HomeMy WebLinkAbout5781 VAN ALLEN WAY; ; FPC2018-0392; PermitCity of
PER]CT REPORT Carlsbad
Print Date: 10/05/2022 Permit No: FPC2018-0392
Job Address: 5781 VAN ALLEN WAY, CARLSBAD, CA 92008-7321 Status: Closed - Finaled
Permit Type: FIRE-Construction Commercial Work Class: Fire Alarm
Parcel #: 2121304400 Track #: Applied: 12/04/2018
Valuation: $0.00 Lot #: Issued: 12/14/2018
Occupancy Group: Project #: Finaled Close Out: 12/05/2019
#of Dwelling Units: Plan #:
Bedrooms: Construction Type: Final Inspection:
Bathrooms: Orig. Plan Check #: INSPECTOR: Salcedo, Felix
Plan Check #: Wong, Cindy
Fieri, Dominic
Project Title:
Description: THERMO FISHER -FIRE ALARM STROBES & HORNS IN BSL2 LAB & COPY CENTER
Applicant: FPContractor:
JOHNSON CONTROLS SECURITY SOLUTIONS JOHNSON CONTROLS SECURITY SOLUTIONS
LLC LLC - DO NOT USE
MALCOLM D'COSTA 3870 MURPHY CANYON RD, 4* 140
3870 MURPHY CANYON RD, 4* 160 SAN DIEGO, CA 92123-4403
SAN DIEGO, CA 92123-4403 (561) 226-8210
(619) 805-5300
FEE AMOUNT
FIRE TI Fire Alarm System $620.00
Total Fees: $620.00 Total Payments To Date: $620.00 Balance Due: $0.00
Fire Department Page 1 of 1
1635 Faraday Avenue, Carlsbad CA 92008-7314 1 760-602-4665 1 760-602-8561 f I www.carlsbadca.gov
HIGHLIGHTED SET
Cut Sheets and CSFM Listing Sheets For:
Thermo Fisher Scientific
BLS2 Lab & Copy Center
Tenant Improvements
5781 Van Allen Way
Carlsbad, California 92008
Installer:
tqCu
Integrated 5erinty
3870 MURPHY CANYON ROAD
SUITE 140
SAN DIEGO, CA. 92123
(800) 289-2647
LIC #977249 (C- 10, C-7)
FPC20I8 -0392
5781 VAN ALLEN WAY
THERMO FISHER - FIRE ALARM STROBES & HORNS IN
BSL2 LAB & COPY CENTER
2121304400
12/412018
FPC20I 8-0392
Flreule®ALarms tncororae
One Fire-Lite Place
Northford, CT 06472
Phone: (203) 484-7161
FAX: (203) 484-7118
0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
000000000
aoaaaooaaaaaaaoaa000aa000000000000a000aa
00000a00000000000000000000000000a000aa00
000a00000000000000a00aa0a000000000000000
0000000aa0000000000a00aua0000000a000000n
oao00a00a00000000000000000000a000000a000
FCPS-24F
FIRE Al AIlS FIELD CHAROERIPOWER SUPPLY
FOR FIRE PRVIECTIORISIORALIRG SERVICE
G
aoaa no anna aaoaa a a aaaaaa on oaanooaaooanoan
000an1300130a00a0n00013000a0000000nn000a000
00000000000000000a0000000000000000000000
0000000000000000000000000000000000000000
000noaaanoanaanannaannnnaaaaaa000annaono
a a a a a a a a a a a a a a a a a a an a a a a a a a a a a a a a a a a a a a a
FCPS-24F/FCPS-24FE
Field Charger/Power Supply
Installation, Operation and Application Manual
Document 50079
09/30/99 Revision:
m- .
Title PN 50079:E 09/30/99
System Overview Specifications
To Transformer #2
To Transformer #1
N>N R'
En En S
+ + + + I -4- +
TB'
Cut JP1 to disable
battery charger or
enable MPM-4
Voltmeter/
Ammeter
To MPM-4
(Voltmeter/Ammeter)
Connection
C) E, 0 3140
)JP1
TB2M
Battery fuse bA, 3AG slow blow
R27
1 0000000
--;-'L) 5 2 9vu 1,'.-r 0
uIu
-0oc0
<5,5
R175 I __ - —C. I
— I
— R76 JP2(D31
In+ (Control Input I
In- fromFACP)
I Out +/Trouble Contact
lOut.
I
,"WrI
R176 Trouble Contact
In+ (Control lnput2
R63 In - from FACP)
r Auxiliary Output
R134 Common
TBS
Note: Auxiliary Output
supplies Specific Application
Power, 45 mA Short Circuit
Figure 1.1 FCPS Board Layout
8 Title PN 50079:E 09/30/99
ARM-4 Installation Installation
Top
2.85" (7.3 CL 0 0 o 0 0
Backbox = 14.5"
(36.8 cm)
Depth = 3.562"
(9.05 cm)
U H S
U
Bottom 11.125"\
(2.868 cm)
Figure 2.1 Backbox Mounting Dimensions
Transformer
Bottom Nut
vU
----- k-i if
MPM4 Meter - Ii Bracket
Meter Assembly Cable
Figure 2.2 MPM4 Installation Diagram
Title PN 50079:E 09/30/99 11
External Device Power Battery Calculations
SECTION 5 Battery Calculations
5.1 External Device Power
The FCPS provides filtered 24 VDC power that may be used for operating Notification Appliance
Circuits or other external devices. The power for operating external devices is limited. Use Table
5.1 (standby or nonalarm) and Table 5.2 (alarm) to determine if external loading is within the
capabilities of the power supply.
Refer to the device manufacturer's data sheets packaged with each device to find the standby and
alarm current draws to use in the tables that follow.
5.2 Device Standby Current Draw
The following table should include the total standby current draw of all devices on each active
output, including End-of-Line relays when used for supervision.
Device Type # of Devices Current
(amps)
Total Current
(amps)
Main PC Board without AC
Fail Report Delay Enabled
OR
Main PC Board with AC Fail
Report Delay Enabled
(1 maximum) X
(1 maximum) X
0.032 =
0.048 =
MPM-4 [ I X 0.008
EOL Relays [ ] X =
Smoke Detectors [ ] X =
Smoke Detectors [ ] X =
Annunciators { I . X =
Auxiliary Devices [ I X =
Auxiliary Devices [ I X =
Auxiliary Devices [ ] X =
Sum Column for Standby Load = amps
Table 5.1 Load in Standby@24 VDC
5.2.1 Current Calculations
1. When Using the 6.0 amps Maximum Current Available:
Five minutes under full load (6.0 amps current draw) requires 3.0 AH (Amp Hour) or a 7.0
AH capacity battery. The remaining 4.0 AH capacity must support the FCPS during its
required standby time. Because of this, the standby current draw cannot exceed the figures
listed below:
For 24 hour standby time, the standby current draw cannot exceed 0.166 amps at 24 VDC
(24 hours X 0.166A) = 3.984 AH
For 60 hour standby time, the standby current draw cannot exceed 0.066 amps at 24 VDC
(60 hours X 0.066A) = 3.96 AH
To calculate Standby Current, subtract total standby load calculated above from 0.166
amps for 24 hours standby or 0.066 amps for 60 hours standby. This figure should not be
less than zero. If the amount is less than zero, the required standby time will not be
achieved
Title PN 50079:E 09/30/99 23
Battery Calculations Device Standby Current Draw
When Using Less than 6.0 amps Maximum Current, use the following tables to determine
the proper battery size
When Battery Amp-Hour Requirements are for Greater than 7.0 All, cut FCPS jumper
JP 1 to disable onboard battery charger and use an external battery charger
Device Type # of Devices Current
(amps)
Total Current
(amps)
Main PC Board without AC
Fail Report Delay Enabled
OR
Main PC Board with AC Fail
Report Delay Enabled
(1 maximum) X
(1 maximum) X
0.032
0.048 =
MPM-4 [ J X 0.008
EOL Relays [ ] X =
Smoke Detectors [ I X =
Smoke Detectors [ I X =
Annunciators [ ] X =
Auxiliary Devices [ ] X =
Auxiliary Devices [ ) X =
Auxiliary Devices [ J X =
Notification Appliances [ J X
Notification Appliances [ ] X =
Notification Appliances [ ] X =
Sum Column for Standby Load = amps
Table 5.2 Load in Alarm@24 VDC
5.2.2 Secondary Power Source Calculations
Use the Total Standby and Alarm Load Currents calculated in Table 5.1 and Table 5.2 for the
following battery calculation.
Standby Load
Current (amps)
[I
X Required Standby Time in Hours
[ I
(24 or 60 Hours)
=
Alarm Load
Current (amps)
[I
X Required Alarm Time in Hours
(i.e. 5 mm. = 0.084 hours))
[ I
=
Add Standby and Alarm Load for Required Ampere Hours =
Multiply by the Derating Factor of 1.2 X
Total Ampere Hours (AH) Required =
Table 5.3 Secondary Power Source Calculations
Notes.
1, Battery size is limited to 7.0,AH using the internal FCPS battery charger
2. For battery sizes greater than 7.0 AH, cut FCPS jumper JP I to disable the internal battery
charger and use an external battery charger
24 Title PN 50079:E 09/30/99
D L ::
65 L ii
DISCHARGE CHARACTERISTICS AT 25 C(77 F)
I
I
I I I
II I,
2 3 5 00 20 30 60 2 3 5 10 20 30
itii0 g 1 Discharge Time
Chargeing Time (h)
Cycle service life
D2 0e2e60
200 400 600 600 1000 1200
Life (cycle)
II
2
0.
c_I 6
0
POER
KINGDOM (eaIed Lead-Acid Batteries)
Specifications
Nominal Voltage 12V
Rated Capacity 7Ah
Dimensions
Total Height 3.98 inches (101mm)
Height 3.74 inches (95mm)
Length 5.94 inches (151mm)
Width 2.56 inches (65mm)
Approximate Weight 4.52 lbs. (2.05kg)
Characteristic
Capacity
770F(250C)
20h rate 7.00Ah
10h rate 6.50Ah
5h rate 5.95Ah
lh rate 4.20Ah
15 min rate 3.15Ah
Internal Resistance Full Charged Battery
770F(25°C)
25m
Capacity
Affected by
Temperature
(20h rate)
1040F(400C) 102%
770F(25°C) 100%
32°F(0°C) 85%
50F(-150C) 65%
Self-Discharge
68°F(200C)
(Capacity after)
3 month storage 90%
6 month storage 80%
12 month storage 60%
Max. Discharge
Current_77°F(25°C) 105A(55)
Terminal TI , T2
Charge
(Constant Voltage,250C)
Cycle I
14.5.44.9V(-24mV/0C)
max. current: 2.1 A
Float 13.6-13.8V(-18mVJ°C)
Constant Current 1)iachar Characteristics (A.25C'i
F.V/TIME 5min 10min 15min 30min 60min 3h 5h 10h 20h
9.60V 27.0 18.0 14.0 8.40 4.70 1.73 1.15 0.71 0.37
10.2V 25.7 17.1 13.4 8.06 4.55 1.70 1.13 0.70 0.36
10.5V 24.2 16.1 12.7 7.66 4.35 1. 65 1.10 0.68 0.35
Constant Current fliachare Characteristmes IVvatt.251'i
F.V/TIMIE 5min 10min 15min 30min 60min 3h 5h 10h 20h
9.60V 301 203 160 94.2 54.4 20.6 13.8 8.52 4.43
10.2V 287 191 153 90.4 52. 7 20.2 13.6 8.40 4.33
10.5V 270 180 145 86.0 50.4 19.6 13.2 8.17 4.21
Indoor Selectable-)
Output Strobes and
Horn Strobes for
Ceiling Applications
System Sensor L-Series audible visible notification
products are rich with features guaranteed to cut
installation times and maximize profits with lower
current draw and modern aesthetics.
Features
Plug-in design with minimal intrusion into the back box
Tamper-resistant construction
Automatic selection of 12- or 24-volt operation
at 15 and 30 candela
Field-selectable candela settings on ceiling units:
15, 30, 75, 95, 115, 150, and 177
Horn rated at 88+ dBA at 16 volts
Rotary switch for horn tone and two volume selections
Universal mounting plate for ceiling units
Mounting plate shorting spring feature checks wiring continuity
before device installation
Electrically Compatible with legacy SpectrAlert and SpectrAlert
Advance devices
Compatible with MDL3 sync module
Listed for ceiling mounting only
Agency Listings
SIGNAUNG
(9 LISTED APPROVED
S5512 FM approved except 7125-1653:0504
S4011 for ALERT models 7135-1653:0503
3057383
The System Sensor L-Series offers the most versatile and
easy-to-use line of horns, strobes, and horn strobes in the industry
with lower current draws and modern aesthetics. With white and red
plastic housings, wall and ceiling mounting options, System Sensor
L-Series can meet virtually any application requirement.
The entire L-Series product line of ceiling-mount strobes and horn
strobes include a variety of features that increase their application
versatility while simplifying installation. All devices feature a plug-in
design with minimal intrusion into the back box, making installations
fast and foolproof while virtually eliminating costly and time-
consuming ground faults.
To further simplify installation, the L-Series utilizes a universal
mounting plate so installers can mount them to a wide array of back
boxes. With an onboard shorting spring, installers can test wiring
continuity before the device is installed.
Installers can also easily adapt devices to a suit a wide range of
application requirements using field-selectable candela settings,
automatic selection of 12- or 24-volt operation, and a rotary switch
for horn tones with two volume selections.
L-Series Specifications
General
[-Series ceiling-mount strobes and horn strobes shall mount to a standard 4 x 4 x 11/2-inch back box, 4-inch octagon back box, or double-
gang back box. Two-wire products shall also mount to a single-gang 2 x 4 x 17/8-inch back box. A universal mounting plate shall be used
for mounting ceiling and wall products. The notification appliance circuit wiring shall terminate at the universal mounting plate. Also, L-Series
products, when used with the Sync.Circuit°° Module accessory, shall be powered from a non-coded notification appliance circuit output
and shall operate on a nominal 12 or 24 volts. When used with the Sync•Circuit Module, 12-volt-rated notification appliance circuit outputs
shall operate between 8.5 and 17.5 volts; 24-volt-rated notification appliance circuit outputs shall operate between 16.5 and 33 volts. Indoor
[-Series products shall operate between 32 and 120 degrees Fahrenheit from a regulated DC or full-wave rectified unfiltered power supply.
Ceiling strobes and horn strobes shall have field-selectable candela settings including 15, 30, 75, 95, 115, 150, and 177.
Strobe
The strobe shall be a System Sensor L-Series Model listed to UL 1971 and shall be approved for fire protective service. The strobe
shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible
signaling appliances, flashing at 1 Hz over the strobe's entire operating voltage range. The strobe light shall consist of a xenon flash tube and
associated lens/reflector system.
Horn Strobe Combination
The horn strobe shall be a System Sensor [-Series Model listed to U[ 1971 and U[ 464 and shall be approved for fire protective
service. The horn strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act
requirements for visible signaling appliances, flashing at 1 Hz over the strobe's entire operating voltage range. The strobe light shall consist
of a xenon flash tube and associated lens/reflector system. The horn shall have two audibility options and an option to switch between a
temporal three pattern and a non-temporal (continuous) pattern. These options are set by a multiple position switch. The horn on horn strobe
models shall operate on a coded or non-coded power supply.
Synchronization Module
The module shall be a System Sensor Sync.Circuit model MD[3 listed to UL 464 and shall be approved for fire protective service. The module
shall synchronize [-Series strobes at 1 Hz and horns at temporal three, Also, while operating the strobes, the module shall silence the horns
on horn strobe models over a single pair of wires. The module shall mount to a 4 11/16 x 4 11/16 x 2 1/8-inch back box. The module shall also
control two Style Y (class B) circuits or one Style Z (class A) circuit. The module shall synchronize multiple zones. Daisy chaining two or more
synchronization modules together will synchronize all the zones they control. The module shall not operate on a coded power supply.
Physical/Electrical Specifications
Standard Operating Temperature 32°F to 120°F (0°C to 49°C)
Humidity Range 10 to 93% non-condensing
Strobe Flash Rate 1 flash per second
Nominal Voltage Regulated 12 VDC or regulated 24 DC/FWR1
Operating Voltage Range2 8 to 17.5 V (12 V nominal) or 16 to 33 V (24 V nominal)
Operating Voltage Range (MDL3) 8.5 to 17.5V (12 V nominal) or 16.5 to 33 V (24V nominal)
Input Terminal Wire Gauge 12 to 18 AWG
Ceiling-Mount Dimensions (including lens) 6.8' diameter x 2.5' high (173 mm diameter x 64 mm high)
Ceiling-Mount Surface Mount Back Box Skirt Dimensions 6.9' diameter x 3.4 high (175 mm diameter x 86 mm high)
(SBBCRL, SBBCWL)
Notes:
Full Wave Rectified (FWR) voltage is a non-regulated, time-varying power source that is used on some power supply and panel outputs
P, 5, PC, and SC products will operate at 12 V nominal only for 15 and 30 cd.
AVDS86800
UL Current Draw Data
Candela
8-17.5 Volts
DC
i6-33 Volts)
(bQ FWR
(15) 87 (41) 60
30 153 63 86
75 N/A 111 142
95 N/A 134 164
115 N/A 158 191
150 N/A 189 228
177 N/A 226 264
UL Max. Current Draw (rnA RMS), 2-Wire Horn Strobe
8 175 Volts (16-33 Vits)
DC Input 15cd 30cd 15cd 30cd (cd) 95cd 115cd 150cd 177cd
ejemporal High) 103 167 71 90 (143) 165 187 217 254
Temporal Low 96 165 54 71 137 161 185 211 249
Non-Temporal High 106 173 71 90 141 165 187 230 273
Non-Temportal Low 95 166 54 71 124 161 170 216 258
3.1KTemporal High 111 164 69 94 147 163 184 229 257
3.lKTemporal Low 103 163 54 88 143 155 185 212 252
3.1K Non-Temporal High 111 172 69 94 144 164 202 229 271
3.1K Non-Temporal Low 103 169 54 88 131 155 187 217 259
FWR Input
16-33 Volts
15cd 30cd 75cd 95cd 115cd 150cd 177cd
Temporal High 107 135 179 198 223 254 286
Temporal Low 78 101 151 172 199 229 262
Non-Temporal High 107 135 179 198 223 254 286
Non-Temportal Low 78 101 151 172 199 229 262
3.1K Temporal High 108 135 179 200 225 255 289
3.lKTemporal Low 79 101 150 171 196 229 260
3.1K Non-Temporal High 108 135 179 200 225 255 289
3.1 K Non-Temporal Low 79 101 150 171 196 229 260
Horn Strobe Tones and Sound Output Data
8-17.5 16-33
Volts Volts
Switch Position Sound Pattern dB DC DC FWR
1 Temporal High 84 89 89
2 Temporal Low 75 83 83
3 Non-Temporal High 85 90 90
4 Non-Temporal Low 76 84 84
5 3.1 KHz Temporal High 83 88 88
6 3.1 KHz Temporal Low 76 82 82
7 3.1 KHz Non-Temporal High 84 89 89
8 3.1 KHz Non-Temporal Low 77 83 83
AVDS86BOO
L-Series Dimensions
247
1.37 06.92 2.5O
0
Ceiling-Mount Horn Strobes Ceiling Surface Mount Back Box
Ceiling Mount Horn Strobes with Ceiling Surface Mount Back Box
L-Series Ordering Information
Ceiling Horn Strobes
çRL) (2 Wire Horn Strobe Red)
PC2WL 2-Wire, Horn Strobe, White
Ceiling Strobes
(SCR (Strobe Red
SCWL Strobe, White
SCWL-CLR-ALERT Strobe, White, ALERT
Accessories
TRC-2 Universal Ceiling Trim Ring Red
TRC-2W Universal Ceiling Trim Ring White
SBBCRL Ceiling Surface Mount Back Box, Red
SBBCWL Ceiling Surface Mount Back Box, White
}I5 7,f 3B25 Ohio Avenue • St. Charles, IL 60174 @2017 System Sensor.
Product specifications subject to change without notice. Visit systemseosor.com 5JJ5Qf Phone: 800-SENSOR2 • Fax: 630-377-6495 for current product information, including the latest version of this data sheet.
AVDS86801 - 03/1 7
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM
LISTING SERVICE
LISTING No. (1-1653:0503) Page 1 of 2
CATEGORY: (7135 --AUDIBLE DEVICE)
LISTEE: (ystem_Sensor)Unincorporated Div of Honeywell Int'l lnc.3825 Ohio Ave, St. Charles, IL
60174
Contact: Vladimir Kireyev (203) 484-6277 Fax (203) 484-7309
Email: Vladimir.Kireyevhoneywell.com
DESIGN: System Sensor Indoor 2-wire and *4..wire Models:
HWL, HRL, HGWL and HGRL Horns;
CHWL and CHRL Chimes;
P2RL, P2WL, P2GRL, P2GWL, P2RL-P, P2WL-P, P2RL-SP, P2WL-SP, *P4RL and *P4WL
Wall Horn Strobes;
(PC2RL PC2WL, *PC4RL and *PC4WL Ceiling Horn Strobes;
CHSRL and CHSWL Wall Chime Strobes;
CHSCRL and CHSCWL Ceiling Chime Strobes;
Wall Bezel Parts:
BZR-F, BZR-AL, BZR-AG, BZR-EV, BZR-P, BZR-SP, BZR-PG,
BZW-F, BZW-AL, BZW-AG, BZW-EV, BZW-P, BZW-SP, BZW-PG,
BZGR-F, BZGR-AL, BZGR-AG, BZGR-EV, BZGR-P, BZGR-SP, BZGR-PG,
BZGW-F, BZGW-AL, BZGW-AG, BZGW-EV, BZGW-P, BZGW-SP and BZGW-PG,
Ceiling Bezel Parts:
BZRC-F, BZRC-AL, BZRC-AG, BZRC-EV, BZRC-P, BZRC-SP, BZRC-PG,
BZWC-F, BZWC-AL, BZWC-AG, BZWC-EV, BZWC-P, BZWC-SP and BZWC-PG.
Color Lens:
LENS-A2, LENS-132, LENS-G2, LENS-R2, LENS-AC2, LENS-BC2, LENS-GC2 and
LENS-RC2.
WallTrim Rings:
*TR2 and *TR2W
CeilingTrim Rings:
*TRC2 and *TRC2W
Wall Surface Mounted Back Boxes:
SBBRL, SBBGRL, SBBWL and SBBGWL,
Ceiling Surface Mounted Back Boxes:
Revision 08-21-2017 dcc
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed
the test results and/or other data but does not make an independent verification of any claims. This listing is not
an endorsement or recommendation of the item listed. This listing should not be used to verify correct
operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other
Date Issued: July 01, 2018 (Listing Expires)(J une 3O,2O19)
Authorized By: DAVID CASTILLO, Program Coordinator
Fire Engineering Division
Listing No. 7135-1653:0503
Page 2 of 2
SBBCRL and SBBCWL
MP120KL 120 VAC Adapter Mounting Plate
Refer to listee's data sheet for detailed product description and operational considerations.
RATING: 12 VDC regulated and 24 VDC/FWR
INSTALLATION: In accordance with listee's printed installation instructions, NFPA 72, applicable codes &
ordinances and in a manner acceptable to the authority having jurisdiction.
MARKING: Listee's name, model number, electrical rating, and UL label.
APPROVAL: Listed as audible devices when used with separately listed compatible fire alarm control
units. Suitable for indoor use, wall or ceiling mounted. Authority having jurisdiction should be
consulted prior to installation. Refer to listee's Installation Instruction Manual for details.
Revision 08-21-2017 dcc
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed
the test results and/or other data but does not make an independent verification of any claims. This listing is not
an endorsement or recommendation of the item listed. This listing should not be used to verify correct
operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other
Date Issued: July 01, 2018 (June 3O,2019)
Authorized By: DAVID CASTILLO, Program Coordinator
Fire Engineering Division
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION ..,..
OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM
6- ";;
LISTING SERVICE
LISTING No. (7125-1653:05) Page 1 of 2
CATEGORY: (25 -- FIRE ALARM DEVICES FOR THE HEARING IMPAIRED)
LISTEE: System Sensor3Unincorporated Div of Honeywell Intl lnc.3825 Ohio Ave, St. Charles, IL
60174
Contact: Vladimir Kireyev (203) 484-6277 Fax (203) 484-7309
Email: Vladimir.Kireyevhoneywell.com
DESIGN: System Sensor Indoor 2-wire Models:
SRL, SWL, SGRL, SGWL, SRL-P SWL-P, SRL-SP, SWL-CLR-ALERT and SWL-ALERT
Wall Strobes;
(SCRL) SCWL and SCWL-CLR-ALERT Ceiling Strobes.
Wall Bezel Parts:
BZR-F, BZR-AL, BZR-AG, BZR-EV, BZR-P, BZR-SP, BZR-PG,
BZW-F, BZW-AL, BZW-AG, BZW-EV, BZW-P, BZW-SP, BZW-PG,
BZGR-F, BZGR-AL, BZGR-AG, BZGR-EV, BZGR-P, BZGR-SP, BZGR-PG,
BZGW-F, BZGW-AL, BZGW-AG, BZGW-EV, BZGW-P, BZGW-SP and BZGW-PG,
Ceiling Bezel Parts:
BZRC-F, BZRC-AL, BZRC-AG, BZRC-EV, BZRC-P, BZRC-SP, BZRC-PG,
BZWC-F, BZWC-AL, BZWC-AG, BZWC-EV, BZWC-P, BZWC-SP and BZWC-PG.
Color Lens:
LENS-A2, LENS-132, LENS-G2, LENS-R2, LENS-AC2, LENS-BC2, LENS-GC2 and
LENS-RC2.
WallTrim Rings:
TR2 and TR2W
CeilingTrim Rings:
TRC2 and TRC2W.
Wall Surface Mounted Back Boxes:
SBBRL, SBBGRL, SBBWL and SBBGWL,
Ceiling Surface Mounted Back Boxes:
SBBCRL and SBBCWL
Refer to listee's data sheet for detailed product description and operational considerations.
02-14-17 gt
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed
the test results and/or other data but does not make an independent verification of any claims. This listing is not
an endorsement or recommendation of the item listed. This listing should not be used to verify correct
operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other
Date Issued: July 01, 2018 (June 30, 2019)
Authorized By: DAVID CASTILLO, Program Coordinator
Fire Engineering Division
Listing No. 7125-1653:0504
Page 2 of 2
RATING: Regulated 12 VDC setting: 8-17.5 VDC
Regulated 24 VDC/fwr setting: 16-33 VDC
INSTALLATION: In accordance with listee's printed installation instructions, NFPA 72, applicable codes &
ordinances and in a manner acceptable to the authority having jurisdiction.
MARKING: Listee's name, model number, electrical rating, and UL label.
APPROVAL: Listed as two wire strobe units used for synchronous application when used with separately
listed compatible fire alarm control units. Suitable for indoor use, vertical wall or horizontal
ceiling mounted. Authority having jurisdiction should be consulted prior to installation. Refer
to listee's Installation Instruction Manual for details.
02-14-17 gt
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed
the test results and/or other data but does not make an independent verification of any claims. This listing is not
an endorsement or recommendation of the item listed. This listing should not be used to verify correct
operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other
Date Issued: July 01, 2018 (yigExpfes (June 30, 2019
Authorized By: DAVID CASTILLO, Program Coordinator
Fire Engineering Division
Indoor Selectable-)
Output Strobes and
Horn Strobes for
Ceiling Applications
SpectrA lertO Advance audible visible notification products
are rich with features guaranteed to cut installation times
and maximize profits. SPECTRQUert
Features
Plug-in design with minimal intrusion into the back box
Tamper-resistant construction
Automatic selection of 12- or 24-volt operation at 15 and
15/75 candela
Field-selectable candela settings on ceiling units: 15, 15/75, 30,
75, 95, 110, 115, 135, 150, 177, and 185
Horn rated at 88+ dBA at 16 volts
Rotary switch for horn tone and three volume selections
Universal mounting plate for ceiling units
Mounting plate shorting spring checks wiring continuity before
device installation
Electrically Compatible with legacy SpectrAlert devices
Compatible with MDL sync module
Listed for ceiling or wall mounting
Agency Listings
SIGNAUNG
zzMEA
LISTED APPROVED approved 7125-1653:186 indoor strobes)
7125-1653:188 (horn strobes,
S4011 (chimes, horn strobes, horns) 3023572 M8A452-05-E chime strobes)
S5512 (strobes) 7135-1653: 189 (horns, chimes)
The SpectrAlert Advance series offers the most versatile and
easy-to-use line of horns, strobes, and horn strobes in the industry.
With white and red plastic housings, wall and ceiling mounting
options, and plain and FIRE-printed devices, SpectrAlert Advance
can meet virtually any application requirement.
Like the entire SpectrAlert Advance product line, ceiling-mount
strobes and horn strobes include a variety of features that increase
their application versatility while simplifying installation. All devices
feature plug-in designs with minimal intrusion into the back box,
making installations fast and foolproof while virtually eliminating
costly and time-consuming ground faults.
To further simplify installation and protect devices from construction
damage, SpectrAlert Advance utilizes a universal mounting plate
with an onboard shorting spring, so installers can test wiring
continuity before the device is installed.
Installers can also easily adapt devices to a suit a wide range of
application requirements using field-selectable candela settings,
automatic selection of 12- or 24-volt operation, and a rotary switch
for horn tones with three volume selections.
SpectrAlert Advance Specifications
General
SpectrAlert Advance strobes and horn strobes shall mount to a standard 4 x 4 x 11/2-inch back box, 4-inch octagon back box, or double-
gang back box. Two-wire products shall also mount to a single-gang 2 x 4 x 17/8-inch back box. A universal mounting plate shall be used for
mounting ceiling and wall products. The notification appliance circuit wiring shall terminate at the universal mounting plate. Also, SpectrAlert
Advance products, when used with the Sync.Circuit°° Module accessory, shall be powered from a non-coded notification appliance circuit
output and shall operate on a nominal 12 or 24 volts. When used with the Sync-Circuit Module, 12-volt-rated notification appliance circuit
outputs shall operate between 9 and 17.5 volts; 24-volt-rated notification appliance circuit outputs shall operate between 17 and 33 volts.
Indoor SpectrAlert Advance products shall operate between 32 and 120 degrees Fahrenheit from a regulated DC or full-wave rectified
unfiltered power supply. Strobes and horn strobes shall have field-selectable candela settings including 15, 15/75, 30, 75, 95, 110, 115, 135,
150, 177, and 185.
Strobe
The strobe shall be a System Sensor SpectrAlert Advance Model listed to UL 1971 and shall be approved for fire protective service
The strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act requirements for
visible signaling appliances, flashing at 1 Hz over the strobe's entire operating voltage range. The strobe light shall consist of a xenon flash
tube and associated lens/reflector system.
Horn Strobe Combination
The horn strobe shall be a System Sensor SpectrAlert Advance Model listed to UL 1971 and UL 464 and shall be approved for
fire protective service. The horn strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with
Disabilities Act requirements for visible signaling appliances, flashing at 1 Hz over the strobe's entire operating voltage range. The strobe light
shall consist of a xenon flash tube and associated lens/reflector system. The horn shall have three audibility options and an option to switch
between a temporal three pattern and a non-temporal (continuous) pattern. These options are set by a multiple position switch. On four-wire
products, the strobe shall be powered independently of the sounder. The horn on horn strobe models shall operate on a coded or non-coded
power supply.
Synchronization Module
The module shall be a System Sensor Sync.Circuit model MDL listed to UL 464 and shall be approved for fire protective service. The module
shall synchronize SpectrAlert strobes at 1 Hz and horns at temporal three. Also, while operating the strobes, the module shall silence the horns
on horn strobe models over a single pair of wires. The module shall mount to a 411/16 x 411/16 x 21/8-inch back box. The module shall also
control two Style Y (class B) circuits or one Style Z (class A) circuit. The module shall synchronize multiple zones. Daisy chaining two or more
synchronization modules together will synchronize all the zones they control. The module shall not operate on a coded power supply.
Standard Operating Temperature 32°F to 120°F (0°C to 49°C)
Humidity Range 10 to 93% non-condensing
Strobe Flash Rate 1 flash per second
Nominal Voltage Regulated 12 DC/FWR or regulated 24 DC/FWR1
Operating Voltage Range2 8 to 17.5 V (12 V nominal) or 16 to 33 V (24 V nominal)
Input Terminal Wire Gauge 12 to 18 AWG
Ceiling-Mount Dimensions (including lens) 6.8" diameter x 2.5" high (173 mm diameter x 64 mm high)
Ceiling-Mount Back Box Skirt Dimensions (BBSC-2, BBSCW-2) 7.1"diameter x 22" high (180 mm diameter x 57 mm high)
Ceiling-Mount Trim Ring Dimensions (sold as a 5 pack) (TRC-HS, 6.9-diameter x 0.35" high (175 mm diameter x 9 m high)
Notes:
Full Wave Rectified (FWR) voltage is a non-regulated, time-varying power source that is used on some power supply and panel outputs.
F, 5, PC, and SC products will operate at 12 V nominal only for 15 and 15/75 cd.
AVDSOO5O1
UL Current Draw Data
',,UL,--Max. Strobe'CUrrObt Draw (tiikR
8-17.5 Volts 16-33 Volts
Candela DC FWR DC FWR
Standard Candela Range 15 123 128 66 71
15/75 142 148 77 81
30 NA NA 94 96
75 NA NA 158 153
95 NA NA 181 176
110 NA NA 202 195
115 NA NA 210 205
High 135 NA NA 228 207
Candela Range 150 NA NA 246 220
177 NA NA 281 251
185 NA NA 286 258
UL Max. Current Draw (mA RMS), 2-Wire Horn Strobe, Standard Candela Range (15-115 cd)
8-17.5 Volts C16-33 Volts)
FD C!npJ 15 15175 15 15175 30 (75) 95 110 115
(Temporal High) 137 147 79 90 107 (17 194 212 218
Temporal Medium 132 144 69 80 97 157 182 201 210
Temporal Low 132 143 66 77 93 154 179 198 207
Non-Temporal High 141 152 91 100 116 176 201 221 229
Non-Temporal Medium 133 145 75 85 102 163 187 207 216
Non-Temporal Low 131 144 68 79 96 156 182 201 210
FWR Input
Temporal High 136 155 88 97 112 168 190 210 218
Temporal Medium 129 152 78 88 103 160 184 202 206
Temporal Low 129 151 76 86 101 160 184 194 201
Non-Temporal High 142 161 103 112 126 181 203 221 229
Non-Temporal Medium 134 155 85 95 110 166 189 208 216
Non-Temporal Low 132 154 80 90 105 161 184 202 211
DC Input
16-33 Volts
135 150 177 185 FWR Input
16-33 Volts
135 150 177 185
Temporal High 245 259 290 297 Temporal High 215 231 258 265
Temporal Medium 235 253 288 297 Temporal Medium 209 224 250 258
Temporal Low 232 251 282 292 Temporal Low 207 221 248 256
Non-Temporal High 255 270 303 309 Non-Temporal High 233 248 275 281
Non-Temporal Medium 242 259 293 299 Non-Temporal Medium 219 232 262 267
Non-Temporal Low 236 254 291 295 Non-Temporal Low 214 229 256 262
Horn Strobe Tones and Sound Output Data
8-17.5 16-33 24-Volt Nominal
Switch Volts Volts Reverberant Anechoic
Position Sound Pattern dB DC FWR DC FWR DC FWR DC FWR
1 Temporal High 78 78 84 84 88 88 99 98
2 Temporal Medium 74 74 80 80 86 86 96 96
3 Temporal Low 71 73 76 76 83 80 94 89
4 Non-Temporal High 82 82 88 88 93 92 100 100
5 Non-Temporal Medium 78 78 85 85 90 90 98 98
6 Non-Temporal Low 75 75 81 81 88 84 96 92
7t Coded High 82 82 88 88 93 92 101 101
8t Coded Medium 78 78 85 85 90 90 97 98
9t Coded Low 75 75 81 81 88 85 96 92
Settings 7, 8, and 9 are not available on 2-wire horn strobes.
AV0500501
(Ceiling-mount horn strobes)
.8"
a.
SpectrAlert Advance Dimensions
,-7.1" 2.25'1
Dia. I________
2 Q O
Ic
(çeijjngbaci_box skirt
SpectrAlert Advance Ordering Information
Ceiling Horn Strobes
PC2R*) (2-Wire Horn Strobe, Standard Cd, Red)
PC2RH 2-Wire Horn Strobe, High Cd, Red
PC2W*t 2-Wire Horn Strobe, Standard Cd, White
Model Description
Ceiling Strobes
(SCR) (Strobe, Standard cd, Red)
SCRH Strobe, High Cd, Red
SCW* Strobe, Standard Cd, White
PC2WH* 2-Wire Horn Strobe, High Cd, White SCWH Strobe, High Cd, White
PC4R 4-Wire Horn Strobe, Standard Cd, Red Accessories
PC4RH 4-Wire Horn Strobe, High Cd, Red
PO4W 4-Wire Horn Strobe, Standard Cd, White
(13BSC-2 Back Box Skirt, Ceiling, Red)
Back Box Skirt, Ceiling, White
TRC-HS Trim Ring Ceiling, Redj
TRCW- Trim Ring, Ceiling, White
HS
Notes:
* Add "-P' to model number for plain housing (no "FIRE" marking on Cover), e.g., P2R-P.
f Add '-SP" to model number for "FUEGO" marking on cover, e.g., P2R-SP.
I: "Standard cd' refers to strobes that include 15, 15/75, 30, 75, 95, 110, and 115 candela settings. 'High Cd" refers to strobes that include 135, 150, 177, and 185
candela settings.
3825 Ohio Avenue • St. Charles, IL 60174 @2012 System sensor.
Product spoof cat one subject to change without notice. Visit systemsensor.com
SENSOR' Phone: 800-SENSOR2 • Fax: 630-377-6495 AVDSOO5OS •3/12
for current product information, including the latent version of this data sheet
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
OFFICE OF THE STATE FIRE MARSHAL -
FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM
-
LISTING SERVICE
LISTING No. (7125-1653:0188J Page 1 of 1
CATEGORY: (7125 ---FIRE ALARM DEVICES FOR THE HEARING IMPAIRED)
LISTEE: (System Sensor, Unincorporated Div of Honeywell Int'l Inc.3825 Ohio Ave, St. CharIesIL
60174
Contact: Vladimir Kireyev (203) 484-6277 Fax (203) 484-7309
Email: Vladimir.KireyevhoneywelI.com
DESIGN: Models CHSR and CHSW Chime/Strobes.
Models P2R, P2W, P2RH and P2WH Horn/Strobes two-wire type, rectangular enclosure.
ModeIs(Pë) PC2W, PC2RH and PC2WH Horn/Strobes two-wire type, round enclosure
Models P4R, P4W, P4RH and P4WH Horn/Strobes four-wire type, rectangular enclosure.
Models PC4R, PC4W, PC4RH and PC4WH Horn/Strobes* four-wire type, round enclosure.
All models are intended for indoor use only unless other wise indicated. Models may be
followed by the suffix "K" indicating indoor or outdoor use, or may be followed by suffix "P' for
plain housing with no lettering. "K" suffix models are suitable for outdoor applications at
temperatures from -40°F to +151°F (-40°C to +66°C) and are rated NEMA 4X when used with
the System Sensor weather proof back boxes models SA-WBB (Wall), SA-WBBW (Wall),
SA-WBBC (Ceiling) and *SA..WBBCW (Ceiling). Refer to listee's data sheet for additional
detailed product description and operational considerations.
RATING: Standard Horn/Strobes and Chime/Strobes 8 - 17.5 or 16-33 VDC/FWR
Hi CD Horn/Strobes 16-33 VDC/FWR
INSTALLATION: In accordance with listee's printed installation instructions, applicable codes and ordinances,
and in a manner acceptable to the authority having jurisdiction.
MARKING: Listee's name, model number, electrical rating, and UL label.
APPROVAL: Listed as *horn/strobes or chime/strobes suitable for signaling appliances and equipment for
the hearing impaired applications when used with separately listed compatible fire alarm
control units. Horn/strobes with -K suffix are suitable for indoor or outdoor use, ceiling or wall
mount. Chime section is suitable for private mode and indoor use only.
Horn/Strobes or chime/strobes* can generate the distinctive three-pulse audible Temporal
Pattern Fire Alarm Evacuation Signal (for total evacuation) in accordance with NFPA 72,
2010 Edition. Refer to listee's Installation Instruction Manual for details.
*Corrected 12-15-11 bh
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed
the test results and/or other data but does not make an independent verification of any claims. This listing is not
an endorsement or recommendation of the item listed. This listing should not be used to verify correct
operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other
Date Issued: July 01, 2018 ExpireJ (June 30, 2019)
Authorized By: DAVID CASTILLO, Program Coordinator
Fire Engineering Division
SECTION2 FIRE ALARM CABLE
I PART NUMBER AWG IC0N0b0RI SHIELDED! OVERALL I
UNSHIELDED DIAMETER I
CONDUCTOR
COLOR COLOR
VOLTAGE
I RATING
WEIGHT
I (Ibs)flJnit
MARKINGS TEMP purl
I 14 AWG I WHITE I 300v I 50.0 ADT 494479 2/C 60°C 500
BLACKJ RED, LBS 14 AWG 2/C lB AWG REEL
18AWG TYPE FPLR/
CL3R UOHT BLUE / (UL) YELLOW
BLACK, RED RED 20.0 2C 14AWG (UL)
LBS FPLR
WHITE 20,0 AOl 494478 75O
LBS 2C14AWG
TYPE FPLR/
CL3R
(UL) (CSA)
BLACK, RED, RED 35.0 FPLRJCL3R
BROWN, BLUE LBS 14 AWG (UL)
BLACK, RED WHITE 33.0 AOl 494480
LBS 2012AW5
TYPE FPLR/
CL3R
(UL) (GSA)
!IJ 1 2.12
DON'T SEE IT? CALL 1-888-4238947 ORDERS: PHONE 1-888-423-8947, FAX 847-797-3853
V'\ I 2.1
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION .....
OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM
LISTING SERVICE
LISTING No. (7161-2075:0100) Page 1 of 1
CATEGORY: (T161 -- CABLES-FIRE PROTECTIVE SIGNALING)
LISTEE: (Paige Electric Companyjj9)Springfield Road, Union, NJ 07083
Contact: Cindy Regner (908) 687-7810 Fax (908) 687-8860
Email: cregnerpaigeelectric.com
DESIGN: Types FPL, FPLP and [power limited fire protective signaling cables.
Insulation - PVC compound AlphaGary Smokeguard 4010, Synergistics 1349-1028 FRD,
1360-1021-PID, PP, HDPE or LDPE.
Shields - (Optional) All metal or Aluminum Polyester tape.
Braid - (Optional) All metal.
Jacket - PVC compound AlphaGary Smokeguard 11 6920, Gitto Global GA-8705-03,
AlphaGary GW2038, Synergistics 1690-1060, 1604-1007 FR, 1100-1092 FRD, JAP6IA or
1410-1011 FRD, Solef 31008-0003.
Refer to listee's data sheet for additional detailed product description and operational
considerations.
INSTALLATION: In accordance with listee's printed installation instructions, NEC Article 760, applicable
codes and ordinances, and in a manner acceptable to the authority having jurisdiction.
MARKING: Listees name, Type FPL, FPLP or FPLR, rating and UL label.
APPROVAL: Listed as power-limited fire protective signaling cables.
NOTE: Formally 7161-1677:100
XLF: 7161-1509:0100
mt 09-09-11 mt
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed
the test results and/or other data but does not make an independent verification of any claims. This listing is not
an endorsement or recommendation of the item listed. This listing should not be used to verify correct
operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other
Date Issued: July 01, 2018 e3O,2O19)
Authorized By: DAVID CASTILLO, Program Coordinator
Fire Engineering Division