HomeMy WebLinkAbout3111 AFTON WAY; ; FPR2018-0003; PermitPER]tT REPORT
-
Print Date: 08/30/2022 Permit No: FPR2018-0003
Job Address: 3111 AFTON WAY, CARLSBAD, CA 92008-2093 Status: Closed - Finaled
Permit Type: FIRE-Construction Residential Work Class: Single Family Fire Sprinkl
Parcel #: 1675314500 - Track #: Applied: 01/08/2018
Valuation: $610,327.18 Lot #: Issued: 06/27/2018
Occupancy Group: Project #: DEV14053 Finaled Close Out: 03/09/2021
#of Dwelling Units: Plan #:
Bedrooms: Construction Type: Final Inspection:
Bathrooms: Orig. Plan Check #: INSPECTOR: Fieri, Dominic
Plan Check #:
Project Title: AFTON WAY
Description: NEW SFD (PLAN 2A) -SPRINKLER
Applicant: FPContractor:
PREMIER FIRE PROTECTION PETRICORP
STEVE PETRI P0 BOX 2027
P0 BOX 2027 LAKESIDE, CA 92040-0921
LAKESIDE, CA 92040 (619) 871-9795
(619) 871-9795
FEE AMOUNT
FIRE NFPA 13D Single Family System (Insp/Bldg) $121.00
FIRE NFPA 13D Single Family System (Plan Review) $239.00
Total Fees: $360.00 Total Payments To Date: $360.00 Balance Due: $0.00
Fire Department Page 1 of 1
1635 Faraday Avenue, Carlsbad CA 92008-7314 1 760-602-4665 1 760-602-8561 f I www.carlsbadca.gov
Steve petri
From: Christopher Glassen <Christopher.Glassen@carlsbadca.gov>
Sent: Tuesday, December 05, 2017 8:04 AM
To: steve petri
Subject: RE: water pressure request
I'm getting 89psi at a 240' elevation. The pressure zone is 446 for that area. Thanks,
CCity of
Carlsbad
Christopher Glassen
Engineering Technician
City of Carlsbad
1635 Faraday Avenue
Carlsbad, CA 92008
www.carlsbadca.gov
760-602-2784 1 760-602-1052 fax I christopher.glassen@carlsbadca.gov
NEW ENERGOV PERMITTING SYSTEM IS HERE!
Appointment-Based Submittals and Resubmittals beginning October 17, 2016
Appointments can be made by phone: 760-602-2723 or E-mail: devappt@carlsbadca.gov
From: steve petri [maifto: premierfire@cox.net}
Sent: Monday, December 04, 2017 4:35 PM
To: Land Development Engineering <LandDev@CarlsbadCA.gov>
Subject: water pressure request
Hi
Can you send water pressure for 3104 Afton way, Carlsbad ca 92008, apn:167-531-4700?
Thanks
Jinlan Cao
Premier Fire Protection
619-390-5047
Virus-free. www.avast.com
1
Page 1 HYDRONICS: RESIDENTIAL FIRE SPRINKLER HYDRAULICS 5.8 - SUBMITTAL
ENGINEERS : PREMIER FIRE PROTECTION. (61.9)-390-5047.
ADDRESS : 12651 Ridgetori Drive, Lakeside CA 92040.
JOB : AFTON WAY LOT 3 TWO HEAD CALC 16 X 16
DATE: 12-10-2017 FILE: C:\RESDEN58\AFTON3.RES
I SPRINKLER MANUF : VIKING
MODEL : VK486
I DENSITY : 0.05 Gpm/Sq Ft FIXED PRESS : 6.0 Psi
I AREA / SPR : 256 Sq Ft DESIGN AREA : 512 Sq Ft
I SPRINKLER Q : 13.0 Gpm
I NODES : 10 PIPES : 9
SOURCE I STATIC : 89 Psi RESIDUAL : 88 Psi FLOW : 31 Gpm
NODE ELEVATION K-FACTOR PRESSURE DISCHARGE
NO. Feet Psi Gpm -----------------------------------------------------------
1 10.0 4.00 10.5 13.0
2 10.0 4.00 10.8 13.1
3 10.0 11.1
4 10.0 16.8
T 10.0 23.1
B 0.0 29.6 DOME 5.0
A 0.0 34.6
Al 0.0 41.8
M 0.0 47.8
S 0.0 SOURCE 50.2 31.1
SPRINKLERS FLOWING
AREA PER SPRINKLER
TOTAL DESIGN AREA
MIN SPRINKLER FLOW
REQUIRED DENSITY
COMPUTED DENSITY
TOTAL SPRINKLER FLOW
TOTAL DOMESTIC FLOW
TOTAL WATER REQUIRED
TOTAL SPRINKLER PRESS
FIXED PRESS LOSS
SUPPLY PRESS AVAILABLE
DEMAND PRESS REQUIRED
PRESSURE CUSHION
MAXIMUM VELOCITY
2
256 Sq Ft
512 Sq Ft
13 Gpm
0.051 Gpm/Sq Ft
0.051 Gpm/Sq Ft
26.1 Gpm
5.0 Gpm
31.1 Gpm
44.2 Psi
6.0 Psi
Copyright (2012)
88.0 Psi by
50..2 Psi Hydronics Engineering
37.8 Psi 34119 Fremont Bi, Suite 609
Fremont, CA, 94555
12.8 F/S (800) 845-9819
HYDRONICS: RESIDENTIAL FIRE SPRINKLER HYDRAULICS 5.8 - SUBMITTAL.
ENGINEERS : PREMIER FIRE PROTECTION. (619)-390-5047.
ADDRESS : 12651 Ridgeton Drive, Lakeside CA 92040.
LICENSE : 939040
DESIGNER : STEVE PETRI
DATE : 12-10-2017
FILE : C:\RESDEN58\AFTON3.RES
JOB NAME : AFTON WAY LOT 3 TWO HEAD CALC 16 X 16
LOCATION : 3111 AFTON WAY
DESIGN DATA.
DESIGN CRITERION: 13D
MIN SPR FLOW : 13 Gpm
AREA PER SPRINKLER : 256 Sq Ft
TOTAL CALCULATED AREA : 512 Sq Ft
TOTAL SPRINKLERS CALCULATED : 2
FLOW DATA.
TOTAL SPRINKLER FLOW : 26.1 Gpm
DOMESTIC DEMAND : 5.0 Gpm
TOTAL WATER REQUIRED : 31.1 Gpm
BASE OF RISER NODE : B
FLOW : 31.1 Gpm
PRESS : 29.6 Psi
AUTHORITY HAVING JURISDICTION : CARLSBAD FIRE
PHONE :
HYDRONICS: RESIDENTIAL FIRE SPRINKLER HYDRAULICS 5.8 - SUBMITTAL. Page 2
ENGINEERS : PREMIER FIRE PROTECTION. (619)-390-5047.
ADDRESS : 12651 Ridgeton Drive, Lakeside CA 92040.
JOB : AFTON WAY LOT 3 TWO HEAD CALC 16 X 16
DATE: 12-10-2017 FILE: C:\RESDEN58\AFTON3.RES
PIPE BEG FLOW K-FACTOR LENGTH C-FACTOR PRESSURE
NO. Gpm FITTING TYPE FTG FRI-LOSS (Psi)
END DIAMETER TOTAL (Psi/Ft)
1 q= 13.0 K=
-------------------------------------------------------------------------------
4.00 L= 13.0 Pt 10.5 Pt 10.5
1 Q= 12.9 F= BR F= 6.0 C= 150 Pe 0.0 Pv -0.1
Vel= 4.4 D= 1.101 TL= 19.0 0.0304 Pf 0.6 Pn 10.4
3 Pt 11.1
2 q= 13.1 K= 4.00
--------------------------------------------------------------------------
L= 7.0 Pt 10.8 Pt 10.8
2 Q= 13.1 F= B F= 5.0 C=150 Pe 0.0 Pv -0.1
Vel= 4.4 D= 1.101 TL= 12.0 0.0310 Pf 0.4 Pn 10.6
3 - Pt 11.1
3 q= 0.0 K= 0.00 L= 38.0 Pt 11.1 Pt 11.1
3 Q= 26.0 F= B9R F= 14.0 C= 150 Pe 0.0 Pv -0.5
Vel= 8.8 D= 1.101 TL= 52.0 0.1107 Pf 5.8 Pn 10.6
4 Pt 16.8
4 q= 0.0 K= 0.00
--------------------------------------------------------------------------
L= 37.0 Pt 16.8 Pt 16.8
4 Q= 26.0 F= LLEEB3RF= 20.0 C= 150 Pe 0.0 Pv -0.5
Vel= 8.8 D= 1.101 TL= 57.0 0.1107 Pf 6.3 Pn 16.3
T Pt 23.1
T q= 0.0 K= 0.00
--------------------------------------------------------------------------
L= 10.0 Pt 23.1 Pt 23.1
5 Q= 26.0 F= SCRR F= 10.0 C= 150 Pe 4.3 Pv -0.5
Vel= 8.8 D= 1.101 TL= 20.0 0.1107 Pf 2.2 Pn 22.6
B Pt 29.6
B q= 5.0 DOME
--------------------------------------------------------------------------
L= 5.0 Pt 29.6 Pt 29.6
6 Q= 31.0 F=LLL F= 15.0 C150 Pe 0.0 Pv -1.1
Vel= 12.8 D= 0.995 TL= 20.0 0.2510 Pf 5.0 Pn 28.5
A Pt 34.6
A q= 0.0 K= 0.00
--------------------------------------------------------------------------
L= 270.0 Pt 34.6 Pt 34.6
7 Q= 31.0 F= LLEECC F= 12.0 C= 150 Pe 0.0 Pv -0.2
Vel= 5.0 D= 1.590 TL= 282.0 0.0256 Pf 7.2 Pn 34.4
Al Pt 41.8
Al Q= 31.0
--------------------------------------------------------------------------
Pt 41.8
MET FIXED PRESSURE LOSS Valve 6.0
M Pt 47.8
M q 0.0 K= 0.00
--------------------------------------------------------------------------
L= 10.0 Pt 47.8 Pt 47.8
8 Q= 31.0 F= G F= 0.0 C= 150 Pe 0.0 Pv -1.1
Vel= 12.8 D= 0.995 TL= 10.0 0.2510 Pf 2.5 Pn 46.7
S -------------------------------------------------------------------------- Pt 50.3
Q= 31.1 <<<
--------------------------------------------------------------------------
-------------------------------------------------------------------------- SOURCE >>> Pt 50.2
E=45-Elb L=90-Elb B=TeeBch R=TeeRun C=CouPlg S=SwgChk G=GatVlv
HYDRONICS: RESIDENTIAL FIRE SPRINKLER HYDRAULICS 5.8 - SUBMITTAL.
ENGINEERS : PREMIER FIRE PROTECTION. (619)-390-5047.
ADDRESS : 12651 Ridgeton Drive, Lakeside CA 92040.
JOB : AFTON WAY LOT 3 TWO HEAD CALC 16 X 16
FILE : C:\RESDEN58\AFTON3.RES
DATE : 12-10-2017
PSI FIRE SPRINKLER HYDRAULIC GRAPH
100
90
80
70
60
50
40
30
20
10
0
100 150 200 250 300
0- ------0 Water Supply
Static : 89 Psi
Resid : 88 Psi
Flow : 31 Gpm
0 Water Demand
Avi Press : 88.0 Psi @ 31 Gpm
Req Press : 50.2 Psi @ 31 Gpm
Press Cush: 37.8 Psi
350 400 450 500
FLOW - GPM
Copyright: Hydronics Engineering, 2012.
34119 Fremont Bl, Suite 609
Fremont, CA 94555.
(800) 845-9819.
Page 1 of 5
FREEDOM® RESIDENTIAL \ill(It'IG CONCEALED PENDENT
SPRINKLER VK494 (K4.9)
The Viking Corporation, 210 N Industrial Park Drive, Hastings Ml 49058
Telephone: 269-945-9501 Technical Services: 877-324-5464 Fax: 269-818-1680 Email: techsvcsvikingcorp.com
Visit the Viking website for the latest edition of this technical data page.
DESCRIPTION
Viking Freedom® Residential Concealed Pendent Sprinkler VK494 is a small
thermosensitive, glass-bulb residential sprinkler designed for installation on concealed
pipe systems where the appearance of a smooth ceiling is desired. The orifice design,
with a K-Factor of 4.9 (70.6 metric*), allows the sprinkler's efficient use of available
water supplies for the hydraulically designed fire-protection system. The fast
response glass bulb operating element and special deflector characteristics meet
the challenges of residential sprinkler standards.
The sprinkler is pre-assembled with a threaded adapter for installation with a
low-profile small-diameter cover assembly installed flush to the ceiling. The two-
piece design allows installation and testing of the sprinkler prior to installation of
the cover plate. The "push-on", "thread-off' design of the concealed cover plate
assembly allows easy installation of the cover plate after the system has been
tested and the ceiling finish has been applied, while also providing up to %" (13
mm) of vertical adjustment. The cover assembly can be removed and reinstalled,
allowing temporary removal of ceiling panels without taking the sprinkler system out
of service or removing the sprinkler. The Electroless Nickel PTFE (ENT) coating
has been investigated for installation in corrosive atmospheres and is C-UL-US-EU
Listed as corrosion resistant as indicated in the Approval Charts. The ENT finish is
only available for the sprinkler assembly, the cover plate is not plated.
2. LISTINGS AND APPROVALS
UL Listed (C-UL-US-EU): Category VKKW
j Refer to the Approval Charts and Design Criteria on for C-UL-US-EU Listing
requirements that must be followed.
TECHNICAL DATA
Specifications:
Minimum Operating Pressure: Refer to the Approval Chart..
Maximum Working Pressure: 175 psi (12 bar). Factory tested hydrostatically to 500
psi (34.5 bar).
Thread size: 1/2" (15 mm) NPT
Nominal K-Factor: 4.9 U.S. (70.6 metric*)
Glass-bulb fluid temperature rated to -65 °F (-55 °C)
* Metric K-factor measurement shown is in Bar. When pressure is measured in kPa, divide the metric
K-factor shown by 10.0.
Material Standards:
Sprinkler Body: Brass UNS-C84400 or QM Brass
Deflector: Phosphor Bronze UNS-051000
Deflector Pins: Stainless Steel UNS-S30200
Button: Brass UNS-C36000
Pip Cap and Insert Assembly: Copper UNS-C11000 and SS UNS-S30400
Compression Screw: 18-8 Stainless Steel
Yoke: UNS-543000 Stainless Steel
Belleville Spring Sealing Assembly: Nickel Alloy, coated on both sides with PTFE Tape
Cover Adapter: Cold Rolled Steel UNS-G10080, Finish: Clear Chromate over Zinc Plating
Shipping Cap: Polyethylene
Cover Plate Materials:
Cover Plate Assembly: Copper UNS-C11000 and Brass UNS-C26800
Spring: Beryllium Nickel
Solder: Eutectic
Ordering Information: (Also refer to the'-current Viking price list.)
Viking Freedom® Residential Concealed Pendent Sprinkler VK494 and Cover Plate Assembly must be ordered separately:
Sprinkler: Order Sprinkler VK494 by first adding the appropriate suffix for the sprinkler finish and then the appropriate suffix for the
temperature rating to the sprinkler base part number.
Finish Suffix: Brass = A and ENT = JN
Temperature Suffix: 155 °F (68 °C) = B, 175 °F (79 °C) = D, 200 °F (93 °C) = E
For example, sprinkler VK494 with a Brass finish and a 200 °F (93 °C) temperature rating = Part No. 20759AE.
Cover Plate Assembly: Base Part No. 13504 (2-3/4" diameter), Base Part No. 13642 (3-5/16" diameter), or Base Part No. 15394
(square cover plate, 3-5/16" diameter)
Form No. F_012116 16.06.27 Rev 16.1 (New product, new page)
Page 2 of 5
FREEDOM® RESIDENTIAL
II[I1iUIFIfA CONCEALED PENDENT KjI \rj IPttrr1G®
SPRINKLER VK494 (K4.9)
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcsvikingcorp.com
Visit the Viking website for the latest edition of this technical data page.
Specify finish and temperature rating of the cover plate assembly by adding the appropriate suffixes for the finish and the cover
temperature rating to the base part number:
Finish Suffix: Polished Chrome = F, Brushed Chrome = F-/B, Bright Brass = B, Antique Brass = B-/A, Brushed Brass = B-/B, Brushed
Copper = E-/B, Painted White = M-/W, Painted Ivory = M-/I, Painted Black = M-/B
Temperature Suffix: 135 °F/57 "C =A
For example, cover 13504 with a Polished Chrome finish and a 135 °F/57 °C temperature rating = 13504FA.
Available Finishes And Temperature Ratings: Refer to Table 1
Accessories: (Also refer to the "Sprinkler Accessories' section of the Viking data book.)
Sprinkler Wrenches**:
Heavy Duty Part No. 14047W1B** (available since 2006), or
Head Cabinet Wrench Part No. 14031*** (available since 2006)
Optional Concealed Cover Plate Installer Tool Part No. 14412 (available since 2007)
Optional Large Concealed Cover Plate Installer Tool Part No. 14867 (available since 2007)
**Requires a /2" ratchet (not available from Viking). ***Also optional for removal of the protective cap. Ideal for sprinkler cabinets.
Sprinkler Cabinet: Part No. 01731A (available since 1971)
INSTALLATION
Refer to appropriate NFPA Installation Standards.
OPERATION
During fire conditions, when the temperature around the sprinkler approaches its operating temperature, the cover plate detaches,
releasing the deflector. Continued heating of the exposed sprinkler causes the heat-sensitive liquid in the glass bulb to expand,
causing the glass to shatter, releasing the yoke and pip cap and sealing spring assembly. . Water flowing through the sprinkler
orifice strikes the deflector, forming a uniform spray pattern over a specific area of coverage determined by the water supply pres-
sure at the sprinkler to extinguish or control the fire.
INSPECTIONS, TESTS AND MAINTENANCE
Refer to NFPA 25 for Inspection, Testing and Maintenance requirements.
AVAILABILITY
Viking Sprinkler Model VK494 is available through a network of domestic and international distributors. See The Viking Corporation
web site for the closest distributor or contact The Viking Corporation.
GUARANTEE
For details of warranty, refer to Viking's current list price schedule or contact Viking directly.
f:1I 1: AVAILABLE SPRINKLER TEMPERATUREJ RATINGS lI
Sprinkler Maximum Temperature Rating SquaSprre Cover Large
T Iflmr Nominal Ambient of the Cover Plate Cover Plate Cover Plate 0 F Bulb Color
rmPra tire
assi ica iOfl Temperature Ceiling Assembly Base Part Base Part Base Part
Rating' Temperature' (Re re Number4 Number'Number4
Ordinary 155 "F (68 "C) 100 "F (38 "C) 135 "F (57 "C) 13504 13642 15394 Red
Intermediate 175 "F (79 "C) 150 "F (65 °C) 135 "F (57 "C) 13504 13642 15394 Yellow
Intermediate 200 "F (93 °C) 150 "F (65 "C) 135 °F (57 "C) 13504 13642 15394 Green
Sprinkler Finishes: Brass and ENT
Cover Plate Finishes: Polished Chrome, Brushed Chrome, Bright Brass, Antique Brass, Brushed Brass, Brushed Copper, Painted
White, Painted Ivory, or Painted Black
Corrosion Resistant Coatings5: ENT
Footnotes
1 The sprinkler temperature rating is stamped on the deflector.
2 Based on NFPA-13, NFPA 13R, and NFPA 13D. Other limits may apply, depending on fire loading, sprinkler location, and other requirements of the Authority Having
Jurisdiction. Refer to specific installation standards.
Maximum ambient temperature for cover assembly is 100 ¶ (38 "C).
Part number shown is the base part number. For complete part number, refer to current Viking price list schedule.
The corrosion resistant coatings have passed the standard corrosion test required by the approving agencies indicated in the Approval Charts. These tests cannot and
do not represent all possible corrosive environments. Prior to installation, verify through the end-user that the coatings are compatible with or suitable for the proposed
environment. For automatic sprinklers, the ENT coating is applied to all exposed exterior surfaces, including the waterway. For ENT coated sprinklers, the Belleville spring
is exposed.
Form No. F_012116 16.06.27 Rev 16.1
Page 3of5
FREEDOM® RESIDENTIAL
l:II[.qu.yM CONCEALED PENDENT
SPRINKLER VK494 (K4.9)
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcsvikingcorp.com
Visit the Viking website for the latest edition of this technical data page.
Approval Chart
Viking VK494, 49 K-Factor Residential Concealed Pendent Sprinkler
For systems designed to NFPA 13D or NFPA 13R For systems designed to NFPA 13 refer to the design criteria For Ceiling types refer to
current editions of NFPA 13 13R or 13D
Sprinkler Base NPT Thread Size Nominal K-Factor Maximum Water Wor-
Part Number SIN king Pressure. Inches mm U.S. metric 2
20759 VK494 1/2 15 4.9 70.6 175 psi (l2bar)
Max. Coverage Flow Pressure Listings and Minimum
Area 6 GPM
(LPM) PSI (bar) Deflector to Installation Approvals35 Spacing WXL Ceiling Type
155°F (68 °C), 175°F (79 °C), 200°F (93 °C) Ft. X Ft.
(m)
(m X m) Temperature Rated Sprinklers CNZYUS
EU
12X12 13 7.0
(3.7X3.7) (49.2) (0.48)
14X14 13 7.0
(4.3X4.3) (49.2) (0.48)
Refer to Figure 2
Concealed with
Cover Plate See Footnotes 7,10, & 11 8 16X 16 13 7.0
(4.9 X 4.9) (49.2) (0.48) Assembly.
See Footnote 9.
(2.4)
18X 18 17 12.0
(5.5X5.5) (64.4) (0.83)
20X20 20 16.7
(6:1X6.1) (75.7) (1.15)
Footnotes
Part number shown is the base part number. For complete part number, refer to current Viking price schedule.
2 Metric K-factor measurement shown is when pressure is measured in Bar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0.
This chart shows the listings and approvals available at the time of printing. Other approvals may be in process. Check with the manufacturer for any additional approvals.
Refer also to Design Criteria.
Listed by Underwriter's Laboratories, Inc. for use in the U.S., Canada, and European Union.
Meets New York City requirements, effective July 1, 2008.
° For areas of coverage smaller than shown, use the "Flow" and "Pressure" for the next larger area listed. Flows and pressures listed are per sprinkler. The distance from
sprinklers to walls shall not exceed one-half the sprinkler spacing indicated for the minimum "Flow" and "Pressure" used.
Cover Temperature Rating is 135 °F (57 °C). Cover Part No. 135041, 136421 (large diameter), or 153941 (square cover plate).
Other paint colors are available on request with the same listings as the standard finish colors. Listings and approvals apply for any paint manufacturer. Contact Viking
for additional information. Custom colors are indicated on a label inside the cover assembly. Refer to Figure 3.
10 Accepted Cover Plate Finishes are: Polished Chrome, Brushed Chrome, Bright Brass, Antique Brass, Brushed Brass, Brushed Copper, Painted White, Painted Ivory, or
Painted Black 1.
11 C-UL-US-EU Listed as corrosion resistant - Electroless Nickel PTFE (ENT)
Form No. F_012116 16.06.27 Rev 16.1
Wrench
14047W/B**
Sprinkler and Adapter Assembly
Protective cap removed
Use wrench l
step 1:
Carefully slide the
wrench sideways around
the deflector and pins
Step 2: t
Carefully press the wrench upward and
turn slightly to ensure engagement with
the sprinkler wrench flats.
2-1/4" (57 mm)
diameter opening
required in the
ceiling.
Page,4 of 5
lI[I1iUI7AfA
FREEDOM® RESIDENTIAL
CONCEALED PENDENT
P44J II(Ir%1G® -
SPRINKLER VK494 (K4.9)
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcsvikingcorp.com
Visit the Viking website for the latest edition of this technical data page.
DESIGN CRITERIA
(Also refer to the Approval Chart on page 3)
UL Listing Reguirements (C-UL-US-EU):
When using Viking Residential Concealed Pendent Sprinkler VK494 for systems designed to NFPA 13D or NFPA 13R, apply the listed areas of cover-
age and minimum water supply requirements shown in the Approval Chart.
For systems designed to NFPA 13: The number of design sprinklers is to be the four contiguous most hydraulically demanding sprinklers. The minimum
required discharge from each of the four sprinklers is to be the greater of the following:
The flow rates given in the Approval Chart for NFPA 13D and NFPA 13R applications for each listed area of coverage, ar
Calculated based on a minimum discharge of 0.1 gpm/sq. ft. over the design area" in accordance with sections 8.5.2.1 or 8.6.2.1.2 of NFPA 13.
Minimum distance between residential sprinklers: 8 ft. (2.4 m).
NOTE: Concealed sprinklers must be installed in neutral or negative pressure plenums only.
IMPORTANT: Always refer to Bulletin Form No. F_080415 - Best Practices for Residential Sprinkler Handling and Installation.
Also refer to Form No. F_080614 for general care, installation, and maintenance information. Viking sprinklers are to be in-
stalled in accordance with the latest edition of Viking technical data, the appropriate standards of NFPA and any other similar
Authorities Having Jurisdiction, and also with the provisions of governmental codes, ordinances, and standards, whenever
applicable. Final approval and acceptance of all residential sprinkler installations must be obtained from the Authorities
Having Jurisdiction.
NEVER install the sprinkler by applying the installation
wrench across the frame arms. DO NOT overtighten.
Use only the designated sprinkler wrenches, Viking
Part Numbers 14047W/B** or 14031**. A leak tight seal
should be achieved by turning the sprinkler clockwise
Ito 1-1/2 turns beyond finger tight.
Sprinkler
wrench flat
Sprinkler
frame arms
Figure 1: Sprinkler Installation and Proper Wrench Usage
** A 1/2" ratchet is required (Not available from Viking)
Form No. F012116 16.06.27 Rev 16.1
Page 5of5
0 NIJUM4 FREEDOM® RESIDENTIAL
Il[*UI1f CONCEALED PENDENT
- SPRINKLER VK494 (K4.9)
The Viking Corporation, 210 N Industrial Park Drive, Hastings Ml 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcsvikingcorp.com
Visit the Viking website for the latest edition of this technical data page.
1/2" (15 mm) NPT 2-9/16" (65 mm)
Maximum 2-1/16" (52 mm)
Minimum
Ln
2-3/4" (70 mm) or
NOTE: Upon sprinkler activation, the deflector descends 3-5/16" (84 mm)
to approximately 13/16" (21 mm) below the sprinkler body.
Figure 2: Sprinkler Dimensions and Cover Installation
All custom color painted cover plates will have an
identifying label affixed to the inside of the cover that
indicates the custom color and will have a representative
sample (a paint dot) of the paint on the label.
Figure 3: Identification of Custom Paint for Concealed Covers I
3-5116" (84 mm)
Figure 4: Square Cover Assembly 15394
Form No. F_012116 16.06.27 Rev 16.1 (New product, new page)
Page 1 of 6
MICROFAST® QUICK sj I 1(1 I1GI SPRINKLER VK302 (K5.6)
l.1II[s1iUI7AIfA RESPONSE PENDENT
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-8184680 Email: techsvcsvikingcorp.com
DESCRIPTION
The Viking Microfast' Quick Response Pendent Sprinkler VK302 is a small
thermosensitive glass bulb spray sprinkler available with various finishes
and temperature ratings to meet design requirements. The special Polyester,
Polytetrafluoroethelyne (PTFE), and Electroless Nickel PTFE (ENT) coatings
can be used in decorative applications where colors are desired. In addition,
these coatings have been investigated for installation in corrosive atmospheres
and are listed/approved as corrosion resistant as indicated in the Approval
Charts. (Note: FM Global approves ENT finish as corrosion resistant. FM Global has no approval classification for PTFE and Polyester coatings as corro-
sion resistant.)
LISTINGS AND APPROVALS
c®us cULus Listed: Category VNlV
FM Approved: Class Series 2000
VdS VdS Approved: Certificates G414009 and G414010
,, LPCB Approved
CE Certified: Standard EN 12259-1, EC-certificate of conformity 0832-CPD-2001
Refer to Approval Chart I and Design Criteria cULus Listing requirements, and refer to Approval Chart 2 and Design Criteria
for FM Approval requirements that must be followed.
TECHNICAL DATA
Specifications:
Minimum Operating Pressure: 7 psi (0.5 bar) Viking Technical Data may be found on
Rated to 175 psi (12 bar) water working pressure The Viking Corporation's Web site at
Factory tested hydrostatically to 500 psi (34.5 bar) http://www.vikinggroupinc.com. Thread size: 1/2" NPT, 15 mm BSP The Web site may include a more recent Nominal K-Factor: 5.6 U.S. (80.6 metric**) edition of this Technical Data Page. Glass-bulb fluid temperature rated to -65 °F (-55 °C)
Overall Length: 2-1/4" (58 mm)
*CULUS Listing, FM Approval, and NFPA 13 installs require a minimum of 7 psi (0.5 bar). The minimum operating pressure for LPCB and CE Approvals ONLY is 5 psi (0.35 bar).
Material Standards:
Frame Casting: Brass UNS-C84400 or QM Brass
Deflector: Phosphor Bronze UNS-051000 or Copper UNS-C19500
Bulb: Glass, nominal 3 mm diameter
Belleville Spring Sealing Assembly: Nickel Alloy, coated on both sides with PTFE Tape
Screw: Brass UNS-C36000
Pip Cap and Insert Assembly: Copper UNS-C11000 and Stainless Steel UNS-S30400
For PTFE Coated Sprinklers: Belleville Spring-Exposed, Screw-Nickel Plated, Pip Cap-PTFE Coated
For Polyester Coated Sorinklers: Belleville Spring-Exposed
For ENT Coated Sørinklers: Belleville Spring-Exposed, Screw and Pipcap - ENT plated.
Ordering Information: (Also refer to the current Viking price list.)
Order Quick Response Pendent Sprinklers by first adding the appropriate suffix for the sprinkler finish and then the appropriate
suffix for the temperature rating to the sprinkler base part number.
Finish Suffix: Brass = A, Chrome = F, White Polyester = M-/W, Black Polyester = M-/B, Black PTFE = N, and ENT = JN Temperature Suffix: 135°F (68 °C) =A, 155 °F (68 °C) = B, 175°F (79 °C) = D, 200°F (93 °C) = E, 286°F (141 °C) = G For example, sprinkler VK302 with a Brass finish and a 155 °F (68 °C) temperature rating = Part No. 12979AB Available Finishes And Temperature Ratings: Refer to Table 1.
Accessories: (Also refer to the "Sprinkler Accessories" section of the Viking data book.)
Form No. F_033314 Rev 14.2 (Added 06662B and 18021)
Page 2 of 6
I:ll[.1i..7f RESPONSE PENDENT Kj I4(1E ® MICROFAST® QUICK
SPRINKLER VK302 (K5.6)
The Viking Corporation, 210 N Industrial Park Drive, Hastings Ml 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcscvikingcorp.com
Sprinkler Wrenches:
Standard Wrench: Part No. 10896W/13 (available since 2000).
Wrench for Recessed Pendent Sprinklers: Part No. 16036W/13 (available since 2011)
Optional Protective Sprinkler Cap Remover/Escutcheon Installer Tool*** Part No. 15915 (available since 2010)
A 1/2 ratchet is required (not available from Viking).
***Allows use from the floor by attaching a length of 1" diameter CPVC tubing to the tool. Ideal for sprinkler cabinets. Refer to Bulletin F_051808.
Sprinkler Cabinets:
Six-head capacity: Part No. 01724A (available since 1971)
Twelve-head capacity: Part No. 01725A (available since 1971)
INSTALLATION
Refer to appropriate NFPA Installation Standards.
OPERATION
During fire conditions, the heat-sensitive liquid in the glass bulb expands, causing the glass to shatter, releasing the pip cap and
sealing spring assembly. Water flowing through the sprinkler orifice strikes the sprinkler deflector, forming a uniform spray pattern
to extinguish or control the fire.
INSPECTIONS, TESTS AND MAINTENANCE
Refer to NFPA 25 for Inspection, Testing and Maintenance requirements.
AVAILABILITY
The Viking Microfást® Quick Response Pendent Sprinkler VK302 is available through a network of domestic and international dis-
tributors. See The Viking Corporation web site for the closest distributor or contact The Viking Corporation.
GUARANTEE
For details of warranty, refer to Viking's current list price schedule or contact Viking directly.
Protective Sprinkler Isma Wrench Flat __
Clip
''--
___
: •.
Protective Sprinkler
Cap
40
Figure 1: Standard Sprinkler Wrench 10896W/B
Form No. F_033314 Rev 14.2
Page 3 of 6
MICROFAST® QUICK "11 I I(II'1G RESPONSE PENDENT
SPRINKLER VK302 (K5.6)
The Viking Corporation, 210 N Industrial Park Drive, Hastings Ml 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcsvikingcorp.com
TABLE 1: AVAILABLE SPRINKLER TEMPERATURE RATINGS AND FINISHES
Sprinkler Temperature Sprinkler Nominal Maximum Ambient Bulb-Color Classification Temperature Rating'
--
Ceiling Temperature'
Ordinary 135 OF (57 °C) 100 OF (38 °C) Orange
Ordinary 155 OF (68 °C) 100 OF (38 °C) Red
Intermediate 175 OF (79 °C) 150 OF (65 °C) Yellow
Intermediate 200 OF (93 °C) 150 OF (65 °C) Green
High 286 OF (141 °C) 225 OF (107 °C) Blue
Sprinkler Finishes: Brass, Chrome, White Polyester, Black Polyester, Black PTFE, and ENT
Corrosion-Resistant Coatings3: White Polyester, Black Polyester, and Black PTFE. ENT in all temperature ratings except 135 OF
(57 °C)
Footnotes
The sprinkler temperature rating is stamped on the deflector.
2 Based on NFPA-13. Other limits may apply, depending on fire loading, sprinkler location, and other requirements of the Authority Having Jurisdiction.
Refer to specific installation standards.
The corrosion-resistant coatings have passed the standard corrosion test required by the approving agencies indicated in the Approval Charts. These
tests cannot and do not represent all possible corrosive environments. Prior to installation, verify through the end-user that the coatings are com-
patible with or suitable for the proposed environment. For automatic sprinklers, the coatings indicated are applied to the exposed exterior surfaces
only. Note that the spring is exposed on sprinklers with Polyester, PTFE, and ENT coatings. For ENT coated automatic sprinklers, the waterway is
coated
Sprinkler wrench 16
for recessed pei
sprinklers
** A 1/2" ratchet is
(not available from
00 Carefully slide the wrench sideways around
the protective cap, ensuring engagement with
No the sprinkler wrench flats
Figure 2: Wrench 16036W/B for Recessed Pendent Sprinklers
Form No. F033314 Rev 14.2