HomeMy WebLinkAbout2525 EL CAMINO REAL; 208; FPC2017-0197; Permit4ity of
Carlsbad
Au(~~
Print Date: 10/24/2022 Permit No: FPC2017-0197
Job Address: 2525 EL CAMINO REAL, #208, CARLSBAD, CA 92008 Status: Closed - Finaled
Permit Type: FIRE-Construction Commercial Work Class: Fire Sprinklers
Parcel #: 1563020900 Track #: Applied: 07/19/2017
Valuation: $888,943.90 Lot #: Issued: 07/27/2017
Occupancy Group: Project #: Finaled Close Out: 02/07/2019
#of Dwelling Units: Plan #:
Bedrooms: Construction Type: Final Inspection:
Bathrooms: Orig. Plan Check #: INSPECTOR: Wong, Cindy
Plan Check #:
Project Title:
Description: YARD HOUSE -SPRINKLER TI >100 HEADS (102) SHELL PORTION
Applicant: FPContractor:
VFS FIRE AND SECURITY SERVICES BERN EL INC
SALVADOR JASSO 501W SOUTHERN AVE
501 W SOUTHERN AVE ORANGE, CA 92865-3217
ORANGE, CA 92865-3217 (714) 778-6070
(714) 919-8351
FEE AMOUNT
FIRE NFPA 13 or 13R System > 100 heads $634.00
Total Fees: $634.00 Total Payments To Date: $634.00 Balance Due: $0.00
Fire Department Page 1 of 1
1635 Faraday Avenue, Carlsbad CA 92008-7314 1 760-602-4665 1 760-602-8561 f I www.carlsbadca.gov
FPC20I7-0197
2525 EL CAMINO REAL
UNIT208 FILE Copy
FIRE & SECURITY SERVICES
VFS Fire & Security
501 W Southern Ave
Orange CA., 92865
714-778-6070
Job Name : THE SHOPPELS AT CARLSBAD
Building : FP-3.1
Location : 2525 EL CAMINO REAL CARLSBAD, CA
System : SYS-1 1 AREA 1
Contract : 163173
Data File : SYS-1 1 YARD HOUSE .WXF
Computer Programs by Hydratec Inc. Revision: 50.52.1
Water Supply Curve C
VFS Fire & Security Page 1
THE SHOPPELS AT CARLSBAD Date 05-10-2017
City Water Supply: Demand:
Cl - Static Pressure : 82.8 Dl - Elevation : 13.210
C2 - Residual Pressure: 37.8 D2 - System Flow : 364.347
C2 - Residual Flow : 6050 D2 - System Pressure : 73.500
Hose ( Demand) : 250
D3 - System Demand : 614.347
Safety Margin : 8.646
150
140
130
p120
R°
E10°
S 90 C1
DZ- s 80
U7°
R 60
E
50 --
40
:
20
-9-1— 10 -
I — ...l I I I _____________________________
750 1500 2250 3000 3750 4500 5250 6000 6750
FLOW (NA1.85)
Computer Programs by Hydratec Inc. Revision: 50.52.1
Flow Summary - NFPA 2007
/FS Fire & Security Page 2
THE SHOPPELS AT CARLSBAD Date 05-10-2017
SUPPLY ANAL YSIS
Node at
Source
Static
Pressure
Residual
Pressure Flow
Available
Pressure Total Demand Required Pressure
CON 82.8 37.8 6050.0 82.146 614.35 73.5
NODE ANALYSIS
Pressure Discharge
Node Tag Elevation Node Type at Node at Node Notes
HD1 26.5 5.6 21.56 26.0
1 26.5 5.27 24.3 26.0 K=K @ HD2
2 26.5 5.27 24.97 26.35 K=K @ HD2
3 26:5 5.27 25.86 26.82 K=K @ HD2
4 26.5 5.27 27.77 27.79 K=K @ HD2
5 26.5 5.27 31.11 29.42 K=K@ HD2
6B 26.5 42.09
7 26.5 5.27 24.33 26.01 K=K @ HD2
8 26.5 5.27 24.99 26.37 K=K @ HD2
9 26.5 5.27 25.89 26.83 K=K @ HD2
10 26.5 5.27 27.8 27.81 K=K@ HD2
11 26.5 5.27 31.14 29.43 K=K @HD2
12B 26.5 42.13
13 26.5 5.27 32.5 30.06 K=K@ HD2
14 26.5 5.27 33.36 30.46 K=K @ HD2
15 26.5 5.27 34.53 30.99 K=K @ HD2
16B 26.5 44.81
6 26.5 46.82
12 26.5 46.86
16 26.5 47.07
17 26.5 51.05
TRS 26.5 54.41
BRS2 2.0 65.17
UG -4.0 67.8
UGI -4.0 68.2
UG2 -4.0 68.2
DC1 -4.0 68.24
DC2 -4.0 73.34 250.0
CON -4.0 73.5
Computer Programs by Hydratec Inc. Revision: 50.52.1
FS Fire & Security Page 3
THE SHOPPELS AT CARLSBAD Date 05-10-2017
Nodel Elevi K Qa Nom Fitting Pipe CFact Pt
to or Ftngs Pe ******* Notes
Node2 Elev2 Fact Qt Act Eqv. Ln. Total Pf/Ft Pf
HD1 26.500 5.60 26.00 1 E 2.0 6.000 120 21.556
to T 5.0 7.000 0.0
HD2 26.500 26.0 1.049 0.0 13.000 0.2115 2.749 Vel 9.65
0.0
HD2 26.00 24.305 K Factor = 5.27
1 26.500 5.27 26.00 1.5 4E 19.799 11.500 120 24.305 K = K@ HD2
to 0.0 19.799 0.0
2 26.500 26.0 1.682 0.0 31.299 0.0212 0.664 Vel = 3.75
2 26.500 5.27 26.35 1.5 0.0 11.500 120 24.969 K= K@HD2
to 0.0 0.0 0.0
3 26.500 52.35 1.682 0.0 11.500 0.0774 0.890 Vel = 7.56
3 26.500 5.27 26.82 1.5 0.0 11.500 120 25.859 K= K@ HD2
to 0.0 0.0 0.0
4 26.500 79.17 1.682 0.0 11.500 0.1664 1.914 Vel = 11.43
4 26.500 5.27 27.79 1.5 0.0 11.500 120 27.773 K= K@ HD2
to 0.0 0.0 0.0
5 26.500 106.96 1.682 0.0 11.500 0.2903 3.339 Vel = 15.44
5 26.500 5.27 29.42 1.5 T 9.9 14.208 120 31.112 K= K@ HD2
to 0.0 9.900 0.0
6B 26.500 136.38 1.682 0.0 24.108 0.4552 10.974 Vel = 19.69
6B 26.500 0.0 1.5 T 9.9 0.500 120 42.086
to . 0.0 9.900 0.0
6 26.500 136.38 1.682 0.0 10.400 0.4552 4.734 Vel = 19.69
0.0
6 136.38 46.820 K Factor = 19.93
7 26.500 5.27 26.01 1.5 4E 19.799 11.500 120 24.329 K= K@ HD2
to 0.0 19.799 0.0
8 26.500 26.01 1.682 0.0 31.299 0.0212 0.665 Vel = 3.76
8 26.500 5.27 26.37 1.5 0.0 11.500 120 24.994 K= K@ HD2
to 0.0 0.0 0.0
9 26.500 52.38 1.682 0.0 11.500 0.0775 0.891 Vel = 7.56
9 26.500 5.27 26.83 1.5 0.0 11.500 120 25.885 K= K@ HD2
to 0.0 0.0 0.0
10 26.500 79.21 1.682 0.0 11.500 0.1666 1.916 Vel = 11.44
10 26.500 5.27 27.81 1.5 0.0 11.500 120 27.801 K= K@ HD2
to 0.0 0.0 0.0
11 26.500 107.02 1.682 0.0 11.500 0.2906 3.342 Vel = 15.45
11 26.500 5.27 29.43 1.5 T 9.9 14.208 120 31.143 K= K@ HD2
to 0.0 9.900 0.0
12B 26.500 136.45 1.682 0.0 24.108 0.4556 10.984 Vel = 19.70
12B 26.500 0.0 1.5 T 9.9 0.500 120 42.127
to 0.0 9.900 0.0
12 26.500 136.45 1.682 0.0 10.400 0.4556 4.738 Vel = 19.70
0.0
12 136.45 46.865 K Factor= 19.93
13 26.500 5.27 30.06 1.5 4E 19.799 11.500 120 32.496 K= K@ HD2.
to 0.0 19.799 0.0
14 26.500 30.06 1.682 0.0 31.299 0.0277 0.868 Vel = 4.34
Computer Programs by Hydratec Inc. Revision: 50.52.1
Final Calculations - Hazen-Williams
'JFS Fire & Security Page 4
THE SHOPPELSAT CARLSBAD Date 05-10-2017
Nodel Elevi K Qa Nom Fitting Pipe CFact Pt
to or Ftngs Pe ******* Notes
Node2 EIev2 Fact Qt Act Eqv. Ln. Total Pf/Ft Pf
14 26.500 5.27 30.47 1.5 0.0 11.500 120 33.364 K= K@ HD2
to 0.0 0.0 0.0
15 26.500 60.53 1.682 0.0 11.500 0.1013 1.165 Vel = 8.74
15 26.500 5.27 30.99 1.5 T 9.9 37.333 120 34.529 K= K@ HD2
to 0:0 9.900 0.0
16B 26.500 91.52 1.682 0.0 47.233 0.2176 10.277 Vel = 13.21
16B 26.500 0.0 1.5 1 9.9 0.500 120 44.806
to 0.0 9.900 0.0
16 26.500 91.52 1.682 0.0 10.400 0.2176 2.263 Vel = 13.21
0.0
16 91.52 47.069 K Factor = 13.34
6 26.500 136.38 4 0.0 9.208 120 46.820
to 0.0 0.0 0.0
12 26.500 136.38 4.26 0.0 9.208 0.0049 0.045 Vel = 3.07
12 26.500 136.45 4 0.0 11.500 120 46.865
to 0.0 0.0 0.0
16 26.500 272.83 4.26 0.0 11.500 0.0177 0.204 Vel = 6.14
16 26.500 91.52 4 2E 26.334 78.333 120 47.069
to 1 26.334 52.668 0.0
17 26.500 364.35 4.26 0.0 131.001 0.0304 3.977 Vel = 8.20
17 26.500 0.0 4 3E 39.501 71.417 120 51.046
to 0.0 39.501 0.0
TRS 26.500 364.35 4.26 0.0 110.918 0.0304 3.367 Vel= 8.20
TRS 26.500 0.0 8 2E 42.282 38.000 120 54.413
to T 41.108 83.390 10.611
BRS2 2 364.35 8.249 0.0 121.390 0.0012 0.147 Vel = 2.19
BRS2 2 0.0 8 E 21.141 5.000 120 65.171
to 0.0 21.141 2.599
UG -4 364.35 8.249 0.0 26.141 0.0012 0.032 Vel = 2.19
UG -4 0.0 8 5E 105.706 218.250 120 67.802
to 0.0 105.706 0.0
UG1 -4 364.35 8.249 0.0 323.956 0.0012 0.393 Vel = 2.19
UG1 -4 0.0 8 0.0 10.000 140 68.195
to 0.0 0.0 0.0
UG2 -4 364.35 8.27 0.0 10.000 0.0009 0.009 Vel = 2.18
UG2 -4 0.0 8 0.0 33.417 150 68.204
to 0.0 0.0 0.0
DC1 -4 364.35 7.98 0.0 33.417 0.0010 0.032 Vel = 2.34
DC1 -4 0.0 8 5E 142.34 6.000 140 68.236
to 0.0 113.872 5.000 *Fixed Loss 5
DC2 -4 364.35 8.27 0.0 119.872 0.0009 0.108 Vel = 2.18
DC2 -4 H250 250.00 8 T 52.855 10.000 150 73.344
to 0.0 52.855 0.0
CON -4 614.35 7.98 0.0 62.855 0.0025 0.156 Vel = 3.94
0.0
CON 614.35 73.500 KFactor= 71.66
Computer Programs by Hydratec Inc. Revision: 50.52.1
Fittings Used Summary
VFS Fire & Security Page 5
THE SHOPPELS AT CARLSBAD Date 05-10-2017
Fitting Legend
Abbrev. Name 1/2 % 1 11/4 11/2 2 2% 3 31/ 4 5 6 8 10 12 14 16 18 20 24
E NFPA 13 90 Standard Elbow 1 2 2 3 4 5 6 7 8 10 12 14 18 22 27 35 40 45 50 61
T NFPA 1390 Flow thru Tee 3 4 5 6 8 10 12 15 17 20 25 30 35 50 60 71 81 91 101 121
Unit Summary
Diameter Units Inches
Length Units Feet
Flow Units US Gallons per Minute
Pressure Units Pounds per Square Inch
Note: Fitting Legend provides equivalent pipe lengths for fittings types of various diameters.
Equivalent lengths shown are standard for actual diameters of Sched 40 pipe and CFactors
of 120 except as noted with *• The fittings marked with a * show equivalent lengths values
supplied by manufacturers based on specific pipe diameters and CFactors and they require no
adjustment. All values for fittings not marked with a * will be adjusted in the calculation
for CFactors of other than 120 and diameters other than Sched 40 per NFPA.
Computer Programs by Hydratec Inc. Revision: 50.52.1
STANDARD RESPONSE:
/ - A UTOMA TIC SPRINKLERS
U
(Z)
GLSERIES N'QVF L_11_)[
~L
UPRIGHT PENDENT FIRE SPpNLERtORPORATOr VERTICAL SIDEWALL
HORIZONTAL SIDEWALL
CONVENTIONAL (OLD STYLE)
DESCRIPTION AND OPERATION
The Globe Standard Response GL Series Sprinklers are a low
profile yet durable design which utilizes a 5mm frangible glass
ampule as the thermosensitive element. While the Standard
Response Sprinkler provides an aesthetically pleasing appear-
ance, it can be installed wherever standard spray sprinklers are
specified when allowed by the applicable standards. It offers
the additional feature of greatly increased safety to life and is
available in various styles, orifices, temperature ratings and fin-
ishes to meet varying design requirements. Standard Response STANDARD RESPONSE
Sprinklers should be used advisedly and under the direction of UPRIGHT CONVENTIONAL
approving authorities having jurisdiction.
The heart of Globe's GL Series sprinkler proven actuating
assembly is a hermetically sealed frangible glass ampule that I
contains a precisely measured amount of fluid. When heat is
absorbed, the liquid within the bulb expands increasing the
internal pressure. At the prescribed temperature the internal
pressure within the ampule exceeds the strength of the glass
causing the glass to shatter. This results in water discharge which is I
distributed in an approved pattern depending upon the deflector
style used. STANDARD RESPONSE
The sprinkler and escutcheon are not factory assembled. PENDENT VERTICAL
Assembly is done in the field. SIDEWALL
TECHNICAL DATA
See reverse side for Approvals and Specifications.
Temperature Ratings - 135°F (57°C), 155°F (68°C),
175°F (790C), 200°F (93°C), 286°F (141°C), 360°F (182°C) .3
500°F(260°C)Available Upon Request Without Approvals J Water Working Pressure Rating -175 psi (12 Bars)
Factory tested hydrostatically to 500 psi (34 Bars) STANDARD RESPONSE Maximum low temperature glass bulb rating is -67°F (-55°C) LPCICE HORIZONTAL
Frame - bronze • Deflector - brass • Screw - brass HORIZONTAL SIDEWALL
Lodgement Wire - stainless steel • Bulb seat - copper SIDEWALL
Spring - nickel alloy• Seal - teflon
Bulb - glass with glycerin solution, 5mm size
Escutcheon Assembly - steel
SPRINKLER TEMPERATURE RATING/CLASSIFICATION and COLOR CODING
CLASSIFICATION AVAILABLE SPRINKLER
TEMPERATURES
I BULB COLOR
J
N.F.P.A. MAXIMUM I
CEILING TEMPERATURE
ORDINARY I 35'F/1 -15"F 5' C58 ORANGE/RED 100'F 8C 1
INTERMEDIATE 175 F:2OOF 7C93C YELLOW/GREEN 100 0 66 C
HIGH 286I 11C BLUE 225C 107C
EXTRAHIGH 3600 82 C I MAUVE 300T 14'C
ULTRAHIGH 560C - 260 C - BLACK 4751 246C
APR 2017 GFS-100b (Formerly A-65)
7/U' MAX.
ORDERING INFORMATION
SPECIFY
Quantity Model• Number Style" Orifice
Thread Size Temperature. Finish desired
Quantity - Wrenches/Recessed Wrenches -
P/N 325390/325391 (1/2"); P/N 312366/325401 (L.O.)
Quantity Protective Caps - P/N 327109-CAP (Friction Fit Recessed)
FIRE 4 4NKLC0RF:)FAfltJ7
APR 2017
STANDARD RESPONSE
A UTOMA TIC SPRINKLERS
GL SERIES
UPRIGHT • PENDENT • VERTICAL SIDEWALL
HORIZONTAL SIDEWALL ° CONVENTIONAL (OLD STYLE)
SPECIFICATIONS
NOMINAL "K" FACTOR THREAD SIZE LENGTH' FINISHES
2.8 (40 metric) 1/2 NPT(l5mm) 21/4 (57cm) Factory Bronze
4.2 (60 metric) 1/2"NPT(15mm) 2 1/4 (5.7cm) Chrome
5.6 (80 metric) 1f2 NPT (15mm) 2 1/4 (57cm) White Polyester'
8.0 (115 metric) 1/2"NPT(15mm) 2 1/4'(5.7cm) Black Polyester 2.3
8.0 (115 metric) 3/4"NPT (20mm) 2 7/16 (6.2cm) Wax Coated 2.1.1
NOTE: METRIC CONVERSIONS ARE APPROXIMATE. 'AVAILABLE AS cULus LISTED COROSION RESISTANT WHEN SPECIFIED ON ORDER.
'HORIZONTAL SIDEWALL IS 29/16". 'WAX COATING cULus LISTED UP TO 200"F (93°C) ONLY.
'FINISHES AVAILABLE ON SPECIAL ORDER. APPROVALS
TEMPERATURE
STYLE SIN
MODEL
K
FACTOR HAZARD cULus FM LPC CE NYC-DOB
MEA 101-92-E
-'--- 135°F 155°F 175°F - 200°F **286F 11360°F
(57°C) (68°C) (79°C) (93°C) (141°C) (182°C)
GL2861 2.8 LH X X X X X X X X
GL4261 42 LH X X X X X X X X
UPRIGHT GL5661 56 ALL X X X X X X X X X X X
GL8161 8.0" ALL X X X X X X X X
GL8164 8.0 ALL . X X X X X X X X X X X
GL2851 2.8 LH X X X X X X X X
PENDENT GL4251 4.2 LH X X X X X X X X
RECESSED GL5651 5.6 ALL X X X X X X X X X X X
PENDENT GL8151 8.0° ALL X X X X X X X X
GL8156 8.0 ALL X X X X X X X X' X X X
VERTICAL GL5675 5.6 LH X X X X X X X X
SIDEWALLt 0L8176 8.0 LH X X X X X X X
HORIZONTAL GL2870 2.8 LH X X X X X X X X
SIDEWALL GL4270 4.2 LH X X X X X X X X
RECESSED GL5670 5.6 LH/OH X X X X X X X X X
HORIZONTAL GL56710 5.6 LH/OH X X X X X X --- --- X X
SIDEWALL GL8171 8.0 LH/OH X X X X X X X
CONVENTIONAL GL5668 5.6 LH/OH X X X X X X --- --- X X
(OLD STYLE) GL8169 8.0 LH/OH X X X X X X --- --- X X
'SPRINKLERS SHALL BE LIMITED AS PER THE REQUIREMENTS OF NFPA13 AND ANY OTHER RELATED DOCUMENTS. 'BRASS FINISH ONLY WHEN RECESSED
§HORIZONTAL SIDEWALL cULus LISTED FOR DEFLECTOR 4' TO 12" BELOW THE CEILING, FM APPROVED 4" TO 6" BELOW THE CEILING. "NO FM APPROVALS FOR RECESSED
aINSTALL IN ACCORDANCE TO B55306 AND ANY OTHER RELATED DOCUMENTS. "NO FM APPROVALS
fPENDENT VERTICAL SIDEWALL cULus LISTED FOR 6' MIN. SPACING. OR ORDINARY HAZARD
tUPRIGHT VERTICAL SIDEWALL cULus LISTED FOR 9' MIN. SPACING. LH: LIGHT HAZARD
500°F (260°C) AVAILABLE UPON REQUEST WITH NO APPROVALS. ALL: ALL HAZARDS
°1/2"NPT, RETRO-FIT ONLY
GLOBE® PRODUCT WARRANTY
Globe agrees to repair or replace any of its own manufactured
products found to be defective in material or workmanship for a
period of one year from date of shipment.
For specific details of our warranty please refer to Price List
Terms and Conditions of Sale (Our Price List),
4077 AIRPARK DRIVE, STANDISH, MICHIGAN 48658
989-846-4583 FAX 989-846-9231
1-800-248-0278 www,globesprinkler,com
PRINTED U.S.A. GFS-100b (Formerly A-65)
-------2 15/16" DIA.-
- 2" DIR. MIN.
HOLE IN CEILING
129/32- OIA.
- -1" 1/2' REDUCER
I kERT I N.