) PSI (bar)
12 x 12(3,6 x 3,6) 12(3,6) 13(49) 7.0 (0,48)
Smooth Ceilings ½ to 1(13 to 25.4) using 14 x 14(4,3 x 4,3) 14(4,3) 13(49) 7.0 (0,48) COP.
1/2 to 1 (13 to 25.4) using FR escutcheon. 16 x 16 (4,9 x 4,9) 16(4,9) 14 (53) 8.2 (0,56) Beamed Ceilings per NFPA 130, 13R or 13
installed in beams ½ to 1(13 to 25.4) using
8(2.4)
18 x 18(5,5 x 5,5) 18(5,5) 18(68,1) I 13.5 (0,93) COP.
V2 to 1(13 to 25.4) using FR escutcheon, 20 x 20 (6,1 x 6, 1) 20(6,1) 20(75,7) 16.7 (1,14)
i-or ueiiing types reterto NbF-1A 13, 13H or 130
Technical Data: F1 Res 58 CCP Pendent and Recessed Pendent/FP (SIN R3513)
Thread Nominal I Max. I CCP Assembly I Max. I K I Sprinkler I
Size Orifice Pressure Temp. Rating Ambient Temp. I Length I OF I °C I C Inch (mm) psi (bar) Factor I I Inch (mm)
½" NPT
(R½)1/2" (13) 175(12) 135 57
f0F
f38 5.8 (83.5) 2.25 (57)
Max. Coverage area Max. Spacing
FtxFt(mxm) Ft (m)
12 x 12(3,6 x 3,6) I 12(36)
Minimum
Spacing
Ft (m)
8(2,4)
Max. Coverage j Ordinary Temp. Rating Minimum Max. Spacing (1550F/680C) lop of Deflector to Ceiling area
Ft x Ft (m x m) Ft (m) Inch (mm) Spacing
Ft (m)
Flow Pressure
GPM (11mm) PSI (bar)
12 x 12(3,6 x 3,6) 12(3,6) 16(61) 7.6 (0,53)
Smooth Ceilings ½ to 1(131025.4) using COP.
½ to 1(13 to 25.4) using FR escutcheon.
14 x 14 (4,3 x 4,3) 14(4,3) 16(61) 7,6 (0,53)
16 x 16(4,9 x 4,9) 16(4,9) 16(61) 7.6 (0,53) Beamed Ceilings per NFPA 13D, 13R or 13 installed in beams 1/2 to
1(13 to 25.4) using OCR
8(2,4)
18 x 18 (5,5 x 5,5) 18(5,5) 19(72) 10.8(0,75) ½ to 1(13 to 25.4) using FR escutcheon.
20 x 20 (6,1 x 6, 1) 20(6,1) 22(83,3) 14.4(1,0)
-or Ueiling types reler to Nh-PA 13, 13H or 130
5.
Model Fl Res 44 & 58 Recessed HSW/F2
F2 escutcheon,
1/2" (13mm) adjustment
Technical Data: Fl Res 76 CCP Pendent and Recessed Pendent/FP (SIN R7618)
Thread Nominal Max. CCP Assembly Max. K Sprinkler
Size Orifice Pressure Temp. Rating Ambient Temp. Factor Length
OF I °C OF °C Inch (mm) psi (bar) Inch (mm) I
NPT
LJ i
I 17/32 (13.5) 175 (12) I 135 100
1 50 I
I 38
66 7.6 (109) I I
2.25 (57)
Max. Coverage Ordinary Temp. Rating
Minimum area Max. Spacing (155°F/68°C) Top of Deflector to Ceiling Spacing Ft x Ft (mx m) Ft (m) Flow Pressure Inch (mm) Ft (m) GPM (Llmin) PSI (bar)
12 x 12(3,6 x 3,6) 12(3,6) 21(79,5) 7.6 (0,53)
Smooth Ceilings ½ to 1(13 to 25.4) using COP.
/2 to 1(13 to 25.4) using FP escutcheon.
14 x 14 (4,3 x 4,3) 14(4,3) 21(79,5) 7.6 (0,53)
16 x 16 (4,9 x 4,9) 16(4.9) 21(79,5) 7.6 (0,53) Beamed Ceilings per NFPA 13D, 13R or 13 installed in beams ½
to 1(13 to 25.4) using CCP.
8(2,4)
18 x 18(5,5 x 5,5) 18(5,5) 22 (83,3) 8.4 (0,58) ½ to 1(13 to 25.4) using FP escutcheon.
20 x 20(6,1 x 6,1) 20(6,1) 25(94,6) 10.8 (0,74)
rui l,miriy LJ0Z2 IINHI 10 INTFP, ii, ldh or iju
Model Fl Res 44 & 58 HSW
r~"
FACE OF FITTING TO -
WALL DIMENSION
7 r ri
1 1/4" MIN.
2 1/4" HOLE DIA. [31.8mm]
—H---1/8 I r [5 7.2mm]
DEFLECTOR
I" X 1/2" REDUCER
[32mm]I CEILING TO
DIMENSION
I 15/16"DIA.1LJ
27 [49.2m
I
/32" DIA.
- COLLAR UNTIL
. [72.2mm]
TURN
TIGHT AGAINST SPRINKLER
WRENCH soss.
1/2" [13mm] 135rC06-D H ADJUSTMENT
Fl RES 58 & 44 HSW/F2
Hg. 5
Technical Data: F1 Res 44 HSW & HSW/F2 (SIN R3531)
Thread Nominal Max. Sprinkler Max.
Ambient
I
K Sprinkler
Size Orifice Pressure Temp. Rating Temp. Factor Length
Inch (mm) psi (bar) Inch (mm) 1°F 1°C OF -C
½" NPT
(R½) /8" (10) 175(12)
I
155
175 I
68
79
100
150
38
66 4 .4 (63) 2.45 (62)
Escutcheon, F2, Data:
Face of Fitting
Type Adjustment to wall Inch (mm) Inch (mm)
F2 1/2 (13) 1/16 - 11/16
_____ __________
(4.7-17.4)
91
Max. Coverage area
Ft x Ft (m x m)
Max. Spacing
Ft (m)
Ordinary Temp. Rating
(1550Fi80C)
Intermediate Temp. Rating
(175°F/79°C) Top of Deflector to
Ceiling
Inch (mm)
Minimum
Spacing
Ft (m)
Flow
GPM (L/min)
Pressure
PSI (bar)
Flow
GPM (Llmin)
Pressure
PSI (bar)
12 x 12 (3,6 x 3,6) 12(3.6) 12(45,4) 7.5(0,52) 12 (45,4) 7.5 (0,52)
4to6(100t0 152);
112 (13) recessed
using F2 escutcheon
8(2,4)
14 x 14 (4,3 x 4,3) 14(4,3) 14(53,0) 10.2(0,71) 14 (53,0) 10.2 (0,71)
16x 16(4,9X4,9) 16(4,9) 16(60,6) 13.3(0,92) 16(60,6) 13.3(0,92)
16 x 18(4,9 x 5,5) 16(4,9) 18(68,1) 16.8(1,16) 18(68,1) 16,8 (1,16)
18 x 18(5,5 x 5,5) 18(5,5) 19(72,0) 18.7 (1,29) 19(72,0) 18.7(l.29)
16 x 20(4,9 x 6,1) 16(4,9) 23(87,1) 27.4(1,89) 23(87,1) 27.4 (1,89)
12 x 12(3,6 x 3,6) 12(3,6) 14(53,0) 10.2(0,71) 14(53,0) 10.2 (0,71)
6t0 12 (152 to 305);
½ (13) recessed
using F2 escutcheon
14 x 14(4,3 x 4,3) 14(4,3) 16(60,6) 13.3(0,92) 16 (60,6) 13.3 (0,92)
16 x 16(4,9 x 4,9) 16(4,9) 17(64,4) 15.0(1,04) 17(64,4) 15.0(1,04)
16 x 18(4,9 x 5,5) 16(4,9) 20(75,7) 20.7(1,43) 20(75,7) 20.7 (1,43)
16 x 20 (4,9 x 6,1) 16(4,9) 23(87,1) 27.4(1,89) 23(87,1) 27.4(1,89)
For Ceiling types refer to NFPA 13, 13R or 13D
Technical Data: F1 Res 58 HSW & HSWIF2 (SIN R3533)
Escutcheon, F2, Data:
Nominal Max. Sprinkler Adjustment
Max. Sprinkler Face of Fitting Thread Orifice Ambient K Length Pressure Temp. Rating Type Size Inch Temp. Factor Inch Inch (mm) to wall
Inch (mm) psi (bar) (mm) OF I °c OF I °C (mm) ______
/I6- 11/16 ½" NPT 155 68 100 38 F2 1/2 (13) (47 17.4) 1/2 (13) 175 (12) 5.8 (83.5) 2.45 (62) _______ ______ (R½) 175 79 150 66
Ordinary Temp. Rating Intermediate Temp. Rating Top of Deflector to Minimum Max. Coverage area Max. Spacing (155°Fi80C) (175°F/79°C) Ceiling Spacing Flow Pressure Flow Pressure Ft x Ft (m x m) Ft (m) Inch (mm) Ft (m) GPM (1/mm) PSI (bqrL GPM (1/mm) PSI (bar)
12 x 12(3,6 x 3,6) 12(3.6) 16(60,6) 7.6(0,53) 16(60,6) 7.6 (0,53)
4 to 6 (100 to 152);
14 x 14(4,3 x 4,3) 14(4.3) 18(68,2) 9.7(0,69) 18(68,2) 9.7(0,69)
16 x 16(4,9 x 4,9) 16(4,9) 21(79,5) 13.2 (0,91) 21(79,5) 13.2 (0,91) ½ (13) recessed
using F2 escutcheon 16 x 18(4,9 x 5,5) 16(4,9) 25(94,7) 18.6(l.28) 25(94,7) 18.6 (1,28)
8(2,4) 16 x 20(4,9 x 6,1) 16(4,9) 29(109,8) 25.0(1,73) 29(109,8) 25.0 (1,73)
12 x 12(3,6 x 3,6) 12(3,6) 22(83,3) 14.4(1,0) 22(83,3) 14.4(1,0)
6 to 12 (152 to 305);
½(13) recessed
14 x 14(4,3 x 4,3) 14(4,3) 22(83,3) 14.4(1,0) 22(83,3) 14.4(1,0)
16 x 16(4,9 x 4,9) 16(4,9) 26(98,4) 20,1 (1,39) 26(98,4) 20.1 (1,39) using F2 escutcheon
16 x 18(4,9 x 5,5) 16(4,9) 31(117,4) 28.6 (1,97) 31(117,4) 28.6(l.97)
or Ceiling types refer to NFPA 13, 138 or 130
Model Fl Res 44 SWC
(.
'It
1'
'-- -
* Not listed for corrosion resistance,
Technical Data: F1 Res 44 SWC SIN R3531)
4' to 72" [I0I.60n,ln To
I I/4[3I.75n,,'nJ Mooi,rn,n 304.80ooJ
Foco Of Fitting
To Wall O,n,ens,00 PUSH ON COVER. THEN TURN TO ADJUST UNTIL
TIGHT AGAINST WALL.
I'D I/2 Rd*o,'
-- Recommended
f, 1 1-4 74m
2Y?6,
3 5116-
TURN COLLAR UNTIL
TIGHT AGAINST SPRINKLERWRENCH 1 21132- BOSS.
- I/2 7O
Adjustment
Fl RES 44 SWC
Fig. 6
Nominal Max. Cover Max. Sprinkler Thread Orifice Pressure Temp. Ambient K Length Size Inch (mm) psi (bar) Rating Temp.Factor I Inch (mm)
½" NPT
(R½)
/e" (10) 175(12) 135 57 100 38 4.4 (63) 2.45(62)
Max. Coverage area
Ft x Ft (mx m)
Max. Spacing
Ft (m)
Ordinary Temp. Rating
(155°FI8°C) Top of Deflector to
Ceiling
Inch (mm) PSI (bar)
Minimum I
Spacing
Ft (m) Flow
GPM (1/mm)
Pressure
12 x 12(3,6 x 3,6) 12(3,6) 13(49,2) 8,7(0,60)
4t06(100to 152),
½ (13) recessed
using F2 escutcheon
8(2,4)
14x 14(4,3x4,3) 14(4,3) 14(53,0) 10.2 (0,71)
16 x 16(4,9 x 4,9) 16(4,9) 17(64,3) 15.0(1,1)
16 x 18 (4,9 x 5,5) 16(4,9) 19(71,8) 18.7(1,13)
16 x 20(4,9 x 6,1) 16(4,9) 23(87,1) 27.4 (1,89)
12 x 12(3,6 x 3,6) 12(3,6) 14(52,9) 10.2 (0,71)
6 to 12 (152 to 305):
½ (13) recessed
using F2 escutcheon
14 x 14(4,3 x 4,3) 14(4,3) 15(56,7) 11.7(0,81)
16 x 16(4,9 x 4,9) 16(4,9) 18(68,1) 16.8 (1,16)
16 x 18(4,9 x 5,5) 16(4,9) 20(75,6) J 20.7(1,43)
For Ceiling types refer to NFPA 13, 13R or 13D
F;J
TURN COLLAR UNTIL
TIGHT AGAINST SPRINKLER
WRENCH BOSS.
135FG08
rl~/~ I
--1
[318mm] I 6" MIN.
':4',
CEILING TO [32mm] DEFLECTOR
DIMENSION
2 27/32" DIA.
(72.2mm]
7/2" [13mm]
ADJUSTMENT
FACE OF FITTING TO
WALL DIMENSION
2 1/4" HOLE DIA.
[57.2mm]
1" X 1/2" REDUCER
iy I ?5/I6DIA.4J - -
Fl RES 58 HSWX
Fig. 7
Technical Data: Fl Res 58 HSWX (SIN RA3533)
Thread Nominal I Max. Sprinkler A
Max.
mbient K Sprinkler Sprinkler Orifice Size
_____________
Pressure Temp. Rating Temp. ___________ Factor Length Identification Inch (mm) psi (bar) Inch (mm) OFOC
Number (SIN) OF bc
Bulb ½" NFl
(R½) 1/2' (13) 175 (12) 155
175
68
79
100
150
I 38
66 5.8 (83.5) 2.45 (62) RA3533
Max. Coverage area
Ft x Ft (m x m)
Max. Spacing
Ft (m)
Ordinary Temp. Rating
(155°F/680C)
Intermediate Temp. Rating
(175°F/79°C) of Deflector to Top
Ceiling
Inch (mm)
Minimum
Spacing
Ft (m)
Flow
GPM (Umin)
Pressure
PSI (bar)
Flow
GPM (Umin)
Pressure
PSI (bar)
18 x 20(5,5 x 6,1) 18(5,5) 30(114) 26.8 (1,85) 30(114) 26.8 (1,85)
4t06(100to 152),
1/2(13)recessed
using F2 escutcheon
8(2,4)
20x 20(6,1 x 6,1) 20(6,1) 30(114) 26.8 (1,85) 30(114) 26.8 (1,85)
16 x 22(4,9 x 6,7) 16(4,9) 33(125) 32.4 (2,23) 33(125) 32.4 (2,23)
16 x 24 (4,9 x 7,3) 16(4,9) 38(144) 42.9 (2,96) 38(144) 42.9 (2,96)
14 x 26(4,3 x 7,9) 14(4,3) 42(160) 52.4 (3,75) 42(160) 52.4 (3,75)
18 x 20(5,5 x 6,1) 18(5,5) 35 (133) 36.4 (2,5) 35(133) 36.4 (2,5)
6 to 12 (152 to 305);
1/2 (13) recessed
using F2 escutcheon
16 x 22(4,9 x 6,7) 16(4,9) 38(144) 42.9 (2,96) 38(144) 42.9 (2,96)
16 x 24 (4,9 x 7,3) 16(4,9) 42(160) 52.4(3,6) 42(160) 52.4 (3,6)
14 x 26(4,3 x 7,9) 14(4,3) 46(174) 62.9 (4,34) 46(174) 62.9 (4,34)
For Ceiling types refer to NFPA 13, 13R or 13D
Model Fl Res 58 HSWX (Bulb)
Model KRes58 HSWX (Link)
I
•
.•
91
Technical Data: KRes58 HSWX (RA3593)
Thread Nominal Max. Max.
Ambient K Sprinkler Sprinkler
Size Orifice Pressure Temp. Factor Length Identification
Inch (mm) psi,(bar) Inch (mm) Number (SIN) I °C
½" NPT 1/2" (13) 175 (12)
f0F
0
(R½)_______
38 5.8(83.5) 2.45(62) RA3593
Max. Coverage area
Ft x Ft (m x m)
Max. Spacing
Ft (m)
Ordinary Temp. Rating
(165°Fu740C) lop of Deflector to
Ceiling
Inch (mm)
Minimum
Spacing
Ft (m) Flow
GPM (Limin)
Pressure
PSI (bar)
18 x 20 (5,5 x 6,1) 18(5,5) 29(109) 25(1,72)
4t06(lo0to 152);
½ (13) recessed
using F2 escutcheon
8(2,4)
20 x 20 (6,1 x 6, 1) 20(6,1) 30(114) 26.8(1,85)
16 x 22(4,9 x 7,3) 16(4.9) 33(125) 32.4 (2,23)
16 x 24 (4,9 x 7,3) 16(4,9) 38(144) 42.9 (2,96)
14 x 26(4,3 x 7,9) 14(4,3) 42 (160) 52.4 (3,75)
18 x 20(5,5 x 6,1) 18(5,5) 35(133) 36.4 (2,5)
6 to 12 (152 to 305);
½ (13) Recessed
using F2 escutcheon
16 x 22(4,9 x 6,7) 16(4,9) 38(144) 42.9(2,96)
16 x 24(4,9 x 7,3) 16(4,9) I 42(160)
1
52.4(3,6)
14 x 26(4,3 x 7,9) 14(4.3) 46(174) 62.9(4,34)
For Ceiling types refer to NFPA 13, 13R or 13D
Maintenance
Model Fl Res 30, 49, Fl Res 58, Fl Res 76 and Fl Res
44 Sprinklers should be inspected and the sprinkler sys-
tem maintained in accordance with NFPA 25, 13, 13D,
and 13R. Do not clean sprinkler with soap and water, Am-
monia or any other cleaning fluids. Remove dust by using
a soft brush or gentle vacuuming. Remove any sprinkler
which has been painted (other than factory applied) or
damaged in any way. A stock of spare sprinklers should
be maintained to allow quick replacement of damaged or
operated sprinklers. Prior to installation, sprinklers should
remain in the original cartons and packaging until used.
This will minimize the potential for damage to sprinklers
that could cause improper operation or non-operation.
Model Fl Res 30, 49 & 58 Pendent
Sprinkler Specifications
Sprinklers shall be [cULus Listed] [New York City MEA
Approved (258-93-F)] low flow residential pendent sprin-
klers engineered to provide a minimum design density of
0.05 gpm/ft2 over the listed coverage area. Listed flows
as specified by the manufacturer's technical data sheets
are to be used. Residential sprinklers shall be installed
in conformance with the manufacturer's installation guide-
lines and the applicable installation standard. Deflector-
to-ceiling distance listing shall be 1" to 8" maximum, only
for FiRes 49. Sprinkler frame and deflector shall be of
bronze frame construction having a ½" NPT thread. Wa-
ter seal assembly shall consist of a Teflon* coated Bel-
leville spring washer with top-loaded extruded or cold
head cup with 3 mm glass bulb containing no plastic
parts, and having a temperature rating of [155°F (681C)]
[175°F (79°C)]. Sprinklers shall have a nominal K-factor
of 3.0, 4.9 and 5.8. Standard finish: [Bronze] [Chrome-
plated] [White Polyester] [Special finish- specify]. Resi-
dential pendent sprinklers shall be Reliable Model Fl Res
30, 49 & 58, SIN R3511, R3516 & R3513 (Bulletin 135).
Model Fl Res 49 & 58 Recessed Pendent/Fl,
Model Fl Res 30, 49 & 58 Recessed Pendent/
F2, Model Fl Res 30,49 & 58 Recessed Pendentl
FP
Sprinklers shall be [cULus Listed] [New York City MEA
Approved (258-93-F)] low flow residential recessed pen-
dent sprinklers engineered to provide a minimum design
density of 0.05 gpm/ft2 over the listed coverage area.
Listed flows as specified by the manufacturer's technical
data sheets are to be used. Residential sprinklers shall
be installed in conformance with the manufacturer's in-
stallation guidelines and the applicable installation stan-
dard. Deflector-to-ceiling distance listing shall be ito 8"
maximum, only for Fl Res 49. Sprinkler frame and deflec-
tor shall be of bronze frame construction having a ½" NPT
thread. Water seal assembly shall consist of a Teflon*
coated Belleville spring washer with top-loaded extruded
"DuPont Registered Trademark
10.
or cold head cup with 3 mm glass bulb containing no
plastic parts, and having a temperature rating of [155°F
(68°C)] [175°F (791C)]. Sprinklers shall have a nomi-
nal K-factor of 3.0, 4.9 & 5.8. Standard finish: [Bronze]
[Chrome-plated] [White Polyester] [Special finish— spec-
ify]. Recessed escutcheon assembly shall be a steel,
two-piece escutcheon [with 1/2" adjustment (Model F2)]
[with 3/4" adjustment (Model Fl)] [of push-on and thread
off design with 1/2" adjustment (Model FP)]. Standard fin-
ish shall be [brass][bright chrome] [white painted]. Resi-
dential recessed pendent sprinklers shall be Reliable
[Model Fl Res 30, 49 & 58 Recessed Pendent/Fl] [Model
Fl Res 30, 49 & 58 Recessed Pendent/F2] [Model Fl Res
30, 49 & 58 Recessed Pendent/FP] SIN R3511, R3516 &
R3513 (Bulletin 135).
Model Fl Res 30, 49 & 58 CCP Pendent
(Concealed)
Sprinklers shall be [cULus Listed] [New York City MEA
Approved (258-93-E)] low flow residential concealed
sprinklers engineered to provide a minimum design den-
sity of 0.05 gpm/ft2 over the listed coverage area. Listed
flows as specified by the manufacturer's technical data
sheets are to be used. Residential sprinklers shall be in-
stalled in conformance with the manufacturer's installa-
tion guidelines and the applicable installation standard.
Sprinkler frame and deflector shall be of bronze frame
construction having a 1/2" NPT thread. Water seal as-
sembly shall consist of a Teflon* coated Belleville spring
washer with top-loaded extruded or cold head cup with 3
mm glass bulb containing no plastic parts, and having a
temperature rating of 155°F (680C). Cover plate assem-
bly shall consist of a brass cover plate and copper alloy
retainer flange. Method of attaching the cover plate to the
sprinkler cup shall be a push-on and thread-off design
allowing a 1/2" cover plate adjustment. Cover plate tem-
perature rating shall be 135°F (57C). A plastic protec-
tive cap shall be provided and factory installed inside the
sprinkler cup to protect the sprinkler from damage, which
could occur during construction before the cover plate
is installed. Standard cover plate finish: [White] [Custom
Color— specify]. J. Concealed pendent sprinklers shall
be Reliable Model Fl Res 30, 49 & 58 CCP, SIN R3511,
R3516 & R3513 (Bulletin 135).
Model Fl Res 44, Fl Res 58 Horizontal
Sidewall, Fl Res 58 HSWX & KRes58 HSWX
Residential Sprinkler Specifications
Sprinklers shall be [cULus Listed] low flow residential
horizontal sidewall sprinklers engineered to provide a
minimum design density of 0.05 gpm/ft2 over the listed
coverage area. Listed flows as specified by the manu-
facturer's technical data sheets are to be used. Residen-
tial sprinklers shall be installed in conformance with the
manufacturer's installation guidelines and the applicable
installation standard. Sprinkler frame and deflector shall
be of bronze frame construction having a ½" NPT thread.
Water seal assembly shall consist of a Teflon* coated Bel-
leville spring washer with top-loaded extruded or cold
head cup with 3 mm glass bulb containing no plastic
parts, and having a temperature rating of [155°F (680C)]
[175°F (79°C)]. The solder element (Link) version, the
water seal consist of a cap with a bellville spring washer
and a temperature rating of 165°F (74°C). The recessed
assembly forthe HSWX (Bulb & Link) should be a steel
two pieces escutcheon with 1/2" adjustment (Model F2)
standard finish should be Bright Chrome and white paint-
ed. The El Res 58 HSW is also available with low lead
frame. Fl Res 58 HSW and HSWX sprinklers shall have a
nominal K Factor of 5.8 and Fl Res 44 a nominal K factor
of 4.4. Standard finish: [Bronze] [Chrome-plated] [White
Polyester] [Special finish— specify]. Residential horizontal
sidewall sprinklers shall be Reliable Model Fl Res 44, Fl
Res 58, Fl Res 58 HSWX & Model KRes58 HSWX, SIN
R3531, RA3533 & RA3593 (Bulletin 135).
Model Fl Res 44 Recessed
Horizontal Sidewall Sprinkler
Use description for the Model El Res 44 horizontal side-
wall sprinkler with the following modifications: Replace
"horizontal sidewall sprinkler" with "recessed horizontal
sprinkler." Add: Recessed escutcheon assembly shall be
a steel, two-piece escutcheon with ½" adjustment (Model
E2). Standard finish shall be [brass][bright chrome] [white
painted] [Special finish— specify]. Residential recessed
horizontal sidewall sprinklers shall be Reliable Model El
Res 44/F2, SIN R3531 (Bulletin 135).
Model Fl Res 76 Pendent
Sprinklers shall be [cULus Listed] low flow residential
pendent sprinklers engineered to provide a minimum
design density of 0.05 gpm/ft2 over the listed coverage
area. Listed flows as specified by the manufacturer's
technical data sheets are to be used. Residential sprin-
klers shall be installed in conformance with the manufac-
turer's installation guidelines and the applicable installa-
tion standard. Sprinkler frame and deflector shall be of
bronze frame construction having a 3/4" NPT thread. Wa-
ter seal assembly shall consist of a Teflon* coated Bel-
leville spring washer with machined or cold head cup with
3 mm glass bulb containing no plastic parts, and having
a temperature rating of [155°F (68°C)] [175°F (79°C)].
Sprinklers shall have a nominal K-factor of 7.6. Standard
finish: [Bronze] [Chrome-plated] [White Polyester] [Spe-
cial finish— specify]. Residential pendent sprinklers shall
be Reliable Model El Res 76, SIN R7618 (Bulletin 135).
*DuPont Registered Trademark
Model Fl Res 76 Recessed Pendent/Fl,
Model Fl Res 76 Recessed Pendent/F2,
Model Fl Res 76 Recessed Pendent/FP
Sprinklers shall be [cULus Listed] low flow residential
recessed pendent sprinklers engineered to provide a
minimum design density of 0.05 gpm/ft2 over the listed
coverage area. Listed flows as specified by the manu-
facturers technical data sheets are to be used. Residen-
tial sprinklers shall be installed in conformance with the
manufacturer's installation guidelines and the applicable
installation standard. Sprinkler frame and deflector shall
be of bronze frame construction having a 3/4" NPT thread.
Water seal assembly shall consist of a Teflon* coated Bel-
leville spring washer with machined or cold head cup with
3 mm glass bulb containing no plastic parts, and hav-
ing a temperature rating of [155°F (680C)] [175°F (790C)].
Sprinklers shall have a nominal K-factor of 7.6. Standard
finish: [Bronze] [Chrome-plated] [White Polyester] [Spe-
cial finish— specify]. Recessed escutcheon assembly
shall be a steel, two-piece escutcheon [with 1/2" adjust-
ment (Model F2)] [with 3/4" adjustment (Model Fl)] [of
push-on and thread off design with ½" adjustment (Mod-
el FP)]. Standard finish shall be [brass][bright chrome]
[white painted]. Residential recessed pendent sprinklers
shall be Reliable [Model Fl Res 76 Recessed Pendent/
Fl] [Model Fl Res 76 Recessed Pendent/F2] [Model Fl
Res 76 Recessed Pendent/FP] SIN R7618 (Bulletin 135).
Model Fl Res 76 CCP Pendent (Concealed)
Sprinklers shall be [cULus Listed] low flow residential
concealed sprinklers engineered to provide a minimum
design density of 0.05 gpm/ft2 over the listed coverage
area. Listed flows as specified by the manufacturer's
technical data sheets are to be used. Residential sprin-
klers shall be installed in conformance with the manufac-
turer's installation guidelines and the applicable installa-
tion standard. Sprinkler frame and deflector shall be of
bronze frame construction having a 3/4" NPT thread. Wa-
ter seal assembly shall consist of a Teflon* coated Bel-
leville spring washer with machined or cold head cup with
3 mm glass bulb containing no plastic parts, and having
a temperature rating of 155°F (68°C). Cover plate assem-
bly shall consist of a brass cover plate and copper alloy
retainer flange. Method of attaching the cover plate to the
sprinkler cup shall be a push-on and thread-off design
allowing a 1/2" cover plate adjustment. Cover plate tem-
perature rating shall be 135°F (57C). A plastic protec-
tive cap shall be provided and factory installed inside the
sprinkler cup to protect the sprinkler from damage, which
could occur during construction before the cover plate
is installed. Standard cover plate finish: [White] [Custom
Color— specify]. ]. Concealed pendent sprinklers shall be
Reliable Model Fl Res 76 CCP, SIN R7618 (Bulletin 135).
Finishes (1)
Standard Finishes
Sprinkler F1 F2 FP CoverPlates Escutcheons
Bronze Brass White Painted
Chrome Plated Bright Chrome Plated Chrome
White and Black White Painted
Polyester(2) Coated
Special Application Finishes
Sprinkler Fl, F2, FP
Escutcheons
Electroless Nickel PTFE(Teflon®))2) Electroless Nickel PTFE (Teflona)
Bright Brass Bright Brass
Black Plated Black Plated
Black Paint Black Paint
Off White Off White
Chrome Dull Chrome Dull
Other finishes and colors are available on special order.
Consult factory for details.
(2) cULus listed Corrosion Resistant
Note: Paint or any other coating applied over the factory finish will void
all approvals and warranties.
Ordering Information
Specify:
Sprinkler Model
Sprinkler Type
Temperature Rating
Sprinkler Finish
Escutcheon Finish
Cover Plate Finish
*DuPont Registered Trademark
The equipment presented in this bulletin is to be installed in accordance with the latest published Standards of the National Fire Protection Association, Factory
Mutual Research Corporation, or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable.
Products manufactured and distributed by Reliable have been protecting life and property for over 90 years, and are installed and serviced by the most highly
qualified and reputable sprinkler contractors located throughout the United States, Canada and foreign countries.
Manufactured by
Reliable Automatic Sprinkler Co., Inc. Recycled ® (800) 431-1588 Sales Offices W Paper
(800) 848-6051 Sales Fax Reliable (914) 829-2042 Corporate Offices Revision lines indicate updated or new data.
www.reliablesprinkler.com Internet Address EG. Printed in U.S.A. 06/15 P/N 9999970235
Bulletin 014 Rev. P
liable Model Fl FR Series
Quick Response
Glass Bulb Sprinklers
C
0
CD
Model Fl FR56 Sprinkler Types
Standard Spray Upright
Standard Spray Pendent
Conventional Upright/Pendent
Vertical Sidewall
Horizontal Sidewall
Model Fl FR56 Recessed Sprinkler Types
Standard Spray Pendent
Horizontal Sidewall
Model F1 FR56 Concealed Sprinkler Types
Standard Spray Pendent
Model Fl FR42, Fl FRXLH & Fl FR28 Sprinkler
Types
Standard Spray Upright
Standard Spray Pendent
Model F1FR40 Sprinkler Types
Standard Spray Pendent
Model Fl FR42, Fl FR40, Fl FRXLH & Fl FR28
Recessed Sprinkler Types
Standard Spray Pendent
Model Fl FR56LL & Fl FR42LL Low Lead Sprinkler
Types
Standard Spray Pendent with less than 0,25% Lead
Content
Listing & Approvals
The following organizations provide Listings or Approvals
for various Model F1 FIR series sprinklers. See the Design
and Installation table in this Bulletin for information on
specific listings and approvals applicable to each sprin-
kler.
Underwriters Laboratories Inc. and Certified for
Canada (cULus) in accordance with ANSl/UL199.
FM Approvals (FM)
Loss Prevention Certification Board (LPCB)
VdS SchadenverhUtung GmbH (VdS)
Underwriters Laboratories Inc. and Underwriters
Laboratories of Canada Certified for Health Effects
to NSF/ANSI Standard 61 Annex G (ULH)
EC Certificate: 0786-CPD-40239 (RA1414), 0786-
CPD-4025 1 (RA1 425), 0786-CPD-40252 (RA1 475)
(EC)
UL Listing Category
Sprinklers, Automatic & Open (VNIV)
Quick Response Sprinkler
4\4
Upright Pendent Conventional
T:.
Vertical Sidewall Horizontal Sidewall Recessed
PendenVF1/F2
Recessed Concealed Recessed
Horizontal Sidewall Pendent Pendent/FP
XLH Upright XLH Pendent XLH Recessed
Pendent F1/172
Product Description
Reliable Model Fl FR series sprinklers
are quick-response automatic sprin-
klers with a glass bulb thermal element.
Model F1FR series sprinklers are Stan-
dard Spray sprinklers, with the excep-
tion of the Model Fl FR56 Conventional XLH Recessed
sprinkler which is an Old-style/Conven- Pendent FP
tional sprinkler.
The Model Fl FR Series automatic sprinklers utilize a 3.0
mm frangible glass bulb. These sprinklers have demonstrat-
ed response times in laboratory tests which are five to ten
times faster than standard response sprinklers. This quick
response enables the Model Fl FR Series sprinklers to apply
water to a fire faster than standard-response sprinklers of the
same temperature rating.
The glass bulb consists of an accurately controlled amount
of special fluid hermetically sealed inside a precisely man-
ufactured glass capsule. This glass bulb is specially con-
structed to provide fast thermal response.
Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York 10523
At normal temperatures, the glass bulb contains the fluid
in both the liquid and vapor phases. The vapor phase can
be seen as a small bubble. As heat is applied, the liquid
expands, forcing the bubble smaller and smaller as the liq-
uid pressure increases. Continued heating forces the liquid
to push out against the bulb, causing the glass to shatter,
opening the waterway and allowing the deflector to distrib-
ute the discharging water.
Model Fl FR Series sprinklers provide a wide range of op-
tions where quick-response, glass bulb sprinklers are used:
Pendent, recessed pendent, upright, horizontal
sidewall, and vertical sidewall deflectors
K-factors of 2.8 (40 metric), 4.0 (57 metric), 4.2 (60
metric), and 5.6 (80 metric)
Flush, recessed, and concealed installations
See the Design and Installation Information table in this
Bulletin for information on the approvals and availability of
specific Model Fl FR series sprinkler configurations.
Model Fl FR Recessed Pendent and Recessed Horizon-
tal Sidewall sprinklers are required to be used with Reliable
Model Fl, F2, or FP recessed escutcheons. See the Re-
cessed Escutcheon Data table in this Bulletin for listing and
approval information with each specific Model Fl FR series
sprinkler. Model Fl and F2 recessed escutcheons, shown in
Fig. 1 and 3, are a friction fit assembly allowing for 3/4-inch
(19mm) and 1/2-inch (12.7mm) of adjustment, respectively.
Model FP recessed escutcheons, shown in Fig. 2, provide a
1/2-inch (12.7mm) threaded adjustment.
Model Fl FR56 Concealed Pendent and Model Fl FR56LL
Concealed Pendent sprinklers are required to be used with
Model CCP cover plates. A standard profile Model CCP cov-
er plate is available that provides up to 1/2-inch (12.7mm) of
cover plate adjustment. In addition, a low profile Model CCP
cover plate is also available that provides up to 5/16-inch
(8.0mm) of cover plate adjustment. See the Design and In-
stallation Information and Listed and Approved Temperature
Ratings tables in this Bulletin for further information on ap-
proved cover plate options.
Application
Model F1FR Series sprinklers are intended for use in
accordance with NFPA 13, FM Property Loss Prevention
Data Sheets, and the requirements of the Authority Hav-
ing Jurisdiction. Care must be exercised that the k-factor,
temperature rating, deflector style, and sprinkler type are
in accordance with the requirements of the applicable
design and installation standards. In addition, Model
Fl FR Series sprinklers must be used in accordance with
their listings and approvals, as well as the information
provided in this Bulletin.
Installation
Glass bulb sprinklers have orange bulb protectors or pro-
tective caps to minimize bulb damage during shipping, han-
dling and installation. Reliable sprinkler installation wrench-
es are designed to install sprinklers with bulb protectors in
place. Remove the bulb protector at the time when the sprin-
kler system is placed in service for fire protection. Removal
of the bulb protector before this time may leave the bulb vul-
nerable to damage. Remove bulb protectors by undoing the
clasp by hand. Do not use tools to remove bulb protectors.
2.
Model Fl FR Series sprinklers must be installed with the
Reliable sprinkler installation wrench identified in the Design
and Installation Information table in this Bulletin. Any other
wrench may damage the sprinkler. A leak tight sprinkler joint
can be obtained with a torque of8to 18 lb-ft (11 to 24 N-m),
Do not tighten sprinklers over the maximum recommended
installation torque. Exceeding the maximum recommended
installation torque may cause leakage or impairment of the
sprinkler.
Recessed Sprinklers
Model Fl FR Series Recessed sprinklers are to be installed
as shown in Fig. 1, Fig. 2, or Fig. 3, as applicable to the spe-
cific model being installed. The Recessed Escutcheon Data
table in the Bulletin identifies the only recessed escutcheons
that are permitted to be used with each Model Fl FR Series
Recessed sprinkler. The use of any other recessed escutch-
eon will void all approvals and negate all warranties.
Concealed Sprinklers
Model Fl FR Series Concealed Pendent sprinklers are to
be installed as shown in Fig. 4 or Fig. 5, as applicable to the
selected cover plate. Model Fl FR56 Concealed Pendent
and Model Fl FR56LL Concealed Pendent sprinklers have
a factory-installed Model CCP cup. A protective cap is in-
stalled at the factory that should remain on the sprinkler until
the sprinkler is installed and should then be reinstalled on
the sprinkler until the cover plate is installed. The concealed
sprinkler assemblies are completed by the installation of a
Model CCP push-on/thread-off cover plate assembly. The
cover plate and sprinkler cup assemblies are joined using
a cover plate skirt with flexible tabs for threaded engage-
ment. A choice of two Model CCP cover plate assemblies
provides either 1/2-inch (13mm) or 5/8-inch (8mm) of cover
adjustment. Do not install Model F1FR Series Concealed
Pendent sprinklers in ceilings which have positive pressure
in the space above.
Model Fl FR Sees Concealed Pendent sprinklers require a
2-5/8-inch (67mm) diameter hole to be cut in the ceiling. The
Model RC1 wrench is used to engage the sprinkler wrenching
surfaces and to install the sprinkler in the fitting. Remove the
protective cap to install the sprinkler, then reinstall the protective
cap until the cover plate is installed. When inserting or remov-
ing the wrench from the sprinkler/cup assembly, care should be
taken to prevent damage to the sprinkler. Do not wrench any
other part of the sprinkler/cup assembly Installation is com-
pleted by removing the protective cap from the sprinkler and
pushing the cover plate onto the cup. Anal adjustment is made
by hand turning the cover plate until the skirt flange makes full
contact with the ceiling. Cover plate removal requires turning the
cover plate in the counter clockwise direction. After installation,
inspect all sprinklers to ensure that there is a gap between the
cover plate and ceiling and that the four cup slots are open and
free from any air flow impediment to the space above.
Concealed cover plate/cup assemblies are listed only for
use with specific sprinklers. The use of any concealed cover
plate/cup assembly other than the Reliable Model COP with
Model Fl FR56 Concealed Pendant and Model Fl FRS6LL
Concealed Pendent sprinklers or the use of the Model COP
Concealed cover plate assembly on any sprinkler with
which it is not specifically listed my prevent good fire pro-
tection and will void all guarantees, warranties, listings and
approvals.
Technical Data:
Sensitivity: Quick-response
Thread Size: 1/2-inch NPT standard; ISO 7-R1/2 optional
Maximum Working Pressure: 175 psi (12 bar) - 100% Factory tested hydrostatically to 500 psi (34.5 bar)
SIN RA1425, RA1414 & RA1435 cULus listed for 250 psi (17 bar)
Design and Installation Information
Model
Nominal
K-factor
Nominal
Orifice
Diameter Deflector/
Orientation
Nominal
Sprinkler
Height Installation
Wrench SIN
Listings
and
Approvals
Approval
Notes
US Metric inches mm inches mm
F1FR28 2.8 40 3/8 10
Pendent 2.25 57 DorW2 RA1411 cULus 2
Recessed Pendent 2.25 57 GFR2 RA1411 cULus 2
Upright 2.25 57 DorW2 RA1421 cULus 1,2
F1FR40 4.0 57 3/8 10 Pendent 2.25 57 DorW2 RA1418 VdS
Recessed Pendent 2.25 57 GFR2 RA1418 VdS
F1FR42 4.2 60 7/16 10
Pendent 2.25 57 DorW2 RA1413 cULus 2
Recessed Pendent 2.25 57 GFR2 RA1413 cULus 2
Upright 2.25 57 DorW2 RA1423 cULus 1,2
F1FR42LL 4.2 60 7/16 10 Pendent 2.25 57 DorW2 RA1410 cULus, ULH
Recessed Pendent 2.25 57 GFR2 RA1410 cULus, ULH
F1FRXLH
(F1FR42
with Pintle)
4.2 60 7/16 10
Pendent 225 57 DorW2 RA1413 cULus 2
Recessed Pendent 2.25 57 GFR2 RA1413 cULus 2
Upright 2.25 57 DorW2 RA1423 cULus 1,2
F1FR56 5.6 80 1/2 15
Pendent 2.25 57 DorW2 RA1414 cULus, FM,
LPCB, VdS, EC
1,2,3,4
Recessed Pendent 2.25 57 GFR2 RA1414 cULus, FM ,
LPCB, VdS, EC
1,2,3,4
Concealed Pendent 2.25 57 RC1 RA1414 cULus,VdS,EC 5,6
Upright 2.25 57 DorW2 RA1425 cULus, FM,
LPCB,VdS,EC
123,4
"Conventional 2.25 57 (Pendent or Upright)"
DorW2 RA1475 LPCB,VdS,EC 4
F1FR56LL 5.6 80 1/2 15
Pendent 2.25 57 DorW2 RA1415 cULus, ULH 1
Recessed Pendent 2.25 57 GFR2 RA1415 cULus, ULH
Concealed Pendent 2.25 57 RC1 RA1415 cULus, ULH 6
F1FR56 5.6 80 1/2 15
Horizontal Sidewall 2.63 67 D or W2 RA1435 cULus, FM 1,2,3,7
Recessed Horizontal 2.63 67 Sidewall
GFR2 RA1435 cULus, FM 8
F1FR56 5.6 80 1/2 15 Vertical Sidewall
(Pendent or Upright) 2.25 57 DorW2 RA1485 cULus, FM,
LPCB I
1,2,3,9
cULus Listed Corrosion Resistant sprinkler when ordered with available Polyester coating.
cULus Listed Corrosion Resistant sprinkler when ordered with available Electroless Nickel PTFE plating.
3) Available with FM approved Polyester coating in black or white.
(4) Available with LPCB and VdS approved Polyester coating.
VdS and EC approvals of the F1FR56 Concealed Pendent sprinkler are for 155°F (68°c) temperature rated sprinklers only. VdS approved sprin-
klers must use Norbulb brand glass bulbs with the 1/2-inch (12,7mm) adjustment Model CCP cover plate only.
(6) Model F1FR56 Concealed Pendent and Model F1FR56LL concealed Pendent sprinklers must be used with Reliable Model CCP cover plates,
available as either standard depth with 1/2-inch (12.7mm) of adjustment or low profile with 5/16-inch (8.0 mm) of adjustment.
7) cULus Listing of the F1FR56 Horizontal Sidewall sprinkler is for Light and Ordinary Hazard occupancies only. FM Approval of the F1FR56 Hori-
zontal Sidewall sprinkler is for Light Hazard occupancies only.
cULus Listing and FM Approval of the Fl FR56 Recessed Horizontal Sidewall sprinkler is for Light Hazard occupancies only.
The F1FR56 Vertical Sidewall sprinkler is listed and approved for use only in Light Hazard occupancies. Minimum to maximum deflector to ceil-
ing distance shall be 4 inches to 12 inches (102mm to 305mm). LPCB approval of the F1FR56 Vertical Sidewall sprinkler is for installation in the
Pendent position only.
3.
Listed and Approved Temperature Ratings
Model Deflector/
Orientation
Ordinary Temp.
Classification
100°F (38°C) Max. Ambient
Temp. __________
Intermediate Temp.
Classification
150°F (65°C) Max. Ambient
Temp.
High Temp.
Classification
225°F (1070C) Max.
Ambient Temp.
135°F (57°C)
Temp. Rating
I 1550F( 80C)
I Temp. Rating
175°F (79°C)
Temp. Rating
I 200°F (93°C)
I Temp. Rating
286°F (141°C) Temp.
I Rating
Orange Bulb Red Bulb I Yellow Bulb I Green Bulb Blue Bulb -
Pendent cULus
F1FR28 Recessed Pendent cULus I --
_________ Upright cULus
F1FR40 Pendent VdS
Recessed Pendent VdS I --
Pendent cULus
F1FR42 Recessed Pendent cULus --
_________ Upright cULus
F1FR42LL Pendent -- cULus, ULH I I -- I Recessed Pendent -- I cULus, ULH I
Pendent cULus
F1FRXLH Recessed Pendent cULus I --
_________ Upright cULus
Pendent cULus, FM, LPCB, VdS, EC
Recessed Pendent cULus, FM, LPCB, VdS, EC -- I
F1FR56 Concealed Pendent* cULus I cULus,VdS,EC I cULus I --
Upright cULus, FM, LPCB, VdS, EC
"Conventional
(Pendent or Upright)" LPCB, VdS, EC
Pendent -- I cULus, ULH I --
F1FR56LL rRecessed Pendent -- I cULus, ULH --
_________ Concealed Pendent* I cULus, ULH --
Horizontal Sidewall cULus, FM
F1FR56
_________
Recessed Horizontal
Sidewall cULus, FM
I --
F1FR56 Vertical Sidewall (Pen-
dent _or_Upright) cULus, FM, LPCB
* Model Fl FR56 Concealed Pendent and Fl FR56LL Concealed Pendent sprinklers must be used with Reliable Model
CCP cover plates. For Ordinary Temperature Classification sprinklers use a 1350F (57°C) temperature rated cover
plate. For Intermediate Temperature Classification sprinklers use a 165°F (74°C) temperature rated cover plate.
Recessed Escutcheon Data
Listed and Approved Recessed Escutcheons
Model Fl Model F2 Model FP Deflector/ Model Orientation (Fig. 1 & 3) (Fig. 1 & 3) (Fig. 2) SIN
3/4-inch (19mm) 1/2-inch (12.7mm) 1/2-inch (12.7mm)
adjustment adjustment adjustment
F1FR28 Recessed Pendent cULus cULus cULus RA1411
F1FR40 Recessed Pendent VdS VdS VdS RA1418
F1FR42 Recessed Pendent cULus cULus cULus RA1413
F1FR42LL Recessed Pendent cULus, ULH cULus, ULH cULus, ULH RA1410
F1FR42XLH Recessed Pendent cULus cULus cULus RA1413
F1FR56 Recessed Pendent cULus, LPCB, VdS, cULus, FM,LPCB, cULus, VdS, EC RA 1414 EC VdS,EC
F1FR56LL Recessed Pendent cULus, ULH cULus, ULH cULus, ULH RA 1415
F1FR56 Recessed Horizontal Sidewall cULus cULus, FM cULus RA 1435
4.
TURN COLLAR
UNTIL TIGHT
AGAINST SPRINKLER
WRENCH BOSS ----\
F? ESCUTCHEON
3/4(79mm]
ADJUSTMENT
F2 ESCUTCHEON
1/2[12.7mm]
ADJUSTMENT
2 7/4' HOLE OH.
[57,2mm]
--d
_ 7 75/16" 0/A
[49.2mm]
F
\ /
(1
Ii
1 X 1/2 REDUCER
FACE OF FITTING
TO FACE OF CEILING DIMENSION
Fl ESCUTCHEON
AT MAXIMUM RECESS = 1 "[25.4mm]
AT MINIMUM RECESS = 3/8 "[9.5mm]
F2 ESCUTCHEON
AT MAXIMUM RECESS = 3/4(19mm]
77777-71 AT MINIMUM RECESS = 3/8[9.5mm]
F! ESCUTCHEON
AT MAXIMUM RECESS = 7/8(22.2mm]
[j.'mm] ESS 1-5/8 "[41.3mm] / AT MINIMUM REC =
F2 ESCUTCHEON
AT MAXIMUM RECESS = 1-1/8 "[28.6mm]
AT MINIMUM RECESS = I-5/8"[41.3mm]
2 27/32" 0/A.
[72,2mm]
Model F1FR56, F1FR56LL, F1FR42, F1FR40, F1FR42LL, F1FRXLH & F1FR28
Recessed Pendent sprinkler with Model Fl or F2 escutcheon
1" X 1/2" REDUCER
2 5/8" 0/A. [66.7mm] -
HOLE IN CEILING /
2 5/16" 0/A. [58.7mm]
CUP
CEILING FACE OF FITTING
TO FACE OF CEILING
AT MAXIMUM RECESS = 1-1/2"[38mm]
DIMENSION
AT MINIMUM RECESS
AT MAXIMUM RECESS = 9/16"[14.3mm]
? "[12.7mm] JAr
AT MINIMUM RECESS = 1 "(25.4mm]
ADJUSTMENT
3 1/4" 0/A.
[82.6mm]
Model Fl FR56, Fl FR56LL, Fl FR42, Fl FR40, Fl FR42LL, Fl FRXLH & Fl FR28
Recessed Pendent sprinkler with Model FP escutcheon
5.
FACE OF FITTING
TO FACE OF CEILING DIMENSION
F! ESCUTCHEON
AT MAXIMUM RECESS = 1 "[25.4mm]
AT MINIMUM RECESS = 3/8"[9.5mm]
F2 ESCUTCHEON
AT MAXIMUM RECESS = 3/4"[19mm]
AT MINIMUM RECESS = 3/8"[9.5mm]
2 1/4" HOLE OIA.
[5 7.2mm]
Fl ESCUTCHEON
LLJ AT AdA VIAAJIAA DCC -. l_ /P"I.4 o,,.,.,.,7
AT MINIMUM RECESS = 2— 1/16"[52.4mm]
F2 ESCUTCHEON
AT MAXIMUM RECESS = 1-5/8'14 1.3mm]
AT MINIMUM RECESS = 2-1/16 "[52.4mm]
[3.2mm]
1" X 1/2" REDUCER
II 1 15/16" DIA.jJ4
(49.2mm] '1 2 27/32" DIA.
[72.2mm]
T (1)
4"-12"
[101.6mm —304.8mm]
CEILING TO
DEFLECTOR
TURN COLLAR UNTIL --
TIGHT AGAINST SPRINKLER
WRENCH BOSS. Fl ESCUTCHEON
H [ 3/4 "[19mm] ADJUSTMENT
F2 ESCUTCHEON
1/2"[12. 7mm] ADJUSTMENT
OIJFSE
RECESSED HSW w/F1 OR F2 ESCUTCHEON
(1) FM APPROVED FOR 4" - 6" [101.6MM - 152.4MM] CEILING TO DEFLECTOR WITH F2 ONLY.
Fig.3
Model Fl FR56 Recessed Horizontal Sidewall sprinkler with Model Fl or F2 escutcheon
1" x 1/2" REDUCING
TEE OR ELBOW
TF
2 5/8" 0/A.
2 5/16 0/A - u HOLE IN CEILING
CUP
00 VU 1 1/2 MAX.
-j j4 j]fl FACE OF FITTING
/
TO FACE OF CEILING
DIMENSION
CEILING
1/2" MAX. 15/16" COVER ADJUSTMENT /
COVER PLATE /
ASSEMBLY / 3 5/16 0/A.
SPRINKLER
CONCEALED, 1/2" ADJUSTMENT 017FG01A
Fig. 4
Model Fl FR56/F1 FR56LL Concealed Pendent sprinkler with standard depth
1/2-inch (12.7mm) adjustment - Model COP cover plate
1" x 1/2" REDUCING
TEE OR ELBOW
EI
_
[ 258 0/A
2 5/16" 0/A
- j.. HOLE IN CEILING
CUP
03 V8 1 1/2k MAX.
FACE OF FITTING
CE OF CEILING
CEILINGJ
5116 " MAX. 314
COVER ADJUSTMENT
TO DIMENSION
COVER PLATE
ASSEMBLY
- 3 5/16 0/A.
SPRINKLER
CONCEALED, _5/16"ADJUSTMENT 017F502A
Fig. 5- Model Fl FR56/F1 FR56LL Concealed Pendent sprinkler with low profile
5/16-inch (8.0mm) adjustment - Model COP cover plate
Maintenance
The Model Fl FR Series sprinklers should be inspected and
the sprinkler system maintained in accordance with NFPA
25. Do not clean sprinklers with soap and water, ammonia or
any other cleaning fluids. Remove dust by using a soft brush
or gentle vacuuming. Replace any sprinkler which has been
painted (other than factory applied) or damaged in any way.
A stock of spare sprinklers should be maintained to allow
quick replacement of damaged or operated sprinklers.
Finishes (1)
StandardFinishes
Sprinkler Escutcheon I Cover plate(
Bronze Brass Chrome
ChromePlated Chrome White
Polyester Plated
Coated (4)(5)(6) WhitePainted
Special Application Finishes
Sprinkler Escutcheon Cover plate(')
Electroless Nickel
PTFE71
Electroless Nickel
PTFE Bright Brass rig
BrightBrass31 BrightBrass BlackPlating
BlackPlated BlackPlated BlackPaint
BlackPaintt21161 i BlackPaint I Off White
Off White 5 Off White I SatinChrome
ChromeDull ChromeDull I
Other finishes and colors are available on special order. Consult the
factory for details. Custom color painted sprinklers may not retain their
UL Corrosion resistance listing. Coverplate custom paint is semi-gloss,
unless specified otherwise.
cULus Listed only.
200°F (93°C) maximum.
4) cULus listed "corrosion resistance" applies to SIN Numbers RA1435
(HSW), RA1485(VSW), RA1425 (Upright), RA1414 (Pendent) and
RA1415 (Pendent) in standard black or white. Corrosion resistance in
other polyester colors is available upon request.
FM Approvals finish as "Polyester coated" applies to SIN Number
RA1414, RA1435 and RA1425 in standard black or white.
LPCB and VdS Approved finish applies only to RA1425, RA1414, RA1418
(VdS) and RA1475.
7) cULus listed Corrosion Resistant
MaterialData
Frame: DZRBrass,QMBrass,orLowLeadBrass
Deflector: CDAAlloy220,260,or 510
LoadScrew\Pintle: CDAAlloy360 or544
Cup: CDAAlloy651or693
Washer: Nickel Alloy 440 or 360, coated with PTFE
AdhesiveTape
Bulb: Glass
Ordering Information
Specify:
Sprinkler Model: [Fl FR28][F1 FR4O][F1 FR42]
[Fl FR42LL][F1 FRXLH][F1 FR56][F1 FR56LL]
Sprinkler Deflector/Orientation: [Pendent][Recessed
Pendent] [Upright] [Conventional] [Horizontal Sidewall]
[Recessed Horizontal Sidewall] [Vertical Sidewall]
Sprinkler threads: [1/2-inch NPT][ISO 7-R1/2]
Sprinkler Temperature Rating: [135°F (570C)][155°F
(680C)] [175°F (790C)] [200°F (930C)] [286°F (141 00)]
Sprinkler Finish
Escutcheon Model: [F1][F2][FP]
Escutcheon Finish (where applicable)
Cover plate Model: [standard profile COP 1/2-inch
(12.7mm) adjustment][low profile COP 5/16-inch
(8.0mm) adjustment]
Cover plate Temperature Rating: [135°F (57°C) for use
with Ordinary Temperature sprinklers][165°F (74°C)
for use with Intermediate Temperature sprinklers]
Cover plate Finish
Note: When Model Fl FR Series Recessed sprinklers are ordered, the
sprinklers and escutcheons are packaged separately.
7.
Reliable ... For Complete Protection
Reliable offers a wide selection of sprinkler components. Following are some of the many
precision-made Reliable products that guard life and property from fire around the clock.
Automatic sprinklers
Flush automatic sprinklers
Recessed automatic sprinklers
Concealed automatic sprinklers
Adjustable automatic sprinklers
Dry automatic sprinklers
Intermediate level sprinklers
Open sprinklers
Spray nozzles
Alarm valves
Retarding chambers
Dry pipe valves
Accelerators for dry pipe valves
Mechanical sprinkler alarms
Electrical sprinkler alarm switches
Water flow detectors
Deluge valves
Detector check valves
Check valves
Electrical system
Sprinkler emergency cabinets
Sprinkler wrenches
Sprinkler escutcheons and guards
Inspectors test connections
Sight drains
Ball drips and drum drips
Control valve seals
Air maintenance devices
Air compressors
Pressure gauges
Identification signs
Fire department connection
The equipment presented in this bulletin is to be installed in accordance with the latest published Standards of the National Fire Protection Association, Factory
Mutual Research Corporation, or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable.
Products manufactured and distributed by Reliable have been protecting life and property for almost 100 years.
Manufactured by
Reliable Automatic Sprinkler Co., Inc. Ack Recycled
® (800)431-1588 Sales Offices Paper
Reliable (800) 848-6051 Sales Fax Revision lines indicate updated or new data.
(914) 829-2042 Corporate Offices
www.reliablesprinkler.com Internet Address EG. Printed in U.S.A. 03/17 PIN 9999970300