Press Alt + R to read the document text or Alt + P to download or print.
This document contains no pages.
HomeMy WebLinkAbout5781 VAN ALLEN WAY; ; FA080072; PermitCity ot Carlsbad
Fire Alarm Permit
Permit No: FA080072
5781 VAN ALLEN
Job Address:
WY
Permit Type: FALARM
Parcel No: 2121304400
Lot #: 0
Reference No.:
PC #:
Status: ISSUED
Applied 10/14/2008
Approved: 10/15/2008
Issued: 10/15/2008
Inspector:
Project Title: INVITROGEN - CPI3D TI FIRE ALARM PLAN CHECK &
INSPECTIONS
Applicant:
ADT SECURITY SERVICES, INC.
3830 CALLE FORTUNADA
SAN DIEGO, CA
(858) 654-3224
Owner:
GRIFFIN CAPITAL CARLSBAD POINTE
INVESTORS L L C
C/O INVITROGEN CORPORATION
1600 FARADAY AVE
CARLSBAD CA
Fees ($) Add'l Fees ($) Total ($) Balance ($)
125 0 125 0
INVITROGEN
ROOM 6016 T.I.
5781 VAN ALLEN WAY
CARLSBAD, CA. 92008
FIRE ALARM T.I. SUBMITTAL
Submitted By:
3830 Calle Fortunada
San Diego, CA 92123
(858) 654-3133
Lic. # 707408
Contact: DAVE WELLS
FILE Copy
k DQDfl?
INVITROGEN
T.I. ROOM # 6016
FIRE ALARM SUBMITTAL
Pm MODEL # MA-NF. CSFM#
1 HORN/STROBE MULTI-CD WALL AS-24MCW WHEELOGK 7125-0785:131
LOT 14/2 FIRE CABLE ADT/GENESIS 7161-1487:100
LOT 18/2 FIRE CABLE ADT/GENESIS 7161-1487:100
Series AS Audible Strobe Appliances and Series AH Audibles
iU
SERIES AH
Description
The Wheelock patented 2-wire Series AS Audible Strobe Appliances and Series AH Audible, offer more features with
low current draw.
Strobe options for wail mount models indude 1575cd or the Wheelock patented MCW multi-candela wall strobes with field selectable candela settings of 15130/75/110cd, or the high intensity MCWH strobe with field selectable 135/185cd.
Ceiling mount models incorporate Wheelock's patented MCC multi-candela ceiling strobe with field selectable intensities of
15/30175/95cd or the high intensity MCCH strobe with field
selectable 1151177cd.
The audible provides a selectable choice of either a continuous horn or temporal pattern (Code 3) when
constant voltage from a Fire Alarm Panel (FACP) Is
applied. Each tone has 3 dBA settings to choose from.
When used with the Wheelock Series SM.DSM Sync
Modules, Wheelock Power Supplies or other manufacturers
panels incorporating the Wheelock Patented Sc Prptocol,
synchronization of the continuous horn tons provides the temporal (code 3) tone (mandated by NFPA72) simultaneously for all audible appliances. This ensures a distinct temporal
(code 3) pattern when 2 or more audible& are within hearing
distance. If not synchronized the temporal sound could overlap
and not be distinctive. At the same time the strobes will be synchronized. This provides the ability to comply with ADA
guidelines concerning photosensitive epilepsy and the NFPA standards when installing 2 or more visual appliances within
the field of view all of this plus the ability to silence the audible is achieved by using only 2 wire.
Features
Approvals Include: UL Standard 1971 UL Standard 464
New York City (MEA), California State Fire Marshal (CSFM),
Factory Mutual (FM), and Chicago (BFP). See approvals by model in Specifications and Ordering Information
ADNNFPMJFC/ANSI Compliant
Wall mount models are available with Field Selectable
Candela Settings of 15/3W75/110cd or 135/185cd (Multi.
Candela models) or 1575cd (single candela model)
Ceiling mount models are available with field selectable
candela settings of 15/30/75/95cd or 115/177cd (multi-candela ceiling models)
Selectable Continuous Horn or Temporal (Code 3).
3 Selectable dBA settings (99, 95 and 90 dBA) in both tones
Patented 2-Wire Audible Strobe Appliance.
Patented Universal Mounting Plate
Weatherproof models are available for outdoor use
Strobes produce 1 flash per second over the regulated voltage range
12 and 24 VDC models with wide UL "Regulated Voltage Range using filtered DC or unfiltered FWR input voltage
Synchronize using the Wheelock Sync Modules or panels with built-In Wheelock Patented Sync Protocol
Fast installation with IN/OUT screw terminals using
#12 to #18 AWG wires
For Weatherproof Series AS, See Ctatasheet S9004
(D =1-4 14 <~>
PROVW ESG48 16152-€ 7125..O7U131 SUM
24 VDC Models AH.24 AS-24`1575W
1575Od
High (99)J
dBA
24 We 0.062 0.100
UL max' 1 0.080 0.121
Mod (95)
CiBA
24 We 0.033 01080
UL max* 0.043 0.107
Low (90)
dBA
24 vdc 0.017 0.072
UL max* 0.021 0.100
12 VDC Models
Audible
Wall Mount
Audible
Strobe
*11-12 *3-121678W
High (99) 12 vdc 0.163 0,260
UL max* 0.192 0.320 dBA
Mid (95) 12 vdc 0,078 0.196
Ut. max* 0.104 0.275 dBA
Low (90) 12 vdc 0.039 0.175
Ut. max' i 0.058 0.265 dBA
MOTE: All CAUTIONS and WARNINGS are Identified by the symbol A. All warnings are printed In bold capital letters. A WAllNG: PLEASE READ THEN $PICFICATION$ AND ASSOCIATED IN$1*LLAT$ON INSTRUCTIONS CAREFULLY BEFORE USING, SPECIFtINO OR APPLYING THIS PRODUCT VISIT WWW.000PWONHEEI.00K.CCM OR CObW.0T COOPER WHEELOCK FOR THE CURRENT INSTAUATION INSTRUCliONS. FALL= TO COMPLY WITH ANY OPINESI 14*TRUCTION$, CAUTIONS 0RVURMNG$ COULD RESULT II IPPERAPPUCA11ON, IN5TA(.t.A'flON ANOR
OPERATiON OF THESE PRODUCTS UI AN OUR0111HOYITUATICil,WHIemu DWU4TPI !. C.PERT( DAMAGL AND SERIOUS INJURY OR DEATH TO YOU AMWOR OTHERS.
General Notes: . ,... Strobes are designed to flash .11 flash per second minimum Over their Regulated Voltage Range. Note that NFPA-72 specifies a flash rate of 1 to 2 flashes per second sndAGuIdelin.s specify flash rats of I 1o38h.s per second. AN candela ratings represent minimum effective StrObe intensity based on UI. Standard 1971. Srl.s NS Strobe products are listed under UI. Standard 1971 for indoor two with a t.rrçerature range of 32F to 120F (OC to 49C) and ma,dmum humidity of 93% (12%). Series NH horns are listed under Ut. Standard 464 for audible signal appliances (Indoor use only). "Regulated VoIt4gs Range" I. the newest terminology used by ULto Identify the voltage rang.. Prior to this change UL used the terminology Ust.d V9ltags Rang.".
Table 2; ciBA Ratings for 12 VDC and 24 VDC Series AS/
AN 12 and 24 VDC Audible
Reverberant
Description Volume
dBAAnechoic
Per UL 454 dBA
10 ft.
IM 10 ft.
High 91 99
Continuous Medium
Horn
88 95
Low 83 90
High 87 99
CodeS Horn MedIum 64 95
Low 79 90
Table I: Ratings Per UL 1971
Model
Number
Input
Voltage
VDC
Regulated
Voltage Range
VDCIFWR
Strobe
Candela (Cd)
AS-24MCW 24 16.0-33.0 15/30175/110
AS-24MCCH 24 16.0-33.0 . 1181177
AS-241575W 24 18.0-33.0 15(75onAxis)
AS-121575W 12 8.0-17.5 15(75onAxis)
AS-24MCC 24 16.0.33.0 15130175/95
AS-24MCWH 24 16.0 -33.0 135/185
ASWP-2475W j 24 j 16.0-33.0 j 75 Q-31"F
Table 3: Average RMS Current
Audible I Wall Mount Audible Strobe Models Ceiling Mount Audible Strobe Modçls
A$-34MCW AS-24MCWH AS-24MCC AS-24MCCH
ISod
-
300d 75cd
-
hOod
-
135cd IBScO
-
15cd
-
30cd 75cd 95cd 115cd
0.080 0.102 0.160 0.194 0.250 0.320 0.088 0.114 0.166 0.205 0.250
0.080 0.125 0.200 0.267 0.355 0.480 0,095 0.138 0.221 0.285 0.355
0.060 0.084 0.132 0.173 0.230 0.306 0.095 0.092 0.14.5 0.188 0.230
0.074
-
0.110 0.190
-
0.253
-
0.340
-
0.465
-
0.080 6.122 0.201 0.269 0.340
0.082
-
0.076 0.121 0.168 0.220 0.295 0.056 0.082 0.132 0.173 0.220
0.068
-
0.105 0.
.
182
-
0.2451
-
0.335
-
0.460 0.074 0.113 0.198 0.263 0.335
Table 4: Average CurTent (AMPS) For Series ASWP'
Voltage
High dBA
Batting
(99)dBA
Medium dBA
Setting
(95)dBA
Low dBA
Setting
(90) dBA
24.0 VDC 0.128 0.105 0.098
UL Max 0.168 1 0.155 0.150
RMS current ratings are per UL average RMS method. UL max current rating is the maximum RMS currentwlthin the listed voltage range (16-33v
tor .24v un). For stmbes.the UL max current Is usually at the minimum listed voltage.06vfor 24v units), For audibles the max current Is usually at th. maximum listed vottege (33v for 24v unite). For unfiltered FWR
ratings, eel Inst latlon Instructions.
177cd
0.320 t
30
48
6
0.465
0.295
0.460
Wiring Diagrams
SERIES AS APPUANCES NON-SYNCHRONIZED
FROND TO NEXTO
APPLIANCED OR EOLRD
PRECEDINGO tPPLIANCEO
OR FACPD
SERIES AS & RSS APPLIANCES SYNCHRONIZED WITH
PS-12124-8CP and PS-121244MP
o7pr.7r .JN_J LX
FO 1-40
010 me &M
CD A0
J-
1sis FP-09 PI-J2/24-$I
SERIES AS APPLIANCES SYNCHRONIZED WITh DSM MODULE
CLASS"Am MAC CIRCUIT WITH NO AUDIBLE SILENCE FEATURE
SERIES AS APPLIANCES SYNCHRONIZED WITH SM MODULE SIN-
GLE CLASS mEN MAC CIRCUIT WITH AUDIBLESILENCE FEATURE
SMIL
-Ooio I AD '-;FE4Q)
CLeaitc co eL—
Audi1i0
NAM Ciceit
SERIES AS APPLIANCES SYNCHRONIZED WITH MULTIPLE DSM
MODULES
FD 1 #20
AD
CD #30
PD '!il
D1 Interconnecting wiring shown. Maximum
twenty (20)0
For detail using SM or DSM Sync Module refer to Data Sheet
83000 or Installation Instruction* P83123 for SM and P83177 for DSM. For wUing Informationon the power supplies refer to
Installation Instructions P84662 for PS-24-6MC.
Specifications and Ordering Information
Modal Number Order
co
Strobe
Candela
Nofl
Syria DSIM or voc 24 12 Wall
Mount
eiUn
MountMounting OpUons
AgencyApprovals
- UL MEAjCSFM FM BFP'
S-24MCW-FR 9024 15/30/75/110 X X X - X - A,B,D,E,F,G,H,J,N,ORX X X X X X 24MCW-FW 9025 15/30/75/110 X X X X -A,B,D,E,F,G,HJN,OR.X X X X X
3468 135/185 X X X
X
24MCWH-FR X -AB,D,E.F,G,I,J,N,O,R,X X X X X
24MCWH-FW
E
3469 135/185 X X X - X AB,D,E,F,G,H,J,N,O,R,X X X X X
241575W-FR 7405 15(75onAxis) X X X - X - AB,D,E,F,GmH,J.N,O,RX X X X X X
121575W-FR 7410 15(75onAxls) X X - X X - A.8,DEF,GH,JNORX X X X X X '8-24MCC-FR 3161 15/30/76/95 X X X - - X A,B,D,E,F,G,H,J,N,OR,X X X X X S-24MCC-FW 3162 15/30175/95 X X X - • X B,D,EF,GH,J,N,O,R,X X X X X S-24MCCH-FW 3467 115/177 X X X - X B,D,E,FGH,JNO,R,X X X X X - S-2475W-FR' 9012 75 © -31'F X X X X - I(see Data Sheet S9004) X X X X X J4-24-R 7892 - X X X • X X A,BD,E,F,G,HJN,O,R.X X X X X X
H-24-W 7893 - X X X - X X A,BD,EF,GHJ,N,O,R,X X X X X - J-4-12-R 7891 - X X - X X X A,B,D,E,F,G,H,JN,OR.X X X X X X H-12-W 7894 - X - X X X X A.B,D,EF,G,HJ,N,OR,X X X X X X H-24WP-R"7416 - X X X - X X K X X X
- X H-R"-R 7415 X X - X X X K j.X X X X
For Weatherproof Series AS/AH specifications see data sheet 89004. PENDING "Refer to Data Sheet $7000 for MountIng Options.
Note: Models are available in ether Jed or White. Contact Customer Service for Order Cod. and Delivery.
NOTE: Due to continuous development of our products, specifications and offerings are subject to change without notice In accordance with Wheelock Inc. standard terms and conditions.
Notification Coopsi' Natiiclon is Wheelock"
The notification appliances shall be Wheeiocic Series AS Audible Strobe appliances and Series MM uuaibie appliances or approved equals. The Series AS Audible be listed for UL Standard 1971 (Emergency Devices forth. Hearing-Impaired) for Indoor Fire Protection
Scribe. The Series AH Audible shall be UL Listed under Standard 464 (Fire Protective Signaling), Both shall meet the requirements of FCC Part 15 Class B. All inputs shall be compatible with standard revere, polarity supervision of circuit wiring by a Fire Alarm Control Panel (FACP). . .• ........
The audible portion of the appliance shall have a minimum Of three (3) field selectable settings for dBA levels and shall have a choice of continuous or temporal (code 3) audible outputs. ...
The sftbe portion of the appliance shall produce a hash rate of on. (1) flash per second over the Regulated Voltage Range and shall incorporate a Xenon 1tasttube enclosed in a rugged LoxanQ lens. The Series AS shall be of low current design. Where Multi-Candela appliances are specified, the strobe intensity shall have field selectable settings and shall be rated per UL Standard 1971 at 15r"75/11 0 or 135/185 candela forwall mount and I 6130175/95 or 115/177 candela for ceding mount The solectoruwtich forselecting the candela shall be tamper resistant The 1575 candelq strobe shalt be specified when 15 candela UL Standard 1971 Listing with 75 candela on-axis Is required (e.g. ADA compliance).
When synchronization is required, the appliance shall be compatible with Wneelock's SM, DSM Sync Modules, Wheelock Power Supplies
or other manufacturers panels with built-in Wheelock Patented Sync Protocol,. Th. strobes shall not drift out of synchronization at any
time during operation, if the sync module or Power Supply falls tp operate, (i.e., contacts remain closed), the strobe shall revert to a non-synchronized flash-rats. The appliance shall also be designed so thatthe audible signal may be silenced while maintaining strobe
activation when used with Wheelock synchronization.
The Senes AS Audible Strobe and SenesAH Audible shall incorporate a Patented Universal Mounting Plate that shall allow mounting
to a single-gang, double-gang, 4-inch square, 100mm Europ..n lyp. backboxes, orthe SHBB Surface Backbox. If required, an NATP (Notification Appliance Trlrnplata) shall be provided............ ..:.;:
All notification appliances shall be backward compatible.
WE ENCOURAGE AND SUPPORT NICEr CERTIFICATION
YFAR WARRANTY
Made In USA
SR1nn AS/Al-I 'rnm'y ... . . . :. ,;. .
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
OFFICE OF THE STATE FIRE MARSHAL I - FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM I *s
LISTING SERVICE
LISTING No. 7125-0785:131 . Page 1 of 2
CATEGORY: Fire Alarm Devices for the Hearing-Impaired
LISTEE: Wheelock Inc., 273 Branchport Ave., Long Branch NJ 07740
Contact: Deborah Piserchia (732) 433-6001 Fax (732) 222-5607
DESIGN: Models AS-1215, -2415, -1230, -2430, -121575, -241575, -2475 and -24110 audible/strobes for
the hearing impaired followed by any three alpha/numeric characters indicating lens
orientation, lettering and color.
Models AS-1215W, -2415W, -1230W, -2430W, -121575W, -241575W, -2475W and -24110W
audible/strobes for the hearing impaired followed by any three alpha/numeric characters
indicating lens orientation, lettering and color. These units with suffix -W are for wall mount
only. *Models AS-121575W and AS-241575W lens color may be white, red, blue, green, or
amber.
Models AS-2415C, -2430C, -2475C and -24100C audible/strobes for the hearing impaired
followed by two alpha/numeric characters indicating lens lettering, orientation and color. These
units are intended for ceiling mount only.
Model AH-12, -24, AH-12WP, -24WP audible appliances (no strobe), followed by an alpha or
numeric character indicating product color.
Model AS-24MCW and AS-24MCC audible/strobe, followed by any two alpha or numeric
character indicating lettering and product color. *Lens color may be white, red, blue, green, or
amber.
Models ASWP-2475W and *AsWP2475c audible/strobe with integral private mode
fire/emergency visual signaling for non-hearing impaired applications. Lens color may be white,
red, blue, green, and amber. Both models are suitable for outdoor use when mounted on the
Model WPBB back box.
Models AS-24MCWH, AS-24MCCH, *ASWP24MCWH and *ASWP24MCCH
audible/strobes for the hearing impaired followed by two alpha/numeric characters
indicating lens lettering and product color. Units with suffix CH are for ceiling mount only.
Units with suffix WH are for wall mount only. Lens color may be white, red, blue, green,
or amber.
Refer to the listees data sheet for detailed product description and operational considerations.
RATING: Electrical: 8-17.5/16-33 VDC/VFWR
Flash Rate: 60 flashes/minute
Candela: 15:15cd, 1575:15/75cd, 30:30cd, 75:75cd, 95:95cd, 100:100cd, 110:11Ocd
MCW: Selectable 15cd, 30cd, 75cd, 110cd
MCC: Selectable 15cd, 30cd, 75cd, 95cd
MCWH: Selectable 135cd, 185cd (65cd, 90cd at -40 C)
MCCH: Selectable 115cd, 177cd (50cd, 75cd at -40 C)
Listing No. 7125-0785:131
Page 2 of 2
INSTALLATION: In accordance with listee's printed installation instructions, applicable codes and ordinances and
in a manner acceptable to the authority having jurisdiction. Models ASWP-2475W, ASWP-
24MCWH, AS-24MCW and AS-24MCWH are for wall mount only. Models ASWP-2475C,
ASWP-24MCCH, AS-24MCCH, AND AS-24MCC are for ceiling mount only. Models with suffix -
W or WH are for wall mount only. Models with suffix -c or -CH are for ceiling mount only.
MARKING: Listees name, model number, electrical/candela rating, and UL label.
APPROVAL: Listed as audible and audible/visual signaling devices suitable for the hearing impaired when used
in conjunction with separately listed electrically compatible fire alarm control units. For indoor use
only except Models AH-I2WP, AH-24WP, *Aswp.2475w ASWP-2475C, ASWP-24MCWH, and
ASWP-24MCCH audible appliances are suitable for indoor/outdoor. For synchronization, Models
AS Series must be used with Model SM-12i24, SMX-12124, DSM-12124 or DSMX-12/24 sync
control module (CSFM Listing No. 7300-0785:132). Refer to listee's Installation Instruction Manual
for details.
These appliances can generate a distinctive three-pulse Temporal Pattern Fire Alarm
Evacuation Signal (for total evacuation) in accordance with NFPA 72, 2002 Edition.
NOTE: Models AH-12, AH-24, -12WP and -24WP audible devices are not suitable for the hearing
impaired applications.
Rev. 10-01-07
This listing is based upon technical data submitted by the applicant CSFM Fire Engineering staff has reviewed the test results
and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or
recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation
criteria. Refer to listee's data sheet installation instructions and/or other suitable information sources.
Date Issued: JUNE 26, 2008 Listing Expires June 30, 2009
Authorized By: BEN HO, Chief
Fire Engineering Division