Fire Sprinklers
Applied: 03/24/2022
Issued: 04/07/2022
Finaled Close Out: 06/22/2022
Final Inspection:
INSPECTOR: Salcedo, Felix
Project Title:
Description: CAMSTON WRATHER -SPRINKLER TI IN OFFICES, RESTROOM & PREFAB CONTAINER (16 HEADS)
Applicant: FPContractor:
EPIC FIRE PROTECTION INC EPIC FIRE PROTECTION INC
ADAM BOISVERT 765 TURTLE POINT WAY
765 TURTLE POINT WAY SAN MARCOS, CA 92069-8126
SAN MARCOS, CA 92069-8126 (760) 310-6122
(760) 310-6122
FEE AMOUNT
FIRE NFPA 13 or 13R System 7-100 heads $607.00
Total Fees: $607.00 Total Payments To Date: $607.00 Balance Due: $0.00
Fire Department Page 1 of 1
1635 Faraday Avenue, Carlsbad CA 92008-7314 1 760-602-4665 760-602-8561 f I www.carlsbadca.gov
[",-I.A7ERI AL DATA SUBh1177AL
CIAh1STON WRATHER T.I.
CARLSBAD, CA
EPIC FIRE PROTECTION, INC.
75 TURTLE POINT WAY
SAN hIARCOS, CA 020GO
(7GO)310-022 FAX(7O)78-055
A Lightweight Schedule 40 Replacement Pipe
That Has a Corrosion Resistance Ratio of 1.0
Bull Moose Tube Company has been making pipe for a long time and is recognized as a producer of quality pipe
products. Eddythread 40 is designed with the same thoroughness as our other fine pipe products and now our
customers have an option to buy a carefully designed replacement for Schedule 40 that:
Has a Corrosion Resistance Ratio of 1.0
Has a Pressure Rating of 300 psi
Is Lighter Weight Than Schedule 40
Is Approved by Factory Mutual and Listed by Underwriters Laboratories
Is Produced in Accordance to ASTM A-135 and A-795
Can be Used With Standard Schedule 40 Threaded Fittings,
Couplings and Valves
Is Produced From Steel With Excellent Properties of
Strength and Threadability
Can be Used in Wet, Dry, Preaction, and Deluge Type Sprinkler Systems*
Offers Lower Freight Costs
EDDYTHREAD 40 SPECIFICATIONS
-i 11
1 1.461 1.083 70
11/4 2.070 1.418 51
11/2 2.547 1.654 44
2 3.308 2.123 30
CORROSION RESISTANCE RATIOS
() I 4 I 1
1 1.00 1.00
11/4 1.00 1.00
11/2 1.00 1.00
2 1.00 1.00
* Eddythread 40 can be hot dipped galvanized to meet FM'S requirement for dry systems
1819 Clarkson Road For additional information,
Chesterfield, MO 63017 contact your salesperson today at 0 (800) 325-4467 (800) 325-4467 or (636) 537-2600 LISTED BULL. MOOSE TUBE COMPAfJV FAX: (636) 537-2645 in the USA, or from Canada
______ www.bullmoosetube.com call (800) 882-4666
A CRE company e-mail:sa1es@bu11moosetube.com <i > APPROVED
All information contained herein is accurate as known at the time of publication. Bull Moose Tube reserves the tight to change product specifications without notice and without incurring obligation.
8/08
Worldwide tqC00 Contacts www.tyco-fire.com
Series TYFRB, 56 K-factor
Upright, Pendent, and Recessed Pendent Sprinklers
Quick Response, Standard Coverage
General
Description
The TYCO Series TY-FRB, 5.6 K-factor,
Upright (TY313) and Pendent (TY323)
Sprinklers described in this data sheet
are quick response, standard coverage,
decorative 3 mm glass bulb-type spray
sprinklers designed for use in light or
ordinary hazard, commercial occupan-
cies such as banks, hotels, and shop-
ping malls.
The recessed version of the Series
TY-FRB Pendent Sprinkler, where
applicable, is intended for use in areas
with a finished ceiling. This recessed
pendent sprinkler uses one of the
following:
A two-piece Style 15 Recessed
Escutcheon with recessed adjust-
ment up to 5/8 in. (15,9 mm) from
the flush pendent position.
A two-piece Style 20 Recessed
Escutcheon with recessed adjust-
ment up to 1/2 in. (12,7 mm) from
the flush pendent position.
The adjustment provided by the
Recessed Escutcheon reduces the
accuracy to which the fixed pipe drops
to the sprinklers must be cut.
Intermediate level versions of Series
TY-FRB Sprinklers are described in
Technical Data Sheet TFP357. Sprin-
kler guards and shields are described
in Technical Data Sheet TFP780.
IMPORTANT
Refer to Technical Data Sheet
TFP2300 for warnings pertaining to
regulatory and health information.
Always refer to Technical Data
Sheet TFP700 for the "INSTALLER
WARNING" that provides cautions
with respect to handling and instal-
lation of sprinkler systems and com-
ponents. Improper handling and
installation can permanently damage
a sprinkler system or its compo-
nents and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
Page 1 of 4
_NOTICE ]
The TYCO Series TY-FRB Sprinklers
described herein must be installed
and maintained in compliance with
this document, as well as with the
applicable standards of the National
Fire Protection Association, in addition
to the standards of any other authori-
ties having jurisdiction. Failure to do so
may impair the performance of these
devices.
The owner is responsible for main-
taining their fire protection system
and devices in proper operating con-
dition. Contact the installing contrac-
tor or product manufacturer with any
questions.
Sprinkler
Identification
Number (SIN)
TY313.... Upright 5.6K, 1/2 in. NPT
TY323. .. .Pendent 5.6K, 1/2 in. NPT
Technical
Data
Approvals
Refer to Table A
Maximum Working Pressure
175 psi (12.1 bar)
250 psi (17.2 bar)*
The maximum working pressure of 250 psi (17.2 bar)
only applies to the listing by Underwriters Laborato-
ries, Inc. (UL).
Discharge Coefficient
K=5.6 GPM/psi" (80,6 LPM/bar1/')
Temperature Rating
Refer to Table A
Finishes
Sprinkler: Refer to Table B
Recessed Escutcheon: White Coated,
Black Coated, Chrome Plated, or Brass
Plated
Physical Characteristics
Frame ............................Bronze
Button ......................Brass/Copper
Sealing Assembly ... Stainless Steel w/TEFLON Bulb...............................Glass
Compression Screw .................Bronze
Deflector ..........................Bronze
AUGUST 2018
Operation
The glass bulb contains a fluid which
expands when exposed to heat. When
the rated temperature is reached, the
fluid expands sufficiently to shatter the
glass bulb, allowing the sprinkler to
activate and water to flow.
Design
Criteria
The TYCO Series TY-FRB, 5.6 K-factor,
Upright (TY313) and Pendent (TY323)
Sprinklers are intended for fire protec-
tion systems designed in accordance
with the standard installation rules
recognized by the applicable Listing or
Approval agency (such as, UL Listing
is based on the requirements of NFPA
13, and FM Approval is based on the
requirements of FM's Loss Prevention
Data Sheets). Only the Style 15 or Style
20 Recessed Escutcheon is to be used
for recessed pendent installations.
TFPI72
2-7/8 (73,0 mm) DIA.
TFPI72
Page 2 of 4
Components: * Temperature rating is ** Pipe thread connections per ISO 7-1 1 - Frame 4 - Bulb indicated on Deflector, can be provided on special request. 2 - Button 5 - Compression
3 - Sealing Screw ESCUTCHEON PLATE 1/2 7/16 (11,1 mm) Assembly 6 - Deflector* DEFLECTOR* SEATING SURFACE NPT** NOMINAL MAKE-IN
* 6
_______ I NOMINAL 2 \—E
2"
:S
I I I I
(11,1mm) ______
MAKE-IN (50,8 mm)
_____
7/16"
I WR 3 -
" (50,8 mm) I 'N.
______________ I I Fl
I 1/2 NPT** DEFLECTOR*
STYLE 150r20
RECESSED
ESCUTCHEON
CROSS SECTION UPRIGHT PENDENT RECESSED PENDENT
FIGURE 1
SERIES TY-FRB UPRIGHT (TY313) AND PENDENT (TY323) SPRINKLERS
5.6 K-FACTOR, 1/2 INCH NPT, QUICK RESPONSE
Installation
The TYCO Series TY-FRB, 5.6 K-factor,
Upright (TY313) and Pendent (TY323)
Sprinklers must be installed in accor-
dance with this section.
General Instructions
Do not install any bulb-type sprin-
kler if the bulb is cracked or there is
a loss of liquid from the bulb. With the
sprinkler held horizontally, a small air
bubble should be present. The diam-
eter of the air bubble is approximately
1/16 in. (1,6 mm) for the 135°F (57°C) and
3/32 in. (2,4 mm) for the 286°F (141°C)
temperature ratings.
A leak-tight 1/2 in. NPT sprinkler joint
should be obtained by applying a
minimum to maximum torque of 7 to
14 lb-ft (9,5 to 19,0 N.m). Higher levels
of torque can distort the sprinkler Inlet
with consequent leakage or impairment
of the sprinkler.
Do not attempt to compensate for
insufficient adjustment in the Escutch-
eon Plate by under- or over-tightening
the sprinkler. Re-adjust the position of
the sprinkler fitting to suit.
Upright and Pendent Sprinklers
The Series TY-FRB Upright and
Pendent Sprinklers must be installed
in accordance with the following
instructions.
Step 1. Install Pendent sprinklers in the
pendent position. Install upright sprin-
klers in the upright position.
Step 2. With pipe-thread sealant
applied to the pipe threads, hand-
tighten the sprinkler into the sprinkler
fitting.
Step 3. Tighten the sprinkler into the
sprinkler fitting using only the W-Type
6 Sprinkler Wrench (Figure 2). With ref-
erence to Figure 1, apply the W-Type 6
Sprinkler Wrench to the wrench flats.
Torque sprinklers 7 to 14 lb-ft (9,5 to
19,0 Nm).
Recessed Pendent Sprinklers
The Series TY-FRB Recessed Pendent
Sprinklers must be installed in accor-
dance with the following instructions.
Step A. After installing the Style 15
or Style 20 Mounting Plate over the
sprinkler threads, and with pipe-thread
sealant applied to the pipe threads,
hand-tighten the sprinkler into the
sprinkler fitting.
Step B. Tighten the sprinkler into the
sprinkler fitting using only the W-Type
7 Recessed Sprinkler Wrench (Figure
3). With reference to Figure 1, apply the
W-Type 7 Recessed Sprinkler Wrench
to the sprinkler wrench flats. Torque
sprinklers 7 to 14 lb-ft (9,5 to 19,0 N'm).
Step C. After ceiling installation and
finishing, slide on the Style 15 or Style
20 Closure over the Series TY-FRB
Sprinkler and push the Closure over the
Mounting Plate until its flange comes in
contact with the ceiling.
/ WRENCH RECESS
/ (USE ONLY
FIGURE 2
W-TYPE 6
SPRINKLER WRENCH
WRENCH
RECESS
PUSH WRENCH
IN TO ENSURE
ENGAGEMENT
WITH SPRINKLER
WRENCHING AREA
FIGURE 3
W-TYPE 7 RECESSED
SPRINKLER WRENCH
TFPI72
Page 3 of 4
Care and
Maintenance
The TYCO Series TY-FRB, 5.6 K-factor,
Upright (1Y313) and Pendent (TY323)
Sprinklers must be maintained and ser-
viced in accordance with this section.
Before closing a fire protection system
main control valve for maintenance
work on the fire protection system
that it controls, obtain permission to
shut down the affected fire protection
systems from the proper authorities
and notify all personnel who may be
affected by this action.
Absence of the outer piece of an
escutcheon, which is used to cover
a clearance hole, can delay sprinkler
operation in a fire situation.
The owner must assure that the sprin-
klers are not used for hanging any
objects and that the sprinklers are only
cleaned by means of gently dusting
with a feather duster; otherwise, non-
operation in the event of a fire or inad-
vertent operation may result.
Sprinklers which are found to be
leaking or exhibiting visible signs of
corrosion must be replaced.
Automatic sprinklers must never be
painted, plated, coated, or other-
wise altered after leaving the factory.
Modified sprinklers must be replaced.
Sprinklers that have been exposed to
corrosive products of combustion, but
have not operated, should be replaced
if they cannot be completely cleaned
by wiping the sprinkler with a cloth or
by brushing it with a soft bristle brush.
Care must be exercised to avoid
damage to the sprinklers before,
during, and after installation. Sprin-
klers damaged by dropping, striking,
wrench twist/slippage, or the like, must
be replaced. Also, replace any sprin-
kler that has a cracked bulb or that has
lost liquid from its bulb. (Ref. Installa-
tion Section.)
The owner is responsible for the
inspection, testing, and maintenance of
their fire protection system and devices
in compliance with this document, as
well as with the applicable standards
of the National Fire Protection Asso-
ciation (e.g., NFPA 25), in addition to
the standards of any other authorities
having jurisdiction. Contact the install-
ing contractor or product manufacturer
with any questions.
Automatic sprinkler systems are rec-
ommended to be inspected, tested,
and maintained by a qualified Inspec-
tion Service in accordance with local
requirements and/or national codes.
Limited
Warranty
For warranty terms and conditions, visit
www.tyco-fire.com.
Ordering
Procedure
Contact your local distributor for avail-
ability. When placing an order, indicate
the full product name and Part Number
(P/N).
Sprinkler Assemblies with NPT
Thread Connections
Specify: Series TY-FRB Upright or
Pendent (specify) Sprinkler, SIN
(specify), K=5.6, Quick Response,
(specify) temperature rating, (specify)
finish, P/N (specify, refer to Table A).
Recessed Escutcheon
Specify: Style 15 Recessed Escutch-
eon with (specify*) finish, P/N (specify*)
Specify: Style 20 Recessed Escutch-
eon with (specify*) finish, P/N (specify*)
* Refer to Technical Data Sheet TFP770
Sprinkler Wrench
Specify: W-Type 6 Sprinkler Wrench,
P/N 56-000-6-387
Specify: W-Type 7 Sprinkler Wrench,
P/N 56-850-4-001
2-7/8 DIA.
(73,0 mm)
- 2-1/4 DIA.
FITTING
FACE OF (57,2 mm)
SPRINKLER
5/8 (15,9 mm)
3/8±5/16"
FLUSH
(9,5±7,9 mm)
SURFACE (3,2 mm) MOUNTING 1/8 J
CLOSURE SERIES MOUNTING 1-3/8" (34,9 mm)
TY-FRB PLATE 3/4" (19,1 mm)
FIGURE 4
SERIES TY-FRB RECESSED PENDENT SPRINKLER ASSEMBLY (TY323)
WITH TWO PIECE 5/8 INCH TOTAL ADJUSTMENT STYLE 15
RECESSED ESCUTCHEON
- 2-7/8" DIA.
(73,0 mm)
FACE OF
SPRINKLER - 2-1/4" DIA.
FITTING (57,2 mm)
5/16±1/4"
\
1/2 (12,7 mm) (7,9±6,4 mm)
FLUSH I
MOUNTING \ 1/8" j I
SURFACE \ (3,2 mm)
CLOSURE SERIES MOUNTING 1-3/8" (34,9 mm)
TYFRB PLATE 7/8' (22,2 mm)
FIGURE 5
SERIES TY-FRB RECESSED PENDENT SPRINKLER ASSEMBLY (TY323)
WITH TWO PIECE 1/2 INCH TOTAL ADJUSTMENT STYLE 20
RECESSED ESCUTCHEON
TFPI72
Page 4 of 4
SPRINKLER FINISH (See Note 7)
K
FACTOR TYPE BULB LIQUID
COLOR TEMPERATU RE NATURAL
BRASS
I CHROME
PLATED J POLYESTER-
135°F (57°C) Orange
UPRIGHT
(TY313) 155°F (68°C) Red
175°F (79°C) Yellow and 1, 2, 3, 4, 5, 6
5.6
1/2 in. NPT
PENDENT
(TY323)
________________
200°F (93°C) Green
286°F (141°C) Blue
135°F (57°C) Orange
RECESSED
PENDENT
(TY323)
Figures 4a and 5b
1,2,3,4 155°F (68°C) Red
175°F (79°C) Yellow
200°F (93°C) Green
Notes:
Listed by Underwriters Laboratories, Inc., (UL) as Quick Response Sprinklers.
Listed by Underwriters Laboratories, Inc., for use in Canada (C-UL) as Quick Response Sprinklers.
Approved by Factory Mutual Research Corporation (FM) as Quick Response Sprinklers.
Approved by the City of New York under MEA 354-01-E.
VdS Approved (For details, contact Johnson Controls, Enschede, Netherlands, Tel. 31-53-428-4444/Fax 31-54-428-3377.)
Approved by the Loss Prevention Certification Board (LPCB Ref. No. 094a/06) as Quick Response Sprinklers.
Where Polyester Coated Sprinklers are noted to be UL and C-UL Listed, the sprinklers are UL and C-UL Listed as Corrosion-Resistant Sprinklers.
Installed with Style 15 (1/2 in. NPT) 5/8 in. Total Adjustment Recessed Escutcheon, as applicable.
Installed with Style 20 (1/2 in. NPT) 1/2 in. Total Adjustment Recessed Escutcheon, as applicable.
Frame and Deflector only. Listings and approvals apply to color (Special Order).
TABLE A
LABORATORY LISTINGS AND APPROVALS FOR
5.6 K-FACTOR SPRINKLERS
P/Na77_XX__XXX________
SIN SPRINKLER TEMPERATURE
FINISH RATINGS
370 5.6K UPRIGHT (1/2 in.NPT) TY313 1 NATURAL BRASS 135 135°F (57°C)
371 5.6K PENDENT (1/2 i PURE WHITE (RAL9010)a rt.NPT) TY323 POLYESTER 155 155°F (68°C)
Notes: SIGNAL WHITE (RAL9003) a. Use suffix "I" for ISO 7-I connection; for example, 4 175°F (79°C)POLYESTER 175
77-370-4-175-I -
JET BLACK (RAL9005) 200 200°F (93°C) POLYESTER
9 CHROME PLATED 286 286°F (141°C)
Notes:
a. Eastern Hemisphere sales only
TABLE B
SERIES TY-FRB UPRIGHTAND PENDENT SPRINKLERS
PART NUMBER SELECTION
1400 Pennbrook Parkway, Lansdale, PA 19446 I Telephone +1-215-382-0700 ,JJ 0r
02518 Johnson Controls. All rights reserved. All specifications and other information shown were current anal document revision date and are subject to change without notice. Johnson
NATIONAL FIRE PROTECTION ASSOCIATION and NFPA ole rnIsternd l,udon,anks ci Nctionni FI,e Protection Assoolollon; Controls TEFLON isa regiotoled l,odcmo,k 01 DoPvnl
Threaded Mechanical Branch Tee
The MT-30 mechanical tee serves the
same function as the MI-] and MT-8, but
uses a steel electro-plated u-bolt to save
space and for easier installation in tight
places.The MT-30 is ideal for direct
connections with sprinkler heads and
drop nipples. The MT-90 is the BSPT
equivalent.
For the latest UL/ULC listed, LPCB, VdS
and FM Approved pressure ratings versus
pipe schedule, see www.anvilintl.com or
contact your local Anvil Representative.
LISTED APPROVED
For Listings/Approval Details and Limitations,
visit our website at waw.anvllintLcOm or
contact an Anvil* Sales Representative.
HOUSING:
Ductile Iron conforming to ASTM A-536, Grade 65-45-12
U-BOLT & NUTS:
U-bolt is carbon steel SAE J429 Gr. 2, zinc plated complete with hex flanged lock
nuts conforming to ASTM A-563 Gr. A or B of SAE J995 Gr. 2.
THREADS:
NPT per ANSI/ASME 81.20.1.
COATINGS:
Zinc Electroplated
Other available options: Example: RAL3000 or RAL9000 Series
GASKETS: Materials
Properties as designated in accordance with ASTM D-2000.
0 Grade "E" EPDM (Green color code)
-40°F to 230°F (Service Temperature Range)(-40°C to 110°C)
Recommended for water service, diluted acids, alkalies solutions,
oil-free air and many chemical services not involving hydrocarbons, oils
or gases.
NOT FOR USE WITH HYDROCARBONS.
PROJECT INFORMATION APPROVAL STAMP
Project: 0 Approved
Address:[]Approved as noted
Contractor: []Not approved
Engineer: Remarks:
Submittal Date:
Notes 1:
Notes 2:
FP-10.16
<E~
Threaded Mechanical Branch Tee
T
I- 1 [.3
iIc1u THREADED Ik'J
Nominal Hole Dimensions ___________ Max. Dimensions
Approx. Size O.D.
Mm. Diameter
___________
Max. Diameter
I
i Workng
PressureA A B C I
Take-out Wt
In/DN(mni) In/mm In/mm In/mm PSI/bar In/mm In/mm In/mm In /mm Lbs/Kg ]¼XY2 1.660x0.840 1/l6 15116 300 2/8 31/2 21/4 P/s 08 32x12 42.4x21.3 30 33 20.7 1 54 89 57.2 42 0.4 11/4 x '/4 1.660 x 1.050 1/16 PAt 300 21/8 31/2 21/4 ]5/ 0.8 32 x19 42.4 x 26.7 30 33 20.7 54 89 57.2 42 0.4 1¼x 1 1.660x 1.315 1116 ]5/j 300 21/4 31/2 21/4 P/s 1.1 32x25 42.4 x33.7 30 33 20,7 58 89 57.2 41 0.5 P/2x½ 1.900x0.840 1/jt 1%t 300 21/4 31/2 2¼ 1Y4 0.8 40x12 48.3x21.3 30 33 1 20.7 57 89 57.2 48 0.4 11/2 x3h 1.900x 1.050 ]3As P/it 300 21/4 31/2 21/4 1% 0.9 40x19 48.3x26.7 30 33 20.7 57 89 57.2 48 0.4 1½x1 1.900x1.315 13A6 1/t6 300 2% 31/3 21/4 1/4 1.1 40x25 48.3 x33.7 30 33 20.7 61 89 57.2 48 0.5 2 x ½ 2.375 x 0.840 P/is 1%6 300 21/2 33/4 21/4 2 0.9 SOs 12 60.3x21.3 30 33 1 20.7 64 95 57.2 51 0.4 2 x 1/4 2.375 x 1.050 ]3/ 1 5/ 300 21/2 31/4 21/4 2 0.9 50x19 60,3x26.7 30 33 20.7 64 95 57.2 51 0.4 2 x 1 2.375 x 1.315 ]3/ 1!i6 300 21/a 31/4 2114 2 Li 50Y 25 60,3x 33.7 30 33 20.7 67 95 57.2 50 0.5 2½x½ 2J75x0.840 P/is P'is 300 21/4 41/4 21/4 21/4 0.9 65x 12 73.0 x21.3 30 33 20.7 1 70 108 57.2 57 0.4 21/2 x 1/4 2.875 x 1.050 )3/j P/is 300 2% 41/4 2¼ 21/4 0.9 65x19 73,0x26.7 30 33 20.7 70 108 57.2 57 0.4 2½ xi 2.875 x 1.315 PAt 1%6 300 2¼ 41/4 21/4 21/4 1.1 65x25 73.0x33,7 30 33 20.7 73 1 108 57.2 56 0.5 BSP equivalent is available as a MT-90.
A -Working Pressure Ratings are for reference only and based an Sch. 10 and Sch. 40 pipe. For the latest UL/ULC, FM, VdS and LPCB pressure ratings versus pipe schedule, please visit anvilintl.com or contact your local Anvil Representative.
Note: lighten nuts alternately to a recommended torque of 18-22 ft-lbs. (25-30 Nm) on pipe wall less than schedule 10 (Din 2440) or 23-27 ft-lbs. (31-37 Nm) an pipe walls schedule 10 (DIN 2440) and above.
I WARNING
For dry pipe systems and freezer applications
lubrication of the gasket is required,
Gruvioke XiremeTM Lubricant is required.
FP-10.16
Threaded Mechanical Branch Tees MAWIL
qCSPF/RN~V~L
Alignment
U Align the gasket and fitting above the 1.19(30mm) pipe hole.
BRANCH SIZE HOLE SAW ISIZE PIPE LENGTH
Inches (mm) Inches +1,, -o (mm +3, -0) (088 note)
1 1.19 5
25 30.23 1.52
Note: Flow Data is expressed as Feet/Meters of Schedule 40 steel
outlet pipe with a "Hazen-Williams coefficient of friction value of 120'
75 Housing Assembly
Attach the U-bolt from the other side and fasten the nuts
finger tight.
Step 3
Specified bolt torque is for the u-bolt used on SPF® threaded
mechanical branches. The nuts must be tightened alternately and
evenly until fully tightened.
Caution: Proper torquing of mechanical branch u-bolt is required
to obtain specified performance. Over torquing the u-bolt may result in damage to the pipe and/or casting which could result
In pipe joint separation. Under torquing the u-bolt may result in
lower pressure retention capabilities, lower bend load capabilities,
joint leakage and pipe joint separation. Pipe joint separation may
result in significant property damage and serious injury.
3Tighten Nuts
Making sure the fitting is properly located over the pipe hole,
use a 9/16" (14 mm) wrench to tighten the nuts alternatively to a
recommended torque of 18-22 ft.-lbs. (25-30 Nm) on pipe wall
less than schedule 10 (DIN 2440) or 23-27 ft-lbs. (31-37 Nm)
on pipe walls schedule 10 (DIN 2440) and above.
FP-10.16
1/2 through 2" Size
Rounded Edge Design
USTED APPROVED
21/2 through 8" Size
]F]1g0 69 (Formerly Afcon Fig. 300) Adjustable Swivel Ring, Tapped Per NFPA Standards
Size Range: /2' through 8"
Material: Carbon steel
Finish: Strap is Pre-Galvanized Zinc Material. Nut is Zinc Plated.
Service: Recommended for suspension of non-insulated stationary pipe line.
Maximum Temperature: 4500 F
Approvals: Complies with Federal Specification A-A-1192A (Type 10), WW-H-171-E (Type 10),
and ANSI/MSS SP-58 (Type 10). UL Listed and FM Approved (Sizes 3/4"
- 8").
Features:
1/2" - 2" sizes designed for use with steel and CPVC piping and manufactured with
FBC System Compatible oil.
Threads are countersunk so that they cannot become burred or damaged.
Knurled swivel nut provides vertical adjustment after piping is in place.
Captured swivel nut in the 1/2" through 6" sizes. The capture is permanent in the bottom
portion of the band, allowing the hanger to be opened during installation if desired, but
not allowing the nut to fall completely out.
Ordering: Specify size, figure number and name.
A Non-captured nut also available upon request. 4
11/4" through 2" pipe 21/2 through 8" pipe
FIG. 69: DIMENSIONS (IN) o LOADS (LBS) o WEIGHT_(LBS)
Pipe Size Max Load Weight Rod Size
A B C F G
Width
1,4
300
0.10
%
1/811/4
2,4 2 19A6
11/s
3/4 0.10 2/4 1/8 15A6
1 0.10 29A6 111A6 1
0.10 2/8 1A
1/8 1/8 1'/2 0.10 2/
2 0.11 31/4 2/s
2½ 525 0.20 4 2/4 15A6
3/4
3 0.20 313A6 21 '/16 1/is
4 650 0.30 411/is 313A6 1/16 4% 5
1,000
0.54
1/2
55A6
6 0.65 611/16 59A6 21/4
8 1.00 8/is 7/is 1 314
IQXG
1/3m through 1" pipe
PROJECT INFORMATION APPROVAL STAMP I
Project: Approved
Address: []Approved as noted
Contractor: []Not approved
Engineer: Remarks:
Submittal Date:
Notes 1:
Notes 2:
PH-1.18
MMYS
APPROVED
UL Max Pipe UL Test Minimum FM Max FM Test Minimum l
BX P/N WOOD UL Size, in. Load Wood FM Pipe Size Load Wood
Thickness, In, Thickness 4 In.
8007957 GST 10 X CPVC 1-1/2 300 1.5
- 8020957 SWG 10 X CPVC 1-1/2 300 1.5
8008957 GST 20 X 2-1/2 850 1.5 X 4 1475 1.5
8068925 GST 2OSS X 2-1/2 850 1.5
8010957 GST 30 X 4 1500 1.5 X 4 1475 1.5
-8009925 GST 25-380 X 4 1500 1.5 X 4 1475 1.5
8022925 SWG 25-380 X 3-1/2 - 4" 1500 1.5 X 4 1475 1.5
8021957 SWG 20 X 2-1/2 -3k" 1250 1.5
8073925 SWG 2OSS X 2-1/2 1250 1.5
8139957 SH GST 2O X 3 1050 1.5 X 4 1475 1.5
8141957 SH GST 3O X 4 1500 1.5 X 4 1475 1.5
8140957 SH GST 20 SS X 3 1050 1.5
8142957 SH GST 3OSS X 4 1500 1.5
UL Max Pipe UL Test Minimum FM Max FM Test Minimum
BX PIN STEEL UL Size, in. load Steel FM Pipe Size Load Steel
Thickness in. Thickness in.
8038957 DSTR1 X 4 '•' 1500 ' 0.035 X 4 1475 0.1050
8037957 DSTR 1-1/2 X 4 1500 0.035 X 4 1475 0.1050
8039957 DSTR 516 X 4 1500 0.037 X 4 1475 0.1050
8045957 DST 516 X 4 1500 0.188 X 4 1475 0.1875
8046957 TEK50 X 4 1500 0.250 X 4 1475 0.1875
8055957 SWDR 1 X 4 1500 0.037 X 4 1475 0.0600
8056957 SWDR 516 X 4 1500 0.037 X 4 1475 0.0600
8054957 SWDR 1-1/2 X 4 1500 0.037 X 4 1475 0.0600
8137957 SH DSTR 1 X 4 1500 0.035 X 4 1475 0.1050
8150922 XP 20 X 2 750 0.027 X 4 1475 0.1050
8153922 XP 35 X 3-1/2 1250 0.043 X 4 1475 0.1050
BX PIN CONCRETE FM FM Max FM Test Material Pipe Size Load
j 8059957 CST 20 X 4 1475 3000 PSi
8061957 SWC20 X 4 1475 3000 PSI
* SWG 25-380 Maximum pipe size in composite wood joist allowed by UL is 3-1/2"
SWG 25-380 Maximum pipe size in wood timber or joist allowed by UL is 4"
** SWG 20 Maximum pipe size in composite wood joist allowed by UL is 2-1/2"
** SWG 20 Maximum pipe size in wood timber or joist allowed by UL is 3"
UL and FM tests were performed in compliance with NFPA-13 Standards.
Fastening requirement: 5 times weight of water filled schedule 40 pipe plus 250 pounds
Buildex
www.itwbuildex.com
800-284-5339
SSS26