HomeMy WebLinkAbout6269 EL FUERTE ST; ; AS100001; Permit9/27/22, 11:15AM AS100001 Permit Data
City of Carlsbad
Sprinkler Permit
Permit No: ASI0000I
Job Address: 6269 EL FUERTE ST
Permit Type: SPRINK
Parcel No: 2131221300
Lot #: 0
Status: ISSUED
Applied 1/4/2010
Approved: 1/4/2010
Reference No.: Issued: 1/4/2010
PC #: Inspector:
Project Title: PACIFIC RIDGE SCHOOL THREE FIRE SPRINKLER
INSPECTIONS @ $65/EA
Applicant:
A & D FIRE SPRINKLERS, INC.
2ND FLOOR
11465 W000SIDE AVE
SANTEE, CA 92071
619-448-1962
Owner:
PRS ACQUISITION&CONSTRUCTION L L
C
6269 EL FUERTE ST
CARLSBAD CA
Fees ($) Add'l Fees ($) Total ($) Balance ($)
195 0 195 0
about:blank 1/1
Carlsbad Fire Department f[
Plan Review Requirements Category: SPRINK, COMM
Date of Report: 0 1 -05 -2010 Reviewed by:
Name: A & D FIRE SPRINKLERS, INC.
Address: 2ND FLOOR
11465 WOODSIDE AVE
SANTEE, CA 92071 n C-% (D
~ / ~-1 /,-U
Permit #: AS 100001
Job Name: PACIFIC RIDGE SCHOOL
Job Address: 6269 EL FUERTE ST CBAD
cannot
carefully all comments attached. Please resubmit the necessary plans and/or specifications, with changes "clouded",
to this office for review and £p5röval ' 1)
Conditions:
-
Cond: C0N0003812
[MET] ** PROVIDE SSU/SSP COVERAGE IN ROOM 106 (SERVER ROOM). CFD DOES NOT PERMIT THE
EXCLUSION OF
WET SPRINKLER PROTECTION IN 'IT EQUIPMENT' ROOMS. CFD DOES PERMIT THE INSTALLATION OF ULTRA-HIGH
TEMP HEADS IN THESE ROOMS.
—_.Eniiy: 01/05/2010 By: GR Action: AP
- O J(A t6C
Ad t4 ajv-z~.~ 4LA'T
ASooco (
FIRE SRRINKLERS INC,
PACIFIC RIDGE SCHOOL
6269 El Fuerte Street
Carlsbad, CA 92009
Install Fire Sprinklers
These plans hive been reviewed loripparent compliance
with the ciii'I'CIiT applicable codes and standards in knee
in thc junsdiction, The owner or contractor may utilize
hr r,.'vres iii tipporr of' an application Imr a building
pr to with tho e press understanding that this review
ii, way r'l ieves the owner or contractor or their
po ifessuirtral erleirtecu or archuiectfor sole responsibility
tot liii I compliance with said codes and standards.
riieludrng the building code or for-any respoutsubtlty for
deficiencies, errors. o
r
missions or ncglrgence in these
plans whethe or no noted in this review.
Dille: /f1,'07 Reviewer c,)
RECOMMEND APPROVAL
0 RFCOMMFNI) APPROVAL. AS NOTEE)
>
0
0 HYDRAULIC CALCULATIONS '
APPR.OI7AS 3UB[ITTED
CAR[1(RE DEPARl1iJNT
**
Materials of equal design, utility, and performance maybe substituted for submitted materials so as to avoid delays in the
construction schedule and shall be deemed accepted by the Purchaser.
'I'---
F.~TA-imw
- - - Fire Protection by Computer Design
A&D Fire Sprinklers
11465 Woodside Ave.
Santee ca 92071
619-448-1962
Job Name : Pacific Ridge
Building : FP03 Level 2
Location 6269 El Fuerte St. Carlsbad CA 92009
System : 1
Contract F-428
Data File : Calc-1 L2-corridor.WXF
[I:
Comruter . Proarnms hv Hvdrtr mr. Rriifp 111 \A/indhm M I It (VñQ7
72.82-Psi
A&D Fire Sprinklers Page 1 Pacific Ridge Date 09-02-09
HYDRAULIC CALCULATIONS
for
Project name: Pacific Ridge High School
Location: 6269 El Fuerte St. Carlsbad CA 92009
Drawing no: FP03 Level 2
Date: 09-28-09
Design
Remote area number: 1
Remote area location: Exterior corridor
Occupancy classification: Ligh Hazard
Density: 0.10 - Gpm/SqFt
Area of application: 1000 - SqFt
Coverage per sprinkler: 195 - SqFt
Type of sprinklers calculated: VICTAULIC V27 Pendents
No. of sprinklers calculated: 12
In-rack demand: - GPM
Hose streams: 100 -GPM
Total water required (including hose streams): 381.98 -GPM
Type of system: TREE
Volume of dry orpreaction system: -Gal
Water supply information
Date: 08-20-09
Location: 6269 El Fuerte St. Carlsbad CA 92009
Source: Street Water
Name of contractor: A&D Fire Sprinklers
Address: 11465 Woodside Ave. Santee CA 92071
Phone number: 619-448-1962
Name of designer: Maria lniguez
Authority having jurisdiction: Carlsbad Fire Department
Notes: (Include peaking information or gridded systems here.)
Computer Proarams by Hvdratec Inc. Route 111 Winr1hm NJ k I I nn7
Water Supply Curve (C)
A&D Fire Sprinklers
Pacific Ridge Page 2
Date 09-02-09
City Water Supply: Demand: Cl - Static Pressure : 112.5 Dl - Elevation : 13.045 C2 - Residual Pressure: 103.5 D2 - System Flow : 281.984 C2 - Residual Flow : 1075 D2 - System Pressure : 86.470
Hose (Adj City)
Hose ( Demand) : 100
03- System Demand : 381.984
Safety Margin : 24.703
150
140
- I
130
p120
110
C1
R - _______ ________
100 E
90
580
U70
R6°
E50
40
30
20
10 --Dl—
..... ... .. ... 200 400 600 800 1000 1200 1400 1600 1800 FLOW (NA1.85)
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
., . . Fittings Used Summary
A&D Fire Sprinklers Page 3 Pacific Ridge Date 09-02-09
Fitting Legend
Abbrev. Name 'A 1'/ 11/2 2 2'/ 3 3% 4 5 6 8 10 12 14 16 18 20 24
E NFPA 13 90 Standard Elbow 1 2 2 3 4 5 6 7 8 10 12 14 18 22 27 35 40 45 50 61 F NFPA1345Elbow 1 1 1 1 2 2 3 3 3 4 5 7 9 11 13 17 19 21 24 28 G NFPA13 Gate Valve 0 0 0 0 0 1 1 1 1 2 2 3 4 5 6 7 8 10 11 13 T NFPA139O Flow thruTee 3 4 5 6 8 10 12 15 17 20 25 30 35 50 60 71 81 91 101 121
Units Summary
Diameter Units Inches
Length Units Feet
Flow Units US Gallons per Minute
Pressure Units Pounds per Square Inch
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Pressure I Flow Summary - STANDARD
A&D Fire Sprinklers Page :4 Pacific Ridge Date 09-02-09
Node Elevation K-Fact Pt Pn Flow Density Aea Press No. Actual Actual Req.
30 2212 5.6 12.13 na 19.5 0.1 195 . 7.0 31 21.91 5.6 12.61 na 19.69 0.1 195 7.0 31A 22.25 14.42 na 32 21.91 5.6 15.28 na 21.89 0.1 195 7.0 32A 22.25 16.99 na 33 22.12 5.6 14.52 na 21.34 0.1 195 7.0 33A 22.25 17.24 na 34 21.91 5.6 18.6 na 24.15 0.1 , 195 .. 7.0 34A 22.25 20.24 na 35 22.12 5.6 16.95 na 23.06 0.1 195 7.0 35A 22.25 20.56 na 41 19.41 5.6 22.14 na 26.35 0.1 195 7.0 35B 20.91 23.66 na 35C 20.91 27.35 na 36 22.12 5.6 17.54 na 23.45 0.1 195 7.0 37 22.12 5.6 17.04 na 23.12 0.1 ' 195 7.0 37A 20.91 22.11 na . 37B 20.91 27.82 na .' 38 22.12 5.6 23.15 na 26.94 0.1 195 7.0 38A 20.91 29.35 na . . 39 22.12 5.6 20.42 na 25.31 0.1 ' 195 7.0 40 19.41 5.6 23.23 na 26.99 0.1 ' 195: 7.0 40A 20.91 24.47 na 40B 20.91 30.55 na 40C 20.91 35.97 na M8 20.91 41.49 na 76C 20.66 45.81 na M9 20.66 46.96 na 28C 20.66 52.46 na 21C 20.66 53.75 na 13C 20.66 55.21 na 7C 20.66 58.73 na Mil 20.66 59.72 na M12 10.37 65.49 na M13 10.37 66.31 na TOR 10.37 67.12 na , FSI ' 8.37 . 68.01 na FS2 8.37 69.03 na BOR 0.5 72.83 na hG -3.0 74.47 na BF1 2.5 72.36 na .' BF2 2.5 81.37 na UG1 -3.0 84.01 na UG2 -4.0 84.53 na '. SOR -8.0 86.47 na 100.0 . 0
The maximum velocity is 18.32 and it occurs in the pipe between nodes 40A and 40B '
E
Computer Programs by Hydratec Inc. Route 111 Winrlhm M H I IS (ñ7
Final Calculations - Hazen-Williams - 2007
A&D Fire Sprinklers Page 5 Pacific Ridge Date 09-02-09
Nodel Elevi K Qa Nom Fitting Pipe CFact Pt
to or Ftngs Pe Notes Node2 Elev2 Fact Qt Act Eqv. Ln. Total Pf/Ft Pf
30 22.120 5.60 19.50 1 3E 6.914 9.160 120 12.125
to IT 5.762 12.676 -0.056 31A 22.250 19.5 1.08 0.0 21.836 0.1078 2.353 Vel = 6.83
0.0
31A 19.50 14.422 ----K Factor= 5.13
31 21.910 5.60 19.89 1 1E 2.305 3.660 120 12.614
to 2T 11.524 13.829 -0.147 31A22.250 19.89 1.08 0.0 17.489 0.1118 1.955 Vel = 6.97
31A 22.250 19.50 1 0.0 6.500 120 14.422 to 0.0 0.0 0.0 32A 22.250 39.39 1.08 0.0 6.500 0.3957 2.572 Vel = 13.80
0.0
32A 39.39 16.994 K Factor 9.56
32 21.910 5.60 21.89 1 2E 4.61 3.580 120 15.279 to IT 5.762 10.372 -0.147 32A 22.250 21.89 1.08 0.0 13.952 0.1335 1.862 Vel = 7.67
32A 22.250 39.39 1.25 0.0 1.000 120 16.994 . to 0.0 0.0 0.0 33A22.250 61.28 1.408 0.0 1.000 0.2460 0.246 Vel = 12.63
0.0
33A 6.1.28 17.240 KFactor= 14.76
33 22.120 5.60 21.34 1 3E 6.914 9.160 120 14.517 to IT 5.762 12.676 -0.056 33A 22.250 21.34 1.08 0.0 21.836 0.1273 2.779 Vel -7.47
33A 22.250 61.28 1.25 0.0 7.000 120 17.240 to 0.0 0.0 0.0
34A 22.250 82.62 1.408 0.0 7.000 0.4281 2.997 Vel = 17.02
0.0
34A 82.62 20.237 K Factor= 18.37
34 21.910 5.60 24.15 1 1E 2.305 3.080 120 18.600 to IT 5.762 8.067 -0.147
34A 22.250 24.15 1.08 - 0.0 11.147 0.1600 1.784 Vel = 8.46
34A 22.250 82.62 1.5 0.0 1.000 120 20.237 to 0.0 0.0 0.0 35A 22.250 106.77 1.639 0.0 1.000 0.3280 0.328 Vel = 16.24
0.0
35A 106.77 20.565 K Factor = 23.54
35 22.120 5.60 23.06 1 4E 9.219 10.000 120 16.951 to IT 5.762 14.981 -0.056 35A 22.250 23.06 1.08 0.0 24.981 0.1469 3.670 Vel = 8.08
35A 22.250 106.76 2 2E 10.902 7.080 120 20.565 to 0.0 10.902 0.580 35B 20.910 129.82 2.104 0.0 17.982 0.1397 2.512 Vel = 11.98
S 35B
0.0
129.82 23.657 K Factor = 26.69
41 19.410 5.60 26.35 1 1E 2.305 3.450 120 22.141
to IT 5.762 8.067 . -0.650 35B 20.910 26.35 1.08 0.0 11.517 0.1881 2.166 Vel = 9.23
Comouter Proorms by Hvdrter mr. Priit 111 \A!irdhr, M W I IOe rrQ-7
Final Calculations - Hazen-Williams - 2007
A&D Fire Sprinklers Page 6 Pacific Ridge Date 09-02-09
Nodel Elevi K Qa Nom Fitting Pipe CFact Pt
to or Ftng's Pe Notes Node2 Elev2 Fact Qt Act Eqv. Ln. Total Pf/Ft Pf
35B 20.910 129.82 2 1E 5.451 2.450
to IT 10.902 16.353
35C 20.910 156.17 2.104 0.0 18.803
35C 20.910 0.0 2.5 0.0 8.080
to 0.0 0.0
37B 20.910 156.17 2.703 0.0 8.080
0.0
37B 156.17
36 22.120 5.60 23.45 1 5E 11.524 9.440
to IT 5.762 17.286
37A -20.910 23.45 1.08 0.0 26.726
0.0
37A 23.45
37 22.120 5.60 23.12 1 5E 11.524 13.520
to IT 5.762 17.286
37A 20.910 23.12 1.08 0.0 30.806
37A 20.910 23.45 1 IT 5.762 4.830
to 0.0 5.762
37B 20.910 46.57 1.08 0.0 10.592
378 20.910 156.17 2.5 0.0 16.200
to 0.0 0.0
38A 20.910 - 202142.703 0.0 16.200
0.0
38A 202.74
38 22.120 5.60 26.94 1 5E 11.524 11.660
to IT 5.762 17.286
38A 20.910 26.94 1.08 0.0 28.946
38A 20.910 202.74 2.5 0.0 10.160
to 0.0 0.0
408 20.910 229.68 2.703 0.0 10.160
0.0
40B 229.68
120 23.657
0.0
0.1966 3.697 Vel = 14.41
120 27.354
0.0
0.0580 0.469 Vel = 8.73
27.823 K Factor = 29.61
120 17.536
0.524
0.1516 4.051 Vel = 8.21
22.111 K Factor = 4.99
120 17.039
0.524
0.1476 4.548 Vel= 8.10
120 22.111
0.0
0.5393 5.712 Vel= 16.31
120 27.823
0.0
0.0940 1.523 Yel= 11.34
29.346 K Factor = 37.43
120 23.149
0.524
0.1960 5.673 Vel = 9.43
120 29.346
0.0
0.1185 1.204 Vél= 12.84
30.550 KFactor= 41.55
39 22.120 5.60 25.31 1 SE 11.524 8.660 120 20.425 to 0.0 11.524 0.524 40A 20.910 25.31 1.08 0.0 20.184 0.1745 3.523 Vel = 8.86
0.0
40A 25.31 24.472 K Factor = 5.12
40 19.410 5.60 26.99 1 1E 2.305 1.540 120 23.233 to IT 5.762 8.067 -0.650 40A 20.910 26.99 1.08 0.0 9.607 0.1966 1.889 Vel = 9.45 - - 40A 20.910 25.31 1 IT 5.762 3.330 120 24.472 to 0.0 5.762 0.0 40B 20.910 52.3 1.08 0.0 9.092 0.6685 6.078 Vel = 18.32
40B . 20.910 229.68 2.5 3E 27.976 3.330 120 30.550 to 0.0 27.976 0.0 40C 20.910 281.98 2.703 0.0 31.306 0.1732 5.422 Vel = 15.77
400 20.910 0.0 3 2E 20.383 65.660 120 35.972 to 0.0 20.383 0.0 M8 20.910 281.98 3.314 0.0 86.043 0.0642 5.522 Vel = 10.49
Comouter . Proarams by Hvdrat In Rruitp 111 \A/i4h M I-I 11(Z1\ (VIQ7
Final Calculations - Hazen-Williams - 2007
A&D Fire Sprinklers Page 7 Pacific Ridge Date 0902-09
Nodel Elevi K Qa Nom Fitting Pipe CFact Pt
to or Ftngs Pe Notes Node2 Etev2 Fact Qt Act Eqv. Ln. Total Pt/Ft Pf
M8 - 20.910 0.0 3 4E 40.765 24.830 120 41.494 to 0.0 40.765 0.108 76C 20.660 281.98 3.314 0.0 65.595 0.0642 4.211 Vet = 10.49
- 76C 20.660 0.0 3 1E 10.191 7.700 120 45.813 to 0.0 10.191 0.0
M9 20.660 281.98 3.314 0.0 17.891 0.0642 1.149 Vet = 10.49
M9 20.660 0.0 3 2E 20.383 65.330 120 46.962 to 0.0 20.383 0.0 28C 20.660 281.98 3.314 0.0 85.713 0.0642 5.501 - Vet = 10.49
-- 28C 20.660 0.0 3 0.0 20.000 120 52.463 to 0.0 0.0 0.0 21C 20.660 281.98 3.314 0.0 20.000 0.0642 1.284 Vet = 10.49
21C 20.660 0.0 3 0.0 22.830 120 53.747 to 0.0 0.0 0.0 13C 20.660 281.98 3.314 0.0 22.830 0.0642 1.465 Vet = 10.49
13C 20.660 0.0 3 2E .20.383 34.370 120 55.212 to 0.0 20.383 0:0 . 7C 20.660 - 281.98 3.314 0.0 54.753 0.0642 3.515 Vel 10.49
7C 20.660 0.0 3 IE 10.191 5.250 120 58.727 to 0.0 10.191 0.0 Mil 20.660 281.98 3.314 0.0 15.441 0.0642 0.991 Vet = 10.49
Mill 20.660 0.0 3 1E 10.191 10.290 120 59.718 to 0.0 10.191 4.457 M12 10.370 281.98 3.314 0.0 20.481 0.0642 1.314 Vet = 10.49
M12 10.370 0.0 4 1E 13.937 4.250 120 65.489 to iT 27.874 41.811 0.0
- M1310.370
- 281.98 4.31 0.0 46.061 0.0179 0.823 Vel= 6.20
M13 10.370 0.0 4 2E 27.874 17.400 120 66.312
--
to 0.0 27.874 0.0
-TOR 10.370 281.98 4.31 0.0 45.274 0.0178 -.0.808 Vet = 6.20
TOR 10.370 0.0 4 0.0 1.500 120 67.120 to 0.0 0.0 0.866 FS1 8.370 281.98 4.31 0.0 1.500 0.0180 0.027 Vet = 6.20 FS1 8.370 0.0 4 0.0 1.000 120 68.013 to 0.0 0.0 1.000 * Fixed toss = 1 FS2 8.370 281.98 4.31 0.0 1.000 0.0180 0.018 Vet = 6.20
FS2 8.370 0.0 4 1E 13.937 7.870 120 69.031 to 0.0 13.937 3.408 BOR .500 281.98 4.31 0.0 21.807 0.0178 0.389 Vel = 6.20
BOR .500 0.0 6 2E 40.168 11.660 140 72.828 to 0.0 40.168 1.516 UG -3 281.98 6.16 0.0 51.828 0.0024 0.122 Vet = 3.04 UG -3 0.0 6 3E 64.749 60.500 150 74.466 to 0.0 64.749 -2.82 . BF1 2.500 281.98 6.09 0.0 125.249 0.0022 0.275 Vet = 3.11 BF1 2.500 0.0 6 0.0 5.290 140 - 72.359 to 0.0 0.0 9.000 * Fixed toss = 9 BF2 2.500 281.98 6.16 0.0 5.290 0.0025 0.013 Vet = 3.04
Comouter Proarams by Hvdratec Inc. Rni itp. 111 \Aflrrlhm M I-I I 1QA fl'flQ7
Final Calculations - Hazen-Williams - 2007
A&D Fire Sprinklers Page 8
Pacific Ridge Date 09-02-09
Nodel Elevl K Qa Nom Fitting Pipe CFact Pt
to or Ftngs Pe Notes
Node2 Elev2 Fact Qt Act Eqv. Ln. Total Pf/Ft Pf
BF2 2.500 0.0 6 iT 46.249 21.830 150 81.372
to 1G 4.625 94.040 2.382
UG1 -3 281.98 6.09 2E 43.166 115.870 0.0022 0.254 Vel = 3.11
UG1 -3 0.0 8 iF 13.591 85.160 150 84.008
to 1G 6.041 72.487 0.433
UG2 -4 281.98 7.98 IT 52.855 157.647 0.0006 0.093 Vel = 1.81
UG2 -4 0.0 8 3F 40.774 240.400 150 84.534
to iT 52.855 105.711 1.732
SOR -8 281.98 7.98 2G 12.081 346.111 0.0006 0.204 Vel = 1.81
100.00 Qa= 100.00
SOR 381.98 86.470 KFactor= 41.08
Cemnuter Prccirms by Hvrlrnter. Inr Rni itp 111 Windhm KI I-I I I<ZA fV17
... Fire Protection by Computer Design
A&D Fire Sprinklers
11465 Woodside Ave.
Santee ca 92071
619-448-1962
Job Name : Pacific Ridge
Building i FP03 Level 2
Location : 6269 El Fuerte St. Carlsbad CA 92009
System : 2
Contract F-428
Data File Calc-2_1-2-Reading Lounge.WXF
flrmni tr Prrm h, I-1,,-Irf.- In,' Pni On 111 pu Li I I,'
C
A&D Fire Sprinklers Page 1 Pacific Ridge Date 09-02-09
HYDRAULIC CALCULATIONS
for
Project name: Pacific Ridge High School
Location: 6269 El Fuerte St. Carlsbad CA 92009
Drawing no: FP03 Level 2
Date: 09-28-09
Design
Remote area number: 2
Remote area location: Reading Lounge
Occupancy classification: Ligh Hazard
Density: 0.10 - Gpm/SqFt
Area of application: Entire Area - SqFt
Coverage per sprinkler: 210.6 - SqFt
Type of sprinklers calculated: VICTAULIC V27 Pendents
No. of sprinklers calculated: 17
In-rack demand: - GPM
Hose streams: 100 -GPM
Total water required (including hose streams): 461.14 -GPM @ 72.61 -Psi Type of system: TREE
Volume of dry or preaction system: -Gal
Water supply information
Date: 08-20-09
Location: 6269 El Fuerte St. Carlsbad CA 92009
Source: Street Water
Name of contractor: A&D Fire Sprinklers
Address: 11465 Woodside Ave. Santee CA 92071
Phone number: 619-448-1962
Name of designer: Maria lniguez
Authority having jurisdiction: Carlsbad Fire Department
Notes: (Include peaking information or gridded systems here.)
Computer Proarams by Hvdratec Inc RcIItA 111 Afkidhn, M LI I IQA V11107
. . . Water Supply Curve (C)
A&D Fire Sprinklers
Pacific Ridge
Page 2
Date 09-02-09
City Water Supply: Demand: Cl - Static Pressure : 112.5 Dl - Elevation : 14.920 C2 - Residual Pressure: 103.5 D2 - System Flow : 361.146 C2 - Residual Flow : 1075 D2 - System Pressure : 87.811
Hose (Adj City)
Hose ( Demand) : 100
D3 - System Demand : 461.146
Safety Margin : 22.809
150
140
130
p120
R 110
E 100
90
80
fffQ2
—1-13
u 70
R60
E50
40
30
20
D1_ 10
...,. ... ..
200 400 600 800 1000 1200 1400 1600 1800 FLOW (NA1.85)
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
. . . Fittings Used Summary
A&D Fire Sprinklers Page 3
Pacific Ridge Date 09-02-09
Fitting Legend
Abbrev. Name /2 1'/ 1'/z 2 2Y2 3 31/2 4 5 6 8 10 12 14 16 18 20 24
E NFPA 13 90 Standard Elbow 1 2 2 3 4 5 6 7 8 10 12 14 18 22 27 35 40 45 50 61
F NFPA 134SElbow 1 1 1 1 2 2 3 3 3 4 5 7 9 11 13 17 19 21 24 28
G NFPA 13Gate Valve 0 0 0 0 0 1 1 1 1 2 2 3 4 5 6 7 8 10 11 13
T NFPA 13 90 Flow thru Tee 3 4 5 6 8 10 12 15 17 20 25 30 35 50 60 71 81 91 101 121
Units Summary
Diameter Units Inches
Length Units Feet
Flow Units US Gallons per Minute
Pressure Units Pounds per Square Inch
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Pressure / Flow Summary - STANDARD
A&D Fire Sprinklers
Pacific Ridge
Node Elevation K-Fact Pt
No. Actual
65 26.45 5.6 7.1
66 26.45 5.6 7.38
66A 26.95 7.59
67 26.45 5.6 9.22
67A 26.95 9.53
68 26.45 5.6 10.38
68A 26.95 10.74
69 26.45 5.6 11.38
69A 26.95 11.8
70 26.45 5.6 13.0
70A 26.95 13.5
70B 23.25 29.25
71 26.45 5.6 7.0
72 26.45 5.6 7.28
72A 26.95 7.49
73 26.45 5.6 9.1
73A 26.95 9.4
74 26.45 5.6 10.24
74A 26.95 10.6
75 26.45 5.6 11.23
75A 26.95 11.64
76 26.45 5.6 12.82
76A 26.95 13.31
76B 23.25 29.33 76C 22.08 34.95
M9 20.66 37.38
28C 20.66 46.07
21C 20.66 48.1
13C 20.66 50.42
7C 20.66 55.97
Mu 20.66 57.54
M12 10.37 64.07
M13 10.37 65.37
TOR 10.37 66.65
FS1 8.37 67.56
FS2 8.37 68.59
BOR 0.5 72.61
UG -3.0 74.32
BF1 2.5 72.37
BF2 2.5 82.39
UG1 -3.0 85.18
UG2 -4.0 85.76
SOR -8.0 87.81
77 20.16 5.6 29.89
77A 20.91 32.8
77B 20.91 33.15
78 20.16 5.6 29.9
78A 20.91 33.16
79 20.16 5.6 29.94
79A 20.91 33.21
80 20.16 5.6 30.02
80A 20.91 33.29 81 20.16 5.6 30.19
81A 20.91 33.49
M8 20.91 34.09
Page 4
Date 09-02-09
Pn Flow
Actual
Density Area Press
na 14.92 0.1 122.4 7.0
na 15.22 0.1 122.4 7.0 na
na 17.01 0.1 122.4 7.0
na
na 18.04 0.1 122.4 7.0
na
na 18.89 0.1 122.4 7.0
na
na 20.19 0.1 122.4 7.0
na
na
na 14.82 0.1 122.4 7.0
na 15.11 0.1 122.4 7.0 na
na 16.89 0.1 122.4 7.0
na
na 17.92 0.1 122.4 7.0 na
na 18.76 0.1 122.4 7.0
na
na 20.05 0.1 122.4 7.0
na
na
na
na
na
na
na
na
na
na
na
na
na
na
na
na
na
na
na
na
na 100.0
na 30.61 0.1 1 7.0
na
na
na 30.62 0.1 1 7.0 na
na 30.64 0.1 1 7.0 na
na 30.68 0.1 1 7.0 na
na 30.77 0.1 1 7.0 na
na
The maximum velocity is 15.86 and it occurs in the pipe between nodes 70A and 70B
Cnmniitr Prnnrm hv Hvdrtr. Inr' Pniifo 111 \Ahindhrn KI I-I I IQt ()Qr07
Vel = 5.23
K Factor = 5.41 -
Vel =5.33
Vel 10.56
K Factor= 9.76
Vel _5.96
Vel 9.71
K Factor = 14.38
Vel = 6.32
Vel _9.91
KFactor _18.97
Vel= 6.62
Vel= 12.79
K Factor = 22.88
Vel =
Vel=
Vel=
7.07
15.86
5.83
K Factor = 19.25
Final Calculations - Hazen-Williams - 2007
A&D Fire Sprinklers Page 5 Pacific Ridge Date 09-02-09
Nodel Elevl K Qa Nom Fitting Pipe CFact Pt to - or Ftng's Pe ******* Notes Node2 Elev2 Fact Qt Act Eqv. Ln. Total Pf/Ft Pf
65 26.450 5.60 14.92 1 1E 2.305 8.540 120 7.098 to 0.0 2.305 -0.217 66A26.950 - 14.92 1.08 0.0 10.845 0.0657 0.712
0.0
66A 14.92 7.593
66 26.450 5.60 15.22 1 iT 5.762 0.500 120 7.383 to 0.0 5.762 -0.217 66A26.950 15.22 1.08 0.0 6.262 0.0682 0.427
66A 26.950 14.92 1 0.0 8.040 120 7.593 to 0.0 0.0 0.0 67A 26.950 30.14 1.08 0.0 8.040 0.2410 1.938
0.0
67A 30.14 9.531
67 26.450 5.60 17.01 1 1 5.762 0.500 120 9.224 to 0.0 5.762 -0.217 67A 26.950 17.01 1.08 0.0 6.262 0.0837 0.524
67A 26.950 30.13 1.25 0.0 8.000 120 9.531 S to 0.0 0.0 0.0 68A 26.950 47.14 1.408 0.0 8.000 0.1516 1.213
0.0
68A ____47.14 10.744
68 26.450 5.60 18.04 1 1 5.762 0.500 120 10.377 to 0.0 5.762 -0.217 68A26.950 18.04 1.08 0.0 6.262 0.0933 0.584
68A 26.950 47.14 1.5 0.0 8.040 120 10.744 to 0.0 0.0 0.0 69A 26.950 65.181.639 0.08.040 0.13181.060
0.0
69A 65.18 11.804
69 26.450 5.60 18.89 1 1 5.762 0.500 120 11.384 to 0.0 5.762 -0.217 69A26.950 18.89 1.08 0.0 6.262 0.1017 b.637
69A 26.950 65.19 1.5 0.0 8.040 120 11.804 to 0.0 0.0 0.0 70.A----26.950 84.081.639 0.08.0400.21091.696
0.0
70A 84.08 13.500
70 26.450 5.60 20.19 1 iT 5.762 0.500 120 12.997 to 0.0 5.762 -0.217 70A 26.950 20.19 1.08 0.06.262 0.1150 0.720
70A 26.950 84.08 1.5 4E 17.453 18.830 120 13.500 to 1 8.727 26.180 1.602 70B 23.250 104.27 1.639 0.0 45.010 0.3142 14.143
5 70B
to
23.250 0.0 2.5 0.0
0.0
3.200
0.0
120 29.245
0.0 76B23.250 104.27 2.703 0.0 3.200 0.0275 0.088
0.0
76B 104.27 29.333
Computer Proarams by Hvdratec Inc Rriif p ill \Ahir,dhn M U I IQA ry,r01
0 Final Calculations - Hazen-Williams - 2007
A&D Fire Sprinklers Page 6 Pacific Ridge Date 09-02-09
Nodel Elevi K Qa Nom Fitting Pipe CFact Pt to or Ftngs Pe Notes Node2 Elev2 Fact Qt Act Eqv. Ln. Total Pf/Ft Pf
71 26.450 5.60 14.82 1 IE 2.305 8.540 120 7.000 to 0.0 2.305 -0.217 72A 26.950 14.82 1.08 0.0 10.845 0.0648 0.703 Vel = 5.19
0.0
72A 14.82 7.486 KFactor = 5.42 72 26.450 5.60 15.11 1 IT 5.762 0.500 120 7.282 to 0.0 5.762 -0.217 72A 26.950 15.11 1.08 0.0 6.262 0.0672 0.421 Vel = 5.29
72A 26.950 14.82 1 0.0 8.040 120 7.486 to 0.0 0.0 0.0 73A 26.950 29.93 1.08 0.0 8.040 0.2381 1.914 VeI= 10.48
0.0
73A 29.93 9.400 K Factor _=9.76 - 73 26.450 5.60 16.89 1 1 5.762 0.500 120 9.099 to
. 0.0 5.762 -0.217 73A - 26.950 16.89 1.08 00 6.262 0.0827 0.518 Vel = 5.92 -
S 73A
to
26.950 29.93 1.25 0.0
0.0
8.000
0.0
120 9.400
0.0 74A 26.950 46.821.408 0.0 8.000 0.1498 1.198 Vel = 9.65
0.0
74A 46.82 10.598 K Factor = 14.38
74 26.450 5.60 17.92 1 IT 5.762 0.500 120 10.238 to 0.0 5.762 -0.217 74A 26.950 17.92 1.08 0.0 6.262 0.0921 0.577 Vel = 6.28
74A 26.950 46.82 1.5 0.0 8.000 120 10.598 to 0.0 0.0 0.0 75A 26.950 64.74 1.639 0.0 8.000 0.1301 1.041 Vel= 9.84
0.0
75A - 64.74 11.639 KFactor= 18.98
75 26.450 5.60 18.76 1 IT 5.762 0.500 120 11.227 to 0.0 5.762 -0.217 75A 26.950 18.76 1.08 0.0 6.262 0.1004 0.629 Vel = 6.57 75A 26.950 64.74 1.5 0.0 8.040 120 11.639 to 0.0 0.0 0.0 76A 26.950 83.5 1.639 0.0 8.040 0.2083 1.675 Vel = 12.70
0.0
76A 83.50 13.314 KFactor= 22.88 76 26.450 5.60 20.05 1 IT 5.762 0.500 120 12.820 to 0.0 5.762 -0.217 76A 26.950 20.05 1.08 0.0 6.262 0.1135 0.711 Vel -7.02 76A 26.950 83.50 1.5 4E 17.453 20.290 120 13.314 - - to IT 8.727 26.180 1.602 76B 23.250 103.55 1.639 0.0 46.470 0.3102 14.417 Vel = 15.75 76B 23.250 104.27 2.5 2E 18.651 14.580 120 29.333 to
.
IT 18.651 37.302 0.507 76C 22.080 207.82 2.703 0.0 51.882 0.0985 5.109 Vel = 11.62
- 76C 22.080 153.33 3 1E 10.191 7.700 120 34.949 to 0.0 10.191 0.615 M9 20.660 361.15 3.314 0.0 17.891 0.1014 1.815 Vel = 13.43
Computer ProqramsbvHvdratecInc. Rciitp 111 \NinThm 1\1 w I 4Z A (tQ7
0 Final Calculations - Hazen-Williams - 2007
A&D Fire Sprinklers Page 7 Pacific Ridge Date 09-02-09
Nodel Elevi K Qa Nom Fitting Pipe CFact Pt
to or Ftngs Pe ******* Notes Node2 Elev2 Fact Qt Act Eqv. Ln. Total Pf/Ft Pf
M920.660 0.0 3 2E 20.383 65.330 120 37.379 to 0.0 20.383 0.0 280 20.660 361.15. 3.314 0.0 85.713 0.1014 8.695 Vel = 13.43
28C 20.660 0.0 3 0.0 20.000 120 46.074 to 0.0 0.0 0.0 210 20.660 361.15 3.314 0.0 20.000 0.1014 2.029 Vel = 13.43
21C 20.660 0.0 3 0.0 22.830 120 48.103
to 0.0 0.0 0.0 13C 20.660 361.15 3.314 0.0 22.830 0.1014 2.316 Vel = 13.43
13C 20.660 0.0 3 2E 20.383 34.370 120 50.419 to 0.0 20.383 0.0 7C 20.660 361.15 3.314 0.0 54.753 0.1015 5.555 VeI= 13.43
7C 20.660 0.0 3 1E 10.191 5.250 120 55.974
to 0.0 10.191 0.0 M11 20.660 361.15 3.314 0.0 15.441 0.1014 1.566 Vel = 13.43
Mil 20.660 0.0 3 1E 10.191 10.290 120 57.540 to 0.0 10.191 4.457 M12 10.370 361.15 3.314 0.0 20.481 0.1015 2.078 Vel = 13.43
M12 10.370 0.0 4 1E 13.937 4.250 120 64.075 to IT 27.874 41.811 0.0 M13 10.370 361.15 4.31 0.0 46.061 0.0282 1.299 Vel = 7.94
M13 10.370 0.0 4 2E 27.874 17.400 120 65.374 to 0.0 27.874 0.0 TOR 10.370 361.15 4.31 0.0 45.274 0.0282 1.278 Vel= 7.94
TOR 10.370 0.0 4 0.0 1.500 120 66.652 to 0.0 0.0 0.866 F518.370 361.15 4.31 0.0 1.500 0.0280 0.042 Vel= 7.94
FS1 8.370 0.0 4 0.0 1.000 120 67.560 to 0.0 0.0 1.000 * Fixed loss FS2 8.370 361.15 4.31 0.0 1.000 0.0280 0.028 Vel = 7.94
FS2 8.370 0.0 4 1E 13.937 7.870 120 68.588 to 0.0 13.937 3.408 BOR .500 361.15 4.31 0.0 21.807 0.0282 0.616 Vel = 7.94
BOR .500 0.0 6 2E 40.168 11.660 140 72.612 to 0.0 40.168 1.516 UG -3 361.15 6.16 0.0 51.828 0.0037 0.193 Vel = 3.89
U -3 0.0 6 3E 64.749 60.500 150 74.321 to 0.0 64.749 -2.382 BF1 2.500 361.15 6.09 0.0 125.249 0.0035 0.434 Vel = 3.98 BF1 2.500 0.0 6 0.0 5.290 140 72.373 to 0.0 0.0 10.000 * Fixed loss = 10 6F22.500 361.15 6.16 0.0 5.290 0.0038 0.020 Vel= 3.89
BF2 2.500 0.0 6 IT 46.249 21.830 150 82.393 to 1G 4.625 94.040 2.382 S UG1 -3 361.156.092E43.166115.8700.00350.402 Vel = 3.98
UG1 -3 0.0 8 IF 13.591 85.160 150 85.177 to 1G 6.041 72.487 0.433 UG2 -4 361.15 7.98 IT 52.855 157.647 0.0009 0.147 Vel = 2.32
Computer Procrams by Hvdratec Inc. Route 111 Winrhm NJ I- I I (Vfl7
40.774 240.400 150 85.757
52.855 105.711 1.732
12.081 346.111 0.0009 0.322 Vel = 2.32
4.61 2.660
5.762 10.372
0.0 13.032
8.727 2.000
0.0 8.727
0.0 10.727
120
- 0.2482
120
0.0326
87.811
29.887
-0.325
3.235
32.797
0.0
0.350
Qa = 100.00
KFactor= 49.21
Vel = 10.72
Vel = 4.65
0.0 12.000 120 33.147
0.0 0.0 0.0
0.0 12.000 0.0010 0.012 Vel = 1.14
33.159 K Factor = 5.32
4.61 4.080 120 29.896
5.762 10.372 -0.325
0.0 14.452 - 0.2483 3.588 Vel = 10.72
0.0 14.000 120 33.159
0.0 0.0 0.0
0.0 14.000 0.0039 0.054 Vel = 2.28
Final Calculations - Hazen-Williams - 2007
A&D Fire Sprinklers Page 8
Pacific Ridge Date 09-02-09
Nodel Elevi K Qa Nom Fitting Pipe CFact Pt
to or Ftng's Pe Notes
Node2 Elev2 Fact Qt Act Eqv. Ln. Total Pf/Ft Pf
UG2 -4 0.0 8 3F
to IT
SOR-8 361.15 7.98 2G-
100.00
SOR 461.15
77 20.160 5.60 30.61 1 2E
to IT
77A - 20.910 30.61 1.08
77A 20.910 0.0 1.5 IT
to
77B 20.910 30.61 1.639
77B 20.910 0.0 3
to
78A 20.910 30.61 3.314
0.0
78A 30.61
78 20.160 5.60 30.62 1 2E
to IT
78A 20.910 30.62 1.08
78A 20.910 30.61 3
to
79A - 20.910 61.23 3.314
0.0
79A 61.23 33.213 KFactor= 10.62
79 20.160 5.60 30.64 1 2E 4.61 4.080 120 29.944
to IT 5.762 10.372 -0.325
79A 20.910 30.64 1.08 0.0 14.452 0.2487 3.594 Vel = 10.73
79A 20.910 61.24 3 0.0 10.000 120 33.213
to 0.0 0.0 0.0
80A 20.910 91.88 3.314 0.0 10.000 - 0.0080 0.080 Vel = 3.42
0.0
BOA 91.88 33.293 K Factor= 15.92
80 20.160 5.60 30.68 1 2E 4.61 4.080 120 30.016
to IT 5.762 10.372 -0.325
BOA 20.910 30.68 1.08 0.0 14.452 0.2492 3.602 Vel = 10.74
80A 20.910 91.88 3 0.0 14.000 120 33.293
to 0.0 0.0 0.0
81 20.910 122.56 3.314 0.0 14.000 0.0138 0.193 Vel = 4.56
0.0
81A 122.56 33.486 KFactor= 21.18
81 20.160 5.60 30.77 1 2E 4.61 4.080 120 30.189
to IT 5.762 10.372 -0.325
81A 20.910 30.77 1.08 0.0 14.452 0.2506 3.622 Vel = 10.78
81A 20.910 122.56 3 2E 20.383 8.750 120 33.486 S to 0.0 20.383 0.0
M8 20.910 153.33 3.314 0.0 29.133 0.0208 0.605 Vel = 5.70
M8 20.910 0.0 3 4E 40.765 24.830 120 34.091
to 0.0 40.765 -0.507
760 22.080 153.33 3.314 0.0 65.595 0.0208 1.365 Vel 5.70
Comouter Proarams by Hvdratec Inc. Route 111 Winrlhm N H t IRA flI7
Final Calculations - Hazen-Williams - 2007
A&D Fire Sprinklers Page 9 Pacific Ridge Date 09-02-09
Nodel Elevi K Qa Nom Fitting Pipe CFact Pt
to or Ftngs Pe Notes Node2 Elev2 Fact Qt Act Eqv. Ln. Total Pf/Ft Pf
0.0
76C 153.33 34.949 KFactor 25.94
Computer Proarams by Hvdratec Inc. Rott 111 \A/inr1hm ri -i I IA nro7
- - Fire Protection by Computer Design
A&D Fire Sprinklers
11465 Woodside Ave.
Santee ca 92071
619-448-1962
Job Name : Pacific Ridge
Building : FP03 Level 2
Location : 6269 El Fuerte St. Carlsbad CA 92009
System : 3
Contract : F-428
Data File : Calc-3_L2-classroom.WXF
('.rmr,i itr Prr)nrqmQ h, I-h,dri,' I,,- Q— fn -iii I;.--Jl.-..._ ,,
I
A&D Fire Sprinklers Page 1
Pacific Ridge Date 09-02-09
HYDRAULIC CALCULATIONS
for
Project name: Pacific Ridge High School
Location: 6269 El Fuerte St. Carlsbad CA 92009
Drawing no: FP03 Level 2
Date: 09-28-09
Design
Remote area number: 3
Remote area location: Classrooms
Occupancy classification: Ligh Hazard
Density: 0.10 - Gpm/SqFt
Area of application: 1000 - SqFt
Coverage per sprinkler: 190 - SqFt
Type of sprinklers calculated: VICTAULIC V27 Pendents
No. of sprinklers calculated: 14
In-rack demand: - GPM
Hose streams: 100 -GPM
Total water required (including hose streams): 373.12 -GPM @ 72.13 - Psi
Type of system: TREE
Volume of dry or preaction system: -Gal
Water supply information
Date: 08-20-09
Location: 6269 El Fuerte St. Carlsbad CA 92009
Source: Street Water
Name of contractor: A&D Fire Sprinklers
Address: 11465 Woodside Ave. Santee CA 92071
Phone number: 619-448-1962
Name of designer: Maria lniguez
Authority having jurisdiction: Carlsbad Fire Department
Notes: (Include peaking information or gridded systems here)
D-.rr, h, W,,eqrnfpr Inr. Rrnif. 111 Windhm N.H. USA 03087
. . . Water Supply Curve (C)
A&D Fire Sprinklers
Pacific Ridge Page 2
Date 09-02-09
City Water Supply: Demand: Cl - Static Pressure : 112.5 Dl - Elevation : 11.980 C2 - Residual Pressure: 103.5 D2 - System Flow : 273.12 C2 - Residual Flow : 1075 D2 - System Pressure : 84.720
Hose (Adj City)
Hose ( Demand) : 100
D3 - System Demand : 373.12
Safety Margin : 26.509
140
150
130
p120
110
-;j—
R
E 100
90 2 S
80 -*— /D3
u 70
R6°
E5°
40
30
20
10 :
200 400 600 800 1000 1200 1400 1600 1800
FLOW ( N ' 1.85)
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
. I • Fittings Used Summary
A&D Fire Sprinklers Page 3
Pacific Ridge Date 09-02-09
Fitting Legend
Abbrev. Name '/ 1/. 1 1% 1'/z 2 21/2 3 31/2 4 5 6 8 10 12 14 16 18 20 24
E NFPA 13 90' Standard Elbow 1 2 2 3 4 5 6 7 8 10 12 14 18 22 27 35 40 45 50 61
F NFPA 13 45 Elbow 1 1 1 1 2 2 3 3 3 4 5 7 9 11 13 17 19 21 24 28
G NFPA 13 Gate Valve 0 0 0 0 0 1 1 1 1 2 2 3 4 5 6 7 8 10 11 13
T NFPA 139O Flow thruTee 3 4 5 6 8 10 12 15 17 20 25 30 35 50 60 71 81 91 101 121
Units Summary
Diameter Units Inches
Length Units Feet
Flow Units US Gallons per Minute
Pressure Units Pounds per Square Inch
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Pressure I Flow Summary - STANDARD
A&D Fire Sprinklers Page 4
Pacific Ridge Date 09-02-09
Node Elevation K-Fact Pt Pn Flow Density Area Press
No. Actual Actual -Req.
15 19.66 5.6 10.33 na 18.0 0.1 180 7.0
16 19.66 5.6 10.95 na 18.53 0.1 180 7.0
16A 21.16 12.1 na
17 19.66 5.6 11.04 na 18.61 0.1 180 7.0
18 19.66 5.6 11.28 na 18.81 0.1 180 7.0
18A 21.16 11.36 na
18B 21.16 14.68 na
19 19.66 5.6 12.71 na 19.96 0.1 180 7.0
20 19.66 5.6 12.96 na 20.16 0.1 180 7.0
20A 21.16 13.86 na
21 19.66 5.6 16.02 na 22.42 0.1 180 7.0
21A 21.16 17.47 na
21B 21.16 17.75 na
22 19.66 5.6 10.4 na 18.06 0.1 180 7.0
23 19.66 5.6 11.01 na 18.58 0.1 180 7.0
23A 21.16 12.13 na
24 19.66 5.6 11.2 na 18.74 0.1 180 7.0
25 19.66 5.6 11.44 na 18.94 0.1 180 7.0
25A 21.16 11.53 na
25B 21.16 14.72 na
26 19.66 5.6 15.29 na 21.9 0.1 180 7.0
26A 21.16 17.13 na
27 19.66 5.6 12.96 na 20.16 0.1 180 7.0
28 19.66 5.6 13.09 na 20.26 0.1 180 7.0
28A 21.16 14.12 na •
28B 21.16 18.07 na
28C 20.66 53.25 na
21C 20.66 53.59 na
13C 20.66 54.97 na
7C 20.66 58.28 na
Mil 20.66 59.22 na
M12 10.37 64.91 na
M13 10.37 65.69 na
TOR 10.37 66.45 na
FS1 8.37 67.34 na
FS2 8.37 68.36 na
BOR 0.5 72.13 na
UG -3.0 73.77 na
BF1 2.5 71.64 na
BF2 2.5 79.65 na
UG1 -3.0 82.28 na
UG2 -4.0 82.8 na
SOR -8.0 84.72 na 100.0
The maximum velocity is 28.16 and it occurs in the pipe between nodes 28B and 28C
Comøuter Proarams by Hvdratec Inc. Route 111 Windham N.H. USA 03087
Final Calculations - Hazen-Williams - 2007
A&D Fire Sprinklers Page 5 Pacific Ridge Date 09-02-09
Nodel Elevl K Qa Nom Fitting Pipe CFact Pt to or Ftngs Pe Notes Node2 Elev2 Fact Qt Act Eqv. Ln. Total Pf/Ft Pf
15 19.660 5.60 18.00 1 3E 6.914 13.330 120 10.332 to iT 5.762 12.676 -0.650 16A 21.160 18.0 1.08 0.0 26.006 0.0929 2.417 Vel = 6.30
0.0
16A 18.00 12.099 K Factor = 5.17
16 19.660 5.60 18.53 1 3E 6.914 5.660 120 10.950 to 1 5.762 12.676 -0.650 16A 21.160 18.53 1.08 0.0 18.336 0.0981 1.799 Vel = 6.49 16A 21.160 18.00 1 0.0 7.500 120 12.099 to 0.0 0.0 0.0 18B 21.160 36.53 1.08 0.0 7.500 0.3441 2.581 Vel= 12.79
0.0
18B 36.53 - 14.680 K Factor = 9.53
17 19.660 5.60 18.61 1 1E 2.305 7.500 120 11.041 to 0.0 2.305 -0.650 18A 21 .160 18.611.08 0.09.805 0.0989 0.970Vel= 6.52
0.0 . 18A 1861 -. 11.361KFactor=5.52
18 19.660 5.60 18.81 1 1 5.762 1.500 120 11.278 to 0.0 5.762 -0.650 18A 21.160 18.811.08 0.0 7.262 0.1009 0.733 Vel = 6.59 18A 21.160 18.60 1 1E 2.305 1.160 120 11.361 to iT 5.762 8.067 0.0 18B21.160 37.411.08 0.09.2270.3597 3.319 Vel =13.10
18B 21.160 36.54 1.25 0.0 8.000 120 14.680 to 0.0 0.0 0.0 .11 _21.160 73.951.408 0.08.0000.3488 2.790 Vel =15.24
0.0
21A 73.95 - 17.470 K Factor 17.69
19 19.660 5.60 19.96 1 3E 6.914 9.080 120 12.710 to 0.0 6.914 -0.650 20A21.160 19.96 1.08 0.0 15.994 0.1125 1.800 Vel = 6.99
0.0
20A 19.96 13.860 K Factor= 5.36
20 19.660 5.60 20.16 1 1E 2.305 5.500 120 12.956 to 1 5.762 8.067 -0.650 20A 21.160 20.16 1.08 0.0 13.567 0.1145 1.554 Vel = 7.06
20A 21.160 19.96 1 iT 5.762 3.750 120 13.860 to 0.0 5.762 0.0 21B 21.160 40.12 1.08 0.0 9.512 0.4094 3.894 Vel = 14.05
0.0
21B 40.12 17.754 KFactor= 9.52 21 19.660 5.60 22.42 1 2E 4.61 4.660 120 16.023 to iT 5.762 10.372 -0.650 S 21A 21.160 22.42 1.08 0.0 15.032 0.1395 2.097 Vel = 7.85 21A 21.160 73.94 1.25 0.0 0.500 120 17.470 to . 0.0 0.0 0.0 21B 21.160 96.36 1.408 0.0 0.500 0.5680 0.284 Vel = 19.86
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA flflR7
Final Calculations - Hazen-Williams - 2007
A&D Fire Sprinklers Page 6 Pacific Ridge Date 09-02-09
Nodel Elevi K Qa Nom Fitting Pipe CFact Pt to or Ftngs Pe Notes Node2 Elev2 Fact Qt Act Eqv. Ln. Total Pf/Ft Pf
9.925 16.330
6.617 16.542
0.0 32.872
6.914 12.700
5.762 12.676
0.0 25.376
6.914 5.290
5.762 12.676
0.0 17.966
0.0 7.500
0.0 0.0
0.0 7.500
2.305 7.500
0.0 2.305
0.0 9.805
5.762 1.500
0.0 5.762
0.0 7.262
2.305 0.700
5.762 8.067
0.0 8.767
0.0 6.830
0.0 0.0
0.0 6.830
6.914 8.950
0.0 6.914
0.0 15.864
6.914 5.950
5.762 12.676
0.0 18.626
0.0 1.660
0.0 0.0
0.0 1.660
21B 21.160 40.12 1.25 3E
to iT
210 20.660 136.48 1.408
0.0
210 136.48
22 19.660 5.60 18.06 1 3E
to 1
23A 21.160 18.06 1.08
0.0
23A 18.06
23 19.660 5.60 18.58 1 3E
to 1
23A 21.160 18.58 1.08
23A 21.160 18.06 1
to
! 21.160 36.64 1.08
0.0
25B 36.64
24 19.660 5.60 18.74 1 1E
to
25A 21.160 18.74 1.08
0.0
25A 18.74
25 19.660 5.60 18.94 1 IT
to
25A 21.160 18.94 1.08
25A 21.160 18.74 1 1E
to 1
25B 21.160 37.68 1.08
25B 21.160 36.64 1.25
to
26A 21.160 74.32 1.408
0.0
26A 74.32
26 19.660 5.60 21.90 1 3E
to iT
26A 21.160 21.9 1.08
26A 21.160 74.32 1.25
to
28B 21.160 96.22 1.408
0.0
28B 96.22
27 19.660 5.60 20.16 1 3E
.to
28A 21.160 20.16 1.08
0.0
28A 20.16
120 17.754
0.217
1.0835 35.618
53.589
120 10.405
-0.650
0.0936 2.374
12.129
120 11.008
-0.650
0.0986 1.771
120 12.129
0.0
0.3461 2.596
14.725
120 11.198
-0.650
0.1002 0.982
11.530
120 11.438
-0.650
0.1022 0.142
120 11.530
0.0
0.3644 3.195
120 14.725
0.0
0.3520 2.404
17.129
120 15.291
-0.650
0.1336 2.488
120 17.129
0.0•
0.5675 0.942
18.071
120 12.956
-0.650
0.1146 1.818
14.124
VeI= 28.12
K Factor = 18.64
Vel= 6.32
KFactor= 5.19
Vel =-6.51
Vel= 12.83
KFactor 9.55
Vel=6.56
K Factor= 5.52
Vel = 6.63
Vel= 13.20
VeI= 15.31
KFactor 17.96
Vel = 7.67
Vel = 19.83
K Factor = 22.63
Vel= 7.06
K Factor= 5.36
Computer Programs by Hydratec Inc. Route 111 Windham N.H I IRA (VftR7
0 Final Calculations - Hazen-Williams - 2007
A&D Fire Sprinklers Page 7
Pacific Ridge Date 09-02-09
Nodel Elevi K Qa Nom Fitting Pipe CFact Pt
to or Ftngs Pe Notes
Node2 Elev2 Fact Qt Act Eqv. Ln. Total Pf/Ft Pt
28
to
28A
28A
to
28B
28B
to
28C
5.60 20.26 1 1E 2.305 6.500
1 5.762 8.067
20.26 1.08 0.0 14.567
19.660
21.160
21.160
21.160
21.160
20.660
2016 1 iT
40.42 1.08
96.22 1.25 3E
iT
136.64 1.408
5.762 3.750
0.0 5.762
0.0 9.512
9.925 15.660
6.617 16.542
0.0 32.202
120 13.089
-0.650
0.11571.685
120 14.124
0.0
0.41493.947
120 18.071
0.217
1.0858 34.965
Vel 7.10
Vel =14.16
Vel = 28.16
28C 20.660 0.0 3
to
21C 20.660 136.64 3.314
21C 20.660 136.48 3
to
13C 20.660 273.12 3.314
13C 20.660 0.0 3 2E
S to 7C 20.660 273.12 3.314
7C 20.660 0.0 3 1E
to
Mil 20.660 273.12 3.314
Mil 20.660 0.0 3 1E
to
M12 10.370 273.12 3.314
M12 10.370 0.0 4 1E
to 1
M13 10.370 273.12 4.31
M13 10.370 0.0 4 2E
to
TOR 10.370 273.12 4.31
TOR 10.370 0.0 4
to
FS1 -8.370 273.124.31
FS1 8.370 0.0 4
to
FS2 8.370 273.12 4.31
FS2 8.370 0.0 4 1
to
BOR .500 273.12 4.31
BOR .500 0.0 6 2E
to
UG -3 273.126.16
UG -3 0.0 6 3E . to
BF1 2.500 273.126.09
BF1 2.500 0.0 6
to
BF2 2.500 273.12 6.16
120 53.253
0.0
0.0168 0.336 Vel = 5.08
120 53.589
0.0
006051.382 Vel =10.16
120 54.971
0.0
0.0605 3.313 Vel = 10.16
120 58.284
0.0
0.0605 0.934 Vel = 10.16
120 59.218
4.457
0.06051.239 Vel _10.16
120 64.914
0.0
0.0168 0.775 Vel = 6.01
120 65.689
0.0
0.0168 0.761 Vel = 6.01
0.0 1.500 120 66.450
0.0 0.0 0.866
0.01.5000.01730.026 Vel _6.01
0.0 1.000 120 67.342
0.0 0.0 1.000 * Fixed loss = 1
0.0 1.000 0.0170 0.017 Vel = 6.01
13.937 7.870 120 68.359
0.0 13.937 3.408
0.0 21.807 0.0168 0.367 Vel = 6.01
40.168 11.660 140 72.134
0.0 40.168 1.516
0.0 51.828 0.0022 6.115 Vel = 2.94_
64.749 60.500 150 73.765
0.0 64.749 -2.382
0.0125.249 0.00210.259Vel = 3.01
0.0 5.290 140 71.642
0.0 0.0 8.000 * Fixed loss = 8
0.0 5.290 0.0023 0.012 Vel = 2.94
0.0 20.000
0.0 0.0
0.0 20.000
0.0 22.830
0.0 0.0
0.0 22.830
20.383 34.370
0.0 20.383
0.0 54.753
10.191 5.250
0.0 10.191
0.0 15.441
10.191 10.290
0.0 10.191
0.0 20.481
13.937 4.250
27.874 41.811
0.0 46.061
27.874 17.400
0.0 27.874
0.0 45.274
ComDuter Proarams by Hvdratec Inc. Route 111 Windham N.H. USA 03087
Final Calculations - Hazen-Williams - 2007
A&D Fire Sprinklers Page 8 Pacific Ridge Date 09-02-09
Nodel Elevi K Qa Nom Fitting Pipe CFact Pt
to or Ftng's Pe Notes ******
Node2 Elev2 Fact Qt Act Eqv. Ln. Total Pf/Ft Pf
BF2 2.500 0.0 6 iT 46.249 21.830 150 79.654
to 1G 4.625 94.040 2.382 UG1-3 273.12 6.09 2E 43.166 115.870 0.0021 0.240 Vel = 3.01
UG1 -3 0.0 8 1 52.855 85.160 150 82.276 to 1 13.591 72.487 0.433 UG2 -4 273.12 7.98 1 6.041 157.647 0.0006 0.087 Vel = 1.75
UG2 -4 0.0 8 3F 40.774 240.400 150 82.796 to iT 52.855 105.711 1.732 SOR -8 273.12 7.98 2G 12.081 346.111 0.0006 0.192 Vel = 1.75
100.00 Qa = 100.00 SOR 373.12 84.720 K Factor= 40.54
Computer Programs by Hydratec Inc. Route lii Windhm N k i IA fl'f7
AL
pw.~.Ll.~Mq
- - - Fire Protection by Computer Design
A&D Fire Sprinklers
11465 Woodside Ave.
Santee ca 92071
619-448-1962
Job Name Pacific Ridge
Building : FP03 Level 2
Location : 6269 El Fuerte St. Carlsbad CA 92009
System : 4
Contract F-428
Data File t Calc-4_L2-bio-chem-grid.WXF
171
S
Computer ProQrams by Hvdratec inc. Rotitp.111 \Ahinrihm NI 4 I It 1VrQ7
A&D Fire Sprinklers Page 1
Pacific Ridge Date 09-02-09
HYDRAULIC CALCULATIONS
for
Project name: Pacific Ridge High School
Location: 6269 El Fuerte St. Carlsbad CA 92009
Drawing no: FP03 Level 2
Date: 09-28-09
Design
Remote area number: 4
Remote area location: Bio./Chem.
Occupancy classification: Ordinary Hazard
Density: 0.20 - Gpm/SqFt
Area of application: Entire Area - SqFt
Coverage per sprinkler: 117 - SqFt
Type of sprinklers calculated: VICTAULIC V27 Pendents
No. of sprinklers calculated: 13
In-rack demand: - GPM
Hose streams: 250 - GPM
Total water required (including hose streams): 608.24 -GPM @ 67.27 - Psi
Type of system: TREE
Volume of dry or preaction system: -Gal
S Water supply information
Date: 08-20-09
Location: 6269 El Fuerte St. Carlsbad CA 92009
Source: Street Water
Name of contractor. A&D Fire Sprinklers
Address: 11465 Woodside Ave. Santee CA 92071
Phone number: 619-448-1962
Name of designer: Maria lniguez
Authority having jurisdiction: Carlsbad Fire Department
Notes: (Include peaking information or gridded systems here.)
I]
('.rmnijtpr Prcirm by Hvdrntp.c nc'. Rntitp 111 Winrlhm N H LiSA OflR7
Water Supply Curve (C)
A&D Fire Sprinklers Page 2
Pacific Ridge Date 09-02-09
City Water Supply: Demand:
Cl - Static Pressure : 112.5 Dl- Elevation : 11.980
C2 - Residual Pressure: 103.5 D2 - System Flow : 358.247
C2 - Residual Flow : 1075 D2 - System Pressure : 77.458
Hose (Adj City)
Hose ( Demand ) : 250
D3 - System Demand : 608.247
Safety Margin : 31.904
150
140
130
p120 C11
R 110
E 100
90
D2 580
u 70 D3
R6°
E50
40
30
20
10 D1
.a.... .. ... ..
200 400 600 800 1000 1200 1400 1600 1800
FLOW( N"1.85)
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
. . . Fittings Used Summary
A&D Fire Sprinklers Page 3
Pacific Ridge Date 09-02-09
Fitting Legend
Abbrev. Name 1/2 3/ 1 11/i 1% 2 21/. 3 3% 4 5 6 8 10 12 14 16 18 20 24
E NFPA139OStandardElbow 1 2 2 3 4 5 6 7 8 10 12 14 18 22 27 35 40 45 50 61
F NFPA1345Elbow 1 1 1 1 2 2 3 3 3 4 5 7 9 11 13 17 19 21 24 28
G NFPA 13 Gate Valve 0 0 0 0 0 1 1 1 1 2 2 3 4 5 6 7 8 10 11 13
T NFPA139O Flow thruTee 3 4 5 6 8 10 12 15 17 20 25 30 35 50 60 71 81 91 101 121
Units Summary
Diameter Units
Length Units
Flow Units
Pressure Units
Inches
Feet
US Gallons per Minute
Pounds per Square Inch
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Pressure I Flow Summary - STANDARD
A&D Fire Sprinklers
Page 4
Pacific Ridge
Date 09-02-09
Node Elevation K-Fact Pt Pn Flow Density Area Press
N Actual Actual Re
1 1966 5.6 27.22 na 29.21 0.2 100 7.0
2 19.66 5.6 24.64 na 27.8 0.2 118 7.0
2A 21.16 26.56 na
2B 21.16 29.24 na
3 19.66 5.6 28.1 na 29.68 0.2 100 7.0
3A 21.16 30.42 na
4 19.66 5.6 31.51 na 31.43 0.2 100 7.0
4A 21.16 34.17 no
5 1966. 5.6 24.76 na 27.86 0.2 110 7.0
5A 21.16 26.69 na
6 18.66 5.6 25.77 no 28.43 0.2 90 7.0
6A 21.16 27.63 no
7 19.66 5.6 26.29 na 28.71 0.2 110 TO
7A 21.16 28.37 na
7B 21.16 34.58 na
8 19.66 5.6 17.76 no 23.6 0.2 118 7.0
8A 21.16 19.01 na
9 19.66 5.6 18.88 no 24.33 0.2 118 7.0
9A 21.16 20.24 no
10 19.66 5.6 20.96 no 25.64 0.2 112 7.0
9B 21.16 22.44 na
11 19.66 5.6 24.35 na 27.63 0.2 112 7.0
hA 21.16 26.24 na
12 18.66 5.6 22.53 na 26.58 0.2 90 7.0
13 . 19.66 5.6 23.81 na 27.33 0.2 110 7.0
13A 21.16 24.96 na
12A 21.16 23.19 na
13B 21.16 25.06 no
11B 21.16 27.8 na
13C 20.66 49.57 na
7C 20.66 50.73 no
Mil 20.66 52.28 na
M12 10.37 58.78 na
M13 10.37 60.06 no
TOR 10.37 61.32 na
FS1 8.37 62.23 na
FS2 8.37 63.26 no
BOR 0.5 67.27 no
UG -3.0 68.98 na
BF1 2.5 67.02 no
BF2 2.5 72.04 no
UG1 -3.0 74.82 no
UG2 -4.0 75.41 no
SOR -8.0 77.46 na 250.0
The maximum velocity is 30.89 and it occurs in the pipe between nodes 7B and 7C
(n,rfr Prrrirms hv Hvrirntpr. Inc Route 111 Windham N.H. USA 03087
Final Calculations - Hazen-Williams
A&D Fire Sprinklers
Pacific Ridge
- 2007
Page 5
Date 09-02-09
Nodel Elevi K Qa Nom Fitting Pipe CFact Pt to or Ftngs Pe Notes Node2 Elev2 Fact Qt Act Eqv. Ln. Total Pf/Ft Pf
1 19.660 5.60 29.21 1 3E 6.914 4.830 120 27.215 to 0.0 6.914 -0.650 2B 21.160 29.21 1.08 0.0 11.744 0.2277 2.674 Vel = 10.23
0.0
2B 29.21
2 19.660 5.60 27.80 1 2E 4.61 2.000
to iT 5.762 10.372
2A 21.160 27.8 1.08 0.0 12.372
2A 21.160 0.0 1 iT 5.762 7.160
to 0.0 5.762
2B 21.160 27.8 1.08 0.0 12.922
2B 21.160 29.21 1.25 0.0 5.500
to 0.0 0.0
3A 21.160 57.01 1.408 0.0 5.500
29.239 K Factor = 5.40
120 24.637
-0.650
0.2076 2.569 Vel = 9.74
120 26.556
0.0
0.2076 2.683 Vel = 9.74
120 29.239
0.0
0.2155 1.185 Vel= 11.75
0.0
3A 57.01 -30.424KFactor=10.34
3 19.660 5.60 29.68 1 2E 4.61 2.330 120 28.096 to .
3A
iT 5.762 10.372 -0.650
21.160 29.68 1.08 0.0 12.702 0.2345 2.978 Vel = 10.39
3A 21.160 57.01 1.25 0.0 8.000 120 30.424 to 0.0 0.0 0.0
4A 21.160 86.69 1.408 0.0 8.000 0.4680 3.744 Vel = 17.86
0.0
4A 86.69 34.168 KFactor= 14.83
4 19.660 5.60 31.43 1 2E 4.61 2.330 120 31.507 to 1 5.762 10.372 -0.650 4A 21.160 31.43 1.08 0.0 12.702 0.2607 3.311 Vel = 11.01
4A 21.160 86.70 1.25 0.0 0.500 120 34.168 to 0.0 0.0 0.0 7B 21.160 118.13 1.408 0.0 0.500 0.8300 0.415 Vel = 24.34
0.0
7B 118.13 34.583 KFactor= 20.09
5 19.660 5.60 27.86 1 2E 4.61 2.000 120 24.759 to IT 5.762 10.372 -0.650 5A 21.160 27.86 1.08 0.0 12.372 0.2086 2.581 Vel = 9.76
5A 21.160 0.0 1 0.0 4.500 120 26.690 to 0.0 0.0 0.0 6A 21.160 27.86 1.08 0.0 4.500 0.2087 0.939 Vel = 9.76
0.0
6A 27.86 27.629 K Factor = 5.30
6 18.660 5.60 28.43 1 1E 2.305 5.500 120 25.775 to 1 5.762 8.067 -1.083 6A 21.160 28.43 1.08 0.0 13.567 0.2165 2.937 Vel = 9.96
6A 21.160 27.87 1.25 0.0 3.500 120 27.629 . to 0.0 0.0 0.0 7A 21.160 56.3 1.408 0.0 3.500 0.2106 0.737 VeI= 11.60
0.0
7A 56.30 28.366 KFactor= 10.57
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Final Calculations - Hazen-Williams - 2007
A&D Fire Sprinklers Page 6 Pacific Ridge Date 09-02-09
Nodel Elevi K Qa Nom Fitting Pipe CFact Pt
to or Ftngs Pe Notes
Node2 Elev2 Fact Qt Act Eqv. Ln. Total Pf/Ft Pf
7 - 19.660 5.60 28.71 1 2E 4.61 2.000 120 26.288
to iT 5.762 10.372 -0.650
7A 21.160 28.71 1.08 0.0 12.372 0.2205 2.728 Vel = 10.05
7A 21.160 56.30 1.25 iT 6.617 7.160 120 28.366
to 0.0 6.617 0.0
7B 21.160 85.01 1.408 0.0 13.777 0.4513 6.217 Vel = 17.52
76 21.160 118.13 1.5 1 8.727 6.040 120 34.583
to 0.0 8.727 0.217
7C 20.660 203.14 1.639 0.0 14.767 1.0790 15.934 Vel = 30.89
0.0
7C 203.14 50.734 KFactor 28.52
8 19.660 5.60 23.60 1 2E 4.61 2.000 120 17.760
to 1 5.762 10.372 -0.650
8A 21.160 - 23.6 1.08 0.0 12.372 0.1534 1.898 Vel = 8.27
8A 21.160 0.0 1 0.0 8.000 120 19.008 to 0.0 0.0 0.0
9A 21.160 23.6 1.08 0.0 8.000 0.1534 1.227 Vel = 8.27
•
0.0
9A 23.60 20.235 K Factor = 5.25
9
____
19.660 5.60 24.33 1 2E 4.61 2.000 120 18.877
to iT 5.762 10.372 -0.650
9A 21.160 24.33 1.08 0.0 12.372 0.1623 2.008 Vel = 8.52
9A 21.160 23.60 1.25 iT 6.617 7.500 120 20.235
to 0.0 6.617 0.0
9B 21.160 47.93 1.408 0.0 14.117 0.1563 2.207 Vel = 9.88
0.0
9B 47.93 22.442 K Factor = 10.12
10 19.660 5.60 25.64 1 3E 6.914 5.000 120 20.962 to 0.0 6.914 -0.650
9B 21.160 25.64 1.08 0.0 11.914 0.1788 2.130 Vel = 8.98
9B 21.160 47.93 1.25 0.0 11.000 120 22.442 to 0.0 0.0 0.0 hA 21.160 73.57 1.408 0.0 11.000 0.3455 3.800 Vel = 15.16
0.0
hA - 73.57 26.242 K Factor = 1436
11 19.660 5.60 27.63 1 2E 4.61 2.000 120 24.351 to iT 5.762 10.372 -0.650 hA 21.160 27.63 1.08 0.0 - 12.372 0.2054 2.541 Vel = 9.68
hA 21.160 73.57 1.25 0.0 2.500 120 26.242 to 0.0 0.0 0.0 11321.160 101.2 1.408 0.0 2.500 0.6232 1.558 Vel = 20.85 - - 0.0
11B 101.20 - 27.800 K Factor = 19.19
S 12
to
18.660 5.60 26.58 1 2E 4.61
0.0
4.500
4.610
120 22.532
-1.083 12A 21.160 26.58 1.08 0.0 9.110 0.1912 1.742 Vel = 9.31
0.0
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Final Calculations - Hazen-Williams - 2007
A&D Fire Sprinklers Page 7
Pacific Ridge Date 09-02-09
Nodel Elevi K Qa Nom Fitting Pipe CFact Pt
to or Ftngs Pe ******* Notes
Node2 EIev2 Fact Qt Act Eqv. Ln. Total Pf/Ft Pf
12A 26.58 - 23.191 K Factor = 5.52
13 19.660 5.60 27.33 1 3E 6.914 2.000 120 23.812
to 0.0 6.914 -0.650
13A 21.160 27.33 1.08 0.0 8.914 0.2013 1.794 Vel = 9.57
13A 21.160 0.0 1 0.0 0.500 120 24.956
to 0.0 0.0 0.0
13B 21.160 27.33 1.08 0.0 0.500 0.2020 0.101 Vel = 9.57
0.0
--
13B 27.33 25.057 K Factor = 5.46
12A 21.160 26.58 1 1 5.762 4.000 120 23.191
to 0.0 5.762 0.0
13B 21.160 26.58 1.08 0.0 9.762 0.1911 1.866 Vel = 9.31
13B 21.160 27.33 1.25 IT 6.617 7.500 120 25.057
to 0.0 6.617 0.0
11B 21.160 53.91 1.408 0.0 14.117 0.1943 2.743 Vel 11.11 -
11B 21.160 101.20 1.5 3E 13.09 11.080 120 27.800
to
13C 20.660 155.11 1.639
iT 8.727
0.0
21.817
32.897 0.6551
0.217
21.552 Vel = 23.59
13C 20.660 0.0 3 2E 20.383 34.450 120 49.569
to 0.0 20.383 0.0
7C 20.660 155.11 3.314 0.0 54.833 0.0212 1.165 Vel = 5.77
7C 20.660 203.14 3 1E 10.191 5.250 120 50.734
to 0.0 10.191 0.0
Mil 20.660 358.25 3.314 0.0 15.441 0.1000 1.544 Vel = 13.33
Mil 20.660 0.0 3 1E 10.191 10.290 120 52.278
to 0.0 10.191 4.457
M12 10.370 358.25 3.314 0.0 20.481 0.0999 2.046 Vel = 13.33
M12 10.370 0.0 4 1E 13937 4.250 120 58.781
to iT 27.874 41.811 0.0
- M13 10.370 358.25 4.31 0.0 46.061 0.0278 1.281 Vel = 7.88
M13 10.370 0.0 4 2E 27.874 17.400 120 60.062
to 0.0 27.874 0.0
TOR 10.370 358.25 4.31 0.0 45.274 0.0278 1.258 Vel = 7.88
TOR 10.370 0.0 4 0.0 1.500 120 61.320
to 0.0 0.0 0.866
FS1 8.370 358.25 4.31 0.0 1.500080 0.042 Vel = 7.88
FS1 8.370 0.0 4 0.0 1.000 120 62.228
to 0.0 0.0 1.000 * Fixed loss = 1
FS2 8.370 358.25 4.31 0.0 1.000 0.0280 0.028 Vel = 7.88
FS2 8.370 0.0 4 1E 13.937 7.870 120 63.256
to 0.0 13.937 3.408
BOR .500 358.25 4.31 0.0 21.807 0.0278 0.606 Vel = 7.88
BOR .500 0.0 6 2E 40.168 11.660 140 67.270
to 0.0 40.168 1.516
UG -3 358.25 6.16 0.0 51.828 0.0037 0.190 Vel= 3.86
UG -3 0.0 6 3E 64.749 60.500 150 68.976
to 0.0 64.749 -2.382
BF1 2.500 358.25 6.09 0.0 125.249 0.0034 0.428 Vel = 3.95
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Final Calculations - Hazen-Williams - 2007
A&D Fire Sprinklers Page 8 Pacific Ridge Date 09-02-09
Nodel Elevi K Qa Nom Fitting Pipe CFact Pt to or Ftngs Pe Notes Node2 Elev2 Fact Qt Act Eqv. Ln. Total Pf/Ft Pf
BF1 2.500 0.0 6 0.0 5.290 140 67.022
to 0.0 0.0 5.000 * Fixed loss = 5 BF2 2.500 358.25 6.16 0.0 5.290 0.0038 0.020 Vel = 3.86
BF2 2.500 0.0 6 iT 46.249 21.580 150 72.042
to 1G 4.625 94.040 2.382 UGI -3 358.25 6.09 2E 43.166 115.620 0.0034 0.395 Vel = 3.95
UG1 -3 0.0 8 1E 27.183 85.160 150 74.819
to iT 52.855 86.077 0.433 UG2 -4 358.25 7.98 1G 6.041 171.237 0.0009 0.157 Vel = 2.30
UG2 -4 0.0 8 3F 40.774 240.400 150 75.409 to iT 52.855 105.711 1.732 SOR -8 358.25 7.98 2G 12.081 346.111 0.0009 0.317 Vel = 2.30
250.00 Qa = 250.00 SOR 608.25 77.458 K Factor= 69.11
Computer Programs by Hydratec Inc. Route iii Windham N.H. USA 03087
S - - - Fire Protection by Computer Design
A&D Fire Sprinklers
11465 Woodside Ave.
Santee ca 92071
619-448-1962
Job Name : Pacific Ridge
Building : FP02 Level 1
Location 6269 El Fuerte St. Carlsbad CA 92009
System : 5
Contract : F-428
Data File : Calc-5_1-1-corridor_revl1-18-09.WXF
S
S
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
A&D Fire Sprinklers Page 1
Pacific Ridge Date 09-02-09
HYDRAULIC CALCULATIONS
for
Project name: Pacific Ridge High School
Location: 6269 El Fuerte St. Carlsbad CA 92009
Drawing no: FP02 Level 1
Date: 09-28-09
Design
Remote area number: 5
Remote area location: Exterior Corridor
Occupancy classification: Ligh Hazard
Density: 0.10 - Gpm/SqFt
Area of application: 1000 - SqFt
Coverage per sprinkler: 164 - SqFt
Type of sprinklers calculated: VICTAULIC V27 Pendents
No. of sprinklers calculated: 14
In-rack demand: - GPM
Hose streams: 100 - GPM
Total water required (including hose streams): 352.73 -GPM @ 79.92 -Psi
Type of system: TREE
Volume of dry or preaction system: -Gal . Water supply information
Date: 08-20-09
Location: 6269 El Fuerte St. Carlsbad CA 92009
Source: Street Water
Name of contractor. A&D Fire Sprinklers
Address: 11465 Woodside Ave. Santee CA 92071
Phone number: 619-448-1962
Name of designer: Maria lniguez
Authority having jurisdiction: Carlsbad Fire Department
Notes: (Include peaking information or gridded systems here.)
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Water Supply Curve (C)
A&D Fire Sprinklers Page 2
Pacific Ridge Date 09-02-09
City Water Supply: Demand:
Cl - Static Pressure : 112.5 Dl - Elevation : 8.012
02 - Residual Pressure: 103.5 D2 - System Flow : 252.735
C2 - Residual Flow : 1075 D2 - System Pressure : 91.392
Hose (Adj City)
Hose ( Demand) : 100
D3 - System Demand : 352.735
Safety Margin : 19.962
150
140
130
p120 --:j—
R 110
E 100 2
S 90
s 80
u 70
R60
E50
40
30
20
Dl
.....
10
... .... .. ..
200 400 600 800 1000 1200 1400 1600 1800
FLOW( N ' 1.85)
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
. . . Fittings Used Summary
A&D Fire Sprinklers Page 3
Pacific Ridge Date 09-02-09
Fitting Legend
Abbrev. Name 1/2 % 1 11/4 11/2 2 21/2 3 3% 4 5 6 8 10 12 14 16 18 20 24
E NFPA 139OStandardElbow 1 2 2 3 4 5 6 7 8 10 12 14 18 22 27 35 40 45 50 61
F NFPA 13 45 Elbow 1 1 1 1 2 2 3 3 3 4 5 7 9 11 13 17 19 21 24 28
G NFPA 13 Gate Valve 0 0 0 0 0 1 1 1 1 2 2 3 4 5 6 7 8 10 11 13
T NFPA 139O Flow thruTee 3 4 5 6 8 10 12 15 17 20 25 30 35 50 60 71 81 91 101 121
Units Summary
Diameter Units Inches
Length Units Feet
Flow Units US Gallons per Minute
Pressure Units Pounds per Square Inch
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Pressure I Flow Summary - STANDARD
A&D Fire Sprinklers Page 4
Pacific Ridge Date 09-02-09
Node Elevation K-Fact Pt Pn Flow Density Area Press
No. Actual Actual Reg.
50 4.0 5.6 7.9 na 15.74 0.1 1 7.0
51 5.5 5.6 7.85 na 15.72 0.1 1 7.0
51A 5.5 8.37 na
52 8.0 5.6 10.01 na 17.72 0.1 1 7.0
52A 0.0 13.82 na
53 10.5 5.6 11.62 na 19.09 0.1 177 7.0
53A 11.0 12.35 na
53B 11.0 21.07 na
54 10.5 5.6 7.0 na 14.82 0.1 118 7.0
55 10.5 5.6 7.36 na 15.19 0.1 125 7.0
55A 11.0 7.77 na
56 10.5 5.6 9.58 na 17.33 0.1 120 7.0
56A 11.0 10.16 na
57 10.5 5.6 11.0 na 18.57 0.1 1 7.0
57A 11.0 11.69 na
58 8.0 5.6 13.17 na 20.32 0.1 1 7.0
58A 11.0 13.97 na
58B 11.0 21.08 na
59 10.5 5.6 9.32 na 17.1 0.1 1 7.0
60 10.5 5.6 9.84 na 17.56 0.1 1 7.0
60A 11.0 10.44 na
61 10.5 5.6 12.74 na 19.99 0.1 1 7.0
61A 11.0 13.56 na
63 10.5 14.04 na
64 10.5 5.6 12.98 na 20.17 0.1 1 7.0 64A 11.0 13.82 na
64B
.
11.0 15.36 na
62 10.5 5.6 17.47 na 23.41 0.1 1 7.0 62A 11.0 18.65 na
62B 11.0 22.85 na
62C 11.0 32.71 na
Ml 11.0 47.12 na
M2 9.87 60.96 na
825 9.87 67.66 na
M3 9.87 68.42 na
M13 9.87 73.85 na
TOR 9.87 74.51 na
FSI 8.37 75.19 na
FS2 8.37 76.2 na
BOR 0.5 79.93 na
UG -3.0 81.54 na
SF1 2.5 79.39 na
BF2 2.5 86.4 na
UG1 -3.0 88.98 na
UG2 -4.0 89.49 na
SOR -8.0 91.39 na 100.0
The maximum velocity is 14.94 and it occurs in the pipe between nodes 62A and 62B
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Final Calculations - Hazen-Williams - 2007
A&D Fire Sprinklers Page 5
Pacific Ridge Date 09-02-09
Nodel Elevi K Qa Nom Fitting Pipe CFact Pt
to or Ftngs Pe Notes
Node2 Elev2 Fact Qt Act Eqv. Ln. Total Pf/Ft Pf
50 4 5.60 15.74 1 4E 9.219 6.200
to 0.0 9.219
51A 5.500 15.74 1.08 0.0 15.419
0.0
51A 15.74
51 5.500 5.60 15.72 1 IT 5.762 1.000
to 0.0 5.762
51A 5.500 - 15.721.08 0.06.762
51A 5.500 15.74 1 3E 6.914 5.700
to 0.0 6.914
52A 0 __31.46 ______31.461.08 1.0 0.012.614
0.0
52A 31.46
120 7.898
-0.650
0.0725 1.118 Vel = 5.51
8.366 K Factor = 5.44
120 7.877
0.0
0.0723 0.489 Vel = 5.51 -
120 8.366
2.166
0.2610 3.292Vel _11.02
13.824 K Factor = 8.46
52 8 5.60 17.72 1 iT 5.762 0.500 120 10.010
to 0.0 5.762 3.248
52A 0 17.72 1.08 0.0 6.262 0.0904 0.566 Vel = 6.21
52A 0 31.45 1.25 2E 6.617 12.120 120 13.824 . to 0.0 6.617 -4.548
53A ii 49.171.408 0.018.7370.16403.072Vel=10.13
0.0
53A 49.17 12.348 KFactor 13.99
53 10.500 5.60 19.09 1 1E 2.305 1.000
to iT 5.762 8.067
53A 11 19.09 1.08 0.0 9.067
53A 11 49.18 1.25 3E 9.925 12.450
to iT 6.617 16.542
53B11 68.27 -- 1:408 0.028.992
53B 11 0.0 2.5 0.0 1.160
to 0.0 0.0
58B 11 68.27 2.703 0.0 1.160
0.0
58B 68.27
54 10.500 5.60 14.82 1 2E 4.61 10.620
to 0.0 4.610
55A 11 14.82 1.08 0.0 15.230
0.0
55A 14.82
55 10.500 5.60 15.19 1 . 1E 2.305 1.160
to iT 5.762 8.067
55A 11 15.19 1.08 0.0 9.227
55A 11 14.82 1 0.0 10.000
to 0.0 0.0
56A11 30.01 1.08 0.0 10.000
0.0
56A 30.01
56 10.500 5.60 17.33 1 1E 2.305 1.160
to iT 5.762 8.067
56A 11 17.33 1.08 0.0 9.227
120 11.625
-0.217
0.10370.940 Vel =6.69
120 12.348
0.0
0.3008 8.720 Vel = 14.07
120 21.068
0.0
0.0129 0.015 Vel = 3.82
21.083 KFactor = 14.87
120 7.000
-0.217
0.06490.988Vel =5.19
7.771 K Factor = 5.32
120 7.361
-0.217
0.0680 0.627 Vel = 5.32
120 7.771
0.0
0.2392 2.392 Vel = 10.51
-10.163K Factor = 9.41
120 9.580
-0.217
0.0867 0.800 Vel = 6.07
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Final Calculations - Hazen-Williams - 2007
A&D Fire Sprinklers Page 6
Pacific Ridge Date 09-02-09
Nodel Elevi K Qa Nom Fitting Pipe CFact Pt
to or Ftng's Pe ******* Notes
Node2 EIev2 Fact Qt Act Eqv. Ln. Total Pf/Ft Pf
- 56A 11 30.01 1.25 0.0 10.000 120 10.163
to 0.0 0.0 0.0
57A 11 47.34 1.408 0.0 10.000 0.1528 1.528 Vel = 9.75
0.0
57A 47.34 11.691 K Factor = 13.85
57 10.500 5.60 18.57 1 1E 2.305 1.160 120 10.999
--
to iT 5.762 8.067 -0.217
57A 11 18.57 1.08 0.0 9.227 0.0985 0.909 Vel = 6.50
57A 11 47.34 1.25 IE 3.308 4.790 120 11.691
to 0.0 3.308 0.0
58A 11 65.91 1.408 0.0 8.098 0.2819 2.283 Vel = 13.58
0.0
58A 65.91 13.974 KFactor 17.63
58 8 5.60 20.32 1 2E 4.61 7.750 120 13.166
to IT 5.762 10.372 -1.299
58A 11 20.32 1.08 0.0 18.122 0.1163 2.107 VeI= 7.12 . 58A
to
11 65.91 1.5 3E
iT
13.09
8.727
10.330
21.817
120 13.974
0.0
58B 11 86.23 1.639 0.0 32.147 0.2211 7.109 Vel = 13.11
58B 11 68.27 2.5 0.0 31.000 120 21.083
to 0.0 0.0 0.0
62B 11 154.5 2.703 0.0 31.000 0.0569 1.763 Vel = 8.64
0.0
62B - 154.50 22.846 KFactor= 32.32
59 10.500 5.60 17.10 1 2E 4.61 11.160 120 9.325
to 0.0 4.610 -0.217
60A - 11 17.1 1.08 0.0 15.770 0.0845 1.333 Vel = 5.99
0.0
60A 17.10 10.441 K Factor = 5.29
60 10.500 5.60 17.56 1 1E 2.305 1.160 120 9.838
to iT 5.762 8.067 -0.217
60A 11 17.56 1.08 0.0 9.227 0.0889 0.820 Vel = 6.15
60A 11 17.11 1 0.0 10.000 120 10.441
to 0.0 0.0 0.0
61A 11 34.67 1.08 0.0 10.000 0.3124 3.124 Vel= 12.14
0.0
61A 34.67 13.565 K Factor = 9.41
61 10.500 5.60 19.99 1 1E 2.305 1.160 120 12.741
to iT 5.762 8.067 -0.217
61A 11 19.99 1.08 0.0 9.227 0.1128 1.041 Vel 7.00
61A 11 34.66 1.25 1 6.617 2.370 120 13.565 - to 0.0 6.617 0.0
64B ii 54.65 1.408 0.0 8.987 0.1993 - 1.791 Vel = 11.26 . 0.0
64B _ 54.65 15.356 K Factor =13.95
63 10.500 0.0 1 2E 4.61 8.160 120 14.037
to 0.0 4.610 -0.217 64A 11 0.0 1.08 0.0 12.770 0.0001 0.001 Vel = 0
Computer Programs by Hydratec Inc.. Route 111 Windham N.H. USA 03087
Final Calculations - Hazen -Williams - 2007
A&D Fire Sprinklers Page. 7.
Pacific Ridge Date 09-02-09
Nodel Elevi K Qa Nom Fitting Pipe CFact Pt
to or Ftngs Pe Notes
Node2 Elev2 Fact Qt Act Eqv. Ln. Total Pt/Ft Pt
0.0
64A co 13.821 K Factor 0
64 10.500 5.60 20.17 1 1E 2.305 1.160 120 12.978
to iT 5.762 8.067 -0.217
64A 11 20.17 1.08 0.0 9.227 0.1149 1.060 Vel = 7.06
64A 11 0.0 1 1 5.762 7.620 120 13.821
to 0.0 5.762 0.0
64B11 20.17 1.08 0.0 13.382 0.1147 1.535 Vel 7.06
64B 11 54.66 1.5 3E 13.09 6.250 120 15.356
to 0.0 13.090 0.0
62A11 7483 1.639 0.0 19.340 0.1701 3.290 Vel 11.38
0.0
62A 74.83 18.646 KFactor= 17.33
62 10.500 5.60 23.41 1 1E 2.305 1.160 120 17.469
to iT 5.762 8.067 -0.217
62A 11 23.41 1.08 0.0 9.227 0.1511 1.394 Vel = 8.20 . 62A 11 74.82 1.5 iT 8.727 6.200 120 18.646
to 0.0 8.727 0.0
62B 11 98.23 1.639 0.0 14.927 0.2814 4.200 Vel = 14.94
62B 11 154.51 2.5 1E 9.325 51.120 120 22.846
to 2F 9.325 18.650 0.0
62C 11 252.742.703 0.069.770 0.14149.867 Vel = 14.13
62C 11 0.0 2.5 3E 27.976 73.870 120 32.713
to 0.0 27.976 0.0
Ml 11 252.742.703 0.0101.8460.141414.403 .Vel _14.13
Ml 11 0.0 2.5 4E 37.301 38.500 120 47.116
to iT 18.651 55.952 0.489
M2 9.870 252.742.703 0.094.452 0.141413.357 __Vel = 14.13
M2 9.870 0.0 3 2E 20.383 90.000 120 60.962
to 4F 17.471 37.854 0.0
82B9.870 252.74 3.314 0.0127.8540.0524 6.701 Vel 9.40
82B 9.870 0.0 3 0.0 14.500 120 67.663
to 0.0 0.0 0.0
M3 9.870 252.74 3.314 0.0 14.500 0.05250.761 Vel 9.40
M3 9.870 0.0 3 SE 50.956 52.660 120 68.424
to 0.0 50.956 0.0
M13 9.870 252.743.314 0.0103.616 0.05245.431 _Vel _.9.40
M13 9.870 0.0 4 2E 27.874 17.400 120 73.855
to 0.0 27.874 0.0
TOR 9.870 252.744.31 0.0 45.2740.0146 0.660 Vel _5.56
TOR 9.870 0.0 4 0.0 1.500 120 74.515
to 0.0 0.0 0.650
FS1 8.370 252.74 4.31 0.0 1.500 0.0140 0.021 Vel =t 5.56
FS1 8.370 0.0 4 0.0 1.000 120 75.186 •
to 0.0 0.0 1.000 * Fixed loss = 1
FS2 8.370 252.74 4.31 0.0 1.000 0.0150 0.015 _Vel =5.56
FS2 8.370 0.0 4 1E 13.937 7.870 120 76.201
to 0.0 13.937 3.408
BOR .500 252.74 4.31 0.0 21.807 0.0146 0.318 Vel = 5.56
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 63087
0 Final Calculations - Hazen-Williams - 2007
A&D Fire Sprinklers Page 8
Pacific Ridge Date 09-02-09
Nodel Elevi K Qa Nom Fitting Pipe CFact Pt
to or Ftngs Pe Notes
Node2 Elev2 Fact Qt Act Eqv. Ln. Total Pt/Ft Pf
BOR .500
to
UG -3
UG -3
to
BF1 2.500
BF1 2.500
to
BF2 2.500
BF2 2.500
to
UG1 -3
UG1 -3
to
UG2 -4
UG2 -4
to
SOR -8
0.0 6 2E 40.168 11.660
0.0 40.168
252.74 6.16 0.0 51.828
0.0 6 3E 64.749 60.500
0.0 64.749
252.74 6.09 0.0 125.249
0.0 6 0.0 5.290
0.0 0.0
252.74 6.16 0.0 5.290
0.0 6 iT 46.249 21.830
1G 4.625 94.040
252.74 6.09, 2E 43.166 115.870
0.0 8 1 13.591 85.160
iT 52.855 72.487
252.74 7.98 1G 6.041 157.647
140 79.927
1.516
0.0019 0.100 Vel = 2.72
150 81.543
-2.382
0.0018 0.224 Vel = 2.78
140 79.385
7.000 * Fixed loss = 7
0.0019 0.010 Vel = 2.72
150 86.395
2.382
0.0018 0.208 Vel = 2.78
150 88.985
0.433
0.0005 0.076 Vel = 1.62
0.0 8 3F 40.774 240.400 150 89.494
iT 52.855 105.711 1.732
252.74 7.98 2G 12.081 346.111 0.0005 0.166 Vel = 1.62
100.00 Qa = 100.00
SOR 352.74 91.392 K Factor = 36.90
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Fire Protection by Computer Design
A&D Fire Sprinklers
11465 Woodside Ave.
Santee ca 92071
619-448-1962
Job Name Pacific Ridge
Building : FP02 Level I
Location 6269 El Fuerte St. Carlsbad CA 92009
System : 5
Contract F-428
Data File : Calc-5_1-I-corridor.WXF
APPRO
,
)EAS SUBMITTED
CARL-SMADIF-1RE DEPARTMENT
Computer Programs by Hydratec Inc. Route 111 Windham NH. USA 03067
c COPY
A&D Fire Sprinklers Page 1
Pacific Ridge Date 09-02-09
HYDRAULIC CALCULATIONS
for
Project name: Pacific Ridge High School
Location: 6269 El Fuerte St. Carlsbad CA 92009
Drawing no: FP02 Level 1
Date: 09-28-09
Design
Remote area number: 5
Remote area location: Exterior Corridor
Occupancy classification: Ligh Hazard
Density.- 0.10 - Gpm/SqFt
Area of application: 1000 - SqFt
Coverage per sprinkler., 164 - SqFt
Type of sprinklers calculated: VICTAULIC V27 Pendents
No. of sprinklers calculated: 12
In-rack demand: - GPM
Hose streams: 100 -GPM
Total water required (including hose streams): 325.46 - GPM @ 72.98 - Psi
Type of system: TREE
Volume of dry orpreactlon system: -Gal
Water supply information
Date: 08-20-09
Location: 6269 El Fuerte St. Carlsbad CA 92009
Source: Street Water
Name of contractor: A&D Fire Sprinklers
Address: 11465 Woodside Ave. Santee CA 92071
Phone number: 619-448-1962
Name of designer: Maria lniguez
Authority having jurisdiction: Carlsbad Fire Department
Notes: (Include peaking information or gridded systems here),
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Water Supply Curve (C)
A&D Fire Sprinklers Page 2 Pacific Ridge Date 09-02-09
City Water Supply; Demand: Cl - Static Pressure : 112.5 Dl - Elevation : 7.722 C2 - Residual Pressure: 103.5 D2 - System Flow : 225.462 C2 - Residual Flow : 1075 D2 - System Pressure : 84.302
Hose(Adj City)
Hose Demand : 100
D3 - System Demand : 325.462
Safety Margin : 27.211
150
140
130
p120
R 110 - -_ C2
E 100
S90
S80
)3
--
u 7°
R6
Es:
40
30
20
10
Dl
.. -,-.. .... -.... .. .. .. -- ..
200 400 600 800 1000 1200 1400 1600 1800
FLOW (NA 1.85)
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Fittings Used Summary
A&D Fire Sprinklers Page 3 Pacific Ridge Date 09-02-09
Fitting Legend
Abbrev. Name V2 % 1 1% 1% 2 2% 3 31% 4 5 6 8 10 12 14 16 18 20 24
E NFPA 13 90 Standard Elbow 1 2 2 3 4 5 6 7 8 10 12 14 18 22 27 35 40 45 50 61 F NFPA 1345Elbow 1 1 1 1 2 2 3 3 3 4 5 7 9 11 13 17 19 21 24 28 G NFPA 13 Gate Valve 0 0 0 0 0 1 1 1 1 2 2 3 4 5 6 7 8 10 11 13 L NFPA 13 Long Turn Elbow 0.5 1 2 2 2 3 4 5 5 6 8 9 13 16 18 24 27 30 34 40 I NFPA 13 90 Flowthru Tee 3 4 5 6 8 10 12 15 17 20 25 30 35 50 60 71 81 91 101 121
Units Summary
Diameter Units
Length Units
Flow Units
Pressure Units
Inches
Feet
US Gallons per Minute
Pounds per Square Inch
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
- Pressure / Flow Summary - STANDARD
A&D Fire Sprinklers Page 4 Pacific Ridge Date 09-02-09
Node
No.
Elevation K-Fact Pt
Actual
Pn Flow
Actual
Density Area Press
Req.
50 4.0 5.6 7.59 no 15.43 0.1 1 7.0 51 5.5 5.6 7.55 no 15,39 0.1 1 7.0 51A 5.5 8.02 no 52 8.0 5.6 9.56 no 17.32 0.1 1 7.0 52A 8.0 10.1 no 52B 9.45 14.37 no 52C 9.45 14.53 no 52D 9.45 16.45 no 53 9.83 5.6 13,5 no 20.57 0.1 1 7.0 54 9.83 5.6 7.0 no 14.82 0.1 1 7.0 55 9.83 5.6 7.51 no 15.35 0.1 1 7.0 55A 10.5 7.87 no 56 9.83 5.6 12.92 no 20.13 0.1 1 7.0 57 8.0 5.6 13.25 no 20.38 0.1 1 7.0 57A 9.45 13.89 no 55B 9.45 14.3 no 53A 9.45 15.43 no 53B 9.45 17.99 no 58 9.83 5.6 16.21 no 22.55 0.1 1 7.0 58A 9.45 18.23 no 58B 9.45 18.53 no 59 9.83 5.6 11.42 no 18.93 0.1 1 7.0 59A 9.45 19.23 no 59B 9.45 19.45 no 60 9.83 5.6 15.68 no 22.18 0.1 1 7.0 61 8.0 5.6 16.04 no 22.43 0.1 1 7.0 61A 9.45 16.87 no 613 9.45 19.36 no 61C 9.45 20.43 no 61D 9.66 29.37 no Ml 9.66 40.01 no M2 9.66 51.41 no 82C 9.66 62.34 no M3 9.66 63.01 no M13 9.66 66.97 no TOR 9.66 67.72 no FS1 8.37 68.3 no FS2 8.37 69.31 no BOR 0.5 72.99 no UG -3.0 74.58 no BFI 2.5 72.38 no BF2 2.5 79.39 no UG1 -3.0 81.94 no 1JG2 -4.0 62.44 no SOR -8.0 84.3 no 100.0
The maximum velocity is 15.62 and it occurs in the pipe between nodes 61A and 61B
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Final Calculations - Hazen-Williams - 2007
A&D Fire Sprinklers Page 5
Pacific Ridge Date 09-02-09
Nodel Elevi K Qa Nom Fitting Pipe CFact Pt
to or Ftng's Pc **** Notes
Node2 Elev2 Fact Qt Act Eqv. Ln. Total PfIFt Pf
50 4 5.60 15.43 1 4E 9.219 6.200 120 7.591
to 0.0 9.219 -0.650
51A 5.500 15.43 1.08 0.0 15.419 0.0698 1.077 Vet = 5.40 -.
0.0
51A 15.43 8.018 K Factor = 5.45
51 5.500 5.60 15.39 1 1 5.762 1.000 120 7.548
to 0.0 5.762 0.0
51A 5.500 15.39 1.08 0.0 6.762 0.0695 0.470 Vel= 5.39
51A 5.500 15.42 1 3E 6,914 5.700 120 8.018
to 0.0 6.914 -1.083
52A 8 30.81 1.08 0.0 12.614 0.2513 3.170 Vel = 10.79
0.0
52A 30.81 10.105 KFactor = 9.69
52 8 5.60 17.32 1 iT 5.762 0.500 120 9.563
to 0.0 5.762 0.0
52A 8 17.32 1.08 0.0 6.262 0.0866 0.542 Val = 6.07
52A 8 30.81 1.25 3E 9.925 14.540 120 10.105
to IT 6.617 16.542 -0.628
52B 9.450 48.13 1.408 0.0 31.082 0.1576 4.897 Vel = 9.92
52B 9.450 0.0 1.25 0.0 1.000 120 14.374
to 0.0 0.0 0.0
52C 9.450 48.13 1.408 0.0 1.000 0.1580 0.158 Vel = 9.92
52C 9.450 0.0 1.5 IT 8.727 16.790 120 14.532 to 0.0 8.727 0.0
2P 9.450 48.13 1.639 0.0 25.517 0.0752 1.918 Vel = 7.32
52D 9.450 0.0 1.5 IT 8.727 11.700 120 16.450
to 0.0 . 8.727 0.0
-53B 9.450 48.13 1.639 * 0.0 20.427 0.0752 1.536 Vel = 7.32
0.0
53B 48,13 17.986 KFactor= 11.35.
53 9.830 5.60 20.57 1 2E 4.61 4.450 120 13.498
-
to IT . 5.762 10.372 0.165 53A 9.450 20.571.08 0.014.8220.11891.763 Vel _=_7.20
0.0
53A 20.57 15.426 KFactor= 5.24
54 9.830 5.60 14.82 1 2E 4.61 13.330 120 7.000 to 0.0 4.610 -0.290 55A 10.500 14.82 1.08 0.0 17.940 0.0648 . 1.163 Vel = 5.19
0.0
55A 14.82 --. 7.873KFactor=5.28
55 9.830 5.60 15.35 1 1E 2.305 1.330 120 7.513 - to ii 5.762 8.067 -0.290 55A 10.500 15.35 1.08 0.0 9.397 0.0692 0.650 Vet = 5.38 55A 10.500 14.82 1 2E 4.61 14.370 120 7.873 to IT 5.762 10.372 0.455 55B 9.450 30.17 1.08 0.0 24.742 0.2415 5.976 Vet = 10.57
0.0
55B 30.17 14.304 K Factor = 7.98
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Final Calculations - Hazen-Williams - 2007
A&D Fire Sprinklers Page 6
Pacific Ridge Date 09-02-09
Nodel Elevi K Qa Nom Fitting Pipe CFact Pt
to or Ftng's Pe *** Notes
Node2 Elev2 Fact Qt Act Eqv. Ln. Total PfIFt Pf
56 9.830 5.60 20.13 1 2E 4.61 2.410 120 12.920
to 0.0 4.610 0.165
57A 9.450 - 20.13 1.08 0.0 7.020 0.1142 0.802 Vet = 7.05
0.0
57A 20.13 - 13.887 K Factor = 5.40
57 8 - 5.60 20.38 1 1E 2.305 2.740 120 13.250
to IT 5.762 8.067 -0.628
57A 9.450 20.38 1.08 0.0 10.807 0.1171 1.265 Vet = 7.14
57A 9.450 20.13 1 0.0 1.000 120 13.887
to 0.0 0,0 0.0
55B 9.450 40.51 1.08 0.0 1.000 0.4170 0.417 Vel = 14.19
55B 9.450 30.17 1.25 0.0 3,500 120 14.304 to 0.0 0.0 0.0
53A 9.450 70.68 1.408 0.0 3.500 0.3206 1.122 Vel = 14.56
53A 9.450 20.57 1.5 1 8.727 1.700 120 15.426 to 0.0 8.727 0.0 538 9.450 91.25 1.639 0.0 10.427 0.2455 2.560 VeI= 13.88
53B 9.450 48.13 2.5 0.0 10.200 120 17.986 to 0.0 0.0 0.0
58B 9.450 139.38 2.635 0.0 10.200 0.0532 0.543 Vel = 8.20
0.0
58B 139.38
- 18.529 KFactor= 32.38
- 58 9.830 5.60 22.55 1 2E 4.61 8.500 120 16.214 to 0.0 4.610 0.165 58A 9.450 22.55 1.08 0.0 13.110 0.1409 1.847 Vel = 7.90
58A 9.450 0.0 1.25 IT 6.617 1.200 120 18.226 to 0.0 6.617 0.0 588 9.450 22.55 1.408 0.0 7.817 0.0388 0.303 Vet = 4.65
588 9.450 139.38 2.5 0.0 13.160 120 18.529 to 0.0 0.0 0.0 59B 9.450 161.93 2.635 0.0 13.160 0.0703 0.925 Vet = 9.53
0.0
59B 161.93 19.454 KFactor 36.71
59 9.830 5.60 18.93 1 2E 4.61 70.410 120 11.421 to 0.0 4.610 0.165 59A 9.450 _18.931.08 0.075.0200.10207.649 Vet _6.63
59A 9.450 0.0 1.25 IT 6.617 1.200 120 19.235 to 0.0 6.617 0.0 59B 9.450 18.93 1.408 0.0 7.817 0.0280 0.219 Vel= 3.90 59B 9.450 161,93 2.5 0.0 11.290 120 19.454 to 0.0 0.0 0.0 .1ç 9.450 180.86 2.635 0.0 11.290 0.0862 0.973 Vel= 10.64
0.0
SiC 180.86 . - 20.427 K Factor = 40.02 60 9.830 5.60 22.18 I 2E 4.61 2.870 120 15.680 to 0.0 4.610 0.165 61A9.450 22.181.08 0.0 7.480 - 0.1368 1.023 Vel= 7.77
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
- Final Calculations - Hazen-Williams - 2007
A&D Fire Sprinklers Page 7
Pacific Ridge Date 09-02-09
Nodel 8evI K Qa Nom Fitting Pipe CFact Pt
to or Ftng's Pe Notes
Node2 Elev2 Fact Qt Act Eqv. La. Total Pf/Ft Pf
0.0
61A 22.18 16.868 K Factor = 5.40
61 8 5.60 22.43 1 1 2.305 2,370 120 16.039
to IT 5.762 8.067 -0.628
61A 9.450 22.43 1.08 0.0 10.437 0.1396 1.457 Vel = 7.86
61A 9.450 22.17 1 0.0 5.000 120 16.868
to 0.0 0.0 0.0
61B 9.450 44.6 1.08 0.0 5.000 0.4978 2.489 Vet = 15.62
616 9.450 0.0 1.25 IT 6.617 1.200 120 19.357
to 0.0 6.617 0.0
61C 9.450 44.6 1.408 0.0 7.817 0.1369 1.070 Vet = 9.19
61C 9.450 180.86 2.5 IE 8.237 50.500 120 20.427
to , 2L 10.983 19.220 -0.091
61D 9.660 225.46 2.635 0.0 69.720 0.1296 9.037 Vel = 13.26
61D 9.660 0.0 2.5 1E 8.237 73.870 120 29.373
to 0.0 8.237 0.0
Ml 9.660 225.46 2.635 0.0 82.107 0.1296 10.641 Vet = 13.26
Ml 9.660 0.0 2.5 4E 32.948 38.500 120 40.014
to IT 16.474 49.422 0.0
M2 9.660 225.46 2.635 0.0 87.922 0.1296 11.396 Vel= 13.26
M2 9.660 0.0 3 14E 131.707 90.000 120 51.410
to 4F 16.127 147.834 0.0
82c 9.660 225.46 3.26 0.0 237.834 0.0460 10.933 Vel = 8.67
82C 9.660 0.0 3 0.0 14.500 120 62.343 to 0.0 0.0 0.0
M3 9.660 225.46 3.26 0.0 14.500 0.0460 0.667 Vel = 8.67
M3 9.660 0.0 3 4E 37.631 48.540 120 63.010
to 0.0 37.631 0.0 M13 9.660 225.46 3.26 0.0 86.171 0.0460 3.961 Vel = 8.67
M13 9.660 0.0 4 3E 39.501 20.870 120 66.971 to 0.0 39.501 0.0 TOR 9.660 225.46 4.26 0.0 60.371 0.0125 0.754 Vet = 5.08
TOR 9.660 0.0 4 0.0 1-500 120 67.725 to 0.0 0.0 0.559 FSI 8.370 225.46 4.26 0.0 1.500 0.0120 0.018 Vel = 5.08
FSI 8.370 0.0 4 0.0 1.000 120 68.302 to 0.0 0.0 1.000 *Fixed loss _ 1 FS2 8.370 225.46 4.26 0.0 1.000 0.0130 0.013 Vet = 5.08
FS2 8.370 0.0 4 1 13.167 7.870 120 69.315 to 0.0 13.167 3.408 BOR .500 225.46 4.26 0.0 21.037 0.0125 0.263 Vel = 5.08
BOR .500 0.0 6 2E 40.168 11.660 140 72.988 to 0.0 40.168 1.516 IJG -3 225.46 6.16 0.0 51.828 0.0016 0.081 Vel= 2.43
UG -3 0.0 6 3E 64.749 60.500 150 74.583 to 0.0 64.749 -2.382 BF1 2.500 225.46 6.09 0.0 125.249 0.0014 0.181 - Vel = 2.48
BF1 2.500 0.0 6 0.0 5.290 140 72.382 to 0.0 0.0 7.000 'Fixed loss = 7 BF2 2.500 225.46 6.16 0.0 5.290 0.0015 0.008 Vet = 2.43
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Final Calculations - Hazen-Williams - 2007
A&D Fire Sprinklers Page 8
Pacific Ridge Date 09-02-09
Nodel Elevi K Qa Nom Fitting Pipe CFact Pt
to or Ftngs Pe Notes
Node2 Elev2 Fact Qt Act Eqv. Ln. Total Pf/Ft Pf
BF2
to
UG1
2.500
-3
0.0
225.46
6
6.09
IT
IG
2E
46.249 21.830
4.625 94.040
43.166 115.870 -
150
0.0015
79.390
2.382
0.169 Vel = 2.48
UG1 -3 0.0 8 1 13.591 85.160 150 81.941
to IT 52.855 72.487 0.433
UG2 -4 225.46 7.98 1G 6.041 157.647 00004 0.061 Vel = 1.45
UG2 -4 0.0 8 3F 40.774 240.400 150 82.435
to IT 52.855 105.711 1.732
SOR -8 225.46_.98 2G12.081 346.111 0.0004 0.135 Vel= 1.45
100.00 Qa = 100,00 SOR 325.46 84.302 K Factor= 35.45
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
EI CE ILPCBI ) O1$u
SEE VICTAULIC PUBLICATION 10.01 FOR DETAILS
Standard Spray/Pendent, Upright and Recessed Pendent
MODELS V2703, V2704, V2725, V2726, V2727 AND V2728
STANDARD AND QUICK RESPONSE
These Model V27 standard spray and conventional spray sprinklers are designed to produce
a hemispherical spray pattern for standard commercial applications. They are available with
either standard or quick response bulbs. The Model V27 conventional sprinkler is designed
to produce a hemispherical pattern which deflects approximately half of the spray upwards
toward the ceiling and the other half downwards and can be installed in either the upright or
pendent position. The design incorporates a state-of-the-art, heat responsive, frangible glass
bulb design (standard or quick response) for prompt, precise operation.
The die cast frame is more streamlined and attractive than traditional sand cast frames. It
is cast with a hex-shaped wrench boss to allow easy tightening from many angles, reducing
assembly effort. This sprinkler is available in various temperature ratings (see chart on page 2)
and finishes to meet many design requirements.
Sprinkler Operation
The operating mechanism is a frangible glass bulb which contains a heat responsive liquid.
During a fire, the ambient temperature rises causing the liquid in the bulb to expand. When
the ambient temperature reaches the rated temperature of the sprinkler, the bulb shatters.
As a result, the waterway is cleared of all sealing parts and water is discharged towards the
deflector. The deflector is designed to distribute the water in a pattern that is most effective in
controlling the fire.
Coverage
For coverage area and sprinkler placement, refer to applicable installation standards.
t UL, ULC Listed
f UL, ULC Listed; FM Approved
4,
U
CONVENTIONAL PENDENT
(V2725t (G4020048, (V2727 (G4020047, Nr1264/2002) AND V2726t Nr1266I2002) AND V2728t
(G4020045, Nr1263/2002)I (G4020044, Nr1265I2002)I
UPRIGHT
IV270* IG4020046,
Nr1268/20021 AND V27041
(G4020043, Nr1267/2002)l
TECHNICAL SPECIFICATIONS
Exaggerated for clarity
JOB/OWNER
System No.
Location
Models: V2703, V2704, V2725, V2726, V2727,
V2728
Style: Pendent, Upright or Conventional
Nominal K-Factor: 80S.l. (Bar)/5.6 Imp.
Nominal Thread Size: 15mm BSP or / NPT
Max. Working Pressure: 12.5 Bar/175 psi
Factory Hydrostatic Test:
100% © 34,5Bar/500 psi
Mm. Operating Pressure: .5Bar/7 psi
Temperature Ratings: See chart on page 2
MATERIAL SPECIFICATIONS
Upright Deflector: Bronze per UNS C22000
Pendent Deflector: Bronze per UNS C51000
Conventional Deflector: Bronze per UNS
C51000
Bulb: Glass with glycerin solution.
Bulb Nominal Diameter:
Standard: 5.0mm
Quick Response: 3.0mm
Load Screw: Bronze per UNS C65100
Pip Cap: Bronze per UNS C65100
Seal: Teflon* tape
Spring: Beryllium nickel
Frame: Die cast brass 65-30
Lodgement Spring:
Stainless steel per UNS S30200
CONTRACTOR
Submitted By
Date
ACCESSORIES
Installation Wrench:
Open End: V27
Recessed: V38-3
Sprinkler Finishes:
Plain brass
Chrome plated
White paintedt
RAL 9001 Off-whitef
Custom painted
Nickel/Teflon* coatedt
For cabinets and other accessories refer to
separate sheet.
A For K-Factor when pressure is measured in
kPa, divide K-Factor in (SI.) Bar units by
10.0.
* Teflon is a registered trademark of Dupont Co.
**These finishes are UL Listed for corrosion
resistance.
ENGINEER
Spec Sect Para
Approved
Date
www.victaulic.com
ICTAUC IS REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2007 VICTAULIC COMPANY. ALL RIGHTS RESERVED. PRINTED IN THE LISA.
REVE
\4tauIic
401,18111
FIRE PROTECTION PRODUCTS - AUTOMATIC SPRINKLERS 40.18
V27, K80
Standard Spray/Pendent, Upright and Recessed Pendent
MODELS V2703, V2704, V2725, V2726, V2727 AND V2728
STANDARD AND QUICK RESPONSE
APPROVALS/LISTINGS
V2703
1 13 80 Standard Upright 2,3, 4,5, - A
V2727 13 80 Standard Pendent 2,3,4 ' 5, 6 u
V2725 Standard Conventional
- -
V2704 J 13 80 Quick Upright 1,2,3,4,5.6-6
V2778 13 80 Quick Pendent 73.4,5,6 - D
Quick Conventional 2, 5, -
* Listings and approval as of printing.
A For K-Factor when pressure is measured in kPa (SI.), divide K-Factor bar (SI.) units by 10.0
@ All are approved open, except quick response.
APPROVED TEMPERATURE RATINGS
- --. -----.
1 - Vds/CES A - 57CI1351`, 68C/155F, 79C/1751`, 93C/200F, 141C/286F, e2-c/360F
2-- UL B - 57C/135F, 68C/155F, 79C/t75F, 93C/200F, 141C/286'F
3 - FM C - 57C/135F, 68C/155F, 79C/175F, 93C/200F
4-ULC 0-No
5-NYC/MEAt
6 - CSFM §
#CE: Tested to EN12259-1 Standards
I- MEA #62-99-E
§ CSFM 47690-0531:112
RATINGS All glass bulbs are rated for temperatures from -67°F/--55°C to those shown in table below,
* Standard response only.
All are approved open, except for areas designated "No."
vIcTAuLIC IS REGISTERED TRADEMARK OF vlclAuuc COMPANY. © 2007 VICTAULIC COMPANY. ALL RIGHTS RESERVED. PRINTED IN THE USA. X04. _ta ___ U1 ii la~
40.182 REV E
FIRE PROTECTION PRODUCTS AUTOMATIC SPRINKLERS
V27, K8O
Standard Spray/Pendent, Upright and Recessed Pendent
MODELS V2703, V2704, V2725, V2726, V2727 AND V2728
STANDARD AND QUICK RESPONSE
ORDERING INFORMATION Please specify the following when ordering:
40.18
WARNING A
Sprinkler Model Number
Style
Temperature Rating
K-Factor
Thread Size
Quantity
Sprinkler Finish
Wrench Model Number
WARNING
Always read and understand installation, care and maintenance
instructions, supplied with each box of sprinklers, before proceeding
with installation of any sprinklers.
-, • Always wear safety glasses and toot protection.
Depressurize and drain the piping system before attempting to
install, remove or adjust any Victaulic piping products.
Installation rules, especially those governing obstruction, must be
strictly followed.
O • Painting, plating or any re-coating of sprinklers (other than that
supplied by Victaulic) is not allowed.
Failure to follow these instructions could result in serious personal
injury and/or property damage.
The owner is responsible for maintaining the fire protection system and
devices in proper operating condition. For minimum maintenance and
O
inspection requirements, refer to the current National Fire Protection
Association pamphlet that describes care and maintenance of sprinkler
systems. In addition, the authority having jurisdiction may have additional
maintenance, testing and inspection requirements that must be followed.
If you need additional copies of this publication, or if you have any
questions about the safe installation of this product, contact Victaulic
Europe, Prijkelstraat 36, 9810 Nazareth Belgium, Phone: 32-93-811500.
www.victaulic.com
A—c—ta—uhic~ vIcTAULIc ISA REGISTERED TRADEMARK OF VICTAULIC COMPANY. O 2007 VICTAULIC COMPANY. ALL RIGHTS RESERVED. PRINTED IN THE USA.
REVE 40.18 3
'U(LERS
Sd
Standard Spray/Pendent, Upright and Recessed Pendent
MODELS V2703, V2704, V2725, V2726, V2727 AND V2728
STANDARD AND QUICK RESPONSE
DIMENSIONS Standard Pendent - V2727, V2728
40.18
Standard Upright - V2703, V2704
37 mm/
AVAILABLE WRENCHES
60 mm!
2%
41 mm! I 1W 41 mm/
60 mm/ 1%
2W I
25 mm!
Conventional Pendent/Upright - V2725, V2726
I a6" 61 mm!
2%
42 mm!
1W
31mm
V2727, V2728 Pendent yes yes
V2725, V2726 Conventional Upright/Pendent yes yes
V2703, V2704 Upright yes yes
VICTAULIC IS A REGISTERED TRADEMARK OF vIcTAIJLIc COMPANY. © 2007 VIcTALJLIc COMPANY. ALL RIGHTS RESERVED. PRINTED IN THE USA. ktaul
1~ iC
4014
FIRE PROTECTION PRODUCTS AUTOMATIC SF -ERS
V27, K8O
Standard Spray/Pendent, Upright and Recessed Pendent
MODELS V2703, V2704, V2725, V2726, V2727 AND V2728
STANDARD AND QUICK RESPONSE
40.18
DISTRIBUTION PATTERNS
Refer to notes on page 7
Refer to notes on page 7
www.victaulic.com
VICTAULIC IS REGISTERED TRADEMARK OF VICTAULIC COMPANY. 0 2007 VICTAULIC COMPANY. ALL RIGHTS RESERVED. PRINTED IN THE USA. ,ct -au l.c
REV E 40:185
FIRE PRO PRO()J(TS TIC SRi K
V27, K8O
Standard Spray/Pendent, Upright and Recessed Pendent
MODELS V2703, V2704, V2725, V2726, V2727 AND V2728
STANDARD AND QUICK RESPONSE
DISTRIBUTION PATTERNS Models V2725, V2726
K8.0 standard conventional - pendent position distribution patterns - trajectory
Refer to notes on page 7
Models V2725, V2726
K8.0 standard conventional - upright position distribution patterns - trajectory
'
Refer to notes on page 7
VICTAULIC IS A REGISTERED TRADEMARK OF VICTAIJLIC COMPANY. C 2007 VICTAIILIC COMPANY, ALL RIGHTS RESERVED. PRINTED IN THE LISA. X/C-t:8~9-1 i.5
4018 6 REV E
FIRE PROTECTION PRODUCTS AUTOMATIC SPRINKLERS
V27, K80
Standard Spray/Pendent, Upright and Recessed Pendent
MODELS V2703, V2704, V2725, V2726, V2727 AND V2728
STANDARD AND QUICK RESPONSE
DISTRIBUTION PATTERNS NOTES:
1 Data shown is approximate and can vary due to differences in installation.
2 These graphs illustrate approximate trajectories, floor-wetting and wall-wetting patterns for these
specific Victaulic FireLock automatic sprinklers. They are provided as information for guidance
in avoiding obstructions to sprinklers and should not be used as minimum sprinkler spacing
rules for installation. Refer to the appropriate Fire Code and the authority having jurisdiction
for specific information regarding obstructions, spacing limitations and area of coverage
requirements. Failure to follow these guidelines could adversely affect the performance of the
sprinkler and will void all Listings, Approvals and Warranties.
3 All patterns are symmetrical to the centerline of the waterway.
WARRANTY Refer to the Warranty section of the current Price List or contact Victaulic for details.
NOTE This product shall be manufactured by Victaulic or to Victaulic specifications. All products to be
installed in accordance with current Victaulic installation/assembly instructions. Victaulic reserves the
right to change product specifications, designs and standard equipment without notice and without
incurring obligations.
www.victaulic.com
-
VICTAULIC IS REGISTERED TRADEMARK OF VICTAULIC COMPANY, © 2007 viclAuLic COMPANY. ALL RIGHTS RESERVED. PRINTED IN THE LISA. iCtaulic
REVE 40.i87
Standard Spray/Pendent, Upright and Recessed Pendent
MODELS V2703, V2704, V2725, V2726, V2727 AND V2728
STANDARD AND QUICK RESPONSE
II IIIIIIIIIIIIIIIIIUIIIIIIIIIIIIIIJI
WCAS-65JLAZ
For complete contact information, visit www.victaulic.com
40.18 3476 REV E UPDATED 3/2007
VICTAUUc IS REGISTERED TRADEMARK OF VIcTAULIc COMPANY. © 2007 vicTAuLic COMPANY. ALL RIGHTS RESERVED. PRINTED IN THE USA. ____________
40.18
.WCONC Wi
TEW OVER
C
INSE 200k -AL 1,
07 ED.
DUCTIEIN
HIGH AREA
(see £pO3Y
PIPE TO RUN EXPOSED
AT RRE
DOOR
Y= {-3(101-61/2)+55
Y= 39.257 AREA REDUCTION
Y= 1500 SQ FT-39.257. AREA REDUCTION
Y= 912 SQ. FT.
FRA 13. 2002 1
'
24 E......
OVER
LO
ZONE OF INFLUENCE
SPRINKERS UNDER
'STEEL CANOPY
(see bldg, section B)
225 SOFT, MAX
EA REDUCTION FOR QUICK RESPONSE
RE SPRINKLERS PER NFPA 13, 2007 ED,
ICTION 1123.23.1
VET PIPE YSTEM
LIGHT HAZARD
10'-6' CEILING HEIGHT
(4- NO CEILING POCKETS
[I - - Fire Protection by Computer Design
A&D Fire Sprinklers
11465 Woodside Ave.
Santee ca 92071
619-448-1962
Job Name : Pacific Ridge
Building : FP02 Level 1
Location 6269 El Fuerte St. Carlsbad CA 92009
System : 6
Contract : F-428
Data File : Calc-6_L1-ap-chem.WXF
1]
Computer Programs by Hydratec Inc. Route 1.11 Windham N.H. USA 03087
S
A&D Fire Sprinklers Page 1
Pacific Ridge Date 09-02-09
HYDRAULIC CALCULATIONS
for
Project name: Pacific Ridge High School
Location: 6269 El Fuerte St. Carlsbad CA 92009
Drawing no: FP02 Level 1
Date: 09-28-09
Design
Remote area number: 6
Remote area location: AP/Chemistry
Occupancy classification: Ordinary Hazard 2
Density: .20 - Gpm/SqFt
Area of application: Entire Area - SqFt
Coverage per sprinkler: 126 - SqFt
Type of sprinklers calculated: VICTAULIC V27 Pendents
No. of sprinklers calculated: 14
In-rack demand: - GPM
Hose streams: 250 - GPM
Total water required (including hose streams): 599.75 -GPM @ 64.43 - Psi
Type of system: TREE
Volume of dry or preaction system: -Gal . Water supply information
Date: 08-20-09
Location: 6269 El Fuerte St. Carlsbad CA 92009
Source: Street Water
Name of contractor: A&D Fire Sprinklers
Address: 11465 Woodside Ave. Santee CA 92071
Phone number: 619-448-1962
Name of designer: Maria lniguez
Authority having jurisdiction: Carlsbad Fire Department
Notes: (Include peaking information or gridded systems here.)
Computer Proqrams by Hydratec Inc. Route 111 Windham N.H. USA 03087
Water Supply Curve (C)
A&D Fire Sprinklers Page 2
Pacific Ridge Date 09-02-09
City Water Supply: Demand:
Cl - Static Pressure : 112.5 Dl - Elevation : 8.012
C2 - Residual Pressure: 103.5 D2 - System Flow : 349.752
C2 - Residual Flow : 1075 D2 - System Pressure : 74.548
Hose (Adj City)
Hose ( Demand) : 250
D3 - System Demand : 599.752
Safety Margin : 34.894
150
140
130
120 j
R 110
E 100
- 90
s 80
u 7° I D3
R 60
E5°
40
30
20
Dl 10
.....
200 400 600 800 1000 1200 1400 1600 1800
FLOW (IN "1.85)
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Fittings Used Summary
A&D Fire Sprinklers
Page 3
Pacific Ridge
Date 09-02-09
Fitting Legend
Abbrev. Name '/2 ½ 1 1% 1'/2 2 21/2 3 31/2 4 5 6 8 10 12 14 16 18 20 24
E NFPA 13 90 Standard Elbow 1 2 2 3 4 5 6 7 8 10 12 14 18 22 27 35 40 45 50 61
F NFPA1345 Elbow 1 1 1 1 2 2 3 3 3 4 5 7 9 11 13 17 19 21 24 28
G NFPA13 Gate Valve 0 0 0 0 0 1 1 1 1 2 2 3 4 5 6 7 8 10 11 13
T NFPA139O Flow thruTee 3 4 5 6 8 10 12 15 17 20 25 30 35 50 60 71 81 91 101 121
Units Summary
Diameter Units Inches
Length Units Feet
Flow Units US Gallons per Minute
Pressure Units Pounds per Square Inch
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Pressure I Flow Summary - STANDARD
A&D Fire Sprinklers Page 4
Pacific Ridge Date 09-02-09
Node
No.
Elevation K-Fact Pt
Actual
Pn Flow
Actual
Density Area Press
Req.
75 9.0 5.6 12.09 na 19.47 0.2 95 7.0
76 9.0 5.6 11.8 na 19.24 0.2 95 7.0
76A 10.5 13.33 na
77 9.0 5.6 14.43 na 21.27 0.2 80 7.0
77A 10.5 16.01 na
78 9.0 5.6 14.84 na 21.57 0.2 100 7.0
78A 10.5 16.13 na
79 9.0 5.6 21.71 na 26.09 0.2 100 7.0
80 9.0 5.6 19.21 na 24.55 0.2 116 7.0
80A 10.5 20.52 na
79A 10.5 24.21 na
81 8.0 5.6 25.05 na 28.03 0.2 1 7.0
82 8.0 5.6 25.07 na 28.04 0.2 1 7.0
82A 10.5 26.35 na
82B 10.5 27.84 na
82C 10.5 46.91 na
83 10.5 5.6 18.37 na 24.0 0.2 120 7.0
84 8.0 5.6 19.46 na 24.7 0.2 1 7.0
84A 10.5 20.98 na
85 9.0 5.6 21.42 na 25.92 0.2 100 7.0
85A 10.5 23.32 na
86 8.0 5.6 24.19 na 27.54 0.2 1 7.0 86A 10.5 26.29 na
87 9.0 5.6 25.03 na 28.01 0.2 100 7.0
87A 10.5 27.32 na
88 8.0 5.6 31.28 na 31.32 0.2 1 7.0
88A S 10.5 33.46 na
M3 10.5 47.35 na
M13 10.37 57.31 na
TOR 10.37 58.52 na
FS1 8.37 59.42 na
FS2 8.37 60.45 na
BOR 0.5 64.44 na
UG -3.0 66.13 na
BF1 2.5 64.16 na
BF2 2.5 69.18 na
UG1 -3.0 71.94 na
UG2 -4.0 72.51 na
SOR -8.0 74.55 na 250.0
The maximum velocity is 28.63 and it occurs in the pipe between nodes 82B and 82C
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
5
Final Calculations - Hazen-Williams - 2007
A&D Fire Sprinklers Page 5
Pacific Ridge Date 09-02-09
Nodel Elevl K Qa Nom Fitting Pipe CFact Pt
to or Ftng's Pe Notes
Node2 Elev2 Fact Qt Act Eqv. Ln. Total Pf/Ft Pf
75 9 5.60 19.47 1 3E 6.914 4.950 120 12.086
to iT 5.762 12.676 -0.650
76A 10.500 19.47 1.08 0.0 17.626 0.1075 1.894 Vel = 6.82
0.0
76A 19.47 13.330 K Factor = 5.33
76 9 5.60 19.24 1 3E 6.914 8.040 120 11.803
to iT 5.762 12.676 -0.650
76A 10.500 19.24 1.08 0.0 20.716 0.1051 2.177 Vel = 6.74
76A 10.500 19.47 1 0.0 7.000 120 13.330
to 0.0 0.0 0.0
77A10.500 38.711.08 0.0 7.000 0.3831 2.682Vel =13.56
0.0
77A 38.71 16.012 K Factor= 9.67
77 9 5.60 21.27 1 3E 6.914 4.950 120 14.431
to iT 5.762 12.676 -0.650
77A 10.500 21.27 1.08 0.0 17.626 0.1266 2.231 Vel = 7.45
77A 10.500 38.71 1.25 0.0 0.500 120 16.012
S to 0.0 0.0 0.0
78A10.500 59.98 1.408 0.0 0.500 0.23600.118 Vel = 12.36
0.0
78A 59.98 16.130 KFactor= 14.93
78 9 5.60 21.57 1 1 2.305 6.870 120 14.840
to iT 5.762 8.067 -0.650
78A 10.500 21.57 1.08 0.0 14.937 0.1299 1.940 Vel = 7.55
78A 10.500 59.98 1.25 0.0 10.500 120 16.130
to 0.0 0.0 0.0
80A 10.500 81.55 1.408 0.0 10.500 0.4180 4.389 Vel = 16.80
0.0
80A 81.55 20.519 K Factor = 18.00
79 9 5.60 26.09 1 3E 6.914 4.410 120 21.708
to iT 5.762 12.676 -0.650
79A 10.500 26.09 1.08 0.0 17.086 0.1847 3.156 Vel = 9.14
0.0
79A . 26.09 24.214 KFactor = 5.30
80 9 5.60 24.55 1 3E 6.914 4.950 120 19.212
to 0.0. 6.914 -0.650
80A 10.500 24.55 1.08 0.0 11.864 0.1650 1.957 Vel = 8.60
80A 10.500 81.55 1.5 iT 8.727 2.660 120 20.519
to 0.0 8.727 0.0
79A10.500 - - 106.1 1.639 0.0 11.387 0.3245 3.695 Vel = 16.13
79A 10.500 26.09 1.5 1E 4.363 3.080 120 24.214
to 0.0 4.363 0.0 82B 10.500 132.19 1.639 0.0 7.443 0.4874 3.628 Vel = 20.10
0.0
82B 132.19 27.842 KFactor= 25.05
W 81 8 5.60 28.03 1 1E 2.305 9.040 120 25.046 to 0.0 2.305 -1.083 82A 10.500 28.03 1.08 0.0 11.345 0.2108 2.392 Vel = 9.82
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Final Calculations - Hazen-Williams - 2007
A&D Fire Sprinklers Page 6
Pacific Ridge Date 09-02-09
Nodel Elevi K Qa Nom Fitting Pipe CFact Pt
to or Ftngs Pe Notes
Node2 Elev2 Fact Qt Act Eqv. Ln. Total PfIFt Pf
0.0
82A 28.03 -. - 26.355 K Factor 5.46
82 8 5.60 28.04 1 1E 2.305 3.160 120 25.069
to IT 5.762 8.067 -1.083
82A 10.500 28.041.08 0.011.2270.21102.369 Vel = 9.82
82A 10.500 28.02 1.25 IT 6.617 0.500 120 26.355
to 0.0 6.617 0.0
82B10.500 56.061.408 0.07.1170.20891.487Vel _11.55
82B 10.500 132.19 1.5 1E 4.363 7.250 120 27.842
to IT 8.727 13.090 0.0
82C 10.500 188.25 1.639 0.0 20.340 0.9374 19.067 Vel =28.63
82C 10.500 0.0 3 0.0 14.500 120 46.909
to 0.0 0.0 0.0
M3 10.500 188.25 3.314 0.014.5000.03030.440Vel =7.00
0.0
M3 - 188.25 47.349 K Factor = 27.36
83 10.500 5.60 24.00 1 3E 6.914 9.580 120 18.367 S to 0.0 6.914 0.0
84A10.500 -24.01.08 0.016.4940.15822.610. Vel =8.41
0.0
84A 24.00 20.977 K Factor = 5.24
84 8 5.60 24.70 1 1E 2.305 7.540 120 19.455
to IT 5.762 8.067 -1.083
84A 10.500 24.7 1.08 0.0 15.607 0.1669 2.605 - Vel = 8.65
84A 10.500 24.00 1 0.0 4.000 120 20.977
to 0.0 0.0 0.0
85A 10.500 48.7 1.08 0.0 4.000 0.5860 2.344 Vel = 17.06
0.0
85A - 48.70 23.321 KFactor= 10.08
85 9 5.60 25.92 1 2E 4.61 3.580 120 21.425
to IT 5.762 10.372 -0.650
85A 10.500 25.92 1.08 0.0 13.952 0.1825 2.546 Vel = 9.08
85A 10.500 48.70 1.25 0.0 8.370 120 23.321
to 0.0 0.0 0.0
86A 10.500 74.62 1.408 0.0 8.370 0.3546 2.968 Vel = 15.38
0.0
86A 74.62 -26.289K Factor= 14.55
86 8 5.60 27.54 1 1E 2.305 7.540 120 24.186
to IT 5.762 8.067 -1.083
86A 10.500 27.54 1.08 0.0 15.607 02041 3186 Vei= 9.65
86A 10.500 74.62 1.25 0.0 1.620 120 26.289
to 0.0 0.0 0.6
-87A. 10.500 102.161.408 0.0 1.620 0.6340 1.027 --Vel -=-, 21.05
0.0 O 87A 102.16 27.316K Factor =19.55
87 9 5.60 28.02 1 2E 4.61 3.580 120 25.027
to IT 5.762 10.372 -0.650
87A 10.500 28.02 1.08 0.0 13.952 0.2107 2.939 Vel = 9.81
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Final Calculations - Hazen-Williams - 2007
A&D Fire Sprinklers Page 7
Pacific Ridge Date 09-02-09
Nodel Elevi K Qa Nom Fitting Pipe CFact Pt
to or Ftng's Pe ******* Notes
Node2 Etev2 Fact Qt Act Eqv. Ln. Total Pf/Ft Pf
87A 10.500 102.16 1.5 - 2E 8.727 4.250 120 27.316 - -
to 0.0 8.727 0.0
88A 10.500 -- 130.18 1.639 0.0 12.977 0.4738 6.148 Vet = 19.80 -
0.0
88A 130.18 33.464 K Factor = 22.50
88 8 5.60 31.32 1 1E 2.305 4.540 120 31.282
to iT 5.762 8.067 -1.083
88A 10.500 31.32 1.08 0.0 12.607 0.2590 3.265 Vel = 10.97
88A 10.500 130.18 1.5 1E 4.363 6.580 120 33.464
to iT 8.727 13.090 0.0
M3 10.500 161.5 1.639 0.0 19.670 0.7059 13.885 Vel= 24.56
M3 10.500 188.25 3 5E 50.956 52.660 120 47.349
to 0.0 50.956 0.056
M13 10.370 349.75 3.314 0.0 103.616 0.0956 9.907 Vet = 13.01
M13 10.370 0.0 4 2E 27.874 17.400 120 57.312
to 0.0 27.874 0.0
TOR 10.370 349.754.31 0.045.2740.0266 1.204Vel=7.69
TOR 10.370 0.0 4 0.0 1.500 120 58.516
to 0.0 0.0 0.866
FS18.370 349.754.31 0.01.5000.02670.040Vet =7.69
FS1 8.370 0.0 4 0.0 1.000 120 59.422
to 0.0 0.0 1.000 * Fixed toss = 1
FS28.370 349.754.31 0.01.000 0.02700.027Vet =7.69
FS2 8.370 0.0 4 1E 13.937 7.870 120 60.449
to 0.0 13.937 3.408
BOR.500 349.75 4.31 0.0 21 .8070.02660.580Vet =7.69
BOR .500 0.0 6 2E 40.168 11.660 140 64.437
to 0.0 40.168 1.516
UG -3 349.75 6.16 0.0 51.828 0.0035 0.182 Vet = 3.77
UG -3 0.0 6 3E 64.749 60.500 150 66.135
to 0.0 64.749 -2.382
BF1 2.500 349.75 6.09 0.0 125.249 0.0033 0.409 Vet = 3.85
BF1 2.500 0.0 6 0.0 5.290 140
to 0.0 0.0 5.000 * Fixed toss 5
- BF2 2.500 349.75 6.16 0.0 5.290 0.0036 0.019 - Vet =3.77
BF2 2.500 0.0 6 1 46.249 21.830 150 69.181
to 1G 4.625 94.040 2.382
UG1 -3 349.756.092E43.166115.8700.0033 0.378Vet =3.85
UG1 -3 0.0 8 iT 52.855 85.160 150 71:941
to iG 6.041 72.487 0.433
UG2-4 349.757.981F13.591157.647 - 0.00090.138 Vet =2.24
UG2 -4 0.0 8 3F 40.774 240.400 150 72.512
to iT 52.855 105.711 1.732
SOR-8 349.75 7.98 2G12.081346.111 0.00090.304Vet =2.24
250.00 Qa = 250.00 SOR 599.75 - 74.548 KFactor= 69.46
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
rlsbad Municipal Water Dist t
Potable Water Discharge
Event Report
Date: . 1ñ ZO
Location:
Reason for Discharge Event:
Type of Event:
Dewate ring Water Mains
Note: Includes flow testing and flushing
Dewatering Reservoirs
Unscheduled Water Discharge
Clear flow path of debris, surface
contaminants and/or hazardous
materials. Do not remove native
vegetation.
Erosion control, i.e.
sandbags, silt fencing, hay bales,
gravel bags, decreasing the velocity
of discharge water.
Initial
Estimated Discharge Flow:
Start Time ' ?
( v)
End Time
Pre-Dechlorination Residual:
ostDechlorination Residual:
. (less than 0.1 mg/L)
pH within limits of 6.0 and 9.0
7,,
Upon completion of dewatering, ensure
that the flow path is free of all
temporary erosion prevention materials.
-
Upon completion of dewatering, ensure
that any sediment or silted areas are
cleared.
Water Sampling Performed by:
Comments:
Flow Test Record
Test Hydrant
Location _ ;T C4 g c c-iFl
Hydrant ID Nc.Q LSize Main
911 0-4N
Static.............(
Residual ......... I
Pressure Drop 10 (PDI 1).....K factor for PDI 1 a '-7
Flow Hydrant(s)
Hydrant I iocation6pj .sf -Afl CA
Hydrant 2 location
Hydrant ') location_________
Hydrant 1 Pitot 'O PSI GPM: (O15 Size of Orifice______
Hydrant 2 Pitot PSI GPM: Size of Orifice___________
Hydrant 3 Pitot PSI GPM: Size of Orifice__________
Total:Lc5i
I) I* Calculated test and flow data - Q_x PD2L = Q2
PDI*k
Static....................
Desired Residual.......20
Pressure Drop (PD 2)..j' .................................K factor PD 2:
(015 x I 2€2.divided by 3_L equals 0 GPM at 20 psi residual
Q PD 2.k PD Ik - Q2
Comments:
Test conducted for
,I.
- C:onductedby: VA-\A
Date: OYOQ7 Time......0)
:... ...... .. . .,, .
Flow Test Record Formulas
GPM-Flow
2 V2" 4"
PSI GPM PSI GPM PSI GPM PSI GPM 1 170 16 670 1 430 16 1720
2 240 17 690 2 610 17 1770
3 290 18 710 3 740 18 1820
4 340 19 730 4 860 19 1870
5 380 20 750 5 960 20 1920
6 410 22 790 6 1050 22 2020
7 440 24 820 7 1140 24 2110
8 480 26 860 8 1220 26 2190
9 500 28 890 9 1290 28 2280
10 530 30 920 10 1360 30 2330
11 560 33 950 11 1430 32 2430
12 580 34 980 12 1490 34 2510
13 610 36 1010 13 1550 36 2580
14 630 '38 1040 14 1610 38 2650
15 650 40 1060 15 1660 40 2720
K 11 actor Formula
PD K PD K PD K PD K PD K .
1= 1.0 21= 5.18 41= 7.43 61= 9.21 81= 10.73
2= 1.45 22= 5.31 42= 7.53 62= 9.29 82= 10.80
3= 1.81 23= 5.44 43= 7.62 63= 9.37 83= 10.87
4= 2.11 24= 5.56 44= 7.72 64= 9.45 84= 10.94
5= 2.39 25= 5.69 45= 7.81 65= 9.53 85= 11.01
6= 2.63 26= 5.81 46= 7.91 66= 9.61 86= 11.08
7= 2.86 27= 5.93 47= 8.00 67= 9.69 87= 11.15
8= 3.07 28= 6.05 48= 8.09 68= 9.76 88= 11.22
9= 3.28 29= 6.16 49= 8.18 69= 9.84 89= 11.29
- 10= 3.47 30= 6.28 50= 8.27 70= 9.92 90= 11.36
11= 3.65 31= 6.39 51= 8.36 71= 9.99 91= 11.43
12= 3.83 32= 6.50 52= 8.44 72= 10.07 92= 11.49
13= 4.00 33= 6.61 53= 8.53 73= 10.14 93= 11.56
14= 4.16 34= 6.71 54= 8.64 74= 10.22 94= 11.63
15= 4.32 35= 6.82 55= 8.71 75= 10.29 95= 11.69
16= 4.48 36= 6.93 56= 8.79 76= 10.37 96= 11.76
17= 4.72 37= 7.03 57= 8.88 77= 10.44 97= 11.83
18= 4.76 38= 7.13 58= 8.96 78= 10.51 98= 11.89
19= 4.90 39= 7.23 59= 9.04 79= 10.59 99= 11.96
20= 5.04 40= 7.33 60= 9.12 80= 10.66 100= 12.02
*PD"'- Pressure drop K = K factor
S
/8tocoot
FIRE SPRINKLERS INC
PACIFIC RIDGE SCHOOL
Thc' Plans ho o been br 1,parcl0 ctIi1Ptiah1l
269 El F lie r te Street
-
o ii u ppori ot an appl%c0 ot S building
or nh the prns0 e undcrsia(tiltg thai ibis revie"
their
ny re, o" es the owner or or
Iesi0ii engineer or architect tor sole i espoflsihilitv
d codes and %tillfoar.LK
Carl s ba ci, C A 92009 tiCiCCu- errors. orni ons or negilgeflee in these
plans whether or 11.4 flOtCd in this review
\
" / evtCw er. XT
Install Fire Sprinklers
MMND APPROVAL. AS
Q
RECO NOTED
PRODUCT SUBMITTALS
MAUI ACTURE' S DATA SHEETS
ng
* Materials of equal design',
D
utility, and performance may b
construction schedule and shall b:
so as to avoid delays in the
4-. •
TABLE OF CONTENTS
FIRE SPRINKLERS
PIPING
FITTINGS
HANGERS
VALVES
GAUGE
DEVICES
FIRESTOPPING
BACKFLOW (FOR INFORMATION ONLY)
1) FIRE SPRINKLERS
® <@> JLPCB
SEE VICTAULIC PUBLICATION 10.01 FOR DETAILS
02
Standard Spray; Upright, Pendent and Recessed Pendent
MODELS/SIN. V2703 AND V2707 STANDARD RESPONSE
MODELS/SIN. V2704 AND V2708 QUICK RESPONSE
These Model V27 standard spray sprinklers are designed to produce a
hemispherical spray pattern for standard commercial applications. They are
available with either standard or quick response bulbs. The design incorporates
state-of-the-art, heat responsive, frangible glass bulb design (standard or quick
response) for prompt, precise operation.
The die cast frame is more streamlined and attractive than traditional sand cast
frames. It is cast with a hex-shaped wrench boss to allow easy tightening from many
angles, reducing assembly effort. This sprinkler is available in various temperature
ratings (see chart on page 2) and finishes to meet many design requirements.
The recessed pendent should be utilized with a Model V27 recessed escutcheon
which provides up to 3/4719 mm of adjustments.
f
UPRIGHT PENDENT RECESSED (V2703 AND (V2707 AND PENDENT V2704) V2708) (V2707 AND
V2708)
SPRINKLER OPERATION The operating mechanism is a frangible glass bulb which contains a heat responsive liquid. During a
fire, the ambient temperature rises causing the liquid in the bulb to expand. When the ambient tem-
perature reaches the rated temperature of the sprinkler, the bulb shatters. As a result, the waterway
is cleared of all sealing parts and water is discharged towards the deflector. The deflector is designed
to distribute the water in a pattern that is most effective in controlling the fire.
COVERAGE For coverage area and sprinkler placement, refer to NFPA 13 standards.
TECHNICAL SPECIFICATIONS
Cp
Exaggerated for clarity
Models/SIN.: V2703, V2704, V2707, V2708
Style: Pendent, Upright or Recessed Pendent
Nominal Orifice Size: 1/2"/13mm
K-Factor: 5.61mp./8.1S.l.A
Nominal Thread Size: ½" NPT/15mm
Max. Working Pressure:
175 psi/1200kPa FM Global
250psi/1725kPa UL
Factory Hydrostatic Test:
100% @ 500p5i/3450kPa
Mm. Operating Pressure: 7p5i/48kPa
Temperature Rating: See charts on page 2 & 3.
MATERIAL SPECIFICATIONS
Upright Deflector: Bronze per UNS C22000
Pendent Deflector: Bronze per UNS C51000
Bulb: Glass with glycerin solution.
Bulb Nominal Diameter:
Standard: 5.0 mm
Quick Response: 3.0 mm
Load Screw: Bronze per UNS C65100
Pip Cap: Bronze per UNS C65100
Spring: Beryllium nickel
Seal: Teflon* tape
Frame: Die cast brass 65-30
Lodgement Spring: Stainless steel per UNS
S30200
ACCESSORIES
Installation Wrench:
Open End: V27
Recessed: V27-2
Finishes:
Plain brass
Chrome plated
White painted**
Black palnted**
Custom painted**
Proprietary nickel Teflon* coating**
For cabinets and other accessories refer to
separate sheet.
NOTE: Weather resistant recessed escutcheons
available upon request.
A For K-Factor when pressure is measured in
Bar, multiply S.I. units by 10.0.
* Teflon is a registered trademark of Dupont Co.
**UL Listed for corrosion resistance in all
configurations.
JOB/OWNER CONTRACTOR
Sysfern No. __________________________ Submitted By
dtion Date__________________________________
wwv,victaulic .com
vR:ui ft iS A ii CiA i iii.!) I iiADi MARK UI VICIAU Lir COMPANY. U ?O08 vic i-Aol iC COMPANY. ALL vim i is vrsirivro.
RE G
ENGINEER
Spec Sect
Approved
Date
Para___________
XAi
4010 1
FIRE PRE P ODUC2S UTQMAT(C SPRINKLERS 40.10
V27, K%06
Standard Spray; Upright, Pendent and Recessed Pendent
MODELS/SIN. V2703 AND V2707 STANDARD RESPONSE
MODELS/SIN. V2704 AND V2708 QUICK RESPONSE
Orifice Size (inches)
Orifice Size (mm)
½
13
½
13
½
13
/2
13
½
13
/r
53
Nominal K Factor Imperial 5.6 5.6 5.6 5.6 5.6 5.6
Nominal K Factor S.l. 8.1 8.1 8.1 8.1 8.1 8.1
Response Standard Standard E Standard Quick Quick Quick
Deflector Type Upright Pendent lecesed UPendentpright Pendent Recessed
Pendent
Adjustment up to 4' up to 4'
135Ff57C 135F/57C
155Ff68C 155F/68C 135F/57'C 135F/57C 135Ff57C 135F/57'C
UL 175Ff79C 175F/79C 155F/68C 155FI68C 155F/68C 1S5F/68C 200F/93C 200F/93C 175F/79C 175Ff79C 175Ff79C 175Ff79
286F/141C 286F/l4tC 200F/93C 200Ff93C 200F/93C 200F/93C 360F/182C 360 c Ff182 286'F/141'C 286 Ff141 C 286'F/141'C
135F/57C 135F/57C =
155Ff68C 155F/68.0 135 F/57 C 135 Ff57 C 135'F/57'C
ULC 175Ff79C 175F/79C 155Ff68C 155Ff68C 155Ff68C
2007/93T 200T/9 175'F/79'C 1750F/790C 175OF/790C
286OF/14laC 286'F/1410 200F/
3602*c 36F/1C 286C 286'U141C 286'F/14]'C
135Ff57C 135F/57C
1557/68C 155Ff68C . 135F/57C
t35p/57C t3SF/57C
. 135Ff57C
FM # 175F/79C 175F/79C 155F/68C 155'F/68'C 155 Ff68 C 1557/68C
200F/93C 200F/93C 175F/79C 5Ff79C 1750F/790C 1757f79C
286 F/141C 286 F/141C 200 Ff93 C 200'F/93*C 200'F/93'C 200 Ff93 C
360'F/182'C 360*F/182'c 286 FfMtC 286 41C
1557/68T 155T/68T 135Ff57*C 135F/57C 135F/57C 135F/57C
NYC/MEA 6 62-99. 175Ff79C 175F/79C 155 Ff68C 1551Ff68C 155F/68C
155F/68C
200F/93C 2O0Ff93C 175'F/79'C 175'F/79'C 175'F/79'C 175F/79C W 286F/141C 286Ff141C 200'F/93'C 200Ff930C 200Ff93C 200F/93C
360 2' 360Ff182C 286 F/t41C 286F/141C 286F/141C
) 135F/57*C 135F/57C
155Ff68C 155F/68C 135Ff57C 135F/57C 135F/57C 135'F/57'C
CSFM # 7690-0531:112 155 Ff68C 15 F/C 155 Ff68 C 1550F/68'C
2000F/93T 200'F/93*C 175'F/79'C 175 Ff79 F/79'C
286Fft4rC 28&F/141C 200 Ff93 C 200 Ff93 C 200 Ff93 C 200F/93C 360 F/182 C 360 Ff182 C 286 F/141 C 286'F/141'C 286 Ff141 C
135'F/57'C
: LPCB t7SF/79C 135Ff57C 155Ff68C 135'F/57'C
200F/93C 175Ff79C 175F/79C 175F/79C None None
28MF/141C 200F/93C 200F/93C 200F/93C
....0Ffi82C .286F/1 41C
135Ff57C 135Ff57C ..
155T/68T 155Ff68C 135Ff57*C 35f57:C 135F/57C
135F/57C
VNIIPO E 175F/79C 175Ff79C 155Ff68C 1557/68T 1550F/680C 155Ff68C 200Ff93C 200F/93C 17SFf79C 1757/79T 175 Ff79 C 175Ff79C
286Ff141C 286Ff141C 200Ff93C 200 Ff93 C 200F/93C 200Ff93C
360'F/182'C 360'F/182'C 286 Ff141 C 286'F/141'C
S Listings and Approvals as of printing. All are approved open, except for areas designated'No".
For K Factor when pressure is measured in Bar, multiply S.I. units by 10,0
a FM Approved with 1/2 adjustment escutcheon only - quick response
www.vjctauljc.com / VICTAULIC ISA REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2008 VICTAULIC COMPANY. ALL RIG HIS RESERVED.
4O.1Q2 '•
FIRE PROTECTION PRODUCTS AUTOMATIC SPRINKLERS 40.10
E
1127, FA5.6
Standard Spray; Upright, Pendent and Recessed Pendent
MODELS/SIN. V2703 AND V2707 STANDARD RESPONSE
MODELS/SIN. V2704 AND V2708 QUICK RESPONSE
RATINGS All elass hnIh, Arp. rated for temrreratiirec from -FC7°FI-AA°C to Shone ehorun in table helew
Ordinary A 1535 100 Orange 38
Ordinary c 155 13tl30 Red 68 .
Intermediate E 175 150 Yellow 65
Intermediate F 200 150 Green 93 65
High 286 225- Blue 141 107
Extra High ..K .360 300 Purple 182 149
-* M . Open - No Bulb
ORDERING INFORMATION
h Standard response only.
All are approved open, except for areas designated "No.
- 150/65 if wax coated.
Please specify the following when ordering:
www.victaulic.com
VII: I nra IC IS A IliOlsiFlul) mACIMAge or vlc I An IC COMPANY. © 2008 VICTAUIIC COMPANY. Alt 9101 I iS rirsErivED.
REV C xk—auhcl
40.10 3
Standard Pendent - V2707, V2708
6n
1 14,17
25mm
Standard Upright - V2703, V2704
t— 32A/
317MM
6IYJbñ/ 41 t~lihn
RNcLER% 40.10
Standard Spray; Upright, Pendent and Recessed Pendent
MODELS/SIN. V2703 AND V2707 STANDARD RESPONSE
MODELS/SIN. V2704 AND V2708 QUICK RESPONSE
WARNING A
- - àWARNING
Always read and understand installation, care, and maintenance
instructions, supplied with each box of sprinklers, before proceeding
with installation of any sprinklers.
Always wear safety glasses and foot protection.
Depressurize and drain the piping system before attempting to
install, remove, or adjust any Victaulic piping products.
Installation rules, especially those governing obstruction, must be
strictly followed.
Painting, plating, or any re-coating of sprinklers (other than that sup-
plied by Victaulic) is not allowed.
Failure to follow these instructions could result in serious personal
injury and/or property damage.
The owner is responsible for maintaining the fire protection system and
devices in proper operating condition. For minimum maintenance and
inspection requirements, refer to the current National Fire Protection
Association document NFPA 25 that describes care and maintenance
of sprinkler systems. In addition, the authority having jurisdiction may
have additional maintenance, testing, and inspection requirements that
must be followed.
If you need additional copies of this publication, or if you have any
questions about the safe installation of this product, contact Victaulic
World Headquarters: P.O. Box 31, Easton, Pennsylvania 18044-0031
USA, Telephone: 001-610-559-3300.
S
½ Adjustment Recessed - V2707, V2708 (drawing not to scale)
2/51 mm
Min Hole
7Hm/m 30 Typical Ceiling
3 Finished Surface
MAXIMUM RECESS
30 m
7S mnn
MAXIMUM EXTENSION
www.victaulic.com
VICTAULIC ISA REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 28 VICTAULIC COMPANY. ALL RIGHTS RESERVED.
... 40t04
REV (
FIRE PROTECTION PRODUCTS ..• AUTOMATIC SPRINKLERS 40.10
"' . Standard Spray; Upright, Pendent and Recessed Pendent
MODELS/SIN. V2703 AND V2707 STANDARD RESPONSE
MODELS/SIN. V2704 AND V2708 QUICK RESPONSE
DIMENSIONS 3/4 Adjustment Recessed - V2707, V2708 (drawing not to scale)
2W/HO mm
Mao. Hole
M! Hole
240
MAXIMUM RECESS
2'Rr/
75 MM
MAXIMUM EXTENSION
PA
AVAILABLE WRENCHES
Sprinkler Type V27-2 Recessed V27 Open End
V2707,V2708Pendent yes yes
V2707, V2708 Recessed Pendent yes -
V2703, V2704 Upright yes yes
DISTRIBUTION PATTERNS Models/SIN. V2707, V2708
K5.6 standard pendent and recessed pendent distribution patterns - trajectory
10• S,_•__ 30m - ;---..
4..
••%. _'44•4_. • 04% S 4
2.4ro
"s4 444
F
6'
1 Sm S444_ *•
\ 0 %
44
\\ 44
4' 12m 4
\ t4
44
2'
06m I
1 4
44
1 f -
O . 444
2' 4' 6 8' 10' 12' 14'
OEm 12m 18m 24m 30m 33m 43m
7p5i 15 psi 30po 48kPa 103kPa 207kPa
See notes on next page.
www.victaulic.com
I t VICIAULIC IS 10[ CISVEIIED TRADEMARK OF VICTAULIC COMPANY. 02008 VICTAULIC COMPANY. ALL FlIGHTS RESERVED.
REV G
40,10 5
10
3Cm
j - ---- 2.
4' 6 a' is' 12'
1.2m 1.8m 2.4m 3Cm 3.7m
15 psi 30 psi
103 kPa 207 kPa
%44,4
16
4.3m 4gm
FIRE PROTECTION t ' ITOMATIC SPRINKLERS 40.10
V27, K56
Standard Spray; Upright, Pendent and Recessed Pendent
MODELS/S.I.N. V2703 AND V2707 STANDARD RESPONSE
MODELS/SIN. V2704 AND V2708 QUICK RESPONSE
DISTRIBUTION PATTERNS Models/SIN. V2703, V2704
K5.6 standard upright distribution patterns - trajectory
NOTES:
1 Data shown is approximate and can vary due to differences in installation.
2 These graphs illustrate approximate trajectories, floor-wetting, and wall-wetting patterns for
these specific Victaulic FireLock automatic sprinklers. They are provided as information for
guidance in avoiding obstructions to sprinklers and should not be used as minimum sprinkler
spacing rules for installation. Refer to the appropriate NFPA National Fire Code or the authority
having jurisdiction for specific information regarding obstructions, spacing limitations and area
of coverage requirements. Failure to follow these guidelines could adversely affect the perfor-
mance of the sprinkler and will void all Listings, Approvals and Warranties.
3 All patterns are symmetrical to the centerline of the waterway.
www.victaulic.com
\ vICIAULIC IS A IlECISIEHED rHADEMARK OF VICTAUU 4 taulic C COMPANY. © 2003 vICTAuLIC COMPANY. ALL RIGHTS RESERVED, ------ 40.106
REV C
IC SPRiNkLERS 40.10
Standard Spray; Upright, Pendent and Recessed Pendent
MODELS/SIN. V2703 AND V2707 STANDARD RESPONSE
MODELS/SIN. V2704 AND V2708 QUICK RESPONSE
WARRANTY Refer to the Warranty section of the current Price List or contact Victaulic for details.
NOTE This product shall be manufactured by Victaulic or to Victaulic specifications. All products to be
installed in accordance with current Victaulic installation/assembly instructions. Victaulic reserves the
right to change product specifications, designs and standard equipment without notice and without
incurring obligations.
I www.victaufic.com
VICTAU IC IS A ALGiSTEIlCi) I RADEMARK OF VICTAULIC COMPANY. 0 2008 ViCTAULic COMPANY, ALL RIGHTS RESERVED.
S Standard Spray; Upright, Pendent and Recessed Pendent
MODELS/S.I.N. V2703 AND V2707 STANDARD RESPONSE
MODELS/SIN. V2704 AND V2708 QUICK RESPONSE
III I III ID IIIIIIIIIIIIIIIIIIIIIIIIIIIIIII III
WCAS-7L5H QV
For complete contact information, visit www.victaulic.com \J/f 40.10 :2544 REV G UPDATED 11/2008
VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2008 VICTAULIC COMPANY. ALL RIGHTS RESERVED.
40W
ILPCBI(E
SEE VICTAULIC PUBLICATION 10.01 FOR DETAILS
Adjustable Concealed Standard Spray Pendent Standard and Quick Response
V3801 STANDARD RESPONSE
V3802 QUICK RESPONSE
This concealed, designer style sprinkler allows up to'½713mm adjustment to accommodate
concealment needs. The "standard" design provides a consistent hemispherical spray pattern.
The separate two-piece mounting cup/cover plat allows easy installation and testing prior to
ceiling installation. It also permits removal of suspended ceiling panels without system shut-
down. The design incorporates state-of-the-art, heat responsive, frangible glass bulb design
(standard or quick response) for prompt, precise operation.
This sprinkler is available in various temperature ratings (see chart on page 2) and finishes to
meet many design requirements.
V3801 AND V3802
SPRINKLER OPERATION: The operating mechanism is a frangible glass bulb which contains a heat responsive liquid. During
a fire, the ambient temperature rises causing the liquid in the bulb to expand. When the ambient
temperature reaches the rated temperature of the sprinkler, the bulb shatters. As a result, the water-
way is cleared of all sealing parts and water is discharged towards the deflector. The deflector is
designed to distribute the water in a pattern that is most effective in controlling the fire.
COVERAGE: For coverage area and sprinkler placement, refer to NFPA 13 standards.
Exaggerated for clarity
JOB/OWNER
System No,
Location
Models: V3801, V3802
Style: Adjustable concealed, ordinary hazard,
light hazard
Nominal Orifice Size: ½/13 mm
K-Factor: 5.61mp./8.1S,l.A
Nominal Thread Size: 1/2"/15mm
Max. Working Pressure: 175 psi/1200 kPa
Factory Hydrostatic Test: 100% @ 500 psi,
3450 kPa
Mm. Operating Pressure: 7 psi/48 kPa
Temperature Rating: See chart on page 2.
MATERIAL SPECIFICATIONS
Deflector: Bronze per UNS C22000
Cover Plate: Fusible solder
Bulb: Glass with glycerin solution.
Bulb Nominal Diameter:
Standard: 5,0 mm
Quick Response: 3,0 mm
Load Screw: Bronze per UNS C65100
Pip Cap: Bronze per UNS C65100
Spring: Stainless steel per UNS S30100
Seal: Teflon* tape
Frame: Die cast brass 65-30
Pins: Stainless steel per UNS S30400
Cup: Cold rolled steel, zinc chrome plated
Cover/Escutcheon: Brass per UNS C26000
Lodgement Spring: Stainless steel per UNS
S30200
Protective Cap: Polyethylene
CONTRACTOR
Submitted By
Date
ACCESSORIES
Installation Wrench:
Concealed: V38-4 or V38-5
Sprinkler Finishes:
Plain brass (only)
Cover Finishes:
Chrome plated
White painted
Flat black
Custom painted
A For K-Factor when pressure is measured in
Bar, multiply S.I. units by 10.0.
* Teflon is a registered trademark of Dupont Co.
ENGINEER
Spec Sect Para
Approved
Date
www.victaulic.com
vICTAuLIC IS A REGISTERED TRADEMARK OF VICTAuLIC COMPANY. Q 2009 vIcTAuuC COMPANY. ALL RIGHTS RESERVED.
REV K
'Lic
40,50 1
FIRE PROTECTION PRODUCTS AUTOMATIC SPRINKLERS
1138, K56
Adjustable Concealed Standard Spray Pendent Standard and Quick Response
V3801 STANDARD RESPONSE
V3802 QUICK RESPONSE
40.50
Orifice Size (inches) ½
Orifice Size (mru)
Nominal K Factor Imperial 5.6 5.6
Nominal K' Factor S.I. 8.1 8.1
Standard Quick# Response p . 5mm bulb 3mm bulb
Concealed Concealed Deflector Type Pendent . Pendent
Adiustment
135°F/57°C 1350F/57°C
155°F/680C 155°F/680C UL 175"F/79°C 175°F/790C
2000F/930C 200°F/930C
1350F/570C 135°F/57°C
155°F/68°C 1550F/680C ULC 1750l/79°C 175°F/790C
200017/930C 200°F/93°C
155°F/68°C#
FM# 175°F/79°C#
20 00F/930C 44
1350F/570C 1350F/570C
rccotlrcoor
NYC/MEA 41 62-99-E 1750F/790C . 1750F/79°C
2000F/930C 2000F/930C
135°F/570C 135°F/57°C
1550F/680C 155°F/68°C CSEM It 7690-0531:112 1750F/790C 175°F/79°C
2000F/930C 200°F/93°C
155"F/68"C Sprinkler/138"F/59"C Cover I 155"F/68"C Sprinkler/138"F/59"C Cover
LPCB 175"1/79"C Sprinkler/165"F/74"C Cover 1757/79"C 5prinkler/165"F/74"C Cover
200'F/93'C Sprinkler/165'F/740C Cover 200'F/93'C Sprinkler/165'F/74'C Cover
135°F/57°C i. 135°F/57°C
15501/68cC 155°F/68°C
VNIIPO 175°F/79°C 175°F/79°C
2000F/930C 2000F/930C
286°F/1410C 286°1/141°C
Recognized by FM as standard response only
6 Listings and Approvals as of printing. All are approved open, except for areas designated "No.
For K Factor when pressure is measured in Bar, multiply S.I. units by 10,0
www.victaulic.com
vic lAlILIC IS l'lEClSi lIVED tRADEMARK OF VICTAUL?C COMPANY. © 2009 viclAuLic coM PAN Y. ALL RICHES RESERVED.
4050 2 REV K
FIRE PROTECTION PRODUCTS. AUTOMATIC SPRINKLERS 40.50
61
S Adjustable Concealed Standard Spray Pendent Standard and Quick Response
V3801 STANDARD RESPONSE
V3802 QUICK RESPONSE
RATINGS All glass bulbs are rated for temperatures from -67°F/-55°C to those shown in table below.
--: i
Ordinary .A 135 100
57 38 Orange A iiø luu
57 38
Ordinary
.
C 155 100
68 38 Red DF 165 150
74 65
Intermediate E . 175 16 5
50 Yellow
Intermediate . F 200 150
93 65 Green
ORDERING INFORMATION
A For use with Standard or Quick Response Concealed Sprinkler 135FI57C or 155F/68C.
* D For use with Standard or Quick Response Concealed Sprinkler I75F/79C or 200F/93C
Custom Finish - Customer to provide paint specification, allow 4-6 weeks for samples.
0 138F/59C per LPBC
Please specify the following when ordering:
L4
WARNING A A WARNING
Proper temperature rated cover must be used with the correct sprinkler rating per the
Temperature Chart Ratings.
The plastic shipping cap must be removed for the sprinkler to operate properly.
If shipping cap is replaced over an installed sprinkler for purposes of painting or plaster-
ing, then the fire protection system shall be considered out of service, the Authority Having
Jurisdiction notified, and a firewatch is suggested.
Failure to do so may result in failure of sprinkler to operate causing serious personal injury or
property damage.
S www.victaulic.com
vlclAuuc IS REGISTERED TRADEMARK OF vicTAuLic COMPANY. © 2009 VICTAULIC COMPANY. ALL RIGHTS RESERVED.
REV K
JIE( F. ODUCTS.. A C SPRINKLERS
.) )
Adjustable Concealed Standard Spray Pendent Standard and Quick Response
V3801 STANDARD RESPONSE
V3802 QUICK RESPONSE
......................... A ...
40.50
WARNING -- WARNING
Always read and understand installation, care, and maintenance
instructions, supplied with each box of sprinklers, before proceeding
with installation of any sprinklers.
Always wear safety glasses and foot protection.
Depressurize and drain the piping system before attempting to
install, remove, or adjust any Victaulic piping products.
Installation rules, especially those governing obstruction, must be
strictly followed.
Painting, plating, or any re-coating of sprinklers (other than that sup-
plied by Victaulic) is not allowed.
Failure to follow these instructions could result in serious personal
injury and/or property damage.
The owner is responsible for maintaining the fire protection system and
devices in proper operating condition. For minimum maintenance and
inspection requirements, refer to the current National Fire Protection
Association pamphlet that describes care and maintenance of sprinkler
systems. In addition, the authority having jurisdiction may have addi-
WE
tional maintenance, testing, and inspection requirements that must be
followed.
If you need additional copies of this publication, or if you have any
questions about the safe installation of this product, contact Victaulic
World Headquarters: P.O. Box 31, Easton, Pennsylvania 18044-0031
USA, Telephone: 001-610-559-3300.
... ....... _ .............. -..- ......... .. .............. ......................... ........... . . - .............. . . . ............... ............
www.victaulic.com
VIC IAULIC IS YLCISI Eli LO I RADYMARK UI VIC IALJUC COMPANY 02009 VIC TAULIC COMPANY. ALL RIGHTS RESERVED.
40b04
2A/68 mm
Max. Hole
T 2W/SO mm
r•-
Mix. Hole
ll
2hs'/
MINIMUM EXTENSION Finished Surface
3t1/780 mm
TC s AUTOMATIC SPRINKLERS
Adjustable Concealed Standard Spray Pendent Standard and Quick Response
V3801 STANDARD RESPONSE
V3802 QUICK RESPONSE
DIMENSIONS IModels V3801, V3802 (drawings not to scale)
40.50
mm
mm
½713 mm Adjustment
3W/83mm _____
Cover Plate
MAXIMUM EXTENSION
2/51 mm
Typical Ceiling Tile
s'— Finished Surface
AVAILABLE WRENCHES
Concealed Pendent -V3801,V3802 V38-4 or V38-5
40 www.victaulic.com I - ' Fuctaulic VicrAULIC IS A REGIS IEAED TRADEMARK OF VICTAULIc COMPANY. © 2009 VICTAULIC COMPANY. ALL RIGHTS REScrrvEo. -_- -_ REV K 4050 5
"V.
FEE PROTECTiON PRODUCTS AUTOMATIC SPRINKLERS . Adjustable Concealec Standard Spray Pendent Standard and Quick Response
V3801 STANDARD. RESPONSE
V3802 QUICK RESPONSE
DISTRIBUTION PATTERNS Models V3801, V3802
K5.6 standard concealed pendent distribution patterns - trajectory
b ° 3m
8.
2' '
0.6w 1.2w iBm 2.4m 3.0w 3.7m 4.3w
NOTES:
1 Data shown is approximate and can vary due to differences in installation.
2 These graphs illustrate approximate trajectories, floor-wetting, and wall-wetting patterns for
these specific Victaulic FireLock automatic sprinklers. They are provided as information for
guidance in avoiding obstructions to sprinklers and should not be used as minimum sprinkler
spacing rules for installation. Refer to the appropriate NFPA National Fire Code or the authority
having jurisdiction for specific information regarding obstructions, spacing limitations and area
of coverage requirements. Failure to follow these guidelines could adversely affect the perfor-
mance of the sprinkler and will void all Listings, Approvals and Warranties.
3 All patterns are symmetrical to the centerline of the waterway.
www.victaulic.com
\J'tauuic VIC'IAU s. i IS A iiFGiSIEAi 0 TRADEMARK DI VICIAULIC COMPANY. 02009 VICTAULIC COMPANY, ALL RIGHTS RESERVED.
FIRE PROTECTION PRODUCTS ... AUTOMATIC SPRINKLERS 40.50 . Adjustable Concealed Standard Spray Pendent Standard and Quick Response
V3801 STANDARD RESPONSE
V3802 QUICK RESPONSE
WARRANTY Refer to the Warranty section of the current Price List or contact Victaulic for details.
...............................
NOTE This product shall be manufactured by Victaulic or to Victaulic specifications. All products to be
installed in accordance with current Victaulic installation/assembly instructions. Victaulic reserves the
right to change product specifications, designs and standard equipment without notice and without
incurring obligations.
........... ............. .....
www.victaulic.com . 1 ictauluc ViUiAui]CIS A il [CIS 1LREi) IRADEMASKOI- vicinuuc COMPANY. 02009viCTAIJLic COMPANY. ALL RIG HIS REsEIYv[o
. Adjustable Concealed Standard Spray Pendent Standard and Quick Response
V3801 STANDARD RESPONSE
V3802 QUICK RESPONSE
11111 I I III liii 111111111 III III 111111 liii III
WCAS-7MYMKY
For complete contact information, visit www.victaulic.com
40.50 2558 REV K UPDATED 1/2009
VICTAULIC IS REGISTERED TRADEMARK OF VICTAULIC COMPANY. 0 2009 vICTAUUC COMPANY. ALL RIGHTS RESERVED. XA -ti~~u -h C~ 4050
. Standard Spray Horizontal Sidewall and Recessed Horizontal Sidewall Standard and
Quick Response
MODELS/SiN. V2709 AND V2710
These Model V27, standard spray horizontal sidewall sprinklers are designed for up to ordinary
Hazard per NFPA 13, and can be used for standard or recessed installations. The design provides
a crescent-shaped water discharge pattern for installation along a wall or under a beam or ceiling.
The design incorporates state-of-the-art, heat responsive, frangible glass bulb design (standard or
quick response) for prompt, precise operation.
The die cast frame is more streamlined and attractive than traditional sand cast frames. It is cast with
a hex-shaped wrench boss to allow easy tightening from many angles, reducing assembly effort.
This sprinkler is available in various temperature ratings (see chart on page 2) and finishes to meet
many design requirements.
The recessed pendent should be utilized with a Model V27 recessed escutcheon which provides up
to /4/19 mm of adjustments.
STANDARD HORIZONTAL SIDEWALL
(V2709, V2710)
RECESSED HORIZONTAL SIDEWALL
(V2709, V2710)
SPRINKLER OPERATION: The operating mechanism is a frangible glass bulb which contains a heat responsive liquid. During a fire,
the ambient temperature rises causing the liquid in the bulb to expand. When the ambient temperature
reaches the rated temperature of the sprinkler, the bulb shatters. As a result, the waterway is cleared of
all sealing parts and water is discharged towards the deflector. The deflector is designed to distribute the
water in a pattern that is most effective in controlling the fire.
COVERAGE: For coverage area and sprinkler placement, refer to NFPA 13 standards
JOB/OWNER CONTRACTOR ENGINEER
System No._ Submitted By - Spec Sect - Para
Location Date Approved -
Date
www.viCtaulic.Com
ViCTAuLiC is A REGISTERED TRADEMARK OF vicTAuLic COMPANY. © 2009 ViCTAULIC COMPANY. ALL RIGHTS RESERVED, 'JtauIic
REVG 40,11 1
FIRE PROTECTION PRODUCTS AUTOMATIC SPRINKLERS
V27, K56
40.11
S Standard Spray Horizontal Sidewall and Recessed Horizontal Sidewall Standard and
Quick Response
MODELS V2709 AND V2710
TECHNICAL SPECIFICATIONS:
óy
Exaggerated for clarity
Models/S.l.N.: V2709, V2710
Style: Horizontal Sidewall or Recessed
Horizontal Sidewall
Nominal Orifice Size: ½/13mm
K-Factor: 5.6 Imp./8.1 S.l.A
Nominal Thread Size: W715 mm
Max. Working Pressure:
175 psi/1200kPa FM Global
250 psi/1725 kPa UL
Factory Hydrostatic Test: 100% © 500 psi/
3450 kPa
Mm. Operating Pressure: 7p5i/48kPa
Temperature Rating: See chart on page 2.
MATERIAL SPECIFICATIONS
Horizontal Deflector: Commercial bronze per
UNS C22000
Bulb: Glass with glycerin solution.
Bulb Nominal Diameter:
Standard: 5.0mm
Quick Response: 3.0mm
Load Screw: Low Silicon bronze per
UNS C65100
Pip Cap: Low Silicon bronze per UNS C65100
Seal: Teflon* tape
Spring: Beryllium nickel
Frame: Die cast brass 65-30
Lodgement Spring: Stainless steel per
UNS S30200
ACCESSORIES
Installation Wrench:
Open End: V27
Recessed: V27-2
Sprinkler Finishes:
Plain brass
Chrome plated
White painted**
Flat black painted"
Custom painted"
Proprietary Nickel/Teflon* Coating**
For cabinets and other accessories refer to
separate sheet.
NOTE: Weather resistant recessed escutcheon
available upon request.
A For K-Factor when pressure is measured in
Bar, multiply S.I. units by 10.0.
* Teflon is a registered trademark of Dupont Co.
**Also, UL Listed for corrosion resistance in all
configurations.
S
vicrAuLIc IS REGISTERED TRADEMARK OF VICTAuLIC COMPANY. © 2009 vlcrAuuc COMPANY. ALL RIGHTS RESERVED.
4011 2 REV G
F Et ON PRODUCTS AUTOMATIC SPRINKLERS riiiui
\I27 '(-
Standard Spray Horizontal Sidewall and Recessed Horizontal Sidewall Standard and
Quick Response
MODELS V2709 AND V2710
iIL
Orifice Size (inches) /2 Ii
.
Orifice Size (mm) 13 13 13 13 13
Nominal K Factor Imperial 5.6 5.6 5.6 5.6 5.6
Nominal K Factor S.I.° 8.1 8.1 8.1 8.1 8.1
Response . Standard . Standard Standard Quick Quick
Recessed Recessed Recessed
Deflector T Type Horizontal Horizontal Horizontal Horizontal
Sidewall 9
5
izonl
5 I ewa Sidewall Sidewall (up to ½ Sidewall (up to 3C
= . adjustment) adjustment)
135°F/57°C
155°F/680C 135°F/57°C 135 1/570 C 135°F157°C 1350 F1570C
UL 17501/790C 155°F/68°C 155 Ff68 C
175 1/79 C 1550F/680c 155°F/68°c
20001/930c 175°F/79°c 175°F/79°c 175°F/79°C
286°F/141°C 200°F/93°C 200 Ff93 C 200°F/93°C 200°F/93°C
360°F/182°C 286 F/141
135°F/57°C 135 °F/s7°c
1
0F/570C . 155°F/68°C 135°F/57°C 155 Ff68 C 1350F1570C
ULC 1750F179°C 155°1/68°C 175 19C 155°F/68°C . 155°F/68°C
200°F/93°C 175°F/79°C 1750F/790C 175°F/79°C
286 Ff141 C 200 Ff93 C 80 Ff141 C 200 Ff93 C 200 Ff93 C
135°Ff57°C 1350Ff570C 155°F/68°C 135°1/57°C 155 ° /68°C 1350F157°C
FM# 175°F/79°C 155°F/68°C 175 F 9 155°Ff68°C None 200°F193°C 17501/790C
20001/930C
1750Ff790C
200°F/93°C
135°1157°C
155°1/68°C 135°1157°C 0 135 1/5
0
C 135°F/57°C 1350F/57°C
6 NYC/MEA 6299 E 175°Ff79°C
200°1193°C
155°F/68°C 155F/68
175 Fl 9C 155°Ff680C 1550F1680C
1750F/79°C 175°F/79°C 1750Ff790C
286°Ff141°C . 200°F193°C 200°F/93°C 200°Ff930C
360°F/182°C otioc
135°F/57°C
155°F/68°C 135°F/57°C 135°F/57°C 135°F/57°C 135°F157°C
CSFM U 7690-0531112 175°1f79°C 555°F/68°C . 155 Ff68 C
175 F/9C 1550F/68°C 1550Ff680C
200°1f93°C . 175°F/790C 175°F/79°C 175°Ff79°C
286°Ff141°C 200°Ff93°C 200°F/93°C 200°F/93°C
360-F/ 182-C 286°F/ 141°C
135°F157°C
1550Ff680C 135 7
LPCB:104b/01
# 104b/02 None None . None
286°Ff141°C
360°F/182°C 86°F/141°C 2
135°F157°C
15501168°C . 135°F/57°C 1 °Ff 7° 135°F/57°C
VNIIPO 175°Ff79°C 155°F168°C 155°F/68°C 155°F/68°C
200°1f93°C 175°F/79°C 175°F/79°C 175°Ff79°C None
286°F/1410C 200°F/93°C 2 °F/93°C 200°F/93°C
360°F1182°C 2 8 6°F/141°C
I Listings and Approvals as of printing. All standard responses are approved open.
For K Factor when pressure is measured in Bar, multiply S.I. units by 10,0
II Light Hazard ONLY
www.victauljc.com
VIcLAULIc IS REGISTERED TRADEMARK OF VlCTAuLIc COMPANY. © 2009 VICTAULIc COMPANY. ALL RIGHTS RESERVED.
REV C
XA-9~t-auhl~i
4011 3
n
JIEC QD1JC1S AUTOMATiC SPRINKLERS 40.11
V27xV
Standard Spray Horizontal Sidewall and Recessed Horizontal Sidewall Standard and
Quick Response
Models V2709 and V2710
RATINGS All glass bulbs are rated for temperatures from -67°F/-55°C to those shown in table below.
100 Orange 38
100 Red 38
150 Yellow 65
150 Green 65
225 Blue 107
300 Purple 149
No Bulb
Ordinary A . 15375
Ordinary c 16585
Intermediate E 175
79
Intermediate F 200
93
High 286
141
Extra High 4 K 360
182
-k M Open
4 Standard response only.
All standard responses are approved open.
ORDERING INFORMATION Please specify the following when ordering:
[IJ
VICTAULIC IS REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2009 VICTAULIC COMPANY. ALL RIGHTS RESERVED.
40-11 4
DRINKLERS 40. 11 . Standard Spray Horizontal Sidewall and Recessed Horizontal Sidewall Standard and
Quick Response
MODELS V2709 AND V2710
WARNING A àWARNING
Always read and understand installation, care, and maintenance
instructions, supplied with each box of sprinklers, before proceeding
with installation of any sprinklers.
Always wear safety glasses and foot protection.
Depressurize and drain the piping system before attempting to install,
remove, or adjust any Victaulic piping products.
Installation rules, especially those governing obstruction, must be
strictly followed.
Painting, plating, or any re-coating of sprinklers (other than that
supplied by Victaulic) is not allowed.
Failure to follow these instructions could result in serious personal injury
and/or property damage. O The owner is responsible for maintaining the fire protection system and
devices in proper operating condition. For minimum maintenance and
inspection requirements, refer to the current National Fire Protection
Association pamphlet that describes care and maintenance of sprinkler
systems. In addition, the authority having jurisdiction may have
additional maintenance, testing, and inspection requirements that must
LP¼...j be followed.
If you need additional copies of this publication, or if you have any
questions about the safe installation of this product, contact Victaulic
World Headquarters: P.O. Box 31, Easton, Pennsylvania 18044-0031
USA, Telephone: 001-610-559-3300.
. wWw.tlictaulic.com
ViCTAULiO.5 A REGISTERED TRADEMARK OF VICTALJLIC COMPANY 0 2009 vicTAuuc COMPANY. ALL RIGHTS RESERVED. ic tau l.c
FiRE F 'PRODUCTS AUTOMATIC SPRINKLERS 40.11
V27, K%6 . Standard Spray Horizontal Sidewall and Recessed Horizontal Sidewall Standard and
Quick Response
MODELS V2709 AND V2710
DIMENSIONS Standard HSW - V2709, V2710 - 3,789 MM
2W/57 mm
8mmf JilMin
3 mm
½" Adjustment Recessed - V2709, V2710 (drawing not to scale)
1/l6/ 17nm
23/16/ l)116 Viol 56r,,n, 43 mm 30rrn,,
olling Finished Coiling 4-127102-305—
YMin.:J2:;
4 200
-1 L-iypicaiwaii
75 mm n.Hole Max.
I
Hole
Fin
L- rypiiwii
W MAXIMUM EXTENSION MAXIMUM RECESS
3/4' Adjustment Recessed - V2709, V2710 (drawing not to scale)
— 11116'l 24rnrnl
56 mm 37rom 7—
4 12/0 30Sr,r
1_1_1Q 4
12/I00....if Per NFPA
Mirr. Hole Max. Hole 2 15/16'/ 75 mm Min. Hole Max, Hole
Finished Surface Fira,h,cl tSu,fac, t -.1 L_ lypalw&l __J L- TypiaI WII
MAXIMUM EXTENSION MAXIMUM RECESS
/
!CTAULIc IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. 0 2009 VICTAULIC COMPANY ALL RIGHTS RESERVED.
FIRE PROTECTION PRODUCTS AUTOMATIC SPRINKLERS 40.11
.'.nT 5o . Standard Spray Horizontal Sidewall and Recessed Horizontal Sidewall Standard and
Quick Response
MODELS V2709 AND V2710
AVAILABLE WRENCHES
4 Sprinkler Type rm-.
No escutcheon yes yes
With escutcheon i yes -
DISTRIBUTION PATTERNS Models V2709, V2710
K5.6 Standard Horizontal Sidewall and Recessed Horizontal Sidewall Distribution Patterns - Trajectory
b°m 3
I 2.1
1.2
2' 4' 6' 8' 10' 12' 14' 16' 18' 20' 22' 24' 26' 0,6 m 1,2 m 1,8m 2.4 m 30m 3.7 m 4.3 m 4.9 m 5.5 rn 6.1 m 6.7 re 7.3 m 7.9 m
7p6 _.._.. 15p6 31 p
48 kPa 03kP 207kP
Models V2709, V2710
K5.6 Standard and Recessed Horizontal Sidewall Distribution Patterns - Plan View
a
www.eictaulic.com
VICTALJLIC IS REGISTERED TRADEMARK OF vicTAuLic COMPANY. © 2009 VICTALJLIC COMPANY ALL RIGHTS RESERVED.
REV
\J4taLJ lic'
40,11 7
V27,
Standard Spray Horizontal Sidewall and Recessed Horizontal Sidewall Standard and
Quick Response
MODELS V2709 AND V2710
WARRANTY Refer to the Warra'nty section of the current Price List or contact Victaulic for details.
NOTE Data shown is approximate and can vary due to differences in installation.
These graphs illustrate approximate trajectories, floor-wetting, and wall-wetting patterns for these
specific Victaulic FireLock Automatic Sprinklers. They are provided as information for guidance
in avoiding obstructions to sprinklers and should not be used as minimum sprinkler spacing rules
for installation. Refer to the appropriate NFPA National Fire Code or the Authority Having Jurisdiction
for specific information regarding obstructions, spacing limitations and area of coverage requirements.
Failure to follow'ihese guidelines could adversely affect the performance of the sprinkler and will
void all Listings, Approvals and Warranties.
S
1
I For cornplte contact information, visit wwv.victaulic.com
40.11 2545 IEV C UPDATED 1/2009
VICTAULIC IS REGISTERED TRADEMARK OF vlcTAuuc COMPANY. © 2009 VICTAULIc COMPANY. ALL RIGHTS RESERVED.
4011 .
XA"Uliic~
SEE VICTAULIC PUBLICATION 10.01 FOR DETAILS
STANDARD HORIZONTAL RECESSED HORIZONTAL SIDEWALL SIDEWALL (V3415 AND V3416) (V3415 AND V3416)
Extended Coverage/Light Hazard (ECLH) Horizontal Sidewall and
Recessed Horizontal Sidewall Standa.d and Quick Response
V3415 STANDARD RESPONSE, V3416 QUICK RESPONSE
These Mpdel V34 ECLH horizontal sifewall sprinklers are designed with a large orifice to minimize
operating pressures while providing extended coverage light hazard protection. The design
incorporates state-of-the-art, heat responsive, frangible glass bulb design (standard or quick
response) for prompt, precise operation.
The die cast frame is more streamlined and attractive than traditional sand cast frames. It is cast
with a hex-shaped wrench boss to allow easy tightening from many angles, reducing assembly
effort. This sprinkler is available in various temperature ratings (see chart on page 2) and finishes
to meet niny design requirements.
SPRINKLER OPERATION: The operating mechanism is a frangible glass bulb which contains a heat responsive liquid. During a fire,
the ambient temperature rises causing the liquid in the bulb to expand. When the ambient temperature
reaches the rated temperature of the sprinkler, the bulb shatters. As a result, the waterway is cleared of
all sealing parts and water is discharged towards the deflector. The deflector is designed to distribute
the water in a pattern that is most effective in controlling the fire.
COVERAGE: Extended spray coverage is up to 384 square feet/35.7 sq. m per NFPA 13.
TECHNICAL SPECIFICATIONS:
(Exaggerated for clarity)
JOB/OWNER
System No
Location
Models: V3415, V3416
Style: ECLH - Horizontal Sidewall or Recessed
Horizontal Sidewall
Nominal Orifice Size: 112114mm
K-Factor: 8.0 Imp./11.5 S.I.A
Nominal Thread Size: 3/4" NPT/20mm
Max. Working Pressure: 175 psi/l200kPa
Factory Hydrostatic Test: 100% @ 500 psi/
3450 kPa
Mm. Operating Pressure: 7psi/48kPa
Temperature Rating: See chart on page 2.
MATERIAL SPECIFICATIONS
Deflector: UNS C51000
Bulb: Glass with glycerin solution
Bulb Nominal Diameter:
Standard: 5.0 mm
Quick Response: 3.0mm
Load Screw: UNS C65100
Pip Cap: UNS C65100
Spring Beryllium nickel
Seal: Teflon* tape
Frame: Die cast brass 65-30
Lodgement Spring: UNS S30200
CONTRACTOR
Submitted By
Date
ACCESSORIES
Installation Wrench:
Open End: V34
Recessed: V34
Sprinkler Finishes:
Plain brass
Chrome plated
White painted**
Custom painted**
Proprietary Nickel Teflon* Coated**
For escutcheons, boxes and other accessories
refer to separate sheet.
NOTE: Weather resistant recessed escutcheon
available upon request.
A For K-Factor when pressure is measured in
Bar, multiply S.I. units by 10.0.
* Teflon is a registered trademark of Dupont Co.
** UL Listed for corrosion resistance in all
configurations.
ENGINEER
Spec Sect __________ Para
Approved __________________
Date
WWw.victaulic,com
vicTAuLic is A REGISTERED TRADEMARK OF vicTAuLic COMPANY, © 2007 VICTAULiC COMPANY, ALL RIGHTS RESERVED. PRINTED IN THE USA
REE
4t1 33 1
FIRE PROTECTION PRODUCTS AUTOMATIC SPRINKLERS 4033 . Extended Coverage/Light Hazard (ECLH) Horizontal Sidewall and
Recessed Horizontal Sidewall Standard and Quick Response
V3415 STANDARD RESPONSE, V3416 QUICK RESPONSE
APPROVALS/LISTINGS
-. --- t•
,- I i
V3415 8.0 17/32 !14 Standard 11., ECLH HSW = =
V34t51 14 t80 1.5 Standard Recessed [CLH HSW.
Up to 1/2"Adjustrnent. 1 -c i - c i - c 1-A I -A
V3415 152 8.0 dard Recessed ECLH HSW.
j C 1 - C 1 - C 1 -A I -A 14 11 -
V5416 152 8.0 Quick ECLH Hsw I : C iiC 1-AR 1-A
- 15 80 Vr4t6 Quick Recessed ECLH HSW 1 - C 1 - C 1 - C 1 - AR 1 - A
14 115 Up to WAdjustrneni 2- A E 2-A E 2-A El 2- A E 2-A E
V3416 ,32 8 Quirk Recessed ECLH HSW tC 1-C 1-C i - AR i-A 14 11.5
4 Listings and approval as of printing
AFor K-Factor when pressure is measured in Bar, multiply S.I.units by 100
Approved by FM as standard response.
APPROVED TEMPERATURE RATINGS
1 -ULJULC A- 135F/57'C,4- 127102-305mm
2-FM B - i 35'F/57C to 175'F/29'C, 4- 67102 - i 52mm
3-Nyc/MEAt = C - i 3s'F/57C to 200F/93'C, 4- 127102 - 305mm
4 - CSFM § D - t35F/57'C to t55F/68'C, 4-12/102 - 305mm
E - 155T/68C, 4-12/102 - 305mw
t WA Pending
§ CSFM Pending
vicrAuLic IS REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2007 vicTAuLic COMPANY. ALL RIGHTS RESERVED. PRINTED IN THE USA XX ~~_t-a9 hc~
40332
REV F
FIRE PROTECTION PRODUCTS AUTOMATIC SPRINKLERS 40.33
"3 KaO
Extended Coverage/Light Hazard (ECLH) Horizontal Sidewall and
Recessed Horizontal Sidewall Standard and Quick Response
V3415 STANDARD RESPONSE, V3416 QUICK RESPONSE
RATINGS All glass bulbs are rated for temperatures from -67°F/-55°C to those shown in table below
Temperature Victaulic
* Sprinkler ~Fmperature_____Part______ Temperature
__
Maximum Ambient
_________
Ordinary A 135 I Orange 57 38
Ordinary C 155 100 Red . 68 38
Intermediate E 175 150 Yellow 79 65
Intermediate F 200 150 Green 93 65
ORDERING INFORMATION Please specify the following when ordering:
www.victauljc.com
VJCTAULIC IS A REGISTERED TRADEMARK OF vicrAuLic COMPANY. © 2007 VJCTAULIC COMPANY. ALL RIGHTS RESERVED. PRINTED IN THE USA
REV
40333
S
40.33
WARNING
Always read and understand installation, care, and maintenance
instructions, supplied with each box of sprinklers, before proceeding
with installation of any sprinklers.
Always wear safety glasses and foot protection.
Depressurize and drain the piping system before attempting to install,
remove, or adjust any Victaulic piping products.
Installation rules, especially those governing obstruction, must be
strictly followed.
Painting, plating, or any re-coating of sprinklers (other than that
supplied by Victaulic) is not allowed.
Failure to follow these instructions could result in serious personal injury
and/or property damage.
The owner is responsible for maintaining the fire protection system and
devices in proper operating condition. For minimum maintenance and
inspection requirements, refer to the current National Fire Protection
Association pamphlet that describes care and maintenance of sprinkler
systems. In addition, the authority having jurisdiction may have
additional maintenance, testing, and inspection requirements that must
be followed.
If you need additional copies of this publication, or if you have any
questions about the safe installation of this product, contact Victaulic
World Headquarters: P.O. Box 31, Easton, Pennsylvania 18044-0031
USA, Telephone: 001-610-559-3300.
FIRE PROTECTION PRODUCTS - AUTOMATIC SPRINKLERS
V3
Extended Coverage/Light Hazard (ECLH) Horizontal Sidewall and
Recessed Horizontal Sidewall Standard and Quick Response
V3415 STANDARD RESPONSE, V3416 QUICK RESPONSE
- ............
.. .... .............. --- ........ ............ ....
WAR A NING
........
VICTAULIC IS REGISTERED TRADEMARK OF VICTAULIC COMPANY, © 2007 VICTAULIC COMPANY. ALL RIGHTS RESERVED. PRINTED IN THE USA
X/9 taul iic
4033.4
REV F
FIRE PROTECTION PRODUCTS - 1JTOMAT1C SPRINKLERS 40.33
V34, K8AJ
Extended Coverage/Light Hazard (ECL) Horizontal Sidewall and
Recessed Horizontal Sidewall Standard and Quick Response
V3415 STANDARD RESPONSE, V3'16 QUICK RESPONSE
DIMENSIONS Standard HSW - V3415, V3416
3tU778 mm
2U'/59 mm
1AE/ 1AR/ 10 mm Tff 14mm 40 mm 33 Prim
½ Adjustment Recessed - V3415, V3416 (drawing not to scale)
Finished Ceilhig Feii,hed Ceiling
2751 nm 2%'/60 2751 -nn, 241,760 mrn Min Hole M- Hole 2'wl Min. Hole Max. Hole 75
Finished Sod—Finished 5IIIMAe 4-Typical wall -1 4- TypIUUIWUIt
MAXIMUM EXTENSION MAXIMUM RECESS
- 1/4"Adjustment Recessed - V3415, V3416 (drawing not to scale)
24r,,r,,
L
12710 305 Ceiling
a
2/02305n Per NFPA In
Min le Max, Hole 21WI 275 1 m 2%/60 mm
75 mm F7F Min.
I
Hole Max. Hole
Finished Soil- - -4 4-- TypXAWMI Finished Surface -4 4- TyTCUIWUI
MAXIMUM XICIENSION MAXIMUM EXCESS
- See "Approvals/Listings"chart on page 2 for allowable deflector to ceiling heights.
www.victaulic.com
vIcTAuLIc Is A REGISTERED TRADEMARK OF vlcrauLIc COMPANY. 102007 VICTAULIC COMPANY. ALL RIGHTS RESERVED PRINTED IN THE USA XA—ta U I i C~
REVE
FIRE PROTECTION PRODUCTS ... AUTOMATIC SPRINKLERS
V34, K8O
40.33
F-1 Extended Coverage/Light Hazard (ECLH) Horizontal Sidewall and
Recessed Horizontal Sidewall Standard and Quick Response
V3415 STANDARD RESPONSE, V3416 QUICK RESPONSE
AVAILABLE WRENCHES
No escutcheon
With escutcheon
yes yes
yes -
ROOM SIZE
16x16 32 26 28 16 10.0 23 49x49 121 98 106 Ito 73 85
16x18 36 29 33 20 132 17 4.9x5.5 136 110 125 140 St 118
16x20 40 32 35 25 16 192 49x61 151 121 132 170 110 132
16x22 44 36 36 30 203 203 49x67 16/ 136 136 05 140 140
16x24 48 39 41 36 238 263 49x73 182 148 155 250 164 I81
t auIiC VICTAULIC IS A REGISTERED TRADEMARK OF vICTAuLIc COMPANY. © 2007 VICTAuLIC COMPANY. ALL RIGHTS RESERVED, PRINTED IN THE USA
40336
F'1E.
FIRE PROTECTION PRODUCTS AUTOMATIC SPRINKLERS
j3L . Extended Coverage/Light Hazard (ECLH) Horizontal Sidewall and
Recessed Horizontal Sidewall Standard and Quick Response
V3415 STANDARD RESPONSE, V3416 QUICK RESPONSE
40.33
DISTRIBUTION PATTERNS Models V3415, V3416
K8.0 Extended Coverage/Light Hazard (ECLH)
Horizontal Sidewall And Recessed Horizontal Sidewall Distribution Patterns -Trajectory
2,411,
0,6m 1,2m 1,8m 2,4m 30m 3,7m 4,3m 4,9m 5,5m 6,1m 6,7m 7,3m 79m 8,5m 9,1m
26 GPM -. - -. 29 GPM 32 GPM ------
C8LPM 11OLPM 121 LPM
36 GPM -- -- 39 GPM -- - 13CLPM 148LPM
V3415 -Standard 1.8
V3416-Quick 1.8
NOTES:
1 Data shown is approximate and can vary due to differences in installation.
2 These graphs illustrate approximate trajectories, floor-wetting, and wall-wetting patterns for these
specific Victaulic FireLock automatic sprinklers. They are provided as information for guidance in
avoiding obstructions to sprinklers and should not be used as minimum sprinkler spacing rules for
installation. Refer to the appropriate NFPA National Fire Code or the authority having jurisdiction
for specific information regarding obstructions, spacing limitations and area of coverage
requirements. Failure to follow these guidelines could adversely affect the performance of the
sprinkler and will void all Listings, Approvals and Warranties.
3 All patterns are symmetrical to the centerline of the waterway.
www.victauljc.com
vicrAuLic is A REGISTERED TRADEMARK OF vIC1'AuLIc COMPANY. Q 200/ vICTAuLIC COMPANY. ALL RIGHTS RESERVED. PRINTED IN THE USA
REV .E 40.337
. Extended Coverage/Light Hazard (ECLH) Horizontal Sidewall and
Recessed Horizontal Sidewall Standard and Quick Response
V3415 STANDARD RESPONSE, V3416 QUICK RESPONSE
WARRANTY Refer to the Warranty section of the current Price List or contact Victaulic for details.
NOTE This product shell be manufactured by Victaulic or to Victaulic specifications. All products to be
installed in accordance with current Victaulic installation/assembly instructions. Victaulic reserves the
right to change product specifications, designs and standard equipment without notice and without
incurring obligations.
[I
IIlIII 1111111 IlliliD 1111111111 IIlI Ill
WCAS-6ARRRC
For complete contact information visit www.victaulic.com
........... I .......... --- . ....... ........... ..............
40.33 2820 REV E UPDATED 10/2007
. uctauI.c VICTAuuc IS A REGISTERED TRADEMARK OF vICTAuLIc COMPANY. 2007 vicrAuLIc COMPANY. ALL RIGHTS RESERVED. PRINTED IN THE USA
4033
SAl -000-0000
%JtaUIiC®
AUToMATrS1 -
FIRE_______________________
Sprinkler
Cabinets
- 1
PRODUCT DESCRIPTION
Victaulic Automatic Sprin-
kler Cabinets provide for
storage of a supply of sprin-
klers. Maintaining a supply
of spare sprinklers on the
premises of automatic
sprinkler systems will aid in
the prompt replacement of
operated or damaged sprin-
klers and returning a fire
protection system to ser-
vice as soon as possible.
This is a requirement of
NFPA and most Authori-
ties Having Jurisdiction.
Refer to the applicable
NFPA standard governing
your specific installation for
further details.
Six or twelve sprinkler
capacity cabinets are avail-
able. This also provides for
storage of the appropriate
wrench which is required
for the installation and
removal of sprinklers.
NFPA 25 requires the total
number of spare sprinklers
to be stored on the pre-
mises of an automatic
sprinkler system meet the
minimum quantities shown
in the accompanying table.
When the sprinkler system
includes more than one
type of temperature rating
sprinkler, the stock of spare
sprinklers must include a
proportional sampling of
each type and temperature
rating; however, a mini-
mum of 3 each is recom-
mended.
Sprinklers
in Building
Mm. Number of
Spare Sprinklers
Under 300 6*
300t01000 12
Over-1000 24
A minimum of three sprinklers of each
type and temperature rating are required
for residential fire sprinkler systems in
one- and Iwo-family dwellings and mobile
homes.
SA2-000-0000
L7
I 1
SA4-000-0000
SA3-000-0000
TECHNICAL SPECIFICATIONS
Models:
O 12 sprinklers
O 6 sprinklers o 3 sprinklers
(NFPA/3D, Residential)
O 6 large sprinklers
Material: Heavy gauge steel,
red enamel.
Cabinets are available in six or
twelve sprinkler capacities with
dimensions and shelf variations
as shown on page 2. The cabi-
nets are of welded construction
fabricated from low carbon steel
sheet. The box and shelves are
fabricated from 0.030" thick
material and the cover is fabri-
cated from 0.042" thick material.
The cover is mounted to the box,
at the top, with two 0.036 thick
steel butt type hinges. A coat of
red enamel paint is applied
inside and out, and a label indi-
cating that the cabinet is for
spare sprinklers is bonded to the
cover.
VICTAULIC® IS AN ISO 9001 CERTIFIED COMPANY
Vktaulic Company of A1TArica Viciaullc Company of Canada Victnxniic Eti,opo V!Ttaulic America Latin: Victaulic ASia Pacific Phone: 1-800-PICK-f/IC (1-800.742.5842) Phone: 416-675-5575 Phone: 32 9-381-1500 Phone: 610-559-3300 Phone: 65-235-3035 Fax 610-250-8817 Fax: 416.675-5565 Fax: 32-9-380-4438 Fax: 610-559-3608 Fax: 65-235-0535 e-niail:pickvicxPvic1au1ic.com e-mail: viccanada@vjclauliccom e-mail: viceuro@viclaulic.be e-mail: xical@viclaulic.com e-mail: vicap@xicleulic.com
nnv.o /IUZ QQ Registered Trademark of Victaulic 0 copyright 2002 Victaulic Printed in USA
DIMENSIONS
Inches!: Dimensions hii
Victaulic .
Part Number Description Use With H W D
VlO, V26, V29, V27, V34 (except 5.25 14.31 4.00
SAl 000-0000 For 12 Sprinklers V3403 & V3404)
5.25
L.
1l 238
SA2-000-000 For 6 Sprinklers V27. V3403, V3404, V34 .
5.25 7.31 28
SA3.000-0000 For 3 Sprinklers (NFPA 13D) V27, V29 Residential
V40, V38, V39 Concealed, Ki ESFR,
SA4-000-0000 For 6 Large Sprinklers . All Intermediate Level Sprinklers, 6.50 14.31 3.13
All Guards*
Specify part rumberand capacity when ordering.
Guards will only fit it NOT assembled to sprinkler. Capacity may be reduced.
=- .
INSTALLATION
Automatic Sprinkler Cabinets must
be installed and the spare sprinkler
stock maintained in compliance with
the applicable standards of the
NFPA, in addition to the standards of
any other Authorities Having
Jurisdiction.
Failure to do so may result in property
damage and impair the ability to return
an automatic sprinkler system to ser-
vice as soon as possible.
CAUTION
The owner is responsible for
maintaining a supply of spare
sprinklers in proper condition. The
installing contractor should be
contacted with any questions.
Failure to do so may result in property
damage.
WARRANTY Refer to the Warranty section of
the current Price List or contact
Victaulic for details.
•
This product shall be manufactured by Victaulic company. All products lobe installed in accordance with current Victaulic installation/assembly instructions
Victaulic reserves the right to change product specifications, designs and standard equipment without notice and without incurring obligations.
40.81 - 2
2) PIPING
S
Ej
'9 DYNA-FLOW ®
S.
Dyna-Flow®
High Strength Steel Pipe
The original high-strength light wall sprinkler pipe with hydraulics superior to Schedule-10.
Specifications
NPS Nominal I.D. WI. WI. (1120 Filled) Pcs/ Wt/Lift (21') WI/Lift (24') WI/Lift (25)
In; mm In; mm Lbs/Ft; Kg/rn Lbs/Ft; Kg/rn Lift Lbs; Kg Lbs; Kg Lbs, Kg
1.191 0.830 1.31 91 1,586 1,812 1,888
25 30.3 1.2 1.95 91 719 822 856
11/4 1.536 1.059 1.87 61 1,356 1,550 1,615
32 39.0 1.6 2.78 61 615 703 733
1'/2" 1.728 1.667 2.71 61 2,135 2,440 2,542
40 43.9 2.5 4.03 61 968 1107 1153
2.203 2.104 3.79 37 1,634 1,868 1,946
50 56.0 3.1 5.64 37 741 847 883
21/2" 2.703 2.564 5.10 30 1,615 1,846 1,923
65 68.7 3.8 7.59 30 733 837 872
3.314 3.387 7.18 19 1,351 1,544 1,608
80 84.2 5.0 10.69 19 613 700 729
4.310 4.473 10.86 19 1,784 2,039 2,124
90 109.5 6.7 16.16 19 809 925 963
Dyna-Flow pipe is the "original" high-
strength lightwall sprinkler pipe. Dyna-
Flow has outstanding hydraulic
capabilities and is recognized as the
most popular alternative to Schedule- 10
pipe. Lightweight, easy to cut and easy
to handle for installation. Dyna-Flow is a
valuable addition to any fire protection
system.
With an inside diameter of up to 11%
larger than Schedule-40 and up to 7%
larger than Schedule- 10, Dyna-Flow
pipe hydraulics are exceptional. Larger
I.D.s enable Dyna-Flow, and related
components, to be down-sized within the
system, thus increasing the potential for
job cost savings. For complete Hazen-
Williams charts, refer to "Dyna-Flow
Hydraulic Data Tables."
I
Dyna-Flow products are coated with
an environmentally approved and
specially formulated modified-acrylic or
water-based coating. This durable coating
is paintable. The black coating acts as
an excellent primer and is resistant to
weathering and U.V. degradation from
outdoor storage.
Metallurgical properties provide excellent
fabrication characteristics for end prep
finishes, welding and roll grooving.
There is no special process or equipment
needed for fabrication and installation.
The internal surface of all black Allied
Tube & Conduit Fire Sprinkler pipe
products up to 4.5000" in diameter is
coated with our new Antibacterial
Formula, "ABF". In scientific laboratory
test, ABS proved to have superior
resistance to microbial colonization of
pipe walls, thereby delaying or possibly
preventing the onset of Microbiologically
Influenced corrosion (MIC) when the
First Sprinkler System is first installed.
Dyna-Flow/Super Flo pipe is manufac-
tured to meet ASTM A-795 Type E,
Grade A and is in compliance with
NFPA-13 and NFPA-14. All sizes of
Dyna Flow/Super Flo are UL Listed, FM
Approved and ULC Listed.
(P <S>
Listed Approved Listed
Dyna-Flow/Super Flo is UL/ULC Listed
for use with roll grooved, plain-end
couplings, and welded joints for wet, dry,
preaction and deluge systems. It is FM
Approved for roll grooved, plain-end, and
welded joints for wet systems. Refer to
appropriate documentation for up-to-date
listing and approval information. Dyna-
Flow/Super Flo is now available "hot-
dip" galvanized and has been specifically
approved by FM for dry systems uses.
Lightweight and easy to install,
resulting in more efficient use of your
freight and labor dollars.
Provides stability needed to comply
with standard hanger spacing
(15 ft 0. C.) per NFPA.
Available in Standard lengths for your
convenience, or can be ordered in
custom lengths upon approval.
Fast cutting and welding, as well as
easy roll grooving and end preparation.
Available in Factory roll grooved form
for quicker shop turnaround.
Clean, durable mill coating provides
longer "shelf life" and acts as an
excellent primer for custom paint
applications.
U
tqcc.i/Flow Control I 16100 S. Lathrop• Harvey, IL 60426 Customer Service: PT- cIIecJ 11350 Norcom Rd. • Philadelphia, PA 19154 (800) 882-5543
TUBE &CONDUIT 2525 N. 27thAve. Phoenix, AZ 85009 Fax 708-339-1806
S2 -3
riiii. c
Wt.
EIITTiITiIii
NPS Nominal I.D. Wt. (H20 Filled) CRR
In; mm In; mm Lbs/Ft; kg/rn
., Lbs/F0,m Unthreaded'
1" 1.191 0.830 1.31 2.41
25 30.3 1.2 1.95 -
11/4 1.536 1.059 1.87 1.55
32' . 39:0 . 1.6 . 2.78 -
11/2 1.728 1.667 2.71 3.44
40 43.9 . - 2.5 . 4.03 ... -
2.203 2.104 3.79 2.78
50 56.0__. .•.• _3.1' .5.64 .-
2½" . 2.703 2.564 5.10 1.60
65 68.7 3.8 7.59 -
3.314 3.387 7.18 1.48
80 84.2 5.0 10.69 -
4.310 4.473 10.86 1.00
90 109.5 .. _6.7 . _16.16 -
.--- --- --
S.',
Job"
Exceptional hydraulics
Lightweight and easy to
install
Available factory roll
H grooved
' ABFII coated ID
.• UL and cUL listed
E FM approved
® Superior Coating
Dyna-Flow products are coated with an
environmentally approved and specially
formulated modified-acrylic or water-based
coating. This durable coating is paintable
and acts as an excellent primer while
resisting weather and UV degradation
from outdoor storage.
The internal surface of all black Allied Tube
& Conduit Fire Sprinkler pipe products
up to 4.500" in diameter is coated with
our new Antibacterial Formula, "ABFli".
In scientific laboratory tests, ABFII proved
to have superior resistance to microbial
colonization of pipe walls, thereby
inhibiting or possibly preventing the onset
of Microbiologically Influenced Corrosion
(MIC) upon installation and the first 25
flushes of the fire sprinkler system.*
® American Made
Meets "Buy American" requirement and is
available through distributors in the USA,
Canada, Mexico and Latin America.
Specifications & Approvals
Dyna-Flow pipe is manufactured to meet
ASTM A-795 Type E, Grade A and is in
compliance with NFPA-13 and NFPA-14.
All sizes of Dyne-Flow are UL and cUt
listed and FM approved.
Dyne-Flow is UL and cUL listed for use
with roll grooved, plain-end and welded
joints for wet, dry, pre-action and deluge
systems. It is FM approved for roll grooved,
plain end and welded joints for wet
systems. Dyna-Flow is available "hot-dip"
qalvanized** an., has been specifically
approved by FM for dry system uses.
Dyna-Flow complies with Nc'PA '13 and is
rated at 300 psi working pressure.
The original high-strength
light wall sprinkler pipe
with superior hydraulics.
Dyna-Fiow is the "original" high-strength . light wall sprinkler pipe. With outstanding
hydraulic capabilities, Dyna-Flow is
recognized as the most popular alternative
to Schedule-i 0 pipe. Lightweight and easy
to cut, Dyne-Flow is a valuable addition to
any fire protection system.
With an inside diameter (ID) of up to
11% larger than Schedule-40 and up
to 7% larger than Schedule -10, Dyna-
Flow pipe hydraulics are exceptional.
Larger D's enable Dyna-Flow and related
components to be down-sized within the
system, increasing the potential for job
-. cost savings. For complete Hazen Williams : charts, refer to "Dyne-Flow Hydraulic Data
Tables".
Dyne-Flow pipe has metallurgical
properties that provide excellent
fabrication characteristics for end prep
finishes, welding and roll grooving. There
are no specl processes or equipment
needed for fhrication and installation
See ABFII warranty
* must he ordered in 10 bundre ncremepts
aIheci Customer Service (800)882-5543 Fax: (708) 339-1806
TUBE & CONDUIT 16100 S Lathrop • Hawey, IL 60426 1 11350 Norcom Rd. • Ph ladelphra, PA 19154 1 2525 N 27thAve. • Phoenix,Az 85009 S2-3
EV 0
:
I: DYNA' THREAD ®
n
S Full Line Sch-40 Replacement
Dyna-Threar offers the life expectancy of Sch-40 with superior hydraulics and greater value.
Dyna-Thread sprinkler pipe represents an engineering advancement for the sprinkler pipe industry. It combines the safety
and longevity of traditional Sch-40 pipe with quality and superior hydraulic advantages.
Dyna-Thread's inside diameter is up
to 3.6% larger than Sch-40 giving it
superior hydraulics. And, when used
in combination with Dyna-Flow pipe,
down sizing often occurs.
Dyna-Thread is fully listed and
approved by UL, ULC, and FM for
fire sprinkler applications.
The life expectancy of Dyna-Thread
and Sch-40 are equal based on the
calculated wall thicknesses per UL.
The consistent quality of steel used to
make Dyna-Thread facilitates smooth
threading and lower maintenance
costs.
The exterior of Dyna-Thread is
protected by a clean, durable mill
coating for extended shelf life and
easy paint application.
U0 L
Listed Approved Listed
With its increased strength and lighter
weight, Dyna-Thread reduces
installation fatigue and is ideal for
retro-fit applications.
Corrosion Resistance Ratio (CRR) is a
UL (Underwriters Laboratory) term for
the estimated life expectancy of a pipe
joint. This is based on the calculated
wall thickness at the base of the first
exposed thread, assumed to be the
weakest point of the pipe length. Dyna-
Thread and Sch-40 have the same
calculated wall thicknesses at this point
and are both assigned the same CRR of
1.00.
The internal surface of all black Allied
Tube & Conduit Fire Sprinkler pipe
products up to 4.5000" in diameter is
coated with our new Antibacterial
Formula, "ABF". In scientific laboratory
test, ABS proved to have superior
resistance to microbial colonization of
pipe walls, thereby delaying or possibly
preventing the onset of
Microbiologically Influenced corrosion
(MIC) when the First Sprinkler System
is first installed.
More wall thickness at the thread
(CRR1 .00) gives Dyna-Thread
better life expectancy than lightwall
threadable pipe joints.
Unlike lightwall threadable pipe,
Dyna-Thread has no thread gauge
warning.
Dyna-Thread is approved for
standard hanger spacing (15 ft.
O.C.), can be used as earthquake
sway bracing, and is safe to use as
drops.
Dyna-Thread is safer to weld on.
Dyna-Thread is more widely
accepted than lightwall threadable
where Sch-40 is specified.
Super 40/Dyna-Thread pipe is
manufactured to meet: ASTM A-135,
Grade A and is in compliance with
NFPA-13. All sizes of Super 40/Dyna-
Thread are rated at 300 psi working
pressure. Super 40/Dyna-Thread is UL
and ULC Listed for wet, dry deluge and
pre-action sprinkler systems and FM
Approved for use in wet systems. Super
40/Dyna-Thread can be "hot-dip"
galvanized to meet FM requirement for
dry systems. Super 40/Dyna-Thread is
approved for all threaded couplings and
welded outlets and is suitable for all
roll-grooved, and plain-end fittings.
(See listing information).
_
NPS Nominal I.D. WI. WI. (H20 Filled) Pcs/ WlJLifl (21) WI/Lilt (24) WI/Lift (25')
In; mm In; mm Lbs/Ft; Kg/rn Lbs/Ft; Kg/rn Lift Lbs; Kg Lbs; Kg Lbs; Kg
1" , 1.080 1.330 1.75 70 1955 2234 2327
25 27.4 2.0 2.60 70 887 1013 1056
11/4 1.408 1.870 2.54 51 2002 2288 2384
32 35.8 2.8 3.78 51 908 1038 1081
1W 1.639 2.290 3.22 44 2115 2418 2519
40 41.6 3.4 4.79 44 959 1097 114
2 2.104 3.050 4.57 30 1921 2196 2287
50 53.4 4.5 6.80 30 871 996 103
16100 S. Lathrop Harvey, IL 60426 Customer Service: tLICQ/F/ow Control ( IIjeJ 11350 Norcom Rd. • Philadelphia, PA 19154 (800) 882-5543
TUBE & CONDUIT 2525 N. 27thAve. • Phoenix, AZ 85009 Fax 708-339-1806
S3 -3
Nurrrirrl i.D. Wt. Wt. (H20 Filled) CRR CRR
Ii rum - In; mm Lbs/Ft kg/rn Lbs/Ft; kg/rn unthreaded Threaded
1" 1.080 1.330 1.75 11.39 1.00
25 27.4 2.0 ... 2.60 - -
11/4" 1.408 1.870 2.54 9.50 1.00
32 35.8 2.8 3.78 - -
1½" 1.639 2.290 3.22 9.14 1.00
40 41.6 3.4 4.79 - -
2" 2.104 3.050 4.57 8.41 1.00
50 53.4 4.5 6.80
APPROVED
r
L
0
0
•
0
0
Widely accepted substitute
for Schedul640
No thread gauge warnings
Standard hanger spacing
ABFII coated'
.
ID
UL and cUL$sted
FM approved
Combining'the safety and
longevity ofSch-40 with
quality and-hydraulic
advantages.
Dyna-Thread. pipe is tbe full line Schedule
40 replacement with;!the same CRR of
Schedule 40, 1.00, providing Dyna-Thread
with the same life exp. ectancy as Sch-40.
With outstanding hydraulic capabilities,
Dyne-Thread is a m&d widely accepted
product substitutidnhan lightwali
threadahie pipe when6ch-40 is specified.
Dyne-Thread's inside diameter is up to
3.6% larger than Sch140 and provides
improved hydraulics. When used in
combination with yga-Flow pipe, down
sizing of pipe and (elated components
often occurs, thereby reducing costs.
The consistent quality ofsteel used to
make Dyne-Thread fadilitates smooth
threading and lower maintenance costs.
Increased strength andJighter weight
allows Dyna-Thread-to duce installation
fatigue and makes it ideal for ratio-fit
applications.
® Superior Coating
Dyne-Thread products are coated with an
environmentally approved and specially
formulated modified-acrylic or water-based
coating. This durable coating is paintable
and acts as an excellent primer while
resisting weather and UV degradation
from outdoor storage.
The internal surface of all black Allied Tube
& Conduit Fire Sprinkler pipe products
up to 4.500" in diameter is coated with
our new Antibacterial Formula, "ABFII ".
In scientific laboratory tests, ABFII proved
to have superior resistance to microbial
colonization of pipe walls, thereby
inhibiting or possibly preventing the onset
of Microbiologically Influenced Corrosion
(MIC) upon installation and the first 25
flushes of the fire sprinkler system.*
® American Made
Meets "Buy American" requirement and is
available through distributors in the USA,
Canada, Mexico and Latin America.
® Specifications & Approvals
Dyne-Thread pipe is manufactured to meet
ASTM A-135, Glade A, is in compiance
with NFPA-1 3 and all sizes àC rated at
300 psi working pressure. Dyne-Thread
is UL and cUL listed for wet, dry deluge
and pre-action sprinkler systems and FM
approved for use in wet systems. Dyna-
Thread can be hot dip galvanized** to
meet FM requirements for use in dry
systems. Dyra-Thread is approved for all
threaded couplirlgs arid welded outlets
and is suitable for all roll-grooved and
plain end fittings.
See ABFII warranty
" must be ordered in 10 bundle ncremerrs
.®.*,.
QIhecJ 'Customer Service (800) 882-5543 Fax: (708),.339-1806
TUBE & CONDUIT. 16100 S Lathi 'p • Harvey, IL 60426 1 11350 Nor urn Rd. • RI ladelpha, PA 19154 1 2525 N 27th Ave. • Phoenix, AZ 85009 S3-3
J LIE= I 13/4C
Schedule-1O©/Schedule-40®
Fully Listed and FM Approved Sprinkler Pipe
When you specify Schedule-1O/Schedule-40 sprinkler pipe you get a UL listed and FM approved product. Although these
products do not require separate approvals, Schedule-10/Schedule-40 gives you the extra quality assurance you demand.
Our Sch-10 (1"- 8') pipe and Sch-40 (1"- 2141) pipe have passed the same thorough lab testing as our other listed pipe
products, and receive periodic mill inspections from both UL and FM agents to ensure consistent quality.
Schedule-10/Schedule-40 product can be
"hot-dip" galvanized to meet FM
requirements for dry systems in
accordance with the zinc coating
specifications of ASTM A-123.
Meets "Buy American" requirement
and is available through distributors in
the USA, Canada and Mexico.
Schedule-10/Schedule-40 pipe are in
compliance with the following:
ASTM A-135, and NFPA 13. Both pipe
products have a working pressure rating
of 300 psi maximum and also meet the
stringent requirement for the following
tests:
Specifications
NPS Nominal I.D. Wt. WI. (H20 Filled) Pcs/ WI/Lift (21) WI/Lilt (24') WI/lift (25)
In; mm In; mm Lbs/Ft; Kg/rn Lbs/Ft; Kg/rn Lift Lbs; Kg Lbs; Kg Lbs; Kg
1' 1.049 1.680 2.05 70 2,470 2,822 2,940
25 26.6 2.5 3.05 70 1,120 1,280 1,334
1¼" 1.380 2.270 2.93 51 2,431 2,778 2,894
32 35.1 4.36 4.36 51 1,103 1,260 1,313
11/2" 1.610 2.720 3.61 44 2,513 2,872 2,992
40 40.9 4.0 5.37 44 1,140 1,303 1,357
2" 2.067 3.650 5.13 30 2,300 2,628 2,738
50 52.5 5.4 7.63 30 1,043 1,192 1,242
21/2" 2.469 5.790 7.86 19 2,310 2,640 2,750
65 62.7 8.6 11.73 19 1,048 1,197 1,247
' I'ISpecifications
NPS Nominal I.D. WI. WI. (H20 Filled) Pcs/ WI/Lilt (21') WI/Lift (24) WI/Lift (25')
In; mm In; mm Lbs/Ft; Kg/rn Lbs/Ft; Kg/rn Lift Lbs; Kg Lbs; Kg Lbs; Kg
1.097 1.400 1.81 91 2,675 3,053 3,185
25 27.9 2.1 2.70 91 1,213 1,385 1,445
1¼" 1.442 1.810 2.52 61 2,319 2,664 2,760
32 36.6 2.7 3.75 61 1,052 1,208 1,252
11/2 2.080 3.04 61 2,664 3,045 3,172
40 42.7 3.1 4.52 61 1,208 1,381 1,439
2.157 2.640 4.22 37 2,051 2,344 2,442
50 54.8 3.9 6.28 37 930 1,063 1,108
21/2" 2.635 3.530 5.89 30 2,224 2,542 2,648
65 66.9 5.3 8.77 30 1,009 1,153 1,201
3.260 4.330 7.94 19 1,728 1,975 2,057
80 82.8 6.4 11.82 19 784 896 933
4.260 5.610 11.78 19 2,238 2,558 2,665
90 108.2 8.3 17.53 19 1,015 1,160 1,209
5.295 7.77 17.33 10 1,632 1,865 1,943
125 134.5 11.56 25.80 10 740 846 881
6.357 9.290 23.03 10 1,951 2,230 2,322
150 161.5 13.8 34.27 10 885 1,012 1,053
8" 8.249 16.490 40.15 7 2,424 2,770 2,885
200 209.5 24.5 59.75 7 1,100 1,256 11309
Our advanced formularnill coating of-
fers a clean, durable surface. It is also
paint-ready for customcolor applications
without special preparation.
The internal surface of all black Allied
Tube & Conduit Fire Sprinkler pipe
products up to 4.5000" in diameter is
coated with our new Antibacterial For-
mula, "ABF". In scientific laboratory
S test, ABS proved to have superior resis-
tance to microbial colonization of pipe
walls, thereby delaying or possibly pre-
venting the onset of Microbiologically
Influenced corrosion (MC) when the
First Sprinkler System is first installed.
Welded Outlets
Hydrostatic Pressure
Side Wall Rupture
Vibration Test
tqco/Flow Control allied
TUBE & CONDUIT
(P <~> (~~
Listed Approved Listed
16100 S. Lathrop • Harvey, IL 60426 Customer Service:
11350 Norcom Rd. Philadelphia, PA 19154 (800) 882-5543
2525 N. 27 th Ave. • Phoenix, AZ 85009 Fax 708-339-1806
S5 -3
Pie
When you specify Allied Schedule-10/Schedule-40 sprinkler pipe you get a UL listed and FM approved product.
Although these products do not require separate approvals, Schedule-10/Schedule-40 gives you the extra quality
assurance you demand. Our Sch10 (11/4"- 8") pipe and Sch-40 (1"- 21/2") pipe have passed the same thorough lab
testing as our other listed pipe products, and receive periodic mill inspections from both UL and FM agents to
ensure consistent quality.
® Galvanized Pipe
Schedule-10/Schedule-40 product can be "hot-dip"
galvanized to meet FM requirernnts for dry systems
in accordance with the zinc coating specifications of
ASTMA-123.
® Superior Coating
Our advanced formula mill coating offers a clean,
durable surface. It is also paint-ready for custom
color applications without special preparation.
The internal surface of all Allied Tube & Conduit Fire . Sprinkler pipe products up to 4.500" in diameter is
coated with our new Antibacterial Formula, tABFl I
In scientific laboratory tests, ABElI proved to have
superior resistance to microbial colonization of pipe
walls, thereby inhibiting or possibly preventing the
onset of Microbiologically Influenced Corrosion
(MIC) upon installation and the first 25 flushes of
the fire sprinkler system.*
American Made
Meets "Buy American" requirement and is available
through distributors in the USA, Canada, Mexico
and Latin America.
c7 Specifications & Approvals
Schedule-10/Schedule-40 pipe are in compliance
with the following: ASTM A-135, and'NFPA 13.
All pipe products have a rated working pressure
of 300 psi maximum and also meet the stringent
requirements for the following applications and
tests:
Welded Outlets
Hydrostatic Pressure
Side Wall Rupture
* See ABFII warranty
Wt. (H20 Filled) CRR NPS Nominal I.D. Wt.
In; mm. In; mm•.
1.049 1.680 2.05 1
25 . 266 . 2.5 305 -
11/4 2.270 2.93 1
32 351 4.36 . : 4.36 -
1½" 1 610 2.720 3.61 1
40 40.9 . 4.0 . 5.37 . . -
2.067 3.650 5.13 1
50 525 . 5.4 . 7.63 -
2' 2 ' 2.469 5.790 7.86 1
65 62.7 8.6 1 - -
--
NFIS I.L. Wt. Wt. (1-120 Filk..,, CRR
fi,mm - In; min .Lbs/Ft;.kg/m: , s/Ftj kilm . -
11/4 1.810 2.525 7.0955
.32 .36.6 2.7 . 3.75 -
11/2 2.080 3.04 5.6570
.40 42.7 3.1 . 4.52 . -
2.157 2.640 4.22 4.5827
50 54.8 3.9 6.28 -
216" 2.635 3.530 5.89 3.5196
65 . 66.9 5.3 8.77
3.260 4.330 7.94 2.5550
80 82.8.. : 6.4 11.82
4.260 5.610 11.78 1.6020
. 90 108.2 8.3 . 17.53 -
5.295 7.77 17.33 1.4814
125 . .. 134.5. •. 1.1.56 . 25.80
6.357 9.290 23.03 1.0251
150 161,5 . 13.8 34.27 -
8" 8.249 16.490 40.15 1.8365
200 209.5 24.5 59.75 -
APPROVED
9'allied . Customer Service (800) 882-5543 Fax: (708)33971806
TUBE & CONDUIT 16100 S Lathrop • Harvey, ft 60426 1 11350 162ft0rn Rd. • Philadelphia, PA 19154 I 2525N 27th Ave. • Phoenix, AZ 85009 S5-3
LaterM Sway Brace 5pac
Pipe Diameter (In) At 20 ft v At 25 ft At 30 ft At 35 ft At 40 ft v
96 77 63 54 45
1 '14 125 103 88 74
1 1/2 283 227 186 159 133
452 362 296 254 213
2½" 671 537 440 1 377 316
1085 868 711 610 510
1847 1477 1210 1037 869
Pipe L, id meter (1 -1) At 20 ft At 25 ft Iv
Sway Brace Spacing
At 30 ft - At 35 ft1'2 ' At 41 ft
142 114 93 80 67
1 1/4 206 169 145 121
1 ½" 368 294 241 207 173
620 496 406 348 292
2'/2" 1390 1112 911 781 654
2205 1764 1445 1239 1037
2Lr'2l SwayBra.e 4ac1ng'2
Pipe Diameter (In)
At 20 ft '2
140
At 25 ft 2'2
112 .,.....
At 30 ft 1'1
.. 9.l. --
At -
79
At 40 ft
66
1 1/4 188 154 132 q 111
1 ½" 331 265 217 186 156
562 449 368 316 264
2½" 1113 891 730 626 524
.,. 1683 1347 . 1103 . 946 . . ... 792
Notes:
a The tables for the mä'ximun-t load Fpw iñ.thè Zone Of lnfluence.are based on specific configuration of mains,
branch lines and Yield Strength
b Assumes branch lines at the center of the main pipe span and near each sway brace._,
c Assumes branch (ides at'the tThrd poim of the main pipe span and near each sway brace
d Assumes branch lines at the quarter -point of the main pipe span and near each sway biace
(?~alhed. Customer Service (800) 882-5543 Fax: (708) 339-1806
TUBE & CONDUIT 16100 S Lathrop . Harvey, IL 60426 1 11350 Norcorn Rd. Philadelphia, PA 19154 1 2525 N 27th Ave. • Phoerrx, AZ 85009
3)FITTINGS
Welded Outlet Fittings Fire Products Division of Anvil' Intern
For Fire Protection &
Submittal Sheet
*iM6 C'A Other Low Pressure Piping Systems Ek~FR I T.
Merit WeldMiserTM Tee Let® Welding Branch Outlet Fittings offer the
user a high strength, low cost forged threaded and grooved line of
fittings specifically designed and manufactured to be installed on
Schedules 5 thru -1 0, proprietary thin wall flow pipe and standard
I
wall pipe.
Merit Tee Lets are forged steel welding outlet fittings The material
used in manufacture meets the chemical and physical requirements of
ASTM A 53, Grades A or B, Type E, A-i 35, A-795, Tee-Lets employ
a low weld volume design to provide for either a partial or full -
penetration weld employing a single pass with minimum burn-through
and pipe distortion. Weld Miser Tee-Lets are recommended for use on
proprietary thin wall, Schedules 5, 10 and 40 pipe. Threads comply
with ANSI Bi .2Q.i or ISO7/1. They are UL Listed and FM Approved
for use conforming to the requirements of Bulletin 13 1999 of the
National Fire Protection Association. When used in fire sprinkler
systems, Tee-Lets are rated for 300 psi.. When used in mechanical
systems, maximum pressures are calculated using criteria developed
UL u c
for ASME B31 piping code.
APPROVED
For Listing /Approval
- details contact your
AnvilStarTe Representative.
Outlet Model Outlet Pipe Size leader Pipe Size F:.:i Pressure
i,.41 ½.8Sch10,40i
1/2 4 (5th 5, DynoFlow) Tuu1.at Type A 1 1/4, 11/2, 2, 2/2 34 300
2 4 (El-Flow) (F-Threaded End)
2, 4 6 (El-Flow)
Tee-Let Type C 11/4 .8 11/4.8 (Sch.10, 40) 300
21/2-8 /u .4 (Sch. 5, tynoFlow) (Grooved End)
Tee-Let Type C/k 11/4.6 11/8 (All Schedules) 300
(toh Grooved End)
ii i
Project:
Date: Date: Phone:
Architect [Engineer:
Contractor:'
Address:
Motes 1:
Notes 2:
R F5
Merit® Tee-Lets & Drop Nipples For the latest UL/ULC Listed and FM Approved pressure ratings, versus pipe schedule,
REV. 03.03.06-001 go to www.anvilstar.com or contact your local AnvhlStar representative /. ,/
AMJLBtar
Welded Outlet Fittings Fire Products Division of Anvil' InternatioiaO 7 -
Submittal Sheet
N
WIT®
UNIFIED DESIGN TM SERIES
Merits Unified Design Series carries all important
design considerations into its entire line of welding
branch outlet fittings.
Merit® WeldMiserTM Tee,Lets® are designed - - -
and Manufactured to reduce the amount of weld
required to install the Tee-Lets on thin wall or
proprietary flow pipe. Typically only one weld-pass
completes the installation. Merit Tee-Lets install with less
weld volume than any other brand of welding outlet
fittings for fire sprinkler applications. To accomplish this:
The contoured end of the fittings employs a reduced
outside diameter. Two major advantages are
immediately apparent:
The thinner wall on the contoured end permits welding
temperatures to be matched to the thickness of
the branch line or main thereby insuring complete
penetration without cold welds, weld roll-off, burn-
through or excessive distortion. . n smaller sizes a heavier section is maintained
n the threaded end of the fitting. This protects the
threads from damage during shipping and handling
prior to installation as well as from weld distortion.
° Each outlet size 1 1/21t and larger, whether male or
female threaded, cut grooved or beveled requires the
some hole size in the header pipe. This simplifies the
installation process.
GENERAL SPECIFICATIONS
Tee-Let welding outlet fittings are manufactured from
highly weldable steel which conforms to the chemical
and physical requirements of ASTM A-53, Grades
A or B, Type E. Ease of installation is assured when
automatic welding equipment is used to install Merit
Tee-Lets.
Threads are cut in accordance with the requirements
of ANSI BI .20.1, national standard for tapered pipe
threads, or 150-7-1 threads are available.
Tee-Let threaded and grooved welding outlet fittings
are UL/ULC Listed and FM Approved for use in the
fire sprinkler systems installed in accordance with the
requirements of NFPA Bulletin 13. They are rated for
300 PSI operation in fire sprinkler systems, and higher
pressures in other non-critical piping systems.
Tee-Lets are offered in a wide variety of header sizes.
The consolidated header sizes shown in the following
charts allow the fittings to be installed on more than
one header size, permitting the first size listed to fit
the header perfectly, while a small gap along the
longitudinal center line of the header will appear for
the second size listed.
Merit® WeldMiserTM Tee Lets® are identified by a lot
number that provides full traceability per ISO 9000
specifications.
FOR YOUR PIPING SYSTEMS SPECIFY
WELD-MISER TM TEE-LET®
Branch Outlet Fittings shall be Merit Weld-Miser Tee-Let,
Lightweight forged steel, employing low weld volume
profile to provide for full penetration welds with minimum
burn through and pipe distortion on Schedule 5 thru 10,
proprietary thin wall, and standard wall pipe. Threads
are to be ANSI B .20.1, or ISO-7- 1, and the bore of
the fittings calculated to improve flow. Welding outlets to
be UL Listed, FM Approved for use conforming to NFPA,
Bulletin 13 and pressure rated for 300 PSI maximum.
Merit® Tee-Lets & Drop Nipples For the latest ULIULC Listed and FM Approved pressure ratings, versus pipe schedule,
RE','. 0303.06002 go to www.anvilstar.com or contact your local AnvilStar representative .,
'ilL-1i.
Nominal Nominal
I
S Outlet Inside
Outlet Header Length Diameter Make Up
Number A B C 0 M Weight Each
OPT (BSPTI In (mm) In (mm) In (mm) In (tim) In (non) Lb kg)
1002002 1/4 x 1/4-8 1 0,080
6x 6-200 L I I
1005012 11/4 - 11m [ 1.063 1 0.700 0.500 I 0.171
37-40 I, 27] 178 1 12.1 .1 0u1q
1½-2 1 1.063 0.700 1 0.500 1 0.171 1005015
- /2X 4050 27.0 ] 17.8 72] 1 0.08
2- 2½ 1.063 1 0.700 0.500 J 0.171 1005020 73x
-• 50-65 21.0 j 77.8 1 12.7 L 0.08
1005025 21/2 -8 1.063 I 0.700 I 0.500 0.169
65-200 27.0 /7.8 12] { 0.08
1007012 l'/4-1½ 1.125 0.900 o.soo1 0.260
3240 28.6 I 22.9 /2.7 0.12
11/2.2 1.125 1 0.900 1 0.500 1 0.260 1007015
- 3/4 X
iPx
40-50 28.6 22.9 /2" 0.72
1007020 2- 2½ 1.125 0.900 0.500 0.260
50-45 28.6 22.9 12.7 0/2
1007025 2½-8 1.125 1 0.900 1 0.500 0.256
65-200 1 28.6 22.9 12.7 072
1010012 .. 11/4 - 11/2 1 1.250 1 1.145 0.500 0.331
//70017.
'-
3240 I. 31.0 29.1 j 12.7 j 0.15
1010015 1½-2 t[ 1.250 1.145 1 0.500 'I 0.331
/710075 , 4055 37.8 2 9. 1 /27 0.15
1010020 2.21/2 1.250 1.145 0.500 0.320
1/10020 lx
25n
50-65 . 31.8 j 79.? 1 12.7 075
1010025 2½-3 1.250 1 1.145 1 0.500 0.314
11/0025 4580 " 31,8 29.1 I. 12] L 0.14
3-4 1.250 1.145 I 0,500 I 0.309 1010030
1110030 . 80-/OS ,' 37.8 I. 29.1 /2] 0.74
5-8 . 1.250 1 1.145 0.500 1 0.291 1010050 .
1710050 725-200 1 31.8 1 2 9. 1 72.7 0.73
1012012 11/4.1½ 1.375 1.490 0.500 0.432
11 20! '' 41; 4 ip 1 r1 Oil 5
1012015 11/2 -2 . 1.375 1.490 1 0.500 0.421
11128/5
:
40-50 I 34.9 37.8 1 /7.7 .0/9
1012020 2.21/2 1 1.375 1.490 1 0.500 0.421
9112020 1I4x
32 x
30-65 34.9 37.3 1 12.7 .019
1012025 21/2.3 1,375 1.490 1 0.500 0.411
11)202.5 ' 65-60 1. 34.9 3 7. 8 j 72.7 j .019
1012030 3-4 I 1.375 1 1.490 I 0.500 1 0.389
I,' 1 It I I'
1012050 5-8 1.375 1 1.490 I 0.500 I 0.389
v , 225 1 /Q 1 12. 01
1015015 1½ 1 1.625 1 1.610 1 0.075 1 0.417
111~('ii I 40.9
1015020 2 1.625 1.610 0.875 0.477
S ii, / Z I
1015025 21/2 . 1.625 1.610 0.875 0,477
(115825 ' 11/2 x
. 40x
45 47.3 I. 407 22.2 .022
1015030 3-4 1.625 1 1.610 1 0.875 1 0,477
1115,30 _ xi ,2. ,,
1015040 4 1.625 1 1,610 0.875 1 0.477
/1151240 - 1170 I 41.3 1 4109 22.2 I 022
1015050 5-8 1 1.625 1 1,610 1 0.875 1 0.471
791 51)50 ' /25205' J 47,3 1 40,9 122.2 .022
1_1 Le
Nominal Outlet
r
Inside Nominal
Part Outlet Header Length Diameter Make Up
Number A B C D M Weight Each
OPT (BSPT) In (,nni) In (mm) In (mm) in (mm) In (mm) Lb (kg)
1020020 2 1.750 2.067 0,875 8.857
50 44.5 1 52.5 2.2.2 0.98
1020025 21/2 1,750 2.067 0.875 0.829
9720025 65 44.5 52.5 22.2 11.38
1020030 3 1.750 2.067 0.875 0.829
/20030
2 x
80 1 44,552.5 22.2 0.39
1020040 4 1.750 1 2.067 0.875 0.800
1/20040 IrOn 100 4-4.5 j, 52. 11 22.2' 0.36
1020050 5 1.750 1' 2.067 0.875 0.743
II7(tfl511 /75 445 525 777 J 9)34
1020060 6 1.750 2.067 0.875 0.743
1120060 150 44.3 1 52.5 22.2 0.34
1020080 8 1,750 2.067 0,875 0.743
208 44.5 1 32.5 22.2 1034
1025025 2½ 1 2.215 2.469 1.125 1.250
1123025 65 .54.0 62.7 2/1.6 0.35
1025030 3 2.215 2.469 1,125 1.200
1125030 801 54.0 42] 28.6 - 0.55
1025040 4 1 2.215 2.469 1 1.125 1.150
1125040 21h n ,
65x
/00 I 34.0 62.7 1 28.6 0.52
1025050 5 T 2.215 2.469 1.125 1.150
1 /950 /25 54] 1 62.7 28.6 0.57
1025060 6 2.215 I 2.469 1.125 1.150
/125060 150 54.0 62.7. 28.6 1 0.52
1025080 8 2.215 2.469 1 1.125 1.150
7125080 '200 1 54.0 42.7 1 28.6 ".52
1030030 3 T 2.500 3.068 1 1.500 1 1.750
-- 80 633. 779 38.1 079
1030040 4 1 2.500 3.068 1 1.500 1.700
-
3 x
100 1 63. .5 71.9 1 38.1 0./i
1030050 5 2.500 3.068 1 1.500 1.700
- BOx 125 63.5 //,9 1 30.1 17.71
1030060 6 2.500 3.068 I 1.500 1.650
- SR 47] 779 38.1 0.75
1030080 8 I 2.500 I 3,068 I 1.500 1.650
200 43.5 1/7 30.1 j 0.75
1040040 4 3.000 4.026 2.000 3.000
1040050 5 3.000 4.026 2.000 2.900
i'OUx
4x ______
1040060 6 3.000 4.026 2.000 2.800
102.3 50.0 .21
1040080 "8 3.000 4.026 1 2.000 2.800
- I 200 /4.2 902.3 592.8 1.27
NOTE: Part #1002002 is vol UL Lisied or FM Approved.
All size-on-size (ie, 2 x 2) Tee-Lets are not FM Approved.
AiVLStar Welded Outlet Fittings
-
Fire Products Division of Anvil' Internatioea! 8 -
Ae
W MERIT,
Type A
Female Threa
Submittal Sheet
- - - - - I - - - B - -
Merit® Tee-Let & Drop Nipples For the latest ULIULC. Listed and FM Approved pressure ratings, versus pipe schedule, "m
REV. 03.03.06-003 1 go to www.anvilstar.com or contact your local Any//Star representative v /
Type B Type C
Male Thread Cut Groove
Standard Weight Standard Weight
BL:
AL9tr, Welded Outlet Fittings
-
Fire Products Division of Anvil' lnteTnattoi'raI
Submittal Sheet
A/ MERIT
__ __
7Male
I1 __
Cut
read
Outlet
Grve Nomin Outlet Nominal Header Length Inside Diameter Outside Diameter Wall Thickness
OPT (SSPT) J OPT (OSPT) Ia (mm) In' n (ssss)) In (ant) In (mm) in (ins) in (mm)
1310012 T 2010012 1/4-1½ 3 1.049 1.315 0.133
32-40 80 26.6 034 24.
1310015 2010015 11/2.2 3 1.049 1.315 0.133
lx
40-50 00 26.6 33.4 3.4
1310020 2010020 22½ 3 1.049 1.315 0.133
50-65 80 26.6 33.4 3.4
1310025 2010025 2½-4 3 L049 1.315 0.133
65-100 itO 26.6 33.4 3.4
1310050 2010050 5-8 3 1.049 1.315 0.133
125-200 80- 26.6 33.4 3.9
1312012 2012012 1¼ 3 1.368 1.660 0.140
32 88 34.7 42.2 3.6
1312015 2012015 11/2 3 1.368 1.660 0.140
1¼x
40 80 34.7 42.2 3.6
1312020 2012020 2-2½ 3 1.368 1.660 0.140
58-05 80 347 42.2 3,6
1312025 2012025 3-4 3 1.368 1.660 0.140
80-1100 80 347 427 3.9
1312050 2012050 5-8 3 1.368 1.660 0.140
125-280 80 3 4. 7 42.2 3.6
1315015 2015015 11/2 3 1.610 1.900 0.145
40 80 4019 485 3.?
1315020 2015020 2 3 1.610 1.900 0.145
1½x
50 80 40.9 48.3 3.7
1315025 2015025 2½ 3 1.610 1.900 0.145
40x 65 80 40.9 J 48.3 27
1315030 2015030 3-4 3 - 1.610 1 1.900 0.145
80- 100 80 40.9 46.3 57
1315050 2015050 5-8 3 1.610 1.900 0.145
125-200 90 429 423
1320020 2020020 2 3 2.06/ 2.375 0.154
50 I 'Il) 52.5 $0.3 5.9
1320025 2020025 2½ 1 3 2.067 2.3/5 0.154
80 52.5 60.3 3.9
1320030 2020030 3 3 2.067 2.375 0.154
2 x
00 00
1320035 2020035 4 3 2.067 2.375 0.154
______________ SOn 100 80 52.5 60.3 I 3.9
1320050 2020050 5 J 3 2.067 2.3/5 1 0.154
1320060 2020060 6 3 2.067 2.375 0.154
1Sf- 90 52.5 60.3 3.9
1320080 2020080 8 3 2.067 2.375 0.154
.92.5 60.3 2.4
NOTE: Tee-Lets are manufactured to fit size-on-size, that is the contoured shape an a gives Tee-Let is made to lit perfectly as the first listed header size. If installed on the second header size
marked on the lifting, a slight gap of approximately /32' will appear along the longitudinal centerline of the header. For example, a 1 x 2 - 2½' lee-Let, is a ' outlet fining manufactured to
fit perfectly on the 2' header size listed, while leaving o 5/33 gap along the longitudinal centerline s1 the 21/2 size, if a perfect fit is required for a 21/2 header pipe, then a 1 21/2. 3" Tee-Let
- would be ordered. Size consolidations are employed to reduce inventory and provide for greater flexibility.
: Merit® Tee-Lets & Drop Nipples For the latest UL/ULC Listed and FM Approved pressure ratings, versus pipe schedule,
REV. 0303.06-004 go to www.anvilstar.com or contact your local AnvilStar representative
Type C
Cut Groove
Standard Weight
H- E -"H A nnr
Submittal Sheet
Type C/R
Roll Groove
Schedule 10
ii
AWkStar Welded Outlet Fittings
-
Fire Products Division otAnviI Intern 3$n7sI
Type B
Male Thread
Standard Weight
- E -"H A
ffThEILi7Q
______
Inside Diameter - U Well Thickness - F
Male
Thread
Std. Wt.
Cut
Groove Std. Wt.
Roll Groove
5th. 10
Nominal
Outlet
A
Nominal
Header
B
Outlet Length
C
Outside Diameter
E Standard Weight
Schedule
10 Standard Weight
Schedule
10
OPT (ISO -7- 1) OPT (150 7 1 APT (ISO -7- it (rim in (mitt) mm) mm) in (mm) In (mm) in (mm) in (ii n
1325025 2025025 2225025 2½ 3 2.469 2.635 2.875 0.203 1 0.120
2125025 ' . 62.7 50 76.2 5.0
1325030 2025030 2225030 3 3 2.469 2.635 2.875 0.203 0.120
2125030 86 80 6 2. 7 67.0 j 76.2 5.0 3.0
1325035 2025035 2225035 4 3 2.469 2.635 I 2.875 0.203 0.120
2125035 2'/tx 100 30 62.7 67.0 76.2
1325050 2025050 2225050 5 3 2.469 2.635 2.875 0.203 0.120 65x
2125050 725 53 . 62.7 o7.0
1325060 2025060 2225060 6 3 2.469 2.635 1 2.875 0.203 0.120
175 60 62.7 67.0
1325080 2025080 2225080 8 T 3 J' 2.469 2.635 2.875 0.203 0.120
2125'OOi) 200 80 61.7 67.0 76.2 5.0 3.0
1330030 0301330 2230030 3 3 3.068 1 3.260 3.500 0.216 0.120
80 80 /17(1 03.0 '560 5)1 50
1330035 2030035 2230035 31/ 3 3.068 3.260 1 .3.500 0,216 0.120
86.0 Oi1 TO
1330040 1 2030040 2230040 4 3 3.068 3.260 3.500 0.216 0.120
x A)so /8.0 113.0 820 5.0 20
1330050 2030050 2230050 5 3 3.068 3.260 1 3.500 0.216 I 0.120 SOc
78.0
1330060 , 2030060 2230060 6 3 3.068 3.260 I 3.500 0.216 0.120
1330080 . 2030080 2230080 8 3 3.068 3.260 3.500 0.216 0.120
1340040 2040040 . 2240040 4 4 4.026 J 4.260 4.500 - 0.231 0.120
700 110 7112.0 100.0 14.0 .o .I_ 30
1340050 I 2040050 2240050 5 4 4.026 4.260 1 4.500 1' 0.231 0.120
40 325' 00 :02.0 1000 7600 76 50
1340060 2040060 2240060 6 4 4.026 4.260 4.500 I 0.237 0.120 lOOn
1340080 2040080 2240080 8 4 4.026 1 4.260 1 4.500 0.237 1 0.120
- 2060060 2260060 6 J 4 { 6.065 6.357 6.625 - 0.280 0.134
6 x
- 2060080 2260080 8 4 6.065 6.357 6.625 0.280 0.134 ISD x
721.3 7,7 so
- 2080080 - 8 x 8 4 7.981 8,329 8.625 0.322 0.148
700x 700 100 I 203.0- 017.0 j 0150' 80 3.0
-
tOTE: Tee-Lets are manufactured to fit size-on-size. that is the ccsntsr,rsd rkr,r,u or, rr olvor, To-I.f i, rrvrrir, it, LI 014k, ,,r, L,d IIrt ko,lr it , fr,llr,ri or, ikr, ,r,ri i',r,r,rlr,r 6- r,rrrL-ri il-, Liii,,.',
a slight gap of approximately 1/32 will appear along the longitudinal centerline of the header. For example, a 1" x2 -2/2' Ten-Let, is a I' outlet fitting manufactured to fit perfectly on the 2' heoder size listed,
while leaving a ½2" gap along the longitudinal centerline of the 2½' size, if a perfect Fit is required for a 2½" header pipe, then a 1" x 21/2 - 3" Tee-Let would be ordered. Size consolidations are employed to
reduce inventory and provide for greater flexibility.
Merit® Tee-Lets & Drop Nipples For the latest UL/ULC Listed and FM Approved pressure ratings, versus pipe schedule, ( REV. 03.03.06-005 go to www.anvilstarcam or contact your local AnviiStar representative
ice
ViCTAULIC° SAC 1509001 C[RTiFiED\i.A
FreLock® Fittings
DIMENSIONS
h-C to E't
CtoE
to E
-L-0
<
No. 001 No. 003
C
- to E -
C It
to
W i
No. 002 No. 006
FireLock products comprise a unique system specifically designed for fire protection services. FireLock
full-flow elbows and tees are a CAD-developed, hydrodynamic design that has a shorter center-to-end
dimension than standard fittings. A noticeable bulge allows the water to make a smoother turn to maintain
similar flow characteristics as standard full flow fittings.
FireLock fittings are designed for use exclusively with Style 005 and Style 009 FireLock couplings. Use of
other couplings or flange adapters may result in bolt pad interlerence.
VictaLilic FireLock fittings pressure ratings conform to the ratings of Victaulic FireLock Style 005
couplings,
Patented
See Victaulic
publication 10.01
for details.
No. 001 No. 003 No. 002 No. 006
Fitting Size 900 Elbow 450 Elbow Straight Tee Cap
Actual Aprx. Aprx. Aprx. Thickness Aprx.
Nominal Outside C to E Weight C to E Weight C to E Weight '1' Weight
Diameter Diameter Inches Each Inches Each Inches Each Inches Each
Inches/mm Inches/mm mm Lbsikg mm Lbsikg mm Lbsikg mm Lbs/kg
1 11,1 1.660 - - - - - - 0.82 0.3
32 42.4 - - - - - - 21 0.1
11/2 1.900 2.75 1.2 1.75 0.9 2.75 2.0 0.82 0.4
10 48.3 70 0.5 45 4.1 70 0.9 21 01
2 2.375 2.76 1.7 200 1.8 2.75 2.4 0.88 0.6
50 60.3 70 0.8 51 0.8 70 1.1 22 0.3
292 2.875 3.00 3.1 2.25 2.2 3.00 3.6 0.88 1,0
65 73.0 76 1.4 57 1.0 76 1.6 22 0.5
3.000 3.00 3.30 2.25 2.4 - - - - 76 1 mm 701 76 1.5 57 1.1 - - - -
3 3.500 3.38 4.0 2.50 3. t 3.38 5.3 0.88 1.2
80 88.0 Ox 1 8 54 1.4 85 2.4 22 0.5
4.250 .1.00 5 7 3.00 5.1 400 7.5 - -
tOO mm 108.0 102 2.6 76 23 102 34 - -
4 4.500 4.00 6.7 3.00 5.6 4.00 8.7 1.00 2.4
100 114.3 102 3.0 26 2.5 1 102 39 25 1.1
5 5.563 4.88 126 3.25 8.3 4.88 15.7 1.00 4.1
125 1113 124 57 83 38
1
124 7.1 25 1.0
6.250 5.5o 12.6 - 3.50 9.2 3.50 17.9 - - 1,59 mm 158.8 140 5.7 89 4.2 140 8.0 - -
6 6.625 5.50 18,3 3.50 11.7 5.50 22.7 1.00 5.9
1511 1883 140 0.3 89 53 140 103 25 2.7
8 8.625 6.01 25.5 4.25 20.4 6.94 38.7 1.13 12.7
200 219.1 173 11.5 Ilia 9.3 175 17.5 29 5.8
0 REGISTERED TRADEMARK OF VICTAULIC - © COPYRIGHT 2009 VICAULIC - PRINTED IN USA -SKU 6WCAS-671'JUX 1639 REV F
United States . Phone: 1-800-PICK-ViC (1-800-742-5842) Fax: 010-250-8817 • e-mail: pickvin©xictauhc.com
Canada Phone: 905.804-7444 . Fax: 905.884-9774 • e-mail: viccanadur0xictaxFc.rom
Europe • Phone: 32-9-381-1500 . Fax: 32-9-380-4438 • c-mali: vireuro@xictauiic.ba
UK • Piixxt' 44(0)1438741100 Fax: 44t011438313883 . e-mail: viceuro@xictaxhc.be
Central and South America • Phone: 610-559-3300 Fax: 610-559-3608 • e-mail: vicai@victauiic.com
Australasia • Phone: 86.21.54253300 • Fax: 86-21.54253671 • e-mail: vicap@victaulic.com
1003
FLOW DATA . Frictional Resistance
Fittino Size Eazivalent Feet/meters of Straight Pipe
Actual Straight Tee
Nominal Outside No 002
Diameter Diameter 90' Elbow 45' Elbow
Inches/mm Inches/mm No, 001 No, 003 Branch Run
/4 1,660 1.5 0.8 3.7 1.5
32 424 05 0.2 11 0.5
112 1.900 2.2 1.1 5.5 2.2
40 43.3 0.7 0.3 1.7 0.7
2 2.375 3.5 1.8 8.5 3.5
50 60.3 1,1 05 2.6 1.1
20 2.875 4.3 2.2 10.8 4.3
65 73.0 1.3 0.7 3.3 1.3
3.000 4.5 2.3 11.0 4.5 76 1 mm 751 1 4 07 3.4 '1.4
3 3.500 5.0 2.6 13.0 5.0
80 88.0 1.5 0,8 4.0 1.5
4.250 6.4 3.2 .15.3 6.4
108 mm IOaO 2.0 0.9 4.7 2.0
4 4.500 6.8 3.-I 16.0 6.8
100 114.3 2.1 1.0 4.9 2.1
5 5.563 8.5 4.2 21.0 8.5
125 141.3 2.6 1.3 6.4 2.6
6.250 9.4 4.9 25.0 9.6 159 mm 158.6 2.9 1.5 78 2.9
6 6.625 10.0 5.0 25.0 10.0
150 168.3 3.0 1.5 7.6 3.0
8 8.625 13.0 5.0 33.0 13.0
200 219.1 4.0 1.5 10.1 4.0
7 The flow data listed is based upon the pressure drop of Schedule 40 pipe.
V ATERIAL SPECIFICATIONS
Fitting: Ductile iron conforming to ASIM A-536, grade 65-45-12
i. Fitting Coating: Orange enamel
Optional: Hot dipped galvanized
4
This product shall be manufactured by Victaulic or to Victaulic specifications. All products to be installed in accordance with currcrit Victulic installation!sssenlbly ifl5tructIOn.
Victaulic reserves the right to change product specifications, designs and standard equipment without notice and without incurring obligations.
2 Fi reLockw Fittirl95
tLPC and VdSApproved, ee notes on pig kigid D'"- SEE VICTAULIC PUBLICATION 10.01 FOR DETAILS
STYLE 005 . WITH VICPLUSTM GASKET SYSTEM (NORTH AMERICA ONLY)
FireLock® Style 005 rigid coupling has a unique, patented angle-pad design which allows the
housings to offset while clamping the grooves. By permitting the housings to slide on the angled
bolt pads, rigidity is obtained.
Support and hanging requiremens correspond to NFPA 13 Sprinkler Systems. Angle-pad design
permits assembly by removing one nut/bolt and swinging the housing over the gasket. This
reduces components to handle during assembly.
Style 005 FireLock coupling are designed and recommended for use ONLY on fire
protection systems.
Vic_PlusTM Gasket System:
In North America, Victaulicg offers a gasket system which requires no field lubrication on wet
pipe systems that are hydrostatically tested. The VicPlusTM System (patented) is dry, clean, and
non-toxic. It reduces assembly time substantially and eliminates the mess and chance of over-
lubrication. Please refer to the latest copy of the Victaulic Field Installation Handbook (1-100) for
supplemental lubrication requirements and dry pipe fire protection system notes.
/
PATENTED
(. Syte,
0 LISTING/APPROVALS The information provided below is based on the latest listing and approval data at the time of
publication. Listings/Approvals are subject to change and/or additions by the approvals agencies.
Contact Victaulic for performance on other pipe and the latest listings and approvals.
I 1w,
...L;t_/ .7—...........
... 175 F1 .
. . / 59• S c N/A ....N. 300
5-8 300 300 3 6 . 4-2 N/A N/A 300
3D 300 - 8 'u N/A 300
.P ..........300 . .._ . 390 LY5. j o....... '.y
01 1¼-2i 3001 300
EF '7-4 175@ N/A . 175
300 N/A N/A .1¼-3 300 300 300
Mr I ','I -4i 300 we 300
FM approved for service in 116 - 4 pipe.
6 UL Listed for service up to 4 pipe only.
@ US Listed for service up to 3' only.
JOB/OWNER . CONTRACTOR ENGINEER
System No. Submitted By Spec Sect - Para
Location . Date Approved
Date___________________________________
www.victaulic.com
%.A_C _ vICTAULIC IS REGISTERED TRADEMARK OF vIcTAuLIC COMPANY. 0 2006 VIcTAULIC COMPANY. ALL RIGHTS RESERVED. PRINTED IN THE USA.
4,140 4
(PS CARBON STEEL PIPE FIRE PROTECTION PRODUCTS
.1. F J or-
, -10 .
-42 -
STYLE 005
WITH VIC-PLUSTM GASKET SYSTEM (NORTH AMERICA ONLY)
DIMENSIONS
-I
1.2 1¼ 1660 350
337n 1.2 .2755 0.05 /1524 70 114148 05
32 42.4 2413
1½ 1.900 350 990 0.05 2_3,'ax214: 3.00 475 188 12
40 48.3 2413 4415 1.2 76 121:148 0.5
Rated for wet and dry sprinkler systems at 2 2.375 350 1550 0.07 : 2' 350 525 1.88 16
350psi/2413kPa for i¼-4'732-loornm 50 60.3 2413 6900 1.7 :2 ' 39 133 148 0.7
sizes and 300 psi '2068 kPa for 41/ -8 /108 2½ 2 475 350 270 007 400 575 1.8B 9
-.200rrrrn sizes; Schedule 10 roll grooved or 65 73.0 2413 10110 1.7 2 -'/rx 2:2 102 146 148 .09
Schedule 40 cut or roll grooved steel pipe.........
.
Style 005 is rigid and does not accommodate 76.1 mm 370 -
6.1 2413 11010
½ X 2 2 105 146 148 09
expansion, contraction or angular deflection •-.__' -__ ..,, ...,.., .
, ............................................
3. 3.500 350 . 3365 0.07 2 8X 2
. 4.63 6.13 1.88 2.1
80 88.9 1; 2413 l. 14985 1.7 2 . 118 156 148 1.0
4 i 4.500 i 350 5565 0.16 . ,.5.75 7252.13' 31
100 . 114.3 l. 2413 24770 ,ax2/, 146 184 ' 54 1.4
1080mm 4.250 300 4255 016 .-/ x2 563 725 213 1
108.0 2068 18940 , 4.1 143 184i 54 1.4
5 5.563 300 7290, 0,16 6.889.002.13: 45
125 141.3 2068 324451 4.1 2-/sx3175229 54. 2.0
5.250 300 6495' 0.16 ,,.6.63,9.002.13 4.5
133.0 2068 28900 4.1 .2'221,5,, 168 229 54 2.0
5.500 300 •7125 0.16 /25 2 .,.6.88.9.002.13 4.8
139. ' 139.7 2068 31715 : 4.1 2/4 175 . 229 54 2.2
6 6.625 300 10340 0.16 1 .8.00i,10.002.13 5.0
150 168,3 . 2066 . 46020 4.1 2'/2X3 203 . 254 53 2.3
S . 6.250300 9200 0.16 ,:7.63'10.00j2.13i 55
ri 159.0 . 2068 40955 ,
.2-/2X2/4: 194 , 254 . 54 2.5
6.500 I, 300 9955 . 0.16 ' 8.15 10.00 2.13 I 5.5
651r 1651 2068 44295 41 2 -/253 207 254 54 25
8.625 300 17525 0.19 2 - 5,18 x41A 10.50 13.14 2.63 11.3
200 , 219.1 2068 78000 4.8 ,267334i 57. 5.1
Working Pressure and End Load are total, from all internal and external loads, based on standard weight (ANSI)
steel pipe, standard roll or cut grooved in accordance with Victaulic specifications. Contact Victaulic for petfor-
mence on other pipe.
WARNING: FOR ONE TIME FIELD TEST ONLY, the Maximum Joint Working Pressure may be increased to '1/2 tunes
the figures shown.
4 The allowable pipe separation dimension shown is for system layout purposes only. Style 005 couplings are con-
sidered rigid connections and will not accommodate expansion or contraction of the piping system.
@ Number of bolts required equals number of housing segments. Metric thread size bolts are available (color coded
gold) for all coupling sizes upon request Contact Victaulic for details;
Style 005 couplings are VdS and LPC Approved to 128ar/175 psi.
*
www.victaulic.com 14 ctaulic,
VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. 0 2006 VICTAULIC COMPANY. ALL RIGHTS RESERVED. PRINTED IN THE USA.
IPS CARBON STEEL,. FEPROTEC1iON PRODUCTS
STYLE 005
WITH VIC-PLUSTM GASKET SYSTEM (NORTH AMERICA ONLY)
MATERIAL SPECIFICATIONS Housing: Ductile iron conforming to ASTM A-536, grade 65-45-12. Ductile iron conforming to ASTM
A-395, grade 65-45-15, is availabje upon special request.
Housing Coating: Orange enamel (North America); red enamel (Europe)
Optional: Hot dipped galvanized
Gasket:
Grade "E" EPDM - Type A Vic-Plus°'° Gasket System A
(Violet color code). FireLock products have been Listed by Underwriters Laboratories Inc. and
Approved by Factory Mutual Research for wet and dry (oil free air) sprinkler services up to the
rated working pressure using the Grade "E" Type A Vic-Plus'° Gasket System, requiring no field
lubrication for most installation conditions.
Grade "L" Silicone
Recommended for dry heat, air without hydrocarbons to +350°F and certain chemical services.
For dry services, Victaulic continues to recommend the use of Grade "E" Type A FlushSeal® Gasket.
Contact Victaulic for details.
Bolts/Nuts: Heat-treated plated carbon steel, trackhead meeting the physical and chemical
requirements of ASTM A-449 and physical requirements of ASTM A-1.83.
A Standard gasket and FlushSeal gasket approved for dry pipe systems to —40°F/-40°C. Based on
"typical" pipe surface conditions, supplemental lubricant is recommended for services installed
below 0°F/-18°C and for all dry pipe systems or systems to be subjected to air tests prior to being
filled with water. Supplemental lubrication may also be required on pipe with raised or undercut
weld seams or pipe that has voids and/or cracks at the weld seams. Victaulic continues to
recommend the use of FlushSeal gaskets for dry services.
www.victaulic.com 'Jtauhc° VICTAULIC is A REGISTERED TRADEMARK OF vicTAuLic COMPANY. 0 2006 vlcTAuuc COMPANY. ALL RIGHTS RESERVED, PRINTED IN THE USA.
STYLE 005
ITH VIC-PLUSTM GASKET SYSTEM (NORTH AMERICA ONLY)
GENERAL NOTES WARNING: Depressurize and drain the piping system before attempting to install, remove, or adjust
any Victaulic piping products.
WARRANTY Refer to the Warranty section of the current Price List or contact Victaulic for details.
NOTE This product shall be manufactured by Victaulic or to Victaulic specifications. All products to be
installed in accordance with current Victaulic installation/assembly instructions. Victaulic reserves the
right to change product specifications, designs and standard equipment without notice and without
incurring obligations.
INSTALLATION Reference should always be made to the -100 Victaulic Field Installation Handbook for the product
you are installing. Handbooks are included with each shipment of Victaulic products for complete
installation and assembly data, and are available in PDF format on our website at www.victaulic.com.
. Il I III IIItIIItIfI II II{ (II III
WCAS-697KR4
For complete contact information, visit www.victaulic.com
10.02 1538 REV I UPDATED 9/2006 ictauhc
vicTAuLic IS A REGISTERED TRADEMARK OF vIcTAuLIc COMPANY. 0 2006 vIcTAuuc COMPANY. ALL RIGHTS RESERVED. PRINTED IN THE U
S
A
.
Exaggerated for clarity
- -.
I SEE VICTAULIC PUBLICATION 10.01 FOR DETAILS -45 -
STYLE 75
Style 75 is available where moderate pressureare expected or weight
considerations are a factor. Up to 50% lighter in weight than the Style 77,
the Style 75 coupling is recommended for service up to 500 psi/3450kPa
depending on size. Housings are cast in two identical pieces in all sizes.
Hot-dip galvanized and special coatings are available for all sizes.
MATERIAL SPECIFICATIONS Housing: Ductile iron conforming to ASTM A-536, grade 65-45-12. Ductile iron conforming to
ASTM A-395, grade 65-45-15, is available upon special request.
Housing Coating: Orange enamel.
Optional: Hot dipped galvanized and others.
Gasket: (specify choice*)
Grade "E" EPDM
EPDM (Green color code). Temperature range —30°F to +230°F/-34°C to +110°C.
Recommended for hot water service within the specified temperature range plus a variety
of dilute acids, oil-free air and many chemical services. UL classified in accordance with
ANSI/NSF 61 for cold +86°F/+30°C and hot +180°F/+82°C potable water service. NOT
RECOMMENDED FOR PETROLEUM SERVICES.
Grade "T" nitrile
Nitrile (Orange color code). Temperature range —20°F to +180°F/-29°C to +82°C.
Recommended for petroleum products, air with oil vapors, vegetable and mineral oils within
the specified temperature range; except hot, dry air over +140°F/+60°C and water over
+150°F/-i-66°C. NOT RECOMMENDED FOR HOT WATER SERVICES.
* Services listed are General Service Recommendations only. It should be noted that there are
services for which these gaskets are not recommended. Reference should always be made to
the latest Victaulic Gasket Selection Guide for specific gasket service recommendations and for a
listing of services which are not recommended.
Bolts/Nuts: Heat-treated plated carbon steel, trackhead meeting the physical and chemical
requirements of ASTM A-449 and physical requirements of ASTM A-183.
JOB/OWNER
/System No.
Location -
CONTRACTOR ENGINEER
Submitted By Spec Sect
Date Approved
Date
Para
-www.victaulic.com
VICTAULIC IS REGISTERED TRADEMARK OF vicTAuLlc COMPANY. 0 2007 VICTAULIC COMPANY, ALL RIGHTS RESERVED. PRINTED IN THE USA. Lt_
!P •!3 Crs
STYLE 75
DIMENSIONS
1
315 500 680 0-006 2 —43 057 2--/sX2 238 27
108 45
3
06 334 3450 3025 0-16 48 61
1560 500 1080 0-006 045 2— /sx 2 268 461 177 14
06
.32 422 3450 4805 0-16 2 —10'38 68 117 45
1900 500 1420 0-006 1 —56 040 2— /sx2 291 482 177
45
15
06 40 48 3 3450 6320 0-15 33 74 172
2.375 500 2.215 0-006 1 —31 032 2— /sx2 343 522 188 17
08 603 3450 9860 0 15 25 87 133 48
2.875 500 3.245 0-006 025 2— /s x2 388 568
144
188
48
19
09 730 3450 14440 0-15 22 98
3.000 500 3.535 0-005 r - 12 026 2— aX V 2 400
102
590
150
188
48
19
09 751 3450 15730 0— 1 6 22
• 3500 500 4800 0-006 1 —2 022 1 2—/252/4 450
114
700
178
188
48
29
13
0 889 3450 21360 0-16 18 -
4.000 500 6300 0-005 0 —54 - big 2-1252% 500
127
750
191
188
48
29
13 1015 3450 28035 0-16 16
4.500 500 7.950 0-013 1 —36 034 2—/x2% 580
147
803
204
213
54
41
19 • 0 1143 3450 35380 0-32 28
213 37 4.250 450 6.380 0-013 1 —41 035 12 700 2— x 17 1080 3100 28395 0-32 29 141 198 54
5000 450 8820 0-013 1 —26 025 — 2 /aX3/4 613 943 213
54
55
25 1270 3100 39250 —52 21 1SF 240
S 5563
141.3
450
3100
10935
48560
0-013
0-32 1 —18 027
23 2— /a x % 684
175
007
256
213
54
58
26
52501 450 9.735 0-013 1 —21 0.28 2-15x825 555
166
937
238
213 50
2.7 4 1330 3100 43325 0-32 -
24 L 54
5500 450 : 10665 0-013 1 —18 028 2— /ax3A 680 959
244
213
54
63
29 1397 3100 47460 0-32 24 173
6.000 450 2735 0-013 1 —12 021 5 1 2 —/853/8 738 1048 188
48 : 62
28 524 3100 + 56670 + 0-32 8 87 265
6.625 : 450 15525 0-013 800
150
+ 1 5 0.23 2— _/8x3/4 1107 213 70
32 1683 3100 69085 0-32 18 203 281 54
Continued on page 3.
t @ :4: Refer to notes on page 3.
www.victaulic.coirt -.4./ictaulila -
VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2007 VICTAULIC COMPANY. ALL RIGHTS RESERVED, PRINTED IN THE USA.
(445 ••) 04531
-47 -
1590 mm 6.250 450 13.600 0-0.13 1-9 024 2-16x825 763 1049 213 68
31 1590 3100 61405 20 194 266 54
165.1 mm 165 6.500 450 14940 0-013 1 -6 023 2-IsX3/4 784 1066 206 72
1651 3100 66483 0-32 19 199 271 52 33
203.2 mm 8.000 1 450 22.635 0-013 0 016 2- 4x4/3 972 1333 231 126
2032 3100 100725 0-32 13 247 339 58 57
8 : 8.625 450 26.280 0-013 0-50 018 2-Ax4/ 1034 1397 232 124
200 2191 1 3100 116945 0-32 14 263 355 59 56
IqA nmmY 10000 t 350 27500 0-013 0 3' 015 2 - /BX /2 1216 1581 253 208
94 2540 2400 122375 0-32 11 309 , 402 64
12000 350 39500 0-013 0 -36 013 2-/sx5/~ 1416 1769 253 236
3048 2400 175775 0-32 360 449 64 107
Workirg Pressure and End Load are total, from all internal and external loads, based on standard weight (ANSI) steel pipe, standard roll or cut grooved in
accordaflce with Victaulic specifications. Contact Victaulic for performance on other pipe.
WARNING: FOR ONE TIME FIELD TEST ONLY, the Maximum Joint Working Pressure may be increased to 1 1/2 times the figures shown.
t Allowable Pipe End Separation and Deflection figures show the maximum nominal range of movement available at each joint for standard roll grooved
pipe. Figures for standard cut grooved pipe may be doubled. These figures are maximums; for design and installation purposes these figures should be
reduced by: 50% for 1/4 - 3 1/2/20 - 90 mm; 25% for 4/100 mm and larger.
@ Number of bolts required equals number of housing segments.
Metric'.thread size bolts are available (color coded gold) for all coupling sizes upon request. Contact Victaulic for details.
MINE ~11 rJ
9
www.victaulic.com j4tauiióo
vicrAuLic IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. 02007 VICTAULIC COMPANY. ALL RIGHTS RESERVED, PRINTED IN THE USA.
oali * na O2 0
.t
..........
WARRANTY
NOTE
INSTALLATION
-48-
STYLE 75
Refer to the Warranty section of the current Price List or contact Victaulic for details.
This product shall be manufactured by Victaulic or to Victaulic specifications. All
products to be installed in accordance with current Victaulic installation/assembly
instructions. Victaulic reserves the right to change product specifications, designs
and standard equipment without notice and without incurring obligations.
Reference should always be made to the 1-100 Victaulic Field Installation Handbook for the product
you are installing. Handbooks are included with each shipment of Victaulic products for complete
installation and assembly data, and are available in PDF format on our website at www.victaulic.com.
III III IIIIIIIIIIIlIIIIIIIIIIIIIlIIIMIIII
WCAS-6ZA058
For complete contact information, visit www.victaulic.com
06.05 1470 REV I UPDATED 712007 ctauIc
vicTAuLic IS A REGISTERED TRADEMARK OF vicTAuuc COMPANY. © 2007 viciuic COMPANY. ALL RIGHTS RESERVED. PRINTED IN THE USA.
4_ n;
kJu Elbow Straight 1F ALBt ar
Fire Products Division of Anvil' lnternstiq -
AWIL Cast Iron Threaded Fittings Cass 125 (Standard) Submittal Sheet
APPROVED
For listing / Approval
details contact your
AnvilStsrTM Representative.
Weight
Size 4 B
black gals.
NPS/DN In/mm Ia/mm lbs/kg lbs/kg
½
0.25 0.26
10 14 24 0,1 112
11/161 1A 0.4 0.41
15 17 29 SIB 0.19
3/4 IIN lJi& 0.6 0.61
20 22 33 0.27 0.23
1 l½ 1½ 0.92 0.95
25 24 38 0.42 0.43
11/4 1½ 1'4 1.4 1.5
32 22 44 0.65 0.66
1'/t 15/ 11 '/16 2 2
40 .93 4 0.88 0.91
2 16a 21/4 3.1 3.2
50
21A ]½1a 211/16 4.9 5.1
08 2.2 2.3
3 3½ 7.2 7.4
80 56 /9 3.3 3.4
4 2½6 3134 12 13
100 60 911 5.5 5.7
5 . 3Aa 41/2 21
125 84 114 iS -.
6 3½ 5½ 31 33
150 913 1311 II 15
8 534 6A 6 65 67
200 /32 14/ 29 311
I. I. TEll A IIITIIiII1
Anvil standard and extra heavy cast iron threaded fittings are Anvil standard and extra heavy fittings in this section, sizes
manufactured in. accordance with ASME-B16.4 (except plugs 1 1/4 NPS - 12NPS (8-300 DN), are included in the "List of
and bushings, ASME B 16.14). Dimensions also conform to Inspected Fire Protection Equipment and Materials" issued by
Federal Specificdtions, WW-P-501 (except plugs and bushings the Underwriters' Laboratories, Inc.
WW-P-471).
NOTE: See the Tech nipDto section for pressure-temperature ratings. See AnvilStor Web site for the most current listings and approvals.
Anvil Cast & Malleable Iron Fittings For the latest UL/ULC Listed and FM Approved pressure ratings, versus pipe schedule,
RV. 03.03.06-001 ... go to www.anvilstar.com or contact your local AnvilStar representative '.
900 Reducing Elbow 8]'oductsoivcaofi!r
ANVIL Cast Iron Threaded Fittings Class 125 (Standard) Submittal Sheet
( ai
_ -
A block Size
- -- L
Weight A B C D Tack
ght
APPROVED I P5/02 NPS/ThV In 1mm !n./mm hi/mm In/mm Ibs1kg WPS/DN MPS/ON la/mm in /mm In ./mm iniiil/ia lbs 1kg
For Listin / Approval . " l'As 0.4 1½ 1 1P /ii 2½s 2iis 3.7
details contact your : 9 2? 22 29 2½ //
AnvilStarM Representative ', ii p15 034 2 1½ P/i 2½s 2½ i
~ ½ '½u P/s 1½ 1½ 0.51 1½ 1~ 2½s 2½s 2P/s 6
5.
½ P/s /t Ps 067 JT Pa 2~s 2% 2 57
a 1 5 /2 /4 32 3s u3 3
25 ~ P/is P/s P/s P/is 0.16 50 Y 1~ 21/1 2% 215116 5.7
r 1A 1½ 1½ 1.1 2½ 1½ 21/16 3t,16 P/ 6.4
722 /7 27 31/ 28 '119 61 .9/) 5/. 73 /9 79
1/i ~ 1Ao 1½ 1½ 1 3½ 3 2A 27tis 3~ 325 8.9
32 10 72 29 21 4) 2.46 /9 49 51, 6238 6/ 4.1
1 P/is 1½ 1/1 1.2 2 P/s 2% 31/s 35,5 12
25 24
1/7. ~ 11/4 1/S 1~ 1.5 2½ 2336 2/4 3~ 3~ 11
- - J_ 19 32 41 41 0.49 4 85 54 /0 92 2 5.1 T / I 3/4 ~ 125s P//is 11/16 16 ' a00 3 2~s 211/is 35,5 3½ 11 1CA( / I ".5 '1 5 ' -i 1,7 '1/ 4/ 4.' 0.7 611 50 s49J >C 4,9
I I , 4' ] ]1/ 11 9i fl3/ 14 3½ 71,25 211/16 3u1/4 31i,7 12
25 25 32 47 4/ 055 90 22 68 94 94
1'/t P/as 11/4 14 17/t 1.7 213/16 31/2 43/8 43'5 20
4 0 9
½ I 3s 17/u 1% 14 2.2 5 3 213A6 P/s 4½ 4% 19
LL 37 35 61 13 t 8.6
1/4 P/is 1½ 2 2 2.2 4 P//is 35/i6 43/8 4% 16
36 .51 1i 00 84 /5
7 2 1 ]1/i iAs 2 2 2.1 3 P/s 3111 6 41/is 41/is 19
20 25 17 37 51 51 4.9 80 59 53121124 8.8
1'/4 1256 V/16 21/16 2¼6 2.3 6 4 21/is 37/8 4'½s 411/16 24
32 a is F -5
11/2 ]5/i 1½ 21/1 2~,b 2.6 5 3% 31~16 5 5 27
00 33 38 54 54 1.2 /25 96 98 27 i/ 12
1 1 1/4 24 2256 2.9 8 6 4256 5½ 43,5 6% 51
2½ 25 22 44 39 59 1.3 200 150 106 130 1 162 1 1/I 23
65 1 I/4 1256 1/4 2% 2,5 3.4
LI I iIiI LiIIiiIII IJII - -]
Anvil standard and extra heavy cast iron threaded fittings are Anvil standard and extra heavy fittings in this section, sizes
manufactured in accordance with ASME-B16.4 (except plugs 1/4 NIPS - 12NPS (8- 300 DN), are included in the "List of
and bushings, ASME B16.14). Dimensions also conform to Inspected Fire Protection Equipment and Materials" issued by
Federal Specifications, WW-P-501 (except plugs and bushings the Underwriters' Laboratories, Inc.
WW-P-47 1).
NOTE: See the Technical Data section for pressure-temperature ratings. See ArsvilStar Web site for the most current Listings and approvals
Anvil Cast & Malleable Iron Fittings For the latest UL/LJLC Listed and FM Approved pressure ratings, versus pipe schedule,
REV. 03,03.06-002 go to www.anvitstar.com or contact your local AnvilStar representative
AVILta - Straight Tee 4Products Division of!I'Ir
rIIIIII. __L'TiiiI_
AnvilStarTM Representative. Weight
Size A B block gale.
NPS/1)N In/mm la/mm lbs/kg lbs/kg
½ ½ 0.22 0.23
½ ½ 1 0.35 0.36
12 14 24 0.14 0.14
½ hI4 1½ 0.56 0.58
020
½ 1/is 0.84 0.85
1 1½
25 24 30' 0.57 9.50
11/4 11/ 11/4 2 2.1
32 29 0.9 9.9
1½ 1½s 11 /1 2.7 2.7
40 :93
2 1½s 2',4 4.2 4.3
50 40 47 1.9 2
21/2 1% 211/46 6.7 . 6.8
43 47 60 3 2.)
3 21A 31/s 10 10
80i 56 79 4.5 4.4
3½ 2½s 31,0s . 13 14
00 42
4 211/16 3½ 16 17
100 44 95
5 354 6 27 28
125 34 i 3
6 37/8 51,t 41 41
140 94 130 19 19
8 5½s 6/l6 79 81
200 132 167 36 37
_TiTTIiI1
Anvil standard and extra heavy cast iron threaded fittings arer Anvil standard and extra heavy fittings in this section, sizes
manufactured in accordance with ASME-B 16.4 (except plugs 1/4 NPS - 1 2NPS (8 - 300 DN), are included in the "List of
and bushings, ASME B16.14). Dimensions also conform to Inspected Fire Protection Equipment and Materials" issued by
Federal Specifications, WW-P-501 (exceptplugs and bushings ' the Underwriters' Laboratories, Inc.
WW-P-471).
,NOTE See the Technical Data section for pressure-temperature ratings. See ArmvilStar Web site for the most current Listings and approvals.
Anvil Cast & Malleable Iron Fittings For the latest UL/ULC Listed and FM Approved pressure ratings, versus pipe schedule,
REV. 0103,06-005 go to www.anvUstar.com or contact your local AnvilStar representative '-, ,
A1VlL Cast iron Threaded Fittings Class 125 (Standard) Submitta Sheet
.
9~~_g
APPROVED
For Listing I Approval
details contact your
Reducing Tee AiLBtar
Fire Products Division of Anvil' Iflternati
ANVI L Cast Iron Threaded Fittings Class 125 (Standard)
S UL OyLq
APPROVED
For Listing / Approval A----B
details contact your __f_
AnvilStarTM Representative. C F ,.
Submittal Sheet
1T 'TTTT1
.-.'.-,----- I Size A B I U E I F
-block- Size A B C
-
U I E F
-
- UILILI gob -
PS,i
-
n, MM t7im 'in' S. /k, t,/k NP5/BNINPS/Dl iPS/' m w 'g,/g g,/m /tntrin. m I!go.jhIjg
1/4 H116"/16
j.
1,16 ]1j3 119 1½ 0.57 - 4 1 154 ½t 154 1'i2 1½ 11/2 11
1 ' 7 22 '2 29 29 26 .3 ')I 2 /5
-3111 -71/16 11/16 8 B i ½ H116 0.9 -
1/2 ½
U
'
½
b' 1/
s
19
6
29 29 IH
6 5
(II;, 41
½ W4 1/it 0.91 -
22 i2 2 37 31 :2 3l 5 ,9 22 22 Z41
1½ 11 -
'423 29 22 31 3/ 35 4' 2
1/4 ½ 1% 0.B9 —
;fl j2 24 a 32 ,.4 .3 . 12 ,' 4 32 22
- ½ % 1 tA 6 H/ % - o -
- -
14 ½o H116 i 'Ai T 'ii7 T 1 'A 1½ lA 1/2 I.] -
21; 7? 22 2 32 a 332 : 24 24 26 35 3/31.391
14 ½½6%-
25
3/4
3 i4 22 1 u /2 /.S 9 11 1 19 79 22 -
14 p116 a/it m5/ó 116 At 1½ OJS— ½½16%6l½1½1', 1 1
17 25 /2 22 37 -i,a ', 7 11 24 7 31 35 546 94
1 -- At - 14 HAt 1A6 H -
15 4- 2/ 37 31 Jr__
1t9 0/ 4 99 - /i 1½ 1½ 'Aó 1½s 11½6 1½t
7 ,.3 _3,1 /2 97 37 2 01 92 '2 2' 26 43
32 32
.c.... ......TIIT 7TT: .T.
Anvil standard and extra heavy cast iron threaded fittings are Anvil standard and extra heavy fittings in this section, sizes
manufactured in accordance with ASME-131 6.4 (except plugs '/i NPS - 1 2NPS (8 - 300 DN), are included in the "List of
and bushings, ASME B16.14). Dimensions also conform to (Inspected Fire Protection Equipment and Materials" issued by
Federal Specifications, WW-P-501 (except plugs and bushings j the Underwriters' Laboratories, Inc.
WW-P-471). .
NOTE: See the Technical Data section for pressure-temperature ratir,qs. See AnvilStor Web site for the most current Listings and approvals.
Prolect:
Date: Phone:
Architect/Engineer:
VContractor:
-
Notes 2:
PAGF 1(1.F5
Anvil Cast & Malleable Iron Fittings For the latest UL/ULC Listed and FM Approved pressure ratings, versus pipe scneauie,
REV. 03.03.06-006 go to www.anvilstar.com or contact your local AnvilStar representative
FA
[I1
Reducing Tee AwtBtar
Fire Products Division of Anvil' interntio5r -
AWIL Cast Iron Threaded Fittings Class 125 (Standard)
S& fl±
APPROVED: f
For Listing / Approval :
details contactyoiur -
AnvilStarT° Reoresentativet
Submittal Sheet
Size
UMHHHHHH HHHHHHHMA UHHHHHIIHHR HHHHHHHHR • HHHHHHHII HHHHHIIIII HHHHHHHIIR HHHHHHIWW HHHHHHR HHHHHHHMHU HHHHHHHHR HHHHHHHHILIU
HHHHHHiHIi HHHHNHHRRU HHIIIIHR MHHHHHIHHR UHNHHHHHHR HHHHHHHN HHHHHHNH HHHHHHA MEN HHN HH1IHHHHH HHHH HH MEN IHHN
MMMMHMMMM HHHNHHHHR HHHHHHH HHHHHHHIIIi HHHHHHHR IHHHHHHVWR HHHHHHHHR HHHHUHHH HHHNHHH MENEMEM UHHHHWIUU ME ENE
HHHHHWHW HHHHHHH
I
MM
HHHIIIIHHHHR HHHHIIHHA HHHHHHHHA HHHHHHHH HHHHHHHIIR MHHHHHHHHR UHHHHHHNHR HHHHW RHHNNHHHHIII HHHHHHH HHHHHHH
I
1HHHHHHN
HHHHHHMI11 HHHHHIIHH mm =M
HHHHHHMM HHHIIH MEN HHMHHIHH MEMEMMEM
I
Anvil Cast & Malleable Iron Fittings
REV. 03.0306-007
For the latest UL/ULC Listed and FM Approved pressure ratings, versus pipe schedule, ( ANVIL go to www.anvilstar.com or contact your local AnvilStar representative
Star- ANVIL Reducing Tee Fire Products Division of Anvil' Internwit,54
ANVIL Cast Iron Threaded Fittings Cass 125 (Standard) Submitta Sheet
®
APPROVED
For Listing / Approval . -
details contact your .
AnvilStarTM Representative,
iIILt::InIIJ..L:: T:.T:1
504 ' li B 6 U E F Weight
Pork solo.
1175 0½1175/Dl7 i/PS'D0 IoL'nlrn jnrn mm In. mm J5 j7;;
16' 2 1 ½& 11,4 10½ 2'/4 2/8 2¼ 1 3.7 -
54
121,6 1°/a 1'i6 l°As 2½6 2'.'½ 2'/u 5.5 —
4') 4 ,' 4' 6.5?21, --
½ 134k '/¼ 1°A6 11/2 1½ 2.7 2.8
75 72 22 3? 36 36 "8 72 7.1
½ ½ 165 1°/16 1°/it l'A 2.9 —
2
I ½65 65'16 5 65/4 2 3 3.1
2.5 3;'• 74 44 57 2.4
2 11114 1 3/74 46 1/16 1½ 1½ 2'/76 3.4 —
50 .52 2.? 22 21 73 48 '"
1½ 15/54 15/74 11/2 2 2 2½ 3.6 3.7
40 24 24 37? 5 1; 34 4/ 1,)
2½ 1½ 1½ 1,65 2A6 2'/e 2°,¼ 5.2 5.4
18 4n 65/2 4/ 7.3 2.4
4 3 3 2°/ie 31656 3''/ia 3½ 16 —
— 94 94 89 1..?
2 ¼ 21,/8 Aa 5.3 —
/2 5040 ,
477 2. 45 74 --
1 2½. 1'Aó 1'65s l'½6 2556 2/4 2','i6 5.2 —
5 66 61' 68 2.4
3/4 2½ 1'/4a 73/4 111A6' 21'ii6 21/4 217/1i 5.1 —
206547 44 68 57 621 2.3 —
2.Th2½uS-
1 50 40 40 48 '52 54 15 2.3
2.5 60½'i4 _71 '742654 —
44 4/ 414 7i /5 2.4
1½
47]
1544
34
A6
/
653/i6 2A6 1'/io 23/16 4.3 —
134 2 1/,a 1½ 17/8 2°/116 2½ 231e 5 —
2/2 16,
44 2'/t 1 13/56 11,'4 713/1 211/16 2/a 2''/is 5.4 —
74 3/ 41 47 41 /7; 1.1
'7/, 7Aa 134¼ 2346 1656 2A6 4.2 —
10 2" 24 IN, 56 43 6? 19
11/2 2 1A6 11/7 1°/s 2°/u 2'/i 27/16 4.8 —
17; 7 .52 .1? 9? 4'
216 1 65s 71344 1346 21/16 2½s 211/8 5.8 —
'7 1/
½ ½. '0½ 1/4 i'65o 1½ 2/16 3.6 —
2 '4 "6 /s 1 ' 14 1 1,, 2½ 36 —
1 1 ''i 6 13h 1'/,s 1/4 2'6 39 —
W½ 43—
Th 1 6 113 r16 650s 2 4 4.4
1 1116 1½ 265s 2:4 206 5.2 —
2½ 47]
43, 2'2 1'346 iii 113/56 27116 2A6 2'A6 6 — el
6065623444—
2½ 24 r? '1
7 — -— 4 1 2'/ —
27' 44
_¼o BCDJjjj Work _q~v
1175. 00 III'S 37/ NPS DO In. i4i, 17? /1797 In 71116? 321 7/7/3 III. n15iJj1 PW,Ibc7/ jkLk
1 1 1 P/4 P'/u 11116 25s6 4.5 —
11/4 1346 13/6 13/i 2146 2','i6 2½ 4.8 —
—'
4561 765 1565 651 134s 2565 2A6 2656 5.1 —
2 656W16 2346 5.9 6
— Aa 65658 2 —
3 2½ 2/i 2/6 211,6 3½ 7.6
6546
E31/t
14
2½2½ 2½2"A 3
1 3 2½ 2½ 213 211,I1 31/a 8.3
25 110 ¼ 54 54 /9 617 79 3.8
1'/i 3 2½ 2'/a 21,18 3½ 7134 31/t 8.5 —
7,' 80 54 34 34 /9 /3 19 37 .
1½ 21/2 1½ 7T 2½ 21346 2A6 31116 1.7 —
427 6545' 48 54 73 95 79 3,'
1',6 3 2½ 2¼n T, F 31/a 213/16 31/8 8.1 —
40 80 So' 54. 54 79
11,6 13/7 1½ 294a 23/is 2/16 211/16 6.8 —
48 35 37; 44 5376233,'
2 i°/,6 1A6 2°/i6 2/,a 21/4 7/5/fl 1.3
2 50 40 40 59 63 5/ 75 3...
457 21/7 1°/i 1'34a 21/5 265/is 6 3'/7a 1.1 —
45 /4 49 54
3 2½ 2/16 21/8 3½ 21656 3'/o 8.8 —
20 54 59 54 /9 '5 /9 4
TJ 6666
1/5 1½ '3/s 2½ 23/6 2654 23/, 5.9
3 52 22 2? .54 56
/0. 1½ 1°/a 16/ 2111 2/7s 2'53s 2°/u 6.2 6.3
21/7 47;' 35 74
65 2 1556 1½ 23/a 2°/is 265 6 21656 6.8 —
30 4/? .7
2½ 1½ 11/,s 2/4 213/s 21'.'16 3/i6 7.7 —
3 21,18 2½ 2'/8 31,18 3656 3½ 9.1 —
L 4s Vi 2/16 1 ''6 65/a 2 "B 61 62
34 /16 1/16 2"8 14 1'l 75/s 61 62
1 1 65n5 2'/is 65A
ell
1'i 1¼ 71 2',a 2'1a 2°,,s 2'i 68 —
i½ 2/16 2/,a 2',6 2'5is 71 73
2 16 6 1746 2',6 27',a 21 2's 78 78
1'? 1½ 2½ 2'°ts 65 , 3',o 89 9
3,1/ 2'3 2½ 2°'i 3°6 34 3s 3/ 11 —
Anvil Cast & Malleable lrn Fittings For the latest UL/ULC Listed and FM Approved pressure ratings, versus pipe schedule, Ar
REV. 03.03.06-008 go to www.anvilstar.com or contact your local AnvilStar representative
Cdncentric Reducers Fire Products Division at Anvil' In1ernati -
(ANVL Cast Iron Threaded Fittings Class 125 (Standard) Submittal Sheet
0
APPROVED
For Listing I Approval
details contact your
AnvilStarTm Representative.
Sue A B Weight
black Size Weight
black 4
_________ P5/Thi Ifl1(flhll Ibs/A liPS/ON iVPS/DU li/nun In/mm A
lh ½ 0.4 314 18
I 2
'. • 11/16 1fl/16 0.54 il/S 2/l6 2
&,5 /i 1½ 0.63 1½ 34 2 3.1
28 17 38 0.29 2½
s.5
40 79 51 24
1/2:• 9Au 1½ 0.84 2 1 2½e 3
11/4 ½ . 7. 1 21/e ' 1.1 3/ 1/16 2½ 43
25 54 9.49 29) 24 64 2
1 ' i 1A6 2¼ 1.1 3 2 1¼6 2:4/4 4
.50 27 70 24
1/ 1/8 1 2½ 1A6 21¼o 471
1 L71
3/4
.,
' 1/3 1½ 1.2 2 116 21/I6 6.5
11/2 I'i3 ' 19 41 054 50
' i•\
25'
1,13
13
1/4
44
1.5
0.08
2/2
65
1A6
38
31/8
79
7.8
3.5
60 4
100
1¼ ' 1 21/4 1.5 3 11A6 3l/ 1
80 27 79 3.2
1/S •, ½ 2 2 5 4 1¼z 3/16 10
.51 091 125 100 27 84 4.8
2 ' I/i 2 1.9 4 1½ 3¼6 14
6 100 29 87 6.3
1 ' 2 1.8 150 5 1½ 39/16 16
(9 57 033 125 29 . 90 7
8 6 1¼ 31/8 29
I in hex end
Anvil standard and extra heavy cast iron threaded fittings are r Anvil standard and extra heavy fittings in this section, sizes
manufactured in, accordance with ASME-B16.4 (except plugs 1/4 NPS - 12NPS (8- 300 DN), are included in the "List of
and bushings, ASME B16.14.). Dimensions also conform to Inspected Fire Protection Equipment and Materials" issued by
Federal Specifitations, WW-I-501 (except plugs and bushings the Underwriters' Laboratories, Inc.
WW-P-471).
NOTE: See the TechnicoIato section for pressure-temperature ratings. See AsvilStar Web site for the most current Listings and approvals.
--- ---
I Project:
Date: I Phone:
Architect I Engineer:
Contractor:
Address:
otes1:
Notes 2:
Anvil Cast & Malleable Iron Fittings For the latest ULIULC Listed and FM Approved pressure ratings, versus pipe schedule,
REV. 03.03.06-0011 go to www.anvilstar.com or contact your local AnvilStar representative /
Ll
4)HANGERS
~,Eg 0
P.O. Box 3365 South El Monte, CA 91733 626.444.0541 Fax 626.444.3887 www. Afcon.org
650
ALL THREADED ROD 10'- O' LENGTHS
ROD
SIZE
MAX. REC. LOAD LBS.
FOR SERVICE TEMP.
650°F 750°F
1/4 240 215
3/8 610 540
1/2 1130 1010
5/8 1810 1610
3/4 2710 2420
7/8 3770 3360
1 4960 4420
11/4 8000 7140
11/2 11630 10370
NOTE; maximum Temperature: 750°F
SIZE - 1/4 thru 1 1/2 inch rod in 10 - 0 lengths.
MATERIAL - Carbon Steel.
FINISH - Plain, E.G., H.D.G. and S.S.
ORDERING - Part #, rod diameter and finish.
3/00
½ Inch pipe
5 thru 8inch pipe
S P.O. Box 3365 South El Monte, CA 91733 626.444.0541 Fax 626.444.3887 www. Afcon.org
300
RING HANGER
3/4 thru 4 inch pipe
LISTED FOR STEEL/CPVC
SIZE - 1/2 thru 8 inch pipe.
MATERIAL - Carbon Steel, Mu. Galvanized to G-90 spec.
LISTING/APPROVAL -
c®us 203-EX 2551
Approval guide - Pipe Hangers
OSHPD OPA-0601 See Website.
CONFORMS WITH: Federal Specification WW-H-171 Type 10,
Manufacturers Standardization Society ANSI/MSS-SP-58 Type 10.
MAXIMUM TEMPERATURE - 650°F.
FUNCTION - Pipe hanger component for use on steel, CPVC or
copper piping.
INSTALLATION - Per NFPA 13,13R, 13D and
CPVC manufacturers instructions.
SPECIAL NOTE: When installing on CPVC sprinkler system pipe:
Verify that all assembly components are cleaned of any surface oil.
FEATURES -
* Sized and listed exclusively for use with #310 Surge Restrainer.
* Band edge is offset for EASY pipe insertion.
Custom fit swivel nut for better retention in ring body.
* Full length knurl on swivel nut for better grip.
ORDERING - Part #, pipe size.
9/08
NFPAI3
PIPE ROD
MAX REC.
LOAD LEIS.
METRIC
REFERENCE
3/4 3/8 400 20
1 3/8 400 25
11/4 3/8 400 32
400
—40-
2 400 50
2 1/2
11/2r
3/8
600 65
3 600 80
3 1/2 600
4 3/8 1000 100
5 1/2 1250 125
6 1/2 1250 150
8 1/2 1250 200
551
P.O. Box 3365 South El Monte, CA 91733 626.444.0541 Fax 626.444.3887 www. Afcon.org
310
RING RESTRAINER
10
Restraint
SIZE - One size fits 3/4 thru 2 inch AFCON#300 Ring Hanger.
MATERIAL - Carbon Steel.
FINISH - Mu. Galvanized.
LISTINGS -
c us 203-EX 2551
Listed only for use with AFCON #300 Ring Hanger.
FUNCTION - To restrain movement of sprinkler pipe toward the knurl nut of the
ring hanger. To prevent upward movement of pipe that supplies a pendent
sprinkler below the ceiling.
INSTALLATION - Per NFPA 13 and CPVC manufacturers instructions
on steel, CPVC, or copper pipe.
Snap into locking position on swivel nut of AFCON #300 Ring Hanger.
SPECIAL NOTE: When installing on CPVC sprinkler system pipe:
Verify that all assembly components are cleaned of any surface oil.
FEATURES -
* Listed only for use with AFCON #300 Ring Hanger.
ORDERING - Part # and size.
S
Specific AFCONproduets are esclnstvelydesigned to he compatible ONLY with other .4FCON products including parts and fasteners, resulting in a listed swoybroce, restrainer nr hanger assembly. Be advised the following warranty restriction will apply. DISCLAIMER . AFCON will NOT warrant against the failure of its products when used in cnntbination with other products, ports or systems
not manufactured at sold by AFCOtV. AFCOiVshall NOT be liable under any circumstances whatsoever for any director indirect, incidental or consequential damages of any kind, including but not limitetl to inst of ha.siness or profit, when non-AFCON products have been, or are used.
1/08
'.• 00 ZID
P.O. Box 3365 South El Monte, CA 91733 626.444.0541 Fax 626.444.3887 www. Afcon.org
162
UNIVERSAL
RESTRAINING STRAP
Nut optional, if
insufficient rod dimension
a'
SIZE- One size fits both 3/8" and 1/2" rod or set screw.
Available lengths 4" and longer.
MATERIAL - Carbon Steel.
FINISH - Mil. Galvanized.
LISTINGS -
c us 203-EX 2551
PATENT - No. 5,897,088
FUNCTION - To enhance hanger attachment in areas subject to
Earthquakes.
INSTALLATION - Install tight to structure and component parts
Minimum return on strap: 1"
L-dimension is measured from hanger rod center
to the strap end.
FEATURES
* Fast installation for new construction or retrofit. * Requires no hanger disassembly to install.
IMPORTANT NOTE: "No Nut Is Required"
When installed tight to structure and component parts. (See drawings
provided)
ORDERING - Part # and L-dimension.
[1
1/08
P.O. Box 3365 South El Monte, CA 91733 626.444.0541 Fax 626.444.3887 www. Afcon.org
100
REVERSIBLE
BEAM CLAMP 3/4" MOUTH
P_j
SIZE -3/8" and 1/2" rod.
MATERIAL - Ductile iron.
FINISH Plain, E.G. and H.D.G.
LISTINGS -
US 203-EX 2551
Approval guide - Pipe Hangers
FUNCTION - Hanger assembly attachment to steel flange with thickness of less
than 3/4".
INSTALLATION - Per NFPA 13 with set screw up or down.
Torque - 3/8=60 inch lbs. or 1/2= 125 inch lbs. In the absence of a torque
wrench, engage set bolt finger tight then additionally tighten 1/3 turn.
FEATURES
* Listings allow installation with set screw up or down - see drawings. * Maintains CONSTANT HANGER CENTER-LINE, with setscrew up or down.
* Flat throat back to prevent twisting on flange during installation.
ORDERING - Part #, rod size and finish.
1/08
-
P.O., Box 3365 South El Monte, CA 91733 626.444.0541 Fax 626.444.3887 www.Afcon.org
UIb IJ ny. 4
SWAY BRACE ADAPTER
WIDE FLANGE I I-BEAM
Part #
SIZE RANGE - 1/2 Rod.
MATERIAL - Carbon Steel.
FINISH - Plain, E.G. and H.D.G.
LISTING/APPROVAL -
203A-EX 2625, 203-EX 2551
Listed only for use with other AFCON bracing products.
OSHPD OPA-0601 See Website.
PATENT - No. 6,334,285
FUNCTION - Sway brace adapter used to attach an AFCON sway brace assembly
to a wide flange or I-Beam steel structural member. To provide a point of
connection when drilling is not allowed or impractical. Also can be used to attach
to a steel web joist with a formed top chord. (See Drawing)
INSTALLATION - Per NFPA 13. Per drawing, insert 1/2" x 1 1/4" attachment bolt
into 086 bracket. Install 1/2" threaded studs thru both brackets and engage on steel
flange. Assemble nuts on studs and tighten. Install nuts finger tight, then
additionally tighten 1 1/2 turns or torque to 40ft. Lbs. Attach AFCON sway brace assembly on 1/2" bolt.
On steel web joist with formed top chord install within 6" of the panel points.
1/2" threaded studs and fasteners furnished by customer.
FEATURES
* UL load ratings at 300 thru 90° horizontal:
Perpendicular to beam - 2015#
Parallel to beam - 1265# * Universal, any flange width having thickness of 1/4" thru 1 1/4".
* Studs capture head of bolt, providing hold back.
* Alternative to center loading beam clamp.
* UL listed hanger attachment for 8" pipe.
ORDERING - Part # and finish.
Specific . AFCOiVproducls are exclusively designed to be compatible ONLY will, othenAfCONproducts including parts and fasteners, resulting in a listed sway brace, restrainer orhangerasserobty. Be advised the following warranty restriction will apply. DISCLAIMER - AFCON will NOT warrant against the failure of its products when used in combination with other products, parts or systems riot manu factored or sold byAFCON. .4FCON shall NOT be liable under any circumstances whatsoever for any director indirect, incidental or consequential damages of any kind. including but not limited to toss of bosinets or profit, when non-AFCON products have been, orate used.
9
2/09
100-7
P.O. Box 3365 South El Monte, CA 91733 626.444.0541 Fax 626.444.3887 www. Afcon.org
410
SWAY BRACE FITTING
Part # 077.......
rt 8 078
SIZE - 1 thru 8 inch pipe.
MATERIAL - Carbon Steel or S.S. (Type 304).
FINISH - Plain, E.G., and H.D.G.
LISTING/APPROVAL -
203A-EX 2625, 203-EX 2551
Listed only for use with other AFCON bracing products.
OSHPD OPA-0601 See Website.
FUNCTION - Pipe attachment component of a longitudinal or 4-way sway brace,
consisting additionally of AFCON 70 series attachment end, AFCON 80 series
adapter as required and brace pipe element forming a complete sway brace
assembly.
INSTALLATION - Per NFPA 13. Assemble 410 over pipe to be braced, install
70 series attachment end on outside of clamp ears and tighten bolts to minimum
required torque of 40 ft.lbs.
078 is the preferred assembly component for use with the 410 - see drawing.
FEATURES
* UL .Horizontal Load Rating: 1-3 pipe size = 500#
4-8 pipe size = 2015#
* Made with 1/2 bolts to conform with sway brace fittings.
ORDERING - Part #, pipe size and finish.
Spectlic AFCONproducts are exclusively designed to be compatible ONLY with ollter .4 FCON products including parts and fasteners, resulting in a listed sway brace, restrainer or hunger assembly. Be advised the following warranty restriction will apply. DISCLAIMER. AFCON will NOT warrant against the failure of its products when used in combination with other products, parts or systems . not nisnalaciutedorsold hyAFCON. ,-iFCOsVsltall NOT be liable under any curcutcssacces whatsoever forany direct orindirect, incidental orconsequential damages stf any kind, including but not limited to loss olbusiness or profit, when non-AFCON products have been, or are used.
5/08
9
P.O. Box 3365 South El Monte, CA 91733 626.444.0541 Fax 626.444.3887 www. Afcon.org
077
ATTACHMENT FITTING
LOCKING
SIZE - 1 and 11/4 inch bracing pipe.
Use in combination with 1 thru 8 inch AFCON sway brace assemblies.
MATERIAL - Carbon Steel, Ductile Iron or S.S. (Type 304).
FINISH - Plain or E.G.
LISTING/APPROVAL -
203A-EX2625
Listed only for use with other AFCON bracing products.
OSHPD OPA-0601 See Website.
FUNCTION - Structure attachment fitting of a sway brace assembly, consisting
additionally of AFCON 001 thru 040 sway brace fitting and brace element
forming a complete sway brace assembly.
INSTALLATION - Per NFPA 13 . Listed for use with NFPA 13 fastener
tables. For installation on H-beam or steel web joist see AFCON 085 thru 088
sway brace adapters.
ASSEMBLY - Insert brace pipe into fitting against the pivot bolt. Tighten set
bolt until head contacts bracket.
FEATURES
* UL Horizontal Load Rating: 2015#, All Sizes
* Swivel design allows attachment at any angle.
* Visual inspection, proper installation when set bolt head contacts bracket.
* 17/32" Fastener hole, larger hole available.- Consult factory.
ORDERING - Part #, pipe size and finish.
Specific AFCONproducts are exclusively designed to be compatible ONLY with otherAFCONproilxcls including parts and fasteners, resulting in a listed sway brace, restrainer or hanger assembly. Be advised the following warranty restriction will apply. DISCLAIMER. AFCON will NOT warrant against the failure of its products when used in combination with other products, parts or systems not manufactured or sold by AFCON. AFCON Shall NOT be liable under any circumstances whatsoever for any direct or indirect, incidental or consequential damages of any kind, including but not limited to lass olbusinesu or profit, when nun-A FCON products have been, or are used.
1/09
> ~,Vgggz S P.O. Box 3365 South El Monte, CA 91733 626.444.0541 Fax 626.444.3887 www. Afcon.org
001/020
SWAY BRACE
FITTING -MODEL E
Part #077
SIZE - Sprinkler systems pipe: 1" thru 8" Steel Schedule 7 thru 40.
SIZE - Sway brace assembly pipe: Steel 1" or 1 1/4" Schedule 40
MATERIAL - Carbon Steel or S.S. (Type 304).
FINISH - Plain, E.G., and H.D.G.
LISTING/APPROVAL -
C®OS 203A-EX 2625
Listed only for use with other AFCON bracing products.
OSHPD OPA-0601 See Website.
PATENT - No. 3,570,794
FUNCTION - Per NFPA 13. Sway brace fitting of a lateral sway brace assembly.
To foni a 4-way brace on vertical piping, arrange adjacent lateral sway braces.
INSTALLATION - Per NFPA 13. Place Model E over pipe to be braced. Insert
brace pipe through MODEL "F!' under channel bracket, leaving I" minimum
extension beyond. Tighten hex nuts until gage spring lays flat or torque to 65 in-lbs. ASSEMBLY - Per NFPA 13. Combine with AFCON 70 series structure sway brace fitting and pipe brace element forming a complete sway brace.
FEATURES
* UL Horizontal Load Ratings for all sizes Sch. 10 thru 40 = 2015# * UL Horizontal Load Ratings for 1" thru 4" Sch. 7 = 655# * UL Horizontal Load Ratings for 6" Sch. 7 = 1500# * Visual inspection, proper installation when gage spring lays flat.
ORDERING - Part #, pipe size to be braced, brace pipe size and finish.
Specific .4FCON products are exclusively designed lobe compatible ONLY with other AFCOsV prod acts including parts and fasteners, resulting ma listed sway brace. resirarncr or banger assembly. Be advised the following warranty restrict ion will apply. DISCLAIMER. .4FcOlVwill NOT warrant against Site hiSser of its products when used in combination ouSt other products, pant or systems 'lotrrranaihcrured or sold by .4FCUN. ,.lFCONshall NOT be liable under any circumstances whatsoever for any direct lit indirect, incidental or consequential datnages of any blvd including but not fruited to loss of brrai,ress or profit, when non-AFCON products have been, or are used.
1/08 L,___
/LEAJSMIc
;Bujldex
1349 W Bryn Mawr Ave
Itasca, IL 60143
800-BUILDEX
www.itwbuildex.com
Restraint Slnrope and Size Nn:r,)Je 0r 102 ct°200 _-A
Rods Rods ', .: [18 in. :.0'07 0.075 0.C1.3 1,0 2.5
,a!] thread) :: 1 0.129 0.101 0.8"': 1,7 2, .....
Rods 3/8 in. 0.11 0.094 0.8 1,6 2.4 3.1
(threaded at ends only) 1/2 in. 0.196 0.125 1.0 2.1 3.1 4.2
'Reference: NFPA 13,(2010)
Less on site material
Er)
Installation Toot
XPlT Universal XPress le Tool
(Part No. 8194910)
For 3/8" Hod .SXP 20 for 3/8" Rod
Structural attachment for installation of branch/end of line restraint
using 3/8" all thread (299' OD) or end thread rod (.374" OD).
Designed for use in metal deck rangig from 22 ga. through 1/8"
in low slope or pitched roof designs (12/12). The SXP 20 may be
used to attach short length of rod to eliminate seismic bracing per
NFPA 13, 9.3.5.3.8, (2007).
SXP 35 for 318" Rod
Structural attachment for installation of branch/end of line restraint
using 3/8" all thread (.299" 00) or end thread rod (.374" OD).
Designed for use in steel purlin ranging from 16 ga. through 1/8'
in low slope or pitched roof designs (12112), the SXP 35 may be
used to attach short length of rod to eliminate seismic bracing per
NFPA 13, 9.3.5.3.8, (2007).
For 1/2" HeEl
SXP 2.0 for 1/2" Rod
Structural attachment for installation of branch/end of line restraint
using 1/2" all thread (.405' OD) or end thread rod (.500' OD). Designed
for use in metal deck ranging from 22 ga. through 1/8" in low slope or
pitched roof designs (12/12).
SXP 3.5 for 1/2" Rod
Structural attachment for installation of branch/end of line restraint
using 1/2" all thread (.405" OD) or end thread rod (.50000). Designed
for use in steel purlin ranging from 16 ga. through 1/80 in low slope or
pitched roof designs (12/12).
15JiwIveIs 1o'
) .45010 ensure°
Moor
91,
W :taont,
Restrained Pipe Size: Schedule 10 or Schedule 40 pipe 2" or less
Max length of Restraint Material: See Maximum Horizontal Loads table below
Maximum Angle: 450
Material: Carbon Steel
Screw Description: 1/4-20 x 1-1/8" with expandable sleeve
Finish: Electro-zinc
Testing: Tested to GR-63-CORE Standard for performance in structural steel in
seismic restraint applications as outlined for use in NFPA 13)2007),
9.3 at an independent test lab. The calculated force used for the testing
was equal to that found in a Zone 4 and an 8.4 Richter scale seismic event.
Listing: UL 203 listed as pipe hanger
- Perpendicular to structural member - 4' Schedule 40 Pipe
- 45' off vertical - 2-1/2" Schedule 40 pipe
UL 203A Pending
Installation: Must be installed with UXPIT Tool (Part No. 8194910); c YL us pre-drilling required. LISTED
Restrained Pipe Size: Schedule 10 or Schedule 40 pipe 2" or less
Max length of Restraint Material: See Maximum Horizontal Loads table below
Maximum Angle: 450
Material: Carbon Steel
Screw Description: 1/4-20 x 1-1/8" with expandable sleeve
Finish: Electro-zinc
Testing: Tested to GR-63-CORE Standard for performance in structural steel in
seismic restraint applications as outlined for use in NFPA 13(2007),
9.3 at an independent test tab. The calculated force used for the testing
was equal to that found in a Zone 4 and an 8.4 Richter scale seismic event.
Listing: UL 203A Pending
Installation: Must be installed with UXPIT Tool (Part No. 8194910); pre-drilling required.
V '
\UO V Feres
SCaCIOr Guide Structural attachment and • Dogs not require use of a
restraint component combined retaining nut.
ready for selected rod. -
.1.i sic-n
-
Quick and easy installation 294922 SXP 318" 22a Metal Do 25 5
Access to the back ot,tastener 8272957 SXP 20 1/2" 22 ga I/S Metal Deck 25 125
not required Made in USA. 8205922 SXP.. 3/8" 16 ga 1/8" Parlin 25 125
Benefits 0271957 SXP 3.5 1/2' 16ga 1/8 Purlin 25 125
Reduced installation cost. • Less material coordination.
. Design flexibility. Maximum fEorzontaI Leads for Bestrut_ Aesthetically pleasing.with 300, and 400 11 ume Rod Lengle tar Or/if
For 3/8" Roil . SH-TEK 50 for 3/8" Rod
Structural attchment forinstallation of branch/end of line restraint using 3/8" Restrained Pipe Size: Schedule 10 or Schedule 40 pipe 2" or less
threaded rod (:299" 00) or end thread rod (.374" OD). Designed for use in bar Max length of Restraint Material: See Maximum Horizontal Loads table below
joist, I-beam alti hollowstructural steel ranging from 1/8" to 1/2" in low slope or Maximum Angle: 45"
pitched roof designs (12/12). This product maybe used to attach short length of Material: Carbon Steel
rod to eliminate seismic bracing per NFPA 13, 9.3.5.3.8, (2007). Screw Description: 12-24 X 1-5/8" Teks0 5 milled point
Finish: Electro-zinc (cap)
Climaseal' (fastener) The SH-TEK 50mode1 provides upper structural attachment in a wide range
Testing: Tested tsGR-63-CORE Standard for performance in structural steel in seismic of steel thickfresses, from 1/8 through 1/2". This fastening system provides a restraint applications as oallined for use in NFPA 13(2007), 9.3 at an independent
secure and economical attachment to the structure. test lab. The calculated force used for the testing was equal to that found in a
Zone 4 and an 8.4 Richter scale seismic event.
Listing: UL 203 listed as pipe hanger
- Perpendicular to structural member —4" Schedule 40 pipe
- 45" off vertical — 2-1/2" Schedule 40 pipe
UL 203A Pending
Installation: Must be installed with #14 SN Nut Driver (ORANGI) (Part No. 8273910) &US
For 1/2" Rod ' LISTED
SH-TEK 5.0 for 1/2" Rod Restrained Pipe Size: Schedule 10 or Schedule 40 pipe 2" or less
Structural attachment for installation of branch/end of line restraint using 1/2" Max length of Restraint Material: See Maximum Horizontal Loads table below threaded rod (405 OD) or-end thread rod (.500 OD). Designed for use in bar
joist, l-beam'and hollow structural steel ranging from 1/8" to 1/2" in low slope or Maximum Angle. 45
Material: Carbon Steel pitched roof designs (12/12). Screw Description: 12-24 X 1-5/8" Teks0 5 milled point
Finish: Electro-zinc (cap)
The SH-TEK 5.0 model provides upper structural attachment in a wide range Climaseal (fastener)
of steel thicknesses, from 1/8" through 1/2". This fastening system provides a Testing: Tested to GR-63-CORE Standard for performance in structural steel is seismic
restraint applications as ou8ined for use in NFPA 13(2007), 9.3 at an independent secure an economical attachment o e structure. test lab. The calculated force used for the testing was equal to that found is a
Zone 4 or an 8.4 Richter scale seismic event.
In Listing: UL 203A Pending
45010 BUSHt0 Installation: Most be installed with #14 OH Nut Driver (1)/dANCE) (Part No. 8273910)
" proper
ST'
nfl
Structural $t rntllowsmurt.uraISt
wres citnth
Structural attachment and Does not require use of v Model .d e mum — l0ani; A out or Box Ory
restraint component combined, retaining nut.
ready, for selected rod. 689 SH-TEI l(# Structural Steel" 125
Quick and easy installation, 8270957 SH-TEK 50 1/2" 1/8" 1/2" Structural Steel" 25 125
No pre-drilling.
* Beam, Bar Joist Hollow Structural Steel i • Made n USA.
Access to the back of fastener not required. Fi1aXIuiU01 Horizontal Loads for Restraint
with /r-100,200,30Q, and 408 i. MxximurnLength for t)./ I Benefits Rsxintohie and Sizu A"E_Aren2/ IC0 I r co I r
Reduced installation cost Lesson site material (" ' (. I - a Rods .' , 07 , . Reduced material coordination Aesthetically pleasing (all thread) 1/2 in 0.129 0,101 08 1.7 25 34
Rods 3/8 in. 0.11 0.094 0.8 1.6 2.4 3.1
Installation Tool (threaded at ends only) 1/2 in 0.196 0.125 10 21 31 42
,.. • #14 SH Nut Driver (ORANGE.) "Reference: NFPA 13,(2010)
(Part No. 8273910)
O 1M \Lt
i I,
cos1 oV 111
"ei %-_2
Odin
?atet
/ Ii
SE Rae ar er
When rI-ClIE4
. angle sh:uIijt
excee:45
Steel - rW, Descrotion Rod Size Pipe Size ______Test Load Box Qtf Thickness
£294922 SXO K So ye X-Ps1-2O 3/8 6 - 3/4- 21 /2-202s 750 lbs. 25 125
- x,9x22 SXP35 Sve X-Fess 35 38 6 34-35' 6- 12Sx 1250 lbs 25 125
iFi910 .UXPI IT Universe S-Press ItToal inckdes. £0 Rexever, Hex WreFrh, an 2564 Drill £1 - .010 RXPIT ReCo Socket For 8151910
1/52010 XPD 25104 0Bt 5. 4 4 . S Pipe Hanger for XTreme Vinsta.s in-second.s saves 4/use in applications where No retaining nut required.
O Roof Pitches, time .&- installation costs. • easy access to the back.
89° ir 31 rhr
•. of the installed fastener is
45° in metal deck for • I.. • - • iprohibted •
12/12 :itch . . i!i... IrrBuiIdex JL Tested to comply with NFS°. 303-BUILDEX www.itwbuildexcom
4 PatentNo.
(XP)"m,
6,939,881
Parent Pending
for
)SXP)
or
Patent Pending ,
roof it
Product Features
The Sammy X-Press expands to provide
direct vertical attachment in:
- Metal Deck (22-16 gauge)
- Z-Purlin (18-16 gauge)
The Sammy X-Press Swivel allows you
to hang plumb in extreme roof pitches:
- 89" in Z-Purlin
- 45" in metal deck for 12/12 pitch
The Sammy X-Press Sidewinder expands
to provide horizontal attachment in:
- 16 ga - 3/16 steel - puntS, tubular
steel.
Installs in seconds, saving time &
installation costs.
Use in applications where access
to the back of the installed fastener is
prohibited. ie. metal roof deck, tubular
steel, or vapor barrier fabric.
Less jobsite material needed.
No retaining nut required.
Provides design flexibility
— ....."wi- -r-"--"---- ---"" -- ."•"" .............
te rj .(( •• fOr r
1/4 8181922 XP 200 X-Press 200 1146 (22 gal 1 umine
250 (Lunninare) 0561, 125" 25 125 Metal Deck
850/ Pipe) 940 (2 Pipe) 027
. 318 8150922 OP 20 X Pie s 20 1146 (22 gal /85 (mi-Si e /475 (4 Pipe) 250 (Luminal~e~ 027 125 25 125 Metal o
283 (Condull & CaGI '056'
1250(3W Pipe) 060
3/8 8153922 XP 35 X-Press 35 1783 (16 gal .125 25 125 Puntin 250(L) 1475
-
416 )Cssdsit& Cable) 056"
750 )2 Pipe)
3/ 294922 XP 20 w I 0-Pr 20 1061 (22
ca
I'O vertical (Luminairv)
GD @4 (Luminary) 8' (2 Pipe) 027 /25" 25 125 Meld Deck 829 (45' Off Veirfjca;~ 263 verkal(ConduiIC b )
23,3 10145 (Conduit & i- 0°)
1258 (3W Pipe)
82. "car 3/8 8295922 SXP 35 Swivel X Press 35 11558
250 vertical (Luminaine)
80 @ 00" (Luminaine) 635 (2 Pipe) .060 125 25 125 Purlin Off Vertical) 500 vertical (Conduit & Cable)
333 @80" (Conduit & Cable) [[ C Pour Stfuct Metal
0 2 XP 20 S mop 7-Pie s 20 ii (22 x) P50 (2'. ) 25 125 RI ID i-P Par II \0 3 P (I I ( eck
1250 (3W Pipe)
3)8" 8293957 SW)(P 35 Sidewinder X-Press 35 1798 (16 ga) 80 (Luminaire) .000" .125" 25 125 Purlin
416 (Conduit & Cable)
Pre-Pour Structural Concrete @3000 psi Post-Pour Range II LWC:5 35 PCF tibet 10(
-.uxPlT
Pa~~,t Pending
- 1r 1n :;1
510" "10
u2/jti I?La°• . 8104910 UxP X-Pr
81 9 0 io R14P(T Re/no Socket for 8151910 1
0(922(0 XPDB 20104 Dnt( 8I 1
'T .Cl d,de, Sd - a Ci P He, Wrench and 2 u4 U ii 0'
40
To watch a video demonstration of the Sammy X-Press, visit htfp //va-wwsammysuperscrewcom/sammyxpi-ess htnn
MADE INUS.A \'/
B/with
1!p
f Fk
H ce
p p
e g
Quick thread attachment—
ideal for 1 sided forming
coil rod on job
2 dia ters (1/2' and 3/4")
O Lipped anchor body keeps
anchor flush
Easy installation
Keeps all rods same length
Easy inspection
Available in carbon steel,
18-8 and 316 stainless steel
Coil Thread Apc'ho1\
0
chor
Drop-In, Shell-Type Anchors—
SPECIFIED FOR ANCHORAGE INTO CONCRETE
Drop-in, shell-type anchors feature an internally threaded, all-steel shell with expansion cone insert and flush
embedment lip. Anchors are manufactured from zinc-plated carbon steel, 18-8 stainless steel and 316 stainless steel.
=
Anchors should be installed with carbide tipped hammer drill bits made
I Jfl in accordance to ANSI B212.15-1994 specifications.
Anchors should be tested to ASTM E488 criteria and listed by ICC-ES.
Anchors should also be listed by the following agencies as required
by the local building code: UL, FM, City of Los Angeles, California State
fiulti-Set II Drop In Anchors Fire Marshal and Caltrans.
Internally
Threçzded Heavy-
Duty Anchoring
Systems
Depth Charge Stop Drill
and RX Drop-In Anchors
Ideal for HollowCore, Pre-Cast Plank
and Post Tension Slabs
TM
Stop Drill
D Optimized for use in hollow-"\
cofe, pre-cast plank and
post-tension slabs
0 Lip keeps anchor flush
during installation
installation
irRed Head'
Cuff our toll free number 800-899-7890 or visit our web site for the most
current product and technical information an www.itwredhead.com L RED HEAD 65
RX.Drop-In
Ahhor
See page 68 for kits
II.A.RrZ
-
p 7 7 S 7 II.
USER''APPLICATION DRILL BIT THREAD EMBEDMENT QTY/WT QTY/WT BASE CORROSION DROP-IN PART SETTING:P
ER
TYPE MATERIAL RESISTANCE ANCHOR NUMBER TOOL DIA. DEPTH MIN. HOLE PER BOX PER
:INCH LEVEL TYPE PART In. (mm) In. (mm) DEPTH lbs. MASTER (TN
NIJMBER In. (tjL,, lbs.
HVAC/Pire 5p.iiii'Iei "Solid Low RM RM-14 RT-114 1/4 -20 3/0 (9.5) 3/8 (9.5) 1 (25.4) 100/ 2.6 1000/ 2
concrete! RM-38 91-138 3/8-16 1/2 (12.7) 1/2 (12.7) 1-5/8 (41.3) 50/ 3.4 500/ 36
lightweight RM-12 RI-112 1/2 -13 5/8 (15.9) 3/4 (19.1) 2 (50.8) 50/ 5.8 400/ 49
fill deck RM-58 RT-158 5/8 -11 7/8 (22.2) 1 (25.4) 2-1/2 (63.5) 25/ 7.8 125/ 41
RM-34 91-134 3/4 -10 1 (25.4) 1-1/4 (31.8) 3-3/16 (81.0) 25/ 11.9 100/ 49
Hollow-core Low X
-
RX-38
--
RTX-138 3/8"-16
--
1/2 (12.7) 3/8 (9.5) 9.1 i00/3.5 1000ijn
-
. pre-cast RX-12 RTX-112 1/2 -13 5/8 (15.9) 1/2 (12.7) 1 (25.4) 50/ 3.0 500/ 31
or Post-
tension
- Solid Medium SRM'"" SRM-14 RI-114 1/4-20 3/8 (9.5) 3/8 (9.5) 1 (25.4) 100/ 2.7 1000/ 28
concrete! 18-8 5.5. SRM-38 91-138 3/8-16 1/2 (12.7) 1/2 (12.7) 1-5/8 (41.3) 50/ 3.4 500/ 36
lightweight SRM-12 91-112 1/2 -13 5/0 (15.9) 3/4 (19.1) 2 (50.8) 50! 6.0 400! 50
fill deck SRM-58 91-158 5!8"-11 7/8 (22.2) 1 (25.4) 2-1/2 (63.5) 25! 18.0 125/ 42
SRM-34 RT-134 3/4-10 1 (25.4) 1-1/4 (31.8) 3-3/16 (81.0) 25/ 12.0 100! 50
Solid High SSRM* SSRM-38 RT-138 3/8-16 1/2 (12.7) 1/2 (12.7) 1-5/8 (41.3) 50/ 3.4 500/ 36
concrete 316 5.5. SSRM-12 91-112 1/2-13 5/8 (15.9) 3/4 (19.1) 2 (50.8) 50/ 6.0 400/ 50
Concrete Contractor, Solid Low CL-Coil CL-12 81-112 1/2-6 5/8 (15.9) 3/4 (19.1) 2 (50.8) 50! 5.7 400/ 47
General CoO(actor, Highway concrete Threaded CL-34 81-134 3/4-4.5 1 (25.4) 1-1/4 (31.8) 3-3/16 (81.0) 25! 11,9 100/ 49
• 'T
Concrete Cuttios' Solid Low RL RL-14 81-114 1/4-20 3/8 (9.5) 3/8 (9.5) 1 (25.4) 100/ 2.6 1000! 28
Sawing Contractor/Misc. Metal concrete! (win lip) RL-38 81-138 3/8-16 1/2 (12.7) 1/2 (12.7) 1-5/8 (41.3) 50/ 3.4 500/ 36
lightweight RL-12 RT-112 1/2 -13 5/8 (15.9) 3/4 (19.1) 2 (50.8) 50! 5.8 400/49
- fill deck RI-58 81-158 5/8"- 11 7/8 (22.2) 1 (25.4) 2-1/2 (63.5) 25! 7.8 125141
: RL-34 RT-134 3/4" -10 1 (25.4) 1-1/4 (31.8) 3-3/16 (81.0) 25! 11.9 100! 49
.'
1 settingtool per maser carton. ** For continuous extreme low temperature, use stainless steel.
ohcharg.TM
PARFN
DESCRIPTION I DRILLING I Stop Drill
siTURE BENEFITS DEPTH
Shoulder prevents over drilling t... No lost time or energy drilling farther
3 DCX-13 Depth Charge Stop Drill 3/8" (
8
Less likely to hit reinforcing steel or than necessary
DcX-llj 1'' Depth Charge Stop Drill I 1' post-tension cable in concrete 13, Anchor is set at a specified depth, does
not drop too far into hole
imwRedHeatl
Call our toll free number 000-899-7800 or visit Our web site for the most
current product and technical rIo,rnotion or Www.jtwredh!ud,09sp 4 RED HEAD 67
Ultimate Tension and Shear Values (LbslkN) in Concrete*
MIN.EMBEDMENT ANCHOR ____________________ TENSION Lbs. (kN) SHEAR Lbs. (kN) 7 ANCHOR
DIA. DEPTH TYPE f'c = 2000 P51 f'c = 4000PSI f'c = 6000 PSI f'c>2000 PSI
, (mm) In. (mm) (13.8 MPa) (27.6 MPa) (41.4 MPa) (13.8MPa)
.8 (9.5) 1 (25.4)
RM, RL
or CL-Carbon
1,680 (7.5) 2,360 (10.5) 2,980 (13.3) 1,080 (4.8)
3/8 (9.5) 1/2 (12.7) 1-5/0 (41.3) 2,980 (13.3) 3,800 (16.9) 6,240 (27.8) 3,160 (14.1)
1/2 (12.7) 5/8 (15.9) 2 (50.8) or
SRM-18-8 5.5. or
3,300 (14,7) 5,840 (26.0) 0,300 (36.9) 4,500 (20.4)
5/8 (15.9) 7/8 (22.2) 2-1/2 (63.5) SSRM-316 S.S. 5,500 (24.5) 8,640 (38.4) 13,020 (49.0) 7,440 (33.1)
3/4 (19.1) 1 (25.4) 3-3/16 (81.0) 8,280 (36.0) 9,400 (42.2) 12,260 (54.5) 10,480 (46.6)
Allowable values are based upon 1 4 to 1 safety factor. Divide by 4 for allowable load values.
For continuous extreme low terxperalure applications, use stainless steel,
1TtT1!1II Ultimate Tension and Shear Values (Lbs/kN) in
Lightweight Concrete*
-. . - BOLT I ANCHOR MINIMUM ANCHOR LIGHTWEIGHT CONCRETE LOWER FLUTE OF STEEL DECK WITH
lIlA. 018. EMBEDMENT TYPE f'c=3000 PSI (20.7MPa) LIGHTWEIGHT CONCRETE FILL
In. (mm) In. (mm) DEPTH f'c = 3000 P51(20.7 MPa)
TENSION SHEAR TENSION SHEAR In. (mm)
Lbs. (kN) Lbs. (kN) Lbs. (kN) Lbs. (kN)
1/4 (6.4) 3/8 (9.5) 1 (25.4)
RM, RL
or CL-Carbon or
1,212 (5.4) 1??? 1?? P7? 7?? 1??? 771
3/8 (9.5) 1/2 (12,7) 1-5/8 (39.7) 2,034 (9.0) 4,420 (19.6) 3,340 (14.9) 4,420 (19.6)
5/8 15,9) 2 (50.8) 2,742 (12.2) 5,640 (25.1) 3,200 (14.2) 4,940 (22.0)
SSRM-3165.S.
SRM-18-8 S.S.nr
5/8 (15.9) 7/8 (22.2) 2-1/2 (63.5) 4,242 (10.9) 10,440 (46.4) 5,960 (26.5) 5,840 (26.0)
3/4 (19.1) 1 (25.4) 3-3/16 (81.0) 5,382 (23.9) 15,780 (70.2) 8,180 (36.4) 9,120 (40.6)
Allowable values are based upon a 1 to 1 safety factor. Divide by 4 for allowable load values
Combined Tension and Shear Loading-for Multi-Set Anchors
Allowable loads for anchors subjected to combined shear and tension forces are determined by the following equation:
(PsIPt)°°+ (Vs/Vt 1
Ps = Applied tension load Vs = Applied shear load Pt = Allowable tension load Vt =Allowable shear load
Part No, Description
RX-38 3/8" drop-in using 1/2" drill bit
RTX-138 . Setting Tool
DCX-138 Depth Charge Stop Drill
RX-38KlT . Contains: 1,000 RX-38 Anchors, 5 RTX-138 Setting Tools and
2 DCX-130 Depth Charge Stop Drills
Part No. Description
RX-12 1/2" drop-in using 5/8" drill hit
RTX-112 Setting Tool
DCX-112 Depth Charge Stop Drill
RX-12K1T
____________
Contains: 500 RX-12 Anchors, 3 RTX-1 12 Setting Tools and
1 OCX-i 12 Depth Charge Stop Drill
68 ' RED HEAD irRed Head
Call surtsll free number 800-899-7890 or visit ourweb site for thersoss
current product and technical information at www.itwredhead.com
Call our roll free number 000-099-7890 or visit our web site for the most
current product and technical information at www.itwredliopd.com
mRed Head'
,RED HEAD 69
S
Recommended Edge and Spacing Distance Requirements*
BOLT DRILL BIT EMBEDMENT ANCHOR EDGE DISTANCE MIN. EDGE SPACING MIN. ALLOWABLE
DIA, SIZE DEPTH TYPE REQUIRED TO DISTANCE AT WHICH REQUIRED TO SPACING
In. (mm) In. (mm) In, (mm) OBTAIN MAX. LOAD FACTOR APPLIED OBTAIN MAX. BETWEEN ANCHORS
WORKING LOAD =80 FOR TENSION WORKING LOAD LOAD FACTOR APPLIED
In. (mm) =70 FOR SHEAR In, (mm) =80 FOR TENSION
In. (mm) =35 FOR SHEAR
In. (mm)
1/4 (6.4) 3/8 (9.5) 1 (25.4)
RM, RL
or CL-Carbon
1-3/4 (44.5) 7/8 (22.2) 3-1/2 (88.9) 1-3/4 (44.5)
3/8 (9.5) 1/2 (12.7) 1-5/8 (41.3) 2-7/8 (73.0) 1-7/16 (36.5) 5-11/16 (144.5) 2-7/8 (73.0)
1/2 (12.7) 5/8 (15.9) 2 (50.8) or 3-1/2 (88.9) 1-3/4 (44,5) 7 177.8) 3-1/2 (88.9)
SRM-18-8 S.S. or
5/8 (15.9) 7/8 (22,2) 2-1/2 (63.5) SSRM-316 5,5. 4-3/8 (111.1) 2-3/16 (55.6) 8-3/4 (222.3) 4-3/B (111.1)
3/4 (19.1) 1 (25.4) 3-3/16 (81.0) 5-5/8 (142.9) 2-13/16 (71.4) 11-3/16 (284.2) 5-5/8 (142.9)
Spacing and edge distances shall be divided by 0.75 when anchors are placed in structural lightweight concrete. Linear interpolation may be used for intermediate spacing and edge distances.
b, :mZ1
_____7
EMBEDMIENT
Ultimate Tension and Shear Values (LbslkN) for RXseries
(314" and 1" Embedment)*
BOLT DIA. DRILL BIT 2500 PSI (17.2 MPa) CONCRETE 4000 PSI (27.6 MPa) CONCRETE HOLLOW CORE
In. (mm) SIZE ) TENSION SHEAR TENSION SHEAR TENSION SHEAR
(mml Lbs. (kN) Lbs. (kt4) Lbs. (kN) Lbs. (kN) Lbs. (kN) Lbs. (kN)
3/8 (9.5) 1/2 (12.7) 9.1) 1,571 (7.0) 2,295 (10.2) 1,987 (8.8) 2,903 (12.9) 1,908 (8.5) 2,401 (10.7)
1/2 (12.7) 5/8 (15.9)5.4) 2,113 (9.4) 2,585 (11.5) 2,673 (11.9) 3,270 (14.5) 2,462 (11.0) 2,401 (10.7)
* The tabulated valves are for OX anchors installed at a minimum of 12 diameters on center and minimum edge distance of 6 diameters for 100 percent anchor efficiency. Spacing and edge distance may be reduced to 6 diameters spacing and 3 diameter edge
distance provided the values are reduced 50 percent. Linear Interpolation maybe used for intermediate spacings and edge margins.
Allowable values are based upon a4 to 1 safety factor. Divide by 4 for allowable lead values.
J.
i i179jIi Anchoring Overhead in 3000 PSI 2060uge -+ ' 'a,, RXDrop-Io
ii n m • Metal Deck Installed in Lightweight Concrete On Metal Deck Lower Flute Upper Flute
ANCHOR DRILLHOLE EMBEDMENT 3000PSI(20,7MPa)CONCRETE
DIAMETER In. (mm) ULTIMATE TmJUnM LOAD I At i rasmani r tAtnovikir I nun
In. (mm) Lbs. (kN) Lbs. (kN)
RX38 Drop-In 1/2 (12.7) 3/4 (19,1) Upper Flute 1,410 (6.3) 353 (1.6)
Lower Flute 1,206 (5.4) 301 (1.3)
Allowabie values are bused upon a 4w 1 safety factor. Divide by 4 for allowable lead values.
5)VALVES
9
UNITED Biss WORKS, INC.
714 S. Main St., Randleman, NC 27317 1S0001
Tel: 800-334-3035 Fax: 800-498-4696 www.ubw.com
Model 125SUL Globe Valve
Soft Disc
'.- UL Listed for Fire Sprinkler Service at 250 WOG
200 WOG @ 180 1 Max
:1.0.0% Pressure Tested
Threaded Ends -Integral Seat
Rising Stem
Swivel Disc Holder
El
o .
MATERIAL LIST
NO. DESCRIPTION MATERIAL
-
1 Hex Nut Steel
2 Hand Wheel Aluminum
3 Packing Nut Brass
4 Packing Graphite Non-Asb.
Bonnet (1/2 1")
Bonnet (11 ' —2")
Brass
Bronze
6 Stem & Disc Assm. Brass
7 Disc BunaN
Body . Bronze
Size 'A" 3/4 1" 1 ¼" 1 '/2" 2"
A 2.22 2.47 2.97 3.56 4.06 4.69
B 2.03 2.38 2.75 3.00 3.72 3.72
C (closed) 3.38 3.50 4.25 4.75 5.50 5.50
Ship Wt. (lbs.) 0.69 0.94 1.76 2.50 3.26 5.32
Qty. Unit Pack 12 6 6 4 2 2
Qty. Per Case 72 60 36 24 12 12
UNITED BRAss WoRKs, INC. If 714 S. Main St., Randleman, NC 27317
Tel: 800-334-3035 Fax: 800-498-4696 www.ubw.com IS09001
REGISTERED COMPANY
Model 126SUL Angle Valve
Soft Disc
\—/ CL Listed for Fire Sprinkler Service at 250 WOG
200 WOG @ 180 'Max
100% Pressure Tested
Threaded Ends
Rising Stem • Integral Seat
MATERIAL LIST
NO, DESCRIPTION MATERIAL
Hex Nut Steel
2 Hand Wheel Aluminum
3 .. Packing Nut Brass
4 Packing Graphite Non-Asbestos
5. Bonnet (Yz" - 1")
Bonnet (1 '/" - 2")
Brass
Bronze
6 .Stem& Seat Assembly Brass
7 Disc BunaN
8 Body Bronze
Size Y2" 3/4" 1" 1 '/4" 1 1/2 2"
A 1.03 1.22 1.47 1.75 2.00 2.34
B 2.03 2.38 2.75 3.00 3.72 3.72
C (closed) 3.13 3.25 4.38 4.50 5.25 5.63
Ship Wt. (lbs.) 0.69 0.94 1.76 2.50 3.26 5.32
Qty. Unit Pack 12 6 6 4 2 2
Qty. Per Case 72 60 36 24 12 12
S
-.
I TEST •
PusI.V • I,
V
- !1J ±
- r 1 V
,• p o
C
SIZE 1-114' 14 MCOEL 1000
-'- V
V
V - -.. : 1'..' •V
V
V
i - -
The AGF Manufacturing, Inc. Model 1000
TESTANDRAIN® provides both the test function aid
the express drain function for a wet fe sprin<ler
system.
The Model 1000 complies with the rsquirements of
NFPA-1 3, NFPA-1 3R, and NFPA-1 3D.
The Model 1000 TESTANDRAIN® is a compact
single handle ball valve which includes a tamper
resistant test orifice and integral tamper resistant
sight glasses, and is 300 PSI rated.
Available in a full range of sizes from 34" to 20 NPT
and BSPT, with all specifiable orifice sizes W' (2.8K).
7A6' (4.2K), ½" (5.6K), 17/32" (8.0K), %h' (11.2K, ELO),
3/4" (14.0K, ESFR), and K25 as required by NFPA 13.
2007 Edition (see reverse).
The orifice size is noted on the indicaor plate and
the valve features a tapped and plugged port for
system access. V
A locking kit is available and can be crdered with
the valve to provide vandal resistance. or prevent
unintentional alarm activation.
--
MODEL 1000 - FRONT VIEW, VERTICAL INSTALLATION
FROM BRANCH
SYSTEM ACCESS PORT
—
STREET EL
STREET EL OR PIPE TO DRAIN —
TO DRAIN I
RIGHT HAND/STRAIGHT INSTALATION
TESTANDRAIN is a registered trademark of AGF Manufacturing Inc.
FRONT VIEW - HORIZONTAL INSTALL
MATERIALS
Handle: Steel
Stem: Rod Brass
Ball: C.P. Brass
Body: Bronze
Valve Seat: Impregnated Teflon®
Indicator Plate: Steel
Handle Stop: Steel
APPROVALS
UL and ULC Listed (EX4019)
FM Approved
NYC-BSA No. 720-87-SM
A
I
TO
o-
TO DRAIN D
-
TO DRAIN -
1191
DIMENSIONS
Orifice Size Available: %, /i&, /2", 1742", ELO (5/8)*, ESFR (3/4)*, & K25-
SIZE A B C 0 E F G H
~ " 51/&' 1½" 23/16" 3 % " 3" ½ 113/16" 49/16 6 ½ " (128 mm) (37.5 mm) (57 mm) (93 mm) (86 mm) (46 mm) (117 mm) (162.5 mm)
51A6' llh" 2'&' 35/8' 3½" 113A6' 4W16" 6½" (128 mm) (37.5 mm) (57 mm) (93 mm) (86 mm) (46 mm) (117 mm) (162.5 mm)
11/4 57A6" 111/16 2'6" 41/4 35/16 115A& 59A6" 51,'"
(163 mm) (43 mm) (65 mm) (108 mm) (83 mm) (51 mm) (141 mm) (192 mm)
11/2 113/16 31/4" 51fl6' 3/8" 25/8 81/4 107/8" (163 mm) (45 mm) (81.5 mm) (127 mm) (99 mm) (67 mm) (207 mm) (274 mm)
67/16" 116" 31/i" 51/16 3/8" 2%' 81/4 107/8' (163 mm) (45 mm) (81.5 mm) (127 mm) (99 mm) (67 mm) (207 mm) (274 mm)
* Available on 11/4' to 2' size units only
** Available on 11/2" and 2" size units only
THE MODEL 1000 PROVIDES ALL OF THE FOLLOWING
From the 2007 Edition of NFPA 13
Chapter 8.16.2.4.1* Provisions shall be made to properly drain all parts of the system.
Chapter 8.16.2.4.2 Drain connections, interior sectional or floor control valve(s) - shall be provided with a drain
& 8.16.2.4.3 connection having a minimum size as shown in Table 8.16.2.4.2.
Chapter 8.16.2.4.4 Drains shall discharge outside or to a drain capable of handling the flow of the drain.
Chapter A.8.17.4.2 (Wet Pipe System) test connection is permitted to terminate into a drain capable of accepting full
flow.., using an approved sight test connection containing a smooth bore corrosion-resistant orifice
giving a flow equivalent to one sprinkler...
Chapter 8.17.4.2.2 The test connection valve shall be readily accessible.
Chapter 8.17.4.2.4 shall be permitted to be installed in any location.., downstream of the waterfiow alarm.
Chapter 8.17.4.3.1 (Dry Pipe System) a trip test connection not less than 1" in diameter, terminating in a smooth bore
corrosion-resistant orifice, to provide a flow equivalent to one sprinkler...
Chapter 8.17.4.3.2 The trip test connection... with a shutoff valve and plug not less than 1", at least one of which shall
be brass.
'usPt # 4741361 and OtIJ
- AGF Manufacturing Inc. Job Name:
I,A 100 Quaker Lane, Malvern, PA 19355
Architect: / . Phone: 610-240-4900
/1i: I Fax: 610-240-4906 Engineer: www.testandrain.com
Contractor:
6)GAUGE
Ll
The AGF Manufacturing, Inc. Model 7500 Pressure Gauge
is an FM Approved/UL Listed 31/2" gauge designed for use
on "wet" sprinkler systems. The AGF Model 7500 has been
designed to meet the requirements specified in NFPA 13,
2007 Edition Chapters 7.1.1.1 - 7.1.1.2, 7.2.1 - 7.3.1.3, 7.8.7,
8.16.1.2.2, and 8.17.3
SPECIFICATIONS
Range: 0-300 PSI (Inside)
0-2000 Kpa (Outside)
Accuracy: ±3-2-3%
Burdon Tube: Phosphor Bronze
Window: Polycarbonate one-
piece ring and crystal
Dial: Galvalume
Pointer: Aluminum, painted black
Case: PGE Xenoy® DX2735
Connection: Brass, 1/4" ANPT LM
DIMENSIONS 1.16
(
MAX-
0
0 3.46 IN
(MM) . -
OjJ-770 (98.6) )94.0)
.56S0 - (14.2)
.------ -1/4-1SANPT .44±04 l .39±03
The AGF Manufacturing, Inc.
Model 7600 ¼" 3-Way Globe
Valve is an FM Approved/UL
Listed valve designed to connect
the pressure gauge to the sprinkler
systems. The AGF Model 7600
has been designed to meet NFPA
13 System Attachments stating,
"...each gauge shall be equipped
with a shutoff valve and provision
for drainage."
MODEL 7500 PRESSURE GAUGE
WITH MODEL 7600 GLOBE VALVE
FT AGF Manufacturing Inc. Job Name:_____________________________ 100 Quaker Lane, Malvern, PA 19355
I• -i 1 Phone: 610-240-4900 Architect:—
Fax: 610-240-4906 Engineer:
L • • www.testandrajn.com
MADE IN U.S.A. Contractor:
--•• IThl?.
)1 1 T TESTANDRAIN®
r
M2511T
TESTANDRAIN°
M8000 COMMERCIAL RISERPACK®
M8000 RESIDENTIAL RISERPACK®
M801
0
El
ERCIAL RISERPACK®
THE MODEL 7500 PRESSURE GAUGE AND MODEL 7600 3-WAY GLOBE VALVE
ARE ALSO USED ON THE FOLLOWING AGF PRODUCTS:
TESTANDRAIN and RISERPACK are registered trademarks of AGF Manufacturing Inc.
7)DEVICES
0
U.S. Pat, No. 3921989 .Canadian Pat. No. 1009680
Other Patents Pending
Potter Electric, Rd., 1990
GENERAL INFORMATION
The Model VSR-F is a vane type waterfiow switch for use on wet
sprinkler systems. It is UL Listed and FM Approved for use on steel
pipe; schedules 10 through 40, szes 2" thru 8" (50mm thru 200mm).
LPC approved sizes are 2" thru 8" (50mm thru 200mm).
The unit may also be used as a sectional waterfiow detector on large
systems.
The unit contains two single pole, double throw, snap action switches
and an adjustable, instantly recycling pneumatic retard. The switches
are actuated when a flow of 10 gallons per minute (38 LPM) or more
occurs downstream of the device. The flow condition must exist for a
period of time necessary to overcome the selected retard period.
ENCLOSURE: The unit is thclosed in a general purpose, die-cast
housing. The cover is he.d In place with two tamper resistant screws
which require a special key for removal, A field installable cover
tamper switch is available as an option which may be used to indicate
unauthorized removal of the cover. See bulletin no. 5400775 for
installation instructions of this switch.
1•
:
(E)POTTER !_ 41
VS
'4!U
UL, ULC and CSFM Listed, FM and LPCB Approved, NYMIEA
Accepted, CE Marked
Service Pressure: Up to 450 PSI (31 Bi-\.R)
Minimum Flow Rate for Alarm: 10 GPM (38 LPM)
Maximum Surge: 18 FPS (5,5 mIs)
Contact Ratings: Two sets of SPDT (Form C)
15.0 Amps at 125/25OVAC
2.0 Amps at30VDC Resistive
Conduit Entrances: Two knockouts provided for 1/2 conduit
Environmental Specifications:
Suitable for indoor or outdoor use with factory installed gasket and
die-cast housing.
NEIvliA4IIP54 Rated Enclosure - use with appropriate conduit
fitting.
Temperature Range: 40°F/120°F, 4,5°C/49°C
Non-corrosive sleeve factory installed in saddle.
Caution: This device is not intended for applications in explosive
environments.
Sizes Available: Steel Pipe schedules 10 thru 40, sizes 2" thru 8'
BS 1387 pipe 50mm thru 200rnm
Note: For copper or plastic pipe use Model V SR-CF.
Service Use:
Automatic Sprinkler NFPA-13
One or two family dwelling NFPA- I 3D
Residential occupancy up to four stories NFPA-13R
National Fire Alarm Code NFPA-72
Optional: Cover Tamper Switch Kit, Stock No. 0090018
INSTALLATION: See Fig.2
These devices may be mounted on horizontal or vertical pipe. On
horizontal pipe they should be installed on the top side of the pipe
where they will he accessible. The units should not be installed within
6" (15cm) of a fitting which changes the direction of the waterfiow or
within 24" (60 cm) of a valve or drain.
Drain the system and drill a hole in the pipe using a circular saw in a
slow speed drill. The 2" (50mm) and 2 1/2" (65mm) devices require a
hole with a diameter oft 1/4" + 1/8" - 1/16" (33mm ±2mm). All other
sizes require a hole with a diameter of 2" ±1/8" (50mm ±2mm).
Clean the inside pipe of all growth or other material for a distance equal
to the pipe diameter on either side of the hole.
Roll the vane so that it may be inserted into the hole; do not bend or
crease it. Insert the vane so that the arrow on the saddle points in the
direction of the waterfiow. Install the saddle strap and tighten nuts
alternately to an eventual 50 fl-lbs. (68 n-m) of torque (see Fig. 2). The
vane must not rub the inside of the pipe or bind in any way.
Specifications subject to change without notice.
Potter Electric Signal Company 2081 Craig Road, St. Louis, MO, 63146-4161 • Phone: 800-325-3936/Canada 888-882-1833 www.pottersignal.com
PRINTED IN USA 1VII(T, 98800001 - REV W PAGE 1 OF 2 MFG. #5400761 - 7/02
POTTER
The Symbol of Protection
VSR-F
VANE TYPE WATERFLOW
ALARM SWITCH WITH RETARD
FIG. I
SWITCH TERMINAL
CONNECTIONS
CLAMPING PLATE
TERMINAL
FIG. 2
OPTIONAL TAMPER SWITCH Do NOT LEAVE COVER OFF FOR
ENDED PERI OD OF TIME ,
RETARD ADJUSTMENT:
TO CHANGE TIME TURN KNOB (EITHER DIRECTION)
FOR DESIRED TIME DELAY, USE THE MINIMUM
AMOUNT OF RETARD NECESSARY TO PREVENT
FALSE ALARMS, A "B" SETTING IS USUALLY
ADEQUATE FOR THIS. FACTORY IS SET TO "B.
TIGHTEN NUTS
- ALTERNATELY TO AN
EVENTUAL SOFT-LBS (68 o-m)
OF TORQUE
O0 DWGN 923-3
CAUTION:
An uninsulated section of a
single conductor should not
he looped around the terminal
and serve as two separate
Connections. The wire must
be severed, thereby providing
supervision of the connection
in the event that the wire
becomes dislodged from under
the terminal.
nz
TO INSTALL, DRILL HOLE AS INDICATED:
PIPE SIZE HOLE SIZE
2' to 2 1/2" 1 1/4" +1/8" -1/16'
(50mm to 65mm) (33mm +2mm)
3" to 8" 2" ±1/8"
(80mm to 200mm) 50mm ±2mm)
Cover Tamper
(with cover in place)
DECTIONDF
C N.O. N,L'.
(WIlT) (RED) (ISLE)
WATERFLOW
DWG. #761-30
MOUNT ON PIPE SD
ARROW ON SADDLE
POINTS IN DIRECTION
OF WATERFLOW
ROLL PADDLE IN
OPPOSITE DIRECTION
OF WATERFLOW
APPROX. RETARD SETTINGS (IN SECS.)
o
o
A
t0-25
B
20-40
C
35-55
0
50-70
0
60-90
FIG. 3 TYPICAL ELECTRICAL CONNECTIONS
2 SETS OF NORMALLY
OPEN CONTACTS WATERFLOW ZONE EOLR FROM CLOSE ON ALARM ON FIRE PANEL FIRE PANEL
Nc
COM NO NC
THE N.C. AND NO. MARKINOSON
THE SWITCH ARE FOR AN ALARM
CONDITION.
THE CONTACTS ARE REVERSED
WHEN THE DEVICE IS 114 THE
NORMAL CONDITION,
NOTES:
1, The Model VSR-F has two
switches, one can be used
to operate a central station,
proprietary or remote signaling
unit, while the other contact is
used to operate a local audible or
visual annunciator.
FIG. 4
To remove knockouts: Place
screwdriver at edge of knockouts,
not in the center.
5990, 1761-4
POSITIVE DC
OR HOTAC
NEGATIVE DC OR
NEUTRAL AC
A condition of LPC Approval of
this product is that the electrical
entry must be sealed to exclude
BELL moisture.
For supervised circuits see
"Switch Terminal Connections"
drawing and caution note
(Fig. 1).
APPLICATION WARNING!
Due to the possibility of unintended discharges caused by pressure surges, trapped air, or short retard times, waterfiow switches that are monitoring wet pipe 'sprinkler systems should not be used as the sole initiating device to discharge AFFF, deluge, or chemical suppression systems.
TESTING
The frequency of inspection and testing for the model VSR-F and its associated protective monitoring system should be in accordance with
applicable NFPA Codes and Standards and/or the authority having jurisdiction (manufacturer recommends quarterly or more frequently).
If provided, the inspector's test valve, that is usually located at the end of the most remote branch line, should always be used for test purposes
If there are no provisions for testing the operation of the flow detection device on the system. application of the VSR-F is not recommended or
advisable.
A minimum flow of 10 gpm (38 Lpm) is required to activate this device.
IMPORTANT NOTICE: Please advise the person responsible for testing of the fire protection system that this system must be tested in ccordance with the testing instructions.
PRINTED IN USA MKT. 48800001 - REV W PAGE 2 OF 2 lv[FG.#5400761 -7/02
SYSU- ® POTTER OUTSIDE O SCREW AND
1.9
YOKE VALVE
The Symbol of Protection SUPERVISORY SWITCH
UL and CSFM Listed, FM Approved, NYMEA Accepted,
CE Marked
Dimensions: 6. 19'L X 2.25W X 5.88"H
15,7cm LX 5,7cm W X 14,6cm H
Weight: 2 lbs. (0,9 kg.)
Enclosure: Cover - Die-Cast
Finish- Red Spatter Enamel
Base - Die Cast Zinc
All parts have corrosion resistant finishes.
Cover Tamper: Tamper resistant screws,
Optional cover tamper kit available.
Contact Ratings:
OSYSU- 1: One set of SPDT (Form C)
OSYSU-2: Two sets of SPDT (Form C)
15.00 Amps at 125/250VAC
2.50 Amps at 3OVDC resistive
Environmental Limitations:
NEMA 4 and NEM.A 6P Enclosure (IP67) when used
with appropriate watertight conduit fittings.
indoor or Outdoor use (Not for use in hazardous
locations. See bulletin no. 5400705 OSYS-U-EX
for hazardous locations.)
Temperature Range: -40°F to 140°F (-40°C to 60°C)
Conduit Entrances:
2 knockouts for 1/2' conduit provided
Service Use:
Automatic Sprinkler N'FPA- 13
OSYSU-1 Stock No. 10 1. 0106 ' One or two family dwelling NFPA-13D
OSYSU-2 Stock No. 1010206 Residential occupancy up to four stories NFPA-13R
National Fire Alarm Code NFPA-72
GENERAL INFORMATION OPTIONAL COVER TAMPER SWITCH
The OSYSU is used to monitor the. open position of an OS . A field installable cover tamper switch is available as an option
& Y (outside screw and yoke) type gate valve. This device is which maybe used to indicate removal of the cover. See ordering
available in two models; the OS'YSU-1, containing one set of information on page 4.
SPDT (Form C) contacts and the OSYSU'-2, containing two sets TESTING I., of SPDT (Fonn C) contacts.,These switches mount conveniently
,
contacts., These The OSYSU and its associated protective monitoring system to most OS & Y valves ranging in size from 2" to 12" (50mm
to 300mm). They will mounton some valves as small as 1/2"
should be inspected and tested in accordance with applicable
12 , mm1. .
NFPA codes and standards and/orthe authority havmgjurisdiction
'.
, (manufacturer recommends quarterly or more frequently).
The cover is held in place b.' two tamper resistant screws that
require a special tool to remove. The tool is furnished with each
device and should be left with the,building owner or responsible
party. Replacement or additional cover screws and hex keys are
available. See ordering information on page 4.
Potter Electric Signal Company 2081 • Craig Road, St. Louis, MO, 63146-4161 Phone: 800-325-3936/Canada 888-882-1833 wwwpottersignal.com
PRINTED IN USA , . ,• IviKT. #8820004 - ary P PAGE 1 OF 4
i2l0i
OSYSU-11 -2
OUTSIDE SCREW AND YOKE VALVE
SUPERVISORY SWITCH
FIG. 1 SMALL VALVE INSTALLATION - 1/2" THRU 21/2" (12,5mm THRU 63,5mm) SIZES
THESE SWITCHES MOUNT CONVENIENTLY TO MOST 2" TO 12" OS & Y VALVES, THEY WILL MOUNT ON SOME
VALVES AS SMALL AS 1/2' (12,5MM). S-HOOKS MAY BE REQUIRED ON VALVES WITH LIMITED CLEARANCE.
S
CLAMP BAR.
CARRIAGE •C
SLOTTED MOUNTING HOLES
MAY BE USED FOR FINE
ADJUSTMENT OF SWITCH
ON BRACKET
BRACKET
DWG. #979-3
SMALL VALVE INSTALLATION
Remove and dj.'qard "C" washer and roller from the trip rod
With the valve in the FULL OPEN position, locate the OSYSU
across the valv&yoke as far as possible from the valve gland, so
that the trip rod-Jays against the non-threaded portion of the valve
stem.
Loosen the locking screw that holds the trip rod in place and
adjust the rod:length (see Fig. 4). When adjusted properly, the
rod should extend past the valve screw, but not so far that it
contacts the clamp bar. Tighten the locking screw to hold the trip
rod in place.
NOTE:. If trip rod length is excessive, loosen the locking screw
and remove the trip rod from the trip lever. Using pliers, break
off the 1" (25mm) long notched section (see Fig. 5). Reinstall
trip rod and repeatStep 3 procedure.
Mount the OSYSU loosely with the carriage bolts and clamp bar
supplied. On valvs with limited clearance use I-hooks supplied
instead of the carriage bolts and clamp bar to mount the OSYSU
Mark the valve stern at the center of the trip rod.
Remove the OSYSU. File a 1/8" (3,2mm) deep groove centered
on the mark on the valve stem utilizing a 3/16" (4,8mm) round,
non-tapered file. Round and smooth the edges of the groove to
prevent damage to the valve packing and to allow the trip rod to
move easily in and out of the groove as the valve is operated.
Mount the OSYSU with the trip rod centered in groove.
Final adjustment is made by loosening 2 screws (see Fig. 1) and
sliding the OSYSU on the bracket. Adjustment is correct when
switches are not activated with the trip rod seated in the valve
stern groove and that the switches activate when the trip rod
moves out of the groove.
Tighten the adjustment screws and all mounting hardware. Check
to insure that the rod moves out of the groove easily and that the
switches activate within one turn when the valve is operated from
the FULL OPEN towards the CLOSED position.
NOTE: CLOSE THE VALVE FULLY TO DETERMINE THAT
THE STEM THREADS DO NOT ACTIVATE THE SWITCH. THE
SWITCH BEING ACTIVATED BY THE STEM THREADS COULD
RESULT IN A FALSE VALVE OPEN INDICATION.
PRINTED IN USA MET. 98820004 - REV P PAGE 2 OF 4
12/01
[i
FIG. 2 H LARGE VALVE INSTALLATION - 3" THRIJ 12" (76mm THRU 300mm) SIZES
3" THRU 12"' (76mm THRU 300mm) VALVES BRACKET
USE CARRIAGE BOLTS. BOLTS MOUNT
ON INSIDE OF YOKE, IF THERE CLAMP BAR
IS SUFFICIENT CLEARANCE.
CARRIAGE BOLTS
. SLOTTED MOUNTING (2 REQUIRED)
HOLES. MAY BE USED / II ROLLER
FOR FINE ADJUSTMENT / II GROOVE OFSWITCH ON BRACKET.
YOKE
VALVE STEM
TRIP ROD
.WG. #979-4 GLAND
LARGE VALVE INSTALLATION
1. With the valve in the FULL OPEN position, locate the OSYSU
across the valve yoke as far as possible from the valve gland, so
that the trip rod lays against the non-threaded portion of the valve
stem.
2.: Mount the OSYSU loosely with the carriage bolts and clamp bar
supplied.
3. Loosen the locking screw that holds the trip rod in place and
adjust the rod length (see Fig. 4). When adjusted properly, the
rod should extend past the valve screw, but not so far that it
contacts the clamp bar. Tighten the locking screw to hold the trip
rod in place.
NOTE: if trip rod length is excessive, loosen the locking screw
and remove the trip rod from the trip lever. Using pliers, break
off the one 1." (25mm) long notched section (see Fig. 5). Reinstall
trip rod and repeat Step 3 procedure.
A. Mark the valve stem at the center of the trip rod.
5. Remove the OSYSU. File a 1/8' (3,2mm) deep groove centered
on the mark of the valve stem utilizing a 3/8" (9,5mm) round,
non-tapered file. Round and smooth the edges of the groove to
prevent damage to the valve packing and to allow the trip rod to
move easily in and out of the groove as the valve is operated.
Mount the OSYSU loosely with the trip rod centered in groove.
Final adjustment is made by loosening 2 screws (see Fig. 2) and
sliding the OSYSU on the bracket. Adjustment is correct when
switches are not activated with the trip rod seated in the valve
stein groove and that the switches activate within one turn when
the valve is operated from the FULL OPEN towards the CLOSED
position.
Tighten the adjustment screws and mounting hardware. Check
to insure that the rod moves out of the groove easily and that the
switches activate within one turn when the valve is operated from
the FULL OPEN towards the CLOSED position.
NOTE: CLOSE THE VALVE FULLY TO DETERMINE THAT
THE STEM THREADS DO NOT ACTIVATE THE SWITCH. THE
SWITCH BEING ACTIVATED BY THE STEM THREADS COULD
RESULT IN A FALSE VALVE OPEN INDICATION.
r -r--
PRINTED 04 USA MKT. 48820004 - REV P • PAGE 3 OF 4
12/01
ORDERING INFORMATION
MODEL DESCRIPTION STOCK NO.
OSYSU-1 Outside Screw & Yoke-Supervisory Switch (Single switch) 1010106
OSYSU-2 Outside Screw & Yoke-Supervisory Switch (Double switch) 1010206
-- Cover Screw 5490344
-- Hex Key for Cover Screws and installation Adjustments 5250062
-- Optional Cover Tamper Switch Kit 0090131
For pressure reducer type valve installation kits (if required) contact valve manufacturer.
OPEN VALVE POSITION
COW.
SW #1
COW. I
SW #2
CLOSED VALVE POSITION
.01
SW #1
C.
C
OM
SW #2
DWC. #979-2
(E)POTTER OUTSIDE SCREW AND YOKE VALVE The Symbol of Protection SUPERVISORY SWITCH
FIG. 3 DIMENSIONS FIG. 4 PARTS
FOR C(
ROW
Row
ROD
ROD TtNOEO 1r-, ORG. fl79-O
9-9
WREAKING EXCESSIVE ROD
LENGTH
FIG.5
SWITCH TERMINAL
CONNECTIONS
CLAMPING PLATE
TERMINAL
,.,..,..
MING
JtG0 0 OWC. #923-3
CAUTION:
An uninsulated section of a single conductor should
not be looped around the terminal and serve as two
separate connections. The wire must be severed,
thereby providing supervision of the connection
in the event that the wire becomes dislodged from
under the terminal.
TYPICAL ELECTRICAL CONNECTIONS
LOCAL CIRCUIT NO.
INDICATING TO POWER FOR COJ1.N.C. DEVICE INDICATING DEVICE I
TO SUPERVISORY CIRCUIT N.O. END OF OF CONTROL PANEL LINE COM. N.C. c RESISTOR i DWG. #979-1
Contacts shown in normal (valve open) condition.
TYPICAL SWITCH ACTION
PRINTED IN USA MKT. 98820004 - REV P PAGE 4 OF 4 12/01
POTTER
UL, ULC, and FM Approved
The Symbol of Protection PBA-AC & MBA-DC
Sizes Available: 6" (150mm), 8" (200mm) and 10' (250mm)
Voltages Available: 24VAC
I2OVAC
12VDC (10.2 to 15.6) Polarized
24VDC (20.4 to 31.2) Polarized
Service Use: Fire Alarm
General Signaling
Burglar Alarm
Environment: Indoor or outdoor use (See Note 1)
-400 to 150°F (40° to 66°C)
(Outdoor use requires weatherproof
backbox.)
Termination: AC Bells - 4 No. 18 AWG stranded wires
DC Bells - Terminal strip
Finish: Red powder coating
Optional: Model BBK- 1 weatherproof backbpx
Model BBX- 1 deep weatherproof backbox
These Orating type bells are designed for use as fire, burglar or general signaling devices. They have low power consumption
and hjh decibel ratings. The unit mounts on a standard 4(101mm) square electrical box for indoor use or on a model BBK-I
weatherroof backbox for outdoor applications. Weatherproof backbox model BBK- 1, Stock No. 1500001.
ALL T)C BELLS ARE POLARIZED AND HAVE BUILT-IN TRANSIENT PROTECTION:
iS.ize inches
(mm)
Voltage Model Number Stock Number Current (Max.) Typical dB at
10 ft. (3m) (2)
Minimum dB at
10 ft. (3m) (1)
H6 (150) 12VDC MBA126 1750070 .12A 85 76
8 (200) 12VDC MBA128 1750080 .12A 90 77
10 (250) 12VDC MBA1210 1750060 .12A 92 78
6 (150) 24VDC MBA246 1750100 .06A 87 77
8 (200) 24VDC MBA248 1750110 .06A 91 79
10 (250) 24VDC MBA2410 1750090 .06A 94 80
6(150) 24VAC PBA246 1806024 .17A 91 78
8 (200) 24VAC PBA248 1808024 .17A 94 77
10(250) 24VAC PBA2410 1810024 .17A 94 78
6(150) 120VAC PBA1206 1806120 .05A 92 83
8(200) 120VAC PBA1208 1808120 .05A 99 84
10(250) 120VAC PBA12010 1810120 .05A 99 86
Notes:
1: Minimum dB ratings are calculated from integrated sound pressure measurements made at Underwriters Laboratories as specified
in UL Standard 464. UL temperature range is -30° to 150°F (-34° to 66°C).
2 Typical dB ratings are calculated from measurements made with a conventional sound level meter and are indicative of output
levels in an actual installation.
Potter Electric Signal Company • 2081 Craig Road, St. Louis, MO, 63146-4161 • Phone: 800-325-3936/Canada 888-882-1833 www.pottersignal.com
PRINTED IN USA MKT, 48150001 - REV V PAGE I OF 2
MFG. #5400776 - 10/06
DIMENSIONS
INCHES (mm)
FIG. 1 BELLS
FN 1 (2 0) 1
(200) (150)
L:
2 11/16"
(68) D\VGI 775-I
FIG. 2 WEATHERPROOF BACKBOX
BOX HAS ONE THREADED 1/2" CONDUIT ENTRANCE
(105)
DWOS 775-2
FIG. 3 WIRING (REAR VIEW)
A.C. BELLS
ta
-LLI
.1 .
WHITE (IN) . WHITE (OUT)
0
FROM CONTROL
PANEL OR
PRECEDING BELL
0
BLACK (M C-L-C-T)
CAUTION:
WHEN ELECTRICAL SUPERVISION IS REQUIRED USE IN AND OUT LEADS AS SHOWN
NOTES:
I. WHEN USING AC BELLS, TERMINATE EACH EXTRA WIRE SEPARATELY AFTER LAST BELL.
2. END-OF-LINE RESISTOR IS NOT REQUIRED ON AC BELLS.
DWG, 175-2
)
INSTALLATION
The bell shall be installed in accordance with NFPA 13, 72, or local AHJ. The top of the device shall be no less than 90" AFF
and not less than 6" below the ceiling.
Remove the gong.
Connect wiring (see Fig. 3).
Mount bell mechanism to backbox (bell mechanism must be mounted with the striker pointing down).
Reinstall the gong (be sure that the gong positioning pin, in the mechanism housing, is in the hole in the gong).
Test all bells for proper operation and observe that they can be heard where required (bells must be heard in all areas as
designated by the authority having jurisdiction).
PRINTED ON USA . MET. 48850001-Ravv PAGE 2OF2
MFG. #5400776 - 10/06
8)FIRES-TOPPING,
[1
r- . -' -. , •
[I: TECHNICAL DATA SHEET
BOSS® 136 Fireblock/Draftstop Sealant
DES CFUPTON
BOSS® 136 Fireblock/Draftstop Sealant is a single component
fire rated sealant and is a noncombustible filler caulking used for
fireblocking applications in the annular space around wires, pipes,
ducts, vents, cable lines and other penetrations to the building
envelope. It is a non-slumping sealant that sets to form a hard
surface. BOSS® 136 can be applied to any gap or penetration
where the specification is noncombustible and/or ASTM-E136
rated. BOSS® 136 is to be used for interior applications only.
The noncombustible specification is common to one and two family
construction and to non-rated penetrations in multi family and
commercial construction. BOSS® 136 is colored red for ease of
inspection.
In the event of a fire BOSS® 136 will prevent the spread of fire,
smoke and toxic gases through penetration openings.
BOSS® 136 has been tested and meets the American Society for
Testing Materials E-1 36. To pass this test a material must withstand
1,400 degrees Fahrenheit without exhibiting signs of flaming after
the first thirty seconds in the test apparatus.
BOSS® 136 serves to form a 'gasket or seal against air infiltration"
as required by the Model Energy Code in both the performance
and prescriptive versions.
BOSS® 136 Applicable Standards include:
UBC page 1-387, 1997 editions
CABO Section 602.7 item 4, 1995 edition
BO CA (NBC) 704.4.1.11996
ASTM E-136
[UiJi
BOSS® 136 is completely non toxic and contains no asbestos
or PCBs.
Noncombustible
Applied with a conventional caulking gun
Easily applied sealant with water clean up capabilities
An accredited fire block/smoke seal caulk
Single component system, no mixing necessary and no
additions required
Meets residential construction code approvals including
I.R.C.
For interior applications only
Available in NEW 11.0 Oz. Net Wt. aerosol can
Excellent adhesion to a wide variety of substrate material
HO' TO USE
Cut nozzle to desired bead size. Insert
cartridge into standard caulking gun.
.0a smooth seal, hold at 450 angle and
apply by pushing sealant ahead of
nozzle.
Apply at 40°F or above.
To ensure good adheion, all surfaces
should be clean and free of dust, oil,
loose materials or any Qther substances.
Make sure that BOSS® 136 makes
complete contact with the entire surface
of the opening and alsothe surface of
the penetrating items.
Always follow cartridge directions. Clean
the area to be treated so that it is free of all
particles and debris. For large openings,
mineral wool fibers can be used as a backer
to help hold the product in place until cured.
Steel screen wire can be stapled in place
over the material when a large opening is
overhead or configured such that the
material will not support its own weight
during cure.
PERATURE RANGE
BOSS® 136 freezes in the cartridge at
temperatures below 32°F. The product can
be warmed and applied at any temperature
but will not cure below 40°F. :Freeze thaw
cycles do not alter the cured product. Cure
time may exceed 72 hours at non-freezing
temperature.
Keep from freezing
Do not take internally
Keep out of reach of children
CON TA- fINS
Sodium Silicate CAS# 1344:-09-8
SPECIFICATIONS
Meets ASTM E-1 36, standard test method
for behavior of materials in a vertical tube
furnace at 1400°F. Conforms to BOCA
National Building Code (1996), CABO one
and two family dwelling code (1995),
Uniform Building Code (1997) Section 796,
Fire Block and Draft Stop. BOCA-SBCCI-
ICBO-NFPA Building Codes. Consult your
local code official for the proper use of
product.
I FILL, VOID OR cAvrrr' MATERIALS I sSi1,( FOR USE IN THROUGH-PENETRATION I ® FIRESTOP SYSTEMS I I SEE UL DIRECTORY OF PRODUCTS I
US CERTIFIED FOR CANADA AND UL FIRE I
RESISTANCE DIRECTORY I
I 9NA6
ALSO CLASSIFIED IN ACCORDANCE WITH ASTM E 136-96a,
'Standard test method for the behavior of materials in a vertical
tube furnace at 750'C."
COLOR
BOSS® 136 Fireblock/Draftstop Sealant is
red in color for ease of inspection.
BOSS® 136 Fireblock/Draftstop Sealant is
available in standard caulking cartridges
and 28 Fl, Oz. cartridges, 5 gallon pails
and 11.0 Oz. Net Wt. aerosol cans.
STORAGE AND SHELF LIFE
When stored in the original Unopened
containers at or below 90°F (32°C), BOSS®
136 Fireblock/Draftstop Sealant has a shelf
life of 12 months from date of shipment. In
Countries where high heat and humidity
are a factor, special precautions must be
taken. Store product in a covered, well-
ventilated warehouse and avoid excessive
heat conditions. Storage in high heat, high
humidity conditions may reduce shelf life
by up to 30%. Rotation of stock is an
absolute necessity. Cartons should always
be stacked upright with the nozzle tip
pointed upwards. DO NOT stack cartons
on their side. NEVER stack cartons more
than 8 high. DO NOT store within 1 meter
(4 feet) of roofline of the warehouse or
storage building.
The information and data contained herein
is believed to be accurate and reliable;
however, it is the user's responsibility to
determine suitability of use. Since the
supplier cannot know all the uses, or the
conditions of use to which these products
may be exposed, no warranties concerning
the fitness or suitability for a particular use
or purpose are made.
It is the user's responsibility to thoroughly
test any proposed use of our products and
independently conclude satisfactory
performance in the application.
Likewise, if the application, product
specifications or manner in which our
products are used requires government
approval or clearance, it is the sole
responsibility of the user to obtain sure
authorization.
The supplier warrants only that its products
will meet its specifications. There is no
warranty of merchantability or fitness for
use, nor any other express or implied
warranty. The users exclusive remedy and
the suppliers sole liability is limited to refund
of the purchase price or replacement of any
product shown to be otherwise than as
warranted. The supplier will not be liable
for incidental or consequential damages of
any kind.
Suggestions of uses should not be taken
as inducements to infringe any patents.
MADE IN U.S.A.
PRODUCTS
Accumetric, LLC Accumetric Asia Pacific, LTD
350 Ring Road 18 Kitpanit Bldg. 5th Floor
Elizabethtown, #502 Patpong Road
Kentucky 42701 USA Suriyawong, Bangrak
800-928-BOSS(2677) Bangkok, 10500 Thailand
TEL (270)769.3385 TEL (662)634.3060
FAX (270)765-2412 FAX (662)634-3066
Outside U.S.
TEL +1(270)769-3385 FAX +1(270)765-2412
www.bossproducta.com
Ct.
. 041708T05136 . BOSS is registered trademark of Accumerric, LLC
Pagel 6
Print Rev. Date 02/20/2007
MSDS Document
Product BOSS® 136 Fireblock/Draftstop Sealant
I Chemical Product and Company Identification
Trade Name of this Product BOSS® 136 FireblocklDraftstop Sealant
Synonyms 03221 PK1 0, 03425RD10, 03467RD01 03482RD17, C39040RD
MSDSID BOS$136
Manufacturer Phone Number
• Accumetri., LLö (270) 769-3385
350 Ring .oad emergency Phone
Elizabethtown, KY 42701 CHEMTREC (800) 424-9300
• . Revision Date 2/2012007
S.
Fire
Heatth Reactivity
Reactivit
Specific
SpeclificF
2. Composition and Information-on Ingredients
' Ingredient CAS Number Weight % ACGIH TLV PEL
Sodiurnilicate 1344-09-8 20%-60%
Aluminithhydrxide 21645-51-2 20%-60% 10mg/rn 10mg/rn
Water. • 7732-1-5 10%-Max 0
Clay . - -1302-78-9 2%-10%
Iron oxide • 1332-37-2 1%-3%
3. Hazard Identification
Primary Routes of Entry
'skin Inhalation, contact
Eye Contact.
May cause-eye irritation.
STEL
Page 6
Print Rev. Date 02120/2007
MSDS ID B055136
BOSS® 136 Fireblock/Draftstop
Sealant
Skin Contact
May cause skin irritation.
Inhalation
No known effects
Ingestion
May cause irritation Do not induce vomiting.
4. First Aid Information
Eye Contact
Flush eyes, with plenty of water for at least 15 minutes, occasionally lifting upper and lower
eyelids. Check for and remove any contact lens. Do not use an eye ointment without
seeking mdical attention,
Skin Contact
Thoroughly wash exposed skin with soap and water.
Inhalation
Remove to fresh air. If symptoms persist, obtain appropriate medical attention.
Ingestion
Do not induce vomiting. Immediately drink two glasses of water. Never give anything to an
unconscious person. Get medical attention.
Cpmments
Treat according to persons condition and specifics of exposure.
5. Fire Fighting Measures
Flash Point Not determined
Flammability Limits in Air
Not applicable
Extinguishing Media
Carbon Dioxide, Dry Chemical, Foam
Use water fog to cool material in vicinity of fire.
Special Fire Fighting Procedures
Breathing apparatus required when fighting fires in enclosed spaces.
Unusual Fire or Explosion Hazards
N one known
Hazardous Decomposition Products
Thermal breakdown of this product during fire or very high heat conditions may evolve the
following h azardous decompositi on products:
None known
Page 6
Print Rev. Date 02120/2007
MSDS ID BOSS136
BOSS® 136 Fireblock!Draftstop
Sealant
Accidental Release Measures
Steps to be taken in case of spill or release
Observe all personal protection equipment recommendations. Soak up with inert absorbent.
Store in a partly filled, closed container until disposal. Local, state and federal regulations
may apply to releases and disposal of this material, as well as those materials and items
employed in cleanup of releases.
Handling and Storage
Handling
Avoid eye contact and repeated prolonged contact with the skin. Keep out of reach from
children.
Storage
Store in a cool dry place. Protect from freezing and excessive heat. Store away from
caustics and oxidizers.
Exposure Controls and Personal Protection
Eye Protection
Safety goggles or glasses with side shields are recommended.
Skin Protection
Impervious gloves are suggested.
Ventilation
Good general ventilation should be sufficient.
Respiratory Protection
If engineering controls do not maintain airborne concentrations of hazardous ingredients
below TLV, then a NIOSH!MSHA approved organic vapor respirator should be used. Not
required under normal usage and adequate ventilation.
Ingestion
Do not eat, drink or smoke during work.
Physical and Chemical Properties
S
Physical State,
Specific Gravity
Density lbs/Gal.
C olor/Appearance
Odor
pH
Boiling/Cond.. Point
Melting/Freezing Point
Solubility
Paste
1.9
15.85
Red
Slight
12
100C
00
Dilutable in wet stage
Page 6
Print Rev. Date 0212012007
MSDS ID BOSS136
BOSS® 136 FireblocklDrafistop
Sealant
S Evaporation Rate Slowerthan n-butyl acetate
VOC % 0 grams/liter
Percent Volatile 20
Viscosity 750,000 cPs
Vapor Density Lighter than air
Vapor Pressure Not determined
Note
The above informationis not intended for use in preparing product specifications. Contact
Accumetric LLC before writing specifications.
10. Stability and Reactivity
Chemical Stability
Stable
Hazardous Polymerization
Will not occur
Conditions to Avoid
Excessive heat and freezing.
Materials to Avoid I Incompatibility
Reacts with acids, ammonium salts, reactive metals, and some organics.
Toxicological Information
Special Hazard Information on Components
No known applicable information.
Component Toxicology Information
No known applicable information.
Ecological Information
Environmental Fate and Distribution
Complete i.rforrnation is not yet available.
Environmèntàj Effects
High pH isarniful to aquatic life.
Fate and Effects in Waste Water Treatment Plants
Complete infQrmation is not yet available.
Disposal Considerations
Waste Disposal Method
We make no guarantee or warranty of any kind that the use or disposal of this product
complies with all local, state, or federal laws. It is also the obligation of each user of the
Page 6
Print Rev. Date 0212012007
MSDS ID BOSS136
BOSS® 136 Fireb lock/Draft stop
Sealant
product mentioned herein to determine and comply with the requirements of all applicable
statutes.
This product is not known .to be regulated under RCRA regulations. Disposal of unused
portions of this product and process waste containing this product should be done only
after a careful evaluation and in compliance with all federal, local and state laws.
Transportation Information
Ocean Shipment (IMDG)
Not subject to IMDG code.
Air Shipment (IATA)
Not subject to IATA regulations.
DOT Road Shipment Information
Not subject to DOT.
Regulatory Information
The contents of this MSDS comply with the OSHA Hazard Communication Standard 29 CFR
1910.1200.
S TSCA Status
All chemical substances in this material are included on or exempted from listing on the
TSCA Inventory of Chemical Substances.
California Proposition 65
This product contains the following chemical(s) listed by the State of California under the
Safe Drinking Water and Toxic Enforcement Act of 1986 (Proposition 65) as being known to
cause cancer, birth defects or other reproductive harm:
None known
SARA Title Ill Section 302 Extremely Hazardous Substances
None
SARA Title Ill Section 304 CERCIA Hazardous Substances
None
SARA Title Ill Section 311/312
No components subject to 40 CFR 370
SARA Title Ill Section 313 Toxic Chemicals
None present or none present in regulated quantities.
Other Information
Disclaimer
0 i The data contained herein is based upon information that Accumetric LLC believes to be
Page 6
Print Rev. Date 02/20/2007
MSDS ID B05S136
BOSS® 136 FireblockJDrastop
Sealant
reliable. Users of this prduct have the responsibility to determine that suitability of use and
to adopt all necessary precautions to ensure the safety and protection of property and
persons invoIvedin said use. All statements to suggestions are made without warranty,
expressed or imied, regarding the accuracy of the information, the hazards connected with
the use of the-material or the results to be obtained from the use thereof.
J
FS-ONE Technical Data
based cscent Acrylic
Jispelsion
Sed
ci 4F ,5 C t0 .tOC
)x, 20-30 min,
AperCsas
Product
FS-ONE.
High Performance
~71
Intumescent Firestop Sealant
Product description
Intumescent (expands when exposed to fire) firestop sealant that
helps protect combustible and non-combustible penetrations for
up to 4 hours fire rating
Product features
Smoke, gas and water resistant after material has cured
Contains no halogen, solvents or asbestos
High fire rating propeCties
Water based, easy to Clean
Protects most typical firestop penetration applications
Can be painted
Single component systems available
Meets LEEDTM reqitirepients for indoor environmental quality credit
4.1 Low Emitting Materials, Sealants and Adhesives and 4.2 Paints
and Coatings
Areas of application
Steel, copper and EMT pipes
Insulated steel and copper pipes
Cable bundles
Closed or vented plastic pipes
HVAC penetrations
For use with
Concrete, masonry, drywaki and wood floor assemblies
Wall and floor assemblies rated up to 4 hours
•
Examples
Sealing around plastic pipe penetrations in fire rated construction
Sealing around combustible and non-combustible penetrations in
fire rated construction
Installation instructions for FS-ONE
<>
E
FILL V00 OR cp,,rry . '3ERIAL
FIRESTOP5'STEtS , Si'1EM cfe'rlkll.
FOR use a' mRouca-l-pnNErRATIoN
SEE UL CF 5 RElSW45 OIRECTORY I eevr . APPROVED
Smoothing of firestop sealant: To complete the seal,
tool immediately to give a smooth appearance.
Excess sealant, prior to curing, can be cleaned
away from adjacent surfaces and tools with wate
Leave completed seal undisturbed for 48 hours.
For maintenance reasons, a penetration seal coLd
be permanently marked with an identification plate.
In such a case, mark the identification plate and
fasten it in a visible position next to the seal.
Not for use
High movement expansion joints
Underwater
C'n materials where oil, plasticizers or solvents may
bleed i.e. impregnated wood, oi' based seals, green
or partially vulcanized rubber
In, any penetration other than those specifically
cescribed in this manual or the lest reports
Stcrage
Store only in the r ginal packaging in a locatior
protected from moisture at temperatures between
43F (5CC) and 86*F (30C)
Observe expiration date on the packaging
FL 6. 1. Clean opening. 2. Pack mineral wad. 3. Apply FS-:NE. 4. srrranth E. Suave completed 6. Fasten Identrfll,uaton lit required) P5-ONE. seal undisturbed for 411 plate ft requi,sdl. Sown.
It!t r
Aw
1J
JL ,
1. clean opening. 2. Pack mineral wool. 3. Apply VS-ONe. 4. S-rroath E. Laws completed 6. Fasten lit required) nSflNE seal undisturbed fur 43 identification title (it
FeLts required).
HiltL Outperform. Outlast.
Notice
Before handling, read Material Safety DataSheet and
product label for safe usage and health information.
Instructions below are general guidelines - always
refer to the applicable drawing in,the UL Fire
Resistance Directory or Hilt! Firestop Sybtems Guide
for complete installation informattbn
Opening
Clean the openihg. Surfaces to wIich FS-ONE will be
applied should be cleaned of loose de*is, dirt, oil,
moisture, frot And wax. Structurép.suporting
penetrating items must be installed in cothpliartce
with local building and electrical standards.
Application of firestop sealant
Install the prescribed backfilling material type and
depth to obtain the desired rating (if requir). Leave
sufficient depth for applying FS-ONE.
Application of firestop sealant: Apply FS-ONE to the
required depth in order to obtain the desired fire rating.
Make sure FS-ONE contacts all surfaces to provide
maximum adhesion. For application of FS-ONE use a
standard caulking gun, foil pack gun, bulk loader and
bulk gun. With FS-ONE buckets, Graco type sealant
pumps may be used. (Contact pump manufacturer for
proper selection).
0
Inc. (U.S.) 1-800-879-8000 • www.ushiItLcom • en español 1-800-879-5000 • Hilti Firestop Systems Guide 2007
MSOS No.: 259
Revision No.: 010
Revision Date: 08117/04
Page: 1o12 .Product name: FS-ONE High Perforniarice Intumescent Firestop Sealant
Description: One-part acrylic-based sealant
Supplier: Hilti, Inc. P.O. Box 21148 Tulsa, OK 74121
Emergency # (Chem-Trec.): 1 800 424:9300 (USA, PR, Virgin Islands, Canada); 001 703 527 3887 (other countries)
INGREDIENTS AND EXPOSURE LIMITS
Ingredients: CAS Number: PEL: TLV:.STEL.
Polyacrylate dispersion Mixture NE NE ..
Calcium carbonate 001317-653 .5 mg/rnT) 10mg/rn3 (T)NE
Zinc borate 138265-88-0 NE NE NE ............................ Ammonium polyphosphate .. NE .E
Talc 014807-96-6 20 rnppcf 2 mg/rn3 NE
Expandable graphre 012777-87-6 5 mg/m, (T) 2 mg/rn (1) NE
Ethylene glycol 000107-21-1 NE C 100 mg/ml (A) NE
Polybutene 00900.3-29-6 NE NE NE
Iron oxide l9 - ..:1 10 Vv- ................................NE .
Glass filament 06599717-3 NE . 5.m..........................NE
Silicon dioxide 014808 60-7 0.1.06 mg/m, (1) _P11. mg/m, (T) NE
Water .007732-i 8-5 NE NE NE
Abbreviations: PL = OSHA Permissible Exposure Limit. TLV ACIH Threshold Limit Value. 0 Ceiling. STEL = Short Term *pbsure Limit. NE =.None Etabiished. NA.= Not Applicable. (1) indicates astotaldUs1". (R) indicates .as
re$pirable fraction", (A) indicates "as an aerosol'. mppcf = million particles per cubic foot.
PHYSICAL DATA
..-......... ..
Appearance: . Red paste. Odor: Odorless.
Vapor 1) . Not determined. VaporPessure 23mbar @ 200 / 68F
oiling Point: Not applicable. voc content: 750 g/L.
Evaporation Rate Not applicable Solubility in Water Soluble
Specific Gravity: J : 1.5 pH:. Not determined.
FIRE AND EXPLOSION HAZARD DATA.
Flash Point.-Non-flammable. on- iammable Limits: Not app..ble.
Extinguishing Media Not applicable Use extinguishing media as appropriate for surrounding fire
Special Fire Fighting Procedures None known Use a self-contained breathing apparatus when fighting fires involving
chemicals.
Unusual Fire and Explosion Hazards: None-known. Thermal decomposition products can be formed such as oxides of carbon,
sulfur and phosphorous.
REACTIVITY DATA
Stability: Stable Hazardous Polymerization- Will not occur.
Incornpatibiirty, Strong acids peroxides and oxidizing agents
Decomposition ProductsA Thermal decomposition can yield CO and CO2
Conditions to Avoid: . None known,
HEALTH HAZARD DATA
Known Hazards: . None known.
Signs and .Symptoms of Exposure: Possibly irritating upon contact with the eyes or upon repeated contact with the skin
Medical Conditioné . Eye and skin conditions.
Aggravated by Exposure:
Routes of Exposure: Dermal,
Hilti Firestop
- Saving Lives
through innovation
- arid education Hilti. Outperform. Ouliast.
1-800-879-8000 • wWw.us.I-'ltj.co-n. - -80-879-000. --- -8C3-363-4458 www.hiltLca
IVISOS No.: 255
Revision No.: 010
Revision Date: 08/17/04
Page: 2012 . Carcinogenicity: :IARC classifies crystalline silica quartz sand) as Group I based upon evidence among
workers in industries where there has been tong-term and chronic exposure (via
inhalation) to silica dust; e.g. mining, quarry, stone crushing, refractory brick and pottery
workers. This product does not pose a dust hazard; therefore, this classification is not
relevant. Based upon the nature and intended use of this product, it does not pose an
increased cancer risk to workers.
EMERGENCY AND FIRST AD PROCEDURES
Eyes:trnmediate!y flush with plenty of water. Call a physician if Symptoms occur.
Skin Immedibtely wipe off material and wash with soap and water. Material. can .adhere to the
skin. If material has. adhered:to the Skin, use an abrasive containing hand cleaner. If
material does net come off, buff with a pumice ......
lnhalat,iori: Move victim to fresh air ! discomfort develops. • • ..... .physician . . sy ptonispt.
Ingestion: Seek-medical attention. Do not induce vomiting unless directed by a physician. If a large
quantity was ingstéd, give. 1 to 2 glasses of water to dilute. Never give anything by
mouth to an unconscious person. .
Other: Referral to •a physician is recommended if there isany question about the seriousness of
the injury/exposure.
C NT RO.L MEASURES AND. PERSONAL PROTEOTIVE EQUIPMENT
Ventilation! General (natural or mechanically induced fresh air movements).
Eye ProtectIon .Not required, however, safetygiasses should be worn Jnmost industrial settings,
Skin Protection: Avid skin contact Cloth gloves are suitable for hand protect!on .. ........* ........
Respiratory Protection: None normally required. Where ventilation is inadequate to control vapors, use a NIOSH-
approved respIrator with organic vapor cartridges Never enter a confined space without
an appropriate air-supplied respirator.
PRECAUTIONS FOR SAFE HANDLING AND USE
Handling and Storing Precautions: Store in a cool, dry area preferab!y between 40o. and 770 F. Keep from freezing; Do not
store indirêbtsUnliht, Avoid contact with the eyes.or skin. Practice good: hygiene;: i.e.
always wash thoroughly after handling and before eating or smoking. For industrial use
only. Keep out of reach 0.children. FollOw label/usenstruc......
Spill Procedures: Immediately wipe sway spilled material before it hardens. Place in a container for proper
disposal in aôcOrdance with all.àpplicablslocal, state, or federal requirements.
REGULATORY INFORMATION
Hazard Communication: This MSDS has been prepared in accordance with the federal OSHA Hazard
Communication Standard .29 CFR 1910.120.0. .
HMIS• Codes: Health i, Flammability o, Reactivity.0 PPE
DOT Shipping Name: Not regulated.
IATA ICAO Shipping Name: Not regulated.
TSCA Inventory Status: Chemical components listed on TSCA inventory. SARA Title Ill, Section 313: This product
contains < 3% ethylene glycol (CAS 107-21-1) and <15% zinc bOrate (re: zinc
compounds) which are subject to reporting under Section 313 of SARA Title .111(40 CFR
Part 372). .
EPA, 'Waste., C.ode(s):Not regidated by EPA as a hazardOus waste.
Waste Disposal. Methods: Consult with regulatory agencies or your corporate personnel for disposal methods that
comply with local, state, and federal safety,.health and environmental regulations.
CONTACTS
Customer Service: 1 800 879 8000 Technical Service: 1 800 879 8000
Health 1!fetY... ..........................................................................
1800 8796. 11000 Jerry Metcalf (x6704) . .
r...*Y m:Tre...1 800 0 (Y. R Virgin Islands, Canada); 001 703 527 3887 (other countries)
The information and recommendations contained herein are based upon data believed to be correct; however, no guarantee or
warranty of any kind expressed or. implied is made with respect to the informatiOn provided.
.Hiti Ffretop
Saying Liv
t through intlovation
.educ HIItL Outperførr .... O.UTh StW .. and
1-lilt4 Inc 1U S 1 800 879 8000 • www us hiltt corn • er. i.1 1 800 879 5000 i nt" 1 800 363-4458 www hilU ca
.Certificati Number 20.060.214-RI3240E
Report Reference 2006. Feruary 14
Issue Date 2006 February 14
Page lof I
U Underwriters
® L Laboratories Inc..
Issued tO; Hit', Er..c.
540.S 12 ;ND:FastAve
Tulsa, OK 7.4146: USA
This is to cer4fy that
.rep.resefltative samples. of Fit!,. Void or C :ty .at:erjaI.s
FS-ONE.
Have hem iinsri,'ated by Undeneriter% laboratories !nc.1 in
acordaiicc 1111/? rite Slandmfi%) indicahJ on this Cerriticart'.
Star i:(s) for Safety: .ANSL'UL .14.79, N/tJL. 20.79, CAN/LJLC.S;i 15O5
Additional Jvfiir,nation: FS-ONE Sealant for use in Joint Systems and FS-ONE for use in Through-
Penetration Firestop Systems as currently described in the UL Fire Resistance
Directory.
Only those pr d iits hc;i ring the U L ClasJ 0-slilcaLion Marh should be considered as being
covered by UL's s ( l:IitR:iIII)II and lilli'- I; service.
The UL Classification N4ak includes UL in a circle symbol ) with the word
"CLASSIFIED" (as shown); a control nuthber (may b alphanumeric) assigned by UL; a
statement to indicate the extent of UL's evaluation of the product and the product category
name (product. i.dePtity) as indied n the apprpriat UL Directory.
Look for the U.L Classification Mark o.h the product
Issued
S Reviewed by: 4661n~i.Couloute Christopher. on
Ucderwr.iters Jaboratories Inc. . Underwriters L6r4tories Inc.
0
IYIs7LI,J 'J.. Z.JCJ
Revision No.: 010
Revisi:0h1 Date: 08/17/04
MATERIAL SAFETY DATA SHEET
Product name: FS 'ONE High Performance Intumescent Firestop Sealant
Description: One-part acrylic-based sealant
Supplier: Hilti, Inc. P.O. Box 21148, Tulsa, OK 74121
Emergency # (Chem-Trec): 1 800 424 9300 (USA, PR, Virgin Islands, Canada); 001 703 527 3887 (other countries)
INGREDIENTS AND EXPOSURE LIMITS
Ingredients: CAS Number: PEL: TLV STEL:
Polyacrylate dispersion Mixture NE NE NE
Calcium carbonate 001317-65-3 5 mg/m3 (T) 10mg/rn3 (T) NE
Zinc borate 138265-88-0 NE NE NE
Ammonium polyphosphate 068333-79-9 NE NE NE
Talc 014807-96-6 20 mppcf 2 mg/m3 NE
Expandable graphite 012777-87-6 5 Mg/M3 (T) 2mg/rn3 (T) NE
Ethylene glycol 000107-21-1 NE 0:100 mg/rn3 (A) NE
Polybutene 009003-29-6 NE NE NE
Iron oxide • 001309-37-1 10mg/rn3 5 Mg/M3 NE
Glass filament 065997-17-3 NE 5 mg/m3 (T) NE
Silicon dioxide 014808-60-7 0.05 Mg/M3 (T) 0.1 mg/m3 (T) NE
Water 007732-18-5 NE NE NE
Abbreviations: PEL OSHA Permissible Exposure Limit. TLV = ACGIH Threshold Limit Value. C = Ceiling. STEL = Short Term Exposure Limit. NE = None Established. NA = Not Applicable. (1) indicates "as total dust". (R) indicates "as respirable fraction". (A) indicates "as an aerosol". mppcf =million particles per cubic foot.
PHYSICAL DATA
Appearance: + Red paste. Odor: Odorless.
Density: (air- 1)
•
Vapor Not determined. Vapor Pressure: 23mbar © 200 / 68F
Boiling Point: Not applicable. VOC Content: 75.0 g/L.
Evaporation Rate: Not applicable. i Solubility in Water: Soluble.
Specific Gravity: - 1.5 pH: Not determined.
FIRE AND EXPLOSION HAZARD DATA
Flash Point: • Non-flammable. Flammable Limits: : Not applicable.
Extinguishing Media: Not applicable. Use extinguishing media as appropriate for surrounding fire.
Special Fire Fighting None known. Use a self-contained breathing apparatus when fighting fires involving chemicals. Procedures:
Unusual Fire and Explosion None known. Thermal decomposition products can be formed such as oxides of carbon, sulfur
Hazards: and phosphorous.
REACTIVITY DATA
Stability: Stable. Hazardous Polymerization: Will not occur.
Incompatibility:
. Strong acids, peroxides, and oxidizing agents.
Decomposition Products: Thermal decomposition can yield CO and 002.
Conditions to Avoid: None known.
HEALTH HAZARD DATA
Known Hazards: • None known.
Signs and Symptoms of Possibly irritating upon contact with the eyes or upon repeated contact with the skin. Exposure:
Conditions Eye and skin conditions. .Medical
Aggravated by Exposure:
Routes of Exposure: + . Dermal.
HILTI ® is a registered trademark of Hilti Corp.
Carcinogenicity IARC classifies crystalline silica (quartz sand) as Group I based upon evidence among workers in
industries where there has been long-term and chronic exposure (via inhalation) to silica dust;
e.g. mining, quarry, stone crushing, refractory brick and pottery workers. This product does not
)iosea dust hazard; therefore, this classification is not relevant. Based upon the nature and ihtended use of this product, it does not pose an increased cancer risk to workers.
EMERGENCY AND FIRST AID PROCEDURES
Eyes: . I Immediately flush with plenty of water. Call a physician if symptoms occur,
Skin: Immediately wipe off material and wash with soap and water. Material can adhere to the skin. If riiaterial has adhered to the skin, use an abrasive containing hand cleaner. If material does not
come off, buff with a pumice stone.
Inhalation: 1Move victim to fresh air if discomfort develops. Call a physician if symptoms persist.
Ingestion: §eek medical attention. Do not induce vomiting unless directed by a physician. If a large quantity
Was ingested, give 1 to 2 glasses of water to dilute. Never give anything by mouth to an unconscious person.
Other: . Referral to a physician is recommended if there is any question about the seriousness of the
injury/exposure.
CONTROL MEASURES AND PERSONAL PROTECTIVE EQUIPMENT
Ventilation: General (natural or mechanically induced fresh air movements).
Eye Protection::Not required, however, safety glasses should be worn in most industrial settings.
Skin Protection Avoid skin contact. Cloth gloves are suitable for hand protection.
Respiratory Protection: None normally required. Where ventilation is inadequate to control vapors, use a NIOSH-
approved respirator with organic vapor cartridges. Never enter a confined space without an
appropriate air-supplied respirator.
PRECAUTIONS FOR SAFE HANDLING AND USE
'Handling and Storing Store in a cool, dry area preferably between 400 and 77° F. Keep from freezing. Do not store in Precautions: direct sunlight. Avoid contact with the eyes or skin. Practice good hygiene; i.e. always wash thoroughly after handling and before eating or smoking. For industrial use only. Keep out of reach of children. Follow label/use instructions.
Spill Procedures: . immediately wipe away spilled material before it hardens. Place in a container for proper disposal
in accordance with all applicable local, state, or federal requirements.
REGULATORY INFORMATION
Hazard Communication: This MSDS has been prepared in accordance with the federal OSHA Hazard Communication
Standard 29 CFR 1910.1200.
HMIS Codes: Health 1, Flammability 0, Reactivity 0, PPE B
DOT Shipping Name: ' Not regulated.
AlA / ICAO Shipping dame: Not regulated.
TSCA Inventory Status: Chemical components listed on tSCA inventory.
SARA Title Ill, Section 313: This product contains <3% ethylene glycol (CAS 107-21-1) and < 15% zinc borate (re: zinc compounds) which are subject to reporting under Section 313 of SARA Title III (40 CFR Part
- 372).
EPA Waste Code(s): Not regulated by EPA as a hazardous waste.
Waste Disposal Methods: Consult with regulatory agencies or your corporate personnel for disposal methods that comply
with local, state, and federal safety, health and environmental regulations.
CONTACTS
Customer Service: 1 800 879 8000 Technical Service: 1 800 879 8000
Health / Safety: 1 800 879 6000 Jerry Metcalf (x6704)
Emergency # (Chem-Trec): 1 800 424 9300 (USA, PR, Virgin Islands, Canada); 001 703 527 3887 (other countries)
The information and recommendations contained herein are based upon data believed to be correct; however, no guarantee or
warranty of any kind expressed or implied is made with respect to the information provided.
MSDS 259, Page 2of2
9)BACKFLOW
MODEL 350ADA
with OS&Y option
-.•. '. - :•021
ECIFICATON
[I:
(with OS&Y gates) (with BGVIC valves)
FEATURES
Sizes: LI 2 1/2" LI 3" LI 4" LI 6" U 8" LI 10"
Maximum working water pressure 175 PSI
Maximum working water temperature 140°F
Hydrostatic test pressure 350 PSI
End connections (Grooved for steel pipe) A\MNA C606
(Flanged) ANSI B16.1
Class 125
OPTIONS
(Suffixes can be combined)
LI - with flanged end OS & Y gate valves (standard)
LI L - less shut-off valves (grooved body connections)
LI LM - less water meter
LI - with remote reading meter
LI - with gpm meter (standard)
LI - with cu ft/min meter
LI C - with grooved end OS&Y gate valves
LI FG - with flanged inlet gate connection and grooved
outlet gate connection
LI P1 - with Post Indicator Gate Valves (4-10')
LIBGVIC - ,with grooved end butterfly valves
ACCESSORIES
U Repair kit (rubber only)
U Thermal expansion tank (Model XT)
U OS &Y Gate valve tamper switch (OSY-40)
LI Test Cock Lock (Model TCL24)
DIMENSIONS .& WEIGHTS (do not include pkg.)
MODEL
350ADA
SIZE
in. mm
WEIGHT
WITHOUT
GAES
lbs. kg
WITH OS&Y
GATES (GXF)
lbs. kg
WITH OS&Y
GATES (GXG)
lbs, kg
/4TH
BUTTERFLY
VALVES (GXG)
9s kg
2 1/2 65 105 47.5 207 94 199 90.3 123.8 56.2
3 80 104 47 224 101.5 214 97 124.4 56.5
4 100 91 41.3 245 111 219 99.4 123 55.8
6 150 F141 64 377 171 347 158 193 87,6
8 200 302' 137 778 353.2 754 342.3 410 186
10 250 355. 161 1040 472.7 918 416.5 527 239.3
APPLICATION
Designed for installation on potable water lines connections in
fire sprinkler systems to protect against both backsiphonage and
backpressure of polluted water into the potable water supply.
Model 350ADA shall provide protection where a potential health
hazard does not exist. Incorporates metered by-pass to detect
leaks and unauthorized water use.
STANDARDS COMPLIANCE (HORIZONTAL & VERTICAL)
ASSE® Listed 1048
AWNA Compliant C510 (with gates only)
CSA® Certified (4-8")
UL® Classified
C-UL® Classified
FM® Approved
Approved by the Foundation for Cross Connection
Control and Hydraulic Research at the University of
Southern California.
NYC MEA22I-04M-2 (2 1/2-8")
MATERIALS
Main valve body Ductile Iron ASTM A 536 Grade 4
Access covers Ductile Iron ASTM A 536 Grade 4
Coatings FDA Approved electrostatic epoxy finish
Internals Stainless steel, 300 Series
NORYLTM, NSF Listed
Fasteners & springs Stainless Steel, 300 Series
Elastomers EPDM (FDA approved)
Buna Nitrile (FDA approved)
Polymers NORYLTM, NSF Listed
MODEL 350ADA with
BGVIC option
MODEL DIMENSION (approximate) ________
350 ADA
SIZE
in I mm
A
in mm
A WITH
BUTTERFLY
VALVES
in mm
B LESS
GATE
VALVES
in mm
C
in mm
D
in mm
OS&Y OPEN
in mm
E
OS&Y
CLOSED
in mm
E WITH
BUTTERFLY
VALVES
In mm
F
in mm
G
in mm 21/2 65 35 1/8 892 32 1/8 816 20 1/81511 4 1/2 114 9 229 163/8 416 137/8 352 8 203 6 152 71/4 184
3 80 36 1/8 918 33 838 201/8 511 41/21 114 9 229 187/8 479 155/8 397 8 152 71/4 184
4 100 381/47972 33 1/4 845 197/8 505 4 1/21114 9 229 223/4 578 181/4 464 9118 152 8 203
6 150 471/4 1200 401/4 1022,257/8 657 51/2 140 101/2 267 301/8 765 233/4 603 101/8 T2577 178 10 254
8 200 62 1575 55 1397 38 1/2 978 10 254 12 305 373/4 959 29 1/4 743 1115/16 21611 279
10 250 645/8 642 58 1/2 148538 1/2 978 10 254 12 305 453/4 1162 35 3/8 899 135/16 12 216 12 305
(Patent No. 5,913,331)
Attention:
Model 350ADA
(grooved body)
and Model 350DA
(flange body)
have different lay
lengths.
Capacity thru Schedule 40 Pipe (GPM)
Pipe size 5 ft/sec 7.5 ft/sec lOft/sec 15 ft/sec
2 1/2" 75 112 149 224
115 173 230 346
198 298 397 595
6" 450 675 900 1351
8" 780 1169 1559 2339
10" 1229 1843 2458 3687
12" 1763 2644 3525 1 5288
PROTECTIVE
ENCLOSURE
30 MAX.
DIRECTION OFF W
FLOW CHARACTERISTICS
MODEL 350ADA 2 1/2",3" & 4" (STANDARD & METRIC)
51
FLOW RATES (11$)
12.6 25.2 37.9
10
W
Co a, w
a_ U
0 . 200 400 600
FLOW RATES (GPM)
MODEL 350ADA 6', 8" & 10" (STANDARD & METRIC)
FLOW RATES (Es)
0.0 . 63.1 126.2 189.3
15
10
Cn
A
0 boo 2000 3000
FLOW RATES (GPM)
50.5
104
252.4
104 j
69
p
' Rated Flow (Established by approval agencies)
TYPICAL INSTALLATION
Local codes shall govern installation requirements. Unless
otherwise specified, the assembly shall be mounted at a mini-
mum of 12" (305mm) and a maximum of 30" (762mm) above
adequate drains with sufficient side clearance for testing and
maintenance. The installation shall be thade so that no part of . the unit can be submerged.
bJ MODEL 350ADABGVIC (VERTICAL INSTALLATION) MODEL 350ADA (OUTDOOR INSTALLATION)
SPECIFICATIONS
The Double Check Detector Backflow Prevention Assembly shall be ASSE® Listed 1048, and supplied with full port gate valves.
The main" body and access cover shall be epoxy coated ductile iron (ASTM A 536 Grade 4), the seat ring and check valve shall be
NorylTM (NSF Listed), the stem shall be stainless steel (ASTM A 276) and the seat disc elastomers shall be EPDM. The first and
'second chck valves shall be accessible for maintenance without removing the device from the line. The Double Check Detector
Backflow Prevention Assembly shall be a WILKINS Model 350ADA.
..
WILKINS a Zurn company, 1747 Commerce Way, Paso Robles, CA 93446 Phone: 805/238-7100 Fax:805/238-5766
IN CANADA: ZURN INDUSTRIES LIMITED, 3544 Nashua Dr., Mississauga, Ontario L4V 11-2 Phone:905/405-8272 Fax:905/405-1292
Product Support Help Line: 1-877-BACKFLOW (1-877-222-5356) • Website: http://www.zurn.com Page 2of2
AS1oo(
Flow Test Record
Test Hydrant
Location 6 A
Hydrant IDNo%N_Size Main.....12_ta
.. .
Static
Residual..........
Pressure Drop.. 7O (PDX 1).....K factor for PDX I__11T2
Flow Hydrant(s)
Hydrant 1 location =1LJiE 4ST. 4 9ZtF1
Hydrant.2 location L( '-t - r -
Hydrant 3 location U. it
Hydrant 1 Pitot 6 PSI GPM: -i Size of Orifice________
Hydrant 2 Pitot .L4 -6 PSI GPM: _L ic' I Size of Orifice 2'h Hydrant 3 Pitot7 PSI GPM: E Sfe of Orifice. 2 172 L
Total: 5723
Calculated test and flow data - 0 x PD2 k =Q2
PDI*k
Static .....................
Desired Residual.......20
Pressure Drop (PD 2)..1. LO K factor PD 2:
Z—n5 x I1..61 divided by fl2 equaIE55_)GPM at 20 psi residual
Qi P.D2 k PD I k
Comments: .
Test conducted for:
N 5 #-rzAI.ry LCULeci1c
Conducted by: •1 t5D 5 ¶Pr1X ,< -JA
Date: 12-02 Time; 1O'.O2 A.ii.
AP AS 3UiTTED
C I3M) FIRE r E RTENT
FROM (HON>,JAN 4 2010 8:10,Si-. 8;0eN.7s218e7771 P 3
rlsbad Municipal Water Distr
Potable Water Discharge
Event Report
Date:
24 (o 9
Location:
62 47 c,
Reason for Discharge Event: 1'ijt..i,,iJ
Type of Event: Initial
Dewatering Water Mains t.st JA- Estimated Discharge Flow:
. ej I
Mote: Includes flow testing and flushing 1T 5F
Dewatering Reservoirs
Unscheduled Water Discharge
Clear flow path of debris, surface
contaminants and/or hazardous
materials. Do not remove native
vegetation.
Erosion control, i.e.
sandbags, silt fencing, hay bales,
gravel bags, decreasing the velocity
of discharge water.
__ Start Time 10 00
i,i 02.
t' A End Time I (J
Pre-Dechlorination Residual:
Post-Dechlorination Residual: 0 0 1
(less than 0.1 mg/L)
pH within limits of 6.0 and 9.0 'fES
Upon completion of dewatering, ensure
that the flow path Is free of all
temporary erosion prevention materials.
Upon completion of dewatering, ensure
that any sediment or silted areas are
cleared.
Water-Sampling Performed by:
Comments: -
Submitted by: Reviewd by:
(Name & Date) (Name & Date)
F014 (HON)..JAI'4 4 2010 8 10ST. 8:0e,N=. T21887771 P 4
Flow Test Record Formulas
GPM-Flow
2 '/' 4"
PSI GPM PSI GPM PSI GPM PSI GPM
1 170 16 670 1 430 16 1720
2 240 17 690 2 610 17 1770
3 290 18 710 3 740 18 1820
4 340 19 730 4 860 19 1870
5 380 20 750 5 960 20 1920
6 410 22 790 6 1050 22 2020
7 440 24 820 7 1140 24 2110
8 480 26 860 8 1220 26 2190
9 500 28 890 9 1290 28 2280
10 530 30 920 tO 1360 30 2330
11 560 33 950 ii 1430 32 2430
12 580 34 980 12 1490 34 2510
13 610 36 1010 13 1550 36 2580
14 630 38 1040 14 1610 38 2650
15 650 40 1060 15 1660 40 2720
K Factor Formula
PD K PD K PD K PD K PD K
1= 1.0 21= 5.18 41= 7.43 61= 9.21 81= 10.73
2= 1.45 22= 5.31 42= 7.53 62= 9.29 82= 10.80
3= 1.81 23= 5.44 43= 7.62 63= 9.37 83= 10.87
4= 2.11 24= 5.56 44= 7.72 64= 9.45 84= 10.94
.5=. 2.39 25= 5.69 45= 7.81 65= 9.53 85= 11.01
6= 2.63 26= 5.81 46= 7.91 66= 9.61 86= 11.08
7= 2.86 27= 5.93 47= 8.00 67= 9.69 87= 11.15
8= 3.07 28= 6.05 48= 8.09 68= 9.76 88= 11.22
9= 3.28 29= 6.16 49= 8.18 69= 9.84 89= 11.29
10= 3.47.30= 628 50= 827 90= 1136
"5 .... 6,39...: 51= P 8.36 71= 9.99 91= 11,43
l2.. '3,.$3.: .32 6:50 52 8.4.4. 7.2= . 10.07 .92= 11.49
13= 400 33= 6.6.1 53= 853 73= 1014 93= 1156
14 4.16 34= -.6.7'1- 54' 64 " 10.22' '94= .11.63
15= 4.32 35= 6.82 55= . 8.71 75= 10.29 95= 11.69
16= 4.48 36= 6.93 56= .8.79 76= 10.37 96= 11.76
17= 4.72 37= 7.03 57= 8.88 77= 10.44 97= 11.83)
18= 4.76 38= 7.13 58= 8.96 78= 10,51 98= 11.89
19= 4.90 39= 7.23 59= 9.04 79= 10.59 99= 11.96
20= 5.04 40= 7.33 60= 9.12 80= 10.66 100= 12.02
Io5 ,35
*PD = Pressure drop K = K factor 110 2.67
FOH (NON)JAN 4 2010 8: 1O.'ST. 8:08No.. 7521887771 P
A & D FIRE SPRINKLERS INC.
A Division of A & D Companies
Contract Sales I Service Department
11465 Woodside Avenue, 2 d Floor
Santee, CA 92071
Office: 619.448.1962
FIRE SPRINKLERS INC. Fax: 619.448.1265
FAX Transmission
Thisfacsinii!e transmission may contain confidential and/or attorney/client privileged information belonging to the sender. This information is intended onyfor the use
of the individual or entity named on this transmission sheet. Jfyou are not the intended recipient, or the employee or agent responsible to the Intended recipient, you
should return to sender immediately. You are hereby notified that any disclosure, copying, distribution or the taking of any action in reliance on the contents of this
zelecopied information Is strict(yprohibieed.
24 Hour Emergency Service Date o42O tO
Company Crt-( 'cDv c4/AD a Fire Protection & Life
Safety Products
Fire Alarms and Detection Attention i±1i\ \_1 P 44L L
Systems
Fax No. —
Existing Building Retrofits
Commerciat/ Residential From t-1-A4j-
(Wet, Dry Dry & ?reaction) Subject -rs-r 2
Tenant Improvements
No. of pages H Fabrication / Installation (including this one)
Five Year Certification and
Inspection Services
System Upgrade I Repair
Backflow Preventors and
Underground Fire Mains
Systems Hazard Analysis
Specification and Design
Services (Process 2000)
Ca. Licenced : C16 &B
(#602040)
Certified DBE/MBE
Certified 8A
Dominic Fieri
From: James Weigand
Sent: Friday, December 18, 2009 11:44 AM
To: Eduardo
Cc: Dominic Fieri; Brenda Wardwell
Subject: RE: Pacific Ridge High School (Flow Test)
Attachments: imageool .gif; image002.jpg
Eduardo,
You are asking us to give up a looped fire line that will provide adequate water for a dead end
hydrant based on an incomplete flow test. There is no way either of us would survive a court
challenge to a flow test that includes a flow of 10 psi on one of the hydrants.
If we are going to waive the loop system it must be based on data that is credible. That means at least
a 25% drop between static and residual and hydrant flows that are within understandable limits.
Before re conducting the test, please talk with the water department to make sure that the problem
with the hydrant has been addressed.
I am going to be out of town for a couple weeks. In my absence, Fire Prevention Specialist II Dominic
Fieri will be the acting Fire Marshal. He has been briefed on the problem and can act upon the results
of a complete test.
JMW
oCARLSBAD
Fire: Departmr
James M. Weigand
Fire Marshal
City of Carlsbad Fire Department
Fire Prevention Division
1635 Faraday Avenue
Carlsbad, CA 92008
www.carlsbadca.gov
P: (760) 602-4665
F: (760) 602-8561
james.weigand@carlsbadca.gov
Please consider the environment before printing this email.
Confidentiality Statement: This information is intended only for the addressee shown above. It may contain information that is
privileged, confidential, or otherwise protected from disclosure. Any review, dissemination, or use of this transmission or its contents
by persons other than the addressee is strictly prohibited. .11 you have received this transmission in error, please not ift,' the sender
immediately and follow their instructions regarding the disposition of this e-mail.
From: Eduardo [mailto:eduardo@adcompaniesinc.com]
Sent: Friday, December 11, 2009 8:49 AM
To: James Weigand
Cc: john@adcompaniesinc.com
Subject: Pacific Ridge High School (Flow Test)
Hi Jim,
I just wanted to see if you had made a decision on the fire flow test we did for Pacific Ridge High School
Thank you, have a good weekend.
Design/Engineerin
FIRE SPRINKLERS INC. 11465 Woodside Ave. Ste. 200 Santee Ca, 92071
Web: http://www.adfiresprinklers.com/
Office: 619-448-1962
Fax: 619-448-1265
li-Mail: eduardo(adcoinpaniesinc.com
AL
F—w---61~mv
- Fire Protection by Computer Design
A&D Fire Sprinklers
11465 Woodside Ave.
Santee ca 92071
619448-1962
Job Name Pacific Ridge
Building Underground
Location : 6269 El Fuerte St. Carlsbad CA 92009
System
Contract : F-428
Data File Hydrant Calc-1(1 hyd).WXF
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Page 1
Date 09-02-09
A&D Fire Sprinklers
Pacific Ridge
HYDRAULIC CALCULATIONS
for
Project name: Pacific Ridge High School
Location: 6269 El Fuerte St. Carlsbad CA 92009
Drawing no: Underground
Date: 12-29-09
Design
Remote area number:
Remote area location: Hydrant (HYD)
Occupancy classification: I HYDRANT
Density: - Gpm/SqFt
Area of application: - SqFt
Coverage per sprinkler: - SqFt
Type of sprinklers calculated:
No. of sprinklers calculated:
In-rack demand: - GPM
Hose streams: - GPM
Total water required (including hose streams): 2500 -GPM
Type of system:
Volume of dry or preaction system: -Gal
Water supply Information
Date: 08-20-09
Location: 6269 El Fuerte St. Carlsbad CA 92009
Source: Street Water
Name of contractor: A&D Fire Sprinklers
Address: 11465 Woodside Ave. Santee CA 92071
Phone number: 619-448-1962
Name of designer: Maria lniguez
Authority having jurisdiction: Carlsbad Fire Department
Notes: (Include peaking information or gndded systems here.)
@ 54.29 - Psi
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Water Supply Curve (C)
A&D Fire Sprinklers Page 2 Pacific Ridge Date 09-02-09
City Water Supply: Demand: CI - Static Pressure : 130 Dl - Elevation : 3.681 C2 - Residual Pressure: 60 02 - System Flow C2 - Residual Flow : 3723 D2 - System Pressure : 54.299
Hose(Adj City) Hose ( Demand) : 2500
03- System Demand : 2500
Safety Margin : 42.194
150 V
140
Cl
130 zz
P 120 - -
110 •
-
E 100
S 90
S 80
U 70 V
C2
R 60 D2
E5° V
D3 40 --
30
20
VflA. V VVVV VVV•
10
V VV VVV V V V V V V V I
400 800 1200 1600 2000 2400 .2800 3200 3600 FLOW (NA 1.85)
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Fithngs Used Summary
A&D Fire Sprinklers Page 3 Pacific Ridge Date 09-02-09
Fitting Legend
Abbrev. Name Y2 ~ 1 11/a 11/2 2 2% 3 3% 4 5 6 8 10 12 14 16 18 20 24
E NFPA 1390'Standard Elbow 1 2 2 3 4 5 6 7 6 10 12 14 18 22 27 35 40 45 50 61 F NFPA 1345' Elbow 1 1 1 1 2 2 3 3 3 4 5 7 9 11 13 17 19 21 24 28 G NFPA 13 Gate Valve 0 0 0 0 0 1 1 1 1 2 2 3 4 5 6 7 8 10 11 13 T NFPA 13 90' Flowthru Tee 3 4 5 6 8 10 12 15 17 20 25 30 35 50 60 71 81 91 101 121
Units Summary
Diameter Units
Length Units
Flow Units
Pressure Units
Inches
Feet
US Gallons per Minute
Pounds per Square Inch
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Pressure 1 Flow Summary - STANDARD
A&D Fire Sprinklers Page 4
Pacific Ridge Date 09-02-09
Node Elevation K-Fact Pt Pn Flow Density Area Press No. Actual Actual Req.
HYD 257.5 20.0 na 250D.0 HYD2 255.0 33.37 na UG2 254.0 40.6 na SOR 249.0 54.3 na
The maximum velocity is 26.91 and it occurs in the pipe between nodes HYD and HYD2
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Final Calculations - Hazen-Williams - 2007
A&D Fire Sprinklers Page 5 Pacific Ridge Date 09-02-09
Nodel Elevi K Qa Nom Fitting Pipe CFact Pt to or Ftng's Pe ** Notes Node2 Elev2 Fact Qt Act Eqv. Ln. Total Pf1Ft Pf
HYD 257.500 H250500.00 6 IC 4.304 24.580 140 20.000 to IT 43.037 67.425 1.083 HYD2 255 2500.0 6.16 1E 20.084 92.005 0.1336 12.289 Vel = 26.91
HYD2 255 0.0 8 1 13.591 131.330 150 33.372 to 1G 6.041 72.487 0.433 UG2 254 2500.0 7.98 1 52.855 203.817 0.0333 6.793 Vel = 16.04
UG2 254 0.0 8 3F 40.774 240.400 150 40.598 to IT 52.855 105.711 2.166 SOR 249 2500.0 7.98 2G 12.081 346.111 0.0333 11.535 Vel = 16.04
0.0
SOR 2500.00 54.299 K Factor = 339.27
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
- ==-=----- -/ :- -
212O5— r\
Al
- fil
i
i
-
ll
1312206
/ -
Larr 19
LUr19 \
-- ----- ' - - -
ILJ r
213-122-10 -' * / r
400
213-122-11 J7 213-122-
DJ 07 01-09
'2 PW
040) / /J
67
\ - -
/
0N AND RØLIWI5
0 OWOT It RA#4 0004010 041A00 0 — — — - — -
SSU&L
SCUE
RESON DESCRIPT04 4040 4010
PACWIC WGE 801001. EWANSCN II
SCHOOL
0
?
jc~ s"""j - -
' -gpr
III JI!JI!! ij!ji II All
T rn
I rTI
H
JJiHj rn
;i B
(J•I
qj
h
A
S
S
. IjIIL 0 ill
q L
7
VI
Flow Test Record
Test Hydrant
Location
Hydrant ID No. cO426I%1 Size Main
Static..............
Residual ......... '%03
Pressure Drop.. 2 (Pb! 1).....K factor for PD! 1 S.31
Flow Hydrant(s)
Hydrant I location c S)f. CA1
Hydrant 2 location
Hydrant 3 location
Hydrant] Pitot O PSI GPM:i 60Z Size of Orifice
Hydrant 2 Pitot 10 PSI GPM: 5Z0 Size of Orifice 2/." Hydrant 3 Pitot Igo PSI GPM:jS2 Size of Orifice. '2I'
Total: 1634
(Q1)
Calculated test and flow data - 0 x PD2 k =Q2
PDI*k
Static........................
Desired Residual ....... _2O
Pressure Drop (PD 2)..j0 K factor PD 2:
x (h2 divided by . 3"t equals-&-M GPM at 20 psi residual
Q PD2k PD1k .Q2
Comments: cL V. ciSr
Test conducted for: r 60S .A.
Conducted by: o.. CJr\4S,
Date:__________ Time:jOZ0
- - Fire Protection by Computer Design
A & 0 Fire Sprinklers
11465 Woodside Avenue
Santee, CA, 92071
(619) 448-1962
Job Name : Pacific Ridge
Building Underground
Location 6269 EJ Fuerte St. Carlsbad CA 92009
System
Contract : F-428
Data File : Hydrant Calc-1(1 hyd).WXF
.2
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Water Supply Curve (C)
A & D Fire Sprinklers Page Pacific Ridge Date 09-02-09
City Water Supply: Demand: Cl - Static Pressure : 125 Dl - Elevation : 3.681 C2 - Residual Pressure: 103 D2 - System Flow C2 - Residual Flow : 3534 02 - System Pressure : 54.546
Hose (Adj City)
Hose ( Demand) : 2500
03- System Demand : 2500
Safety Margin : 58.858
150
140
el— 130
120
-
P
110 __ - R -
_-.---.--.-------
__ 2
E 100
S90
S80
u 70
R60D2 —e
E50
40 ____ ______
D3
-
30
20
10
400 800 1200 1600 2000 2400 2800 3200 3600 FLOW ( N A 1.85)
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Fittings Used Summary
A & D Fire Sprinklers Page 2
Pacific Ridge Date 09-02-09
Fitting Legend
Abbrev Name 1/2 % 1 1% 1% 2 21/2 3 31/2 4 5 6 8 10 12 14 16 18 20 24
E NFPAI39O' Standard Elbow 1 2 2 3 4 5; 6 7 B 10 12 14 18 22 27 35 40 45 50 61
F NFPAIS45' Elbow 1 1 1 1 2 2 3 3 3 4 5 7 9 11 13 17 19 21 24 28
G NFPA13 Gate Valve 0 0 0 0 0 1 1 1 1 2 2 3 4 5 6 7 8 10 11 13
I NFPA 13 90' Flow thru Tee 3 4 5 6 8 10 12 15 17 20 25 30 35 50 60 71 81 91 101 121
Units Summary
Diameter Units Inches
Length Units Feet
Flow Units US Gallons per Minute
Pressure Units Pounds per Square Inch
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Pressure I Flow Summary - STANDARD
A & D Fire Sprinklers
, Pacific Ridge
Node
No.
Elevation K-Fact Pt Pn Flow
Actual Actual
HYD 257.5 20.0 na 2500.0
HYD2 255.0 33.37 na
UG2 254.0 40.85 na
SOR 249.0 54.55 na
Page 3
Date 09-02-09
Density Area Press
Req.
The maximum velocity is 26.91 and it occurs in the pipe between nodes HYD and HYD2
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Final Calculations - Hazen-Williams
A & D Fire Sprinklers Page 4
Pacific Ridge Date 09-02-09
Hyd. Qa Dia. Fitting Pipe Pt Pt
Ref. "C" or Ftngs Pe Pv Notes ******
Point at Pf/Ft Eqv. Ln. Total Pf Pn
HYD 2500.00 6.16 IG 4.304 24.580 20.000 Oa = 2500
to 140.0 iT 43.037 67.425 1.083
HYD2 2500.0 0.1336 IE 20.084 92.005 12.289 Vel = 26.91
HYD2 0.0 7.98 IF 13.591 138.750 33,372
to 150.0 1G 6,041 72.487 0.433
UG2 2500.0 0.0333 IT 52.855 211.237 7.041 Vel= 16.04
UG2 0.0 7.98 3F 40.774 240.400 40.846
to 150.0 IT 52.855 105.711 2.166
SOR 2500.0 0.0333 2G 12.081 346.111 11.534 Vel = 16.04
0.0
2500.00 54.546 K Factor = 338.50
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087