tqCJ3 Fire & Building
I)Products
Technical Services: Tel: (800) 381-9312 I Fax: (800)'791-5500
Series TY-FRB - 2,8,42,5.6, and 8.0 K-factor
Upright, Pendent, and Recessed Pendent Sprinklers
Quick Response, Standard Coverage
General
Description
The Series TY-FRB, 2.8, 4.2, 5.6, and
8.0 K-factor, Upright and Pendent
Sprinklers described in this data sheet
are quick response - standard cover-
age, decorative 3 mm glass bulb type
spray sprinklers designed for use in
light or ordinary hazard, commercial
occupancies such as banks, hotels,
shopping malls, etc.
The recessed version of the Series
TY-FRB Pendent Sprinkler, where ap-
plicable, is intended for use in areas
with a finished ceiling. It uses either a
two-piece Style 10 (1/2 inch NPT) or
Style 40 (3/4 inch NPT) Recessed Es-
cutcheon with 1/2 inch (12,7 mm) of
recessed adjustment or up to 3/4 inch
(19,1 mm) of total adjustment from the
fiush pendent position, or a two-piece
Style 20(1/2 inch NPT) or Style 30(3/4
inch NPT) Recessed Escutcheon with
1/4 inch (6,4 mm) of recessed adjust-
ment or up to 1/2 inch (12,7 mm) of
total adjustment from the flush pen-
dent position. The adjustment pro-
vided by the Recessed Escutcheon re-
duces the accuracy to which the fixed
pipe drops to the sprinklers must be
cut.
Corrosion resistant coatings, where
applicable, are utilized to extend the
life of copper alloy sprinklers beyond
that which would otherwise be cb-
IMPORTANT
Always refer to Technical Data
Sheet TFP 700 for the "INSTALLER
WARNING" that priwides cautions
with respect to handling and instal-
lation of sprinkler systems and com-
ponents. Improper handling and in-
stallation can permanently damage
a sprinkler system or its compo-
nents and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
tamed when exposed to corrosive at-
mospheres. Although corrosion resis-
tant coated sprinklers have passed the
standard corrosion tests of the appli-
cable approval agencies, the testing is
not representative of all possible cor-
rosive atmospheres. Consequently, it
is recommended that the end user be
consulted with respect to the suitability
of these coatings for any given corro-
sive environment. The effects of ambi-
ent temperature, concentration of
chemicals, and gas/chemical velocity,
should be considered, as a minimum,
along with the corrosive nature of the
chemical to which the sprinklers will be
exposed.
An intermediate level versions of the
Series TY-FRB Pendent Sprinklers
are detailed in Technical Data Sheet
TFP356, and Sprinkler Guards are de-
tailed in Technical Data Sheet TFP780
WARNINGS
The Series TY-FRB Sprinklers de-
scribed herein must be installed and
maintained in compliance with this
document, as well as with the applica-
ble standards of the National Fire Pro-
tection Association, in addition to the
standards of any other authorities hav-
ing jurisdiction. Failure to do so may
impair the performance of these de-
vices.
The owner is responsible for maintain-
ing their fire protection system and de-
vices in proper operating condition.
The installing contractor or sprinkler
manufacturer should be contacted
with any questions.
Model/Sprinkler
Identification
Numbers
TYII3I - Upright 2.81K, 1/2"NPT
TY1231 - Pendent 2.81K, 1/2"NPT
TY2131 - Upright 4.21K, 1/2"NPT
TY2231 - Pendent 4.21K, 1/2"NPT
TY3131 - Upright 5.61K, 1/2"NPT
1Y3231 - Pendent 5.61K, 1/2"NPT
1Y4131 - Upright 8.0K, 3/4"NPT
TY4231 - Pendent 8.01K, 3/4"NPT
Page 1 of 10 APRIL, 2006 TFPI7I
Page 2 of 10
ESCUTCHEON 7/16" (11,1 mm)
PLATE SEATING 1/2" ** NOMINAL
SURFACE MAKE-IN NPT
2-1/4
(57,2 mm)
1-9/16"
(39,7 mm)
TFPI7I
STYLE 10 or 20
RECESSED
ESCUTCHEON Ubi-L.tlOK
_____________ 6
7/16' 1
(11,1mm)
INOMINAL
MAKE-IN
_5
2-3/16" WRENCH
_____
(55,6 mm)
FLATS
1/2" NPT** SSP DEFLECTOR h - 2-7/8" (73,0 mm) DIA.
PENDENT RECESSED PENDENT UPRIGHT CROSS SECTION
1 - Frame 3 - Sealing 4 - Bulb 6- Deflector * Temperature rating is indicated on deflector or adjacent to 2 - Button Assembly 5 - Compression 7 - Bushing orifice seat on frame. Screw **Pipe thread connections per ISO 7/1 can be provided on
special request.
FIGURE 1
QUICK RESPONSE SERIES TY-FRB UPRIGHT (TYII3I) AND PENDENT(TY1231) SPRINKLERS
2.8 K-FACTOR, 1/2 INCH NPT
SSP DEFLECTOR* H--- 2-7/8" (73,0 mm) DIA.
ESCUTCHEON
PLATE SEATING
SURFACE
2-3/16" \
(55,6 mm) (1
1-1/2"
(38,1 mm)
SSU *
DEFLECTOR
(11,1 mm)
7/16"
MAKE-IN
2-3/16"
NOMINAL
RENCH (55,6 mm)
FLATS
1/2" NPT**
7/16(11,1 mm) STYLE 10or20
1/2" ** NOMINAL RECESSED
MO,r MAKE-IN ESCUTCHEON
PENDENT RECESSED PENDENT UPRIGHT CROSS SECTION
1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector * Temperature rating is indicated on deflector or adjacent to 2 - Button Assembly 5 - Compression orifice seat on frame. Screw **Pipe thread connections per ISO 7/1 can be provided on
special request.
FIGURE 2
QUICK RESPONSE SERIES TY-FRB UPRIGHT (TY2131) AND PENDENT (TY2231) SPRINKLERS
4.2 K-FACTOR, 112 INCH NPT
7/16" (11,1 mm) STYLE 10or2C
** NOMINAL RECESSED
MAKE-IN ESCUTCHEON
2-7/8" (73,0 mm) DIA.
ESCUTCHEON
PLATE SEATING
SURFACE
F_
2-3/16" \i
(55,6 mm)
1-1/2
(38,1mm)
SSP DEFLECTOR*
SSU* DEFLECTOR
6*
7/16"
I
5
(11,1 mm)
NOMINAL
MAKE-IN I 2-3/16"
(55,6 mm)
1/2" NPT**
TFPI7I Page 3 of 10
PENDENT RECESSED PENDENT UPRIGHT CROSS SECTION
1 - Frame 3 - Sealing 4 - Bulb 6- Deflector * Temperature rating is indicated on deflector or adjacent to 2 - Button Assembly 5- Compression orifice seat on frame. Screw **Pipe thread connections per ISO 7/1 can be provided on
special request.
FIGURE 3
QUICK RESPONSE SERIES TY-FRB UPRIGHT (TY3131) AND PENDENT (TY3231) SPRINKLERS
5.6 K-FACTOR, 1/2 INCH NPT
ESCUTCHEON 1/2(12,7mm) STYLE 30 or 40
PLATE SEATING ** NOMINAL RECESSED SSU* SURFACE 3/4"MAKE-IN ESCUTCHEON NPT DEFLECTOR
1/2"
6*
2-5/16" (12,7 mm)
(58,7 mm)
SFLATS
NOMINALH1(57,2mm)3
AKE-IN
-
(39,7mm)
SSPDEFLECTOR* - 2-7/8"(73,O mm) DIA. 3/4 NPT**
PENDENT RECESSED PENDENT UPRIGHT CROSS SECTION
1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector * Temperature rating is indicated on deflector or adjacent to 2 - Button Assembly 5 - Compression orifice seat on frame. Screw **Pipe thread connections per ISO 7/1 can be provided on
special request.
FIGURE
QUICK RESPONSE SERIES TY-FRB UPRIGHT (TY4 131) AND PENDENT (TY4231) SPRINKLERS
8.0 K-FACTOR, 314 INCH NPT
Page 4 of 10 TFPI7I
SPRINKLER FINISH (See Note 7)
K TYPE TEMP. BULB NATURAL I CHROME
LIQUID
I
BRASS PLATED
JPWHITE-
OLYESTER
135°F/57C Orange
PENDENT
(TY1231)
and 123,5
155F/68°C Red
175°F/79C Yellow
UPRIGHT 2O0F/93°C Green
2.8
1/2
(TY1I31)
286°F/141°C Blue
NPT 135°F/57C Orange
RECESSED
PENDENT
155°F/68C Red
175F/79°C Yellow (TY1231)*
Figure 5 1,2,5 200°F/93°C Green
135FI57C Orange
RECESSED
PENDENT
155F/68°C Red
175FI79°C Yellow (TY1231)**
Figure 6 200°F193°C Green
135F/57°C Orange
PENDENT
(TY2231) 155°F/68°C Red
175FI79°C Yellow and
UPRIGHT 200°F/93C Green
42
1/2"
(TY2131)
1,2 286°F/141°C Blue
135°F157°C Orange NPT
RECESSED
PENDENT
155°F/68°C Red
175F/79°C Yellow (1Y2231)*
Figure 7 200°F/93C Green
135°F/57C Orange
RECESSED
PENDENT
155°F/68°C Red
175°F/79°C Yellow (TY2231)**
Figure 8 200F/93°C Green
NOTES:
Listed by Underwriters Laboratories, Inc. (UL) as Quick Response Sprinklers.
Listed by Underwriters Laboratories, Inc. for use in Canada (C-UL) as Quick Re-
sponse Sprinklers.
Approved by Factory Mutual Research Corporation (FM) as Quick Response Sprin-
klers.
5. Approved by the City of New York under MEA 354-01-E.
7. Where Polyester Coated Sprinklers are noted to be UL and C-UL Listed, the sprin-
klers are UL and C-UL Listed as Corrosion Resistant Sprinklers.
* Installed with Style 10 (1/2 NPT) or Style 40 (3/4" NPT) 3/4" Total Adjustment
Recessed Escutcheon, as applicable.
** Installed with Style 20 (1/2" NPT) or Style 30 (3/4" NPT) 1/2" Total Adjustment
Recessed Escutcheon, as applicable.
Frame and Deflector only. Listings and approvals apply to color (Special Order).
N/A: Not Available
TABLE A
LABORATORY LISTINGS AND APPROVALS
2.8 AND 4.2 K-FACTOR SPRINKLERS
Technical
Data
Approvals
UL and C-UL Listed.
FM, LPCB, and NYC Approved.
(Refer to Table A and B for complete
approval information including corro-
sion resistant status.)
Maximum Working Pressure
Refer to Table C.
Discharge Coefficient
K = 2.8 GPM/psi112 (40,3 LPM/barl/2)
K = 4.2 GPM/psi112 (60,5 LPM/barl'2)
K = 5.6 GPM/psi112 (80,6 LPM/barl'2)
K = 8.0 GPM/psi112 (115,2 LPM/barl/2)
Temperature Ratings
Refer to Table A and B
Finishes
Sprinkler: Refer to Table A and B.
Recessed Escutcheon: White Coated,
Chrome Plated, or Brass Plated.
Physical Characteristics
Frame ............Bronze
Button ........Brass/Copper
Sealing Assembly ..........
Beryllium Nickel w/Teflont
Bulb ..............Glass
Compression Screw .....Bronze
Deflector .......Copper/Bronze
Bushing (K=2.8) ........Bronze
Operation
The glass Bulb contains a fluid which
expands when exposed to heat. When
the rated temperature is reached, the
fluid expands sufficiently to shatter the
glass Bulb, allowing the sprinkler to
activate and water to flow.
Design
Criteria
The Series TY-FRB Pendent and Up-
right Sprinklers are intended for fire
protection systems designed in ac-
cordance with the standard installation
rules recognized by the applicable
Listing or Approval agency (e.g., UL
Listing is based on the requirements of
NFPA 13, and FM Approval is based
on the requirements of FM's Loss Pre-
vention Data Sheets ). Only the Style
10, 20, 30, or 40 Recessed Escutch-
eon, as applicable, is to be used for
recessed pendent installations.
1—
TFPI7I Page 5 of 10
SPRINKLER FINISH (See Note 8)
K TYPE TEMP. BULB NATURAL I CHROME WHITE*** LEAD
BRASS PLATED
I
LIQUID POLYESTER COATED
135°F/57°C Orange
PENDENT
(TY3231)
and 1,2,3,4,5,6,7 1,2,3,5
155°F/68°C - Red
175°F/79°C Yellow
UPRIGHT 200°F/93°C Green
5.6 (TY3131)
1/2" 286°F/141C Blue
NPT 135F/57°C Orange
RECESSED
PENDENT
(TY3231)* 1,2,4,5 N/A
155°F168°C Red
175°F/79C Yellow
Figure 9 200FI93°C Green
135°F/57C Orange I
RECESSED
PENDENT
(TY3231) 1, 2, 3, 4, 5
I I I 1, 2, 4, 5 I N/A
155F/68°C Red
175°F/79C Yellow
Figure 10 Green 200°F/93C
135°F/57C Orange
PENDENT
(TY4231)
and
UPRIGHT 1,2,3,4,5,6,7
1,2,5
155°F/68°C Red
175°F/79°C Yellow
200F/93°C Green
8.0 (TY4131)
3/4,, 286F/141°C Blue
NPT 135F/57°C Green
RECESSED
PENDENT
(TY4231)* 1, 2, 4, 5 N/A
155F/68°C Orange
175F/79°C Red
Figure 11 200°F/93°C Yellow
135°F/57C Orange
RECESSED
PENDENT
(TY4231)** 1,2,3,4,5 N/A
155°F168°C Red
175°F/79°C Yellow
Figure 12 200°F/93°C Green
NOTES:
Listed by Underwriters Laboratories, Inc. (UL) as Quick Response Sprinklers.
Listed by Underwriters Laboratories, Inc. for use in Canada (C-UL) as Quick Response Sprinklers.
Approved by Factory Mutual Research Corporation (FM) as Quick Response Sprinklers.
Approved by the Loss Prevention Certification Board (LPCB Ref. No. 007k/04) as Quick Response Sprinklers; however, the
LPCB does not rate the thermal sensitivity of recessed sprinklers.
Approved by the City of New York under MEA 354-01-E.
VdS Approved (For details contact Tyco Fire & Building Products, Enschede, Netherlands, Tel. 31-53-428-4444/Fax 31-53-428-3377).
Approved by the Loss Prevention Certification Board (LPCB Ref. No. 094a/06) as Quick Response Sprinklers.
Where Polyester Coated and Lead Coated Sprinklers are noted to be UL and C-UL Listed, the sprinklers are UL and C-UL Listed as
Corrosion Resistant Sprinklers. Where Lead Coated Sprinklers are noted to be FM Approved, the sprinklers are FM Approved as a
Corrosion Resistant Sprinklers.
* Installed with Style 10 (1/2" NPT) or Style 40 (3/4" NPT) 3/4" Total Adjustment Recessed Escutcheon, as applicable.
** Installed with Style 20 (1/2" NPT) or Style 30 (3/4" NPT) 1/2" Total Adjustment Recessed Escutcheon, as applicable.
Frame and Deflector only. Listings and approvals apply to color (Special Order).
N/A: Not Available
TABLE B
LABORATORY LISTINGS AND APPROVALS
5.6 AND 8.0 K-FACTOR SPRINKLERS
Page 6 of 10 TFPI7I
SPRINKLER FINISH
K TYPE NATURAL CHROME WHITE LEAD
BRASS PLATED
I
POLYESTER COATED
PENDENT (TY3231)
and
2.8 UPRIGHT (TY3131) 175 PSI (12,1 BAR) N/A
1/2" RECESSED PENDENT NPT (TY323)
PENDENT (TY4231)
and
4.2 UPRIGHT (TY4131) 175 PSI (12,1 BAR) N/A
RECESSED PENDENT NPT (TY4231)
PENDENT (TY3231)
and 250 PSI (17,2 BAR) 175 PSI (12,1 BAR)
5.6 UPRIGHT (TY3131) OR
1/2' 175 PSI (12,1 BAR) RECESSED PENDENT NPT (TY323) (SEE NOTE 1) N/A
PENDENT (TY4231)
and 175 PSI (12,1 BAR) 175 PSI (12,1 BAR)
8.0 UPRIGHT (TY4131)
RECESSED PENDENT NPT (TY4231) N/A
NOTES:
1. The maximum working pressure of 250 psi (17,2 bar) only applies to the Listing by Underwriters Laboratories Inc. (UL); the Listing by
Underwriters Laboratories, Inc. for use in Canada (C-UL); and ,the Approval by the City of New York.
TABLE C, MAXIMUM WORKING PRESSURE
nections. Higher levels of torque may The Series TY-FRB Recessed Pen-
distort the sprinkler inlet and cause dent Sprinklers must be installed in
leakage or impairment of the sprinkler, accordance with the following instruc-
Installation
The Series TY-FRB Sprinklers must
be installed in accordance with the fol-
lowing instructions:
NOTES
Do not install any bulb type sprinkler if
the bulb is cracked or there is a loss of
liquid from the bulb. With the sprinkler
held horizontally, a small air bubble
should be present. The diameter of the
air bubble is approximately 1/16 inch
(1,6 mm) for the 135°F/57°C to 3/32
inch (2,4 mm) for the 286F/141C
temperature ratings.
A leak tight 1/2 inch NPTsprinklerjoint
should be obtained with a torque of 7
to 14 ft.lbs. (9,5 to 19,0 Nm). A maxi-
mum of 21 ft. lbs. (28,5 Nm) of torque
may be used to install sprinklers with
1/2 NPT connections. A leak tight 3/4
inch NPT sprinkler joint should be ob-
tained with a torque of 10 to 20 ft.lbs.
(13,4 to 26,8 Nm). A maximum of 30
ft.lbs. (40,7 Nm) of torque is to be used
to install sprinklers with 3/4 NPT con-
Do not attempt to make-up for insuffi-
cient adjustment in the escutcheon
plate by under- or over-tightening the
sprinkler. Readjust the position of the
sprinkler fitting to suit.
The Series TY-FRB Pendent and Up-
right Sprinklers must be installed in
accordance with the following instruc-
tions.
Step 1. Pendent sprinklers are to be
installed in the pendent position, and
upright sprinklers are to be installed in
the upright position.
Step 2. With pipe thread sealant ap-
plied to the pipe threads, hand tighten
the sprinkler into the sprinkler fitting.
Step 3. Tighten the sprinkler into the
sprinkler fitting using only the W-Type
6 Sprinkler Wrench (Ref. Figure 13).
With reference to Figures 1, 2, 3, and
4, the W-Type 6 Sprinkler Wrench is to
be applied to the sprinkler wrench
flats.
tions.
Step A. After installing the Style 10.
20, 30, or 40 Mounting Plate, as appli-
cable, over the sprinkler threads and
with pipe thread sealant applied to the
pipe threads, hand tighten the sprin-
kler into the sprinkler fitting.
Step B. Tighten the sprinkler into the
sprinkler fitting using only the W-Type
7 Recessed Sprinkler Wrench (Ref.
Figure 14). With reference to Figure 1,
2, 3, and 4, the W-Type 7 Recessed
Sprinkler Wrench is to be applied to
the sprinkler wrench flats.
Step C. After the ceiling has been in-
stalled or the finish coat has been ap-
plied, slide on the Style 10, 20, 30, or
40 Closure over the Series TY-FRB
Sprinkler and push the Closure over
the Mounting Plate until its flange
comes in contact with the ceiling.
TFPI7I
- 2-7/8 DIA.
5/8±1/4"
(73,0 mm) 3/4" (19,1 mm)
(15,9±6,4 mm) 2-1/4" DIA. 1/4" (6,4 mm)
FACE OF (57,2 mm) I I
MOUNTING I SPRINKLER PLATE I
FITTING
1/8"
'H
MOUNTING
SURFACE
CLOSURE SERIES 1-5/16"( mm)I
TY-FRB 13/16" (20,6 mm)
FIGURE 5
SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT
STYLE 10 RECESSED ESCUTCHEON
2.8 K-FACTOR, 1/2 INCH NPT
2-7/8" DIA.
5/8±1/4" (73,0 mm) 3/4(19,1 mm)
(15,9±6,4 mm) 2-1/4" DIA. 1/4" (6,4 mm) I
(57,2 mm MOUNTING) FACE OF
_J
SPRINKLER
-
PLATE
FITTING
(3,2 m
2
__ _____
MOUNTING
SURFACE/ SERIES
1-1/4" (31 CLOSURE TY-FRB 3/4" (19,1 mm)
FIGURE 7
SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT
STYLE 10 RECESSED ESCUTCHEON
4.2 K-FACTOR, 1/2 INCH NPT
Page 7 of 10
- 2-7/8" DIA.
(73,0 mm) 1/2±1/8" 1/2 (12,7 mm)
[ (12,7±3,2 mm) - 2-1/4" DIA. I 1/4" (6,4 mm)
FACE OF
#
(57,2 mm) I
FITTING
/
SPRINKLER MOUNTING I
PLATE
(3,2 mm)
MOUNT ING
SURFACE
,/
///'
t
CLOSURE SERIES 1-5/16" (33,3 mm)I
TY-FRB 1-1/16" (27,0 mm)
FIGURE 6
SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 20 RECESSED ESCUTCHEON
2.8 K-FACTOR, 1/2 INCH NPT
2-7/8" DIA.
1/2±1/8"
(73,0 mm) 1/2(12,7mm)
[(12,7±3,2mm) 2-1/4" DIA. 1/4" (6,4 mm) I
FACE OF (57,2 mm) I I I
PLATE
MOUNTING
SPRINKLE
I
FITTING
1/8"
(3,2 mm I
T__7_ \
MOUNTING
SURFACE
SERIES 1-1/4(31,8mm) CLOSURE TY-FRB 1" (25,4 mm)
FIGURE 8
SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 20 RECESSED ESCUTCHEON
4.2 K-FACTOR, 1/2 INCH NPT
Care and
Maintenance
The Series TY-FRB Sprinklers must
be maintained and serviced in accord-
ance with the following instructions:
NOTES
Before closing a fire protection system
main control valve for maintenance
work on the fire protection system that
it controls, permission to shutdown the
affected fire protection system must be
obtained from the proper authorities
and all personnel who may be affected
by this action must be notified.
The owner must assure that the sprin-
klers are not used for hanging of any
objects; otherwise, non-operation in
the event of a fire or inadvertent opera-
tion may result.
Absence of an escutcheon, which is
used to cover a clearance hole, may
delay the time to sprinkler operation in
a fire situation.
Sprinklers that are found to be leaking
or exhibiting visible signs of corrosion
must be replaced.
Automatic sprinklers must never be
painted, plated, coated or otherwise
altered after leaving the factory. Modi-
fied sprinklers must be replaced.
Sprinklers that have been exposed to
corrosive products of combustion, but
have not operated, should be replaced
if they cannot be completely cleaned
by wiping the sprinkler with a cloth or
by brushing it with a soft bristle brush.
Care must be exercised to avoid dam-
age to the sprinklers - before, during,
and after installation. Sprinklers dam-
aged by dropping, striking, wrench
twist/slippage, or the like, must be re-
placed. Also, replace any sprinkler
that has a cracked bulb or that has lost
liquid from its bulb. (Ref. Installation
Section).
Frequent visual inspections are rec-
ommended to be initially performed for
corrosion resistant coated sprinklers,
after the installation has been com-
pleted, to verify the integrity of the cor-
rosion resistant coating. Thereafter,
annual inspections per NFPA 25
should suffice; however, instead of in-
specting from the floor level, a random
Page 8 of 10
2-7/8 DIA.
5/8±1/4
(73,0 mm) 3/4" (19,1 mm)
(159±6,4 mm) 2-1/4 DIA 1/4 (6,4
FACE OF
FITTING
SPRINKLER
[T572 mm) MOUNTING
PLATE
1/8 _(32m J
/
MOUNTING
SURFACE
CLOSURE SERIES 1-1/4(31,8 mm) 1 TYFRB 3/4" (19,1 mm)
FIGURE 9
SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT
STYLE 10 RECESSED ESCUTCHEON
5.6 K-FACTOR, 1/2 INCH NPT
2-7/8' DIA. -
5/8±1/4" (73,0 mm) 3/4" (19,1 mm)
(15,9±6,4 mm) 2-1/4" CIA. 1/4" (6,4 mm)
FACE OF (57,2 mm) MOUNTING
SPRINKLER PLATE
FITTING
PLA
MOUNTING / I
SURFACE//
CLOSURE SERIES
TY-FRB 13/16" (20,6 mm)
FIGURE 11
SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT
STYLE 40 RECESSED ESCUTCHEON
8.0 K-FACTOR, 3/4 INCH NPT
TFP1 71
- 2-7/8" DIA.
1/2±1/8" (73.0 mm) 1/2(12,7mm)
E (12,7±3,2 mm) 2-1/4" DIA. 1/4" (6,4 mm)
FACE OF
SPRINKLER
T57,2 mm) MOUNTING
PLATE
FITTING
1/8"
(32mm)
MOUNTING
SURFACE
SERIES 1-1/4"(31,8mm) CLOSURE TY-FRB 1" (25,4 mm)
FIGURE 10
SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 20 RECESSED ESCUTCHEON
5.6 K-FACTOR, 1/2 INCH NPT
2-7/8" DIA. -
1/2±1/8"
2-1/4" DIA. 1/4" (6,4 mm) (12,7±3,2 mm)
p
(73,0 mm) 1/2" (12,7 mm)
(57,2 mm) I FACE OF MOUN TING
SPRINKLER
TING
I
PLATE
FITTING
/ (32mm
T__\_ -
MOUNTING
SURFACE
CLOSURE SERIES 1-5/16" (33,3 mm)
TY-FRB 1-1/16" (27,0 mm)
FIGURE 12
SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 30 RECESSED ESCUTCHEON
8.0 K-FACTOR, 3/4 INCH NPT
sampling of Close-Up visual inspec-
tions should be made, so as to better
determine the exact sprinkler condi-
tion and the long term integrity of the
Corrosion resistant coating, as it may
be affected by the corrosive conditions
present.
The owner is responsible for the in-
spection, testing, and maintenance of
their fire protection system and de-
vices in compliance with this docu-
ment, as well as with the applicable
standards of the National Fire Protec-
tion Association (e.g., NFPA 25), in
addition to the standards of any other
authorities having jurisdiction. The in-
stalling contractor or sprinkler manu-
facturer should be contacted relative
to any questions.
It is recommended that automatic
sprinkler systems be inspected,
WRENCH RECESS
(END "A" USED FOR
1/2" NPT MODELS)
WRENCH RECESS
(END "B" USED FOR
3/4" NPT MODELS)
FIGURE 13
W-TYPE 6 SPRINKLER
WRENCH
tested, and maintained by a qualified
Inspection Service in accordance with
local requirements and/or national
codes.
WRENCH
RECESS
PUSH WRENCH
IN TO ENSURE
ENGAGEMENT
WITH SPRINKLER
WRENCHING AREA
FIGURE 14
W-TYPE 7 RECESSED
SPRINKLER WRENCH
TFPI7I Page 9 of 10
PIN 57- XXX -X--XXX
MODEUSIN
330 2.8K UPRIGHT (1/2"NPT) TY1131
331 2.8K PENDENT (1/2"NPT) TY1231
340 4.2K UPRIGHT (1/2"NPT) TY2131
341 4.2K PENDENT (1/2"NPT) TY2231
370 5.6K UPRIGHT (1/2"NPT) 1Y3131
371 5.6K PENDENT (1/2"NPT) TY3231
390 8.0K UPRIGHT (3/4"NPT) 1Y4131
391 8.0K PENDENT (314"NPT) TY4231
I I
L 135
SPRINKLER
155
178
200
286
RATING
1 NATURAL BRASS 155*F/68*C
4 WHITE POLYESTER 175*F/79*C
3 WHITE (RAL9010)* 200*F/93*C
9 CHROME PLATED 286*F/141*C
7 LEAD COATED
* Eastern Hemisphere sales only.
TABLED
PART NUMBER SELECTION
SERIES TY-FRB PENDENT AND UPRIGHT SPRINKLERS
Limited
Warranty
Products manufactured by Tyco Fire &
Building Products (TFBP) are war-
ranted solely to the original Buyer for
ten (10) years against defects in mate-
rial and workmanship when paid for
and properly installed and maintained
under normal use and service. This
warranty will expire ten (10) years
from date of shipment by TFBP. No
warranty is given for products or com-
ponents manufactured by companies
not affiliated by ownership with TFBP
or for products and components which
have been subject to misuse, improper
installation, corrosion, or which have
not been installed, maintained, modi-
fied or repaired in accordance with ap-
plicable Standards of the National Fire
Protection Association, and/or the
standards of any other Authorities
Having Jurisdiction. Materials found
by TFBP to be defective shall be either
repaired or replaced, at TFBP's sole
option. TFBP neither assumes, nor
authorizes any person to assume for it,
any other obligation in connection with
the sale of products or parts of prod-
ucts. TFBP shall not be responsible for
sprinkler system design errors or inac-
curate or incomplete information sup-
plied by Buyer or Buyer's repre-
sentatives.
In no event shall TFBP be liable, in
contract, tort, strict liability or under
any other legal theory, for incidental,
indirect, special or consequential dam-
ages, including but not limited to labor
charges, regardless of whether TFBP
was informed about the possibility of
such damages, and in no event shall
TFBP's liability exceed an amount
equal to the sales price.
The foregoing warranty is made in lieu
of any and all other warranties, ex-
press or implied, including warranties
of merchantability and fitness for a par-
ticular purpose.
This limited warranty sets forth the ex-
clusive remedy for claims based on
failure of or defect in products, materi-
als or components, whether the claim
is made in contract, tort, strict liability
or any other legal theory.
This warranty will apply to the full ex-
tent permitted by law. The invalidity, in
whole or part, of any portion of this
warranty will not affect the remainder.
Ordering
Procedure
When placing an order, indicate the
full product name. Refer to the Price
List for complete listing of Part Num-
bers.
Contact your local distributor for avail-
ability.
Sprinkler Assemblies with NPT
Thread Connections:
Specify: (Specify Model/SIN), Quick
Response, (specify K-factor), (specify
temperature rating), Series TY-FRB
(specify Pendent or Upright) Sprinkler
with (specify type of finish or coating),
P/N (specify from Table D).
Recessed Escutcheon:
Specify: Style (10, 20, 30, or 40) Re-
cessed Escutcheon with (specify*) fin-ish, P/N (specify*).
* Refer to Technical Data Sheet TFP770.
Sprinkler Wrench:
Specify: W-Type 6 Sprinkler Wrench,
P/N 56-000-6-387.
Specify: W-Type 7 Sprinkler Wrench,
P/N 56-850-4-001.
Page 10 of 10 TFPI7I
TYCO FIRE & BUILDING PRODUCTS, 451 North Cannon Avenue, Lansdale, Pennsylvania 19446
4 . . .
tqC0 /Fire & Building
I Products
Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500 I
Series RFII - 5.6 K-factor
"Royal Flush II" Pendent Concealed Sprinklers
Quick & Standard Response, Standard Coverage
General
Description
The Series RFII Quick Response
(3 mm bulb) & Standard Response (5
mm bulb), 5.6 K-Factor, "Royal Flush
II" Concealed Pendent Sprinklers are
decorative sprinklers featuring a flat
cover plate designed to conceal the
sprinkler. It is the best choice for archi-
tecturally sensitive areas such as hotel
lobbies, office buildings, churches,
and restaurants.
Each unit includes a Cover Plate As-
sembly that conceals the sprinkler op-
erating components above the ceiling.
The separable two-piece design of the
Cover Plate and Support Cup Assem-
blies allows installation of the sprin-
klers and pressure testing of the fire
protection system prior to installation
of a suspended ceiling or application
of the finish coating to a fixed ceiling.
They also permit removal of sus-
pended ceiling panels for access to
building service equipment without
having to first shut down the fire pro-
tection system and remove sprinklers.
Also, the separable two-piece design
of the the Sprinkler provides for 1/2
inch (12,7 mm) of vertical adjustment,
to reduce the accuracy to which the
length of fixed pipe drops to the sprin-
klers must be cut.
The Series RFII Sprinklers are
shipped with a Disposable Protective
IMPORTANT
Always refer to Technical Data
Sheet TFP700 for the "INSTALLER
WARNING" that provides cautions
with respect to handling and instal-
lation of sprinkler systems arid com-
ponents. Improper handling and in-
stallation can permanently damage
a sprinkler system or its compo-
nents and cause the sprinkler to fall
to operate in a fire situation or cause
it to operate prematurely.
Page 1 of 4
Cap. The Protective Cap is temporarily
removed for installation, and then it
can be replaced to help protect the
sprinkler while the ceiling is being in-
stalled or finished. The tip of the Pro-
tective Cap can also be used to mark
the center of the ceiling hole into plas-
ter board, ceiling tiles, etc. by gently
pushing the ceiling product against the
Protective Cap. When the ceiling in-
stallation is complete the Protective
Cap is removed and the Cover Plate
Assembly installed.
As an option, the Series RFII Standard
Response (5 mm bulb) 'Royal Flush II"
Concealed Pendent Sprinklers may be
fitted with a silicone Air and Dust Seal
(Ref. Fig. 5). The Air and Dust Seal is
intended for sensitive areas where it is
desirable to stop air and dust travel
through the cover plate from the area
above the ceiling.
WARNINGS
The Series RFII Concealed Pendent
Sprinklers described herein must be
installed and maintained in compli-
ance with this document, as well as
with the applicable standards of the
National Fire Protection Association,
in addition to the standards of any
other authorities having jurisdiction.
Failure to do so may impair the per-
formance of these devices.
The owner is responsible for maintain-
ing their fire protection system and de-
vices in proper operating condition.
The installing contractor or sprinkler
manufacturer should be contacted
with any questions.
Model/Sprinkler
Identification
Numbers
TY3551 (5mm bulb) & TY3531 (3 mm
bulb): maximum 175 psi (12,1 bar) by
UL, C-UL, FM, LPCB and NYC.
TY3504 (5 mm bulb) & TY3505 (3 mm
bulb): maximum 250 psi (17,3 bar) by
JULY, 2004
UL, C-UL, and NYC. Maximum 175
psi (12,1 bar) by FM.
Technical
Data
Approvals for Series RFII
UL and C-UL Listed. FM Approved.
NYC under MEA353-01-E.LPCB(Ref.
No. 094a109 for TY3551 & 094a/10 for
TY3531) Approved.
The approvals apply only to the serv-
ice conditions indicated in the Design
Criteria section and maximum pres-
sure ratings indicated in the
Model/Sprinkler Identification Num-
bers section.
Approvals for Air & Dust Seal
(Part #10908100)
UL and C-UL Listed for use with the
RFII (TY3551 & TY3504) Standard Re-
sponse Concealed Sprinkler.
Temperature Ratings
155F/68C Sprinkler - 135F/57C Plate
200F/93C Sprinkler - 165F/74C Plate
Discharge Coefiient 1/2 K = 5.6 GPM/psi" (80,6 LPM/bar )
Adjustment
1/2 inch (12,7 mm)
Finishes
Cover Plate: Chrome Plated, Brass
Plated, or White Painted (Custom paint
matches and colors other than white
are available on request.)
TFPIØI
Page 2 of 4 TFPIBI
1I2 NPT SEALING
ASSEMBLY
FRAME
- CAP
SUPPORT -
CUP WITH BULB
ROLL FORMED -
THREADS 1
I
- COMPRESSION
- SCREW
GUIDE
PINS (2)
DEFLECTOR
(DROPPED
DEFLECTOR POSITION) _j_-
SPRINKLER/SUPPORT CUP
ASSEMBLY
THREAD INTO U RETAINER
SUPPORTCUP fi WITH THREAD
UNTIL MOUNTING 0 '- DIMPLES
SURFACEIS (1' FLUSH WITH EJECTION
CEILING SPRING
SOLDER
L
COVER
TABS COVER PLATE/RETAINER PLATE
ASSEMBLY
FIGURE 1
SERIES RFII CONCEALED SPRINKLER
ASSEMBLY -
Physical Characteristics
Frame .............Bronze
Support Cup . Chrome Plated Steel
Guide Pins ......Stainless Steel
Deflector ...........Bronze
Compression Screw ......Brass
Bulb ...............Glass
Cap ........Bronze or Copper
Sealing Assembly ..........
Beryllium Nickel w/Teflon*
Cover Plate ...........Brass
Retainer ............Brass
Ejection Spring . . - . Stainless Steel
Patents
U.S.A. 4,014,388
Operation
When exposed to heat from a tire, the
Cover Plate, which is normally sol-
dered to the Retainer at three points,
falls away to expose the Sprinkler As-
sembly. At this point the Deflector sup-
portd by the Guide Pins drops down
to its operational position.
The glass Bulb contains a fluid that
expands when exposed to heat. When
the rated temperature is reached, the
fluid expands sufficiently to shatter the
glass Bulb, activating the sprinkler and
allowing water to flow.
Design
Criteria
The RFII (TY3551 & TY3504), 5 mm
Bulb Type, Concealed Pendent Sprin-
klers are UL and C-UL Listed as stand-
ard response - standard spray sprin-
klers for use in accordance with the
current NFPA standard. They are FM
Approved as standard response -
standard spray sprinklers for use in
accordance with the current FM Loss
Prevention Data Sheets.
The RFII (TY3531 & TY3505) 3 mm
Bulb Type, Concealed Pendent Sprin-
klers are UL and C-UL Listed as quick
response - standard spray sprinklers
for use in accordance with the current
NFPA standard. They are FM Ap-
proved as standard response - stand-
ard spray sprinklers for use in accord-
ance with the current FM Loss
Prevention Data Sheets.
The Series RFII Concealed Pendent
Sprinklers are only listed and ap-
proved with the Series RFII Concealed
Cover Plates having a metallic or white
painted finish.
The Series RFII must not be used in
applications where the air pressure
above the ceiling is greater than that
below. Down drafts through the Sup-
port Cup could delay sprinkler opera-
tion in a fire situation.
Installation
The Series RFII must be installed in
accordance with the following instruc-
tions:
NOTES
Do not install any bulb type sprinkler if
the bulb is cracked or there is a loss of
liquid from the bulb. With the sprinkler
held horizontally, a small air bubble
should be present. The diameter of the
air bubble is approximately 1/16 inch
(1,6 mm) for the 155°F/680C and 3/32
inch (2,4 mm) for the 200°F/93°C tem-
perature ratings.
A leak tight 1/2 inch NPTsprinkler joint
should be obtained with a torque of 7
to 14 ft.lbs. (9,5 to 19,0 Nm). A maxi-
mum of 21 ft.lbs. (28,5 Nm) of torque
is to be used to install sprinklers.
Higher levels of torque may distort the
sprinkler inlet with consequent leak-
age or impairment of the sprinkler.
Do not attempt to compensate for in-
sufficient adjustment in the Sprinkler
Assembly by under- or over-tightening
the Sprinkler/Support Cup Assembly.
Readjust the position of the sprinkler
fitting to suit.
Step 1. The sprinkler must only be
installed in the pendent position and
with the centerline of the sprinkler per-
pendicular to the mounting surface.
Step 2. Remove the Protective Cap.
Step 3. With pipe thread sealant ap-
plied to the pipe threads, hand tighten
the sprinkler into the sprinkler fitting.
Step 4. Wrench tighten the Sprinkler
using only the RFII Sprinkler Wrench
(Ref. Figure 3). The RFII Sprinkler
Wrench is to be applied to the Sprin-
kler as shown in Figure 3.
Step 5. Replace the Protective Cap
(Ref. Figure 4) by pushing it upwards
until it bottoms out against the Support
Cup. The Protective Cap helps prevent
damage to the Deflector and Arms dur-
ing ceiling installation and/or during
application of the finish coating of the
ceiling. It may also be used to locate
the center of the clearance hole by
gently pushing the ceiling material up
against the center point of the Protec-
tive Cap.
NOTE
As long as the Protective Cap remains
in place, the system is considered to
be "Out of Service".
* Registered Trademark of DuPont
\ H H
-\
3/16" to 11/16" MANUFACTURER DEFLECTOR COVER PLATE (4,8 to 17,5 mm) PRESET GAP IN DROPPED RETAINER
REFERENCE 3/32" (2,4 mm) POSITION ASSEMBLY
COVER PLATE COVER PLATE
- PROFILE DEPTH - DIAMETER
DIMENSION B DIMENSION A
3-1/4" (82,6 mm) C: 2-3/8" to 2-5/8" (60,3 to 66,7 mm)
3/16" (4,8 mm) D: 1-3/4" to 2-1/4" (44,5 to 57,2 mm)
FIGURE 2
SERIES RFII CONCEALED SPRINKLER
INSTALLATION DIMENSIONS
TFPI8I Page 3 of 4
FACE OF CLEARANCE HOLE
SPRINKLER DIAMETER
FITTING
SPRINKLER
SUPPORT CUP
ASSEMBLY
1/2' (12,7 mm)
LMENSIONC
THREADED
D ADJUSTMENT
1
I FACE OF CEILING, I RETAINING RING I MOUNTING I SURFACE 7771
Step 6. After the ceiling has been com-
pleted with the 2-1/2 inch (63,5 mm)
diameter clearance hole and in prepa-
ration for installing the Cover Plate As-
sembly, remove and discard the Pro-
tective Cap, and verify that the
Deflector moves up and down freely. If
the Sprinkler has been damaged and
the Deflector does not move up and
down freely, replace the entire Sprin-
kler assembly. Do not attempt to mod-
ify or repair a damaged sprinkler.
Step 7. When installing an Air and
Dust Seal, refer to Figure 5, otherwise
proceed to Step 8. To attach the Air and
Dust Seal, verify the angle of the out-
side edge of the seal is oriented ac-
cording to Figure 5. Start the edge of
the Retainer in the grooved slot of the
Air and Dust Seal and continue around
the retainer until the entire Air and
Dust Seal is engaged.
NOTE
The Air and Dust Seal is only to be
installed on the periphery of the Re-
tainer.
Step 8. Screw on the Cover Plate/Re-
tainer Assembly until the Retainer -
Figure 2 (or Air and Dust Seal - Figure
5) contacts with the ceiling. Do not
continue to screw on the Cover
Plate/Retainer Assembly such that it
lifts a ceiling panel out of its normal
position. If the Cover Plate/Retainer
Assembly cannot be engaged with the
Support Cup or the Cover Plate/Re-
tainer Assembly cannot be engaged
sufficiently to contact the ceiling, the
Sprinkler Fitting must be repositioned.
Care and
Maintenance
The Series RFII must be maintained
and serviced in accordance with the
following instructions:
NOTES
Absence of the Cover Plato Assembly
may delay sprinkler operation in a fire
situation.
Page 4 of 4 TFPI8I
SUPPORT SPRINKLER FACE OF ORIENT
CUP CEILING SEAL
BEVELAS
COVER SHOWN
PLATE
RETAINER
ASSEMBLY
CLEAN
ROOM
LIP OF COVER SEAL
RETAINER PLATE
FIGURE 5
OPTIONAL AIR AND DUST SEAL FOR SERIES RFII (TY3551 & TY3504)
When properly installed, there is a
nominal 3/32 inch (2,4 mm) air gap
between the lip of the Cover Plate and
the ceiling, as shown in Figure 2. This
air gap is necessary for proper opera-
tion of the sprinkler. If the ceiling is to
be repainted after the installation of
the Sprinkler, care must be exercised
to ensure that the new paint does NOT
seal off any of the air gap.
Factory painted Cover Plates MUST
NOT be repainted. They should be re-
placed, if necessary, by factory
painted units.
Do not pull the Cover Plate relative to
the Enclosure. Separation may result.
Before closing a fire protection system
main control valve for maintenance
work on the fire protection system that
it controls, permission to shut down the
affected fire protection system must be
obtained from the proper authorities
and all personnel who may be affected
by this action must be notified.
Sprinklers that are found to be leaking
or exhibiting visible signs of corrosion
must be replaced.
Automatic sprinklers must never be
painted, plated, coated or otherwise
altered after leaving the factory. Modi-
fied sprinklers must be replaced.
Sprinklers that have been exposed to
corrosive products of combustion, but
have not operated, should be replaced
if they cannot be completely cleaned
by wiping the sprinkler with a cloth or
by brushing it with a soft bristle brush.
Care must be exercised to avoid dam-
age to the sprinklers - before, during,
and after installation. Sprinklers dam-
aged by dropping, striking, wrench
twist/slippage, or the like, must be re-
placed. Also, replace any sprinkler that
has a cracked bulb or that has lost
liquid from its bulb. (Ref. Installation
Section).
If a sprinkler must be removed, do not
reinstall it or a replacement without
reinstalling the Cover Plate Assembly.
If a Cover Plate Assembly becomes
dislodged during service, replace it im-mediately.
The owner is responsible for the in-
spection, testing, and maintenance of
their fire protection system and de-
vices in compliance with this docu-
ment, as well as with the applicable
standards of the National Fire Protec-
tion Association (e.g., NFPA 25), in
addition to the standards of any other
authorities having jurisdiction. The in-
stalling contractor or sprinkler manu-
facturer should be contacted relative to
any questions.
It is recommended that automatic
sprinkler systems be inspected,
tested, and maintained by a qualified
Inspection Service in accordance with
local requirements and/or national
codes.
Limited
Warranty
Products manufactured by Tyco Fire
Products are warranted solely to the
original Buyer for ten (10) years
against defects in material and work-
manship when paid for and properly
installed and maintained under normal
use and service. This warranty will ex-
pire ten (10) years from date of ship-
ment by Tyco Fire Products. No war-
ranty is given for products or
components manufactured by compa-
nies not affiliated by ownership with
Tyco Fire Products or for products and
components which have been subject
to misuse, improper installation, corro-
sion, or which have not been installed,
maintained, modified or repaired in ac-
cordance with applicable Standards of
the National Fire Protection Associa-
tion, and/or the standards of any other
Authorities Having Jurisdiction. Mate-
rials found by Tyco Fire Products to be
defective shall be either repaired or
replaced, at Tyco Fire Products' sole
option. Tyco Fire Products neither as-
sumes, nor authorizes any person to
assume for it, any other obligation in
connection with the sale of products or
parts of products. Tyco Fire Products
shall not be responsible for sprinkler
system design errors or inaccurate or
incomplete information supplied by
Buyer or Buyer's representatives.
IN NO EVENT SHALL TYCO FIRE
PRODUCTS BE LIABLE, IN CON-
TRACT, TORT, STRICT LIABILITY OR
UNDER ANY OTHER LEGAL THE-
ORY, FOR INCIDENTAL, INDIRECT,
SPECIAL OR CONSEQUENTIAL
DAMAGES, INCLUDING BUT NOT
LIMITED TO LABOR CHARGES, RE-
GARDLESS OF WHETHER TYCO
FIRE PRODUCTS WAS INFORMED
ABOUT THE POSSIBILITY OF SUCH
DAMAGES, AND IN NO EVENT
SHALL TYCO FIRE PRODUCTS' LI-
ABILITY EXCEED AN AMOUNT
EQUAL TO THE SALES PRICE.
Ordering
Procedure
When placing an order, indicate the full
product name. Contact your local dis-
tributor for availability.
Sprinkler Assembly:
Specify: (SIN), (specify temperature
rating) Series RFII Concealed Pen-
dent Sprinkler, P/N (specify).
155F/68C 200F/93C
TV3551 51-790-1-155 51-790-1-200
TY3504 51-796-1-155 51-796-1-200
TY3531 51-792-1-155 51-792-1-200
1Y3505 51-797-1-155 51-797-1-200
Separately Ordered Cover Plate:
Specify: (specify temperature rating)
Series RFII Concealed Cover Plate
with (specify finish), P/N (specify).
135F/57C(a) 165F/74C'(b)
Brass 56-792-1-135 56-792-1165 Bright Brass 56-792-2-135 56-792-2-165 Chrome 56-792-9-135 56-792-9-165 Brushed Chrome 56-792-8-135 56-792-8-165 White 66-792-0-135 56-792-0-165
White (RAL9010)' 56-792-3-135 56-792-3-165 Bright White 56-792-4-135 56-792-4-165 Off White 56-792-5-135 56-792-5-165 Black 56-792-6-135 56-792-6-165
Custom 56-792-X-135 56-792-X-165
For use with 155F/68C sprinklers.
For use with 200F/93C sprinklers.
* Eastern Hemisphere sales only.
Sprinkler Wrench:
Specify: RFll Sprinkler Wrench,
P/N 56-000-1-075.
Air and Dust Seal:
Specify: Air and Dust Seal,
P/N 56-908-1-001.
TYCO FIRE PRODUCTS, 451 North Cannon Avenue, Lansdale, Pennsylvania 19446