HomeMy WebLinkAbout1289 CARLSBAD VILLAGE DR; ; AS100004; Permit11/3/2020 AS1 00004 Permit Data
City of Carlsbad
Sprinkler Permit
1289 CARLSBAD
Job Address:
VILLAGE DR
Permit Type: SPRINK
Parcel No: 1561907006
Lot #: 0
Reference No.:
Permit No: ASI00004
Status: ISSUED
Applied 1/7/2010
Approved: 1/7/2010
Issued: 1/7/2010
PC #: Inspector:
Project Title: DR. MONSON T.I. FIRE SPRINKLER PLAN CHECK & INSPECTIONS
Applicant:
VANGUARD FIRE PROTECTION
1604 LA MIRADA DR #105
SAN MARCOS CA
760-727-8540
Owner:
TRACY DAVID J
1207 CARLSBAD VILLAGE DR #A
CARLSBAD CA
Fees ($) Adcrl Fees(s) Total ($) Balance ($)
130 0 130 0
1/1
tqco Fire & Building
IProducts
Technical Services: Tel: (800) 381-9312 I Fax: (800) 791-5500
Series TY-FRB - 2.8,4.2,5.6, and 8.0 K-factor
and Recessed Pendent Sprinklers
Standard Coverage
Description
The Tyco® Series TY-FRB, 2.8, 4.2,
5.6, and 8.0 K-factor, Upright and Pen-
dent Sprinklers described in this data
sheet are quick response - standard
coverage, decorative 3 mm glass bulb
type spray sprinklers designed for use
in light or ordinary hazard, commercial
occupancies such as banks, hotels,
shopping malls, etc.
The recessed version of the Series
TY-FRB Pendent Sprinkler, where ap-
plicable, is intended for use in areas
with a finished ceiling. It uses either a
two-piece Style 10 (1/2 inch NPT) or
Style 40 (3/4 inch NPT) Recessed Es-
cutcheon with 1/2 inch (12,7 mm) of
recessed adjustment or up to 3/4 inch
(19,1 mm) of total adjustment from the
flush pendent position, or a two-piece
Style 20 (1/2 inch NPT)or Style 30(3/4
inch NPT) Recessed Escutcheon with
1/4 inch (6,4 mm) of recessed adjust-
ment or up to 1/2 inch (12,7 mm) of
total adjustment from the flush pen-
dent position. The adjustment pro-
vided by the Recessed Escutcheon re-
duces the accuracy to which the fixed
pipe drops to the sprinklers must be
cut.
Corrosion resistant coatings, where
applicable, are utilized to extend the
life of copper alloy sprinklers beyond
that which would otherwise be ob-
IMPORTANT
Always refer to Technical Data
Sheet TFP700 for the "INSTALLER
WARNING" that provides cautions
with respect to handling and instal-
lation of sprinkler systems and com-
ponents. Improper handling and in-
stallation can permanently damage
a sprinkler system or its compo-
nents and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
tamed when exposed to corrosive at-
mospheres. Although corrosion resis-
tant coated sprinklers have passed the
standard corrosion tests of the appli-
cable approval agencies, the testing is
not representative of all possible cor-
rosive atmospheres. Consequently, it
is recommended that the end user be
consulted with respect to the suitability
of these coatings for any given corro-
sive environment. The effects of ambi-
ent temperature, concentration of
chemicals, and gas/chemical velocity,
should be considered, as a minimum,
along with the corrosive nature of the
chemical to which the sprinklers will b
exposed. I
An intermediate level versions of th
Series TY-FRB Pendent Sprinkles
are detailed in Technical Data Shet
1FP356, and Sprinkler Guards are 4e-
tailed in Technical Data Sheet TFP7&
WARNINGS
The Series TY-FRB Sprinklers de-
scribed herein must be installed and
maintained in compliance with this
document, as well as with the applica-
ble standards of the National Fire Pro-
tection Association, in addition to the
standards of any other authorities hav-
ing jurisdiction. Failure to do so may
impair the performance of these de-
vices.
The owner is responsible for maintain-
ing their fire protection system and de-
vices in proper operating condition.
The installing contractor or sprinkler
manufacturer should be contacted
with any questions.
Model/Sprinkler
Identification
Numbers
TYII3I - Upright 2.8K, 112"NPT
TY1231 - Pendent 2.8K, 1/2"NPT
TY2131 - Upright 4.2K, 1/2"NPT
TY2231 - Pendent 4.2K, 1/2"NPT
TY3131 - Upright 5.6lc, 1iNI'I
,s7ç- TY3231 - Pendent 5.6K, 1/2"NPT
I' ,f TY413T Upright 8.0K, 314"NPT
TY4231 - Pendent 8.01K, 3/4"NPT
TY4831- Upright 8.0K, 1/2"NPT
TY4931- Pendent 8.0K, 1/2"NPT
WRENC
FLATS
1/2" NPT
7/16"
11,1 mm)
'1OMINAL
MAKE-IN
2-3/16"
(55,6 mm)
6*
Page 2 of 10 TFPI7I
ESCUTCHEON
PLATE SEATING
SURFACE
_F_ _,~_
2-1/4" _
(57,2 mm)
1-9/16'
(39,7 mm)
7/16"(ll,lmm) STYLE 10or2C
NOMINAL RECESSED
MAKE-IN ESCUTCHEON SSU*
DEFLECTOR
6
(11,1mm) I
H
7/16"
_5
NOMINAL I
MAKE-IN
7
2-3/16" "
(55,6 mm)
1/2' NPT SSP DEFLECTOR * 2-7/8" (73,0 mm) DIA. -1
PENDENT RECESSED PENDENT UPRIGHT CROSS SECTION
1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector * Temperature rating is indicated on deflector or adjacent to
2 - Button Assembly 5 - Compression 7 - Bushing orifice seat on frame. Screw
FIGURE 1
QUICK RESPONSE SERIES TY-FRB UPRIGHT (TYII3I) AND PENDENT(TY1231) SPRINKLERS
2.8 K-FACTOR, 1/2 INCH NPT
ESCUTCHEON 7/16" (11,1 mm)
PLATE SEATING NOMINAL
SURFACE 1/2,,
NPT MAKE-IN
2J (S m)
1-1/2"
(38,1 mm)
SSP DEFLECTOR * I---- 2-7/8" (73,0 mm) DIA,
PENDENT RECESSED PENDENT UPRIGHT
STYLE 10 or 20
RECESSED
ESCUTCHEON SSU *
DEFLECTOR
CROSS SECTION
1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector * Temperature rating is indicated on deflector or adjacent to
2 - Button Assembly 5 - Compression orifice seat on frame. Screw
FIGURE 2
QUICK RESPONSE SERIES TY-FRB UPRIGHT (TY2131) AND PENDENT (TY2231) SPRINKLERS
4.2 K-FACTOR, 112 INCH NPT
SSU *
DEFLECTOR
7/16"
:11,1 mm)
'JOMINAL
MAKE-IN
2-3/16"
(55,6 mm)
6*
1/2" NPT
UPRIGHT CROSS SECTION
* Temperature rating is indicated on deflector or adjacent to
orifice seat on frame.
1/2'
(12,7 mm)
NOMINAL
MAKE-IN
2-1/4"
(57,2 mm)
CROSS SECTION
TFPI7I Page 3 of 10
ESCUTCHEON 7/16"(11,1 mm) STYLE 10or20
PLATE SEATING NOMINAL RECESSED 1/2 MAKE-IN SURFACE ESCUTCHEON NPT
2-3/16
(55,6 mm)
I n
(38,1 mm) WRENC
FLATS
2-7/8" DIA. SSP DEFLECTOR* (73,0 mm)
PENDENT RECESSED PENDENT
1 - Frame 3-Sealing 4 - Bulb
2 - Button Assembly 5 - Compression
6- Deflector
Screw
FIGURE 3
QUICK RESPONSE SERIES TY-FRB UPRIGHT (TY3131) AND PENDENT (TY3231) SPRINKLERS
5.6 K-FACTOR, 1/2 INCH NPT
STYLE 30 or 40
RECESSED SSU* ESCUTCHEON DEFLECTOR
WRENCH
FLATS
SSP DEFLECTOR * 2-7/8' (73,0 mm) DIA. 3/4" NPT
PENDENT RECESSED PENDENT UPRIGHT
1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector * Temperature rating is indicated on deflector or adjacent to
2 - Button Assembly 5 - Compression orifice seat on frame. Screw
FIGURE 4
QUICK RESPONSE SERIES TY-FRB UPRIGHT (TY4 131) AND PENDENT (TY4231) SPRINKLERS
8.0 K-FACTOR, 314 INCH NPT
ESCUTCHEON 1/2(12,7 mm)
PLATE SEATING NOMINAL
SURFACE MAKE-IN
2-5/16"
NPT
(58,7 mm)
1-9/16"
(39,7 mm)
.4—
Page 4 of 10 TFP171
7/16" (11,1 mm)
NOMINAL SSU 1/2" MAKE-IN DEFLECTOR
NPT
6
* 6
2-1/4 _ __________
___________ 4 (57,2 mm)
.FLATS
tF
mw 1-9/16" WRENCH 2
I (39,7 mm)
3
1
DEFLECTOR CROSS
PENDENT UPRIGHT SECTION
1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector * Temperature rating is indicated on deflector or adjacent to
2 - Button Assembly 5 - Compression orifice seat on frame. Screw
FIGURE 5
QUICK RESPONSE SERIES TY-FRB UPRIGHT (TY4831) AND PENDENT (TY4931) SPRINKLERS
8.0 K-FACTOR, 1/2 INCH NPT
Technical
Data
Approvals
UL and C-UL Listed.
FM, LPCB, and NYC Approved.
(Refer to Table A and B for complete
approval information including corro-
sion resistant status.)
Maximum Working Pressure
Refer to Table C.
Discharge Coefficient
K = 2.8 GPM/psi1l2 (40,3 LPM/barl'2)
K = 4.2 GPM/p5i112 (60,5 LPM/barl'2)
K = 5.6 GPM/p5i112 (80,6 LPM/bar1l2)
K = 8.0 GPM/psi1I2 (115,2 LPM/barll2)
Temperature Ratings
Refer to Table A and B
Finishes
Sprinkler: Refer to Table A and B.
Recessed Escutcheon: White Coated,
Chrome Plated, or Brass Plated.
Physical Characteristics
Frame .............Bronze
Button .........Brass/Copper
Sealing Assembly ..........
Beryllium Nickel w/Teflont
Bulb ...............Glass
Compression Screw .....Bronze
Deflector .......Copper/Bronze
Bushing (K=2.8) .......Bronze
Operation
The glass Bulb contains a fluid which
expands when exposed to heat. When
the rated temperature is reached, the
fluid expands sufficiently to shatter the
glass Bulb, allowing the sprinkler to
activate and water to flow.
Design
Criteria
The Series TY-FRB Pendent and Up-
right Sprinklers are intended for fire
protection systems designed in ac-
cordance with the standard installation
rules recognized by the applicable
Listing or Approval agency (e.g., UL
Listing is based on the requirements of
NFPA 13, and FM Approval is based
on the requirements of FM's Loss Pre-
vention Data Sheets ). Only the Style
10, 20, 30, or 40 Recessed Escutch-
eon, as applicable, is to be used for
recessed pendent installations.
Page 5 of 10 TFPI7I
SPRINKLER FINISH (See Note 7)
K TYPE TEMP. BULB
LIQUID
NATURAL
BRASS
I CHROME
PLATED
I WHITE*
IPOLYESTER
2.8
PENDENT
(TY1231)
and
UPRIGHT
(TYII3I)
135°F/57°C Orange
1,2,3,5 155°F168°C Red
175°F/79°C Yellow
20OF/93°C Green
286°F/141°C Blue
1/2"
NPT RECESSED
PENDENT
(TY1231)*
Figure 6
135°F/57°C Orange
1, 2, 5
155°F/68°C Red
175°F/79°C Yellow
2OOF/93°C Green
RECESSED
PENDENT
(TY1231)
Figure 7
135°F/57°C Orange
155°F/68°C Red
175°F/79°C Yellow
20OFI93°C Green
4.2
1/2"
NPT
PENDENT
(TY2231)
and
UPRIGHT
(TY2131)
135°F/57°C Orange
1,2
155°F/68°C Red
175°F/79°C Yellow
200°F/93°C Green
286F/141°C Blue
RECESSED
PENDENT
(TY2231)*
Figure 8
135F/57°C Orange
155°F/68°C Red
175°F/79°C Yellow
200°F/93°C Green
RECESSED
PENDENT
(TY2231)
Figure 9
135F/57°C Orange
155°F/68°C Red
175°F/79°C Yellow
200°F/93C Green
NOTES:
Listed by Underwriters Laboratories, Inc. (UL) as Quick Response Sprinklers.
Listed by Underwriters Laboratories, Inc. for use in Canada (C-UL) as Quick Re-
sponse Sprinklers.
Approved by Factory Mutual Research Corporation (FM) as Quick Response Sprin-
klers.
5. Approved by the City of New York under MEA 354-01-E.
7. Where Polyester Coated Sprinklers are noted to be UL and C-UL Listed, the sprin-
klers are UL and C-UL Listed as Corrosion Resistant Sprinklers.
* Installed with Style 10 (1/2" NPT) or Style 40 (3/4" NPT) 3/4" Total Adjustment
Recessed Escutcheon, as applicable.
** Installed with Style 20 (1/2" NPT) or Style 30 (3/4" NPT) 1/2" Total Adjustment
Recessed Escutcheon, as applicable.
Frame and Deflector only. Listings and approvals apply to color (Special Order).
N/A: Not Available
TABLE A
LABORATORY LISTINGS AND APPROVALS
2,8 AND 4.2 K-FACTOR SPRINKLERS
Page 6 of 10 TFPI7I
SPRINKLER FINISH (See Note 8)
K TYPE TEMP. BULB
LIQUID
NATURAL
BRASS
I CHROME
PLATED
WHITE
1POLYESTER
LEAD
COATED
5.6
PENDENT
(TY3231)
and
UPRIGHT
(TY3131)
135°F/57°C Orange
1,2,3,4,5,6,7 1,2,3,5 l55F/68°C Red
175°F/79C Yellow
200°F/93°C Green
286°F/141°C Blue
1/2"
NPT RECESSED
PENDENT
(Y3231)*
Figure 10
135°F/57°C Orange
1, 2, 4, 5 N/A 155°F/68°C Red
175°F/79°C Yellow
200°F/93°C Green
RECESSED
PENDENT
(TY3231)**
Figure 11
135°F/57C Orange
1, 2, 3,4, 5 N/A 155°F/68*C Red
175°F/79°C Yellow
200F/93°C Green
8.0
PENDENT
(TY4231)
and
UPRIGHT
(TY4131)
135F/57C Orange
1,2, 3,4,5,6,7
1,2,5
155°F/68°C Red
175°F/79°C Yellow
200F/93°C Green
286°F/141°C Blue
3/4,,
NPT RECESSED
PENDENT
(TY4231)*
Figure 12
135F/57°C Green
1,2,4,5 N/A
155F/68°C Orange
175°F/79°C Red
200°F193°C Yellow
135°F/57°C Orange
1, 2, 3,4, 5 N/A
RECESSED
PENDENT
(TY4231)**
Figure 13
155°F/68°C Red
175°F/79°C Yellow
200°F/93°C Green
8.0
1/2"
NPT
PENDENT
(TY4931)
and
UPRIGHT
(TY4831)
135F/57°C Orange
1,2,4, 5,6
1,2,5 155°F/68°C Red
175°F/79C Yellow
200°F/93°C Green
286F/141°C Blue
NOTES:
Listed by Underwriters Laboratories, Inc. (UL) as Quick Response Sprinklers.
Listed by Underwriters Laboratories, Inc. for use in Canada (C-UL) as Quick Response Sprinklers.
Approved by Factory Mutual Research Corporation (FM) as Quick Response Sprinklers.
Approved by the Loss Prevention Certification Board (LPCB Ref. No. 007k/04) as Quick Response Sprinklers; however, the
LPCB does not rate the thermal sensitivity of recessed sprinklers.
Approved by the City of New York under MEA 354-01-E.
VdS Approved (For details contact Tyco Fire & Building Products, Enschede, Netherlands, Tel. 31-53-428-4444/Fax 31-53-428-3377).
Approved by the Loss Prevention Certification Board (LPCB Ref. No. 094a/06) as Quick Response Sprinklers.
Where Polyester Coated and Lead Coated Sprinklers are noted to be UL and C-UL Listed, the sprinklers are UL and C-UL Listed as
Corrosion Resistant Sprinklers. Where Lead Coated Sprinklers are noted to be FM Approved, the sprinklers are FM Approved as a
Corrosion Resistant Sprinklers.
* Installed with Style 10 (1/2" NPT) or Style 40 (3/4" NPT) 3/4" Total Adjustment Recessed Escutcheon, as applicable.
** Installed with Style 20 (1/2" NPT) or Style 30 (3/4" NPT) 1/2" Total Adjustment Recessed Escutcheon, as applicable.
Frame and Deflector only. Listings and approvals apply to color (Special Order).
N/A: Not Available
TABLE B
LABORATORY LISTINGS AND APPROVALS
5.6 AND 8.0 K-FACTOR SPRINKLERS
TFPI7I Page 7 of 10
SPRINKLER FINISH
K TYPE NATURAL CHROME WHITE LEAD
BRASS PLATED
I
POLYESTER
I
COATED
PENDENT (TY3231)
and
2.8 UPRIGHT (TY3131) 175 PSI (12,1 BAR) N/A
1/2' RECESSED PENDENT NPT (TY323)
PENDENT (TY4231)
and
4.2 UPRIGHT (TY4131) 175 PSI (12,1 BAR) N/A
RECESSED PENDENT NPT (TY4231)
PENDENT (TY3231)
and 250 PSI (17,2 BAR) 175 PSI (12,1 BAR)
5.6 UPRIGHT (TY3131) OR
1/2" 175 PSI (12,1 BAR) RECESSED PENDENT . NPT (TY3231) (SEE NOTE 1) N/A
PENDENT (1Y4231)
and 175 PSI (12,1 BAR) 175 PSI (12,1 BAR)
8.0 UPRIGHT (TY4131)
RECESSED PENDENT NPT (TY4231) N/A
8.0 PENDENT (TY4931)
1/2" and 175 PSI (12,1 BAR) 175 PSI (12,1 BAR)
NPT UPRIGHT (TY4831)
NOTES:
1. The maximum working pressure of 250 psi (17,2 bar) only applies to the Listing by Underwriters Laboratories Inc. (UL); the Listing by
Underwriters Laboratories, Inc. for use in Canada (C-UL); and , the Approval by the City of New York.
TABLE C, MAXIMUM WORKING PRESSURE
Installation
The Series TY-FRB Sprinklers must
be installed in accordance with the fol-
lowing instructions:
NOTES
Do not install any bulb type sprinkler if
the bulb is cracked or there is a loss of
liquid from the bulb. With the sprinkler
held horizontally, a small air bubble
should be present. The diameter of the
air bubble is approximately 1/16 inch
(1,6 mm) for the 135°F/57°C to 3/32
inch (2,4 mm) for the 286°F/141°C
temperature ratings.
A leak tight 1/2 inch NPTsprinklerjoint
should be obtained with a torque of 7
to 14 ft.lbs. (9,5 to 19,0 Nm). A maxi-
mum of 21 ft. lbs. (28,5 Nm) of torque
may be used to install sprinklers with
1/2 NPT connections. A leak tight 3/4
inch NPT sprinkler joint should be ob-
tained with a torque of 10 to 20 ft.lbs.
(13,4 to 26,8 Nm). A maximum of 30
ft.lbs. (40,7 Nm) of torque is to be used
to install sprinklers with 3/4 NPT con-
nections. Higher levels of torque may
distort the sprinkler inlet and cause
leakage or impairment of the sprinkler.
Do not attempt to make-up for insuffi-
cient adjustment in the escutcheon
plate by under- or over-tightening the
sprinkler. Readjust the position of the
sprinkler fitting to suit.
The Series TY-FRB Pendent and Up-
right Sprinklers must be installed in
accordance with the following instruc-
tions.
Step 1. Pendent sprinklers are to be
installed in the pendent position, and
upright sprinklers are to be installed in
the upright position.
Step 2. With pipe thread sealant ap-
plied to the pipe threads, hand tighten
the sprinkler into the sprinkler fitting.
Step 3. Tighten the sprinkler into the
sprinkler fitting using only the W-Type
6 Sprinkler Wrench (Ref. Figure 14).
With reference to Figures 1, 2, 3, 4,
and 5, the W-Type 6 Sprinkler Wrench
is to be applied to the sprinkler wrench
flats.
The Series TY-FRB Recessed Pen-
dent Sprinklers must be installed in
accordance with the following instruc-
tions.
Step A. After installing the Style 10.
20, 30, or 40 Mounting Plate, as appli-
cable, over the sprinkler threads and
with pipe thread sealant applied to the
pipe threads, hand tighten the sprin-
kler into the sprinkler fitting.
Step B. Tighten the sprinkler into the
sprinkler fitting using only the W-Type
7 Recessed Sprinkler Wrench (Ref.
Figure 15). With reference to Figure 1,
2, 3, and 4, the W-Type 7 Recessed
1/2±1/8"
(12,7±3,2 mm)
5/8±1/4'
(15,9±6,4 mm)
FACE OF
SPRINKLER
FITTING
MOUNTING
SURFACE
FACE OF
SPRINKLER
FITTING
t \ -
MOUNTING
SURFACE
CLOSURE SERIES
TY-FRB CLOSURE SERIES
TY-FRB
2-7/8" DIA. - I
(73,0 mm) 3/4(19,1 mm)
2-1/4" DIA. 1/4" (6,4 mm)
(57,2 mm) MOUNTING c 1/8"
3,2 mm)
J
1-5/16" (33,3 mm)[
13/16(20,6mm)
2-7/8" DIA.
(73,0 mm) 1/2" (12,7 mm)
2-1/4' DIA. 1/4 (6,4 mm)
(57,2 mm)
71
MOUNTING
IA.r
1/8
(32mm) I
1-5/16" (33,3 mm)
1-1/16" (27,0 mm)
Page 8 of 10 TFPI7I
FIGURE 6
SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT
STYLE 10 RECESSED ESCUTCHEON
2.8 K-FACTOR, 1/2 INCH NPT
2-7/8" DIA.
(73,0 mm) 3/4(19,1 mm)
2-1/4" DIA. 1/4(6,4 mm)
(57,2 mm) MOUNTING
DI AT
1/8"
(3,2 mm)
MOUNTING
SURFACE
CLOSURE SERIES 1-1/4"(31,8 mm)
3/4" (19,1 mm)
FIGURE 8
SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT
STYLE 10 RECESSED ESCUTCHEON
4.2 K-FACTOR, 1/2 INCH NPT
FIGURE 7
SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 20 RECESSED ESCUTCHEON
2.8 K-FACTOR, 1/2 INCH NPT
- 2-7/8" DIA. -
(73,0 mm) 1/2±1/8" 1/2" (12,7
E (12,7±3,2 mm) - 2-1/4" DIA. 1/4" (6,4 mm) I
FACE OFqR
(572 mm) MOUNTING
1/8"
SPRINKLE PLATE I FITTING 1 M(3,2 mm) I
MOUNTIN
SURFACESERIES
1-1/4" (31,8 mm) CLOSURE TYFRB 1" (25,4 mm)
FIGURE 9
SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 20 RECESSED ESCUTCHEON
4.2 K-FACTOR, 1/2 INCH NPT
5/8±1/4"
(15,9±6,4 mm)
FACE OF
SPRINKLER
FITTING
Sprinkler Wrench is to be applied to
the sprinkler wrench flats.
Step C. After the ceiling has been in-
stalled or the finish coat has been ap-
plied, slide on the Style 10, 20, 30, or
40 Closure over the Series TY-FRB
Sprinkler and push the Closure over
the Mounting Plate until its flange
comes in contact with the ceiling.
Care and
Maintenance
The Series TY-FRB Sprinklers must
be maintained and serviced in accord-
ance with the following instructions:
NOTES
Before closing a fire protection system
main control valve for maintenance
work on the fire protection system that
it controls, permission to shutdown the
affected fire protection system must be
obtained from the proper authorities
and all personnel who maybe affected
by this action must be notified.
The owner must assure that the sprin-
klers are not used for hanging of any
objects; otherwise, non-operation in
the event of a fire or inadvertent opera-
tion may result.
Absence of an escutcheon, which is
used to cover a clearance hole, may
delay the time to sprinkler operation in
a fire situation.
Sprinklers that are found to be leaking
or exhibiting visible signs of corrosion
must be replaced.
Automatic sprinklers must never be
painted, plated, coated or otherwise
altered after leaving the factory. Modi-
fied sprinklers must be replaced.
Sprinklers that have been exposed to
corrosive products of combustion, but
have not operated, should be replaced
if they cannot be completely cleaned
by wiping the sprinkler with a cloth or
by brushing it with a soft bristle brush.
Care must be exercised to avoid dam-
age to the sprinklers - before, during,
and after installation. Sprinklers dam-
aged by dropping, striking, wrench
twist/slippage, or the like, must be re-
placed. Also, replace any sprinkler
that has a cracked bulb or that has lost
liquid from its bulb. (Ref. Installation
Section).
Frequent visual inspections are rec-
ommended to be initially performed for
corrosion resistant coated sprinklers,
after the installation has been corn-
2-7/8" DIA
(73,0 mm) 1/2(12,7mm)
2-1/4" DIA. 1/4(6,4 mm)
(57,2 mm) MOUNTING
1/2±1/8"
(12,7±3,2 mm)
FACE OF
SPRINKLER
FITTING
2-7/8" DIA.
(73,0 mm) 3/4(19,1 mm)
2-1/4" DIA. 1/4(6,4mm)
(57,2 mm) MOUNTING
DI ATC
5/8±1/4"
(15,9±6,4 mm)
FACE OF
SPRINKLER
FITTING
TFPI7I
- 2-7/8" DIA.
5/8±1/4" (73,0 mm) 3/4" (19,1 mm)
SPRINKLE*R 1 PLATE
L_57'2 mm)
(15,9±6,4 mm) 2-1/4" DIA. 1/4' (6,4 mm)
FACE OF MOUNTING
I
1/8'
FITTING
(3,2
MOUNTIN
SURFACESERIES
1-1/4' (31,8 mm) CLOSURE 1YFRB 3/4" (19,1 mm)
FIGURE 10
SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT
STYLE 10 RECESSED ESCUTCHEON
5.6 K-FACTOR, 1/2 INCH NPT
Page 9 of 10
(3,2 mm) I
t \ -
MOUNTING
SURFACE
CLOSURE SERIES 1-1/4" (31,8 mm)
1" (25,4 mm)
FIGURE 11
SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 20 RECESSED ESCUTCHEON
5.6 K-FACTOR, 1/2 INCH NPT
2-7/8" DIA.
1/2±1/8" (73,0 mm) 1/2(12,7 mm)
(12,7±3,2 mm) 2-1/4" DIA. 1/4"(6,4 mm)
/ T
FACE OF
(57,2 mm)
1/8"
SPRINKLER PLA
FITTING
(3.2 mm
MOUNTING
TE
MOUNTING
MOUNTING SURFACE
SURFACE
CLOSURE SERIES 1-5/16" (33,3 mm) CLOSURE SERIES .1-5/16"(33,3 mm)
TY-FRB 13/16" (20,6 mm) TY-FRB 1-1/16"(27,0 mm)
FIGURE 12
SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT
STYLE 40 RECESSED ESCUTCHEON
8.0 K-FACTOR, 3/4 INCH NPT
FIGURE 13
SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 30 RECESSED ESCUTCHEON
8.0 K-FACTOR, 3/4 INCH NPT
pleted, to verify the integrity of the cor-
rosion resistant coating. Thereafter,
annual inspections per NFPA 25
should suffice; however, instead of in-
specting from the floor level, a random
sampling of close-up visual inspec-
tions should be made, so as to better
determine the exact sprinkler condi-
tion and the long term integrity of the
corrosion resistant coating, as it may
be affected by the corrosive conditions
present.
The owner is responsible for the in-
spection, testing, and maintenance of
their fire protection system and de-
vices in compliance with this docu-
ment, as well as with the applicable
standards of the National Fire Protec-
tion Association (e.g., NFPA 25), in
addition to the standards of any other
authorities having jurisdiction. The in-
stalling contractor or sprinkler manu-
WRENCH RECESS
(END "A" USED FOR
1/2" NPT MODELS)
WRENCH RECESS
(END "B" USED FOR
3/4" NPT MODELS)
FIGURE 14
W-TYPE 6 SPRINKLER
WRENCH
facturer should be contacted relative
to any questions.
It is recommended that automatic
sprinkler systems be inspected,
tested, and maintained by a qualified
WRENCH
RECESS
PUSH WRENCH
IN TO ENSURE
ENGAGEMENT
WITH SPRINKLER
WRENCHING AREA
FIGURE 15
W-TYPE 7 RECESSED
SPRINKLER WRENCH
Inspection Service in accordance with
local requirements and/or national
codes.
Page 10 of 10 TFPI 71
P/N 57-XXX-X-XXX
I_ MODEUSIN
330 2.8K UPRIGHT (1/2"NPT) TY1131
331 2.8K PENDENT (1/2"NPT) TY1231
340 4.2K UPRIGHT (1/2"NPT) TY2131
341 4.2K PENDENT (1/2"NPT) 1Y2231
370 5.6K UPRIGHT (1/2"NPT) TY3131
371 5.6K PENDENT (1/2"NPT) TY3231
390 8.0K UPRIGHT (314°NPT) TY4131
391 8.0K PENDENT (3/4"NPT) TY4231
360 8.0K UPRIGHT (1/2"NPT) 1Y4831*
361 1 8.OK PENDENT (1/2°NPT) TY4931*
I
11
I
135
155
175
200
286
RATING
SPRINKLER
1 NATURAL BRASS 155°F/68°C
4 WHITE POLYESTER 175°F179°C
3 WHITE (RAL9010)* 200°F/93°C
9 CHROME PLATED 28&F/141°C
7 LEAD COATED
* Eastern Hemisphere sales only.
TABLE D
PART NUMBER SELECTION
SERIES TY-FRB PENDENT AND UPRIGHT SPRINKLERS
Limited
Warranty
Products manufactured by Tyco Fire &
Building Products (TFBP) are war-
ranted solely to the original Buyer for
ten (10) years against defects in mate-
rial and workmanship when paid for
and properly installed and maintained
under normal use and service. This
warranty will expire ten (10) years
from date of shipment by TFBP. No
warranty is given for products or com-
ponents manufactured by companies
not affiliated by ownership with TFBP
or for products and components which
have been subject to misuse, improper
installation, corrosion, or which have
not been installed, maintained, modi-
fied or repaired in accordance with ap-
plicable Standards of the National Fire
Protection Association, and/or the
standards of any other Authorities
Having Jurisdiction. Materials found
by TFBP to be defective shall be either
repaired or replaced, at TFBP's sole
option. TFBP neither assumes, nor
authorizes any person to assume for it,
any other obligation in connection with
the sale of products or parts of prod-
ucts. TFBP shall not be responsible for
sprinkler system design errors or inac-
curate or incomplete information sup-
plied by Buyer or Buyer's repre-
sentatives.
In no event shall TFBP be liable, in
contract, tort, strict liability or under
any other legal theory, for incidental,
indirect, special or consequential dam-
ages, including but not limited to labor
charges, regardless of whether TFBP
was informed about the possibility of
such damages, and in no event shall
TFBP's liability exceed an amount
equal to the sales price.
This limited warranty sets forth the ex-
clusive remedy for claims based on
failure of or defect in products, materi-
als or components, whether the claim
is made in contract, tort, strict liability
or any other legal theory.
This warranty will apply to the full ex-
tent permitted by law. The invalidity, in
whole or part, of any portion of this
warranty will not affect the remainder.
Ordering
Procedure
When placing an order, indicate the
full product name. Refer to the Price
List for complete listing of Part Num-
bers.
Contact your local distributor for avail-
ability.
Sprinkler Assemblies with NPT
Thread Connections:
Specify: (Specify Model/SIN), Quick
Response, (specify K-factor), (specify
temperature rating), Series TY-FRB
(specify Pendent or Upright) Sprinkler
with (specify type of finish or coating),
P/N (specify from Table D).
Recessed Escutcheon:
Specify: Style (10, 20, 30, or 40) Re-
cessed Escutcheon with (specify*) fin-
ish, PIN (specify*).
* Refer to Technical Data Sheet TFP770.
Sprinkler Wrench:
Specify: W-Type 6 Sprinkler Wrench,
P/N 56-000-6-387.
Specify: W-Type 7 Sprinkler Wrench,
PIN 56-850-4-001.