FIRE FLOW ANALYSIS FOR:
CARLSBAD OAKS LOT 13
Prepared For:
SR Communications
LAND PLANNING ENGINEERING SURVEYING
440 STATE PLACE, ESCONDIDO, CA 92029
PH (760)745-8118 FX (760)745-1890
Excel Reference No.: 14-101
Date:
April 8, 2016
ASi 60127
2864 WHIPTAIL LP
I
I
PURPOSE/PROJECT DESCRIPTION
I This water system analysis was conducted to check the capacities of the proposed on site
private underground fire distribution system and potable water supply lines that will serve the
proposed Carlsbad Oaks Lot 13. A 12" lateral Polyvinyl chloride (PVC) connection will service the
onsite fire system, originating from an existing 16" water line running below Whiptail Loop East.
I The fire line connection will utilize a 10" double detector check valve (DDCV). The connection
services an onsite looped fire system consisting of a 10" line that will serve the fire sprinklers
I
and eight separate hydrants around the site.
CRITERIA AND METHODOLOGY
I The modeling of the onsite fire service lines was completed using the EPANET 2.0 program
(EPANET). Usage of the water and sewer plans provided the scaled distances for the project.
The schematic used in EPANET can be found on Attachment 1.
Head Loss Across Fittings
I Minor loses encountered in the Ductile Iron Pipe (DIP) fittings along the pipelines were
neglected in the model (i.e. elbows, tees, etc.). The head loss (HL) across the backflow
apparatus was addressed and modeled using the method described below.
I The Watts 10" double check detector assembly (DCDA) was modeled as a general purpose valve
(GPV) in series with a check valve. The HL curve can be found on the specification sheet for the
I Watts DCDA on Attachment 2. This information was used to develop Figure 1 below, which
displays the HL curve created for usage in EPANET to model the flow within the system.
Additional information for the proposed backflow device can be found on Attachment 2.
I
I
I
I
I
I
I
I
I
I
Curve Editor
Curve ID Description
110DDCV jWattsDDCV10
Curve Type Equation
Flow T~dloss 18-
1000 5.777 16-
HEADLOSS jj
3000
14- 1500 6.920
2000 9.242
2500 11.55 8-
16.174 6-
0 1,000 2,000 3000
3500 18.485 - .!ow (GPM) -
Load... ] -
Save... OK Cancel
-
help
Fig. 1: HL Curve for the 10" DCDA
Roughness Coefficients
A Hazen-Williams roughness coefficient value of 150 was used for the PVC pipes in the system.
Modeled Demand Flows
To ensure the onsite hydraulics can supply adequate flow to the system during a fire event,
Excel Engineering tested the main scenario. With the fire flow system criteria provided by the
Fire Marshall, the following test scenarios were conducted:
Scenario 1— For this scenario, a demand of 3,500 gpm was supplied to the hydrant
furthest from the building connection, and no flow was provided to either of the
buildings.
Tie-In Pressures Available
Existing flow and pressure data from the public system in Whiptail Loop East was taken from a
flow analysis performed by the City of Carlsbad Fire Department (CCFD) on 04/04/2016. To
model this scenario in EPANET the pressure available was modeled as a reservoir with a total
head equivalent to the Static Pressures given in the analysis provided by the City. This pressure
test data can be found on Attachment 3 to this report, and is summarized in the table below.
I
I
I 2
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
1
I
I
I
I
I
I
I
I
I
I
I
I
I
I
Table 1: CCFD Flow Test Results
Hydrant NO Static Static Elevation (ft) Total Head Reservoir
Pressure (psi) Pressure Available Number
(ft of head) (ft)
H61680 132 305 400 705 1
CALCULATONS AND CONCLUSIONS
This performed analysis confirms that the underground fire distribution system will be adequate
to provide fire flows to the site for Scenario 2 in accordance with the following requirements:
Minimum residual pressure for the project shall be 20 pounds per square inch (psi)
during fire flow demand.
Pipe velocities shall not exceed 10 feet per second (fps).
The velocity and pressure requirements were met for this project.
Scenario 1
For this scenario, the highest velocity found in the system was in multiple pipes.
This velocity was recorded as 9.93 fps. See Attachment 4.
Minimum Pressure - For this scenario, the minimum pressure in the system is
found in Junction 20. The recorded pressure was 102.3 psi. See Attachment 5.
A velocity of 39.7 fps was found in the hydrant (Pipe 19) for this scenario.
3
I
I Attachment I - Site Schematic
I
Junction #19
3,500 gpm to this hydrant
22 22
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
10
Pressure
100.00
110.00
120.00
130.00
psi
Velocil
0.00
5.00
7.50
10.00
fps
I 22 20
Attachment 1.1 - Site Schematic
Day 1, 12:
EPANET2 Page 1
I
I
Job Name Contractor
1 Job Location Approval
ES-757DCDA/757NDCDA
Engineer
I Approval
Series 757DCDA,
757NDCDA
Double Check Detector Assemblies
Sizes: 21h" -10" (65 - 250mm)
Series 757DCDA, 757NDCDA Double Check Detector
Assemblies are used to prevent backflow of non-health hazard
pollutants that are objectionable but not toxic, from entering
the potable water supply system. The 757DCDA, 757NDCDA
may be installed under continuous pressure service and may
be subjected to backpressure and backsiphonage. Series
757DCDA, 757NDCDA is used primarily on fire line sprinkler
systems when it is necessary to monitor unauthorized use of
water.
' Features
Extremely compact design
70% Lighter than traditional designs
I . 304 (Schedule 40) stainless steel housing & sleeve
Groove fittings allow integral pipeline adjustment
Patented tn-link spring check provides lowest pressure loss
I . Unmatched ease of serviceability
Available with grooved butterfly valve shutoffs
May be used for horizontal, vertical or N pattern installations
I . Replaceable check disc rubber
Specifications
The Double Check Detector Assembly shall consist of two I independent tn-link check modules within a single housing,
sleeve access port, four test cocks and two drip tight shutoff
valves. Tr-link checks shall be removable and serviceable, with-
out the use of special tools. The housing shall be constructed
of 304 Schedule 40 stainless steel pipe with groove end con-
nections. Tr-link checks shall have reversible elastomer discs
and in operation shall produce drip tight closure against reverse I flow caused by backpressure or backsiphonage. The bypass
assembly shall consist of a meter, which registers in either gal-
lon or cubic measurement, a double check backflow assem-
bly and required test cocks. Assembly shall be a Watts Series
757DCDA, 757NDCDA.
Contractor's P.O. No.
Representative
757DCDAOSY
757DCDABFG
757NDCDAOSY
NOTICE
The information contained herein is not intended to replace the
full product installation and safety information available or the
experience of a trained product installer. You are required to
thoroughly read all installation instructions and product safety
information before beginning the installation of this product.
I
I
I
I
I
I Watts product specifications in U.S. customary units and metric are approximate and are provided for reference only. For precise measurements,
please contact Watts Technical Service. Watts reserves the right to change or modify product design, construction, specifications, or materials with-
out prior notice and without incurring any obligation to make such changes and modifications on Watts products previously or subsequently sold. M~WAM
I
SIZE (ON)DIMENSIONS WEIG HT
in. mm
A
in. mm
C
in. mm
D
in. mm
6
in. mm in.
H
mm
I
in. mm
J
in. mm
P
in. mm
757DCDABFG
lbs. kgs.
757NDCDA BFG
lbs. kgs.
2½ 65 27% 705 8 203 3½ 89 29/i 759 21½ 546 1415/16 379 8"/16 223 13 330 70 32 78 35
3 80 28¼ 718 85A6 211 311A6 94 301Vis 779 22¼ 565 157As 392 93A6 233 131/2 343 68 31 81 37
4 100 29 737 815As 227 311A6 94 1 31'5/is 811 1 231/2 597 1 161/4 412 1 915A6 252 1 14 356 75 34 1 98 44
6 150 1 361/2 927 10 254 5 127 1 433A6 1097 1 331/4 845 1911A6 500 1 131A6 332 1 141/2 368 131 59 171 78
8 200 1 42% 1086 121/4 311 6½ 165 1 511/is 1297 1 40½ 1019 235As 592 1 15Wis 399 1 183As 462 275 125 1 351 159
Noryl® is a registered trademark of General Electric Company.
I
I
I
I
757DCDABFG, 757NDCDABFG
Available Models
Suffix:
OSY - ULJFM outside stem and yoke resilient
seated gate valves
BFG - UL/FM grooved gear operated butterfly valves
with tamper switch
5y FxG - Flanged inlet gate connection and grooved outlet
gate connection
*OSY GxF - Grooved inlet gate connection and flanged outlet
gate connection
*y GxG - Grooved inlet gate connection and grooved outlet
gate connection
Available with grooved NRS gate valves - consult factory*
Post indicator plate and operating nut available - consult factory*
*Consult factory for dimensions
Materials
Housing & Sleeve: 304 (Schedule 40) Stainless Steel
Elastomers: EPDM, Silicone and Buna-N
Tr-link Checks: Noryl®, Stainless Steel
Check Discs: Reversible Silicone or EPDM
Test Cocks: Bronze Body Nickel Plated
Pins & Fasteners: 300 Series Stainless Steel
Springs: Stainless Steel
Pressure - Temperature
Temperature Range: 33°F - 140°F (0.5°C - 60°C)
Maximum Working Pressure: 175p5i (12.1 bar)
Approvals - Standards
'Approved by the Foundation for Cross-Connection Control
and Hydraulic Research at The University of Southern
California (FCCCHR-USC)
I
I
I
I
I
I
Dimensions - Weight
I I1
C (open)
H
-
A ....................
757DCDA, 757NDCDA
**
®C ®c®us4> US Approved
1048 B64.5 BFG & OSY Only)
UNIN jIiI 150, IijI
I
I
Fj
1
SIZE (DN) DIMENSIONS WEIGHT
in. mm
A
in. mm
C (OSY)
in. mm
D
in. mm
6
in. mm
H
in. mm
I
in. mm
J
in. mm
P
in. mm
757DCDA
lbs. kgs.
757NDCDA
lbs. kgs.
21/2 65 30% 781 16/s 416 31/2 89 29Vis 738 211/2 546 15½ 393 813A6 223 133A6 335 139 63 147 67
380 31% 806 18/8 479 31A6 94 3Q1/4 768 22¼ 565 171/8 435 9/is 233 141/2 368 159 72 172 78
4100 33% 857 22/4 578 4 102 33 838 231/2 597 181/2 470 9's/is 252 153A6 386 175 79 198 90
_6150 1 431/2 1105 1 301/8 765 51/2 140 443/4 1137 1 331/4 845 1 233A6 589 131A6 332 19 483 309 140 350 159
8200 1 49% 1264 1 373/4 959 611A6 170 54½ 1375 1 40½ 1019 1 272/16 697 1 1511A8 399 21 '/16 538 494 224 569 258
10 250 1 573/4 1467 1 453/4 1162 1 8/l6 208 66 1676 1 49/2 1257 1 321/2 826 1 175A6 440 24 610 795 361 965 438
I
I
I
I
Capacity
Series 757DCDA, 757NDCDA flow curves as tested by
Underwriters Laboratory.
Flow characteristics collected using butterfly shutoff valves
Horizontal _____ Vertical ------N - Pattern
2½" (65mm)
PSI Service Flow Rated Flow *UL Rated Flew
12 N
10 v
14
50 100 150 200 250 300 350 gpm
0 190 380 570 760 950 1140 1330 1pm
7.5 15 fps
Flow capacity chart identifies valve performance
based upon rated water velocity up to 25fps
Service Flow is typically determined by a rated
velocity of 7.5fps based upon schedule 40 pipe.
Rated Flow identifies maximum continuous duty
performance determined by AWWA.
UL Flow Rate is 150% of Rated Flow and is not
recommended for continuous duty.
AWWA Manual M22 [Appendix C] recommends
that the maximum water velocity in services be
not more than lofps.
6" (150mm)
)SI Service Flow Rated Flow 111. Rated Flow 12 1 - - N
-
uu
8 1 V
1 -
q 12 _
300 600 900 1200 1500 gpm
0 1140 2280 3420 4560 5700 1pm
7.5 12 fps
I
I
I
I
I
I
3" (80mm) 8" (200mm) Sl Service Flow Rated Flew lii Rated Row psi Service Flow Rated Flow UL Rated Flow 12 12 N
10 H 10 H
_ __ _ i 41 hfl 0 ioo 200 300 400 500 gpm 0 500 1000 1500 2000 2500 gpm
0 380 760 1140 1520 1900 1pm 0 1900 3800 5700 7600 9500 1pm
7.5 15 fps 7.5 10 fps
I
I
LI
4" (100mm)
PSI Service Row Rated Flew *UL Rated Raw
24
N 20
lS j H
12
0 100 200 300 400 500 600 700 800 gpm
0 380 760 1140 1520 1900 2280 2660 3040 1pm
7.5 13 fps
I
I
I
I
Si 10" (250mm) p Service Flow Rated Row IlL Rated Raw 12 --------- -
10 N
d q T
500 1000 1500 2000 2500 3000 3500 gpm
1900 3800 5700 7600 9500 11400 13300 1pm
7.5 10 fps
I
IIIIIIIIIIIIIIIIIIIIIJIMARM
Inquire with governing authorities for local installation
requirements
It is illegal to use this product in any plumbing system providing water
for human consumption, such as drinking or dishwashing, in the United
States. Before installing standard material product, consult your local
water authority, building and plumbing codes.
I
I
LI
I
1
I
I
I
I
J
I
I
ill
1
I
I
I
I
1 \WATFS®
I A Watts Water Technologies Company USA: Tel: (978) 689-6066 • Fax: (978) 975-8350 • Watts.com
Canada: Tel: (905) 332-4090 • Fax: (905) 332-7068 • Watts.ca
Latin America: Tel: (52) 81-1001-8600 • Fax: (52) 81-8000-7091 • Watts.com
ES-757DCDA_757NDCDA 1503 0 2015 Watts
u
0
CARLSBAD FIRE DEPARTMENT
Fire Prevention Division
1635 Faraday Avenue - Carlsbad, CA 92008
760.602.4665
WATER AVAILABILITY FORM
SECTION A: TO BE COMPLETED BY CUSTOMER
PROJECT NAME: Carlsbad Oaks SR#:
(Assigned upon plan submittal)
PROJECT ADDRESS: Lot 13 CITY: Carlsbad
PHONE: ( 760) 745-81185 x231 (Excel Engineering) FAX NUMBER:
I Largest Building (ft.2) Sprinkled? Construction Type:
SECTION B: TO BE COMPLETED BY LOCAL WATER COMPANY. CUSTOMER TO PROVIDE RESULTS TO CFD.
Water Purveyor: City of Carlsbad
Location of test (reference map required): Whiptail Loop East, north of Faraday Ave
TEST INFORMATION IS VALID FOR 6 MONTHS FROM DATE PERFORMED
Flow Test Results
Static pressure: 132 PSI Hydrant Number (if applicable):H61680
Elevation of test 395 Feet bate/Time of Test1
'itot Tube Reading: PSI 'Corresponding Flow: GPM
Total Flow: 3,500 GPM Residual Pressure 126 PSI
Atpeakdemand, this water system is capable of providing a fire flow discharge @ 20 psi of more than 8,000 gpm.
'Test to be performed as close as possible to the time the most conservative flows and pressures are expected.
Note: If the water availability information was obtained in a manner other than a flow test (i.e. computer
modeling), fill out the information above as applicable and check here: x
Name: Jennifer R.Mael.P.E. Eng. Lic. No. (if applicable): C69606
Signature:____________________________________
Title/Org: Prci/Manaer Date: 04/04/2016
I
I
I
I
1
[Ti
I
I
1
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
Whiptail Loop E - Lots 7, 8, & 13
rn
a 84
U.
/7 a
a 7 a H61680
61681
OUCT
\-4~,61682
1/
a
FADAYV
Prepared By: Jennifer R. Mael, P.E. - MCS Date: Monday, April 04, 2016
Attachment 4 - Pipeline Velocities
Network Table - Links
Link ID
Length
ft
Diameter
in
Flow
GPM
Velocity
fps
Pump 1 #NIA #NIA 3500.00 0.00
Pipe 37 22.81 8 0.00 0.00
Pipe 21 12.5 6 0.00 0.00
Pipe 53 32.08 6 0.00 0.00
Pipe 34 23.64 6 0.00 0.00
Pipe 32 37 8 0.00 0.00
Pipe 5 13 6 0.00 0.00
Pipe 13 25.05 6 0.00 0.00
Pipe 29 34.39 6 0.00 0.00
Pipe 52 23.21 6 0.00 0.00
Pipe 8 13 6 0.00 0.00
Pipe 27 23.31 8 0.00 0.00
Pipe 36 43.35 8 0.00 0.00
Pipe 25 28.75 8 0.00 0.00
Pipe 26 31.33 8 0.00 0.00
Pipe 2 23 6 0.00 0.00
Pipe 7 83.88 10 1592.99 6.51
Pipe 9 108.22 10 1592.99 6.51
Pipe 10 49.88 10 1592.99 6.51
Pipe 30 28.01 10 -1592.99 6.51
Pipe 3 133.16 10 1592.99 6.51
Pipe 4 95.84 10 1592.99 6.51
Pipe 6 178.64 10 1592.99 6.51
Pipe 11 20 10 1592.99 6.51
Pipe 16 185.37 10 1592.99 6.51
I
I
I
I
i
I
I
I
I
I
I
I
I
I
I
I
I
Attachment 4 - Pipeline Velocities
Link ID
Length
ft
Diameter
in
Flow
GPM
Velocity
fps
Pipe 17 20 10 1592.99 6.51
Pipe 18 82.36 10 1592.99 6.51
Pipe 14 17.93 10 1592.99 6.51
Pipe 28 171.8 10 -1592.99 6.51
Pipe 15 26.13 10 1592.99 6.51
Pipe 41 116.39 10 1592.99 6.51
Pipe 40 57.22 10 1592.99 6.51
Pipe 45 45.64 10 1592.99 6.51
Pipe 22 30.81 10 -1907.01 7.79
Pipe 23 85.04 10 -1907.01 7.79
Pipe 24 32.89 10 -1907.01 7.79
Pipe 20 327 10 -1907.01 7.79
Pipe 49 63.39 10 -1907.01 7.79
Pipe 50 56.48 10 -1907.01 7.79
Pipe 51 116.84 10 -1907.01 7.79
Pipe 31 12.53 10 -1907.01 7.79
Pipe 43 20.23 10 -1907.01 7.79
Pipe 42 31.94 10 -1907.01 7.79
Pipe 33 37.48 10 -1907.01 7.79
Pipe 48 7.08 10 -1907.01 7.79
Pipe 47 96.07 10 -1907.01 7.79
Pipe 44 67.77 10 -1907.01 7.79
Pipe 46 32.38 10 -1907.01 7.79
Pipe 59 54.57 12 3500.00 9.93
Pipe 39 16.26 12 3500.00 9.93
Pipe 38 5.10 12 3500.00 9.93
I
I
I
I
LI
i
I
I
I
I
I
LI
I
L]
I
I
I
Attachment 4 - Pipeline Velocities
Link ID
Length
ft
Diameter
in
Flow
GPM
Velocity
fps
Pipe 58 1 12 3500.00 9.93
Pipe 57 16.31 12 -3500.00 9.93
Valve 35 #N/A 10 3500.00 14.30
Pipe 19 13 6 3500.00 39.72
I
I
I
Li
I
[1
1
Fill,
I
Id
I
I
I
I
I
LI
F1
I
EPA NET 2
I
Page 1
Attachment 5 - Pressure Values
Network Table - Nodes
Node ID
Elevation
ft
Demand
GPM
Head
ft
Pressure
psi
Resvr48 399.65 -3500.00 399.65 0.00
Junc 20 411.02 3500.00 646.99 102.25
Junc 19 405.81 0.00 654.52 107.77
June 18 405.97 0.00 655.44 108.10
Junc 22 409.38 0.00 659.63 108.43
June 17 405.31 0.00 655.66 108.48
Junc 14 404.72 0.00 658.23 109.85
Junc 21 403.86 0.00 659.63 110.82
Junc 9 406.62 0.00 662.46 110.86
Junc 23 403.77 0.00 660.11 111.07
June 16 400.25 0.00 657.74 111.57
June 12 402.69 0.00 660.47 111.70
Junc 11 402.56 0.00 660.69 111.85
Junc 50 402.01 0.00 660.16 111.85
Junc 51 402.01 0.00 660.16 111.85
June 15 399.54 0.00 658.03 112.00
June 10 402.25 0.00 661.25 112.23
June 13 399.05 0.00 658.23 112.30
Junc 24 402.22 0.00 661.44 112.32
Junc 31 403.32 0.00 663.05 112.54
June 6 404.90 0.00 665.40 112.88
Junc 27 401.42 0.00 661.95 112.89
Junc 28 401.42 0.00 661.95 112.89
June 8 401.59 0.00 662.46 113.04
rJu7nc25 400.67 0.00 661.95 113.21
I
I
I
I
I
I
I
I
I
I
I
I
I
I
$
I
EPA NET 2
I
Page 2
Attachment 5 - Pressure Values
Node ID
Elevation
ft
Demand
GPM
Head
ft
Pressure
psi
June 26 400.59 0.00 661.95 113.25
June 44 400.34 0.00 662.06 113.40
June 35 404.6 0.00 666.54 113.50
June 7 401.07 0.00 663.40 113.67
June 46 399.92 0.00 663.05 114.01
June 30 399.52 0.00 663.05 114.19
June 29 399.18 0.00 663.05 114.34
June 32 398.94 0.00 663.25 114.52
June 3 403.43 0.00 667.97 114.62
June 5 399.96 0.00 665.40 115.02
June 45 397.88 0.00 664.13 115.37
June 38 400.66 0.00 667.35 115.56
June 37 400.66 0.00 667.35 115.56
June 399.37 0.00 666.47 115.74
June 33 398.60 0.00 665.95 115.84
June 42 399.91 0.00 667.86 116.10
June 34 397.51 0.00 666.54 116.57
June 2 398.76 0.00 667.97 116.65
June 36 398.02 0.00 667.35 116.70
June 41 396.83 0.00 667.04 117.08
June 39 398.75 0.00 669.36 117.26
June 40 398.23 0.00 669.27 117.44
June 1 398.2 0.00 669.91 117.73
June 43 398.16 0.00 670.42 117.97
June 58 398 0.00 671.50 118.51
June 56 398 0.00 671.52 118.52
I
I
I
I
I
ii :i
I
I
I
I
I
I
I
I
I
I
I
Attachment 5 - Pressure Values
Node ID
Elevation
ft
Demand
GPM
Head
ft
Pressure
psi
Junc55 398 0.00 671.84 118.66
June 57 398 0.00 690.65 126.80
Junc47 398 0.00 690.75 126.85
June 54 0 0.00 690.33 299.12
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
EPA NET 2
I
Page 3