Parsley Consulfing
Plan Review Comments for Hagey Residence page 2 of 2
1) There was an error in the hydraulic calculations. The plans show the piping from the base of
the riser to the meter as 11/4" PVC, while the calculations show this diameter as 1 ½". A quick
evaluation, attached to the calculations, shows the required pressure at the source will increase
by slightly more than 2.0 psi if the smaller diameter is installed. This would reduce the
pressure margin at the source to 24.2 (26.2-2.1), with a required pressure of 49.4 psi. This
would equal approximately 67% of the available supply pressure, which does not exceed the
maximum of 90% allowed. No resubmittal or revision to the plans is required.
The following comments are for your information and will appear on every residential sprinkler
review.
The alarm bell must be capable of being heard, above background noise, with doors closed, in
all living areas of the residence. This will be checked at final acceptance.
Pressure required at base of riser will be verified to be available at time of final acceptance.
Sprinkler heads are omitted from bathroom areas under 55 SF in area with noncombustible
plumbing fixtures. Fixtures will be verified at final acceptance.
Sprinkler head blockage or pattern disruption caused by beams or other obstructions will be
verified to not exist at final acceptance inspection.
Sprinkler heads should be located the proper distance from heat sources (stoves, kitchen
ranges, fireplaces, heat diffusers, etc.) This will be checked at final acceptance inspection.
Sprinkler heads located in an unconditioned space (garage, water heater closet, etc.) should be
fast response type with an appropriate temperature rating, commercial heads are acceptable in
these areas.
All exposed piping shall be black steel or copper. Concealed piping can be CPVC plastic.
File: C:\Plan Reviews\Rev2 15267.1 .Docx
HYDRONICS: RESIDENTIAL FIRE SPRINKLER HYDRAULICS 5.8 - SUBMITTAL.
ENGINEERS : PREMIER FIRE PROTECTION. (619)-390-5047.
ADDRESS : 12651 Ridgeton Drive, Lakeside CA 92040.
LICENSE : 939040
DESIGNER : STEVE PETRI
DATE : 06-29-2015
FILE : C:\RESDEN58\HAGEY.RES
JOB NAME : HAGEY RES . TWO HEAD CALC 16 X 16
LOCATION : 2425 JEFFERSON STREET
DESIGN DATA.
it
DESIGN CRITERION: 13D
MIN SPR FLOW : 13 Gpm
AREA PER SPRINKLER : 256 Sq Ft
TOTAL CALCULATED AREA : 512 Sq Ft
TOTAL SPRINKLERS CALCULATED : 2
FLOW DATA.
TOTAL SPRINKLER FLOW : 26.1 Gpm
DOMESTIC DEMAND : 5.0 Gpm
TOTAL WATER REQUIRED : 31.1 Gpm
BASE OF RISER NODE : B
FLOW : 26.1 Gpm
PRESS : 32.7 Psi
AUTHORITY HAVING JURISDICTION : CARLSBAD FIRE
PHONE
These plans have been reviewed for apparent compliance
whit the current appliahlc codes and staidards in lowe
in the jurisdiction. The ooner or contractor ittav utiliie
his rev iesv support it all application for a building
perch' svith the express understanding that this rectess
in to was relics on the oss ncr or contractor or their
prolcrnioital engineer or architect icr sole respocisihuluty
For lull eoiitplcance with said Codes and staitdards.
cctcIuidui the hnildiiict code or for ans.respotisthcllv or
rieticiencies. errors. on issuons or tteczltureiice cit these
plan whetiter or not noled it) this review,
Oalc:ii s- Reviewer:
RECOM MENI) AIPRi)VAI.
RECOMMEND A'I'Rt'vAt.. AS t )T-:f)
(')
FYDRONICS: RESIDENTIAL FIRE SPRINKLER HYDRAULICS 5.8 - SUBMITTAL. Page
ENGINEERS : PREMIER FIRE PROTECTION. (619)-390-5047.
ADDRESS : 12651 Ridgeton Drive, Lakeside CA 92040.
JOB : HAGEY RES . TWO HEAD CALC 16 X 16
DATE: 06-29-2015 FILE: C:\RESDEN58\HAGEY.RES
I SPRINKLER MANUF : VIKING
I MODEL : VK457
I DENSITY : 0.05 Gpm/Sq Ft FIXED PRESS : 6.0 Psi
I AREA / SPR : 256 Sq Ft DESIGN AREA : 512 Sq Ft
I SPRINKLER Q : 13.0 Gpm
I NODES : 10 PIPES : 9
SOURCE I STATIC : 75 Psi RESIDUAL : 74 Psi FLOW : 31 Gpm
NODE ELEVATION K-FACTOR PRESSURE DISCHARGE
NO. Feet Psi Gpm -----------------------------------------------------------
1 21.0 4.90 7.0 13.0
2 21.0 4.90 7.2 13.1
3 21.0 7.4
4 21.0 17.1
T 11.0 25.7
B 0.0 32.7
A 0.0 37.4 DOME 5.0
Al 0.0 39.3
M 0.0 45.3
S 0.0 SOURCE 47.8 31.1
SPRINKLERS FLOWING : 2
AREA PER SPRINKLER : 256 Sq Ft
TOTAL DESIGN AREA : 512 Sq Ft
MIN SPRINKLER FLOW : 13 Gpm
REQUIRED DENSITY : 0.051 Gpm/Sq Ft
COMPUTED DENSITY : 0.051 Gpm/Sq Ft
TOTAL SPRINKLER FLOW : 26.1 Gpm
TOTAL DOMESTIC FLOW : 5.0 Gpm
TOTAL WATER REQUIRED : 31.1 Gpm
TOTAL SPRINKLER PRESS : 41.8 Psi
FIXED PRESS LOSS : [J psi
Copyright (2012)
SUPPLY PRESS AVAILABLE : Psi by
DEMAND PRESS REQUIRED : 47.8 Psi Hydronics Engineering
PRESSURE CUSHION : Psi 34119 Fremont Bi, Suite 609
Fremont, CA, 94555
MAXIMUM VELOCITY : 12.8 F/S (800) 845-9819
HYDRONICS: RESIDENTIAL FIRE SPRINKLER HYDRAULICS 5.8 - SUBMITTAL. Page 2
ENGINEERS : PREMIER FIRE PROTECTION. (619)-390-5047.
ADDRESS : 12651 Ridgeton Drive, Lakeside CA 92040.
JOB : HAGEY RES . TWO HEAD CALC 16 X 16
DATE: 06-29-2015 FILE: C:\RESDEN58\HAGEY.RES
PIPE BEG FLOW K-FACTOR LENGTH C-FACTOR PRESSURE
NO. Gpm FITTING TYPE FTG FRI-LOSS (Psi)
END DIAMETER TOTAL (Psi/Ft)
1 q= 13.0 K=
-------------------------------------------------------------------------------
4.90 L= 7.0 Pt 7.0 Pt 7.0
1 Q= 13.0 F= B F= 5.0 C= 150 Pe 0.0 Pv -0.1
• Vel= 4.4 D= 1.101 TL= 12.0 0.0306 Pf 0.4 Pn 6.9
3 Pt 7.4
2 q= 13.1 K= 4.90
--------------------------------------------------------------------------
L= 2.0 Pt 7.2 Pt 7.2
2 Q= 13.1 F= B F= 5.0 C= 150 Pe 0.0 Pv -0.1
Vel= 4.4 D= 1.101 TL= 7.0 0.0312 Pf 0.2 Pn 7.0
3 Pt 7.4
3 q= 0.0 K= 0.00
--------------------------------------------------------------------------
L= 63.0 Pt 7.4 Pt 7.4
3 Q= 26.1 F= 11RBB4EF= 25.0 C= 150 Pe 0.0 Pv -0.5
Vel= 8.8 D= 1.101 TL= 88.0 0.1114 Pf 9.8 Pn 6.9
4 Pt 17.1
4 q= 0.0 K= 0.00
--------------------------------------------------------------------------
L= 23.0 Pt 17.1 Pt 17.1
4 . Q= 26.1 F= RRLL F= 16.0 C= 150 Pe 4.3 Pv -0.5
Vel= 8.8 D= 1.101 TL= 39.0 0.1114 Pf 4.3 Pn 16.6
T Pt 25.7
T q 0.0 K= 0.00
--------------------------------------------------------------------------
L= 10.0 Pt 25.7 Pt 25.7
5 Q= 26.1 F= RRSC F= 10.0 C= 150 Pe 4.8 Pv -0.5
Vel= 8.8 D= 1.101 TL= 20.0 0.1114 Pf 2.2 Pn 25.2
B Pt 32.7
B q= 0.0 K= 0.00
--------------------------------------------------------------------------
L= 5.0 Pt 32.7 Pt 32.7
6 Q= 26.1 F= LLL F= 21.0 C= 150 Pe 0.0 Pv -0.8
Vel= 10.8 D= 0.995 TL= 26.0 0.1824 Pf 4.7 Pn 31.9
A Pt 37.4
q= 5.0 DOME L= 60.0 Pt 37.4 Pt 37.4
7 , fl' ) Q= 31.1 F= LLEECC F= 12.0 C= 150 Pe 0.0 Pv -0.2
\ )) Vel= 5.0 D= 1.590 TL= 72.0 0.0257 Pf 1.9 Pn 37.3
---------------------------------------------------------------------------
Pt 39.3
Al Q= 31.1 Pt 39.3
MET FIXED PRESSURE LOSS Valve 6.0
M Pt 45.3
M q= 0.0 K= 0.00
--------------------------------------------------------------------------
L= 10.0 Pt 45.3 Pt 45.3
8 Q= 31.1 F=G F= 0.0 C=150 Pe 0.0 Pv -1.1
Vel= 12.8 D= 0.995 TL= 10.0 0.2522 Pf 2.5 Pn 44.2
S -------------------------------------------------------------------------- Pt 47.8
Q= 31.1 <<<
--------------------------------------------------------------------------
-------------------------------------------------------------------------- SOURCE >>> Pt 47.8
E=45-Elb L=90-Elb B=TeeBch R=TeeRun C=CouPlg S=SwgChk G=GatVlv
HYDRONICS: RESIDENTIAL FIRE SPRINKLER HYDRAULICS 5.8 - SUBMITTAL.
ENGINEERS : PREMIER FIRE PROTECTION. (619)-390-5047.
ADDRESS : 12651 Ridgeton Drive, Lakeside CA 92040.
JOB : HAGEY RES . TWO HEAD CALC 16 X 16
FILE : C:\RESDEN58\HAGEY.RES
DATE : 06-29-2015
PSI FIRE SPRINKLER HYDRAULIC GRAPH
90
80
70
60
50
40
30
20
10
100 150 200 250 300
-0 Water Supply
350 400 450 500
FLOW - GPM
Static : 75 Psi
Resid : 74 Psi
Flow : 31 Gpm
S Water Demand
Avi Press : 74.0 Psi @ 31 Gpm
Req Press : 47.8 Psi @ 31 Gpm
Press Cush: 26.2 Psi
Copyright: Hydronics Engineering, 2012.
34119 Fremont Bi, Suite 609
Fremont, CA 94555.
(800) 845-9819.
Same Flow - Different Pipe Diameter
Flow (Q) 31 31.000
Size (D) 1.59 1.36
C-Factor 150 150
LPF 0.026 0.055
Velocity 5.009 6.847
Length 72.000 72.000
Pf 1.840 3.939
Difference 2.098585739