HomeMy WebLinkAbout3821 ADAMS ST; ; FA130068; Permit9/27/22, 11:33 AM FA130068 Permit Data
City of Carlsbad
Fire Alarm Permit
Job Address: 3821 ADAMS ST
Permit Type: FALARM
Parcel No: 2052700900
Lot #: 0
Reference No.:
Permit No: FA130068
Status: APPROVED
Applied 10/8/2013
Approved: 10/11/2013
Issued: 10/11/2013
PC #: Inspector:
Project Title: ST PATRICKS PARISH REMODEL INSTALL NEW ADDRESABLE
FA SYSTEM IN CHURCH. WILL PROVIDE SPRINKLER
MONITORING, NOTIFICAITON TO OCCUPANTS & DUCT
SMOKE' DETECTION ON AIR MOVING SYSTEMS EXCEEDING
2000 CFM. THE FA WILL BE MONITORED BY A UL LISTED
MONITORING STATION.
Applicant:
EMCOM ELECTRONIC SYSTEMS, INC.
SUITE H
256 WITHERSPOON WY
EL CAJON, CA
619-667-1200
Owner:
ROMAN CATHOLIC BISHOP OF SAN
DIEGO
P 0 BOX 85728
SAN DIEGO CA
rFees Add'I Fees Total Balance
L 364 0 364 0
about:blank 1/1
St. Patrick Parish Remodel Alarm System Review Comments. Page 2
Review Comments
St. Patrick Parish Remodel Alarm System, 3821 Adams Street, Carlsbad, CA
We strongly recommend the following operational tests be performed once the system installation
has been completed.
A "power off' test, where the normal power supply is shut off, and the system is left to
function on battery power alone for a period of 24 hours, at which time the system should still
be functioning and operational.
At the end of the end of the above test, prior to the primary power being restored, the system
should be placed in an "alarm" condition for a period of not less than five minutes, during
which time all notification appliances, including the off-station notification, are to function as
designed.
Once the two prior tests have been completed, the current level in the batteries should be
checked, the primary power restored, and at the end of 48 hours the current level checked
again to verify that the charging function of the panel is both operational, and able to recharge
the batteries within the time period specified by NFPA-72.
Once the test in item "c" has been completed, one of the leads to the battery should be
disconnected, to determine that the system will provide notification of an "off-normal" power
condition to the monitoring company.
I ..
I EV1COVI
ELECTRONIC SYSTEMS, INC. CALIC. 820216 SEC L1CAC03838
256 WITHERSPOQN WAY, SUITE H . ELCAJON, CA 92020 • PH. (619) 667-1200 • FAX (619) 667-1222
Fire Alarm System
Equipment Submittal
For
St. Patrick Parish
Church Remodel
3821 Adams St.
Carlsbad, Ca. 92008
]tten pann it hnntt re en d tnt tt ateilt
th IL ctIII.IIn pit tbnn' . nt: anti n,tinlaitk it tine
ii lie UFtnllC11' a IT tn, let InC fLint nna tOt/n
ilpnnIl 1 iii pLllIn nIt Inn n' hi
telIttll In dc e\pl e au n iIIl1i fl In tl tilt' tl\ inn
.11 tn atat enlie\e he nnv.IIC II n(null it ant ni
tint! .itnit,ii CttjlnCCl Of ainlllteci Inc l)!e u.pnnnllt'tIIl
lu' lull lui10W with said nttnit' acid itiutdtinl,
uutn'llinlltnit the building tilenr Ice atm ce1tiuumsihill inc
tklncleiltl e,C finlft. )I Ilis, nIna ntf lltlilfellLC Miltee
pIlll n Iieuliei ni muni imi'ied in ihl inn men
Lm,nlc/OI ReteW
IcMMLND AItIt!lIV,\l
l!C!ll\1l'li \ltlnbi tV1! t; "01 I)
— -
I
I
INTELLIGENT FIRE ALARM CONTROL PANELS FX-350-60-DR I Features
Description
The FX-350-60-DR InteIigent Fire Alarm Control Panel
is a single loop addressable panel that supports up to
60 addressable points. The FX-350-60-DR is equipped
with a twc line by 20 character baclit LCD display,
numerical keypad and an integrated UDACT/Digital
Communicator. The LC J display allows or 32 characters
to be configured for user defined messages. In addition
the FX-3EC Series family also includes remote LED and
LCD annunciators.
The FX-2E0-60-DR is ideal for both new and retrofit
applicatio 13. Designed for small to medum commercial,
institutional and industrial occupancies, these panels are
powerful enough to meet today's installation demands.
The FX-350-60-DR is configurable by the keypad for
onsite programming or by a PC for both onsite and
remote pogramming. Easy to instFP and simple to
operate and configure, the FX-350-60-DR enables the
installer to configure the system to meet their specific
requirements.
The FX-350-60-DR is ecuipped with a 5.5 Amp power
supply, auxiliary resettable smoke powe-supply (300mA
max.), an interface for a Remote Trouble Indicator (RTI-
1) and an RS-485 interface for remote LCD and LED
annunciatos.
The FX-35J-60-DR comes complete with a red door,
black enclD3ure, durable CAT-30 lock and key and space
to mount up to 12 AH batteries. An optonal trim ring is
available fo- semi-flush mounting.
Single Addressable SLC Loop that supports 60
addressable points
Points can be any combination of Addressable
Sensors or Modules
Supports Ionization Sensors, Photoelectric Sensors,
Variable Heat Sensors and Multi—Sensor (Heat/Photo)
Equipped with a 2 line by 20 character backlit LCD
display, numerical keypad and an integrated UDACT/
Digital Communicator
LCD display allows for 32 characters to be configured
for user defined messages
Digital Communicator can be configured for DACT
or UDACT mode of operation
Configurable via the front panel, PC Configurator, or
remote dial up through the built-in modem
Sensors can be configured asAlarm, Verified Alarm,
Latching or Non-Latching Supervisory, Monitor and
Trouble-Only
Modules can be configured as Alarm, Latching
Supervisory, Non-Latching Supervisory, Water Flow,
Monitor, Trouble, Fire Drill Switch, Signal Silence
Switch, Aux Disconnect Switch and Buzzer Silence
Switch
Base panel is equipped with Four Class "B" (Style "B")
indicating circuits which may be configured as Class 'A"
(Style "Z") using a Class A" signal converter module
Indicating Circuits may be configured as Silenceable
or Non-Silenceable for both signals and strobes
Built-in sync protocols for the following strobe
manufacturers: Mircom, Amseco, System Sensor,
Gentex, Faraday and Wheelock
Relay contacts for Common Alarm, Auxiliary/
Alarm (Disconnectable), Common Supervisory and
Common Trouble
Configurable Signal Silence Inhibit, Auto Signal
Silence and One-Man Walk Test
SubsequentAlarm, Supervisory, and Trouble operation
RS-485 Interface for Remote LED and LCD
Annunciators
Positive Alarm Sequence
Interface for a Remote Trouble Indicator (RTI-1)
Two event history logs comprised of a 200 event
alarm log for alarm related events and a 200 event
general log for all other events
5.5 Amp Power Supply
Optional modules for additional internal relay circuits
and City Tie/Polarity Reversal
Optional trim ring for semi-flush mounting
® 1•MEA City Of
Approved for S7010 7165-1477:156 313-97-E Class 1 ApplicaSons
I
U
I
I
I
I
I
I
I
I
I
El
I
CATALOG NUMBER NOT TO BE USED FOR INSTALLATION PURPOSES.
Mircom reserves the right to make changes at any time without noe in prices, colours, materials, components, equipment, specifications and models and also to discontinue models.
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
FX-350 Series Installation and Operation Manual
Appendix D: Power Supply and Battery Calculations
POWER REQUIREMENTS (ALL CURRENTS ARE IN AMPERES)
Model Number I Description Qty STANDBY TOTAL ALARM I TOTAL
STANDBY ALARM
FX-350-60-DR Main Panel c/w Dialer X 0.220 = 0.380
FX-351-LW Main Panel clw 1 RAX- X 0.210 = 0.390 (Note i) FX-353-LW 332 LED Displays
FX-351 -LDW/R Main Panel, 01w 1 RAX-
332 LED Displays and X 0.230 0.400 (Note 1) = FX-353-LDR Dialer
ALC-252 252 Point Dual Loop X 0.120 = 0.230 Addressable Adder
RAX-332 32 LED Display X 0.005 = 0.010 =
PR-300 Polarity Reversal and 0.050 = 0.300 = City Tie Module
RAM-300- Remote LCD -
LCDW/R Annunciator X 0.016 = 0.040 -
RAM-208 Remote Annunciator, 8 X 0.0350 = 0.090 = Zone LED
RAM-216 Remote Annunciator, 16 X 0.0350 = 0.140 = Zone LED
RTl-1 Remote Trouble X 0.035 = 0.035 = Indicator
MIX-3000 Ionization Detector X 0.00028 = 0.00028 =
MIX-3100 Photoelectric Detector X 0.0004 = 0.0034 =
MIX-3200 Multi-sensor Detector X 0.0005 = 0.0035 =
MIX-3300 Heat Detector X 0.0005 = 0.0034 =
MIX-lOOP Priority Monitor Module X 0.0006 = 0.0046 =
MIX-10113 X Mini Priority Monitor 0.0006 = 0.0046 = Module
MIX-100R Relay Output Module X 0.00085 = 0.0035 =
MIX-100S Supervised Control X 0.00100 = 0.00100 = Module
MIX-100X (Kit)
100XH (Isolator) lsolatorc/wMounting 0.000035 = 0.000035 = Base 100XB (Base)
MIX-2001R Relay Base X 0.0 0.046 =
Device & Remote LEDs (Maximum 30) X
Load (bells, horns, strobes, and etc.)
Auxiliary
0.0040
Signal
pool
Power Supply for Annunciators, etc. (SeeNote2)
ALARM (B)
=
Total currents (Add above currents) STAN DBY(A) =
51
MS-71 QIDU
ln:eligent Addressable
Dual Action Manual Station
fl
I
ALPHA INTELLIGENT ADDRESSABLE MANUAL STATIONS MS-700IDU SERIES
-
MS-7O1lDU
Intelligent Addressable
Single Action Manual Station
Description
Mircom's MS-700IDU Series provide manual
fire reporting. These high quality, die-cast metal
nteligent Fire Alarm Manual Stations are available
in either single or dLal action configurations with a
permanently attached addressable module.
The MS-700IDU Series stations are available as
single or dual-action devices with key resets and
a permanently attached addressable module . The
addressable manual station has DIP switches which
allD/I for address setting. Pulling the handle initiates
the operation of the aodressable module.
All models are available with CAT-30 keys and mount
on a standard single gang backbox, Mircom model
BB-700 interior surface metal backbox, or BB-700WP
weather proof backbox.
Operation
The MS-7011DU Single Action Intelligent Manual
Station is operated by pulling down the handle marked
"PULL HANDLE" on the front of the station. The
MS-71 OIDU Dual Action Intelligent Manual Station is
operated by pushing the bar labelled PUSH BAR"
anc then pulling down the handle marked "PULL
HANDLE". The MS-70010U Series Manual Stations
are reset by opening the station with the key, placing
the handle in the nrmal upright position and re-
locking the station.
Features
Single or Dual Action
Key resettable
Permanently Attached Intelligent Addressable
Module
High-gloss red enamel finish
Plastic breakrod
Meets ADA 5 lb. maximum manual-force
Mounts on standard single gang box, Mircom's
BB-700 surface metal backbox or BB-700WP
weather proof backbox
Specifications
The manual station shall be Mircom's MS-7001DU
Series. Operating instructions shall be in raised
English lettering and the unit shall be constructed
of high quality die-cast metal and finished in red
enamel paint to provide quick identification. Pulling
the handle shall initiate immediate operation of the
intelligent addressable module.
All manual fire alarm stations shall be installed as per
the specific requirements outlined in the UL codes,
as well as all other applicable national or local codes.
Final acceptance is subject to the local authority
having jurisdiction.
7150-1477:128 S7005 S7005
CATALOG NUMBER 5679 NOT TO BE USED FOR INSTALLATION PURPOSES. -
Mircom reserves the rig r. to make changes at any time without notice in prices, colours, materials, components, equipment, specifications and models and also to discontinue models.
I
ALPHA INTELLIGENT ADDRESSABLE DETECTORS MIX-3000 SERIES
.lIl
I
I
MIX-3000 MIX-3100
Ionization Smoke Detector Photoelectric Smoke Detector
MIX-3200 MIX-3300
Multi-Sensor Detector Thermal Detector
Description
Mircom's Alpha Series Intelligent Addressable
Detectors are designed to meet a wide range
of applications. The detector's address is set in
its base providing a convenient and trouble free
maintenance procedure. The detectors mount into a
selection of base styles to accommodate installation
requirements.
Intelligent Ionization Smoke Detector (MIX-3000)
The Ionization smoke detector incorporates a
unique dual chamber design to respond quickly and
dependably to a broad range of fires. The ionization
detector is equipped with a red LED which flashes
when the detector is polled and turns on steady when
the detector goes into alarm. (UL Listed)
Features
Low profile design
For use with the FX-350 Series Fire Alarm Control
Panels
Fast response time
Automatic addressing with the MIX-ADD card
Variety of mounting bases
Ease of installation
Elegant, unobtrusive design
Digital communications
Intelligent Multi-Sensor Detector (MIX-3200)
The Intelligent Multi-Sensor Detector is a photoelectric
smoke detector with a supplementary thermal sensor.
The Multi-Sensor detector combines photoelectric smoke
and thermal sensor values to provide enhanced detection
performance and reduction of false alarms. Information
from each sensing element is processed and conditioned
by an on-board advanced technology ASIC and digitally
transmitted to the FACP as a single analog value
comprised of the combined responses from both the
photoelectric smoke and thermal detection elements.
Intelligent Thermal Detector (MIX-3300)
The Intelligent Thermal Detector utilizes state of the art
electronic temperature sense to provide fast and accurate
I
I
I
I
temperature monitoring. The thermal detector features
Intelligent Photoelectric Smoke Detector (MIX-3100) an adjustable termperature range that is configured from
The Intelligent photoelectric smoke sensor utilizes the FX-350 Series fire alarm control panel.
I a unique optical sensing chamber that is designed
to sense smoke produced by a wide range of
combustion sources. The photoelectric detector
is equipped with a clear LED which flashes when
I the detector is polled and turns on steady when the S6295 S6965 7271-1477138 MIX-3000. MIX-3100 (MIX-3100
detector goes into alarm. (MIX-3000) & MIX-3200) S MIX-3200) 7272-1477:131 S6299 37498 (MIX-3100)
7272-1477:142 (MIX-3300) (MIX-3300)
I
(MIX-3200)
(MIX-3300)
7270-1477:139 CATALOG NUMBER 5676 NOT TO BE USED FOR INSTALLATION PURPOSES.
Mircom reserves the right to make changes at any time without notice in prices, colours, materials, components, equipment, specifications and models and also to discontinue models.
I
ALPHA INTELLIGENT ADDRESSABLE MODULES MIX-100 SERIES
I
Ill L<-1O1P MIX- 1 C C P
MIX-100S MIX-bOX
Description
Mircom's Alpha Series Intelligent Addressable
Modules are designed to meet a wide range of
applications. The monitor and control modules can
be used to supervise and activate sounders, strobes,
door closers, pull stations, waterflow switches,
conventional smoke detectors and more. An eight
position dip switch allows for the address setting of the
device and the wiring class/style of the devices that
are connected to the module. All modules mount in
a standard 4" x 4" x 2 1/8" junction box.
Intelligent Addressable Priority Monitor Module
(MIX-lOOP)
The Intelligent Addressable Priority Monitor Module
(MIX-100P) provides an address for a group of UL/
ULC Listed normally open (N.O.) initiating devices,
such as heat detectors, beam smoke detectors, 4-
wire smoke detectors, waterflow switches, manual
pull stations, etc. wired in a Class A (Style D) or
Class B (Style B) initiating circuit. The MIX-100P
is equipped with a priority interrupt to provide a fast
response to emergency conditions. The MIX-100P
has an activated red LED.
Features
Designed to meet a wide range of applications
For use with the FX-350 Series FireAlarm Control
Panels
Fast response time
Priority Interrupt feature on monitor modules
Monitor modules can be wired as a Class A (Style
D) or Class B (Style B)
Each module can be addressed from 1 to 126
Eight position dip switch for address setting
Red light indicator
Modules mount in standard 4" junction box
Intelligent Addressable Priority Mini-Monitor
Module (MIX-IOIP)
The Intelligent Addressable Priority Mini Monitor Module
provides an address for a group of UL/ULC Listed
Normally Open (N.O.) initiating devices, such as heat
detectors, projected beam smoke detectors, 4-wire
smoke detectors, waterflow switches, manual pull
stations, etc. wired in a Class A (Style D) or Class B
(Style B) initiating circuit. The MIX-IOIP is equipped
with a priority interrupt to provide a fast response
to emergency conditions. The MIX-I01P has an
activated red LED.
Intelligent Addressable Relay Module (MIX-IOOR)
The Intelligent Addressable Relay Module connects to
the same loop as the initiating devices and provides
two isolated sets of Form-C contacts to control a
variety of normally open or normally closed contact
applications cuch as fan operation and door closures.
The MIX-IOOR has an activated red LED which
follows the state of the relay contacts.
@ @ 0
S5434 S5434 7150-1477:156
CATALOG NUMBER 5675 NOT TO BE USED FOR INSTALLATION PURPOSES.
Mircom reserves the right to make changes at any time without notice in prices, colours, materials, components, equipment, specifications and models and also to discontinue models.
SYSTEM $ SENSOR
4-Wire Photoelectric Duct
Smoke Detector
The lnnovairFlex'° Series are the only duct smoke
detectors flexible enough to fit configurations from
square to rectangular and everything in between.
Features
Photoelectric, integrated low-flow technology
Air velocity rating from 100 ft/min to 4,000 ft/mm (0.5 m/s to 20.32
m/sec)
Versatile mounting options: square or rectangular configuration
Plug-in sensor offers superb false alarm immunity and the latest
sensor technology
Broad ranges for operating temperature (-4°F to 158°F) and
humidity (0% to 95% non-condensing)
Patented sampling tube installs from front or back of the detector
with no tools required
Increased wiring space with a newly added 3/4-inch conduit
knockout
One easy-access Test/Reset button and improved LED status
Patented interconnect feature for multi-fan shutdown
New high contrast terminal designations
Built-in short circuit protection from operator wiring errors
Field selectable settings for configuring the detector
Two DPDT Form-C relay contacts
24VAC/DC or 120 VAC
Backward compatibility with existing Innovair products, including
remote accessories
Innov PDX-
The InnovairFiex D4120 4-wire photoelectric duct smoke
detector features a pivoting housing that fits both square and
rectangular footprints and mounts to round or rectangular ductwork.
This unit senses smoke in the most challenging conditions, operating
in airflow speeds of 100 to 4,000 feet per minute, temperatures
of —4°F to 158°F, and a humidity range of 0 to 95 percent (non-
condensing). A plug-in sensor head offers improved false alarm
immunity and simple installation, testing, and maintenance. An
improved cover design isolates the sensor head from the low-flow
feature for simple maintenance.
The InnovairFIex housing provides ample wiring space, a 1/4-inch
conduit knockout, and built-in short circuit protection to prevent
damage to sensitive components during installation. High contrast
terminal designations make wiring easy. With its 2:1 sensor-to-power
capability, the power board of the D4120 may be used to monitor
a second sensor, D4S, simultaneously (i.e., supply and return side).
As many as 50 InnovairFIex detectors can be interconnected. When
one unit senses smoke, all interconnected detectors will switch
their relays; only the detector sensing smoke will go into alarm, thus
pinpointing the fire source.
An easy-access Test/Reset button makes it possible to test the unit
with the cover on. Three DIP switches can be used to configure field
selectable settings: cover tamper delay, number of sensors to be
controlled, and shut down on trouble option. Each power board
has two LEDs that can be used to indicate the status of connected
sensors, and a quick reference imprinted on the cover explains the
LED status indications (Standby, Maintenance, Trouble, and Alarm).
The lnnovairFlex duct smoke detector can be customized to meet
local codes and specifications without additional wiring. The new
Agency Listings lnnovairFlex product line is compatible with all previous Innovair
models, including remote test accessories.
MSFM area
WARNING: Duct smoke detectors are NOT a substitute for open
smoke detectors; NOT a substitute for early warning detection;
LISTED APPROVED approved NOT a replacement for a building's regular fire detection system.
09fO Refer to NFPA 72 and 90A for additional information.
InnovairFlex' Duct Smoke Detector Specifications
I he air duct smoke detector shall be a Systern Sensor lrrnovairFlex D4120 Photoelectric Duct Smoke Detector: 1 he detector housing shall be UL listed per UL
268A specifically for rise in air handling systems.The flexible housing of the duct smoke detector fits multiple footprints from square to rectangular The detector
shall operate at air velocities of 100 feet per minute to 4000 feet per minute (0.5 to 20.32 meters/second), The unit shall be capable of controlling up to 50 air
handling systems when interconnected with other detectors. The detector shall be capable of providing a trouble signal in the event that the front cover is
removed. It shall be capable of local testing via magnetic switch, test button on the cover, or remote testing using the SSK451 Multi-Signaling Accessory or the
RTS'lSl KEY Remote Test Station. Terminal connections shall be of the strip and clamp method suitable for 12-18 AWG wiring.
Size: (Rectangular Dimensions) 14.38 in (37 cm) Length; Sin (12.74 cm) Width; 7.5 in (6.36 cm) Depth
(Square Dimensions) 7.75 in (19.7cm) Length; 9 in (22.9 cm) Width; 2.5 in (6.35 cm) Depth
Weight: 2.5 lbs (1.14 kg)
Operating Temperature Range: 04120 & D4S: -4 to 158F )-20 to 70CC); D4P120: -40 to 158F (-40W to 70CC)
Storage Temperature Range: 04120 & D4S: -22 to 158T (-30 to 7020; D4131 20: -'10 to 1587 (-40 to 70CC)
Operating Humidity Range: 0% to 95% relative humidity non-condensing
Air Duct Velocity: 100 to 4000 ft/min AS to 70.32 rn/set)
Power supply voltage: 70-79 VDC 74 VAC 50-60 H7 170 VAC 50-60 H7
Input capacitance! 270MFmax. 270pFmax. N/A
Reset voltage: 3.0 VDC mm. 2.0 VAC mm. 10 VAC mm.
Reset time: (with R1S451) .03 to 0.3 sec. .03 to 0.3 sec. .03 to 0.3 sec.
Reset time: (by power down) 0.6 sec. rrlax. 0.6 sec. Max. 0.6 sec. rrrax.
Power up time: I 35 sec. max. 35 sec. max. 35 sec. Max.
Alarm response time: 15 sec. 15 sec. sec. -15
Sensitivity Test; See detector label See detector label See detector label
I Current Requirements: (Using No Accessories)
Max. standby current: 21 mA @ 24VDC 65 mA RMS @ 24VAC 60Hz 20 mA RMS @ 120VAC 60Hz
Max, alarm current:
• 65 mA @ 24VDC 135 mA RMS @ 24VAC 60Hz 35 mA RMS @ 120VAC 60Hz
I Alarm initiation contacts: (SPST) 2.OA @30 VDC (resistive)
Alarm auxiliary contacts: (DPDT) 10A @30 VDC (resistive); 10A @750 VAC (resistive); 1/2 HP @740 VAC; 1/4 HP @ 120 VAC
Note: Alarm auxiliary Contacts shall not be connected to initiating circuits of control panels. Use the alarm initiation contact for this purpose.
I Supervisory contacts: (SPOT)
ON WI I'll 111 4
Device
2.OA @30 VDC (resistive); 2.0A @ 125 VAC (resistive)
. '
Standby Trouble
- i- Ti1
Alarm
APA1 51/APA4S 1 12.5 mA n/a 30 nrA Max.
MHR/MHW OmA n/a 29 mA Max,
RA100Z OmA n/a 12mAMax.
RTS151/RTS151KEY 0rnA/12mA n/a 12mAMax.
RTS7/RTS2-AOS 3,0mA max 16 mA Max. with strobe: 55 mA max; without strobe 30 mA max
Note: Any combination of accessories may I be used such that the given accessory loads are: 110 mA or less at the Aux output, and 50 mA or less at the Alarm output
Installing the InnovairFiex Sampling Tube
The InnovairFiex sampling tube may be installed from the front or back of the detector. The tube locks securely into place and can be removed by releasing
the front or rear locking tab (front locking tab shown below right).
NOTE: All CAUTIONS and WARNINGS are identified by the symbol A. All warnings are printed in bold capital letters.
A WARNING: PLEASE READ THESE SPECIFICATIONS AND ASSOCIATED INSTALLATION INSTRUCTIONS CAREFULLY BEFORE USING, SPECIFYING
OR APPLYING THIS PRODUCT. VISIT WWW.COOPERNOTIFICATION.COM OR CONTACT COOPER NOTIFICATION FOR THE CURRENT INSTALLATION
INSTRUCTIONS. FAILURE TO COMPLY WITH ANY OF THESE INSTRUCTIONS, CAUTIONS OR WARNINGS COULD RESULT IN IMPROPER APPLICATION,
INSTALLATION AND/OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD RESULT IN PROPERTY DAMAGE, AND
SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS.
General Notes:
General Notes
* Strobes are designed to flash at I flash per second minimum over their Regulated Voltage Range'.
All candela ratings represent minimum effective strobe intensify based on UL Standard 1971.
Series Exceder Strobe products are Listed under UL Standards 1971 and 464 for indoor use with a temperature range of 32'F to 120'F )0'C to 49'C) and
Maximum humidity of 937, )i 2%) UL 464 )85% UL 1971)
Series Exceder horns are under IlL Standard 464 for audible signal appliances(Indoor use only)
-ILow LCurrent ii I]1YiT FewerPower Su J I] 1*
Strobe Ratings per UL Standard 1971
UL Max
24VDC/24FWR 12 VDC
Model Regulated Voltage
Range VDC 15 15/75 30 60 75 95 110 115 135 150 177 185 15 15/75
ST 80-33.0 0.057 0.070 0.085 0.135 0.163 0.182 0.2051 0.253 0.110 0.140
STC 8.0-33.0 0.061 0.085 0.103 0.135 0.163 0.182 10.205 0.2til 0.110
Horn Strobe Ratings per UL 1971 & UL 464 at 24 VDC
01 UL Max Currerl at 99 dBA
24 VDC 12 VDC
Model Regulated Voltage
Range VDC 15 15/75 30 60 75 95 110 115 135 150 177 1185 15 15/75
HS 8.0-33.0 0.082 0.095 0.102 0.148 0.176 0.197 0.242 0.282 0.125 0.159
HSC 8.0-33.0 0.082 0.102 0.141 0.148 0.176 0.197 0.242 0.284 0.125
UL Max Current* at 95 dBA .1I.
24 VDC 12VDC
Model Regulated Voltage
Range VDC 15 15/75 30 60 75 95 110 115 135 150 177 185 15 15/75
HS 8.0-33.0 0.073 0.083 0.087 0.139 0.163 0.186 0.272 0.122 0.153
HSC 8.0-33.0 0.073 0.087 0.128 0.139 0.163 0.186 0.230 0.272 0.122
UL Max Current* at 90 dBA m.
24 VDC 12 VDC
Model Regulated Voltage
Range VDC 15 15/75 30 60 75 95 110 1151135 150 177 185 15 15/75
HS 8.0-33.0 0.065 0.075
-
0.084 0.136 0.157 0.184 0.267 0.120 0.148
HSC 8.0-33.0 0.065 0.084 0.120 0.136 0.157 i., I .120
Horn Ratings per UL 464 -
Model Regulated Voltage
Range VDC 99 dB 95 dB 90 dB
HN 16-33.0 0.064 0.044 0.022
HNC 16-33.0 0.084 0,044 0.022
HN 8.0-17.5 0.047 0.026 0.017
HNC 8.0-17.5 0.047 0.026 0.017
Ike.
I
hu t
* UL max current rating is the maximum RMS Current within the listed voltage range (16-33 VDC for-24 VDC units). For strobes the
UL max current is usually at the minimum listed voltage (16 VDC for 24 VDC units). For audibles the max current is usually at the
maximum listed voltage (33 VDC for 24 VDC units). For unfiltered ratings, see installation instructions.
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM
LISTING SERVICE
LISTING No. 7165-1477:0156 Page 1 of 2
CATEGORY: 7165-- FIRE ALARM CONTROL UNIT (COMMERCIAL)
LISTEE: MIRCOM TECHNOLOGIES, LTD.25 Interchange Way, Vaughan, Ontario L4K 5W3 Canada
Contact: Mara Cherubin (888) 660-4655 Ext: 3110 Fax (888) 660-4113
Email: mcherubin@mircom.com
DESIGN: Models FX-350-60-R, FX-350-60-DR, FX-350-126-R, FX-350-126-DR, FX-351-LW,
FX-351-LDW, FX-353-LDR, FX-353-LDW and FX-350-378-DR fire alarm control units. Local,
auxiliary, remote station (PPU), central station (PPU), waterflow and sprinkler supervisory
services. Refer to the listees data sheet for detailed product description and operational
considerations. System components:
MD-815; FX-350/FX-351 Mainboard - with Dialer
MD-837; FX-350/FX-351 Mainboard - No Dialer
MD-749; DSP Core Board
MD-819; Power Supply Board
PR-300; City Tie/Polarity Reversal
TR-061; 120/240 VAC Transformer
CH-613; FX-350 Backbox
FX-350 Door
FX-350 Deadfront
FX-351 Deadfront
FX-351 Door
FX-351 Backbox
MD-825; RAX 232
RAM-300-LCD; Remote LCD Annunciator
MIX-1 OOP; Priority Monitor Module
MIX-101P; Mini Priority Monitory Module
MIX-100S; Supervised Control Module
*MlX100R; Addressable Dual Relay Output Module
MIX-i OOX; Isolator Kit
I
I
I
I
I
I
I
*Rev. 02-07-13 gt
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed
f\ the test results and/or other data but does not make an independent verification of any claims. This listing is not
an endorsement or recommendation of the item listed. This listing should not be used to verify correct
V' operational requirements or installation criteria. Refer to listees data sheet, installation instructions and/or other
Date Issued: July 01, 2013 Listing Expires June 30, 2014
Authorized By: JAMES PARSEGIAN, Program Coordinator
Fire Engineering Division
I
ri
I
I
I
I
I
I
I
Listing No. 7165-1477:0156
Page 2 of 2
RATING: 120 VAC, 60Hz
240 VAC, 50 Hz
INSTALLATION: In accordance with listee's printed installation instructions, applicable codes & ordinances,
and in a manner acceptable to the authority having jurisdiction
MARKING: Listee's name, model number, electrical rating, and UL label.
APPROVAL: Listed as fire alarm control units for use with listee's separately listed electrically and
functionally compatible initiating and indicating devices as indicated in design. Refer to
listee's Installation Instructions Manual for details. These control units can generate a
distinctive three-pulse Temporal Pattern Fire Alarm Evacuation Signal (for total evacuation) in
accordance with NFPA 72, 2002 Edition.
NOTE: For Fire Alarm Verification Feature (delay of fire alarm signal), the maximum
Retard/Reset/Restart period shall not exceed 30 seconds.
This control panel meets the requirements of UL-864, 9th Edition.
Rev. 02-07-1391
i This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed
the test results and/or other data but does not make an independent verification of any claims. This listing is not
an endorsement or recommendation of the item listed. This listing should not be used to verify correct
operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other
Date Issued: July 01, 2013 Listing Expires June 30, 2014
Authorized By: JAMES PARSEGIAN, Program Coordinator
Fire Engineering Division
I ..
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
I OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM
I
LISTING SERVICE
LISTING No. 7150-1477:0128 Page 1 of 1
I CATEGORY: 7150-- FIRE ALARM PULL BOXES
LISTEE: MIRCOM TECHNOLOGIES, LTD.25 Interchange Way, Vaughan, Ontario L4K 5W3 Canada
Contact: Mara Cherubin (888) 660-4655 Ext: 3110 Fax (888) 660-4113
I Email: mcherubin@mircom.com
DESIGN: Models MS-701U, -703U, 704U, -710U, -713U, -714U, 701ADU, -710ADU, -702U, -702ADU,
-70IUP, -710UP, -703U(C), -704U(C), -713U(C), -714U(C), -705U, -715U,-706U(C), -716U(C),
I -707U(C), -717U(C) and -708 fire alarm boxes. These devices are manually actuated, single
or dual action non-coded, fire alarm boxes. Units are to be mounted on standard outlet boxes
or listee's Model BB-700 backbox for indoor use only and BB-700WP backbox for indoor and
I outdoor use.
Models MS- 7011D(U), -702lD(U) and -710lD(U) non-coded, indoor use only, fire alarm boxes.
To be mounted on three-inch deep outlet boxes.
I Refer to listee's data sheet for additional detailed product description and operational
considerations.
I RATING: 30VDC, 1A, 125 VAC, 1A
INSTALLATION: In accordance with listee's printed installation instructions, applicable codes & ordinances
and in a manner acceptable to the authority having jurisdiction.
I MARKING: Listee's name, model number, rating, and UL label.
APPROVAL: Listed as fire alarm manual pull stations for use with separately listed compatible fire alarm
control units. Refer to listee's Installation Instruction Manual for details.
I * These manual pull boxes meet the requirements of UL Standard 38, 1999 Edition with
California amendments.
I
I
II]
*Updated 06-19-2009 fm
1 6TI This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed
the test results and/or other data but does not make an independent verification of any claims. This listing is not
an endorsement or recommendation of the item listed. This listing should not be used to verify correct
I operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other
I
Date Issued: July 01, 2013 Listing Expires June 30, 2014
Authorized By: JAMES PARSEGIAN, Program Coordinator
Fire Engineering Division
I
I
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION I OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM
I LISTING SERVICE
LISTING No. 7272-1477:0131 Page 1 of 1
I CATEGORY: 7272 -- SMOKE DETECTOR-SYSTEM TYPE-PHOTOELECTRIC
LISTEE: MIRCOM TECHNOLOGIES, LTD.25 Interchange Way, Vaughan, Ontario L4K 5W3 Canada
Contact: Mara Cherubin (888) 660-4655 Ext: 3110 Fax (888) 660-4113 I Email: mcherubin@mircom.com
DESIGN: Model MIX-3100 photoelectric smoke detector. Refer to listee's data sheet for additional
detailed product description and operational considerations I RATING: Electrical: 17 to 28 VDC, 5 to 9V protocol
INSTALLATION: In accordance with listee's printed installation instructions, applicable codes and ordinances
I and in a manner acceptable to the authority having jurisdiction.
MARKING: Listee's name, model number, electrical rating, and UL label.
APPROVAL: Listed as a photoelectric smoke detector for use with listee's separately listed compatable
I fire alarm control units and listed Models MIX-2000 Series detector bases (CSFM Listing No.
7300-1477:145). Refer to listee's Installation Instruction Manual for details.
NOTE: The photoelectric type detectors are generally more effective at detecting slow, smoldering
I fires which smolder for hours before bursting into flames. Sources of these fires may include
cigarettes burning in couches or bedding. The ionization type detectors are generally more
effective at detecting fast, flaming fires that consume combustible materials rapidly and
spread quickly. Sources of these fires may include paper burning in a waste container or a I grease fire in the kitchen
XLF: 7272-1394:0104
I
I
I
III
II 04-06-2005
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering
the test results and/or other data but does not make an independent verification of any claims.
staff has reviewed
This listing is not
an endorsement or recommendation of
operational requirements or installation criteria.
the item listed. This listing should not be used
Refer to listee's data sheet, installation instructions and/or other
to verify correct
I
Date Issued:
Authorized By
I
July 01, 2013
JAMES PARSEGIAN, Program Coordinator
Fire Engineering Division
Listing Expires June 30, 2014
1
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION I OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM
I LISTING SERVICE
LISTING No. 3242-1653:0207 Page 1 of 1
I CATEGORY: 3242 -- DUCT SMOKE DETECTOR, PHOTO. (W/ OR W/O BASE)
LISTEE: System Sensor, Unincorporated Div of Honeywell Int'l lnc.3825 Ohio Ave, St. Charles, IL
60174 I Contact: Trish Linhart (630) 377-6580 Fax (630) 377-7245
Email: trish.linhart@systemsensor.com
DESIGN: Models D4120, D4240, RD4120, P270-3000PL, 1D41203, TD41204, LD4S, LD412OX, I LD412OH, D4S, D4P120, CD4P12O LD4P12OX, LD4P12OH, TD4C, PD4120, YD4120,
YD4P12O, and AD4P12O four-wire conventional photoelectric duct smoke detectors and
subassemblies. Unit consists of a duct detector housing, powerboard with electrical
components and relays, exhaust tubes, and listed 2D51 detector head (CSFM Listing No. I 7272-1653:203). ModelAD4S sensor component. Models *TD4C, LD412OX, LD4120H,
LD4P120X and LD4P120H do not contain a 120 VAC transformer. Refer to listee's data
sheet for additional detailed product description and operational considerations. I RATING: 20-29 VDC, *24 VAC, 120 VAC (except Models *TD4C LD412OX, LD4120H, LD4P120X and
LD4P120H *do not have 120 VAC rating).
INSTALLATION: In accordance with listee's printed installation instruction, applicable codes and ordinances I and in a manner acceptable to the authority having jurisdiction.
MARKING: Listees name, model number, rating, air velocity and UL label.
APPROVAL: ' Listed as conventional photoelectric duct smoke detector for use with separately listed fire
alarm control units. Refer to listee's Installation Instruction Manual for details.
I
I
I
I
*Rev. 03-27-13 gt
I This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed
the test results and/or other data but does not make an independent verification of any claims. This listing is not
I V'
an endorsement or recommendation of
operational requirements or installation criteria.
the item listed. This listing should not be used to verify correct
Refer to listee's data sheet, installation instructions and/or other
I
Date Issued: July 01, 2013 Listing Expires June 30, 2014
Authorized By: JAMES PARSEGIAN, Program Coordinator
Fire Engineering Division
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM
LISTING SERVICE
LISTING No. 7300-1653:0212 Page 1 of 1
CATEGORY: 7300-- FIRE ALARM CONTROL UNITACCESSORIESIMISC. DEVICES
LISTEE: System Sensor, Unincorporated Div of Honeywell Int'l lnc.3825 Ohio Ave, St. Charles, IL
60174
Contact: Irish Linhart (630) 377-6580 Fax (630) 377-7245
Email: trish.linhart@systemsensor.com
DESIGN: Models RTS151, RTS151KEYand RA100Z Duct Smoke Detector accessories. Referto
listee's data sheet for detailed product description and operational considerations.
RATING: Refer to the installation manuals.
INSTALLATION: In accordance with listee's printed installation instructions, applicable codes and ordinances
and in a manner acceptable to the authority having jurisdiction.
MARKING: Listee's name, model number, electrical rating, and UL label.
APPROVAL: Listed as control unit accessories for use with separately listed compatible fire alarm control
units. Refer to listee's Installation Instruction Manual for details.
04-03-09 bh
is This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed
f2\ the test results and/or other data but does not make an independent verification of any claims. This listing is not
an en1orsement or recommendation of the item listed. This listing should not be used to verify correct
operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other
Date Issued: July 01, 2013 Listing Expires June 30, 2014
Authorized By: JAMES PARSEGIAN, Program Coordinator
Fire Engineering Division
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM
LISTING SERVICE
LISTING No. 7125-0785:0168 Page 1 of I
CATEGORY: 7125-- FIRE ALARM DEVICES FOR THE HEARING IMPAIRED
LISTEE: Cooper Wheelock lnc.7246 16th St. E., Ste. 105, Sarasota, FL 34243
Contact: Tom Conover (941) 487-2336
Email: thomas.conover@cooperindustries.com
DESIGN: Exceder Series: Models ST strobe, HS horn strobe and HN horn. Model ST is a synchronous
and non-synchronous strobe light. Model HS a visual/audible appliance and Model HN is an
audible signal appliance. All units followed by R (red) or W (white). Additionally, a C may be
added for ceiling models and/or a '-NR' may be added for non-resettable models. For non
-NR models and optional 'S for silver fascia may be added*. Refer to listee's data sheet for
additional detailed product description and operational considerations.
RATING: Electrical: 12 VDC/24VDC/FWR
Candela (wall)*: 15, 15/75, 30, 75, 95, 110, 135 & 185
Candela (ceiling)*: 15, 30, 60, 75, 95, 115, 150, & 177
INSTALLATION: In accordance with listee's printed installation instructions, applicable codes and ordinances
and in a manner acceptable to the authority having jurisdiction. All models are for indoor use
and for wall mount only or ceiling mount only*
MARKING: Listee's name, model number, electrical/candela rating, and UL label.
APPROVAL: Listed as horn for fire alarm signaling and strobe, horn/strobe for the hearing impaired when
used with separately listed electrically compatible fire alarm control units. Refer to listee's
Installation Instructions Manual for details.
I
I
*Rev. 9-24-09 fm
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed
the test results and/or other data but does not make an independent verification of any claims. This listing is not
an endorsement or recommendation of the item listed. This listing should not be used to verify correct
flV operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other
Date Issued: July 01, 2013 Listing Expires June 30, 2014
Authorized By: JAMES PARSEGIAN, Program Coordinator
Fire Engineering Division